Communication Modbus BCM ULP pour Micrologic Modbus BCM ULP communication for Micrologic
FDM121
100
Masterpact NT
menu
33106
DB126722
Masterpact NW
5100512864A-02
5100512864A-02
/60
Sommaire
1 2
Prcautions prendre avant d'excuter une tche quelconque...........................................................................................11 Installation du module de communication "appareil" BCM ULP Modbus............................................................................12 Compact NS fixe manuel............................................................................................................................................................. 12 Compact NS et Masterpact NT/NW fixes commande lectrique.............................................................................................. 15 Compact NS et Masterpact NT/NW dbrochables...................................................................................................................... 17 Installation du module de communication "chssis" CCM Modbus.................................................................................... 19 Compact NS et Masterpact NT/NW dbrochables...................................................................................................................... 19
4 5 6
Paramtres de communication avec Micrologic A.................................................................................................................. 21 Paramtres de communication avec Micrologic E.................................................................................................................. 23 Paramtres de communication avec Micrologic P / H............................................................................................................. 26
5100512864A-02
Consignes de scurit
Informations importantes
REMARQUE IMPORTANTE
Linstallation, lutilisation, la rparation et la maintenance des quipements lectriques doivent tre assures par du personnel qualifi uniquement. Schneider Electric dcline toute responsabilit quant aux consquences de l'utilisation de cet appareil. Une personne qualifie est une personne disposant de comptences et de connaissances dans le domaine de la construction et du fonctionnement des quipements lectriques et installations et ayant bnfici d'une formation de scurit afin de reconnatre et d'viter les risques encourus.
Documents associs
Pour des instructions supplmentaires, se refrer : b la documentation technique du disjoncteur appropri b le manuel utilisateur Masterpact Modbus COMBT32EN (en anglais uniquement) b le manuel utilisateur du systme ULP TRV99100. Vous pouvez tlcharger ces publications techniques ainsi que d'autres informations techniques partir de notre site Web: www.schneider-electric.com.
DANGER
L'indication DANGER signale une situation dangereuse imminente et, si elle n'est pas rsolue, entranera la mort ou des blessures graves.
AVERTISSEMENT
L'indication AVERTISSEMENT signale une situation potentiellement dangereuse et, si elle n'est pas rsolue, risque d'entraner la mort ou des blessures graves.
ATTENTION
L'indication ATTENTION signale une situation potentiellement dangereuse et, si elle n'est pas rsolue, risque d'entraner des blessures d'ampleur mineure modre.
ATTENTION
L'indication ATTENTION, utilise sans le symbole d'alerte de scurit, signale une situation potentiellement dangereuse et, si elle n'est pas rsolue, risque d'entraner des dommages aux quipements. 5100512864A-02 /60
Consignes de scurit
Avant de commencer
1
AVERTISSEMENT
PERTE DE COMMANDE bL e concepteur d'un circuit de commande doit tenir compte des modes de dfaillance potentiels des canaux de commande et, pour certaines fonctions de commande critiques, prvoir un moyen d'assurer la scurit en maintenant un tat sr pendant et aprs la dfaillance. Larrt durgence et larrt en cas de sur-course constituent des exemples de fonctions de contrle essentielles. b Des chemins de contrle spars ou redondants doivent tre fournis pour les fonctions de contrle essentielles. b Les chemins de contrle du systme peuvent comprendre les liaisons de communication. Il est ncessaire de tenir compte des consquences des retards de transmission inattendus ou des dfaillances dune liaison.(1) b Chaque mise en uvre dun disjoncteur dot d'un BCM ULP doit tre teste individuellement et de manire approfondie afin de vrifier son fonctionnement avant sa mise en service. Le non-respect de ces instructions peut provoquer la mort, des blessures graves ou des dommages matriels.
(1) Pour un march aux normes NEMA, se reporter la directive NEMA ICS 1.1 (dernire dition) intitule "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control".
RISQUE DE CHOC LECTRIQUE, DEXPLOSION OU DARC LECTRIQUE b Utilisez des quipements de protection individuelle (EPI) et respectez les procdures de scurit. Pour un march aux normes NEMA, voir NFPA 70E. b Seul un personnel qualifi est autoris installer cet appareil ainsi qu' en assurer l'entretien. b Dbranchez toutes les sources d'alimentation de cet appareil avant toute opration interne ou externe sur l'appareil. b Utilisez toujours un dispositif de mesure de la tension correctement calibr afin de veiller ce que lunit soit hors tension. b Remettez en place tous les quipements, les portes et les capots avant de remettre l'appareil sous tension. Le non-respect de ces instructions entranera la mort ou des blessures graves.
DANGER
5100512864A-02
/60
1 appareil fixe
appareil dbrochable
Dfinition des abrviations BCM = Breaker Communication Module (module de communication disjoncteur). ULP = Universal Logic Plug (Systme de raccordement ULP). CCM = Chassis Communication Module (module de communication "chssis").
5100512864A-02
DB401539
1 unit de contrle Micrologic 2 module de communication "appareil" BCM ULP Modbus 3 module de communication "chssis" CCM Modbus (optionnel)
Prsentation gnrale de loption COM.
/60
Architecture de la communication
2
Appareil dbrochable commande lectrique
2
OF SD SDE
CE CT CD
3 6 3
4 5
MX1 XF OF SDE FP CH
Module CCM Modbus Un module de communication "chssis" CCM Modbus supplmentaire doit tre mont sur un rail DIN proximit de l'appareil et reli : b au module de communication "appareil" BCM ULP Modbus dont il conserve l'adresse si l'appareil est dbroch b des contacts auxiliaires chssis (CD, CT, CE) qui communiquent les positions de l'appareil dans le chssis.
Remarque : une procdure de mise en route spcifique doit tre suivie (voir page 28). 5100512864A-02
DB401540
1 2 3 4 5 6
module de communication "appareil" BCM ULP Modbus module de communication "chssis" CCM Modbus (optionnel) OF, SDE ... micro-interrupteurs contacts CE, CD et CT auxiliaires de commande voltmtrique communicants MX et XF bornier COM (E1 E6)
: Filaire : Modbus
/60
Schma de principe
Caractristiques b Jusqu' 31 appareils fixes ou 15 appareils dbrochables. b Longueur maximum du bus y 1 200 mtres. b Vitesse de transmission maximale = 19 200 bauds. Alimentation des modules COM b Modules COM : 24 V CC b Le module d'alimentation externe (AD) est recommand (voir le formulaire de commande pour les appareils Masterpact NT/NW et Compact NS). L'alimentation de l'unit de contrle doit tre isole. Consommation des modules COM et des units de contrle Micrologic b Module de communication "appareil" BCM ULP Modbus : 40 mA. b Module de communication "chssis" CCM Modbus : 55 mA. b Afficheur de tableau FDM121 : 21 mA b Interface de communication Modbus : 21 mA b Module d'alimentation externe (AD) jusqu' 1 A (24 V CC).
