Вы находитесь на странице: 1из 27

TRANSFORMER CONDITION MONITORING

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

TYPES OF TRANSFORMER FAULT


Phase-ground faults - from winding to core or winding to tank Phase-phase faults - between windings Interturn faults - between single turns or adjacent layers of the same winding Arcing contacts Local hotspots caused by shorted laminations External faults causing thermal or mechanical damage Overloads

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 4 of 80; Part 10.1 Basics of TRANSFORMER CM

TYPES OF TRANSFORMER FAULT


Low level internal partial discharges (moisture ingress or design problems) Bushing faults (internal to the tank) Tapchanger faults (often housed in a separate tank) Terminal faults (external to the tank, but inside the transformer zone)

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 5 of 80; Part 10.1 Basics of TRANSFORMER CM

Role of the Transformer

No Transformer

No Power Delivery
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 6 of 80; Part 10.1 Basics of TRANSFORMER CM

Impact of Transformer Failure

No Power Delivery = Loss of Revenue $$$ Power may have to be purchased to meet contractual obligations $$$ Direct Replacement Cost $$$ Bad Publicity & Environmental Damage
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 7 of 80; Part 10.1 Basics of TRANSFORMER CM

Typical Utility Transformer Fleet


Approx 60% are >35yo (End of Life region)

Approx 8% are <10yo (Design Flaw Region)

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 8 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Failure
There are 3 types of Transformer Failure: 1. Sudden/unexpected due to outside influences 2. Design flaw 3. End of Life Failure risk can be reduced by monitoring the Transformer Condition
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 9 of 80; Part 10.1 Basics of TRANSFORMER CM

Predicted End of Life Failure Rate


Failure distribution for a fleet of Transformers installed between 1964 and 1992

Significant Rise in # of Failures

Source: William H Bartley & Rowland I James Jr.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 10 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Users Pain


{ evaluation from beg of 2000s }

There were typically 730 transformer fire and explosions per year in the USA. Many experts anticipate that this number to go up from 1% at beginning of 2000s to 2% after 2010. The emphasis on renewable will put more burden on the existing Transformers

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 11 of 80; Part 10.1 Basics of TRANSFORMER CM

A growing concern for Corporate Risk Managers and Insurance Companies

Why do Transformers Explode?

Transformers are considered by Corporate Risk Managers and Insurers as the most critical equipment inside plants because of the large quantity of oil in contact with high voltage elements.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 12 of 80; Part 10.1 Basics of TRANSFORMER CM

Loose international transformer norms and lack of regulation

Why do Transformers Explode?

The Norm IEC 76 only includes basic electrical measurements and does not cover mechanical design or protection. By comparison, pressure vessels have to comply with adequate rules and controls. Such directives do not exist for transformers that have proven to be more dangerous

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 13 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer electrical and mechanical protection limits

Why do Transformers Explode?

Pressure Relief Valve inadequacy: pressure gradients developed during low impedance faults are too fast for mechanical devices. All transformers that have exploded have been protected with Pressure Relief Valves.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 14 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer electrical and mechanical protection limits

Why do Transformers Explode?

Buchholz and Rapid Pressure Relay inefficiency: Transformer electrical protections are not designed to react to sharp pressure gradients. During the 62 Transformer Protector tests, the Buchholz always failed to detect any gas and oil movement or pressure variation.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 15 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer electrical and mechanical protection limits

Why do Transformers Explode?

Electrical Breaker opening time: the best breaker technology trips in 50 ms far too late to prevent the explosion, which occurs 10 to 50 ms after the low impedance fault. Additionally, the tank pressure keeps increasing after breaker opening
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 16 of 80; Part 10.1 Basics of TRANSFORMER CM

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 17 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Monitoring can Mitigate

1 Transformer / FAILURE

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 18 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

Various systems

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 20 of 80; Part 10.1 Basics of TRANSFORMER CM

Temperature Monitor
Every 6 to 8 C rise in operating temperatures, the expected life of the transformer will go down by half These temperature build-ups cause localized area of high heat and paper damage, followed by events of partial discharge . One needs to have a long term trending of the operating temperature inside the transformer. Should be performed distributed temperature sensing of all the windings
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 21 of 80; Part 10.1 Basics of TRANSFORMER CM

