Model 12300 Digital Level Transmitter / Controller

Instruction No EU 3500 E 04/2000

With HART Communication Protocol

Table of Contents
General ......................................................................................3 Spare Parts................................................................................3 After Market Support................................................................3 Training......................................................................................3 5.3.1 Direct Reading on the Liquid Specific Gravity Meter [SGMETER].....................15 5.3.2 To Set up Function Parameters...........................16 5.3.2.1 5.3.2.2 5.3.2.3 5.3.2.4 5.3.2.5 Calibrate the Specific Gravity Meter ...........16 Calibration Specific Gravity [SG CAL] .........16 Service Specific Gravity [SG SER] .............16 Output Current Damping [DAMPING]...........16 Reduced Range and /or Zero Shift [SPAN > <], [ZERO <>] .......................16 5.3.2.6 Error Code on Zero and Span Set ...............17 5.3.3 Calibration (for a Level Instrument Service) ......17 5.3.3.1 Principle of Calibration...........................17 5.3.3.2 Conditions to Dry Calibration in Workshop (Simulation by Weights) .........................18 5.3.3.3 Conditions for Calibration in the field with a Liquid ...............................................18 5.3.3.4 Calibration..........................................18 5.3.4 Calibration of an Instrument for Liquid Interface Service ...................................................................19 5.3.4.1 Principle of Calibration...........................19 5.3.4.2 General Information on Interface Service Displacer ...........................................19 5.3.4.2.1 Wet Calibration..........................................20 5.3.4.2.2. Dry Calibration ..........................................21

1. DESCRIPTION - OPERATION...............................4
1.1 PRINCIPLE OF OPERATION.............................................4 1.2 SIGNAL PROCESSING .....................................................4

2. PROTECTION STANDARDS ................................4 3. INSTALLATION .....................................................6


3.1 STORAGE AND CONDITION AT DELIVERY....................6 3.2 MOUNTING ON SITE .........................................................7 3.2.1 3.2.2 a) b) External Mounting (Chamber Type Model)...........7 Internal mounting ...................................................7 Type 12303 Top Flange Mounted Transmitter.......7 Type 12304 Side Flange Mounted Transmitter......8 Guide Brackets for Type 12304 ..............................8 Stilling Well for Type 12303 ....................................9 Instrument Case Mounting .....................................9

4. CASE DESCRIPTION............................................9
4.1 ELECTRONIC COMPARTMENT .......................................9 4.2 MECHANISM COMPARTMENT.........................................9 4.3 CONNECTION COMPARTMENT.......................................9 4.4 ELECTRICAL CIRCUIT .....................................................9 4.4.1 4.4.2 4.4.3 4.4.4 4.4.5 Wiring and Connections ........................................9 Supply - Output Signal .........................................10 Load Resistance ...................................................10 Electric Connection ..............................................10 Milliammeter Connection .....................................11

6. MAINTENANCE...................................................22
6.1 REMOVING THE DLT CASE FROM THE TORQUE TUBE ...22 6.2 HOW TO INSTALL A DLT ON A TORQUE TUBE...........23 6.2.1 6.2.2 6.2.3 6.2.4 6.2.5 On a 12200/300 Series Torque Tube....................23 12120/12800 Series Torque Tube.........................23 Workshop Calibration of Coupling .....................23 Coupling to the Torque Tube on Site ..................25 Setting Adjusting Screws ...................................25

5. OPERATING THE INSTRUMENT .......................11


5.1 GENERAL PRINCIPLES ..................................................11 5.1.1 5.1.2. 5.1.3. 5.1.4. The Liquid Crystal Display...................................11 Pushbuttons ..........................................................11 Working Modes .....................................................11 Pushbuttons Menu Description and How to Use Them ? ..............................................11 5.1.4.1 NORMAL Mode Menu ............................12 5.1.4.2 INFORMATION Menu..............................12 5.1.4.3 MANUAL Mode Menu .............................13 5.1.4.4 CONFIGURATION Menu...........................13 5.1.4.4.1 To change from level service to interface service.......................................................13 5.1.4.5 CALIBRATION Menu...............................13 5.1.4.5.1 To change the Service Specific Gravity......14 5.1.4.5.2 Calibration ................................................14 5.1.4.5.3 Recalibration of the internal ammeter .......14 5.1.4.5.4 To force the current to a required value.....14 5.1.4.5.5 Reposition the Hall effect sensor...............14 5.1.4.6 DIAGNOSTIC Menu ...............................15 5.1.4.7 FAILSAFE Mode Menu ...........................15 5.1.4.8 SETVAL menu ......................................15 5.2 INITIAL CALIBRATION OF AN INSTRUMENT ON LEVEL SERVICE ..........................................................................15 5.3 CALIBRATION PROCEDURES FOR SPECIFIC PARAMETERS AND APPLICATIONS.............................15

6.3 REMOVING A TORQUE TUBE WITH ASSEMBLED DLT CASE ........................................................................26 6.4 INSTALLING A TORQUE TUBE WITH ASSEMBLED DLT CASE ........................................................................27 6.5 TO REVERSE INSTRUMENT CASE MOUNTING RELATING TO DISPLACER POSITION (LEFT OR RIGHT) ............................................................27 6.6 REPLACING THE AMPLIFIER AND/OR THE SENSOR.28 6.6.1 Removing ..............................................................28 6.6.2 Installing ................................................................28 6.7 REPLACING THE MECHANISM SUB-ASSEMBLY (50) 28 6.7.1 Removing ..............................................................28 6.7.2 Installing ................................................................31

7. TROUBLE SHOOTING........................................31
7.1 No Signal .........................................................................31 7.2 No Display but Signal Exists .........................................31 7.3 Signal is Steady, No Change When Level Varies....................31 7.4 if current output is not the same that current displayed ....................................................31 7.5 No HART communication ..............................................31

Section Views & Parts Reference .....................29, 30 APPENDIX A, B, C, D, E, F

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Use of DANGER, WARNING, CAUTION, and NOTE. These instructions contain DANGER, WARNING, CAUTION, and NOTE where necessary to alert you to safety related or other important information. DANGER - Hazards which result in severe personal injury or death. WARNING - Hazards which could result in personal injury. CAUTION - Hazards which could result in equipment or property damage. NOTE - Alerts you to pertinent facts and conditions. Although DANGER and WARNING hazards are related to personal injury, and the CAUTION hazards involve equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process system performance which may lead to personal injury or death. Therefore, comply fully with all DANGER, WARNING, and CAUTION notices.

IMPORTANT: SAFETY WARNING


Please read these instructions carefully BEFORE this instrument is installed or maintained. Products certified for use in explosionproof (flameproof) or intrinsically safe installations MUST a) Be installed in accordance with local and national codes for hazardous area installations. b) Only be used in situations which comply with the certification conditions stated in this handbook. c) Only be maintained by qualified personnel with adequate training on hazardous area instrumentation. Non-compliance with the rules and cautionary notes of this instruction may cause malfunction of the device or serious damage to it. In addition, such negligence may expose area personnel to severe hazards. Not intended for use in life support systems. Items sold by Masoneilan Dresser are warranted to be free from defects in materials and workmanship for a period of one year from the date of manufacture, provided said items are used according to Masoneilan Dressers recommended usages. Masoneilan Dresser reserves the right to discontinue manufacture of any product or change product materials, design, or specifications without notice.

General This manual provides installation, operation and maintenance instructions for the Masoneilan Model 12300 Digital Level Transmitter (DLT) with HART Communication protocol. It also includes a complete parts reference and a list of recommended spare parts. Spare Parts When performing maintenance, use Masoneilan spare parts only. Parts can be obtained through your local Masoneilan Representative or the Spare Parts Department. When ordering parts, always include the Model and Serial Number of the unit being repaired.

After Market Support Masoneilan has a highly skilled After Sales Department available for start-up, maintenance, and repair of our valves and instruments. Contact the nearest Masoneilan Sales Office or Representative or After Sales Department. Training Regularly scheduled classes are conducted at the Masoneilan plant for training customer service and instrumentation personnel in the operation, maintenance, and application of control valves and instruments. Arrangements for these services can be made through your local Masoneilan Representative or the Training Department of Masoneilan.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

1. description-operation
The 12300 type Digital Level Transmitter/controller is a high performance, easy-to-set instrument based on a modular design that permits quick, low-cost upgrades as new features are developed and as your needs change. 1.1 Principle of Operation The Masoneilan 12300 series instrument is a 2-wire, loop powered, digital displacement level transmitter/controller with HART Communication that uses field proven buoyancy and torque tube principles. A change in liquid level varies the apparent weight of the displacer (130), which increases or decreases load on the torque tube (136) by an amount directly proportional to the change in liquid level. The resulting rotation of the torque rod (138) modifies the magnetic field of a frictionless, non-contacting, Hall effect sensor (141). The signal generated by the sensor varies current in the loop in proportion to the level in the vessel. 1.2 Signal Processing The analog signal is converted into an error-free digital signal that can be processed by the on-board microcontroller. After the signal has been processed, the digital result is converted to a 4-20 mA analog output signal *. If the 12300 is configurated as transmitter, this 4-20 mA analog output signal is the level measure. If the 12300 is configurated as controller, this 4-20 mA analog output signal is not the level measure but the position setpoint sent to the valve, so that the valve controls to achieve the required level setpoint. The 12300 electronic turns then the signal of the Hall effect sensor into a different type of signal ( : valve position setpoint) thanks to the control parameters stored. Important: The controller option of the 12300 is available only if the customer has ordered a 12300 controller (see fig.2 - numbering system) he will then be able to configure the 12300 wether as transmitter or as controller. If the customer has ordered a 12300 transmitter (see fig.2 - numbering system) he will then only be able to configure the 12300 as transmitter. The relevant controller information are discribed in annex F and in the HDLT communicator (joined).

The instrument is powered through the 2-wire series loop. The instrument can be retrofitted to old style electronic or pneumatic heads to upgrade an instrument already in service.

To the amplifier

* HART digital signal is superimposed to the 4-20 mA analog signal.

PARTS REFERENCES
130 131 135 136 Displacer Displacer chamber Torque arm Torque tube 137 138 140 141 Torque tube housing Torque rod Magnets Hall effect sensor

Figure 1 Diagram of Principle

2. protection standards
Installation in a hazardous atmosphere must be performed in accordance with the requirements specified in the applicable standard for protection against explosion. a) Transmitters Designed to be Installed in an Intrinsically Safe Circuit, according to European Standards EN 50014 and EN 50020 (CENELEC): EEx ia IIC T6 ( 40 C Ambient temperature 50 C) EEx ia IIC T5 ( 40 C Ambient temperature 60 C) EEx ia IIC T4 ( 40 C Ambient temperature 80 C) The main feature of this protection system is that no spark nor any thermal effect produced under the tests conditions required by the standard is capable of causing ignition of a given explosive atmosphere.

WARNING : Improper replacement or substitution of electronic components or of certain parts whose characteristics do not meet requirements of the applicable standards for explosion protection may void this protection.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

The complete circuit is defined in the approval document issued by a recognized certification agency : Conformity Certificate : Sira No Ex 98E2107. b) Transmitters with Flameproof Housing, according to European Standards EN 50014 and EN 50018 (CENELEC) : EEx d IIC T6 ( 40 C Ambient temperature 75C) EEx d IIC T5 ( 40 C Ambient temperature 80C) WARNING : When servicing the instrument in the field, DO NOT REMOVE THE COVER OR THE CONNECTION COMPARTMENT WHILE THE INSTRUMENT IS ENERGIZED. FOLLOW THE SAFETY INSTRUCTIONS LISTED ON THE FRONT PLATE (80). Following a failure, a spark caused by an internal part of the transmitter may ignite the explosive mixture enclosed in the case. The case, however, can resist the pressure developed by the internal explosion and prevent it from spreading to the outside explosive atmosphere. Conformity Certificate : INERIS No 98.D 5018 X. c) Factory Mutual approved as : Explosionproof Class I, Division 1, Groups B, C, D. Dust-ignitionproof Class II, III, Division 1, Groups E, F, G. T5 @ 80C - T6 @ 75 C. Intrinsically Safe per Entity Requirements Class I, II, III, Division 1, Groups A, B, C, D, E, F, G.

Nonincendive Class I, Division 2, Groups A, B, C, D. suitable for Class II, III, Division 2, Groups F, G. T4 @ 80 C. Installation must be in accordance with the document ES628 B shown below, and manufacturer's instructions. d) CSA approved as : Explosionproof Class I, Division 1, Groups C, D. Dust-ignitionproof Class II, III, Division 1, Groups E, F, G. T5 @ 80C - T6 @ 75 C. Intrinsically Safe per Entity Requirements Class I, Div. 1, Groups A, B, C, D ; Class II, Div. 1, Groups E, F, G. Class III. Nonincendive suitable for Class I, Div. 2, Groups A, B, C, D ; Class II, Div. 2, Groups E, F, G ; Class III,. T4 @ 80 C. Installation must be in accordance with the document ES628 B shown below, and manufacturer's instructions. e) Enclosure The case and the connection /mechanism compartment of the 12300 Transmitter feature : Protection against strong water jets, sea waves, and immersion corresponding to classification IP 66 and IP 67 according to International Standard CEI 529. Protection against climatic attacks and environmental extremes as specified in American Standard NEMA 4X, 6P. CSA enclosure type 4X, 6P.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

ES628 B: MODEL 12300 SERIES LIQUID LEVEL TRANSMITTERS FACTORY MUTUAL & CSA APPROVED INTRINSICALLY SAFE INSTALLATION CONTROL DRAWING
NOTES: 1. THE ELECTRICAL CIRCUIT IN THE HAZARDOUS AREA MUST BE CAPABLE OF WITHSTANDING AN A.C. TEST VOLTAGE OF 500 VOLTS R.M.S. TO EARTH OR FRAME OF THE APPARATUS FOR 1 MINUTE. 2. CABLE CAPACITANCE AND INDUCTANCE PLUS THE I.S. APPARATUS UNPROTECTED CAPACITANCE (Ci) AND INDUCTANCE (Li) PLUS ANY HART COMMUNICATIONS DEVICE CAPACITANCE (Ci) AND INDUCTANCE (Li) MUST NOT EXCEED THE ALLOWED CAPACITANCE (Ca) AND INDUCTANCE (La) INDICATED ON THE ASSOCIATED APPARATUS. 3. BARRIER IN B1 LOCATION TYPE IS: - ACTIVE BARRIER (ISOLATING IS INTERFACE UNIT) or - ANY POSITIVE POLARITY SHUNT ZENER DIODE. BARRIER IN B2 LOCATION TYPE IS: - ACTIVE BARRIER (ISOLATING IS INTERFACE UNIT) or - ANY POSITIVE POLARITY SHUNT ZENER DIODE. BOTH SAFETY BARRIER MUST BE APPROVED BY FMRC AND CERTIFIED BY CSA FOR GROUPS A, B, C, D, E, F, AND G WHOSE OUTPUT PARAMETERS ARE: Voc or Vt 30 V, but not less than 19 V. Isc or It 180 mA Ca Ci + C cable + C com. device La Li + L cable + L com. device Po 900 Mw (applies to FM only) FIED) LOCATIONS) AND THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 OR CANADIAN ELECTRICAL CODE PART 1. INSTALLATION MUST BE IN ACCORDANCE WITH MANUFACTURERS GUIDELINES. DIVISION 2 INSTALLATIONS MUST BE INSTALLED PER THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70 OR CANADIAN ELECTRICAL CODE DIVISION 2 WIRING METHODS. 5. TEMP. CODE T4 AT 80C. MAXIMUM AMBIENT TEMPERATURE. 6. DUST-TIGHT CONDUIT SEAL MUST BE USED WHEN INSTALLED IN CLASS II, AND III ENVIRONMENTS. 7. THE HART COMMUNICATION DEVICE MUST BE CERTIFIED INTRINSICALLY SAFE BY FMRC. HART COMMUNICATOR MODEL 275 MANUFACTURED BY FISHER-ROSEMOUNT OR EQUIVALENT WITH THE FOLLOWING ENTITY PARAMETERS : Voc=1.7Vdc, Isc =32mA, Vmax=30Vdc, Imax=300mA, Ci=0.07F, Li=0 T4. The model 275 Hand Held Communicator is not CSA approved with entity parameteres and must not be connected on the hazardous side of the barrier in a Canadian IS installation.

8. THE HART COMMUNICATION DEVICE MUST ONLY BE CONNECTED IN PARALLEL, IT MUST NOT BE CONNECTED IN SERIES. Isc + Isc (HART COMMUNICATION DEVICE) MUST NOT EXCEED 180mA. 9. THE OPTIONAL DEVICE MAY BE AN I/P OR A VALVE POSITIONNER. THE DEVICE MUST BE FM AND CSA APPROVED FOR THE APPROPRIATE AREA CLASSIFICATION. SEE ALSO NOTE 2. IF THE OPTIONAL DEVICE IS NOT INCLUDED, THEN ALL WIRING COMING FROM BARRIER B1 AND BARRIER B2 ARE SUPPRESSED.

4. THE INSTALLATION INCLUDING THE BARRIER EARTHING REQUIREMENTS MUST COMPLY WITH THE INSTALLATION REQUIREMENTS OF THE COUNTRY OF USE, I.E., ANSI/ISA RP12.6 (INSTALLATION OF INSTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS (CLASSI-

3. installation
3.1 STORAGE AND CONDITION AT DELIVERY
Level instruments have been carefully packed in our premises to prevent them from damage during handling and transportation. Units must be stored in an area where temperatures are between 45 C ( 49 F) and + 93 C (+ 200 F). Units are factory dry calibrated (simulation by weight) to the service specific gravity specified by the customer. When service specific gravity has not been specified, units are factory dry calibrated to a specific gravity of 1. Recalibration is recommended when the actual specific gravity differs from calibration specific gravity. Recalibration is needed when verification of instrument performance is made with liquid in the displacer chamber.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Figure 2 Numbering System

3.2 MOUNTING ON SITE


Unpack the unit carefully and record the serial number for future reference. Remove the shipping stud that secures the displacer in the chamber. Whenever possible, locate the transmitter at some easily accessible, well-lighted place on the vessel. The location should be such that the ambient temperature at the transmitter case is within the range of 40 C to +80 C.

During the level mounting, the displacer has to be unlocked by unscrewing the M6 stern at the drain. 3.2.2 INTERNAL MOUNTING An internally mounted transmitter has no displacer chamber and the mechanism chamber bolts directly to the vessel nozzle flange. a) Type 12303 Top Flange Mounted Transmitter (Figure 4) There are two mounting possibilities : 1. If the overhead space necessary for mounting the instrument is sufficient, attach the displacer to the torque tube before bolting the chamber flange to the nozzle flange on the vessel. 2. If the overhead space is insufficient, install a detachable hanger extension. Before attaching the extension, however, lower the displacer partway into the tank. After the extension has been fastened and pinned to the displacer, the displacer may be hooked to the torque arm and the entire unit lowered into position. When the extension consists of several detachable elements, this operation should be repeated for each element and the displacer lowered progressively into the tank. Mount the instrument and bolt the mechanism chamber onto the nozzle flange.