1 2 3 24 V c 5 6 7 8 9 10 11
OK OK OK Mode Mode Mode
12 13 14
DB401541
Remarque : pour procder la configuration des units de contrle Micrologic lorsqu'il n'y a pas de source auxiliaire, alimenter ces units individuellement l'aide de la mallette test et de la prise test en face avant.
1 2 3 4
Logiciels RSU / RCU Ethernet Passerelle Ethernet (EGX100) Module dalimentation externe (AD) 5 Rseau Modbus
6 Module de communication "chssis" CCM Modbus 7 Afficheur de tableau FDM121 8 Cordon ULP de disjoncteur 9 Bornier COM 10 Cblage prfabriqu
11 Module de communication "appareil" BCM ULP Modbus 12 Module dinterface de communication Modbus 13 Cble ULP 14 Cordon Compact NSX
Schma de principe d'un systme de communication mettant en uvre le protocole Modbus. 5100512864A-02 /60
2
rseau Modbus systme de cblage fourni avec option MX1/XF
E3 E1 E2
E4 E5
E6
1/2
3/4/5/6/7
DB401542
b b b
5100512864A-02
/60
Les appareils dbrochables ncessitent deux modules de communication : b un module de communication "appareil" BCM ULP Modbus mont comme indiqu en page 7 b un module de communication "chssis" CCM Modbus livr sparment dans un emballage spcifique qui doit tre : v mont sur rail DIN v raccord au module de communication "appareil" BCM ULP Modbus, voir page 14 v raccord aux contacts auxiliaires chssis (CE, CD, CT), voir page 20. Une fois les oprations ci-dessus effectues, le module de communication "chssis" CCM Modbus doit tre raccord au rseau Modbus. Description du module de communication "chssis" CCM Modbus 1 Bornes de lalimentation 24 V. 2 Connecteur "rseau" pour le raccordement au rseau Modbus. 3 Connecteur "disjoncteur" pour le raccordement au module de communication "appareil" BCM ULP Modbus. 4 Bornes de sortie 24 V pour l'alimentation du module de communication "appareil" BCM ULP Modbus. 5 Bornes vis pour le raccordement aux contacts auxiliaires chssis (CE, CT, CD). 6 Bouton de synchronisation des adresses. 7 Voyants d'tats de module (voir la section sur les Modes de fonctionnement en page 29).
5100512864A-02
+ +
CCM
Addres sync.
Disjoncteur
3
DB401543
CT
CD
CE
Breaker
CE
Etapes de l'installation du module de communication "chssis" Modbus sur Compact NS et Masterpact NT/NW dbrochables. 1
7 6
Fault
shield
Disjoncteur
Com.
Network
Rseau
Address sync.
CT
CD
CE
Breaker
5 Composants.
4 10/60
DB126731
3
1
push
Appareil fixe Avant toute intervention sur l'appareil, mettez toujours ce dernier hors tension en procdant comme indiqu ici. Les appareils dbrochables doivent tre placs en position dbroch.
O
ON push
OFF push
arged disch
push
ON
OFF
O OFF
disch
arged
O OFF
I
OFF push
ON push
arged disch
O OFF
E47085A
2
E47086A
O OFF
discharged
Appareil dbrochable
O OFF
push
ON
push
disch
arged
O OFF
push
push
ON
OFF
d arge disch
O OFF
I
3
ON
push
push
O OFF
push
OOFF
push
I ON
disch
arge
disch
arged
O OFF
E47084A
2
E47083A
O OFF
discharged
E47082A
O OFF
5100512864A-02
11/60
3
E1 E4 E2 E3 E5 E6
Rseau Modbus
E3 E1 E2
E4 E5
E6
Rseau Modbus
E3 E1 E2
E4 E5
E6
Installation du module de communication "appareil" BCM ULP Modbus sur Compact NS fixe, manuel. 5100512864A-02 12/60
E1 E2
E3 E4
E5 E6
1
E1 E2E3E 4E5 E6
RISQUE DE CHOC LECTRIQUE, DEXPLOSION OU DARC LECTRIQUE Remettez le couvercle du disjoncteur en place avant de mettre le disjoncteur sous tension afin d'viter un contact physique avec des bornes sous tension. Le non-respect de ces instructions entranera la mort ou des blessures graves.
DANGER
E1 E2 E3 E4 E5 E6
E1 E 2 E3 E 4 E5 E6
4
E1 E2 E3 E6 E4 E5
Blue
E1 E2E3E
4E5
E6
E1 E2E3E
4E5
E6
6
DB401545
Cblage de l'option COM (module BCM ULP Modbus) avec ou sans module ULP (FDM121...)
Alimentation externe 24 V c
Micrologic P/H
Modbus Com Adresse 47 Vitesse de transmission 19.2 k 4W, 2W+ULP
A
+ EGX100 Rx- Rx+ Tx- Tx+ + EGX100 Rx- Rx+ Tx- Tx+
w
Micrologic E
4wires
Micrologic P/H
Modbus Com Adresse Vitesse de transmission 19.2 k
B
w
Micrologic E
Cordon ULP de disjoncteur
2W + ULP
4W, 2W+ULP
4 E5 2 E3 E E1 E
E6
E3 E1 E2 E4 E5 E6
DB401546
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise la terre du blindage, toutes les extrmits de blindage non raccordes doivent tre proprement isoles.
5100512864A-02
- +
rouge noir
blanc bleu
BCM ULP
BCM ULP
BCM ULP
14/60
rseau Modbus
rseau Modbus
MX1 / XF
MN MX1 SDE1 SDE1 /MX2 /M2C UC4 /RES XF
PF
MCH
COM
UC1
UC2
UC3
E1 E2E3
E4E5
E6
push
ON
100
%
disc harg ed
40 %
O OFF
DB401547
BCM ULP raccord aux micro-interrupteurs Installation du module de communication "appareil" BCM ULP Modbus sur Compact NS ou Masterpact NT/NW fixes commande lectrique.
5100512864A-02
15/60
Cblage de l'option COM (module BCM ULP Modbus) avec ou sans module ULP (FDM121...)
A RS 485 4 fils Modbus
sans module ULP
100 %
menu
(suite)
Micrologic P/H
Modbus Com Adresse 47 Vitesse de transmission 19.2 k 4W, 2W+ULP
A
o
Micrologic E
4wires
Micrologic P/H
Modbus Com Adresse Vitesse de transmission 19.2 k 4W, 2W+ULP
B
o
Micrologic E
Cordon ULP de disjoncteur rouge noir blanc bleu
2w+ULP
DB401548
bornier client
bornier client
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise la terre du blindage, toutes les extrmits de blindage non raccordes doivent tre proprement isoles.