Overtemperature Monitoring
Two temperatures must be monitored:
> Winding temperature (WT) - this can rise rapidly, without much of an increase in oil temperature > Oil temperature (OT) - this can rise slowly to a critical point without an unacceptable winding temperature increase

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 22 of 80; Part 10.1 Basics of TRANSFORMER CM

(dependent on asset management policy)


winding alarm - 90C to 110 C winding trip - 110C to 135C oil alarm - 80C to 95C oil trip - 95C to 115C Oil trip may be disabled if transformer is readily accessible by maintenance crews on the grounds they can visit sub and may be able to remedy problem this is a controversial practice.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 23 of 80; Part 10.1 Basics of TRANSFORMER CM

Typical alarm and trip levels

Temperature vs life
Economic gains are possible from short time overloads - life used calculations may permit higher temperatures for short periods, but WT trip needs to be more complex or monitored 110 C winding hot spot temperature gives standard 20-25 year life of insulation Roughly every 7 C increase in temperature doubles the rate of loss of life for paper in oil insulation
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 24 of 80; Part 10.1 Basics of TRANSFORMER CM

END WINDING TEMPERATURE SENSING


By incorporating fiber-optic sensors into transformer windings temperature data can be used to monitor for hot spots within the transformer and to provide ratings based on safe operating temperatures. Alternatively, a fiber-optic cable can be installed after the windings have been wound on the core, or fiber-optic point sensors can be placed at strategic locations.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 25 of 80; Part 10.1 Basics of TRANSFORMER CM

FO Cable part of Distributed Temperature Monitoring

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 26 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

Various systems

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 28 of 80; Part 10.1 Basics of TRANSFORMER CM

How about Vibration monitoring


There are significant differences in the low frequency vibration signal amplitudes and frequency content, dependent on the degree of winding looseness.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 29 of 80; Part 10.1 Basics of TRANSFORMER CM

Low frequency vibration measurement ..... symptoms:


I. Detection of significant difference in low frequency response, II. Shift of existing resonance, III. Creation of new resonance, IV. Change in shape of various plots would potentially indicate mechanical or electrical problem with
I. II. the winding and transformer core

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 30 of 80; Part 10.1 Basics of TRANSFORMER CM

Vibration Severity Criteria for Transformers


{velocity sensor data - Eng units: ips }

Started with the following overall levels.


0.25-.50 ips-Minor 0.50-.75 ips- Intermediate Watch list (further investigate) 0.75-1.0 ips- Serious Look for oil leaks, hot metal gasses and increasing sound levels. 1.00 ips or greater-Critical Oil leaks, gas generation rates and hot spots.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 31 of 80; Part 10.1 Basics of TRANSFORMER CM

Vibration Severity Criteria for Transformers


{velocity sensor data - metric units: mm/s }

Started with the following overall levels:


4,5 9,0 mm/s-Minor 9,0-13,5 mm/s - Intermediate Watch list (further investigate) 13,5-18,0 mm/s - Serious Look for oil leaks, hot metal gasses and increasing sound levels. > 18,00 mm/s -Critical Oil leaks, gas generation rates and hot spots.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 32 of 80; Part 10.1 Basics of TRANSFORMER CM

Vibration Severity Criteria


Alarm Parameters for Transformers [ips]
Nominal Freq / Hz Frequency / Hz 5 to 115 Label Name Sub-sync One Times 1st Odd Two Times 2nd Odd Three Times 3rd Odd Four Times Hi End Warning 0.05 0.25 0.1 0.15 0.1 0.15 0.1 0.1 0.1 Alert 0.1 0.5 0.2 0.25 0.2 0.25 0.2 0.2 0.2 Danger 0.25 1.0 0.3 0.5 0.3 0.5 0.3 0.3 0.3

120 240 360 480

115 to 125 125 to 235 235 to 245 245 to 355 355 to 365 365 to 375 375 to 485 485 to 1000

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 33 of 80; Part 10.1 Basics of TRANSFORMER CM

Vibration Severity Criteria


Alarm Parameters for Transformers [mm/s]
Nominal Freq / Hz Frequency / Hz
5 to (2*fLINE 5)

Label Name Sub-sync One Times 1st Odd Two Times 2nd Odd Three Times 3rd Odd Four Times Hi End