Note : Do not remove instrument cover until the unit has been installed and is ready for calibration.
The codes shown on Figure 2 indicate the instrument designation as a function of various installation modes, displacer chamber connections, and environmental standard or protection of the case against explosion. Figures 3 and 6 show the various ways of installing the displacer chamber. 3.2.1 EXTERNAL MOUNTING (Chamber Type Model, Figures 3 and 6) Install the transmitter in a vertical position on the side of the tank or vessel, so that the mid-range mark on the chamber is at normal level. The mid-range is marked on the chamber. The equalizing lines between chamber and vessel should be the same size as the chamber connections. Install a block valve in each line. The use of a drain connection is recommended as shown in Figure 3. The displacer is always immobilized in the displacer chamber to avoid any internal damage during transportation.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Figure 3 Typical Installation

Figure 4 Type 12303

Figure 5 Type 12304

b) Type 12304 Side Flange Mounted Transmitter (Figure 5) When the instrument is side flange mounted, enough clearance must be provided to permit attachment of the displacer after the chamber flange is bolted in place. To attach the displacer, reach into the end of the protective case and depress the torque arm. Then bring the displacer hanger up through the hole in the bottom of the case and slip the displacer hanger over the torque arm pin. Lower the displacer until the pin engages the top of the slot in the hanger. Guide Brackets for Type 12304 (Figure 5) If the liquid is in motion, provide brackets as shown in Figure 5 to guide the lower end of the displacer. The diameter of the hole should be 25 to 35 mm (1 to 1 1/2) larger than the diameter of the displacer for ranges to 1.8 m (6 feet), and 50 to 70 mm (2 to 3) larger for greater ranges. The brackets should be placed at 50 to 70 mm (2 to 3) from each end of the displacer. Locate the centerline of the hole so that the displacer hangs freely.
Type 12300 (NPT Screwed) Type 12301 (Flanged) Type 12309 (NPT Screwed) Type 12302 (Flanged)

Type 12305 (NPT Screwed) Type 12308 (Flanged)

Type 12306 (NPT Screwed) Type 12307 (Flanged)

Figure 6

Left Mounting (Top View)

Figure 7

Right Mounting (Top View)

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Stilling Well for Type 12303 (Figure 4) If the liquid is turbulent, provide a stilling well as shown in Figure 4. The well should be made from tubing or pipe of a suitable diameter to allow sufficient clearance between displacer and pipe. It should be mounted so that it extends at least 75 mm (3) below a free hanging displacer.

A hole at the top of the stilling well should be provided to equalize pressure between well and vessel. Instrument Case Mounting (Figure 7) The standard case mounting is left hand the case is to the left of the displacer. Right hand mounting is optional. To reverse instrument case mounting, refer to Section 6 Maintenance.

4. case description
The purpose of this section is to describe the various subassemblies of the instrument in order to facilitate their use and maintenance. (See Figures 19 to 21). (115). These set screws have no effect when mounting or dismounting the mechanism subassembly.

4.1 ELECTRONIC COMPARTMENT


The electronics compartment, located at the front of the transmitter, can be accessed by removing the main cover (20). This cover contains a window (22) and three push buttons (27). The cover (20) is fully screwed on to the case (2), sealed with an O-ring (109). It may be necessary to unscrew the cover by less than a turn to align the window and LCD display and to install the safety screw (110). The front plate (80), which is attached by three screws (125), protects the push buttons and provides a gasket seal (24). The sensor (40) and its seal (111) are secured by two screws (112), located in the upper part of the electronics compartment. The sensor is positioned so that the blue mark is oriented toward the lower part of the case (see Figure 10). Another blue mark on the case is a visual aid for the operator during reassembly. The microprocessor, the display and the three push buttons are mounted on the potted electronic board which makes the amplifier. This subassembly is inserted into the case with the display facing the top of the case. It is assembled by four screws (201). For wiring, refer to Section 4.4.

4.3 CONNECTION COMPARTMENT


The connection compartment is equipped with a terminal board (90). The flat handle terminal block, the test switch/pins, the HART connection pins and the terminal board connector are mounted on the terminal board. The terminal board is mounted with 2 screws (92). The case is also equipped with radio frequency filter connections between the terminal board connector and the main electronic circuit. To mount the safety screw (106), the cover must be fully screwed on the case and then unscrewed by less than a turn. DANGER : Do not remove either compartment cover in an explosionproof area when the instrument is powered. In an intrinsically safe installation, follow code practice when servicing the instrument in the field.

4.4 ELECTRIC CIRCUIT


4.4.1 WIRING AND CONNECTIONS
FLAT HANDLE TERMINAL BLOCK (90A) This item is located on the top side of the terminal board in the connection compartment. Connect the power supply leads to the terminal block. Pay attention to polarity. Refer to Figures 19 and 20. TERMINAL BOARD CONNECTOR (90B) This item is located on the bottom side of the terminal board in the connection compartment. Ensure terminal board connection with radio frequency filters. Pay attention to polarity. Refer to Figure 20.

4.2 MECHANISM COMPARTMENT


The mechanism compartment (Figures 20 & 21) on the back of the case has an opening on the right side (operator facing instrument) which is closed by a threaded cover (107) and a gasket (108). A second opening at the bottom, closed by a special 3/4 NPT plug (190), allows access to the mechanical flexure (59), which is part of the beam. The mechanism (50) [including parts (51 to 62)] is completely factory assembled and calibrated before being installed into the mechanism compartment. The pivot (51) is positioned toward the back of the case through two pins (52-53) and fastened by two screws (113). The beam (54) must be free to rotate without friction (up to 7 degrees max.). Two set screws (114) are located in tapped holes in the side of the case. The holes are covered by two plugs

NOTE : This connection is made at the factory and must not be adjusted or disconnected, except if the terminal board must be replaced.
SUPPLY TO MAIN BOARD (AMPLIFIER) (7) While facing the instrument this item is located on the bottom left side of the main board in the electronics compartment. It connects the main board to the radio frequency filters. Refer to Figures 19 and 21.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

NOTE : This connection is made at the factory and must not be adjusted or disconnected, except if the amplifier must be replaced. Observe the connecting position by means of the locking lugs, (below).
SENSOR CONNECTOR (40) While facing the instrument this item is located on the top bottom side of the main board in the electronics compartment. It connects the sensor to the main board. Refer to Figures 19 and 21.

Figure 8 Wiring Diagram

NOTE : This connection is made at the factory and must not be adjusted or disconnected, except if the amplifier and/or sensor must be replaced. Observe the connecting position by means of the locking lugs.

4.4.2 SUPPLY - OUTPUT SIGNAL


The standard transmitter provides a 4-20 mA output signal to remotely located receivers such as recorders, indicators or controllers. The supply voltage is : Flameproof version, 9,5 to 50 volts max. Intrinsic safety version, 9,5 to 30 volts max.

4.4.3 LOAD RESISTANCE


DANGER : All wiring shall be made in accordance with all local and national codes appropriate to the area in which the instrument is installed. The maximum load resistance in terms of the supply voltage may be determined from the curves in Figure 9. The R values in brackets correspond to a high alarm of 23 mA. If more accuracy is required, the maximum load resistance (R) may be calculated as follows : For a supply voltage V (V min. = 9,5 Volts) : V (Volts) 9,5 R (Ohms) = I max. (Ampere) In which : Figure 9 Load Resistance Diagram

I = Max loop current (information current of the liquid level : 3,8 to 20,5 mA ; alarm current : 3,6 to 23 mA).

4.4.4 ELECTRIC CONNECTION


Both the terminal strip and the ground terminal are located in an external junction box. A conduit connection (1/2 NPT or M 20) is provided in the lower part of the junction box for connecting the supply leads via a supplied stuffing box with an integrated cable clamp device or any cable gland with cable clamp device suitable for the considered hazardous area. Connect the receiver (load) in series with either one of the power supply leads as shown in Figure 8. Observe the polarities engraved on the terminal strip. Two blue spots to mark the correct sensor position Figure 10 Sensor Installation Position

10

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

4.4.5 MILLIAMMETER CONNECTION


An external milliammeter may be connected to the transmitter to verify the signal without disconnecting the power supply. Remove the safety screw (106) and disassemble the connection compartment cover (104). Put the switch on

the TEST position. Connect the milliammeter on the two pins located on each side of the switch. Before disconnecting the milliammeter put the switch back on the position identified by v. Fully screw the connection compartment cover and unscrew it by less than 1 turn to screw the safety screw. See Figure 19.

5. operating the instrument 5.1 General Principles


Note : 1. Do not overpush on the buttons. A button should be depressed at least one second to perform the action.
2. Accidental pushing of the buttons will not cause any malfunction. After using the buttons, reinstall the front plate (80) for NORMAL mode, which alternately displays the current loop and the level of liquid.

All electronic calibrations of the DLT are made by means of three push buttons and a liquid crystal display on the front of the instrument. The codes or values displayed by the LCD can be seen through a window. Access to the three push buttons is obtained by removing the protective logo plate (80). It is not necessary to open the main cover for calibration or adjustment of the instrument. Except for maintenance, the cover should remain closed.

5.1.1 The Liquid Crystal Display


It displays two lines and a bargraph. The upper line can displays to five numerical digits and a decimal dot. The lower line can display alphanumeric digits. On Normal operation, the LCD sequentially displays the loop current in mA and the level expressed in the unit displayed in the low left corner of the screen ; the level unit is generally % but an engineering unit can be selected through [UNIT] in CALIBRATION menu. The bargraph length is proportional to the loop current. The level value always increases with the height of liquid in the tank or displacer chamber whatever is the instrument action. For direct action, the current signal increases when level height increases ; for reverse action, the current decreases when level increases. The display is also used to Configure, Calibrate and Diagnose the DLT. To facilitate these operations, values, codes or short names appear on the display. The various parameters are listed in the menus (see APPENDIX A, B, C, D, F).

5.1.3 Operating Modes


The instrument can operate under 3 modes : NORMAL Mode : it is the normal operating mode. The 4-20 mA output current is proportional to the level in the tank. The local digital display alternately displays loop current and level expressed in the unit (% or engineering unit) shown in the low left corner of the screen. Reading of the instrument database is possible. MANUAL Mode : enter the manual mode when instrument configuration, calibration or diagnostic (set up or reading of diagnostic parameters) is required. The output current is not proportional to the tank level in this mode. FAILSAFE Mode : the instrument automatically sets to the failsafe mode when an error or an alarm has occurred. The output current is set to the value entered in the CONFIGURATION Menu.

5.1.2 Pushbuttons
Three pushbuttons (27) are located under the plate (80) on the front of the instrument. Remove the three screws (125). The left button is marked with a star D, the middle button with the sign , and the right one with the sign +.
D means enter the function, accept or save to memory ;

5.1.4 Pushbuttons Menu Description And How To Use Them ?


The menu structure for operating the 12300 from the local pushbuttons is shown on the next page. Seven menus are provided to configure, calibrate, diagnose or exit the failsafe mode ; an additional menu is provided to set numerical values of a selected parameter. Five APPENDIX (A, B, C, D, F), display the communication paths within each menu, and provide descriptions and explanations of each screen. NORMAL Mode Menu (see APPENDIX A). INFORMATION Menu : (see APPENDIX A). MANUAL Mode Menu : (see APPENDIX A).

may be replaced by YES. + or means : vertical movement in the program structure ; may be replaced by NO or NEXT or PREVIOUS.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

11

CONFIGURATION Menu : (see APPENDIX B). CALIBRATION Menu : (see APPENDIX C). DIAGNOSTIC Menu : (see APPENDIX D). FAILSAFE Mode Menu : (see APPENDIX A). SETVAL menu : (see APPENDIX D). SPECIFIC menus : (see APPENDIX F). Signs D, + and in the menus mean these buttons should be pressed to move into the menu.
D means : enter the function, accept or save to

5.1.4.1 NORMAL Mode Menu (APPENDIX A)


This menu will allow you to : move to the MANUAL Mode Menu [> MANU] where the instrument is in MANUAL Mode and can be configured, calibrated or diagnosed, move to the INFORMATION Menu [> INFO] where actual configuration, calibration and diagnostics data can be READ ONLY. Note also when you go to [> INFO] the instrument is still in the NORMAL Mode and still generates a 4 to 20 mA signal proportional to the tank level, return to the NORMAL Mode. Press any button to enter the NORMAL Mode Menu from the normal operating mode.

memory; may be replaced by YES. + or means : vertical movement in the program structure; may be replaced by NO or NEXT or PREVIOUS. When screen [D +/nn.nnn] is displayed, stroke + to increase numerical value or to decrease. The various small screens in the menu diagram represent codes and/or numerical values displayed on the LCD : explanations on the codes, on the corresponding function and on the value limits are described in the APPENDIXES. A momentary (>1 s) press of a button either will change menus or increase (or decrease) the displayed value by increments of 1 : see SETVAL menu.

5.1.4.2 INFORMATION Menu [> INFO] (APPENDIX A)


When the instrument is in the NORMAL Mode this menu will allow you to access databases to : Read configuration data : instrument function, direction of head mounting, action, failsafe option, high and low alarms, times before alarms flag are activated, language. Read calibration data : damping coefficient, low and high reference level current, low and high level, level unit, zero shift, reduced span, calibration specific gravity, service specific gravity, calibration specific gravity of specific gravity meter.

12

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Read diagnostic data : accumulated tank filling, time at low or high level, total time of working, electronic board temperature. Read fault : displays all permanent faults which might have occurred since the last clear fault. Clear fault : displays the status of cleared faults.

5.1.4.4 CONFIGURATION Menu [CONFIG] (APPENDIX B)


This menu allows you to set the following configuration options : the instrument function (level or interface), the direction of head mounting (left or right displacer when facing the LCD window), the action (direct:current increases with level; reverse: current decreases when level increases), the FAILSAFE current, the high and low alarms, the time delay prior to triggering off an alarm, the time duration before the instrument goes into the Failsafe mode, the language of the display. To enter the CONFIGURATION Menu : enter the MANUAL Mode menu and move into the menu to [ > CONFG], press D to display [CONFIG] then press any button to enter the menu. To exit the CONFIGURATION Menu and return to the NORMAL Mode display, move into the menu until [< MANU] is displayed and press D to display [STORAGE]. Press any button then D (to save data) or + or (no to save data) to display [MANUAL]. Then press D, , D : the instrument automatically returns to the NORMAL Mode display after [NORMAL] has been displayed for a few seconds. 5.1.4.4.1 To change the configuration from level service to interface level service From the normal operating condition press D, +, D, to display [MANUAL], Press any button then D to display [CONFIG],

NOTE : In the CONFIGURATION, CALIBRATION DIAGNOSTIC AND FAILSAFE menus in APPENDIX A to D, the screens which can be displayed to be READ ONLY under [>INFO ] are noted by INFO .
To enter the INFORMATION Menu from the NORMAL Mode press in sequence : D (or + or ), +, +, D. Then press the + or button to move into the INFORMATION Menu and reach the desired database to be read. Press D to enter the database. To display data, press + or . To exit the database press D. To exit the INFORMATION Menu and return to the NORMAL Mode move to [< NORM] using + or and press D. 5.1.4.2.1 To read the Calibration Specific Gravity [SG CAL] or the Service Specific Gravity [SG SER] From the normal operating condition press D, +, +, to move to the INFORMATION Menu, press D, + to display [D CALIB D] then D and + eight times to display [SG CAL] (or [LSG CAL] and [HSG CAL] for an interface level). Press + one more time to display the Service Specific Gravity [SG SER] or ([LSG SER] and [HSG SER] for an interface level).

5.1.4.3 MANUAL Mode Menu [MANUAL] (APPENDIX A)


The MANUAL Mode menu will allow you to move : to the CONFIGURATION Menu [> CONFG] where configuration options are selected, to the CALIBRATION Menu [> CALIB] where the instrument is calibrated, to the DIAGNOSTIC Menu [ > DIAGN] where diagnostic options are defined, To enter the MANUAL Mode menu from the normal operating mode press D to enter the NORMAL Mode menu, + to reach [> MANU] , D to enter the MANUAL Mode then press any button to enter the MANUAL Mode menu, To exit the MANUAL Mode menu move to [< NORM ] and press D. [NORMAL] appears for a few seconds and the instrument automatically returns to the NORMAL Mode display.

Press any button to display [LEVEL], Press D to display [INTERF]. The instrument is now configured as an interface level transmitter, To return to the NORMAL Mode and save the new configuration move into the menu using + or to display [< MANU], Press D, D, D, , , D to return to the NORMAL Mode.

5.1.4.5 CALIBRATION Menu [CALIBR] (Appendix C)


This menu allows you to: perform instrument coupling to the torque tube, perform the instrument calibration (transmitter and specific gravity meter), change the calibration and service specific gravity, adjust the damping coefficient applied to the loop current,

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

13

set the current corresponding to the low and high levels, select the display unit, adjust the low and high loop current, adjust zero and span for the reduced scale, recalibrate the internal milliammeter and/or force a given loop current. To enter the CALIBRATION Menu from the NORMAL Mode, press D , + , D , D to enter the MANUAL Mode menu and move in the menu to [> CALIB]. Press D to display [CALIBR] then press any button to enter the menu. To exit the CALIBRATION Menu and return to the NORMAL Mode display, move into the menu until [<-MANU] is displayed and press D to display [MANUAL]. Then press D , , D : the instrument automatically returns to the NORMAL Mode display after [NORMAL] has been displayed for a few seconds.

5.1.4.5.2 Calibration To calibrate the instrument :

a) For a level instrument,


Set the Specific Gravity value of the liquid used for calibration [SG CAL] and take the REF L [ZERO] and REF H [SPAN],

b) For an interface instrument,


Set the Low and High Specific Gravities of the liquids used for calibration and take the REF L [ZERO] and REF H [SPAN],

c) For a level or an interface instrument,


Set the currents and levels corresponding to REF L and REF H, Define the unit for level indication, Set the Zero and Span for reduced scale (Refer to Section 5.3.2.5), Set the damping action applied to the loop current (Refer to Section 5.3.2.4),

5.1.4.5.1 To Change the Service Specific Gravity, [To avoid re-calibration if service specific gravity (ies) is (are) different from calibration specific gravity (ies)]

Calibrate the specific gravity meter, (Refer to Section 5.3.2.1), To enter the CALIBRATION Menu from the Normal operating mode, press in sequence : D (or + or ), +, D, D, +, D, to display [CALIBR]. To quit the CALIBRATION Menu and return to Normal Operating mode, move into the menu until [<-MANU] is displayed, then press D to display [MANUAL], via [STORAGE] and [YES NO]. Then press D, , D : [NORMAL] appears for a few seconds and the instrument automatically returns to Normal Operating displaying alternatively the current and the level. 5.1.4.5.3 Recalibration of the internal ammeter

From the NORMAL Operating condition press D, +, D, to display [MANUAL]. Press any button to enter the MANUAL Mode menu. Press + to display [> CALIB] then D to display [CALIBR]. Press +, + to display [CHG SG]. Press D to display the specific gravity.

a) For a level instrument,


Enter the Specific Gravity of Service [SG SER] .

CAUTION : Must be done only if current output is not the same as the current displayed.
Move to sub-menu [4 20 MA]. (Refer to Section 7 Trouble Shooting and APPENDIX C). 5.1.4.5.4 Force the current to display a required value

b) For an interface instrument,


Enter the Low and High Specific Gravities of Service [LSG SER] and [HSG SER]. Press D to enter SETVAL menu. See SETVAL menu (Section 5.1.4.8) to change the service specific gravity. After adjustment press D to exit SETVAL menu. Press + or to display [< ]. Press D to display [STORAGE]. Press any button then D to save new specific gravity. and to display [CHG SG]. To return to the NORMAL Mode move into the menu using + or . to display [< MANU]. Press D , D , , D to return to the NORMAL Mode.

Allows setting another instrument (such as a positioner) in series in the loop, generating a required output current. Move to sub-menu [4 20 MA] then [MA GENE] and proceed as indicated in APPENDIX C).
5.1.4.5.5 Reposition the Hall effect sensor towards the torque tube rod

Only necessary after installation of an instrument on the torque tube. Move to submenu [COUPLNG]. (Refer to Sections 6.2.3 or 6.2.4).

14

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

5.1.4.6 DIAGNOSTIC Menu [DIAGNOS] (Appendix D)


This menu allows you to: Get information on working data : accumulated tank filling, time during which the level was high or low, total time of working, board temperature, Test the Hall effect sensor, Tune manually or automatically the smart filtering function, Test the specific gravity meter, Get the history of faults (permanent and non permanent), Reset the diagnostics database, To enter the DIAGNOSTIC Menu from the NORMAL Mode press D , +, D to enter the MANUAL Mode menu and move in the menu to [> DIAGN]. Press D to display [DIAGNOS] then press any button to enter the menu. To exit the DIAGNOSTIC Menu and return to the NORMAL Mode display, move into the menu until [< MANU] is displayed :and press D to display [MANUAL]. Then press D, , D : the instrument automatically returns to the NORMAL Mode display after [NORMAL] has been displayed for a few seconds.

5.2 Initial Calibration of an Instrument on Level Service


To perform a first calibration and running in case of a level application of the instrument refer to APPENDIX E.