5100512864A-02
- +
- +
Alimentation externe 24 V c - +
Alimentation externe 24 V c
Alimentation externe 24 V c
bornier client
16/60
3
"Chssis" CCM
100% 40%
D1
MX1 / XF
BCM ULP raccord aux micro-interrupteurs Exemple d'installation du module de communication "appareil" BCM ULP Modbus sur Masterpact NT dbrochable.
5100512864A-02
17/60
Cblage de l'option COM (modules BCM ULP et CCM Modbus) avec ou sans module ULP (FDM121...)
+ -
Micrologic P/H
Modbus Com Adresse 47 Vitesse de transmission 19.2 k 4W, 2W+ULP
A
w
Micrologic E
La configuration B est possible uniquement lorsque la face avant du CCM comporte la marque Schneider Electric.
4wires
Micrologic P/H
Modbus Com Adresse Vitesse de transmission 19.2 k 4W, 2W+ULP
Disjoncteur Rseau
Disjoncteur Rseau
Micrologic E
w
A A
B B
A A
B CCM B + -
A A
B B
A A
B B
Disjoncteur Rseau
+ CCM + -
+ -
+ FDM121
+ CCM + -
A A
B B
A A
B B
2w+ULP
blanc bleu
DB401550
bornier client
bornier client
bornier client
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise la terre du blindage, toutes les extrmits de blindage non raccordes doivent tre proprement isoles.
5100512864A-02
18/60
3
u ea s A B ld ie B A B A R A N et w or k sh
s Addres sync.
Installation du module Montez le module de communication "chssis" CCM Modbus sur un rail DIN symtrique proximit du chssis, de telle sorte que la face avant soit accessible pour les raccordements et le paramtrage. Dans le cas d'un montage sur rail vertical, utilisez une bute pour viter le glissement. Le rail DIN doit tre command sparment.
DB401551
YL
CI
is
Com.
jo
nc
te
ur
Fault
re
ak
er
CE CD CT
33110
5100512662
P 99-44
PP-YYYY-WWW-D-T
XXXXXXXXX
CCM
RISQUE DE CHOC LECTRIQUE, DEXPLOSION OU DARC LECTRIQUE L'utilisation du bouton-poussoir CCM et la consultation des indicateurs ncessitent une alimentation 24 V CC du CCM. Le CCM doit tre plac de telle sorte que le personnel ne soit pas expos des tensions ou une nergie dangereuse lors de l'utilisation du bouton-poussoir ou de la consultation des indicateurs d'tat. Le non-respect de ces instructions entranera la mort ou des blessures graves.
DANGER
Address sync.
Disjoncteur
tiquette signaltique
Contenu du carton d'emballage.
CT
CD
CE
Breaker
Made in France
90 3.54
45 1.77
DB126730
53 2.08 Dimensions.
58 2.28
DB126732
CCM
s modbu Fault C om .
s Addre . s ync
Disjoncteur
CT
CD
CE
Breaker
A A
B B
A A
B B
Contacts chssis CD
CT
Breaker
CCM
CD
CE
911
914
811
812
311
314
DB401552
CT
CD
CE
5100512864A-02
20/60
Pralable
Les paramtres de communication BCM ULP doivent tre rgls au moyen de l'unit de contrle Micrologic ou du programme de tlrglage Masterpact RSU (Remote Setting Utility). Les paramtres de communication BCM ULP sont : adresse, vitesse de transmission, parit et raccordement Modbus. La mise en service de la communication Modbus ncessite d'avoir correctement install les modules, puis de les mettre sous tension. Les units de contrle Micrologic doivent galement tre sous tension pour procder aux oprations de configuration qui suivent.
afficheur numrique
boutons de navigation
passe XX
47 1 2 3 : : : 46
(par dfaut)
DB401553
Micrologic A.
Ecran 1 d'adresse.
21/60
4
19200 9600
(par dfaut)
Ecran 2 Vitesse de transmission La vitesse de transmission par dfaut est 19200 bauds. L'cran affiche XXXX, o XXXX est une des trois valeurs, 4800, 9600 ou 19200. Choisissez une vitesse commune tous les appareils, en utilisant le bouton . Chaque appui bref fait passer la valeur suivante. Une fois la vitesse choisie, appuyez sur le bouton pendant trois secondes puis relchez pour passer l'cran suivant. Ecran 3 Parit La parit par dfaut est Paire. L'cran affiche X, o X est une des deux valeurs E (even) et N (none). Choisissez une parit commune tous les appareils, en utilisant le bouton . Chaque appui bref fait passer la valeur suivante. Une fois la parit choisie, appuyez sur le bouton pendant trois secondes puis relchez pour passer l'cran suivant. Raccordement de la communication Modbus La valeur par dfaut du paramtre de communication de raccordement Modbus correspond 4 fils. Le paramtre de communication de raccordement Modbus (4 fils, 2 fils + ULP) ne peut pas tre rgl au moyen de l'unit de contrle Micrologic A. Utilisez le logiciel Masterpact RSU (Remote Setting Utility) pour rgler ce paramtre.
19200
19200
DB401554
4800
Ecran 2 : vitesse de transmission.
pE
E n
(par dfaut)
DB401555
Ecran 3 : parit.
5100512864A-02
22/60
Activez le mode de navigation en arborescence. Appuyez simultanment sur les deux boutons et pendant trois secondes. Une suite de quatre crans de configuration de la communication Modbus apparat. Ecran 1 Adresse L'adresse Modbus par dfaut de l'appareil est 47. L'cran affiche AdXX si l'adresse courante du module de communication est XX. Une icne en forme de cadenas ferm indique que la valeur est verrouille. Appuyez sur le bouton pour ouvrir le cadenas et affichez le premier chiffre (par ex. 4) clignotant prt modifier. Chaque appui bref sur le bouton fait passer la valeur suivante. Appuyez sur le bouton pour valider cette valeur et afficher le second chiffre (par ex. 7) clignotant prt modifier. Chaque appui bref sur le bouton fait passer la valeur suivante. Appuyez sur le bouton pour valider la nouvelle adresse Modbus (les deux chiffres slectionns) qui s'affiche en permanence. Le cadenas est encore ouvert. Appuyez de nouveau sur le bouton pour verrouiller cette valeur et afficher l'cran 2.
Micrologic 6.0
appuyez simultanment
k
DB401556
5100512864A-02
23/60
4
k k
Ecran 2 Vitesse de transmission La vitesse de transmission par dfaut est 19200 bauds. L'cran affiche XXXX, o XXXX est une des trois valeurs, 4800, 9600 ou 19200. Une icne en forme de cadenas ferm indique que la valeur est verrouille. Appuyez sur le bouton pour ouvrir le cadenas et afficher la valeur (par ex. 19,2) clignotante prte modifier. Choisissez une vitesse commune tous les appareils, en utilisant le bouton . Chaque appui bref fait passer la valeur suivante. Une fois la vitesse slectionne, appuyez sur le bouton pour valider cette valeur dont l'affichage devient permanent. Le cadenas est encore ouvert. Appuyez de nouveau sur le bouton pour verrouiller cette valeur et afficher l'cran 3. Ecran 3 Parit La parit par dfaut est E (paire). L'cran peut afficher une valeur n (aucune) si un paramtre antrieur existe dj. Une icne en forme de cadenas ferm indique que la valeur est verrouille. Appuyez sur le bouton pour ouvrir le cadenas et afficher la valeur (par ex. E) clignotante prte modifier. Modifiez la parit existante en appuyant sur le bouton . Appuyez sur le bouton pour valider cette valeur, dont l'affichage devient permanent. Le cadenas est encore ouvert. Appuyez de nouveau sur le bouton pour verrouiller cette valeur.
