Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No DB
Use Distribution board Incomer

Supply fault rms current level (KVA) 349 (taken from FGT short circuit calculations)
% Reactance 1
Protective device MGI125N
Range 125 125
Short circuit rating 25 kA
Short circuit release 10 * Range max
Max energy let through 75 KA2s
Max short circuit setting 1250 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 349 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
35 151117 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


16.0320 Seconds
16032.02 milliseconds
Conductor energy let through capability
25050025 A2s
25050.03 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 1 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES166201
Use No1 Coanda Fan

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA2s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A2s
127.81 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 2 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES266201
Use No2 Coanda Fan

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA2s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A2s
127.81 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 3 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES126101
Use No1 Combustion Fan

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA2s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A2s
127.81 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 4 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES226101
Use No2 Combustion Fan

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA2s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A2s
127.81 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 5 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES132002
Use No1 Analytical supply

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA2s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 6 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES11001
Use No1 Cremator panel supply

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA2s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 7 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES21001
Use No2 Cremator panel supply

Supply fault rms current level (KVA) 349


% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA2s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 8 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES101
Use No1 Control panel isolator

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device PKZM0-16
Range 16 16
Short circuit rating 25 kA
Short circuit release 10 * Range max
Max energy let through 25 KA2s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 9 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No MCB 1
Use PLC and Instrument supplies

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 10 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No MCB 2
Use Underpressure and sockets

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 11 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No MCB 3
Use Burner supplies

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 12 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No MCB 4
Use 230/24V Transformer supply

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 13 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No MCB 5
Use Analytical supply

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 14 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES14101
Use Insertion door supply

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 15 of16 20060101.xls


Short circuit protection calculations

Site Name March Crematorium


Contract Number C4???
Tag No EES13101
Use Deash door supply

Supply fault rms current level (KVA) 37


% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA

Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor Cable test
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed

Heating time (t) seconds = (k2*s2)/I2


7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A2s
46.01 KA2s

Conductor short circuit energy capability Passed


Device tripping speed Passed

Note device OK

Page 16 of16 20060101.xls