5.3 Calibration Procedures for Specific Parameters and Applications


After the 12300 Level Instrument has been installed and connected, remove the front plate (80) located in front of the instrument to gain access to the push buttons and select all required configuration data as indicated in the Section 5.1.4.4. APPENDIX B, then proceed as follows:

NOTE : The electronic circuit has been factory adjusted during instrument manufacturing to 4-20 mA, using a reference milliammeter. So, for calibration on site, no measurement instrument is required. However, if the loop current must be verified and if full compliance with standards requirements for instruments installed in hazardous areas is required, insert the milliammeter in series with the power supply or connect it to the electronic board provided into the connection compartment. Put the switch on the TEST position. Connect the milliammeter on the two pins located on each side of the switch. Before disconnecting the milliammeter put the switch back on the position identified by v. See Figure 19.
Danger : If area cannot be verified as safe, do not remove any covers.

5.1.4.7 FAILSAFE Mode menu (Appendix A)


The FAILSAFE mode menu allows you to : Read fault which has occurred, Clear fault which has occurred, Reset to factory default settings, Return to NORMAL Mode. When the instrument is in the FAILSAFE Mode it displays [FAILSAF]. To enter the FAILSAFE Mode menu press any button. To exit move in the menu to [> NORM] and press D. The instrument automatically returns to the NORMAL Mode display after [REV xxx ] and [NORMAL] have been displayed for a few seconds.

5.3.1 Direct Reading on the Liquid Specific Gravity Meter [SGMETER]


Caution : Direct reading of specific gravity is correct only :

5.1.4.8 SETVAL menu (Appendix D)


This setting values menu is used to set numerical values for any function requiring such an action. To enter or exit SETVAL menu from a function press D. When entering SETVAL menu [<
#.### #.###

If displacer volume is lower than 1270 cm3 and service specific gravity X displacer volume is lower than 1270. If the displacer is fully immersed in the liquid and if the [SGMETER] function has been preliminary calibrated.

] is displayed.

Push + to display [ ^ ], then + or to shift the sign ^ below the number to be changed. Push D to display [ +]. Push + to increase or to decrease to change the number. Validate by D. Repeat for each digit. To exit the SETVAL menu press + or to display #.### [< ]. Then press D.
#.###

To calibrate the [SGMETER] function, refer to

Section 5.3.2.1.
To read specific gravity of the process liquid : Fill the displacer chamber until the displacer is fully immersed in the process liquid. Move into the DIAGNOSTIC Menu (APPENDIX D) until [RD CTR] then [SGMETER] are displayed. Push D to read the value. Return to normal operation.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

15

5.3.2 To Set up Parameters


5.3.2.1 Calibrate the Specific Gravity Meter
This adjustment is made at the factory for complete instruments. Use of the specific gravity function [SGMETER] aids in performing on site new calibrations of simulations with or without liquid.

It should be modified only if zero and span calibration are performed again for a liquid of different specific gravity. Refer to Section 5.3.3.4 Calibration, Steps 1 to 7.

5.3.2.3 Service Specific Gravity [SG SER]


The service specific gravity is the one used for the function [SG SER] in the CALIBRATION Menu. Its value is identical to that of [SG CAL] just after calibration. If the specific gravity of the process liquid is different, modify the value of [SG SER]. Two cases are possible : a) If the specific gravity of the liquid is unknown, you must first measure specific gravity of the liquid by using the function [SGMETER]. See Section 5.3.1, then proceed as follows : b) If the specific gravity is known, it can be modified, regardless of what the liquid level in the displacer chamber is. To adjust the value : Move into the CALIBRATION Menu until [CALIBR], [CHG SG] then [SG SER] are displayed. Validate by D to enter SETVAL menu and set the specific gravity. Return to normal operation. Caution : In interface service , if the [LSG SER] and/or [HSG SER] are modified, an automatic calculation is performed to set a new value in [ZERO <>].

Caution : The Specific Gravity Meter function is factory calibrated at a specific gravity of 1 for complete instrument only if the displacer volume is lower than 1270 cm3 and the weight is 1362 g. For an instrument delivered alone with a torque tube, the Specific Gravity Meter function is factory calibrated at a SG 1 for a displacer with 907 cm3 / 1362 g. If actual displacer characteristics differs from these values, recalibration is necessary and will be possible only if displacer volume is lower than 1270 cm3 and service specific gravity x displacer volume is lower than 1270 :
Proceed as follows : a. Move to CALIBRATION Menu (APPENDIX C) until [SGM CAL], then [SG CAL] are displayed. Validate by D to enter SETVAL menu and set the specific gravity of 1. Store data. b. Empty the chamber or simulate the low level by using weights and stabilize the displacer (or the weights). c. Display [ZERO ] and press D to set the REF L.

NOTE : During the procedure, refer to Section 5.3.2.6 if the LCD displays [ERROR]. d. Attach a set of weights to the torque arm to simulate a high level or fill the displacer chamber until the high level is reached. Stabilize the displacer (or the weight). On site : Fill the displacer chamber until high level (REF H) is reached by a specific gravity 1 liquid.
In workshop : Simulate by weights the high level (REF H) corresponding to the apparent weight of the actual displacer fully immersed in a specific gravity 1 liquid. e. Display [SPAN ] and press D to set the REF H, f. Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [CAL Z S] is displayed, g. Exit the CALIBRATION Menu via [<MANU] and D then move into the DIAGNOSTIC menu (APPENDIX D) until [RD CTR] then [SGMETER] are displayed. Push D to read the value and check if the calibration is successful. Return to NORMAL Operation Mode.

5.3.2.4 Output Current Damping [DAMPING]


In case of rapid oscillations of the level or if the liquid is in motion, it may be necessary to filter the output signal. A first order digital filter is provided for adjusting the damping coefficient. Enter the CALIBRATION Menu, move to display [VAR SET], then [DAMPING] and validate by D to enter SETVAL menu and set the filtering coefficient. Return to normal operation.

5.3.2.5 Reduced Range and /or Zero Shift [SPAN > <], [ZERO <>]
For an application where the level change is smaller than the displacer height, it is possible to obtain the full signal range for this reduced level range. Enter the CALIBRATION Menu, move to display [VAR SET], then [ZERO <>] and validate by D to enter SETVAL menu and set the zero shift value. Return to the [ZERO <>] screen by D, Move to display [SPAN > <] and validate by D to enter SETVAL menu and set the span reduction value. Return to display [SPAN > <] screen by D, Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [VAR SET] is displayed,

5.3.2.2 Calibration Specific Gravity [SG CAL]


The calibration specific gravity is that of the liquid used (or simulated by weights) for calibration of zero and span in the CALIBRATION Menu.

16

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

5.3.2.6 Error Code on Zero and Span Set


a) The value of the span can be accepted before or after the zero value is entered. If you accept the zero without simulating the corresponding level change, the LCD displays [ERROR]. Press D to delete the message and then perform (or simulate) the level change before acquiring the new value. b) The LCD may also display [ERROR] for a new calibration if : The zero value is higher or equal to the span of the preceding calibration. If so, accept and store the span first and then the zero. Figure 11 Schematic Example of Reduced Range The span value of the new calibration is smaller than the zero value of the preceding calibration. If so, accept and store the zero value first and then the span.

Exit the CALIBRATION Menu via [<MANU] and D then return to NORMAL Operation Mode via the MANUAL Mode.

Example : To modify a calibration so that 0 % corresponds to a displacer immersed to 1/4 of its height (25 %), and 100 % corresponds to a displacer immersed to 4 / 5 of its height (80 %), adjust zero shift to 25 % and span reduction to 45 %, (see schematic on Figure 11).

5.3.3 Calibration (for Level Instrument Service)


5.3.3.1 Principle of Calibration
The electronic circuit is calibrated towards two reference levels (REF L and REF H), see Schematic below : REF L corresponds to the displacer completely out of liquid.

Caution : If new calibration is performed, the parameters of the reduced range [SPAN > <] and/or zero shift function [ZERO <>] are automatically set to zero. In interface service : If the [LSG SER] and/or [HSG SER] are modified, an automatic calculation is performed to set a new value in [ZERO <>].

REF H corresponds to the displacer fully immersed in the liquid of Specific Gravity used for calibration [SG CAL]. The loop current corresponding to REF L may be set through [MA L] via [VAR SET] ; it is generally 4 mA. The current corresponding to REF H may be set through [MA H] via [VAR SET] ; it is generally 20 mA.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

17

The value of [MA H] shall always be higher than the value of [MA L]. The level indication corresponding to REF L is set through function [LEVEL L] via [VAR SET] ; it is expressed in the unit set through [UNIT] function ; if UNIT is %, LEVEL L should be 0.0. The level indication corresponding to REF H is set through function [LEVEL H] via [VAR SET] ; it is expressed in the unit set through [UNIT] function ; if UNIT is %, LEVEL H should be 100.0. The electronic circuit is calibrated so that the indicator range 4-20 mA corresponds to the indication of a milliammeter inserted in series with the supply circuit of the DLT. Therefore it is not necessary to connect a milliammeter when performing an on site calibration ; the instrument display is sufficient. Danger : Connection of a milliammeter in series must be compatible with applicable hazardous area standards requirements. Refer to Section 4.4.4.

Wait for the displacer to stabilize to validate the values displayed after each change in liquid level. Take actions necessary to allow a change in the liquid level in the chamber : open/close isolation valves, vent, purge, etc. Proceed as indicated under 5.3.3.4 Calibration :

5.3.3.4 Calibration
1. Switch on the power. Attach a set of weights to the torque arm to simulate a low level or empty the displacer chamber. 2. Enter the CALIBRATION Menu and press in sequence : D (or + or ), +, D, D, +, D, to display [CALIBR], 3. Set the Specific Gravity value of the liquid used for calibration [SG CAL]. Refer to Section 5.1.4.8 for the SETVAL sub-menu, 4. Display [ZERO ] and press D to set the REF L,

5.3.3.2 Conditions for Dry Calibration in Workshop (Simulation by Weights)


Caution : When performing a calibration, use the following parameter units wherever they apply :
Parameter Name Displacer Weight Displacer Volume Water Density (WD) S.I Units g cm3 1 g/cm3 English Units lbm in3 0.036 lbm/in3

NOTE : During the procedure, refer to Section 5.3.2.6 if the LCD displays [ERROR].
5. Attach a set of weights to the torque arm to simulate a high level or fill the displacer chamber until the high level is reached, 6. Display [SPAN ] and press D to set the REF H, 7. Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [CAL Z S] is displayed, 8. Move to [VAR SET] to display successively [MA L], [MA H], [LEVEL L], [LEVEL H] and, if needed, set the currents and levels corresponding to REF L and REF H, 9. Display [UNIT ] and define the unit for level indication, 10. If necessary, display [DAMPING] and set the damping action applied to the loop current. (Ref. to Section 5.3.2.4), 11. If necessary, set zero and span for reduced range. (Ref. to Section 5.3.2.5), 12. Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [VAR SET] is displayed, 13. When the calibration is completed, move into the menu until [<MANU] is displayed, then press D to exit the CALIBRATION Menu and to display [MANUAL], 14. Press D , , D : [NORMAL] appears for a few seconds and the instrument automatically returns to Normal Operating display, 15. Reinstall the front plate (80) with the three screws (125).

The effective change in level will be simulated by a set of weights corresponding to : a) The weight of the actual displacer at low level (REF L), which allows you to calibrate the zero and obtain the minimum value [ 0,0%] of the signal (direct action). b) The apparent displacer weight when the level is high (REF H). This allows you to calibrate the span and obtain the maximum value [100,0%] of the signal (direct action). The corresponding weight is calculated as : Apparent Displacer Weight =
Displacer Actual Weight (Displacer Actual Volume x S.G.x WD)

Caution : Actual volume and weight of the displacer can be read using HART protocol only if they have been previously stored in the DLT head. Otherwise, actual volume of the displacer is marked on the specification plate (124). Weigh the displacer to get the actual weight. Proceed as indicated under 5.3.3.4 Calibration :

5.3.3.3 Conditions for Calibration in the field with a Liquid


The effective change in level will be obtained by emptying and filling of the displacer chamber with a liquid.

18

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

NOTE : The calibration specific gravity [SG CAL] is automatically stored in the service specific gravity function [SG SER]. If the instrument is to be used with a liquid of different specific gravity, reenter the CALIBRATION Menu to set and accept this new value in [SG SER]. (See Section 5.3.2.3).

The electronic circuit is calibrated so that the indicator range 4-20 mA corresponds to the indication of a milliammeter inserted in series with the supply circuit of the DLT. Therefore it is not necessary to connect a milliammeter when performing an on site calibration ; the instrument display is sufficient. Danger : Connection of a milliammeter in series must be compatible with applicable hazardous area standards and requirements. Refer to Section 4.4.4.

5.3.4 Calibration of an Instrument for Liquid Interface Service


5.3.4.1 Principle of Calibration
The level transmitter is used to measure the interface level of two immiscible liquids of different specific gravities. The displacer must always be fully immersed. The electronic circuit is calibrated towards two reference levels (REF L and REF H) : REF L corresponds to the displacer completely out of liquid. REF H corresponds to the displacer fully immersed in the liquid of Specific Gravity used for calibration [SG CAL]. The loop current corresponding to REF L may be set through [MA L] via [VAR SET] ; it is generally 4 mA. The current corresponding to REF H may be set through [MA H] via [VAR SET] ; it is generally 20 mA. The value of [MA H] shall always be higher than the value of [MA L]. The level indication corresponding to REF L is set through function [LEVEL L] via [VAR SET] ; it is expressed in the unit set through [UNIT] function ; if UNIT is %, LEVEL L should be 0.0. The level indication corresponding to REF H is set through function [LEVEL H] via [VAR SET] ; it is expressed in the unit set through [UNIT] function ; if UNIT is %, LEVEL H should be 100.0.

5.3.4.2. General Information on interface service displacers


Under this Section we will consider a standard displacer any displacer with the following characteristics : Volume V : 1270 cm 3 ( 77 in 3 ), marked on specification plate (124), Product of V x SG 1270, Weight = 1362 g (3 lbm).

A standard displacer may be used when the liquid specific gravity difference is between 0.1 and 1.4 (with lower accuracy between 0.1 to 0.2). The lowest specific gravity (d1) liquid is 1.3 max. The highest specific gravity (d2) liquid is between 0.1 and 1.4. Caution : Special displacers may be provided for specific applications (material, service conditions). In these cases, volume and/or weight will differ from standard displacer characteristics. Actual volume and weight of the displacer can be read using HART protocol only if they have been previously stored in the DLT head. Otherwise, actual volume of the displacer is marked on the specification plate (124).

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

19

Weight of the displacer is only necessary on dry calibration to simulate the apparent weight of the displacer immersed into the liquids : Weigh the displacer to get the actual weight.

5. Set and store [SPAN] for interface configuration. 6. Quit CALIBRATION Menu. 7. In the DIAGNOSTIC Menu, move to [SGMETER]. The specific gravity displayed must correspond to the specific gravity of the liquid in the chamber. This assumes the [SGMETER] has been calibrated. 8. Slowly empty the chamber until the LCD displays the lowest S.G. value (d 1 ) and record this value. 9. Quit the [SGMETER] function and the DIAGNOSTIC Menu. 10. Return to CALIBRATION Menu. 11. Set the [ZERO] for interface configuration. 12. Complete the calibration as indicated in Steps 7 to 15 of the Section 5.3.3.4.

NOTE : During following procedures, refer to Section 5.3.2.6 if the LCD displays [ERROR].

5.3.4.2.1 Wet Calibration The effective change in level will be obtained by emptying and filling of the displacer chamber with the two liquids . Wait for the displacer to stabilize to validate the values displayed after each change in interface of liquids. Take actions necessary to allow a change in the interface of liquids in the chamber : open/close isolation valves, vent, purge, etc. The procedure is identical to the one used for calibrating a level transmitter in a liquid on site (see Section 5.3.3.4), except for the differences outlined below.

c. On Site Using Water if the Highest Specific Gravity (d2) is 1 Caution : This procedure is only possible if the [SGMETER] function has been calibrated. Refer to Section 5.3.1. 1. Take necessary action to allow change in liquid interface level in the displacer chamber such as isolating, vent, purge valves etc.... and then empty the chamber. 2. Enter the DIAGNOSTIC Menu and move to [SGMETER]. 3. Increase the water level in the displacer chamber until LCD displays the value of the process lowest specific gravity (d1). 4. Quit [SGMETER] and enter the CALIBRATION Menu. Move until [CAL Z S], then [LSG CAL] and [HSG CAL] is displayed to enter (d1) and (d2). 5. Set and store [ZERO] for this water level (d1). 6. Quit the CALIBRATION Menu and return to [SGMETER] in the DIAGNOSTIC Menu. 7. Increase the water level in the displacer chamber until the LCD displays the value of the highest specific gravity (d2). 8. Quit [SGMETER] and the DIAGNOSTIC Menu, then return to CALIBRATION Menu. 9. Set and store the [SPAN] for this new water level (d2). 10. Complete the calibration as indicated in Steps 7 to 15 of the Section 5.3.3.4.

a. With the Process Liquids 1. Enter the specific gravities to be used for calibration by using the functions [LSG CAL] and [HSG CAL]. 2. Take necessary action to allow change in liquid interface level in the displacer chamber such as isolating, vent, purge valves etc....It is then necessary to put liquids in the chamber to: 3. Set the [ZERO] when the displacer is fully immersed in the lowest specific gravity liquid (d1). 4. Set the [SPAN] when the displacer is fully immersed in the highest specific gravity liquid (d2). 5. Complete the calibration as indicated in Steps 7 to 15 of the Section 5.3.3.4.

b. With the Highest Specific Gravity Liquid (d2) Caution : This procedure is only possible if the [SGMETER] function has been calibrated. Refer to Section 5.3.1. 1. Take necessary action to allow change in liquid interface level in the displacer chamber such as isolating, vent, purge valves etc.... and then : 2. Enter the CALIBRATION Menu. 3. Enter the specific gravities to be used for calibration by using the functions [LSG CAL] and [HSG CAL]. 4. Admit liquid (d 2 ) into the chamber to fully immerse the displacer.

20

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

5.3.4.2.2. Dry Calibration Conditions for Dry Calibration in a Workshop (Simulation by Weights)

b. With or Without Liquid in the Displacer Chamber (Use of Adjusting Screws to calibrate)

Caution : When performing a calibration, use the following parameter units wherever they apply :
Parameter Name Displacer Weight Displacer Volume Water Density (WD) S.I Units g cm3 1 g/cm3 English Units lbm in3 0.036 lbm/in3

Caution : This procedure is only possible if the [SGMETER] function has been calibrated. Refer to Section 5.3.1.
This method uses the [SGMETER] function (set in workshop), to adjust the screws (114) to the interface specific gravities. If a milliammeter is not required, this calibration may be performed with the case closed. Open the access plug (107) on the right side of the case to look at the simulation mechanism. Remove plug (190) and the two 1/8 NPT plugs (115). (Use a 5 mm Hex. wrench). Through this hole, use your finger to move the flexure (59) in the direction of the torque tube until the flexure touches the adjusting screw post (114). While maintaining contact, slide the flexure left or right along the surface of the screw post, (Figure 12).

Caution : Actual volume and weight of the displacer can be read using HART function only if they have been previously stored in the DLT head. Otherwise, actual volume of the displacer is marked on the specification plate (124). Weight of the displacer is only necessary on dry calibration to simulate the apparent weight of the displacer immersed in the liquids : Weigh the displacer to get the actual weight.
a. In the Workshop (Simulation by Weights) The procedure is identical to the one used for a normal level transmitter service (see Section 5.3.3.4), except the set of weights is calculated as follows : To simulate an interface at 0 % (REF L) and calibrate the zero, attach to the torque arm a weight equal to the actual displacer weight when fully immersed in the lowest specific gravity liquid , which is calculated as :
Displacer Apparent Weight for REF L = Displ. Actual Weight (Displ. Actual Volume x d1 x WD)

Adjusting the Screws (114) Adjust the screw (114) on the displacer side, relative to the instrument axis, to simulate the force on the displacer resulting from the highest specific gravity of the process liquids (d2). Adjust the screw (114) on the opposite side to the displacer to simulate the force on the displacer resulting from the lowest specific gravity of the process liquids (d1).