Warning 0.9 4,5 1,8 2,7 1,8 2,7 1,8 1,8 1,8

Alert 1,8 9,0 3,6 4,5 3,6 4,5 3,6 3,6 3,6

Danger 4,5 18 5,4 9,0 5,4 9,0 5,4 5,4 5,4

2*fLINE 4*fLINE 6*fLINE 8*fLINE

(2*fLINE 5) to (2*fLINE + 5) (2*fLINE + 5) to (4*fLINE 5) (4*fLINE 5) to (4*fLINE + 5) (4*fLINE + 5) to (6*fLINE 5) (6*fLINE 5) to (6*fLINE + 5) (6*fLINE + 5) to (8*fLINE 5) (8*fLINE 5) to (8*fLINE + 5) (8*fLINE + 5) to 1000

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 34 of 80; Part 10.1 Basics of TRANSFORMER CM

Where to measure the vibrations


H IG H S ID E

LT C S ID E #2
25C LO HI

X
X

X
X

X
X

S ID E #4

Shell Form
S ID E #3

Eight readings ~ Approx 1,6 m from bottom of core, and 45 cm from corner
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 35 of 80; Part 10.1 Basics of TRANSFORMER CM

Where to measure the vibrations


0.15@240 0.09@360

0.22ips Side 3L 0.9ips

Side 3R

Side 4L

Overhead View of Transformer


Snd=78db AE=30Cts Snd=80db AE=35Cts

Side 2R

Side 4R Side 1L

High Voltage Side Side1R

0.05ip s Side 2L

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 36 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING (ACOUSTIC EMISSION)

Major Failure Mechanisms


Aging of paper Moisture in oil Looseness movement of the windings

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 38 of 80; Part 10.1 Basics of TRANSFORMER CM

For the Aging of Paper


The occurrence of PD reveals the existence of dielectric insulation problems within the circuit breaker and the windings. Typically the higher the emitted power and frequency of occurrence, the higher the chance of failure by dielectric breakdown. PD can be measured: On-Line or Off-Line.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 39 of 80; Part 10.1 Basics of TRANSFORMER CM

Electrical PD diagnostic techniques


PD measuring circuits according to IEC 60270 often applied in onsite/on-line PD investigations frequently used circuit in test laboratories

[Knig, 1993]

a) coupling device in series with the coupling capacitor

b) measurement at a bushing tap

Components: AC voltage source U, optional blocking impedance Z, coupling capacitor CK, measuring impedance Zm, a measuring instrument M and generalized test object Ca.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 40 of 80; Part 10.1 Basics of TRANSFORMER CM

Electrical PD diagnostic techniques


PD Measuring Impedance for Bushing Tap Installation Decoupling of PD signals from the bushing tap in a wide frequency range up to 30 MHz Lower cut-off frequency < 60 kHz
500 kV Transformer Bushing

Additional voltage signal for phase-resolved measurements Superimposed PD and test voltage signal Very fast and safe over-voltage protection TNC-socket for signal output Special feature for continuous PD monitoring (IP 68)
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 41 of 80; Part 10.1 Basics of TRANSFORMER CM

Electrical PD diagnostic techniques


Advanced solution: ACOUSTIC EMISSION added
Electromagnetic (UHF) method
PD (partial discharge) Sound field (acoustic wave)

Acoustic method

))

)) ))

)
))

PiezoSensor

measuring system

Key characteristics:
non-destructive on-line application of the sensors (no bushing tap necessary) immunity against a wide range of disturbing signals on-site (e.g. corona) in principle immun against electric noises signal attenuation depends on PD site very low noise level (faradays cage) very low attenuation in oil and solid insulation

geometric PD location possible PRPD patterns possible short arrival times no apparent charge information is delivered so far
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 42 of 80; Part 10.1 Basics of TRANSFORMER CM

))

