Quantum Performance Report

Job Name Salesman Address AHU - DAIVIET

5-Jul-13

CLCP Euro Quantity Job Comments

AHU2 AHU2-water 1

Base Unit Module


Unit Airflow Plant/Model Unit Unit Insulation Casing Construction Eurovent Certification EUROVENT- AHU Energy Efficiency Class Unit Roof Unit Base 6900.0 L/s Penang / CLCP Euro 030 50mm-S PU 0.4mm Powder Paint External/GI Internal Yes B No Standard CKD At Jobsite Total Unit Length Unit Length for Unit Level 2 Unit Width Unit Height Unit Weight Elevation Number of Breakpoints Run Acoustics

Module Position: Position: 0


No 4158 mm 0 mm 1988 mm 2108 mm 1150 kg 0.0 m 0.00 Number Yes - Eurovent Data

Mixing Box Module


Mixing Box Section Damper Type Door Handle Door Location Sight Glass Mix Box Module PD Back & Top Standard Damper Std. Latched RH No 19.5 Pa Mix Box Section Length Factory Installed Damper Actuator Mixing Box CFM Mix Box Section Weight Module Level Shipping Split ID

Module Position: Position: 1


465 mm No 6.90 m3/s 142 kg 1st Level 1.00 Number

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 1 of 10

Quantum Performance Report


Filter Module
Filter Type Supplied by Prefilter Media Prefilter Condition Filter Media Filter Condition Filter Loading Method Access Section Door Handle Sight Glass Service Light Pressure Gauge Hi-Eff Bag Filter Factory 2"TA(30%Eff, G4(EN779)-EU4) Mid-life 15"Bag(85%Eff, F7(EN779)-EU7) Mid-life Side Sliding Method No No No No 0-1000 Pa Spare Filter (Prefilter Media) Spare Filter (Filter Media) Filter CFM Filter Area Filter - Filter Module PD Filter Velocity Filter Module Length Filter - Module Weight Shipping Split ID Filter - Pre-filter PD Module Level

5-Jul-13 Module Position: Position: 2


No No 6.90 m3/s 3.35 m2 336.9 Pa 2.1 m/s 465 mm 120 kg 1.00 Number 86.4 Pa 1st Level

Coil Module
Coil Mo [3]-1 ]-1 Coil Section Application Entering Dry Bulb Entering Wet Bulb Leaving Dry Bulb Coil - Sensible Cap. Coil - Total Cap. Leaving Wet Bulb Entering Water Temp. Leaving Water Temp. Water Temp. Different Water Press. Drop Water Flow Rate Rows Fins Per Foot Coil Header Coil Type Coil Casing Fluid Type Turbulators Coil Supply Tube Matl Fin Type Horizontal Coil Chilled Water 25.0 C 18.2 C 10.7 C 121.33 kW 169.74 kW 10.6 C 7.0 C 12.5 C 5.5 C 32.3 kPa 7.36 L/s 8 120.00 Number Steel "WL" Type Galvanized Water No RH 1/2" Cu 1/2" Delta Flo H (HE) Fin Matl Coil Airflow Coil Elevation Drip Eliminator Drain Pan Extended Drain Pan Drain Pipe Connection Drain Pan Length Sight Glass Coil Face Area Face Velocity Moist. Carryover Coat'g Air Pressure Drop Coil - Dry Weight Coil - Wet Weight Coil - Water Volume Fluid velocity Reynolds Number Coil Module Press. Drop Coil Module Length Coil Module Weight Module Level Shipping Split ID

Module Position: Position: 3


Aluminium 6.90 m3/s 0.0 m No Galvanized No Std (Same as Coil Supply Conn.) 620 mm No 2.94 m2 2.4 m/s No 215.4 Pa 252 kg 355 kg 102.71 L 3.62 ft/s 10621.39 Number 215.4 Pa 620 mm 622 kg 1st Level 1.00 Number

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 2 of 10

Quantum Performance Report


Blank Module
Blank Section Back Opening Front Opening Sight Glass Drain Pan Additional Inlet/Outlet Yes Yes Yes No No No Blank Section Length Blank Module Total PD Access/Blank Module Weight Module Level Shipping Split ID