Caution : During the dry calibration without mechanism chamber, DO NOT ATTACH A SPECIAL INTERFACE SERVICE DISPLACER (OR ITS EQUIVALENT EFFECTIVE WEIGHT) on the torque arm. These displacers are heavier than those for liquid level service. Any mechanical stop is possible out of mechanism chamber, causing inevitable damage to the torque tube and/or the DLT mechanism. To simulate an interface at 100 % (REF H) and calibrate the span, attach to the torque arm a weight equal to the effective displacer weight when fully immersed in the highest specific gravity liquid, which is calculated as :
Displacer Apparent Weight for REF H = Displ. Actual Weight (Displ. Actual Volume x d2 x WD)

Enter in [LSG CAL] and [HSG CAL] the process liquids specific gravities (d1) and (d2).

Figure 12

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

21

Proceed as follows : 1. Remove the front plate (80). Enter the DIAGNOSTIC Menu then move to [SGMETER] and accept by D. 2. Press the flexure (59) against the adjusting screw shoulder (114) which corresponds to the lowest specific gravity, d1. While maintaining contact and using a 3 mm hex wrench, turn the adjusting screw until LCD displays d1. 3. Press the flexure (59) against the adjusting screw shoulder (114) which corresponds to the highest specific gravity, d2. While maintaining contact and using a 3 mm hex wrench, turn the adjusting screw until LCD displays d2. 4. Slowly move from one shoulder to the other (to avoid displacer oscillations) and verify the value displayed. Correct adjustments if necessary. 5. Quit the [SGMETER] function and return to [MANUAL] display. Calibration with screws (114) 1. Enter the CALIBRATION Menu and move to display [CHG SG], then [LSG SER] and [HSG SER]. Read these two values and return to [CHG SG].

2. Move to [CAL Z S] then to [LSG CAL] and [HSG CAL] to enter the specific gravities (d1) and (d2). 3. Move to display [ZERO]. Press the flexure (59) to contact the lowest specific gravity adjusting screw (114) (opposite to the displacer side). Wait for a few seconds until the displacer stabilizes and accept the zero value. 4. Move to display [SPAN]. Move the flexure (59) to contact the shoulder of the screw (114) corresponding to the highest specific gravity (on displacer side). Wait a few seconds until displacer is stable and accept the span value. 5. Release the flexure. 6. Complete the calibration as indicated in Steps 7 to 15 of the Section 5.3.3.4. 7. Reinstall plugs (107), (190), and (115).

NOTE : If the displacer chamber is empty, the LCD will display an incorrect negative value. The zero of the LCD is correct only when the displacer is fully immersed in the lowest specific gravity liquid.
Moving the flexure from one shoulder to the other varies the display and the loop current from 0 to 100 %.

6. maintenance

CAUTIONS
1. Do not remove the main cover (20) or the connection compartment cover (104) without first switching off the power supply or verifying that the instrument is installed in an intrinsically safe circuit or is not installed in an explosive atmosphere. 2. Operations described below may require you to open the mechanism compartment. Before returning the instrument to normal operation, verify that both covers and the plug are correctly reassembled with gaskets in good condition. Use only original Masoneilan parts. Pay particular attention to the plug (190), which includes a compressible gasket (192).

6.1 Removing the DLT Case From the Torque Tube (Figures 13, 14, 15 & 21).
a. Switch off power supply. Unscrew (106) until it disengages from the case and remove the cover (104) of the connection compartment. Disconnect supply wires from terminals (90). b. Remove cover (107) of the mechanism compartment. Using a 2.5 mm hex wrench, loosen screw (62) to uncouple the beam (54) from the torque rod. c. While holding the case to prevent it from falling, loosen the four screws (121), using a 5 mm hex wrench, and remove them along with the washers (122). Remove the case by pulling it along the axis of the torque tube while being careful to prevent any deformation of the coupling flexure (70).

22

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

d. If the original case or an identical one will be reinstalled on the same torque tube, do not remove the coupling flange (116) from the torque rod. Also, do not disconnect the coupling flexure subassembly (70). As an alternative, loosen screws (119) using a 1.5 mm hex wrench and remove the coupling flange-flexure sub-assembly (116-70). e. If the torque tube is not the 12300 type, remove the DLT case adapter kit, if necessary. This kit includes a flange, a gasket, and screws, (see Figure 14).

6.2 How to Install a DLT on a Torque Tube (see Figures 1, 13, 17 & 21)
6.2.1 On a 12200/300 Series Torque Tube
a. Mount the torque tube (137) on a support. The knife pivot at the back of the tube must be oriented toward the top. b. On the transmission rod (138), mount the coupling flange (116), coupling flexure S/A (70) [incl. flexure (71), pin (72) and washer (73)], flange (117) and its two loosened screws (118). Tighten screws (118) so that the sub-assembly is free to slide on the transmission rod, (see Figure 13). c. Position the sub-assembly vertically on the rod so that the distance between the coupling flexure (71) and the torque tube flange, (see Figure 21) is 59.5 mm 0.5. Firmly tighten this sub-assembly to the rod, using the two lateral screws (119). d. Mount a new O-ring (120) on the torque tube flange. e. Verify that the screw (62) on the beam (54) is loose. f. Position the case correctly oriented toward the front and in line with the axis of the torque tube. g. Slide the case into the torque tube flange while observing through the side opening that the pin (72) is inserted into the beam coupling end. Use a flat tool to easy backup the coupling flexure (71). h. When the case is in contact with the torque tube flange, verify that the beam is free to rotate by placing your finger on the flexure (59) through the lower 3/4 NPT hole. i. Fasten the case with four screws (121) and washers (122). Firmly tighten. j. Verify again that the beam is free to rotate and that the coupling flexure (71) is not deformed. The coupling on the beam (54) will be tightened later. Figure 13 Adjustment of Coupling Flexure (71) on Coupling Flange (116)

6.2.2 12120/12800 Series Torque Tube (See Figure 14)


The transmitter can be mounted on different types of existing torque tubes. Kits including flange, gasket, and screws are provided for the adapter tubes.

6.2.3 Workshop Calibration of Coupling


Coupling between torque tube and mechanism is achieved by simulating a 1.4 specific gravity liquid. The value of the weights is determined by the formula below, (see section d).

NOTE : It is necessary to know the mounting direction (right or left) and the action direction of the signal (direct or reverse) refer to Section 5.1.4.4 CONFIGURATION Menu and APPENDIX B.
a. Using a support, install the transmitter and its torque tube. b. Remove the screw (106 ), the covers (104 & 107) of the connection and mechanism compartments, and the plug (190) located at the bottom of the instrument. c. Assemble the standard torque arm on the right or left side as required. (Refer to Figure 7). d. Attach to the torque arm a weight equivalent to that of a displacer half immersed in a 1.4 specific gravity liquid :
Calibr. Weight = Displacer Actual Weight Displacer Actual Volume x WD x 1.4 2

NOTE : At this point, if instrument service conditions are well defined, refer to Section 6.2.3 Instrument Coupling to the Torque Tube in Workshop or Section 6.2.4 Instrument Coupling to the Torque Tube on Site

e. Connect a 24 V dc supply (switch OFF) to the terminals in the connection compartment in series with a milliammeter. Note polarities. f. Proceed with configuration of the instrument. Refer to Section 5.1.4.4 CONFIGURATION Menu and APPENDIX B.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

23

1 Adapting Flange 1 gasket 4 Lockwashers

ADAPTATION KIT FOR 12800 MASONEILAN TORQUE TUBE EUROPEAN DESIGN

4 Hex. H. Screws

4 Hex. H. Screws

1 O-ring

4 Lockwashers ADAPTATION KIT FOR 12120 MASONEILAN TORQUE TUBE EUROPEAN DESIGN

1 Adapting Flange 4 Lockwashers 1 O-ring

4 Hex. H. Screws ADAPTATION KIT FOR 12800 & 12120 MASONEILAN TORQUE TUBE USA DESIGN Figure 14 Adaptation on 12800 /12120 Torque Tube g. Move to CALIBRATION menu [COUPLNG]. to display

1 Adapting Flange

h. By looking through the side orifice, verify that the screw (62) coupling end of the beam (54) is loose. Through the 3/ 4 NPT hole at the bottom of the case, press the flexure (59) with your finger to verify it is possible to move the beam (54) from left to right. The value displayed should vary accordingly. Pin (72) must rotate freely inside the coupling end of the beam. i. Look at the mechanism through the lateral orifice, and index the oval hole of the flexure towards the special conical ended pin (53) by bending the flexure (59) toward the case front, (see Figure 15). Note the value read on the LCD it should be between 5 and + 5 %.

NOTE : At this step, verify that the weight used to simulate the displacer is stable. To obtain the ideal value (around 0 %), it may be necessary to slightly bend the flexure towards left or right (while keeping the conical pin (53) in the oval hole of the flexure).
j. While holding the flexure (59) in that position, slightly but firmly tighten the screw (62) using a 2.5 mm Allen wrench. k. Remove your finger so that the flexure disengages the conical pin. l. Read the value on the LCD. It should remain between 5 and + 5 %.

24

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Figure 16 Curve of Half Level Simulation in a Liquid with S.G. Between 0.7 and 1.4

Figure 15 Indexing for Coupling Adjustment

If the specific gravity (d3) (or the difference of the SG in case of an interface service) of the available liquid is below 0.7, perform the coupling at a high level. Caution : In this situation, the instrument must be used for specific gravities (or the difference of SG) ranging from 0.2 to 2 d3. a. If necessary, assemble the right adapter kit and verify that the torque tube is satisfactory See Sections 6.2.1 or 6.2.2. b. Install the instrument see Section 6.2.1 or 6.2.2. c. Make electrical connections See Section 4.4. d. Proceed with configuration of the instrument. Refer to Section 5.1.4.4 CONFIGURATION menu. e. Set the coupling between torque tube and mechanism subassembly See Section 6.2.3, Steps g to m. f. Calibrate the instrument See Section 5.3.3 or 5.3.4.

NOTE : The torque applied to tighten the screw (62) will change the value read after Step i. So, if the displayed value is not acceptable, take note of the value gap between before and after tightening screw (62). Loose screw (62) and repeat steps h to m noting the value gap during the new Step i.
m. If the displayed value is acceptable, adjust the specific gravity meter function [SGMETER] into [SGM CAL] (Section 5.3.2.1). Set adjusting screws (Section 6.2.5). Perform instrument calibration (Section 5.3.3 or 5.3.4).

6.2.4 Coupling to the Torque Tube on Site (in the Process Liquid)
The DLT case can be mounted on an installed torque tube. In this case, procedures described in Section 6.2.3 should be performed on site. In coupling the torque tube to the mechanism subassembly (which starts at step 6.2.3. d), two situations may occur : If the specific gravity (or the difference of the SG in case of an interface service) of the available liquid is between 0.7 and 1.4 : simulate half level h (1.4) of a 1.4 specific gravity liquid with a calculated value h (d) of the available liquid (refer to chart Figure 16).

6.2.5 Setting Adjusting Screws for SG 1 in Level Service (Figures 12 & 19 to 21)
Two screws (114) are located in holes on the side of the case, closed by two plugs 1/8 NPT (115). They are positioned at factory assembly using the step following specific gravity meter calibration, (refer to Section 5.3.2.1). They can be adjusted at the time of calibration.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

25

These adjusting screws allow the user on site : For level interface service : To calibrate the instrument, with or without liquid, (see Section 5.3.4.2.2, b.). For liquid level service : To simulate, without liquid, a change in level of a specific gravity 1 liquid. In this last case, proceed as follows : Caution : This procedure is only possible if the [SGMETER] function has been calibrated. Refer to Section 5.3.1. To adjust stops, put the instrument into the preceding calibrated specific gravity meter function [SGMETER] (Refer to APPENDIX D). Open the access plug (107) to look at the simulation mechanism. Remove the 3/4 NPT plug (190) located at the bottom of instrument. Through the 3/ 4 NPT opening, use your finger to move the flexure (59) in the direction of the torque tube until it seats on the smooth end of the screws (114). While maintaining pressure, slide the flexure to the right or the left until it stops against the screw shoulder. See Figure 12. Relative to the instrument axis, adjust the screw on displacer side to simulate a high level of S.G. 1 liquid (REF H). Use the screw on the side opposite to the displacer to simulate a low level (REF L) (displacer chamber empty).

6.3 Removing a Torque Tube with assembled DLT Case (see Figure 17)

a. Switch off power supply. b. For instruments with a displacer chamber, close isolation valves, and purge the chamber. c. Remove upper flange (146) and blind flange (144). d. Lower the torque arm (135) and unhook the displacer (130). A hook-shaped 3 mm steel wire will facilitate unhooking and holding of the displacer. The wire may be inserted through the clevis hole. e. Remove the two torque arm screws (133) and remove the torque arm (135) from the chamber. f. Remove displacer from its chamber (131) or tank. g. Be sure that requirements for instruments installed in explosive areas are strictly followed. Remove screw (106) from connection compartment and unscrew cover (104). Disconnect supply electrical wires and other equipment from terminals (90). h. Remove nuts (142) holding the torque tube subassembly and slide the subassembly out of the mechanism chamber.

In practice, proceed as follows : a. Simulate low level (REF L) : In the workshop, attach to the displacer arm a weight equal to actual displacer. On site, the displacer chamber should be empty. b. Remove plugs (115) using a 5 mm hex wrench. c. Using the push buttons, enter the DIAGNOSTIC Menu and move to the specific gravity meter function [SGMETER]. Validate by D. The LCD display a value around [ 0.000]. d. With your finger, move the flexure (59) until it seats on the shoulder of the screw opposite to the displacer. Adjust screw (114) until LCD displays a value as close as possible to [ 0.000]. e. Move the flexure (59) until it contacts the shoulder of the displacer side screw. Adjust screw until LCD displays a value as close as possible to [ 1.000]. f. Quit the DIAGNOSTIC Menu and return to NORMAL Operation. g. Release the flexure. h. Reassemble the plugs (115-107-190).
PARTS REFERENCE
130. Displacer 131. Displacer Chamber 132. Internal Knife Edge Block 133. Torque Arm Screw 134. Torque Arm Block 135. Torque Arm 137. Torque Tube Housing Assembly 142. Stud Nut 143. Gasket 144. Blind Flange 145. Stud 146. Top Flange 147. Top Flange Stud 148. Top Flange Stud Nut 149. Top Flange Gasket

Figure 17

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

26

6.4 Installing a Torque Tube with assembled DLT Case (Figure 18)
CAUTION : The following method is valid only if the coupling between beam and torque rod has already been adjusted for the required mounting direction. (See Section 6.2.3). The case mounting direction for which the coupling has been made may be identified as follows : When the case is mounted and coupled to the torque tube (without torque arm or displacer), the tip of the conical pin (53) is aligned with one side of the oval hole in the flexure (59) : Left mounting : see Figure 18 a. Right mounting : see Figure 18 b. For installation, reverse the procedure outlined for removing a DLT case and torque tube subassembly (Section 6.3). It is recommended that new gaskets (143 - 149) be used when installation is performed, (refer to Figure 17).

calibrated for the specific application required by the customer. In such a case, however, it is recommended that you check the adjustments of the specific gravity meter function, adjusting screws, and the calibration, before returning the instrument to normal service.

6.5 Reversing Instrument Case Mounting Relative to Displacer Position (Left or Right) (Figures 17, 19 to 21)
a. Follow instructions in Section 6.3 Removing a DLT case and torque tube sub-assembly. b. Install the case/torque tube subassembly on the opposite side of mechanism chamber in place of flange (144) and open the cover (107) of the mechanism compartment. It is recommended that you install a new gasket (143) when reassembling. c. Using a 2,5 mm hex wrench, loosen the screw (62) of beam (54) to uncouple it from the torque rod. d. Replace the displacer in the chamber (131) or in the tank and hold it temporarily with a 3 mm steel hook. e. Insert torque arm (135) in mechanism chamber and assemble it to plate (134) with two screws (133). f. Lower the free end of the torque arm (135) and hook the displacer (130). Reassemble the top flange (146) and blind flange (144) using new gaskets (149 & 143).

NOTE : If the coupling does not match the mounting direction, verify that the screw (62) is loose and pin (72) is free to rotate in the coupling end of the beam (54) before hooking the displacer on the torque arm (135). Continue by performing operations g to i in Section 6.5, unless the instrument is already prepared and

Figure 18 Identifying the Coupling Between the Beam (54) and Torque rod (138) as a Function of Case Mounting Direction Relative to Displacer Position

27

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

g. Remove the front plate (80) located in front of the instrument to gain access to the push buttons (27). h. Enter the CONFIGURATION Menu and select the required configuration data corresponding to the new instrument position (refer to Section 5.1.4.4 and APPENDIX B). i. Perform the coupling adjustment according to Section 6.2.4. If necessary, calibrate the specific gravity meter function and set adjusting screws per Sections 5.3.2.1 and 6.2.5. Proceed with calibration following Sections 5.2, 5.3.3 or 5.3.4.

b. Connect the sensor connector (40) and connector (7) at the back of amplifier (200). Take care to correct position by means of the locking lugs. (above for the (40) connector and below for the (7) one). Refer to Figures 19 and 21. c. Insert the amplifier (200) with four screws (201) inserted into the front of the case with the LCD facing the top. d. Progressively and alternately insert the four screws (201) while pushing the amplifier against the bottom of the case. Tighten the four screws. e. Close the main cover (20) and tighten safety screw (110). Switch on the power supply. f. Configure the transmitter for the required service characteristics. Refer to Section 5.1.4.4. g. Calibrate the specific gravity meter function and perform calibration. Refer to proper Sections 6.2.5 & 5.2 or 5.3.). Return to NORMAL Operating Mode.

NOTE : The specific gravity meter function and the adjusting screws are features of the transmitter. They permit a user to perform simulations that facilitate calibration in situations such as a no liquid low level when special interface displacers are used and for calibration with or without liquid in case of a level interface using a standard displacer. If such conditions are not present, however, these adjustments are optional.

6.6 Replacing the Amplifier and/or the Sensor


6.6.1 Removing (Figures 10, 19 & 21)
a. Switch off power supply. Partially unscrew safety screw (110) from main cover (20) so that it disengages from the case. Remove main cover (20). b. Progressively and alternatively loosen the four screws (201) to remove the amplifier (200). c. Disconnect the sensor connector (40) and connector (7) from the back of amplifier (200). d. If the sensor shall be removed, unscrew the two screws (112) and remove the sensor (40) and its O-ring (111). CAUTION : Do not pull on the sensor wires to remove the sensor from the case. Be careful not to damage the sensor or mechanism subassembly during this operation.

6.7 Replacing the Mechanism Subassembly (50), (Figures 20 & 21)


CAUTION : Parts which constitute the mechanism subassembly (50), including elements (51 to 62) are assembled at the factory using high precision tools that guarantee highly accurate positioning, which is required to achieve specified performance. They should never been disassembled unless a malfunction occurs. The whole sub-assembly must then be replaced or returned to the factory for rebuild.

6.7.1 Removing
a. Switch off power supply. Unscrew safety screw (106) enough to disengage it from case. Remove cover (104) of the connection compartment. Disconnect supply wires from terminals (90). b. Remove cover (107) of mechanism compartment. Using a 2.5 mm hex wrench, loosen screw (62) on beam (54) to uncouple it from the transmission rod. c. While holding the case to prevent it from falling, loosen the four screws (121) with a 5 mm hex wrench and remove them and the associated washers (122). Remove the case by pulling it along the axis of the torque tube, using care to prevent any deformation of the coupling flexure (70).

6.6.2 Installing (See Figures 10, 19 & 21)


a. If the sensor has been removed, slide the new sensor, equipped with new O-ring (111), into the case while observing the following : Orient the blue point toward the center of the case (another blue mark on the back of the case helps to verify correct position of the sensor). Do not turn the sensor while sliding into the case. Maintain horizontal alignment of both holes, especially at the end of the insertion procedure. Insert and tighten the two screws (112).

NOTE : Do not remove flange (116) from torque rod (138) nor the coupling flexure subassembly (70).
d. Using a 3 mm hex wrench, remove the two screws (113) that fasten the mechanism subassembly to the case.