5100512864A-02
DB126756
Micrologic 6.0 E
menu
Micrologic 6.0 E
menu
DB126757
24/60
Ecran 4 Raccordement Modbus (4 fils, 2 fils+ULP) La valeur par dfaut du paramtre de communication de raccordement Modbus est 4 fils. b Si le paramtre de communication "4 fils" est slectionn (valeur par dfaut), 4 fils doivent tre connects entre BCM ULP (bornes E3, E4, E5, E6) et le CCM (bornes A, B, A', B'). Le module d'affichage en face avant FDM121 ne peut pas tre raccord. Le raccordement au rseau 4 fils RS 485 Modbus est possible. b Si le paramtre de communication "ULP" est slectionn, 2 fils doivent tre connects entre BCM ULP (bornes E3, E4) et le CCM (bornes A, B). Le module d'affichage en face avant FDM121 peut tre raccord. Le raccordement au rseau 4 fils RS 485 Modbus n'est pas possible.
Micrologic 6.0 E
w
menu
DB127872
5100512864A-02
25/60
Appuyez sur le bouton puis dans l'cran qui s'affiche : b slectionnez le menu configurer com l'aide des touches de navigation et validez b le choix par la touche b slectionnez ensuite, de la mme manire, le menu paramtres Com. Adresse, vitesse de transmission, parit. Dans le menu paramtres com, rglez les trois paramtres Adresse, Vitesse de transmission et Parit comme dcrit prcdemment. Les valeurs par dfaut et disponibles de chaque paramtre sont les mmes que dans le cas prcdent. Voir les informations des Ecrans 1, 2 et 3. La validation de chaque paramtre se fait par la touche . Aprs la validation du paramtre parit, appuyez sur la touche . Le message "Voulez-vous enregistrer les paramtres ?" s'affiche. Slectionnez Oui et validez par la touche . Les 3 paramtres sont enregistrs.
5100512864A-02
26/60
Historiques
Micrologic 6.0 P
0A
afficheur numrique
A 100
50
Historiques
langue
alarm @ 6 Ir
.7 .6 .5 .4
.8
x In 4
12 16 20 24 Ii
instantaneous
Isd
short time
3 2.5 2 1.5 Ig C B D A
x Ir E
5 6 8 10
on tg
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t o
delay
4 3
6 8 10 12 15 off 2 x In
test
setting
F J
(s)
G H
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t o
ground fault
Historiques
rapport des TP
DB401557
5
RISQUE DE CHOC LECTRIQUE, DEXPLOSION OU DARC LECTRIQUE b Le CCM peut se trouver proximit de tensions ou de sources d'nergie dangereuses. b Un quipement de protection individuelle doit tre utilis lors de l'utilisation du bouton-poussoir CCM ou du contrle des indicateurs d'tat. Se reporter NFPA 70E ou CSA Z462, ou aux codes nationaux appropris pour plus de dtails ce sujet. Le non-respect de ces instructions entranera la mort ou des blessures graves.
Appareils dbrochables
Dans ce cas, le module de communication "chssis" CCM Modbus est une interface entre l'appareil et le rseau de communication. Une procdure existe donc pour lui transfrer les paramtres ncessaires. Ces paramtres seront pralablement saisis comme dcrit prcdemment en fonction de l'unit de contrle (voir page 21 pour Micrologic A, page 23 pour Micrologic E, page 26 pour Micrologic P/H). Configuration du module de communication "chssis" CCM Modbus Le module de communication "chssis" CCM Modbus possde un bouton-poussoir et deux voyants rouge et vert en face avant qui sont utiliss lors de la mise en route. Une fois l'appareil paramtr comme dcrit prcdemment en fonction de l'unit de contrle, pressez le bouton-poussoir "synchronisation des adresses" figurant sur le module de communication "chssis" CCM Modbus. Au terme de cette opration, le module de communication "chssis" CCM Modbus aura automatiquement acquis : b les mmes vitesses de transmission et parits que le module de communication "appareil" BCM ULP Modbus ; b l'adresse affecte au module de communication "chssis" BCM ULP Modbus est l'adresse du module de communication "appareil" Modbus BCM ULP + 50 (@xx+50). Le module de communication "chssis" CCM Modbus activera automatiquement la mise en route en se connectant tous les autres modules "appareil" RS485 prsents sur le rseau de communication.
5100512864A-02
DANGER
Fault
shield
Disjoncteur
Com.
B
Breaker
synchronisation dadresse
DB401558
Address sync.
Network
Rseau
CT
CD
CE
Remplacement d'un appareil dbrochable quip d'un module de communication En cas de remplacement d'un appareil dbrochable contenant un module de communication "appareil" BCM ULP Modbus, la configuration et la mise en route sont effectues automatiquement par le module de communication "chssis" CCM Modbus qui transmet automatiquement les paramtres ncessaires au module de communication "appareil" BCM ULP Modbus avant de le reconnecter au rseau.
28/60
Mode d'exploitation Aucune alimentation ne parvient au module Module aliment mais pas initialis Module aliment, fonctionne correctement Module aliment, fonctionne correctement, dcodage des messages de rseau en cours Module aliment, fonctionne correctement, mais n'est pas en mesure de dcoder les messages de rseau Mode de configuration en cours (le bouton-poussoir "synchronisation des adresses" a t enfonc) Le module de communication "chssis" CCM Modbus est en cours d'envoi de sa configuration au module de communication "appareil" BCM ULP Modbus Le module de communication "chssis" CCM Modbus a envoy sa configuration avec succs au module de communication "appareil" BCM ULP Modbus
Tous les voyants sont teints Rouge constant Vert constant Vert avec de courtes interruptions Vert avec de courts passages au rouge Alternance de vert et de rouge
Fault
shield
Disjoncteur
Com.
B
Breaker
Address sync.
CT
CD
CE
DB401559
Rouge clignotant
Vert clignotant
5100512864A-02
29/60
Aide au dpannage
L'unit de contrle Micrologic n'affiche pas de paramtres de communication (adresse, vitesse de transmission, parit) Cause possible Action/solution
6
Contrlez lalimentation 24 V cc. Contrlez que la polarit positive (+) est sur E1 et que la polarit ngative () est sur E2. Remplacez le BCM existant par un BCM ULP neuf.