Electromagnetic wave example sensor monopole

measuring system

IEC 62478 - IEC Proposal, now already Draft level


"Non-conventional PD-measurements"
In the past few years, there has been the development of many so-called nonconventional PD measurement methods. Partial discharges (PDs) generate pressure waves, sound, light and electromagnetic waves. These physical effects can be detected by different sensors and so there is the possibility to detect PDs with non-conventional methods besides the conventional electrical measurement. The main method for PD measurement is electromagnetic (HF/VHF/UHF) and acoustic measurements. Also, there have been a lot of papers published using these methods. Therefore, IEC TC42 has in the meeting of September 1st , 2005 in Beijing, decided to proceed with this new work item called Measurement of PDs by electromagnetic (e.g. UHF) and acoustic methods and to form a new working group for this task. (......) The task of this new WG is to collect all the used applications of these methods to compare them with each other and to look at their frequency range. Another differentiation of the measuring technique is if it is a narrow bandwidth or a wide band frequency measurement technique. This work will also include the use and the techniques of the different sensors, their frequency range and their sensitivity. Also, it will investigate the issue of the methods, the possibility of PD location and if a calibration or in minimum a sensitivity check is possible. The WG will start with the electromagnetic methods and after finishing will move forward to the acoustic methods.
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 43 of 80; Part 10.1 Basics of TRANSFORMER CM

System Check for UHF (on transformers)

Performance Check
Functional check of the whole measuring path including sensors and partial discharge (PD) acquisition system not necessarily transmission of electromagnetic waves through the test object , one-port solutions are possible

Sensitivity Check
Emission of electromagnetic waves into the test object necessary and known distance between sensors and injection location Pulse Generator injection necessary to determine relation between the apparent charge (pC) and measured quantities (e.g. V,W,J) through simultaneous measurement one-port solutions might be possible in relation to the wave length (for compact objects, not for extended objects)

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 44 of 80; Part 10.1 Basics of TRANSFORMER CM

Instruments classification based on Bandwidth


Class
Mode

Frequency Domain Measurement Zero Span Full Spectra

Time Domain Measurem.

Ultra Wide Band

Frequency Band

PD Pattern

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 45 of 80; Part 10.1 Basics of TRANSFORMER CM

Advanced tools for PD monitoring Electromagn. PD Tests


Cone-shaped active drain valve UHF-sensors
for the decoupling of electromagnetic PD signals from the inner of an oil-paper-insulated transformer PD-signals in the UHF frequency range (mainly 300 MHz 1 GHz) sensors support Performance/Sensitivity Check (high-frequency test impulses can be injected with additionally integrated electrode) sensor head is grounded (for lower frequencies) sensor application at oil valves, which are available e.g. for oil filling or draining (liquid tightness is tested for 120C warm oil with 5 bar compression)

View from inside the transformer


Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 46 of 80; Part 10.1 Basics of TRANSFORMER CM

Type-Test Cone-shaped active drain valve UHF-sensors

Oil pressure estimation

Combined temperature/pressure test

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 47 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING (ACOUSTIC EMISSION)

Advanced tools for PD monitoring Acoustic PD location


Alternatives of arrival time based positioning

1. Mixed-acoustic methods:
electro-acoustic (test laboratory or on-site/off-line) electromagnetic- acoustic (test laboratory or on-site, off-line or on-line)

sensor 3 PD sensor 1
2 s1 s

sensor 3 sensor 2 sensor 2 sensor 1 electrical PD triangulation

Observation equations:

(x x ) + (y y ) + (z z ) = (v
2 2 s1 s1

( x x s 2 )2 + ( y y s 2 )2 + ( z z s 2 )2 = (v s T S 2 )2 (x x s 3 )2 + ( y y s 3 )2 + (z z s 3 )2 = (v s TS 3 )2

T S1 )

t
S3 (xs3 , ys3, zs3 )

unknowns x, y, z

Input parameters: sensor coordinates, sound velocity, meas. time difference


Si (xsi , ysi , zsi )

S4 (xs4 , ys4 , zs4 )


Di

D3

D4

D2 D1

2. All-acoustic methods:
all-acoustic (test laboratory or onsite, off-line or on-line with reduced sensitivity)

PD (x, y, z)

S2 (xs2 , ys2 , zs2 )

S1 (xs1, ys1, zs1 )

schematic view of a transformer tank with acoustic sensors


Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 49 of 80; Part 10.1 Basics of TRANSFORMER CM

Vibration measurements extended with: sound & AE


0.15@240 0.09@360

0.22ips Side 3L 0.9ips

Side 3R

Side 4L

Overhead View of Transformer


Snd=78db AE=30Cts Snd=80db AE=35Cts

Side 2R

Side 4R Side 1L

High Voltage Side Side1R

0.05ip s Side 2L

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 50 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