28

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Figure 19 Type 12300 Transmitter External View of Case, Cover and Amplifier Removed

Type 12300 Transmitter Cross Section View From Back

Figure 20

Type 12300 Transmitter Front View

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

29

Figure 21 Cross Section of Type 12300 Electronic Level Transmitter

PARTS REFERENCE
Ref. Qty No 1 2 t 3 7 8 9 20 21 22 23 q 24 25 26 27 40 50 51 52 53 54 55 56 57 58 59 60 Parts Name Ref. Qty No Parts Name Ref. Qty No
q 108 q 109

Parts Name O-Ring (Access Plug) O-Ring (Main Cover) Safety Screw (Main Cover) O-Ring (Sensor) Screw (Fast.ng of sensor) Screw (Fast.ng of Mechan. S/A) Adjusting Screw 1/8 NPT Plug (Adjusting Screw) Coupling Flange Flexure Flange Screw (Fastening of Coupling Flexure/Flange) Screw (Fast.ng of Coupling Fl. on Torque T Transm. Rod) O-Ring (Case S/A on T. Tube) Screw (Fast.ng of Case S/A on T T.) Lockwasher Drive Screw Specifications Plate Screw (Front Plate/Main Cover) O-Ring (Screw 125) 3/4 NPT Plug S/A (incl. 191 & 192) 3/4NPT Plug Spongy Gasket Type 300 Circuit Board S/A Screw

1 Case S/A (incl. 2 to 9) 1 Case 2 Radio Frequency Filter 1 Connecting Plug 1 Isolated Red Wire 1 Isolated Black Wire 1 Main Cover S/A (incl. 21 to 27) 1 Main Cover 1 Window 1 Truarc Ring 1 O-Ring (Front Plate) 3 Button Spring 3 Button Axis 3 Button 1 Sensor S/A 1 Mechanism S/A (incl. 51 to 62) 1 Pivot 1 Drive Pin 1 Conical Pin 1 Beam 2 Magnet 2 U Flexure 4 Flange (Flexure) 8 Screw (Fastening of Flexure) 1 Adjusting Flexure 1 Screw (Fast.ng of Adj.ng Flexure)

61 1 Washer 62 1 Adjusting Screw 70 1 Coupling Flexure S/A (incl. 71 to 73) 71 1 Coupling Flexure 72 1 Pin 73 1 Coupling Flexure Washer 80 1 Front Plate S/A 90 1 Terminal Board 90A 1 Flat Handle Terminal Block 90B 1 Terminal Board Connector 92 2 Screw (Term. Board Fastening) 93 2 Washer (Term. Board Fastening) 94 2 Lockwasher (Term. Board Fast.ng) 95 1 Washer 96 1 Clamp 97 1 Screw (Clamp) 98 1 Lockwasher 99 1 Washer 100 1 Clamp 101 1 Screw (Clamp) 102 1 Washer 103 1 Caplug (Only for Shipment) 104 1 Connection Compartment Cover q 105 1 O-Ring (Connection Compart.nt) 106 1 Screw (Connection Compartment) 107 1 Access Plug

110
q 111

112 113 114 115 116 117 118

1 1 1 1 2 2 2 2 1 1 2

119 2
q 120

121 122 123 124 125 q 126 q 190 191 192 200 201

1 4 4 4 1 3 3 1 1 1 1 4

t Not Shown

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

30

q Recommended Spare Parts Bold Type : No Dissociable Sub-assembly

NOTE : After removing the two screws (113), dismounting the mechanism subassembly will be facilitated by using a M5 threaded rod with about four threads engaged in pivot (51) in place of right screw (113). The same threaded rod will also be useful during reassembly. (See Figures 20 & 21).

c. Place a new gasket (120) on the torque tube flange. Verify that screw (62) of the coupling part of beam (54) is loose. d. Continue the procedure by performing steps f to j of Section 6.2.1. Mounting a DLT case on a torque tube. e. Adjust coupling (Refer to proper Section 6.2.3 or 6.2.4). f. Calibrate the specific gravity meter function, (Refer to Section 5.3.2.1). Set adjusting screws, (Refer to Section 6.2.5). g. Recalibrate the instrument, (Refer to proper Section 5.2, 5.3.3 or 5.3.4)

6.7.2 Installing
a. Install the new mechanism subassembly by engaging the two pins (52 & 53) in the case holes. b. Assemble the two screws (113) and tighten them progressively and alternately. Be sure that pivot (51) perfectly contacts the back surface of the case so that the beam (54) will move in a plane strictly parallel to this surface.

7. trouble shooting
7.1 No Signal :
Check connection wires to transmitter. Check polarities. Verify the correct position of the connectors (7) and (40) on the amplifier, (refer to Figures 19 & 21). the milliammeter on the two pins located on each side of the switch, To recalibrate the internal milliammeter, move to sub-menu [4 20 MA] via [CALIBR ] in the CALIBRATION Menu. Refer to APPENDIX C, Move to [4 MA] then display [D + ] by D . Decrease or increase value (ranges from 2900 to 3500 increment 1) until the reference milliammeter indicates 4.000 mA. Push D again to return to [4 MA], Move to [20 MA] then display [ D + ] by D . Decrease or increase value (ranges from 2000 to 3500 increment 1) until the reference milliammeter indicates 20.000 mA. Push D again to return to [20 MA], Move to [MA GENE] to generate different output current to verify the current loop regarding the reference milliammeter, Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens, then return to the [4 20 mA], When the setting is completed, move into the menu until [<MANU] is displayed, then press D to exit the CALIBRATION Menu and to display [MANUAL], Press D , , D : [NORMAL] appears for a few seconds and the instrument automatically returns to Normal Operating display, Before disconnecting the milliammeter put the switch back on the position identified by v. See Figure 19.
#### ####

7.2 No Display but Signal Exists :


Replace the amplifier.

7.3 Signal is Steady, No Change When Level Varies:


In case of an external maounting (see 3.2.1), check that the immobilization of the displacer in the displacer chamber (for transportation purpose), has been removed. Verify that the instrument is not in FAILSAFE Mode. If not, verify that the instrument display the Normal Operating screen [the instrument displays alternatively the loop current and the level expressed in the unit (% or engineering unit)], Verify coupling between transmission rod mechanism subassembly by moving flexure (59), which allows you to simulate a level change, Move to [SNR TST] in the DIAGNOSTIC Menu to verify Hall effect sensor. Refer to APPENDIX D.

7.4 If current output is not the same that current displayed :


DANGER : Full compliance with standards requirements for instruments installed in hazardous areas must be insured.
Verify the current loop is in accordance with 4.4.3. That is to say the voltage on the HDLT terminal board must be equal or greater than 9,5V. Insert a reference milliammeter in series with the power supply or connect it to the electronic board provided into the connection compartment, Put the switch on the TEST position. Connect

7.5 No HART communication :


DANGER : Full compliance with standards requirements for instruments installed in hazardous areas must be insured.
Verify the current loop is in accordance with 4.4.3. That is to say the voltage on the HDLT terminal board must be equal or greater than 9,5V.

31

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Verify the Hart communication has been enable in the CONFIGURE MENU - See APPENDIX A [-> INFO] or APPENDIX B [CONFIG].

Check that the torque arm is horizontal without displacer. Recalibrate the transmitter. If the problem remains, contact our After-Sales department.

7.6 The current output doesnt match with the fluid level (linearity issue) :
Check the calibration parameters. For a standard displacer (1362 g), when using the function coupling [COUPLING] in the calibration menu, for the zero (lower level), the given value shall be greater than -37% for a left hand mounting or lower than 37% for a right hand mounting.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

32

APPENDIX A

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

NORMAL MODE, MANUAL MODE, FAILSAFE MODE AND INFORMATION MENU SCREENS DESCRIPTION

APPENDIX A

COLD RESTART WARM RESTART

Fugitive display appearing when the instrument is powered on after a long power cut. Fugitive display appearing when the instrument is powered on after a micro power cut. Display the value of the level or interface plan in the unit indicated in low left corner. Display the value of the output current in mA.

LIMITS

Set if : specific gravity of calibration or service is below .01 for level transmitter or difference of specific gravities of calibration or service is below .01 for interface transmitter. Set if : displacer characteristics specified in the transmitter data base are not adapted regarding specific gravity of calibration or specific gravity used. Transmitter / Sgmeter calibration impossible regarding tests : Tank empty or full left or right mounting. Mounting configuration (left or right) conflicts ZERO and SPAN transmitter calibration : Recoupling torque tube is necessary or recalibrate. Set if : Level range ([LEVEL H] [LEVEL L]) expressed in engineering unit (length) is greater than the displacer height entered in the instrument data base. Instrument configured for interface and the Low Specific Gravity of Service [LSG SER] is set to a value smaller than Low Specific Gravity of Calibration [LSG CAL].

CALIBRATION MOUNTING DISPLACER

NORMAL MANUAL MANUAL CONFIGURATION CALIBRATION DIAGNOSTIC INFORMATION CONFIGURATION CALIBRATION DIAGNOSTIC FAULT CLEAR FAULT FAILSAFE

In NORMAL MODE the screen displays in sequence the value of the level and of the output current. Validate by D to return to [NORMAL ]. Validate by D to go to MANUAL MODE Menu. Validate by D//+ to enter sub-menu [>CONFG ], [>CALIB ], [>DIAGN ] and exit by [>NORM ]. Validate by D to go to CONFIGURATION Menu. Validate by D to go to CALIBRATION Menu. Validate by D to go to DIAGNOSTIC Menu. Validate by D to read the various informations stored in the memory of the instrument. Validate by D to read the actual configuration data. Validate by D to read the actual calibration data. Validate by D to read the actual diagnostic data. Validate by D to read the possible fault(s) which may have occured since the last CLEAR FAULT was performed. Validate by D to read informations on the cleared faults. Displayed when instrument has gone to Failsafe mode ; this may occur when : The alarm(s) have been set on and the level is higher than [ALRMH ] or lower than [ALRML ]. The Hall effect sensor is disconnected. The current loop is frozen to : - The last value before going to FAILSAFE if [FAIL O] was selected in CONFIGURATION Menu. - The value set if [FAIL I] was configured.

TEMPERATURE HARDWARE SOFTWARE HALL CLEAR FAULT SUCCESS RESET STANDARD

Temperature sensor on electronic board out of service or board temperature out of normal range (< 50 C or > 100 C). Voltage reference out of normal range or E2 PROM write procedure failed. No refreshed data from the A/D converter or watch dog set : Software in closed loop or bad main logic initialization. Sensor disconnected or sensor fault (set during [SNR TST] in DIAGNOSTIC Menu) or Hall output out of electronic board input or Hall current incorrect. Validate by D to perform CLEAR FAULT procedure. Indicates that procedure has been correctly executed. Validate by D to return instrument to factory settings : CONFIGURATION
100.0

CALIBRATION
0.0 1.000

DIAGNOSTIC FILLING
0.0 4.0

LEVEL LEFT DIRECT CTRL


3.600

ALRMH
1.0

0 1

DAMPING
4.000

SG CAL
1.000

FILLING
0.0

W L DZ W

INTG
0.61

TIME
1.0

MA L
20.000

SG SER
1.000

TIME
0.0

INTG
0.1

TIME 0 0 ENGLISH

MA H
0.0

SGM CAL L
0.0

TIME
0.0

H W

VAL

LEVEL
100.

TIME LSG CAL


1.0

FAIL
0.0

LEVEL 0/0
0.00

ALRML

HSG CAL
0.0

Display the loop current value during FAILSAFE Mode. The current value is alternatively displayed with the message "FAILSAF"

ZERO SPAN

<>
0.00

LSG SER
1.0

><

HSG SER

AFTER A RESET STANDARD ALL PARAMETERS SHALL BE DONE AGAIN


FAULT NO FAULT FACTORY START HIGH ALARM LOW ALARM Set in CALIBRATION Menu if RESET STANDARD is performed and SPECIFIC GRAVITY METER has never been previously calibrated by the Factory. Set after every power on or HART reset command. Set after TIME 1 has elapsed with level (in engineering unit) > [H ALARM] 5%. Set if TIME 2 has elapsed. Set after TIME 1 has elapsed with level (in engineering unit) < [L ALARM] 5%. Set if TIME 2 has elapsed. YES NO Validate by D to know the fault which has induced going to FAILSAFE Mode. STORAGE Validate by D to start the storage procedure of the resetted to standard parameters in the instrument memory. Storage of standard configuration and calibration will be effective only after completion of next step. It is necessary to go through this step to return to Failsafe sub-menu. Validate by D (YES) to finalize the storing procedure of the resetted to standard parameters. Pushing + or (NO) will abort the storage ; the configuration and calibration parameters set previously will stay in the instrument memory. Validate by D to avoid running the Reset to Standard procedure.

ABORT

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX B

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX B Continuation

CONFIGURATION MENU SCREENS DESCRIPTION

CONFIGURATION LEVEL

Validate by D to enter the CONFIGURATION Menu. The instrument measures the level of a liquid in which the displacer is partially immersed. The transmitter is used to measure the interface level between 2 non miscible liquids of different specific gravities. The displacer must be always immersed. This item should be selected in accordance with the relative mounting positions of the displacer versus the instrument housing ; The standard mounting positions LEFT, also called Left hand mounting. Refer to Figure 7. Optionally, the mounting position may be RIGHT, also called Rigth hand mounting. Standard action is Direct ; an increase in level induces an increase of the loop current. Optionally, a Reverse action can be selected : The loop current decreases when the level increases.

TIME 1

Validate by D to enter SETVAL sub-menu. Set the time duration in seconds which will elapse between the moment the level goes higher than ALRMH value (or lower than ALRML) and the moment the Alarm information is set in FAULTS list. This function is disabled if [TIME 1] is a negative number. Can be set only if [ALRML I] or [ALRMH I] is configured. Value from 1 to 1000 seconds.

INTERFACE

TIME 2

LEFT

Validate by D to enter SETVAL sub-menu. Set the time duration in seconds which will elapse between the moment the level goes higher than ALRMH value (or lower than ALRML) and the moment the instrument goes in FAILSAFE mode. This function is disabled if [TIME 2] is a negative number. Can be set only if [ALRML I] or [ALRMH I] is configured. Value from 1 to 1000 seconds.

RIGHT

ENGLISH FRENCH

The symbols displayed on the screen will be in English language. The symbols displayed on the screen will be in French language. To enable the HART communication if previously disabled To disable the HART communication. In this case the alone command recognized by the HDLT will be command 0 (read basic transmitter information). If the Push-Buttons have been previously locked, be very careful to disable the Hart communication. Special warning are displayed and the user need to enter the Push-Buttons PASSWORD. On time the user disable the Hart communication and come back in NORMAL MODE, the only way to restore the HART communication will be through the PUSH-BUTTONS. So in the case the user wants both HART DISABLE and the Push-Buttons LOCKED, very high cautions must be taken to memorize the Push-Buttons PASSWORD. PASSWORD FORGOTTEN = HDLT IN UNRECOVERED SITUATION FOR THE USER. Validate by D to quit the CONFIGURATION Menu and return to [> CONFG] in Normal Mode menu.This is the only way to quit the CONFIGURATION Menu. Validate by D to start the storage procedure of the configuration parameters set above in the instrument memory. Storage of new configuration will be effective only after completion of next step. It is necessary to go through this step to quit the CONFIGURATION Menu. Validate by D (YES) to finalize the storing procedure of the new configuration. Pushing + or (NO) will abort the storage ; the configuration changes made previously will not become effectif and the old configuration will be kept in the instrument memory.

DIRECT

REVERSE

HART I HART 0

HART I HART 0

CONTROLLER OFF To disable the controller mode. CONTROLLER ON To enable the controller Mode. This function is only available if the custommer has ordered it. Validate by D to enter SETVAL menu and set the loop current value (from 3.6 mA to 23 mA) which will occur in case of failsafe mode but only if [FAIL I] is validated . Push D again to go out of SETVAL menu and to display [FAIL I], then push + to validate [FAIL I] and go to next step [ALRML O] in CONFIGURATION Menu. If [FAIL O] is kept in Configuration, the loop current when instrument goes to FAILSAFE mode will be frozen to the value just before [FAILSAF] is displayed. FAILSAFE IN Validate by pushing + to go to next step in CONFIGURATION MODE menu. If D is pushed, [FAIL O] is displayed. Validate by D to enter SETVAL menu and set the level (value expressed in the unit choosen in CALIBRATION Menu ; value from [LEVEL L] to [LEVEL H]) below which a Low Alarm will be set (only if [TIME 1] is > 0) and instrument will go to Failsafe (only if [TIME 2] is > 0 ). Push D again to go out of SETVAL menu and to display [ALRML I]. When displayed, push + to validate : The next step in configuration [ALRMH O] will appear. To skip setting the Low Alarm On, push D ; [ALRML O] is displayed. Validate by D to enter SETVAL menu and set the level (value expressed in the unit choosen in CALIBRATION Menu ; value from [LEVEL L] to [LEVEL H]) above which a High Alarm will be set (only if [TIME 1] is > 0) and instrument will go to Failsafe (only if [TIME 2] is > 0). Push D again to go out of SETVAL menu and to display [ALRMH I]. When displayed, push + to validate : The next step in configuration [TIME 1] will appear. To skip setting the High Alarm On, push D ; [ALRMH O] is displayed.

FAILSAFE OFF

to MANUAL

STORAGE

ALARM LOW OFF

YES NO

ALARM LOW IN

ALARM HIGH OFF

ALARM HIGH IN

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX C

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

CALIBRATION

MENU SCREENS

DESCRIPTION

APPENDIX C

CALIBRATION CALIBRATION ZERO SPAN SPECIFIC GRAVITY for CALIBRATION ZERO

Validate by D to enter CALIBRATION Menu. Validate by D to get to sub-menu for Specific Gravity of Calibration setting, Zero and Span calibration.