La version BCM est ancienne : la version du firmware doit tre > V3.0.0. Contrler le registre Modbus 577 ou la couleur du bornier de raccordement situ sur la partie fixe du BCM (gris et non pas vert). La version de l'unit de contrle Micrologic (P/H) est ancienne : la version du firmware doit tre > 2009AJ.
L'unit de contrle Micrologic P ou H n'affiche pas le paramtre de raccordement de la communication Modbus : 4 fils / 2 fils + ULP Cause possible Action/solution
Utilisez le logiciel Masterpact RSU (Remote Setting Utility) pour modifier le paramtre de raccordement de la communication Modbus.
La version du module d'affichage en face avant FDM121 est ancienne : la version du firmware doit tre > V2.0.2. La version du firmware est inscrite dans le menu Service du module d'affichage en face avant FDM121.
Le module d'affichage en face avant FDM121 clignote et/ou affiche des valeurs errones Cause possible Action/solution
Utilisez le logiciel Compact NSX RSU (Remote Setting Utility) pour mettre niveau le logiciel du module d'affichage en face avant FDM121.
Raccordements incorrects
Rponses incohrentes suite une requte Modbus (dpassement du temps imparti ou absence de rponse) Cause possible Action/solution
Contrlez le cblage du BCM ULP Avec la configuration A, contrlez que les bornes E5 et E6 ne sont pas raccordes au systme ULP. Avec la configuration B, contrlez que les bornes E5 et E6 ne sont pas raccordes au rseau Modbus. Utilisez 4 fils entre le BCM et le CCM ou remplacez le CCM existant par un CCM nouvelle gnration (CCM portant la marque Schneider Electric sur la face avant). Enlevez le module d'interface Modbus du systme ULP ou dbranchez le rseau Modbus du BCM ULP et raccordez le rseau Modbus au port Modbus du module d'interface Modbus (bornes D0, D1).
Configuration (paramtre 4W/2W+ULP) incompatible avec le cblage du BCM ULP 2 fils seulement sont utiliss entre le BCM ULP et un CCM d'ancienne gnration (CCM ne portant pas la marque Schneider Electric sur la face avant). Le module d'interface Modbus a t raccord au systme ULP, ce qui provoque l'inhibition du port Modbus du BCM ULP.
2 modules ULP de mme type sont connects sur le mme systme ULP. Par exemple, 2 disjoncteurs (1 Compact NSX et 1 Masterpact). 5100512864A-02
Les crans LCD de lunit de contrle Micrologic et/ou du FDM121 clignotent Cause possible Action/solution
Enlevez un des 2 modules ULP du mme type. Par exemple, dconnectez le Compact NSX du systme ULP. 30/60
Contents
1 2
Precautions before carrying out any work .. ........................................................................................................................... 39 Installation of the Modbus BCM ULP "device" communication module ............................................................................. 40 Fixed, manually operated Compact NS....................................................................................................................................... 40 Fixed, electrically operated Compact NS and Masterpact NT/NW.............................................................................................. 43 Withdrawable Compact NS and drawout Masterpact NT/NW..................................................................................................... 45 Installation of the Modbus CCM "chassis" communication module.................................................................................... 47 Withdrawable Compact NS and drawout Masterpact NT/NW..................................................................................................... 47
4 5 6
Communication settings with Micrologic A............................................................................................................................. 49 Communication settings with Micrologic E............................................................................................................................. 51 Communication settings with Micrologic P / H........................................................................................................................ 54
5100512864A-02
Safety instructions
Important information PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved.
Related documents
For additional instructions, refer to: b the appropriate Circuit Breaker technical publications b the COMBT32EN Masterpact Modbus User Manual b the TRV99101 ULP system user manual. You can download these technical publications and other technical information from our website at: www.schneider-electric.com.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in equipment damage. 5100512864A-02 32/60
Safety instructions
Before you begin
1
WARNING
LOSS OF CONTROL bT he designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to archieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop. b Separate or redundant control paths must be provided for critical control functions. b System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.(1) b Each implementation of a circuit breaker equipped with a BCM ULP must be individually and thoroughly tested for proper operation before being placed into service. Failure to follow these instructions can result in death, serious injury, or equipment damage.
(1) NEMA markets: For additional information refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control".
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. For NEMA market, see NFPA 70E. b This equipment must only be installed and serviced by qualified electrical personnel. b Turn off all power supplying this equipment before working on or inside equipment. b Always use a properly rated voltage sensing device to confirm power is off. b Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury.
DANGER
5100512864A-02
33/60
modb
us
CD
CE
Microl
ogic
7.0 A
MAX
s kA
2
Microl ogic 7.0 A
n= t= I tr= tsd= Isd= Ii= Ir= Ig= tg=
Ig= tg=
100
40 %
menu
alarm
MAX
s kA
8 12 time tr long 16 (s) 4 .8 .9 Ir 2 20 .7 .95 1 24 .6 .98 .5 @ 6 Ir .5 1 .4 x In .4 .3 time tsd . short .2 (s) 4 .3 Isd 4 56 .1 3 .2 0off 2.5 8 .1 2t I 2 on 10 delay 1.5 x Ir setting t 350 (ms)230 In 5 710 (A) 3 140 800 2 20 60 1 30 .5
earth leakage
ous
Ii 4 3
instantane
8 10 12 15 off x In
test
100
40 %
1
alarm
withdrawable device
menu
long
time
tr
Ir
.8 .9 .95 .6 .98 .5 1 .4 x In .7
short time
(s) 4
2 1
8 12 16 20 24 .5 @ 6 Ir Ii
ous instantane
tsd .4 .4 .3 .2 (s)
.3 .2 .1
.1
4 3
on
I t
delay
0off
8 10 12 15 off x In
test
fixed device
DB126749
350
800
Definition of the abbreviations BCM = Breaker Communication Module. ULP = Universal Logic Plug. CCM = Chassis Communication Module.
5100512864A-02
1 Micrologic control unit 2 Modbus BCM ULP "device" communication module 3 Modbus CCM "chassis" communication module (option)
General presentation of the COM option.
34/60
Communication architecture
2
Electrically operated, withdrawable device
2
OF SD SDE
CE CT CD
3 6 3
4 5
MX1 XF OF SDE PF CH
Modbus CCM module Additional Modbus CCM "chassis" communication module that must be installed on a DIN rail near the device and connected: b to the Modbus BCM ULP "device" communication module for which it stores the address if the device is disconnected b to the carriage switch contacts (CD, CT, CE) that transmit the position of the device in the chassis.