Major Failure Mechanisms


Aging of paper Moisture in oil Looseness movement of the windings

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 52 of 80; Part 10.1 Basics of TRANSFORMER CM

Moisture In Oil
Moisture in oil is destructive to cellulose, especially in the presence of oxygen. Presence of moisture will facilitate partial discharge. Fiberoptics moisture sensor can be a part of a CM solution
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 53 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

Various systems

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 55 of 80; Part 10.1 Basics of TRANSFORMER CM

Dissolved Gas Analysis (DGA)


Commonly accepted as the most effective method of Transformer Assessment
Power Transformers contain insulating oil When a fault occurs, the oil breaks down generating gas These gases dissolve into the oil Fault type/severity are indicated by gases present
1. 2. 3. 4. Samples collected manually from Transformers Analysis performed by specialist oil laboratories Sample collection to analysis ranges from days -> weeks Performed on an regular (6 12 month) basis
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 56 of 80; Part 10.1 Basics of TRANSFORMER CM

Traditional Methods of DGA

The most important aspects of DGA

The type of gas created indicates the nature of the fault. The rate of increase in these gases indicate the severity of the fault.

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 57 of 80; Part 10.1 Basics of TRANSFORMER CM

Oil pyrolysis (Thermal Heating)


HYDRO GEN H 2

GAS CONSTITUENTS

METH ANE

CH 4

ETH ANE

C2 H 6
ETH YL ENE C 2 H4 ACE TYLENE C 2 H2

R eferences: M . Duval, El ect ra,133, 40 (1990 ). T. V. Oommen, Ga s Generat ion in Power T ra nsformers

250

500

Fault Temperature ( C )

750

1000

1250

1500

1750

2000

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 58 of 80; Part 10.1 Basics of TRANSFORMER CM

Cellulose pyrolysis (Thermal Heating) Life of paper ~ Life of transformer


GAS CONSTITUENTS

CARBON MONOXIDE CO

CARBON DIO XIDE CO2

R eferences: M . D uva l, Ele ct ra ,133,40 (1990 ). T. V. Oomm en, G as Ge ne ra ti on i n Power Transforme rs

100

200

250

300

400

500

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 59 of 80; Part 10.1 Basics of TRANSFORMER CM

The problem with manual sampling...


A fault can develop and cause failure between samples. A single sample cannot provide rate of change or fault severity. Human error sampling & analysis. These weaknesses are relatively insignificant given:

Transformer catastrophic failure can occur in hours, days or weeks


Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 60 of 80; Part 10.1 Basics of TRANSFORMER CM

Online DGA
for a Transformer

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 61 of 80; Part 10.1 Basics of TRANSFORMER CM

Online Monitoring
Monitoring unit is connected to Transformer Unit automatically samples oil from Transformer Gas extracted from oil, concentration measured Oil sample returned to Transformer Process repeated

Benefits
Early fault detection Extend Transformer life

Save Money $$$$

Condition Based Maintenance Defer Capital Expenditure Avoid catastrophic failures


Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 62 of 80; Part 10.1 Basics of TRANSFORMER CM

Examples of Discrete Monitoring Products

TRANSPORT X*
Portable DGA 7 fault gases + moisture Simple & reliable

HYDRAN M2

MINITRANS*

TRANSFIX*

On-line Integrated Monitor Cost-Effective on-line DGA Full 8 gas + Gas & Moisture in oil Discrete gas measurement moisture on-line DGA On-line Models/Data storage (H2, CO, C2H2 + H2O)

Intellix MO150

MULTITRANS*

TAPTRANS*
Full 8 gas on-line DGA for main tank & LTC in one unit

SIGMA TX* (TBC)


Comprehensive transformer monitoring & modelling Full 8 Gas DGA Bushing/PD/Cooling System/FO hot spot

Low Cost Transformer Full 8 gas multi tank DGA Monitoring System

*Kelman Products

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 63 of 80; Part 10.1 Basics of TRANSFORMER CM

Online DGA
for a Transformer an EXAMPLE.....