5-Jul-13 Module Position: Position: 4


620mm 0.0 Pa 63 kg 1st Level 1.00 Number

Electric Heater Module


Electri [5]-1 ]-1 Steps Of Control Volt/Ph/Hz Temperature Rise Total Heating Capacity Sight Glass Electric Heater Section Total Heating Element Qty. 4 380/3/50 6.0 C 50.40 kW No UL Listed Electric Heater 24.00 Number # of Row Step Line Current Total Line Current Elec. Heater Module Lgth Module Level Shipping Split ID

Module Position: Position: 5


1 19.14 A 76.58 A 465 mm 1st Level 1.00 Number

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 3 of 10

Quantum Performance Report


Fan Module
Fan Mod [6]-1 ]-1 Fan Module Fan Fan Size Fan Discharge Inlet Location Airflow Ext. Static Pres. Cabinet effects Loss Total Static Pres. RPM Motor Class Fan/Motor Access Motor Supply By Motor Volt/Ph/Hz Drive Option(P'ley&Belt) Motor Safety Factor Motor KW Fan Isolation Isolator Vibration Efficiency Absorbed Power Motor Power Input Mechanical Efficiency Static Efficiency Fan - Discharge Vel. Fan - Velocity Pressure Motor/Fan Heat Temp Rise Motor - FLA Motor - LRA. Standby Motor Option Standby Motor Standby Drive(Pulley&Belt) Door Handle Type Sight Glass Spare Motor Spare Drive For Duty Motor(Pulley&Belt) Spare Drive For Stby Motor(Pulley&Belt) Fan Modulation - IGV Motor Protection Frequency Inverter VFD Model VFD Casing Supply Fan Standard Fan AF 560C Top-Back(Arr.4/5) Back Inlet (HDT) 6.90 m3/s 350.0 Pa 71.7 Pa 993.5 Pa 1650 rpm TECO, 3Phase, 4P,STD Eff (IE1) RH Factory V 380-415/3/50 Const. Pitch Factory Standard #D160M-11.0kW(15hp) 2"(50mm) Spring 90% 9.72 kW 11.95 kW 78.29 % 70.50 % 13.5 m/s 109.8 Pa 1.5 C 21.5 - 19.7A 152.6 - 140A No No No Std. Latched No No No No No No TR200, Factory Installed TR200 11.0 kW IP55 Shipping Split ID Discharge - 63Hz Discharge - 125Hz Discharge - 250Hz Discharge - 500Hz Discharge - 1kHz Discharge - 2kHz Discharge - 4kHz Discharge - 8kHz Discharge - Overall Inlet+Casing - 63Hz Inlet+Casing - 125Hz Inlet+Casing - 250Hz Inlet+Casing - 500Hz Inlet+Casing - 1kHz Inlet+Casing - 2kHz Inlet+Casing - 4kHz Inlet+Casing - 8kHz Inlet+Casing - Overall Casing - 63Hz Casing - 125Hz Casing - 250Hz Casing - 500Hz Casing - 1kHz Casing - 2kHz Casing - 4kHz Casing - 8kHz Casing - Overall Fan Discharge - 63Hz Fan Discharge - 125Hz Fan Discharge - 250Hz Fan Discharge - 500Hz Fan Discharge - 1kHz Fan Discharge - 2kHz Fan Discharge - 4kHz Fan Discharge - 8kHz Fan Discharge - Overall Fan Intake - 63Hz Fan Intake - 125Hz Fan Intake - 250Hz Fan Intake - 500Hz

5-Jul-13 Module Position: Position: 6


1.00 Number 100 dB 98 dB 101 dB 98 dB 94 dB 88 dB 83 dB 81 dB 100 dBA 88 dB 84 dB 83 dB 75 dB 60 dB 56 dB 52 dB 35 dB 77 dBA 88 dB 84 dB 83 dB 75 dB 62 dB 58 dB 52 dB 35 dB 77 dBA 102 dB 96 dB 101 dB 95 dB 92 dB 85 dB 80 dB 78 dB 98 dBA 90 dB 93 dB 100 dB 93 dB

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 4 of 10

Quantum Performance Report


Outdoor Enclosure for VFD Comunication Card Design Temp. Fan - Elevation Module Level Fan - Module Length Fan - Module Weight Yes No 20.0 C 0.0 m 1st Level 1395 mm 203 kg Fan Intake - 1kHz Fan Intake - 2kHz Fan Intake - 4kHz Fan Intake - 8kHz Fan Intake - Overall Velocity for Eurovent Energy Calculation

