SURGE
Surge is defined as self oscillation of pressure and flow, often including a flow reversal
Every centrifugal or axial comp has a characteristics combination of max.head and and min.flow beyond which it will surge.during surge there is actual reversal of flow accompanied by pressure drop .
SURGE DESCRIPTION . Flow reverses in 20 to 50 milisec. .Surge cycle at a rate of .3 to 3 sec. .Comp. Vibrates . Temperature rises. .Whooshing noise .trips may occur
Hp
DUE TO LOW FLOW ,IT NO LONGER CAN ADHERE TO SUC. SIDE OF BLADE SO STALLING OF FLOW
1. 2. 3.
Pd R loss Pv
. .
.electro motor is started C .machine acc.to normal apeed. Comp.reaches performance curve .flow goes up faster becoz Press. Is integral Of flow
Qs
B C
Pd
.COMP. REACHES SURGE POINT A .comp loses its ability to make pressure .suddenly Pd drops and Pv>Pd A D
. .
B C
Pd A D
.result of flow reversal Is that pressure goes down .presuure goes down ==less negative flow .operating pont goes to c
Qs
. From A TO B
From C TO D ABCDA
.comp. Starts to build pressure .comp rides curve toward surge .point A is reached .surge cycle is complete Pd A D
C .system pressure is going down .comp is again able to overcome Pv .comp jumps back to performance curve to d .forward flow established
Qs
EFFECTS OF SURGING 1. RAPID FLOW OSCILLATION AND PRESSURE OSCILLATION CAUSES PROCESS IN STABILITY 2. RISING TEMP. INSIDE COMPRESSOR 3. TRIPPING OF COMP. 4. MECHANICAL DAMAGE A. RADIAL BEARING LOAD
DURING INITIAL PHASE OF SURGING SIDE LOAD IS PLACED ON ROTAR WHICH ACT PERPENDICULAR TO AXIS
DISCHARGE R
R PROCESS
R PROCESS +VALVE
Q2
SURGE LINES
STOPPING SURGE REQUIRE THE ABILITY TO KNOW THE IMPENDING SURGE WHICH MEANS KNOWING WHERE IS THE OPERATING POINT RELATIVE TO SURGE POINT SO SURGE CONTROL LINE IS DEFINED FOR SET POINT OF ANTISURGE CONTROLLER
Hr
SLL SCL SLL SURGE LIMIT LINE SCL SURGE CONTROL LINE b. Is the distance between two lines(margin of safety)
Q2
Protection 1
SLL B A
SCL
Protection 1
. Since surging is fast so for PI controller to be fast b shuld be high. . But increasing b will limit comp. Operation in lower thruput and unnecessary will recycle SLL Speed can also be increased by adding derivative value, but usingPID will open valve in response to any movement Toward surge,even if op. point Is away from limit.
b SCL
Protection 1
ENHANCING THE EFFECTIVENESS OF PI CONTROLLER BY ADAPTIVE GAIN .WHEN THE OPERATING POINT MOVES FAST
TOWARD SCL ,(by calculating time derivative of operating point)ADAPTIVE GAIN MOVES THE SCL TOWARD OPERATING POINT
SLL
.THIS ALLOWS THE PI CONTROLLER TO REACT EARLIER .AS A RESULT SMALL B CAN BE ACHIEVED WITHOUT SACRIFICING RELIABILITY.
b SCL
Protection 2
ANTISURGE CONTROLER OPERATION RECYCLE TRIP LINE .WHEN PI CONTROLLER IS TOO SLOW
TO CATCH THE DISTURBANCE .OPERATING POINT HITS RTL .OPEN LOOP RESPONSE IS TRIGGERED
SLL C
RTL B A
TOTAL
SCL
O/P VALVE
PI RTL
TIME
Protection 2
ANTISURGE CONTROLER OPERATION RECYCLE TRIP LINE .OPEWRATING POINT MOVES BACK
TO SAFE SIDE OF RTL
-RT FUNCTION DECAYS OUT STEP RESPONSE - PI CONTROLLER INTEGRATE TO STABILIZE ON SCL
SLL C
RTL B A
TOTAL
SCL
O/P VALVE
PI RTL
TIME
Protection 3
RTL
BENEFITS OF SO 1.ADDITIONAL SURGING IS AVOIDED BY LARGE SURGE MARGIN 2.ALARM OF SURGE IS PRODUCED(this has to reset for normalisation)
.VALVE CHARACTERSTICS - it can operate anywhere between 0% to 100%. -linear characterstics is preffered.