DB126750
1 2 3 4 5 6
Modbus BCM ULP "device" communication module Modbus CCM "chassis" communication module (option) OF, SDE ... micro-switches CE, CD and CT contacts MX1 and XF communicating voltage releases COM terminal block (E1 to E6)
Note: specific start-up procedure must be followed (see page 56). 5100512864A-02
35/60
Simplified diagram
Characteristics b Up to 31 fixed or 15 withdrawable (or drawout) devices. b Maximum length of bus y 1200 meters. b Maximum baud rate = 19200 bauds. Power supply for COM modules b COM modules: 24 V DC. b The external power supply module (AD) is recommended (see the order form for Masterpact NT/ NW and Compact NS devices). The control unit power supply must be un-earthed (isolated). Consumption of the COM modules and the Micrologic control units b Modbus BCM ULP "device" communication module: 40mA. b Modbus CCM "chassis" communication module: 55mA. b FDM121 display: 21 mA. b Modbus Communication Interface Module: 21 mA. b External power supply module (AD) up to 1 A (24VDC).
1 2 3 24 V c 5 6 7 8 9 10 11
OK OK OK Mode Mode Mode
12 13 14
Note: to configure the Micrologic control units, if there is no power supply module, they may be individually supplied via the test kit and the test connector on the front panel.
DB126723
1 2 3 4
PC consultation RSU / RCU 6 Ethernet Ethernet gateway (EGX100) 7 8 External power supply 9 module (AD) 10 5 Modbus network
Modbus CCM "chassis" communication module FDM121 display Breaker ULP cord COM terminal block Prefabricated wiring
11 Modbus BCM ULP "device" communication module 12 Modbus Communication Interface Module 13 ULP cable 14 Compact NSX cord
Simplified diagram of a communicating system implementing the Modbus protocol. 5100512864A-02 36/60
2
Modbus network wiring system supplied with MX1/XF option
E3 E1 E2
E4 E5
E6
1/2
v v
3/4/5/6/7
5100512864A-02
37/60
Withdrawable (or drawout) devices require two communication modules : b a Modbus BCM ULP "device" communication module installed as indicated on page 35 b a Modbus CCM "chassis" communication module, supplied separately in a specific package, that must be: v installed on a DIN rail v connected to the Modbus BCM ULP "device" communication module, see page 42. v connected to the carriage switch contacts (CE, CD, CT), see page 48. Once the above operations have been carried out, the Modbus CCM "chassis" communication module must be connected to the Modbus network. Modbus CCM "chassis" communication module components 1 24 V power supply terminals. 2 "Network" connector for connection to the Modbus network. 3 "Breaker" connector for connection to the Modbus BCM ULP "device" communication module. 4 24 V output terminals for the Modbus BCM ULP "device" communication module power supply. 5 screw terminals for connection to carriage switch contacts (CE, CT, CD). 6 address-synchronisation button. 7 module status-conditions LEDs (see the Operating modes section on page 57).
+ +
CCM
s Addres sync.
Disjoncteur
3
DB126729
CT
CD
CE
Breaker
CE
Steps for installation of the Modbus CCM "chassis" communication module on withdrawable Compact NS and drawout Masterpact NT/NW. 1
7 6
Fault
shield
Disjoncteur
Com.
Network
Rseau
Address sync.
CT
CD
CE
Breaker
5 Components.
4 38/60
5100512864A-02
DB126731
3
ON push
Fixed device Before carrying out any work, always de-energize the device as indicated here. Withdrawable devices should be moved to disconnected position.
I
O
OFF push
arged disch
O OFF
push
push
ON
OFF
disch
arged
O OFF
I
OFF push
ON push
arged disch
O OFF
E47085A
2
E47086A
O OFF
discharged
Withdrawable device
O OFF
push
ON
push
disch
arged
O OFF
push
push
ON
OFF
d arge disch
O OFF
I
3
ON
push
push
O OFF
push
OOFF
push
I ON
disch
arge
disch
arged
O OFF
E47084A
2
E47083A
O OFF
discharged
E47082A
O OFF
5100512864A-02
39/60
Installation and wiring of the COM option (Modbus BCM ULP module)
Module installation Supplied with the device, the module is mounted behind the control unit and is wired to the micro-switches (OF, SD, SDE). On the top of the module is a plug-in COM connector for direct connection to the Modbus network. For the connection of the Modbus BCM ULP device, see page 42.
E3 E1 E2 E4 E5 E6
3
E4 E2 E3 E5 E6
Modbus network
E1
Modbus network
100
40 %
DB126725
Installation of the Modbus BCM ULP "device" communication module on a fixed, manually operated Compact NS. 5100512864A-02 40/60
Installation and wiring of the COM option (Modbus BCM ULP module)
Precaution: wire routing Run the wires in such a way as to avoid all risk of pinching or crushing the cable or the wires when the front cover is fitted (see illustration).
E1 E2E3E 4E5 E6
E1 E2
E3 E4
E5 E6
1
E1 E2E3E 4E5 E6
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Replace circuit breaker accessory cover before energizing circuit breaker to prevent access to live terminals. Failure to follow these instructions will result in death or serious injury.
DANGER
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
4
E1 E2 E5 E3 E4 E6
Blue
E1 E2E3E
4E5
E6
E1 E2E3E
4E5
E6
6
DB127871
Wiring of the COM option (Modbus BCM ULP Module) with or without ULP module (FDM121...)
Micrologic P/H
Modbus Com Address 47 Baud-rate 19.2 k 4W, 2W+ULP
A
+ EGX100 Rx- Rx+ Tx- Tx+ + EGX100 Rx- Rx+ Tx- Tx+
w
Micrologic E
4wires
Micrologic P/H
Modbus Com Address Baud-rate 19.2 k 4W, 2W+ULP
B
w
Micrologic E
Breaker ULP cord
2w+ULP
4 E5 2 E3 E E1 E
E6
E3 E1 E2 E4 E5 E6
DB126744
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated. 5100512864A-02 42/60
- +
+ FDM121
version > V2.0.2
red black
white blue
BCM ULP
BCM ULP
BCM ULP
Modbus network
customer terminal block prefabricated connector wires to MX1 / XF plug-in COM connector
E3 E1 E2 E4 E5 E6
Modbus network
MX1 / XF
MN MX1 SDE1 SDE1 /MX2 /M2C UC4 /RES XF
PF
MCH
COM
UC1
UC2
UC3
E3 E1 E2
E4 E5
E6
I
push
ON
100
%
ed harg disc
40 %
O OFF
DB126726
BCM ULP connected to the micro-switches Modbus BCM ULP "device" communication module installation on a fixed, electrically operated Compact NS or Masterpact NT/NW.
5100512864A-02
43/60
Wiring of the COM option (Modbus BCM ULP module) with or without ULP module (FDM121...)