5-Jul-13
89 dB 83 dB 80 dB 77 dB 96 dBA 2.1 m/s

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 5 of 10

Quantum Performance Report


Job Name Salesman Address AHU - DAIVIET

5-Jul-13

CLCP Euro Quantity Job Comments

AHU1 AHU1- water 1

Base Unit Module


Unit Airflow Plant/Model Unit Unit Insulation Casing Construction Eurovent Certification EUROVENT- AHU Energy Efficiency Class Unit Roof Unit Base 13700.0 L/s Penang / CLCP Euro 050 50mm-S PU 0.4mm Powder Paint External/GI Internal Yes D No Standard CKD At Jobsite Total Unit Length Unit Length for Unit Level 2 Unit Width Unit Height Unit Weight Elevation Number of Breakpoints Run Acoustics

Module Position: Position: 0


No 3201 mm 0 mm 3228 mm 2108 mm 1202 kg 0.0 m 1.00 Number Yes - Eurovent Data

Mixing Box Module


Mixing Box Section Damper Type Door Handle Door Location Sight Glass Mix Box Module PD Back & Top Standard Damper Std. Latched RH No 20.6 Pa Mix Box Section Length Mixing Box CFM Mix Box Section Weight Module Level Shipping Split ID

Module Position: Position: 1


465 mm 13.70 m3/s 191 kg 1st Level 1.00 Number

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 6 of 10

Quantum Performance Report


Filter Module
Filter Type Supplied by Prefilter Media Prefilter Condition Filter Media Filter Condition Filter Loading Method Access Section Door Handle Sight Glass Service Light Pressure Gauge Hi-Eff Bag Filter Factory 2"TA(30%Eff, G4(EN779)-EU4) Mid-life 15"Bag(85%Eff, F7(EN779)-EU7) Mid-life Side Sliding Method No No No No 0-1000 Pa Spare Filter (Prefilter Media) Spare Filter (Filter Media) Filter CFM Filter Area Filter - Filter Module PD Filter Velocity Filter Module Length Filter - Module Weight Shipping Split ID Filter - Pre-filter PD Module Level

5-Jul-13 Module Position: Position: 2


No No 13.70 m3/s 5.58 m2 346.8 Pa 2.5 m/s 465 mm 178 kg 1.00 Number 88.9 Pa 1st Level

Break Point Module


Break Point Break Point Type Break Point Section Length Break Point Std 64 mm Break Point Section Weight Module Level Shipping Split ID

Module Position: Position: 3


17 kg 1st Level 1.00 Each

Break Point Module


Break Point Break Point Type Break Point Section Length Break Point Std 64 mm Break Point Section Weight Module Level Shipping Split ID

Module Position: Position: 4


17 kg 1st Level 2.00 Each

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 7 of 10

Quantum Performance Report


Coil Module
Coil Mo [5]-1 ]-1 Coil Section Application Entering Dry Bulb Entering Wet Bulb Leaving Dry Bulb Coil - Sensible Cap. Coil - Total Cap. Leaving Wet Bulb Entering Water Temp. Leaving Water Temp. Water Temp. Different Water Press. Drop Water Flow Rate Rows Fins Per Foot Coil Header Coil Type Coil Casing Fluid Type Turbulators Coil Supply Tube Matl Fin Type Horizontal Coil Chilled Water 26.7 C 19.4 C 19.0 C 130.06 kW 134.46 kW 16.8 C 7.0 C 12.5 C 5.5 C 12.0 kPa 5.83 L/s 2 120.00 Number Steel "WL" Type Galvanized Water No RH 1/2" Cu 1/2" Delta Flo H (HE) Fin Matl Coil Airflow Coil Elevation Drip Eliminator Drain Pan Extended Drain Pan Drain Pipe Connection Drain Pan Length Sight Glass Coil Face Area Face Velocity Moist. Carryover Coat'g Air Pressure Drop Coil - Dry Weight Coil - Wet Weight Coil - Water Volume Fluid velocity Reynolds Number Coil Module Press. Drop Coil Module Length Coil Module Weight Module Level Shipping Split ID

5-Jul-13 Module Position: Position: 5


Aluminium 13.70 m3/s 0.0 m No Galvanized No Std (Same as Coil Supply Conn.) 310 mm No 5.10 m2 2.7 m/s No 59.2 Pa 139 kg 188 kg 49.07 L 2.86 ft/s 8413.91 Number 59.2 Pa 310 mm 451 kg 1st Level 2.00 Number