LEVEL HIGH

Validate by D to enter SETVAL menu and set the level expressed in industrial unit in correspondance with (REF H), (see Section 5.3.3.1). Always set at 100 if UNIT is %. Value ranges from value of [LEVEL L] to 9999.9. Validate by D to display a list of units (one unit at a time) to express the level value (push + to scroll through the list) ; may be % of REF range or heigth or volume of liquid in tank, etc Validate by D to enter SETVAL menu and set the zero of a reduced range (see Section 5.3.2.5 ). In case of an interface instrument, when the specific gravities of service [LSG SER] and [HSG SER] are different from those of calibration [LSG CAL] and [HSG CAL], [ZERO <>] will be automatically set to the value resulting from formula :

UNIT Validate by D to enter SETVAL menu and set the specific gravity of the liquid used during the calibration procedure. Settable value ranges from 0.001 to 10. When displayed, put (or simulate) displacer fully out of liquid. Wait till the displacer is stable before pushing D to let instrument know (REF L). (See Section 5.3.3.1). When displayed, put (or simulate) displacer fully immersed in liquid. Wait till the displacer is stable before pushing D to let instrument know (REF H) , (See Section 5.3.3.1); [ERROR] may be displayed if displacer is still in situation described previously ([ZERO]) while pushing D. Used in case of an Interface instrument. Validate by D to enter SETVAL and declare the Specific Gravity of the lighter liquid used for calibration. Settable values range from .001 to the value of [HSG CAL]. Used in case of an Interface instrument. Validate by D to enter SETVAL and declare the Specific Gravity of the heavier liquid used for calibration. Settable values range from the value of [LSG CAL] to 10.0. Enter that function to set the specific gravity of service in case it is different from the Specific Gravity of Calibration. Validate by D to enter SETVAL menu and set the Specific Gravity of the liquid of service if it is different from the Specific gravity of Calibration. Settable value ranges from 0.001 to 10. Used in case of an Interface instrument. Validate by D to enter SETVAL and set the Specific Gravity of the lighter liquid in service if it is different from [LSG CAL]. Settable values range from .001 to the value of [HSG SER] . Used in case of an Interface instrument. Validate by D to enter SETVAL menu and set the Specific Gravity of the heavier liquid in service if it is different from [HSG CAL]. Settable values range from [LSG SER] to 10.0. Validate by D to enter sub-menu to calibrate [DAMPING], [MA L], [MA H], [LEVEL L], [LEVEL H], [ UNIT] and ZERO and SPAN for reduced scale. First order filtering function which acts on the loop current ; Time set corresponds to response at 63 % assuming a level step change. Can be set between 0.1 s and 32 s. Validate by D to enter SETVAL menu. Validate by D to enter SETVAL menu and set the current corresponding to (REF L) (see Section 5.3.3.1). Allows to correct for best independant linearity. Value ranges from 3.8 mA to the value of [MA H] . Validate by D to enter SETVAL menu and set the current corresponding to (REF H), (see Section 5.3.3.1). Allows to correct for best independant linearity. Value ranges from value of [MA L] to 20.5 mA. Validate by D to enter SETVAL menu and set the level expressed in industrial unit in correspondance with (REF L), (see Section 5.3.3.1). Always set at 0 if UNIT is %. Value ranges from 0 to value of [LEVEL H] . Since [LEVEL L] must be always smaller than [LEVEL H], it may be necessary to set the value of [LEVEL H] before the one of [LEVEL L]. MANUAL STORAGE 4 MILLIAMP SPAN ZERO

SPAN

([LSG SER] [LSG CAL]) / ([HSG SER] [LSG SER]) Value ranges from 9999.9 % to 9999.9 % .
Validate by D to enter SETVAL menu and set the span of a reduced range (see Section 5.3.2.5). Value ranges from 0.0 % to 99 %. Validate by D to enter the sub-menu allowing to calibrate the internal ampmeter or force the loop current to a value set through function [MA GENE]. Allows to calibrate the internal current measurement. This re-calibration is normally not necessary and requires to put in serie with the instrument a very precise ampmeter. If nevertheless required, validate by D to display #### [D + ]. Decrease or increase value (ranges from 2900 to 3500 ; increment 1) until the reference ampmeter indicates 4.000 mA. Push D again to return to [4 MA]. Allows to calibrate the internal current measurement. This re-calibration is normally not necessary and requires to put in serie with the instrument a #### very precise ampmeter. Validate by D to display [D + ]. Decrease or increase value (ranges from 2000 to 3500 ; increment 1) until the reference ampmeter indicates 20.000 mA. Push D again to return to [ 20 MA]. Allows to set another instrument (such that positioner) in serie in the loop, to #.### ] and generating the required output current. Validate by D to display [MA the loop current to any value between 3.6 and 23.0 mA. Default value is 4.000 mA. Push D again to enter SETVAL menu and push D again to display #.### [MA ] and force the current to the displayed value. Push + or to return to [MA GENE]. The value set is not put in the instrument memory. SPECIFIC GRAVITY Validate by D to calibrate the Specific Gravity Meter Proceed with [CAL Z S] METER CALIBRATION sub-menu. Refer to Sections 5.3.1 & 5.3.2.1. COUPLING Only necessary on instrument head delivered alone. Function used while mechanically couple the sensor to the torque tube rod. Requires to simulate a displacer half immersed in a liquid of SG 1.4. The value read should be between 5 % and + 5 %. See Sections 6.2.3 & 6.2.4. Validate by D to return to [MANUAL] in Normal Mode menu. Starts the procedure to store the various calibration data into the memory of the instrument. Validate by D to finalize the storing procedure or push + (or ) to abort and keep the previous data. In both case, the instrument remains in the CALIBRATION Menu.

LOW SPECIFIC menu GRAVITY of CALIBRATION HIGH SPECIFIC menu GRAVITY of CALIBRATION CHANGE SPECIFIC GRAVITY SPECIFIC GRAVITY of SERVICE

4 20 MA

20 MILLIAMP

LOW SPECIFIC menu GRAVITY of SERVICE HIGH SPECIFIC GRAVITY of SERVICE VARIABLES SETTINGS DAMPING

MILLIAMP GENERATOR set

MILLIAMP LOW

MILLIAMP HIGH

LEVEL LOW

YES NO

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX D

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX D Continuation

DIAGNOSTIC

MENU SCREENS

DESCRIPTION

DIAGNOSTIC READ COUNTER FILLING

Validate by D or + or to access to the diagnostic sub-menu. Validate by D to access to the accumulated data sub-menu.

SMART FILTERING AUTOMATIC SUCCESS

Validate by D to proceed to automatic smart filtering parameters setting. Target is to bring influence of noise and waves below 0.3 % of range. Indicates that automatic smart filtering parameters [S - FTR A] procedure has been correctly achieved. Displayed when the automatic TUNE failed. Validate by D to display the value of Specific Gravity of the liquid when the displacer is fully immersed: the Specific Gravity Meter must have been previously calibrated. If not, the case [ERROR] will be displayed. Display the value of the liquid specific gravity. This value is valid only if the displacer is fully immersed in the liquid . If the Specific gravity Meter has not been calibrated, the screen [ERROR] is displayed : this is the only to know if the Specific Gravity Meter has been previously calibrated. In both case, push D to return to main DIAGNOSTIC Menu. Displayed when the Specific Gravity Meter has not been calibrated. Validate by D to read the list (if any) of defaults which occured in the operating system ; this info is stored in RAM and thus lost when instrument is switched off.

Totalizes the amount of liquid entering the tank. Counter increments by 1 when accumulated positive change in level correspond to one height of displacer. ERROR Time (days) during which the instrument worked within 5 % of low level that is between 5% and + 5% of calibrated value. Time (days) during which the instrument worked within 5 % of high level that is between 95 % and 105 % of calibrated value. SPECIFIC GRAVITY METER

TIME - LOW DAY

SPECIFIC GRAVITY METER

TIME - HIGH DAY

TIME WORKING DAY Time (days) during which the instrument has been on service. DEGREE CELSIUS RESET COUNTER Instantaneous temperature ( Celsius) inside housing (printed board). Validate by D to display [YES NO]. Push D again to confirm <Reset counter> procedure or + (or ) to keep the diagnostic data in memory. Push D to finalize Storage or + (or ) to abort the Storage procedure and keep the previous values. Validate by D to perform a test of the Hall effect sensor. The level of liquid shall remain constant during the test. Indicates that result of Hall sensor test is correct. Indicates the instrument is in Failsafe mode. If [FAIL O] was configured, loop current locks on the last value before [FAILSAF] is displayed. If [FAIL I] was configured, the loop current is the value entered through CONFIGURATION Menu. Validate by D to enter the sub-menu to set manually the smart filtering parameters. Smart filtering act on digitally converted sensor signal : it eliminates unwanted sensor signal oscillations ; it has no damping or delaying effect on fast level changes. Validate by D to enter SETVAL menu and set the window width in seconds : from 0.1 s to 32 s. Factory set value (generally suitable) : 4 s. Validate by D to enter SETVAL menu and set the integration dead band : from .01% to 10%. Factory set value (generally suitable) : 0.3 %. Validate by D to enter SETVAL menu and set the time after which a new value validated : from 0.1 s to 32 s. Factory set value (generally suitable) : 0.1 s. Validate by D to start the storage procedure : at this step it is still possible to keep the previous values ; see [YES NO] below. STORAGE Intermediate step of Storage procedure ; validate by D to reach next step [YES NO]. Push D to finalize Storage or + (or ) to abort the Storage procedure and keep the previous values.

ERROR FAULT HISTORY

YES NO

SENSOR TEST

NO ERROR MANUAL Validate by D to return to [MANUAL] in Normal Mode menu.

SUCCESS FAILSAFE

SMART FILTERING MANUAL

WINDOW of INTEGRATION DEAD ZONE of INTEGRATION WINDOW is VALIDATION

YES NO

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

APPENDIX E
The purpose of this Section is to facilitate the first calibration and running in case of a level application of the instrument.
Danger : If area cannot be verified as safe, do not remove any covers.

FIRST OPERATING AND SIMPLE CALIBRATION FOR A LEVEL INSTRUMENT SERVICE


To quit the CONFIGURATION Menu and return to Normal Operating mode, move into the menu until [<MANU] is displayed, then press D to display [MANUAL], via [STORAGE ] and [YES NO]. Then press D, , D : [NORMAL] appears for a few seconds and the instrument automatically returns to Normal Operating displaying alternatively the current and the level. Now, proceed as indicated under Calibration : 6. Display [SPAN ] and press D to take account the REF H, 7. Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [CAL Z S] is displayed, 8. Display successively [MA L], [MA H], [LEVEL L], [LEVEL H] and, if needed, set the currents and levels corresponding to REF L and REF H, 9. Display [UNIT ] and define the unit for level indication, 10.Move until [< ] is displayed and press D to store data via [STORAGE] and [YES NO] screens. [VAR SET] is displayed, 11. When the calibration is completed, move into the menu until [<MANU] is displayed, then press D to exit the CALIBRATION Menu and to display [MANUAL], 12.Press D , , D : [NORMAL] appears for a few seconds and the instrument automatically returns to Normal Operating display, 13.Reinstall the front plate (80) with the three screws (125).

Conditions to Calibration on Site in a Liquid


The effective change in level will be obtained by emptying and filling of the displacer chamber with a liquid. Wait that the displacer is stabilized to validate the values displayed after each change in liquid level. Take actions necessary to allow a change in the liquid level in the chamber : open/close isolation valves, vent, purge, etc. Now, proceed as indicated under Calibration :

Before installation, connection and start to running, carefully read Section 2. Protection Standard and Section 3. Installation. For explanations to general principles, the liquid crystal display, the push buttons and how to use the menus, refer to Sections 5.1 and 5.1.1 to 5.1.3. For the menus description, refer to Section 5.1.4. To perform the instrument calibration proceed as follows : After the 12300 Level Transmitter has been installed, remove the front plate (80) located in front of the instrument to gain access to the push buttons. In NORMAL MODE (refer to APPENDIX A), the instrument displays alternatively the loop current and the level expressed in the unit (% or engineering unit) shown in the low left corner of the screen. Stroking any of the button enters a sub-menu which allows to go to a MANUAL MODE where the instrument can be configured, calibrated and diagnosed :

CALIBRATION (Appendix C)
Conditions to Dry Calibration in Workshop (Simulation by Weights)
Caution : When performing a calibration, use the following parameter units wherever they apply : Parameter Name S.I Units English Units Displacer Weight g lbm in3 Displacer Volume cm3 Water Density (WD) 1 g/cm3 0.036 lbm/in3
The effective change in level will be simulated by a set of weights corresponding to : a) The weight of the actual displacer at low level (REF L), which allows you to calibrate the zero and obtain the minimum value [ 0,0%] of the signal (direct action). b) The apparent displacer weight when the level is high (REF H). This allows you to calibrate the span and obtain the maximum value [100,0%] of the signal (direct action). The corresponding weight is calculated as :
Apparent Displacer Weight = Displacer Actual Weight (Displacer Actual Volume x S.G.x WD)

Calibration
1. Attach a set of weights to the torque arm to simulate a low level or empty the displacer chamber. Switch on the power, 2. Enter the CALIBRATION Menu and press in sequence : D (or + or ), +, D, D, +, D, to display [CALIBR], 3. Set the Specific Gravity value of the liquid used for calibration [SG CAL]. Refer to Section 5.1.4.8 for the SETVAL sub-menu, 4. Display [ZERO ] and press D to take account the REF L, NOTE : During the procedure, refer to Section 5.3.2.6 if the LCD displays [ERROR]. 5. Attach a set of weights to the torque arm to simulate a high level or fill the displacer chamber until the high level is reached,

NOTE : In the CONFIGURATION AND CALIBRATION menus of APPENDIX B & C, the screens which are only necessary for the first operation and simple calibration are highlighted by means of the white text on a colored background.

NOTE : The calibration specific gravity [SG CAL] is automatically stored in the service specific gravity function [SG SER]. If the instrument is to be used with a liquid of different specific gravity, reenter the CALIBRATION Menu to set and accept this new value in [SG SER] to avoid the recalibration. (See Section 5.3.2.3).

CONFIGURATION (Appendix B)
To enter the CONFIGURATION Menu from the Normal operating mode, press in sequence : D (or + or ), +, D, D, D, to display [CONFIG]. Select all required configuration data indicated bellows : the instrument function (level or interface), the direction of head mounting (left or right towards the displacer when facing the LCD window), the action (direct :current increases with level ; reverse : current decreases when level increases), the language of the display (english or french).

Caution : Special displacer may be provided for specific applications (material, service conditions). In this case, volume and/or weight will differ from standard displacer characteristics. Actual volume and weight of the displacer can be read using HART function only if they have been previously stored in the DLT head. Otherwise, actual volume of the displacer is marked on the specification plate (124). Weight the displacer to get the actual weight.

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

SPECIFIC MODES
This annex describes two specific operating modes. 1 Push button locking.
In MANUAL MODE, the use of push button can be locked by sending a specific HART message with the 275 communicator (loaded with the relevant DDL). This locking prevents any change in the menus CONFIGURATION, CALIBRATION and DIAGNOSTIC. However, the MANUAL MODE can be unlocked when using the password stored in the HDLT during the 275 communicator locking operation. Th MANUAL MODE is automatically locked again when the user go back to NORMAL MODE. The MANUAL MODE unlocking through the push buttons is then temporary. The sketch below indicates how unlocking the MANUAL MODE with the pasword:

APPENDIX F
Remarks :
- The controller set point can be modified even if the push buttons are locked. - The loop current doesn't indicate the liquid level but the controller output (which is the valve position set point). - The controller set point is always displayed by the LCD in level unit. - If the set point and level units are different, the ratio control is activated and you have to calculate and enter the good values of the Ratio gain and Ratio bias (see the 275 communicator instruction EU 3500 HC E). A bad set point display is then avoided.

Controller mode.
When the CONTROLLER MODE is enabled in the CONFIGURATION menu:[CTRL I]; the NORMAL MODE menu is displayed differently. Three data are displayed alternatively: the liquid level, the loop current and the controller set point. The following sketch indicates how to modify the controller setpoint:

Instruction No EU 3500 E 04/2000 12 300 Series Level Transmitter/ Controller

Instruction No EU 3500 HC E 04/2000

HDLT 12300 HART COMMUNICATION

1 / 45

HDLT COMMUNICATOR

This guide describes the device specific instructions for using the HART 275 Hand Held Communicator with the Masoneilan HDLT 12300 software revision 4.12 and 5.11 and HART Device Description Language (DDL) revision 65640102.ddl embelled in the Communicator 275. The following pages covers basic instruction for using the communicator. Refer to HART Communicator manual MAN 4250 for more information. The menus structure is a guide to performing all of the operations which are possible from the Hand Held Communicator to configure, calibrate and diagnose the HDLT 12300 serie.

TABLE of CONTENTS
Hart Communicator 275 using........................................................ 3 Hart Communicator 275 connections ............................................ 5 Hart Communicator 275 starting .................................................... 6 Hart Communicator 275 functions ................................................. 8 HOME MENU .................................................................................. 10 INFO MENU .................................................................................. 13 HDLT RESET .................................................................................. 18 CONFIG MENU TAG .......................................................................... 20 SETUP ...................................................................... 22 ALARMS................................................................... 24 SET DATA BASE ..................................................... 26 CTRL PARAMETERS .............................................. 29 CALIBRATE MENU TOOLS ..................................................................... 32 CALIBRATION TRANSMITTER......................................... 34 S.G. METER.............................................. 36 PARAMETERS ......................................................... 38 DIAGNOSTIC MENU DIAGNOSTIC DATA................................................. 40 RESET CONTINUOUS............................................. 40 SENSOR TEST ........................................................ 40 SMART FILTERING ................................................. 40 SG METER ............................................................... 40 FAULT HISTORIC .................................................... 40 CONTROLLER MENU CONTROLLER VIEW............................................... 42 PID SETTING ........................................................... 42 SETPOINT ................................................................ 42 Principle of calibration .................................................................. 44 Trademark information.................................................................. 45

2 / 45

HDLT COMMUNICATOR

HART COMMUNICATOR USING


The table below is limited to basic information for using the HART Communicator with the HDLT 12300. See the HART ref MAN 4250 for more information.

Use this key to turn the Communicator ON or OFF. When the communicator is turned on, it searches for a HART compatible device in the 4-20mA loop.If nothing is found, the message displayed is : No device found.Press OK .

HDLT:TRS1 ** NORMAL MODE** 1 LEVEL 7.0 in 2 PERCENT 50.0 % 3 CURRENT 12.000 mA 4 TO MANUAL MODE 5 INFO HELP SAVE

UP ARROW KEY : Use this key to move the cursor up through a menu or a list of options.

DOWN ARROW KEY : Use this key to move the cursor down through a menu or a list of options.

LEFT ARROW AND PREVIOUS MENU KEY : Use this dual function key to move the cursor to the left or to come back to the previous menu.

RIGHT ARROW AND SELECT KEY : Use this dual function key to move the cursor to the right or to select brightness option.

HOT KEY : Use this key to quickly access important menu or options when the communicator is connected to the HDLT. If the communicator is OFF , pressing on this key turn ON the communicator and displays the INFO menu 5. See the MAN 4250 to customizing the HOT KEY MENU.

Four defined function keys marked F1 to F4 perform action in the different menus regarding the label appearing above these key. Below are some currently label diplayed. See MAN 4250 for all label information. F1 HELP EXIT YES RETRY ON OFF DEL PGUP ABORT HOME PGDN OK ENTER NO access the one line help for the function or the variable diplayed. to leave the current menu. to answer a question. to try to re-establish the HART communication. to select an option. to suppress an option. to delete current character during edition. to move up one help screen. to stop current task. to go to the top menu. to move down one help screen. to acknowledge information on the screen. to accept information on the screen and to display next screen. to answer a question.

3 / 45

HDLT COMMUNICATOR

ALPHANUMERIC AND SHIFT KEYS


These keys perform two functions : 1) the fast selection of menu options : from any menu, you can select option in two ways: use arrow keys previously described or use the fast select feature pressing the corresponding menu number on the keypad . 2) the data entry : to enter new alphanumeric information : The bold characters in the center of the keys are for numbers For example : to enter the letter M press the following key between 0 and 9 plus two symbols . and - .To enter sequence : some letters or others symbols, first press and release the corresponding shift key then press the alphanumeric key. then Press one of the three shift keys causes the corresponding ! arrow icon in the arrow icon to appear in the upper right corner of the display. right corner of the display For example : to enter the letter T press the following key sequence : then " arrow icon in the right corner of the display For example : to enter the letter E press the following key sequence : then # arrow icon in the right corner of the display Pressing the shift key again deactivates shift function.

LIQUID CRYSTAL DISPLAY:


Then connected to the HDLT, the top line of each on-line menu displays the model name of the device and its tag. The bottom line of each menu is reserved for label with its associated function and activated using key F1 to F4. Shift key left activated HART Communication

Low Battery

Up arrow key to display the previous line prcdente par appui sur Down arrow key to display the next line suivante par appui sur

Return to previous menu pressing :

Right key to select brightness option

4 / 45

HDLT COMMUNICATOR

HART COMMUNICATOR CONNECTIONS


WARNING : Before connecting the HART Communicator in an explosive atmosphere, make sure the devices in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices. For more information see the HART Communicator manual: MAN 4250. In addition for explosion proof or flame proof area, a connection on the site through the terminal board is absolutly forbidden.
The HART Communicator can be connected to the HDLT transmitter from different locations: in the control room, on the site through the terminal board on the HDLT head or any wiring termination in the loop. In any case , connect the HART Communicator in parallel with the instrument or a load resistor in the loop. The connection are not polarized. For the HART Communicator to function properly, a minimum of 110 ohms resistance must be present in the loop. See below the wiring connections for non explosive atmosphere.
HDLT 12300

RL >=250 + H + POWER SUPPLY -

FIGURE 1. HART Communicator connected on the HDLT or on the loop termination.

HDLT 12300

RL >=250 + H + POWER SUPPLY -

FIGURE 2. HART Communicator connected across a load resistor.