Micrologic P/H
Modbus Com Address 47 Baud-rate 19.2 k 4W, 2W+ULP
A
w
Micrologic E
+ FDM121
version > V2.0.2
4wires
Micrologic P/H
Modbus Com Address Baud-rate 19.2 k 4W, 2W+ULP
B
w
Micrologic E
Breaker ULP cord red black white blue
2w+ULP
DB126745
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated. 5100512864A-02 44/60
- +
- +
Wiring of the COM option (Modbus BCM ULP and CCM modules)
Module installation The Modbus BCM ULP "device" communication module is installed as previously described for the fixed devices. It is supplied already installed and connected to the micro-switches and the communicating voltage releases. Connection to the customer terminal block The module is equipped with a plug-in COM connector, wired to the prefabricated connector that clips to the top part of the device. When the device is racked in, the prefabricated connector automatically establishes contact with the customer terminal block (spring terminals). The customer terminal block is used for connection to the Modbus network via the Modbus CCM "chassis" communication module. Connection of auxiliaries to the module Same as fixed, electrically operated Compact NS and Masterpact NT/NW. Modbus connector uses the following colour code:
Colour Red Black Brown Yellow White Blue E1 E2 E3 E4 E5 E6 Europe 24 V 0V A B A' B' USA 24 V 0V OutOut+ InIn+ D0 D1
DB126727
3
CCM "Chassis"
customer terminal block prefabricated connector wires to MX1 / XF plug-in COM connector
E3 E1 E2 E4 E5 E6
E3 E1 E2 E4 E5 E6
100% 40%
MX1 / XF
D0 D1
Example of Modbus BCM ULP "device" communication module installation on a drawout Masterpact NT. 5100512864A-02 45/60
Wiring of the COM option (Modbus BCM ULP and CCM modules) with or without ULP module (FDM121...)
+ -
Micrologic P/H
Modbus Com Address 47 Baud-rate 19.2 k 4W, 2W+ULP
A
w
Micrologic E
The B configuration is only possible with CCM marked Schneider Electric on the front face.
4wires
Micrologic P/H
Modbus Com Address Baud-rate 19.2 k 4W, 2W+ULP
Network
Network
Micrologic E
w
A A
B B
A A
B CCM B + -
A A
B B
A A
B B
Network
+ CCM + -
+ -
+ FDM121
version > V2.0.2
+ CCM + -
A A
B B
A A
B B
Breaker
Breaker
2w+ULP
DB126746
Breaker
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated. 5100512864A-02 46/60
3
u ea s A B ld ie B A B A R A N et w or k sh
s Addres sync.
Module installation Mount the Modbus CCM "chassis" communication module on a symmetrical DIN rail near the chassis in a position where the front can be easily accessed for connections and settings. If mounting is on a vertical rail, install a stop to secure the module. DIN rail must be ordered separately.
YL
CI
is
Com.
jo
nc
te
ur
Fault
re
ak
er
CE CD CT
33110
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Use of CCM pushbutton and viewing of indicators requires 24 V DC power to CCM. The CCM must be located so personnel are not exposed to hazardous voltages or energy when operating the CCM pushbutton or viewing its status indicators. Failure to follow these instructions will result in death or serious injury.
DB126728
DANGER
5100512662
P 99-44
PP-YYYY-WWW-D-T
XXXXXXXXX
CCM
Address sync.
Disjoncteur
identification label
Package contents.
CT
CD
CE
Breaker
Made in France
90 3.54
45 1.77
DB126730
53 2.08 Dimensions.
58 2.28
DB126732
CCM
modbu Fault
Addre sync.
ss
Disjoncteur
CT
CD
CE
Breaker
Com.
A A
B B
A A
B B
CD carriage contacts
CT
Breaker
CCM
CD
CE
911 914
314
CT
DB126733
CD
CE
5100512864A-02
48/60
Preliminary remarks
The BCM ULP communication parameters must be set using the Micrologic control unit or the Masterpact Remote Setting Utility (RSU) software. The BCM ULP communication parameters are: address, baud rate, parity and Modbus connection. To start Modbus communication, the modules must have been correctly installed and energized. The Micrologic control units must also be energized in order to carry out the following configuration procedures.
Micrologic 6.0 A
MAX s kA
digital display
100 %
navigation buttons
40 %
menu
long time
Simultaneously press the and the buttons for three seconds. A series of four screens are displayed for configuration of the Modbus communication. Screen 1 Address The default Modbus address for the device is 47. The screen displays AdXX when the existing address for the communication module is XX. Select an address from 1 to 47 (unique for the given device) by pressing the button. Briefly press the button to increment the address by one, where the address displayed after 47 is 1. Once the address has been selected, press the button for three seconds, then release it to go on to the next screen.
.7 .6 .5 .4
.8
x In
alarm
short time
tsd
(s)
on tg
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
Ii
instantaneous
4 3
off
6 8 10 12 15 off 2 x In
test
Ad47
change to XX
47 1 2 3 : : : 46
(by default)
Ig D C B A
F G H J
(s)
on
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
off
ground fault
DB126734
Micrologic A.
5100512864A-02
49/60
4
19200 19200 9600
(by default)
Screen 2 Baud rate The default rate is 19200 bauds. The screen displays XXXX which may be one of three values, 4800, 9600 or 19200. Select a rate that is the same for all devices using the button. Briefly press the button to go on to the next value in the loop. Once the rate has been selected, press the button for three seconds, then release it to go on to the next screen. Screen 3 Parity The default parity is even. The screen displays X which may be one of two values, E (even) or n (none). Select a value that is the same for all devices using the button. Briefly press the button to go on to the next value in the loop. Once the parity has been selected, press the button for three seconds, then release it to go on to the next screen. Modbus connection The default value of the Modbus connection communication parameter is 4 wires. The Modbus connection communication parameter (4 wires, 2 wires + ULP) cannot be set using MicrologicA control unit. In order to set this parameter, use the Masterpact Remote Setting Utility (RSU) software.
19200
DB126735
4800
Screen 2 for baud rate.
pE
E n
(by default)
DB126736
5100512864A-02
50/60
Activate tree navigation mode. Simultaneously press the and the buttons for three seconds. A series of four screens are displayed for configuration of the Modbus communication. Screen 1 Address The default Modbus address for the device is 47. The screen displays AdXX when the existing address for the communication module is XX. A closed padlock icon displayed indicates that the value is locked. Press on the button to open the padlock and display the first digit (e.g. 4) flashing, ready to be modified. Briefly press on the button to increment in a loop the value up to the new setting. Briefly press on the button to validate this value and display the second digit (e.g. 7) flashing, ready to be modified. Briefly press on the button to increment in a loop the value up to the new setting. Briefly press on the button to validate the new Modbus address (the two choosen digits) whose display becomes permanent. The padlock is still open. Briefly press again on the button to padlock this value and display screen 2.