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 8 of 10

Quantum Performance Report


Fan Module
Fan Mod [6]-1 ]-1 Fan Module Fan Fan Size Fan Discharge Inlet Location Airflow Ext. Static Pres. Cabinet effects Loss Total Static Pres. RPM Motor Class Fan/Motor Access Motor Supply By Motor Volt/Ph/Hz Drive Option(P'ley&Belt) Motor Safety Factor Motor KW Fan Isolation Isolator Vibration Efficiency Absorbed Power Motor Power Input Mechanical Efficiency Static Efficiency Fan - Discharge Vel. Fan - Velocity Pressure Motor/Fan Heat Temp Rise Motor - FLA Motor - LRA. Standby Motor Option Standby Motor Standby Drive(Pulley&Belt) Door Handle Type Sight Glass Spare Motor Spare Drive For Duty Motor(Pulley&Belt) Spare Drive For Stby Motor(Pulley&Belt) Fan Modulation - IGV Motor Protection Motor Starter Motor Starter Type Outdoor Enclosure for Motor Starter Supply Fan Standard Fan BC 800T Top-Back(Arr.4/5) Back Inlet (HDT) 13.70 m3/s 350.0 Pa 99.5 Pa 876.1 Pa 1132 rpm TECO, 3Phase, 4P,STD Eff (IE1) RH Factory V 380-415/3/50 Const. Pitch Factory Standard #D180L-22.0kW(30hp) 2"(50mm) Spring 90% 17.73 kW 21.32 kW 76.19 % 67.69 % 13.5 m/s 110.0 Pa 1.4 C 44.2 - 40.5A 283.4 - 260A No No No Std. Latched No No No No No No Yes Star Delta, Basic Type Yes Shipping Split ID Discharge - 63Hz Discharge - 125Hz Discharge - 250Hz Discharge - 500Hz Discharge - 1kHz Discharge - 2kHz Discharge - 4kHz Discharge - 8kHz Discharge - Overall Inlet+Casing - 63Hz Inlet+Casing - 125Hz Inlet+Casing - 250Hz Inlet+Casing - 500Hz Inlet+Casing - 1kHz Inlet+Casing - 2kHz Inlet+Casing - 4kHz Inlet+Casing - 8kHz Inlet+Casing - Overall Casing - 63Hz Casing - 125Hz Casing - 250Hz Casing - 500Hz Casing - 1kHz Casing - 2kHz Casing - 4kHz Casing - 8kHz Casing - Overall Fan Discharge - 63Hz Fan Discharge - 125Hz Fan Discharge - 250Hz Fan Discharge - 500Hz Fan Discharge - 1kHz Fan Discharge - 2kHz Fan Discharge - 4kHz Fan Discharge - 8kHz Fan Discharge - Overall Fan Intake - 63Hz Fan Intake - 125Hz Fan Intake - 250Hz Fan Intake - 500Hz

5-Jul-13 Module Position: Position: 6


2.00 Number 105 dB 103 dB 105 dB 103 dB 100 dB 92 dB 87 dB 83 dB 104 dBA 97 dB 94 dB 99 dB 89 dB 81 dB 78 dB 70 dB 67 dB 93 dBA 96 dB 90 dB 90 dB 82 dB 71 dB 66 dB 61 dB 46 dB 84 dBA 104 dB 99 dB 103 dB 98 dB 95 dB 87 dB 83 dB 80 dB 100 dBA 93 dB 95 dB 102 dB 96 dB

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 9 of 10

Quantum Performance Report


Motor Termination Box Design Temp. Fan - Elevation Module Level Fan - Module Length Fan - Module Weight No 20.0 C 0.0 m 1st Level 1705 mm 348 kg Fan Intake - 1kHz Fan Intake - 2kHz Fan Intake - 4kHz Fan Intake - 8kHz Fan Intake - Overall Velocity for Eurovent Energy Calculation

5-Jul-13
91 dB 86 dB 82 dB 80 dB 98 dBA 2.5 m/s

All weights and dimensions are approximate. Motor power input is electrical power input at full load. Eurovent Certified. Product DLL Version 1.9.5.59-100-900 Trane is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. CLCP EURO is certified under the number 04.01.049 and presented on www.eurovent-certification.com.
Remark: All components,special options that are non TOPSS selectable,resulting in a variation in TOPSS performance and dimensional output will render the Eurovent Certification void.

Page 10 of 10