5 / 45

HDLT COMMUNICATOR

HART COMMUNICATOR STARTING


Switch ON the communicator by keying either ON/OFF or Hot key to access directly to menu INFO 6

1) If no event (fault) has occured since the last dialog between the communicator and the HDLT, the screen corresponding to the operating mode of the HDLT at the instant of connection is displayed : either the "NORMAL MODE" or "MANUAL MODE". 2) if any event has been recorded in the HDLT such as "reset occurred" or "sensor error"; following screen is displayed :
HDLT : Field device has more status available NEXT

Stroke F3 $ the screen below is displayed :


HDLT : Ignore next 50 occurences of status? YES NO

Stroke F1 It is strongly recommended to look at the faults which occured through procedure "1 read fault(s)" of menu INFO 6 and then clear the fault(s) : function "2 clear fault(s)" of menu INFO 6. If this action is skipped, the first message will be displayed again periodically. It will also reappear if any fault occurs during dialog between the communicator and the HDLT. 3) Accelerated procedure Starting from NORMAL MODE or MANUAL MODE. 3.1) To read the fault Push successively keys F6 - 1 to read the first status and then F4 to read the second status (if its exists) or come back to menu INFO. 3.2) To clear the status Stroke key F6-2 : after a few seconds, the screen below is displayed :
HDLT : Clear Fault(s) completed ABORT OK

Stroke key F4 to come back to menu INFO and then on key % to re-enter the original menu : NORMAL MODE or MANUAL MODE.

6 / 45

HDLT COMMUNICATOR

NOTES

7 / 45

HDLT COMMUNICATOR

HART COMMUNICATOR 275 - FUNCTIONS


COMMUNICATOR 275 FUNCTIONS Offline Online See communicator manual. Run the communication procedure between the HDLT transmitter and the communicator. If any fault(s) or event(s) have been recorded by the transmitter, the first message displayed is: Field device has more status available . See STARTING document to know the procedure. See communicator manual. See communicator manual.

Frequency Device Utility

8 / 45

HDLT COMMUNICATOR

COMMUNICATOR 275 - FUNCTIONS

HART Communicator
1 2 3 4 Offline Online Frequency Device Utility

Standard HHT function. In OFFLINE menu, the customer can configured and store in the HHT memory: tag descriptor message final assembly nbr date polling address

Standard HHT functions See HHT manual

HDLT :
Hot key menu : 1 INFO SAVE

9 / 45

HDLT COMMUNICATOR

HOME MENU
NORMAL MODE 1 level : 2 perc : 3 current : 4 TO MANUAL MODE 5 CONTROLLER MENU 6 INFO : 7 HDLT reset : indicate the actual level of liquid in % or in other engineering units indicate the percentage of current in the loop.This value is based on the low and high current values set . Output signal and current loop in mA. To go to MANUAL MODE If controller mode actived on the HDLT, this function allows to display controller parameters, to change the PID parameters and to modify the controller setpoint. Transmitter information: configuration, calibration, diagnostic data, data base, HART identification parameters , faults resume and clear faults. This function perform a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory.

OR
MANUAL MODE 1 level : 2 perc : 3 manual output: indicate the actual level of liquid in % or in other engineering units indicate the percentage of current in the loop.This value is based on the low and high current values set . To control in manual the controller output.The user can set a current loop in mA. The following information is displayed to inform the user of special state of the transmitter output: " Analog output 1 and its digital representation are in fixed mode and not responsive to input changes ". To display the MANUAL MODE MENU. If controller mode is actived on the HDLT, this function allows to display controller parameters, to change the PID parameters and to modify the controller setpoint. Transmitter information: configuration, calibration, diagnostic data, data base, HART identification parameters , faults resume and clear faults. This function perform a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory.

4 MANUAL MODE MENU 5 CONTROLLER MENU 6 INFO : 7 HDLT reset :

10 / 45

HDLT COMMUNICATOR

HOME MENU
HDLT : & **NORMAL MODE** 1 level n.n % 2 perc. 3 current n.n % nn.nnn mA HDLT : TO MANUAL MODE 1 MANUAL MODE--> 2 3 4 SAVE 5 6 7 HDLT : Going to MANUAL MODE do not refresh the current loop for some called functions ! Are your sure you want to go to MANUAL ? ABORT OK HOME 4 TO MANUAL MODE 5 CONTROLLER MENU 6 INFO 7 HDLT RESET HELP SAVE HDLT in NORMAL mode Note 1

&

Note 1: Access to items 2 - 3 - 4 are allowed only if the MANUAL MODE is valided. If it is not the case the following message is displayed: No valid items Press OK...

HDLT : MANUAL MODE MENU 1 NORMAL MODE --> 2 CONFIG MENU 3 CALIBRATE MENU 4 DIAGNOSTIC MENU 1 2 3

HDLT in MANUAL mode

SAVE HOME

HDLT : & **MANUAL MODE** 1 level n.n % 2 perc 3 manual output 4 MANUAL MODE MENU 5 CONTROLLER MENU 6 INFO 7 HDLT RESET 5 6 7 n.n %

HDLT : RETURN TO NORMAL MODE ? 1 NO 2 YES ABORT ENTER

HELP SAVE

11 / 45

HDLT COMMUNICATOR

12 / 45

HDLT COMMUNICATOR

INFO MENU

MENU 6
1 read fault(s) 2 clear fault(s) 3 read identifier Tag Read fault(s) recorded by the HDLT during any bad user configuration, calibration or hardware fault on the electronic module. To clear all fault(s) recorded by the HDLT during any bad user configuration, calibration or hardware fault on the electronic module. Tag- Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label : a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. Descriptor- Text that is associated with the Field Device installation. This text can be used by the user in any way. There is no specific recommended use. Message- Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. Final Assembly Number- Number that is used for identification purposes, and is associated with the overall Field Device. Date- Gregorian calendar date that is stored in the Field Device. This can be used by the user in any way. There is no specific recommended use.Enter MM/DD/YYYY. Polling Address- Adress used by the Host to identify a Field Device, and changeable by the User to control the Multidrop Mode. Manufacturer Identification Code- Rfrences a specific manufacturer, which is usually a company name, that is responsible for the manufacture of this Field Device. Model- Rfrences the type of field Device, usually an advertised mode number, that is unique to a singlemanufacturer. Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. Universal Command Revision- Revision of the Universal Device Description, that the Field Device conforms to. Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to. Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the Field Device. Hardware Revision- Revision that corresponds to the electronics hardware of the Field Device. Physical Signaling Code- the Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port. Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer. Number of Request Preambles- Number of Preambles required from the Host request by the Field Device.

Descriptor Message Final asmbly num Date Poll addr Manufacturer Model Device id Universal cmd rev Transmit cmd rev Software rev Hardware rev Physicl signl code Device flags Num resp preams

4 level config setup buttons alarms language

HDLT configuration information ( current acting, mounting ...) Lock level for push buttons to avoid unintended modifications. Status and limits for low/high level alarms and fail mode. Choice of different languages displayed on the HDLT LCD.

13 / 45

HDLT COMMUNICATOR
5 level calibration damping low signal high signal low level high level zero shift reduce span SG CAL SF SER

Output current filtering. Value expressed in second and corresponding to T63% for first order response step. Low output current for low level (direct acting) or low output current for high level (reverse acting). Must be between 3.8 mA and 14 mA. High output current for high level (direct acting) or high output current for low level (reverse acting). Must be between 8 mA and 20.5 mA. Value in engineering units for low level and corresponding to zero calibration. Value in engineering units for high level and corresponding to span calibration. Value in percentage of calibration scale (zero/span) to shift the ZERO in an other position. The current output is automatically re-ajusted on this new ZERO position. Value in percentage of calibration scale (zero/span) to reduce the SPAN . The current output is automatically re-ajusted to take into account this new SPAN. Specific gravity specified during the calibration procedure and corresponding to the liquid specific gravity in the chamber or the simulation by weight.This specific gravity is used only in LEVEL transmitter. This specific gravity is normally the same as the specific gravity of calibration but need to be change if the liquid specific gravity of the process is not the same as which one used during the transmitter calibration. This specific gravity is used only in LEVEL transmitter. Specific gravity specified during the calibration procedure and corresponding to the LOWER liquid specific gravity in the chamber or the simulation by weight.This specific gravity is used only in INTERFACE transmitter. Specific gravity specified during the calibration procedure and corresponding to the UPPER liquid specific gravity in the chamber or the simulation by weight.This specific gravity is used only in INTERFACE transmitter. This specific gravity is normally the same as the LOWER specific gravity of calibration but need to be change the LOWER liquid specific gravity of the process is not the same as which one used during the transmitter calibration. This specific gravity is used only in INTERFACE transmitter. This specific gravity is normally the same as the UPPER specific gravity of calibration but need to be change if the UPPER liquid specific gravity of the process is not the same as which one used during the transmitter calibration. This specific gravity is used only in INTERFACE transmitter. Specific gravity of calibration for the specific gravity meter. Temperature in Celcius for the elctronic head during the ZERO and SPAN calibration. Total number of filling tanks. Time in days for tank empty. Time in days for tank full . Time in days for HDLT working. Indicate the internal temperature inside the HDLT head. Value in liter or cubic inch Value in gr, kg, pound. Value in in or mm. Value in in or mm. special material , rod extension .... list of all configuration. Special design and material. Material used for the torque tube and the torque tube chamber. Mecanical parameter for the torque tube. arm lenght between the torque tube and the displacer in inches Torque tube extension for high or low process temperature and specification for use in dangerous area.

SG Lower CAL

SG Upper CAL

SG Lower SER

SG Upper SER

SGM SG CAL hall temp cal 6 diagnostic data nbr of filling up time tank empty time tank full time working head temperature 7 Data base displacer volume displacer weight displacer height displacer diameter displacer options chamber type chamber options torque tube force arm lenght general options

14 / 45

HDLT COMMUNICATOR

MENU 6
HDLT : INFO 1 read fault(s) * 2 clear fault(s) * 3 read identifier 4 level config 5 level calibration 6 diagnostic data 7 data base 8 controller config. 9 controller PID burst mode SAVE HOME

&

HDLT : level config 1 setup 2 buttons 3 alarms 4 language

&

xxxx

HELP SEND HOME

HDLT : & read identifier 1 Tag 2 Descriptor 3 Message 4 Final asmbly num 5 Date nn/nn/nn 6 poll addr 7 Manufacturer 8 Model HDLT 9 Device id nnnnn Universalcmd rev Transmit cmd rev n Software rev n Hardware rev n Physicl signl code Device flags Num resp preams n HELP SEND HOME

HDLT : & diagnostic data 1 nbr of filling up 2 time tank empty 3 time tank full 4 time working 5 head temperature HELP SAVE HOME

HDLT : level calibration 1 damping 2 low signal 3 high signal 4 low level 5 high level 6 zero shift 7 reduce span 8 SG CAL 9 SG SER SGM SG CAL hall temp cal

&
n.n s n.n mA n.n mA n.n unit n.n unit n.n % n.n % n.n ** n.n ** n.n n.n C

HELP SEND

HDLT : & data base 1 displacer volume 2 displacer weight 3 displacer height 4 displacer diameter 5 displacer options 6 chamber type 7 chamber options 8 torque tube 9 force arm lenght general options HELP SAVE HOME

*:
Read fault(s) means : Display events or faults that have occured since the last "Clear fault(s)". Clear fault(s) : Reset all fault(s).

** :
In Level : SG CAL SG SER IN Interface : SG Lower CAL SG Upper CAL SG Lower SER SG Upper SER n.nnn n.nnn n.nnn n.nnn n.nnn n.nnn

15 / 45

HDLT COMMUNICATOR

INFO MENU

MENU 6 BIS
8 controller config. Select Controller rate Dead zone Controller output Manu. reset bias Ratio gain HDLT controller configuration information : derivative action, alarm type, controller acting and ratio control . Controller rate to process the PID algorithm. The value must be between 0.2s and 10.0s. The controller don't change its current output if the difference between the setpoint and the process variable (level) is less than the Dead zone. The range is 0.0% to 20.0%. Limits the current output changes. Value expressed in % output / second. The maximum value is 500%/s . It is the controller output at a typical operating steady state.Use in P or PD process algorithm . Use if the process variable (level) and the setpoint are expressed in different engineering units or in different scales. This variable is used with RATIO BIAS in the following formula: SP in process variable units = Ratio gain * SP in its units + Ratio bias Use if the process variable (level) and the setpoint are expressed in different engineering units or in different scales. This variable is used with RATIO GAIN in the following formula: SP in process variable units = Ratio gain * SP in its units + Ratio bias Current controller setpoint. At power up , in case of micro-controller re-start or if HDLT RESET has been performed , this setpoint will be use by the controller. Setpoint low value corresponding to low level of liquid (Low level). Setpoint high value corresponding to low level of liquid (High level). Minimum value for the setpoint allowed by the controller. Maximum value for the setpoint allowed by the controller. Controller low alarm. Alarms can be absolute or deviation. This value is expressed in level engineering unit. Controller high alarm. Alarms can be absolute or deviation. This value is expressed in level engineering unit.

Ratio bias

Local SP Initial local SP Low SP value High SP value Low SP limit High SP limit Low alarm limit High alarm limit

9 controller PID P I D Kd Beta

Proportionnal gain. It is the ratio of proportionnal controller output to error. Value between 0 and 50. Integral time . Value between 0 and 1000 seconds. Derivative time . Value between 0 and 5000 milliseconds. Derivative gain to control the derivative action. Value between 0 and 100. Coefficient to change the proportionnal gain . The range is -9 to +9 . When Beta is 0 no action is done on P. When Beta =+9 , P is multiplied by 2 is error is greater than 20% and decrease to P value for error=0. When Beta =-9 , P is divised by 2 is error is greater than 20% and increase to P value for error=0.

10 burst mode

To activate BURST MODE and to select command 1, 2 or 3 or to desactivate BURST MODE. Burst mode allows more information per second on level of liquid , current in the loop in mA and in percentage.

16 / 45

HDLT COMMUNICATOR

MENU 6 BIS
HDLT : INFO 1 read fault(s) * 2 clear fault(s) * 3 read identifier 4 level config 5 level calibration 6 diagnostic data 7 data base 8 controller config. 9 controller PID burst mode SAVE HOME HDLT : & controller PID 1 P 2 I 3 D 4 Kd 5 Beta HELP SAVE HOME

&

HDLT : controller config. 1 Select 2 Controller rate 3 Dead zone 4 Controller output 5 Manu. reset bias 6 Ratio gain 7 Ratio bias 8 Local SP 9 Initial local SP Low SP value High SP value Low SP limit High SP limit Low alarm limit High alarm limit HELP SAVE HOME

&

HDLT : Command number : xxxxxx PV % range - current Process Vars-current HELP ABORT ENTER

HDLT : Burst mode control : xxxxx Off On ABORT ENTER

17 / 45

HDLT COMMUNICATOR

HDLT RESET
MENU 7 HDLT RESET This function performs a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory.

18 / 45

HDLT COMMUNICATOR

MENU 7

HDLT :
A reset may cause the current loop to change ! Perform RESET ???

ABORT

OK HDLT :
Reset on HDLT

Returns to previous menu without doing anything.

correctly executed

ABORT

OK

returns to previous menu.

19 / 45

HDLT COMMUNICATOR

CONFIG MENU - TAG


TAG MENU 1-1 1 tag Tag Change tag, descriptor, message etc... reported by the HDLT. Text that is associated with the field device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label : a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use. Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. Number that is used for identification purposes, and is associated with the overall Field Device. Gregorian calendar date that is stored in the Field Device. This date can be used by the user in any way. There is no specific recommended use. Enter MM/DD/YYYY. Adress used by the Host to identify a Field Device and changeable by the user to control the Multidrop Mode. Change transmitter configuration reported by the HDLT like mounting sense, current action, level or interface use, buttons level use. Level alarms definition and corresponding values in engineering unit. Failsafe validation and corresponding current loop. Time value before to set alarms or time to go to failsafe mode. Set HDLT data base concerning : chamber type, torque tube material, displacer size ... To change controller configuration.

Descriptor Message Final assembly number Date Polling address 2 setup 3 alarms 4 set data base 5 ctrl parameters

20 / 45

HDLT COMMUNICATOR

MENU 1-1
HDLT : CONFIG MENU 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters HELP SAVE HOME HDLT : tag xxxxxxxxx ######## HELP DEL ABORT ENTER

HDLT : descriptor xxxxxxxxxxxxxxxx ############# HELP DEL ABORT ENTER

Return without modification

HDLT : message xxxxxxxxxxxxxxxxxx ############### HELP DEL ABORT ENTER

HDLT : final assembly number nn ## HELP DEL ABORT ENTER

HDLT : date MM/DD/YYYY ##/ ##/ ## HELP ABORT ENTER HDLT : Record values ? Press : OK for ABORT for YES NO OK HDLT : polling address n ## HELP DEL ABORT ENTER

ABORT

21 / 45

HDLT COMMUNICATOR

CONFIG MENU - SETUP


SETUP MENU 1-2 1 tag 2 setup interface right reverse acting controller Display language Change tag, descriptor, message etc... reported by the HDLT. Change transmitter configuration reported by the HDLT : mounting sense, current action, level or interface use, buttons level use and controller activation. OFF = transmitter used in level indicator. ON = transmitter used in liquid interface indicator. OFF = left mounting. See instruction manual for more information . ON = right mounting. See instruction manual for more information . OFF = direct acting : an increase in level of liquid induces an increase of the loop current . ON = the loop current decreases when the level of liquid increases. OFF = controller not actived ON= controller actived. This is allowed only if the transmitter implement this function. Possibility of different languages displayed on the HDLT LCD. English : All screens are diplayed in English language. French : All screens are diplayed in French language. Define use level: OFF is no restriction. All menus are available. ON is limited use to INFO MENU in NORMAL MODE.

Buttons : lock level Password

If the buttons are in locked position, the user can unlock them entering a password. This password is a number between 1 to 255 with odd parity. This function is not available on firmware 4.12 embelled in the HDLT. Level alarms definition and corresponding values in engineering unit. Failsafe validation and corresponding current loop. Time value before to set alarms or time to go to failsafe mode. Set HDLT data base concerning : chamber type, torque tube material, displacer size ... To change controller configuration.

3 alarms 4 set data base 5 ctrl parameters

22 / 45

HDLT COMMUNICATOR

HDLT : CONFIG MENU 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters HELP SAVE HOME

MENU 1-2
HDLT : Setup interface right reverse acting controller HELP ON OFF OFF OFF ON

ABORT ENTER

HDLT : Buttons: use level Lock level HELP ON

OFF

ABORT ENTER

RETURN WITHOUT MODIFICATION

HDLT : NOTE 1 Password nnn ### HELP DEL ABORT ENTER

HDLT : Display language English English French HELP ABORT ENTER HDLT : Record values ? Press : OK for YES ABORT for NO ABORT OK

NOTE 1 : The password must be ODD and a value between 1 to 255. The password is not available on firmware rev. 4.12

23 / 45

HDLT COMMUNICATOR

CONFIG MENU - ALARMS


ALARMS MENU 1-3 1 tag 2 setup 3 alarms FAIL LOW ALARM Change tag, descriptor, message etc... reported by the HDLT. Change transmitter configuration reported by the HDLT like mounting sense, current action, level or interface use, buttons level use. Level alarms definition and corresponding values in engineering unit. Failsafe validation and corresponding current loop. Time value before to set alarms or time to go to failsafe mode. OFF = in case the instrument must go to failsafe mode the loop current will be: frozen to the last current value if FAIL = OFF, set to a specified current value if FAIL = ON. OFF = not low alarm set ON = low alarm is activated and will be set if Time1 is >0 . If Time 2 is also >0 , the transmitter will be force to faisafe mode after Time 2 elapsed. OFF = not high alarm set ON = high alarm is activated and will be set if Time1 is >0 . If Time 2 is also >0 , the transmitter will be force to faisafe mode after Time 2 elapsed. Displayed only if FAIL=ON. Current value for failsafe mode. This value must be between 3.6mA and 23.0mA. Displayed only if LOW ALARM=ON. Alarm threshold in the same engineering units as the level of liquid corresponding to the level value under which the transmitter set a low alarm or go to failsafe mode regarding Time 1 and Time 2. Displayed only if HIGH ALARM=ON. Alarm threshold in the same engineering units as the level of liquid corresponding to the level value above which the transmitter set a high alarm or go to failsafe mode regarding Time 1 and Time 2. Time duration is seconds which will elapse between the moment the level goes higher than High alarm level (or lower than Low alarm level) and the moment the alarm is set in : INFO MENU/ read fault(s) .The range is -1 to 1000s. Time duration is seconds which will elapse between the moment the level goes higher than High alarm level (or lower than Low alarm level) and the moment the instrument go to : FAISAFE MODE . The range is -1 to 1000s. Set HDLT data base concerning : chamber type, torque tube material, displacer size ... To change controller configuration.