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 64 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Failure Case Study


Normal DGA gas levels

Gas ppm value

Sample Date/Time
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 65 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Failure Case Study

Gas ppm value

Gases rise over 3 days as fault occurs sampling frequency automatically increases

Sample Date/Time
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 66 of 80; Part 10.1 Basics of TRANSFORMER CM

Transformer Failure Case Study


Fault severity high Transformer removed from service

Gas ppm value

Fault occurs rapidly over 8 days manual sampling would not have been sufficient to detect

Sample Date/Time
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 67 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

A COMPLEX
MONITORING

SYSTEM

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 69 of 80; Part 10.1 Basics of TRANSFORMER CM

A 300MVA transformer with a DGA system and a PD On-Line monitoring installed

FARADAY tMEDIC
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 70 of 80; Part 10.1 Basics of TRANSFORMER CM

Purpose: Transformer Monitoring and Diagnostics

Product: System 1 Integrated Substation

HYDRAN

FARADAY, tMEDIC or TMCS Units

Chosen KELMAN products

WAN / LAN

Process: Monitoring Modbus Ethernet Scanning Display Exception Alarm Decision SupportSM

Payoff: Typically 5 to 8 years added life expectancy


Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 71 of 80; Part 10.1 Basics of TRANSFORMER CM

Recommended products for Power Generation Area

SIGMA TX (TBC) TRANSFIX


Full 8 gas (+ moisture) On-Line DGA Comprehensive transformer monitoring & modelling Full 8 Gas (+ moisture) On-Line DGA Bushing/PD/Cooling System/FO hot spot

At less than 1% of the initial Transformer cost: both solutions provide the vital information to protect & maximise Power Station critical assets
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 72 of 80; Part 10.1 Basics of TRANSFORMER CM

DGA en Transformadores de Poder


PT1 PT2

Minitrans DGA Monitor

Minitrans DGA Monitor

Ethernet

System 1

Perception Express

Parmetro Hidrgeno (H2) Acetileno (C2H2) Agua (H2O)

Rango 5 5,000 ppm 0.5 50,000 ppm 1-100% de Humedad Relativa

Monxido de Carbono (CO) 2 50,000 ppm

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 73 of 80; Part 10.1 Basics of TRANSFORMER CM

Descargas Parciales en Transformadores de Poder


TP1 3 x HFCTs ( High Frequency Current Transformers TP2 3 x HFCTs ( High Frequency Current Transformers

PDCheck - Techimp

PDCheck - Techimp

Ethernet

System 1

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 74 of 80; Part 10.1 Basics of TRANSFORMER CM

A SERVER OF
A HS DIAGNOSTIC SYSTEM:

An example with TRANSFIX from KELMAN

UNIT #1 PROTECTION SYSTEM / ESD


{ from BINARY OUTPUTS of the M&PS SYSTEM }

UNIT #2 PROTECTION SYSTEM / ESD


{ from BINARY OUTPUTS of the M&PS SYSTEM }

UNIT #3 PROTECTION SYSTEM / ESD


{ from BINARY OUTPUTS of the M&PS SYSTEM }

Unit 1

Unit 2

...

Unit N
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 75 of 80; Part 10.1 Basics of TRANSFORMER CM

BASICS of TRANSFORMER CM
1. Introduction to TRANSFORMER MAINTENANCE 2. TEMPERATURE SENSING 3. VIBRATION MONITORING 4. PARTIAL DISCHARGES (ACOUSTIC EMISSION) 5. MOISTURE MONITORING 6. GAS MONITORING DGA 7. Examples of SYSTEM SOLUTIONS 8. ENDING

The Cost of Transformer Failure


A study by The Hartford Steam Boiler Inspection and Insurance Company (HSB) estimates the cost of Transformer failure at approx $10,000 per MVA

HSB has been founded in 1866

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 77 of 80; Part 10.1 Basics of TRANSFORMER CM

The Cost of Transformer Failure


A study by The Hartford Steam Boiler Inspection and Insurance Company (HSB) estimates the cost of Transformer failure at approx $10,000 per MVA Online DGA monitoring can cost less than 1% of the initial Transformer Cost
HSB has been founded in 1866
Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 78 of 80; Part 10.1 Basics of TRANSFORMER CM

COST OF PREVENTION

Transformer Life Management

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 79 of 80; Part 10.1 Basics of TRANSFORMER CM

Questions

Ver. 2011-12-01 Ryszard.Nowicki@ge.com : 00:01 Page: 80 of 80; Part 10.1 Basics of TRANSFORMER CM

Вам также может понравиться