DB126753
Micrologic 6.0 E
press simultaneously
k
(see pages 47)
5100512864A-02
51/60
4
k k
Screen 2 Baud rate The default rate is 19200 bauds. The screen displays XXXX which may be one of the three values 4800, 9600 or 19200. A closed padlock icon displayed indicates that the value is locked. Press on the button to open the padlock and display the value (e.g. 19.2) flashing, ready to be modified. Select a rate that is the same for all devices using the button. Briefly press the button to go on to the next value of the loop. Once the rate has been selected press the button to validate this value whose display becomes permanent. The padlock is still open. Briefly press again on the button to padlock this value and display screen 3. Screen 3 Parity The default parity is E (Even). The screen may display n (none) if a previous setting is existing. A closed padlock icon displayed indicates that the value is locked. Press on the button to open the padlock and display the value (e.g. E) flashing, ready to be modified. Change the existing parity to the other value by pressing the button. Press the button to validate this value whose display becomes permanent. The padlock is still open. Briefly press again on the button to padlock this value.
DB126756
Micrologic 6.0 E
menu
Micrologic 6.0 E
menu
DB126757
5100512864A-02
52/60
Screen 4 Modbus connection (4W, 2W+ULP) The default value of the Modbus connection communication parameter is 4 wires. b If "4W" communication parameter is selected (default value), 4 wires must be connected between the BCM ULP (E3, E4, E5, E6 terminals) and the CCM (A, B, A, B terminals). The front display module FDM121 cannot be connected. Connection to Modbus RS 485 4-wire network is possible. b If "ULP" communication parameter is selected, 2 wires must be connected between the BCM ULP (E3, E4 terminals) and the CCM (A, B terminals). The front display module FDM121 can be connected. Connection to Modbus RS 485 4-wire network is not possible.
Micrologic 6.0 E
w
menu
DB127872
5100512864A-02
53/60
Press the button and in the displayed screen: b select the Com. setup menu using the and navigation keys, then confirm b the selection by pressing the key b then select the Com parameter menu in the same manner. Address, baud rate, parity In the Com parameter menu, set the Address, Baud rate and Parity values as indicated on the previous pages. The default and selectable values for each parameter are the same as indicated previously. See the information on Screen 1, Screen 2 and Screen 3. Press the key to confirm the selection for each parameter. After confirming the Parity parameter, press the key. A message is displayed asking you if you want to save the settings. Select Yes and confirm by pressing the key. The three parameters are saved.
5100512864A-02
54/60
Micrologic 6.0 P
Event history
0A A B C
digital display
4W, 2W+ULP
100
4wires
50
Event history Contacts M2C/M6C Micrologic setup Metering setup Com. setup
.7 .6 .5 .4
.8
x In
alarm
short time
tsd
(s)
on tg
.4 .4 .3 .2 .3 .1 .2 .1 2 0
I t
delay
Ii
instantaneous
4 3
off
6 8 10 12 15 off 2 x In
test
Ig D C B A
F G H J
(s)
on
.3 .2 .1
.4 .4 .3
2
I t
.2 .1 0 off
ground fault
Event history
VT ratio
DB126737
5
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH b The CCM may be in proximity to hazardous voltages or energy sources. b Appropriate Personal Protective Equipment must be used when operating the CCM pushbutton or monitoring the status indicators. Refer to NFPA 70E or CSA Z462 or appropriate national codes for additional detail. Failure to follow these instructions will result in death or serious injury.
DANGER
Fault
shield
Disjoncteur
Com.
B
Breaker
Address synchronisation
DB126738
Address sync.
Network
Rseau
CT
CD
CE
Replacement of a withdrawable device equipped with a communication module If a withdrawable device equipped with a Modbus BCM ULP "device" communication module is replaced, configuration and start-up are automatically carried out by the Modbus CCM "chassis" communication module which sends the necessary parameters to the Modbus BCM ULP "device" communication module and then connects it to the communication network.
56/60
Operating mode Module not supplied with power Module supplied with power, but not initialised Module supplied with power, operation OK Module supplied with power, operation OK, currently decoding network messages Module supplied with power, operation OK, currently unable to decode network messages Configuration in progress (the Address synchronisation button was pushed) Modbus CCM "chassis" communication module currently sending configuration to the Modbus BCM ULP "device" communication module Modbus CCM "chassis" communication module successfully sent configuration to the Modbus BCM ULP "device" communication module
All LEDs off Steady red Steady green Green with short interruptions Green interrupted by short red flashes Alternating green and red Flashing red
Fault
shield
Disjoncteur
Com.
B
Breaker
Address sync.
CT
CD
CE
DB400260
Flashing green
5100512864A-02
57/60
Troubleshooting assistance
6
Check the 24 V DC power supply. Check the + is on E1, the on E2. Replace the existing BCM with a new BCM ULP. Use the Masterpact Remote Settings Utility (RSU) software in order to modify the Modbus connection parameter.
Micrologic control unit does not display the communication parameters (address, baud rate, parity) Possible cause Action/remedy
The BCM is an old version: firmware version must be > V3.0.0 Check the Modbus register 577 or check the color of the terminal block located on the fixed part of the BCM (should be grey instead of green). Micrologic control unit (P/H) is an old version: firmware version must be > 2009AJ.
Micrologic control unit P or H does not display the Modbus connection parameter : 4wires / 2w+ULP Possible cause Action/remedy
The front display module FDM121 is an old version: firmware version must be > V2.0.2. Firmware version is readable on the Service menu of the front display module FDM121.
The front display module FDM121 is flashing and/or display wrong values Possible cause Action/remedy
Use the Compact NSX Remote Settings Utility (RSU) software in order to upgrade the firmware of the front display module FDM121.
Wrong connections Configuration (4Wire/2wire+ULP parameter) not consistent with the wiring of the BCM ULP Only 2 wires are used between the BCM and an old version of CCM (CCM not marked Schneider Electric on the front face). The Modbus communication interface module has been connected to the ULP system and therefore the Modbus port of the BCM ULP is disabled.
Check the wiring of the BCM ULP. Within configuration A, make sure the terminal blocks E5 and E6 are not connected to the ULP system. Within configuration B, make sure the terminal blocks E5 and E6 are not connected to the Modbus network. Use 4 wires between the BCM and the CCM or replace the existing CCM with a new version of CCM (CCM marked Schneider Electric on the front face). Either disconnect the Modbus communication interface module from the ULP system, or disconnect the Modbus network from the BCM ULP and connect the Modbus network to the Modbus port of the Modbus communication interface module (terminals D0,D1).
2 ULP modules of the same type are connected on the same ULP system. For example, 2 circuit breakers (1 Compact NSX and 1 Masterpact) 5100512864A-02
Micrologic control unit and/or FDM121 LCDs are flashing Possible cause
Action/remedy
Remove one of the duplicated ULP module. For example, disconnect the Compact NSX from the ULP system. 58/60
Notes
5100512864A-02
59/60
En raison de l'volution des normes et du matriel, les caractristiques indiques par le texte et les images de ce document ne nous engagent qu'aprs confirmation par nos services. As standards and equipment change from time to time, please ask for confirmation of the information given in this document.
Ce document a t imprim sur du papier cologique. This document has been printed on ecological paper.