HIGH ALARM

fail current Low alarm level

High alarm level

Time 1

Time 2

4 set data base 5 ctrl parameters

24 / 45

HDLT COMMUNICATOR

HDLT : CONFIG MENU 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters HELP SEND HOME

MENU 1-3
HDLT : alarms FAIL LOW ALARM HIGH ALARM HELP ON ABORT

ON ON OFF ENTER Nota

Nota: If all is OFF , the following screen is : Record values? . If FAIL =ON only, the alone screen displayed is : fail current .

HDLT : fail current nn.nnn mA #.## HELP DEL ABORT

ENTER

RETURN WITHOUT MODIFICATION

HDLT : Low alarm level n.nn % #.## HELP DEL ABORT

ENTER

HDLT : Time 1 n.n s #.# HELP DEL ABORT

ENTER

HDLT : Time 2 n.n s #.# HELP DEL ABORT

ENTER

HDLT : Record values ? Press : OK for YES ABORT for NO ABORT OK

25 / 45

HDLT COMMUNICATOR

CONFIG MENU - SET DATA BASE


DATA BASE MENU 1-4 1 tag 2 setup 3 alarms 4 set data base displacer torque tube chamber type arm lenght general options 5 ctrl parameters Change tag, descriptor, message etc... reported by the HDLT. Change transmitter configuration reported by the HDLT like mounting sense, current action, level or interface use, buttons level use. Level alarms definition and corresponding values in engineering unit. Failsafe validation and corresponding current loop. Time value before to set alarms or time to go to failsafe mode. Set HDLT data base concerning : chamber type, torque tube material, displacer size ... information : volume, weight, height, diameter with units choice and displacer options material used and normalized torsion couple all available configuration with additional chamber options standard lenghts or special design torque tube extension for high or low service temperature and certificate for use in dangerous area. To change controller configuration.

26 / 45

HDLT COMMUNICATOR

MENU 1-4 1
HDLT : CONFIG MENU 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters HELP SAVE

&

HDLT : volume unit liter liter CuIn ABORT

ENTER

HOME HDLT : displacer volume n.nn xxxxx #.## HELP DEL ABORT ENTER

HDLT: weight unit gr gr kg pound ABORT ENTER

RETURN WITHOUT MODIFICATION

HDLT : displacer weight nnnn.nnn xxx ####.### HELP DEL ABORT ENTER

HDLT : height unit mm in mm ABORT ENTER

HDLT : Record values ? Press OK for YES ABORT for NO ABORT OK

HDLT : displacer height nnnn.nn xxxxx ####.## HELP DEL ABORT ENTER

HDLT : displacer diameter nn.n xxx ##.# HELP DEL ABORT ENTER

FROM MENU 1-4-bis

TO MENU 1- 4-bis

27 / 45

HDLT COMMUNICATOR

75

MENU 1-4-bis FROM MENU 1- 4


Note 1 more configuration available HDLT : displacer options with displacer ON not standard OFF stainless steel ON extention rod OFF OFF ABORT ENTER

HDLT : Note 1 chamber type 12300 12301 ABORT ENTER

TO MENU 1- 4

HDLT: chamber options special steel ON carbon steel OFF stainless steel OFF drain ON vent ON OFF ABORT ENTER

RETURN WITHOUT MODIFICATION

HDLT : Note 1 torque tube inconel/carbon inconel/carbon inconel/stainless ABORT ENTER

HDLT : force 1 force 1 force 2 force 4 force ABORT ENTER

HDLT : arm lenght arm 4 in not standard arm 4 in arm 8 in arm 16 in HDLT : Record values ? Press OK for YES ABORT for NO ABORT OK ABORT ENTER

HDLT : general options extention HT/LT OFF intrinsic safety ON flameproof OFF weatherproof ON ON ABORT ENTER

28 / 45

HDLT COMMUNICATOR

CONFIG MENU - CTRL PARAMETERS


CTRL PARAMETERS MENU 1-5 Change tag, descriptor, message etc... reported by the HDLT. 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters Change transmitter configuration reported by the HDLT like mounting sense, current action, level or interface use, buttons level use. Level alarms definition and corresponding values in engineering unit. Failsafe validation and corresponding current loop. Time value before to set alarms or time to go to failsafe mode. Set HDLT data base concerning : chamber type, torque tube material, displacer size ... To change controller configuration: setpoint startup, units for setpoint (SP) , direct or reverse action and additional parameters. Remarks : the controller mode must be actived on the HDLT to allows to display controller parameters and to change PID parameters. Engineering units for the controller setpoint. A choice of many units is proposed . This unit is also used by Initial local SP, Low SP value, High SP value, SP low limit, SP high limit. Ratio control is ON : -if controller setpoint unit and level units are different . -if same unit but scale for setpoint and scale for level are not the same. Ratio control is automatically set in case of different units but not for different scale. If ratio control is ON, the two parameters RATIO GAIN and RATIO BIAS must be set using the formula : SP in process variable units = Ratio gain * SP in its units + Ratio bias At power up , in case of micro-controller re-start or if HDLT RESET has been performed , this setpoint will be use by the controller. Controller setpoint low value corresponding to low level of liquid (Low level). Controller setpoint high value corresponding to low level of liquid (High level). Minimum value for the setpoint allowed. Maximum value for the setpoint allowed. Alarm type could be absolute or deviation. This alarm is done on the level of liquid. ABSOLUTE= alarm detection is done on the real level of liquid. DEVIATION=alarm detection is done on the error between the level of liquid and the controller setpoint expressed in the level engineering unit . Controller low alarm. Alarms can be absolute or deviation. This value is expressed in level engineering unit. In case of deviation alarm, the Low alarm limit must be a negative number . Controller high alarm. Alarms can be absolute or deviation. This value is expressed in level engineering unit. In case of deviation alarm, the High alarm limit musy be a positive number .

Local SP unit Ratio control

Initial local SP Low SP value High SP value SP low limit SP high limit Alarm

Low alarm limit High Alarm Limit

29 / 45

HDLT COMMUNICATOR

CONFIG MENU - CTRL PARAMETERS


CTRL PARAMETERS MENU 1-5 Controller action DIRECT or REVERSE action. DIRECT action means the controller output increases if the error=level-setpoint is a positive number. REVERSE action means the controller output increases if the error= setpoint - level is a positive number. The derivative action can be done on the process variable (the level of liquid) or on the error. Controller rate to process the PID algorithm. The value must be between 0.2s and 10.0s. For some very slow process, the rate can be ajusted to avoid instability ,fast controller output change or a satured controller output. In other cases the low value is better to ajust the PID parameters. The general rule is to set the controller rate 10 times greater than the frequency cut of the process. Limits the controller output changes. This value is expressed in % output / second. The maximum value is 500%/s . The controller don't change its current output if the difference between the setpoint and the process variable (level) is less than the Dead zone. The range is 0.0% to 20.0%. It is the controller output at a typical operating steady state.Use in P or PD process algorithm . Can be used in PID algorithm if the setpoint change are small and in stable process. Must be set to zero if not used. Use if the process variable (level) and the setpoint are expressed in different engineering units or in different scales. This variable is used with RATIO BIAS in the following formula: SP in process variable units = Ratio gain * SP in its units + Ratio bias Remarks : the formula is made if RATIO CONTROL is ON. Use if the process variable (level) and the setpoint are expressed in different engineering units or in different scales. This variable is used with RATIO GAIN in the following formula: SP in process variable units = Ratio gain * SP in its units + Ratio bias Remarks : the formula is made if RATIO CONTROL is ON.

Derivative source Controller rate

Output Rate Limit Dead zone Manual Reset Bias

Ratio Gain

Ration Bias

30 / 45

HDLT COMMUNICATOR

HDLT : CONFIG MENU 1 tag 2 setup 3 alarms 4 set data base 5 ctrl parameters HELP SEND HOME

MENU 1-5
HDLT : Local SP unit % mA in ABORT ENTER

NOTE 1 HDLT : Output Rate Limit in % /s: nnn.nn ###.## DEL ABORT ENTER

HDLT : Alarm : ABSOLUTE 1 no change 2 absolute 3 deviation ABORT

ENTER

HDLT : Ratio control : ON 1 no change 2 NO 3 YES ABORT ENTER

HDLT : Dead zone : n.n % #.# HELP DEL ABORT ENTER

HDLT : Low Alarm Limit nn.nn ##.## HELP DEL ABORT

HDLT : Initial local SP nn.nn ##.## DEL ABORT

ENTER

HDLT : Manual Reset Bias : nn.n % ##.# HELP DEL ABORT ENTER

HDLT : High Alarm Limit nn.nn ##.## HELP DEL ABORT ENTER

HDLT : Low SP value nn.nn ##.## DEL ABORT

HDLT : Ratio Gain : nn.nn ##.## HELP DEL ABORT ENTER

HDLT : Controller action: reverse 1 no change 2 direct 3 reverse ABORT ENTER

HDLT : High SP value nn.nn ##.## DEL ABORT

HDLT : Ratio Bias : nn.nn ##.## HELP DEL ABORT ENTER

HDLT : Derivative source: ERROR 1 no change 2 ERROR 3 PV ABORT ENTER

HDLT : Low SP limit nn.nn ##.## DEL ABORT

NOTE 1 HDLT : Controller rate n.nn s #.## HELP DEL ABORT ENTER

HDLT : High SP limit nn.nn ##.## DEL ABORT

HDLT : Record values ? Press : OK for YES ABORT for NO ABORT OK

Note 1:
if ENTER is selected, a screen displays the closed value allowed to be recorded.

All ABORT Keys go out the displayed function without modification and return to CONFIG MENU

31 / 45

HDLT COMMUNICATOR

CALIBRATE MENU - TOOLS


TOOLS MENU 2 1 calibrate
TRANSMITTER S.G. METER

For more information about the calibration principle see page 44 .


This sub menu allows the user to calibrate the transmitter and the specific gravity meter: ZERO and SPAN. To calibrate the transmitter function. To calibrate the specific gravity meter function. This sub dialog allows to change the specific gravity(ies) of service , to change the upper and lower values for the current output signal. The values are typically 4 and 20 mA but may be any values between 3.8 and 20.5 mA. This dialog also allows to change the upper and lower values for the level of liquid with a choice of engineering units, the output damping, the zero shift and the reduce span. To change the specific gravity(ies) of service if different from the calibration specific gravity(ies). to change the upper and lower values for the current output signal. The values are typically 4 and 20 mA but may be any values between 3.8 and 20.5 mA. This dialog also allows to change the upper and lower values for the level of liquid with a choice of engineering units, the output damping, the zero shift and the reduce span. Coupling function between the electronic head and the torque tube. A good coupling correspond to display 0.0%. Values between +5.0% and -5.0% are acceptable. See the instruction manual for more information on the precise procedure to follow. This menu also allows to re-calibrate the current output but MUST BE DONE ONLY IF ABSOLUTLY NECESSARY. Current generator is also implemented to set different loop current to test or to calibrate others loop devices. The function allows to change the current to test for example different devices in serie in the loop. The range is 3.6 mA to 23.0 mA 4 mA re_calibration (trim DAC zero). This procedure must be done ONLY in case current output is not correct regards reference milli-ampermeter in the loop. Method: -press 4 mA ADJ : using a current reference meter, read the current loop (ex: 4.52mA) -enter the value of the loop current (ex: 4.52mA). -go out : the 4 mA output current is recalibrated. 20 mA re_calibration (trim DAC gain). This procedure must be done ONLY in case current output is not correct regards reference milli-ampermeter in the loop. Method: -press 20 mA ADJ : using a current reference meter, read the current loop (ex: 19..23mA) -enter the value of the loop current (ex: 19.23mA). -go out : the 20 mA output current is recalibrated. to come back to the CALIBRATE MENU. This procedure must be run during the coupling between the electronic head and the torque tube. The value displays must be between -5% and +5%.See instruction manual before to run this procedure.

2 parameters

CHG SG SER SET VARIABLES

3 tools

4-20mA CAL SET CURRENT 4mA ADJ

20mA ADJ

OUT COUPLING coupling

32 / 45

HDLT COMMUNICATOR

MENU 2

HDLT :
CALIBRATE MENU 1 calibration 2 parameters 3 tools HELP SAVE HOME

&
HDLT :
make your choice zero / span : 1 TRANSMITTER 2 S.G. METER ABORT ENTER

8-1 8-2

HDLT :
make your choice: 1 CHG SG SER 2 SET VARIABLES ABORT ENTER

HDLT :
make your choice 1 COUPLING 2 4-20 mA CAL ABORT ENTER

HDLT:
coupling = nn.nn % ABORT

HDLT :
make your choice 1 SET CURRENT 2 4mA ADJ 3 20mA ADJ 4 OUT ABORT ENTER

HDLT :
Set current loop: nn.nnn mA ##.### mA DEL ABORT OK

HDLT :
Enter the value of the current loop: nn.nnn mA ##.### mA DEL ABORT ENTER

Same procedure for 4mA and 20mA.

HDLT:
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

After to press ABORT key, the loop current is again the mirror of the liquid level.

33 / 45

HDLT COMMUNICATOR

CALIBRATE MENU - TRANSMITTER


MENU 8-1 1 TRANSMITTER 1 SG CAL :

For more information about the calibration principle see page 44 .


To calibrate the transmitter function. This sub menu allows to specify the specific gravity(ies) of calibration for the ZERO and SPAN. In INTERFACE SERVICE: two specific gravities must be set. IN LEVEL SERVICE only one. Specific gravity specified during the calibration procedure and corresponding to the LOWER liquid specific gravity. This specific gravity is used only in INTERFACE MODE. Specific gravity specified during the calibration procedure and corresponding to the UPPER liquid specific gravity. This specific gravity is used only in INTERFACE MODE. Specific gravity specified during the calibration procedure and corresponding to the liquid specific gravity. This specific gravity is used only in LEVEL MODE. To take the low level of liquid corresponding to 4.0mA or 20.0mA in the loop respectively for direct or reverse loop current. To take the high level of liquid corresponding to 20.0mA or 4.0mA in the loop respectively for direct or reverse loop current. to return to CALIBRATE MENU.

LOW SG CAL

HIGH SG CAL

SG CAL

2 ZERO 3 SPAN 4 OUT

34 / 45

HDLT COMMUNICATOR

MENU 8-1
HDLT :
make your choice zero / span for : 1 TRANSMITTER 2 S. G. METER ABORT ENTER

8-1

HDLT :
make your choice : 1 SG CAL 2 ZERO 3 SPAN 4 OUT ABORT ENTER

HDLT :
note1 n.nnn #.### HELP DEL ABORT ENTER

HDLT :
Record values ? Press : 0K for YES ABORT for NO ABORT OK

HDLT :
Fill the tank before to press OK ABORT ENTER

HDLT :
Empty the tank before to press OK ABORT ENTER

HDLT :
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

HDLT :
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

HDLT :
FROM ANY SCREENS DISPLAYED ABOVE ABORT ENTER

HDLT :
CALIBRATE MENU 1 calibration 2 parameters 3 tools HELP SAVE HOME

All ABORT Keys go out the displayed function without modification and return to CALIBRATE MENU

note 1: INTERFACE CONFIGURATION: two screens for low and high specific gravities: LOW SG CAL HIGH SG CAL LEVEL CONFIGURATION: only one sceen with SG CAL

35 / 45

HDLT COMMUNICATOR

CALIBRATE MENU - SG METER


MENU 8-2 2 S. G. METER 1 ZERO 2 SPAN

For more information about the calibration principle see page 44 .


To calibrate the specific gravity meter function. To take the displacer position corresponding to the specific gravity 0.0. The displacer chamber must be EMPTY. SG CAL: Specific gravity specified during the calibration procedure and corresponding to the liquid specific gravity. To take the displacer position corresponding to the specific gravity of calibration : SG CAL. The displacer must be fully immersed with the liquid of specific gravity SG CAL. In case of bad calibration of the specific gravity meter, this function allows the user to come back on to the factory calibration data. to return to CALIBRATE MENU.

3 RESET TO FACTORY 4 OUT

36 / 45

HDLT COMMUNICATOR

MENU 8-2
HDLT :
make your choice zero / span for : 1 TRANSMITTER 2 S. G. METER ABORT ENTER

8-2

HDLT :
make your choice : 1 ZERO 2 SPAN 3 RESET TO FACTORY 4 OUT ABORT ENTER

HDLT :
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

HDLT : HDLT :
SG CAL n.nnn #.### HELP DEL ABORT ENTER PROCEDURE ABORT. SG METER NOT FACTORY CALIBRATED. ABORT ENTER

HDLT :
Fill the tank before to press OK ABORT ENTER

HDLT :
Empty the tank before to press OK ABORT ENTER

HDLT :
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

HDLT :
PROCEDURE CORRECTLY EXECUTED ABORT ENTER

HDLT :
FROM ANY SCREENS DISPLAYED ABOVE ABORT ENTER

HDLT :
CALIBRATE MENU 1 calibration 2 parameters 3 tools HELP SAVE HOME

All ABORT Keys go out the displayed function without modification and return to CALIBRATE MENU

37 / 45

HDLT COMMUNICATOR

CALIBRATE MENU - PARAMETERS


MENU 9 1 CHG SG SER
LOW SG SER

For more information about the calibration principle see page 44 .


To calibrate the transmitter function. This specific gravity is normally the same as the low specific gravity of calibration (LOW SG CAL) but need to be change if the lower specific gravity of the process has changed and not equal to the low specific gravity of calibration (LOW SG CAL). This specific gravity is used only in INTERFACE MODE. This specific gravity is normally the same as the high specific gravity of calibration (HIGH SG CAL) but need to be change if the upper specific gravity of the process has changed and not equal to the upper specific gravity of calibration (HIGH SG CAL). This specific gravity is used only in INTERFACE MODE. This specific gravity is normally the same as the specific gravity of calibration (SG CAL) but need to be change if the specific gravity of the process has changed and not equal to the specific gravity of calibration (SG CAL). This specific gravity is used only in LEVEL MODE.

HIGH SG SER

SG SER

2 SET VARIABLES Damping Output current filtering. This value is expressed in second and corresponding to T63% for a first order response time. Low current High Current Low Level High Level Units Zero Shift Reduce Span Low output current for low level of liquid (direct acting) or low output current for high level of liquid (reverse acting). Must be between 3.8 mA and 14 mA and lower than High Current. High output current for high level of liquid (direct acting) or high output current for low level of liquid (reverse acting). Must be between 8.0 mA and 20.5 mA and greater than Low current. Value in engineering units for low level and corresponding to zero calibration. Value in engineering units for high level and corresponding to span calibration. Engineering units for Low and High Level.Available units are: %, mm, cm, m, liter, m3, inch, feet, cu_inch, cu_feet, kg, gr, pound. Value in percentage of calibration scale (zero/span) to shift the ZERO in an other position. The current output is automatically re-ajusted at this new ZERO position. Value in percentage of calibration scale (zero/span) to reduce the SPAN. The current output is automatically re-ajusted to take into account this new SPAN.

38 / 45

HDLT COMMUNICATOR

MENU 9
HDLT : HDLT :
note1 n.nnn #.### HELP DEL ABORT ENTER make your choice : 1 CHG SG SER 2 SET VARIABLES ABORT ENTER

HDLT :
Damping n.n s #.# HELP DEL ABORT ENTER

HDLT : HDLT :
Low current nn.nnn mA ##.### HELP DEL ABORT ENTER Record values ? Press : 0K for YES ABORT for NO ABORT OK

HDLT :
High Current nn.nnn mA ##.### HELP DEL ABORT ENTER

note 1: INTERFACE CONFIGURATION: two screens for low and high specific gravities: LOW SG SER HIGH SG SER LEVEL CONFIGURATION: only one sceen with SG SER

HDLT :
Low Level nnn.n % ###.# HELP DEL ABORT ENTER

HDLT :
High Level nnn.n % ###.#

HDLT :
Record values ? Press : 0K for YES ABORT for NO ABORT OK

note 2: Units availables: %, mm, cm, m, liter, m3, inch, feet, cu_inch, cu_feet, kg, gr, pound.

HELP

DEL ABORT ENTER

HDLT :
Units inch feet HELP

note 2

DEL ABORT ENTER

HDLT : HDLT :
FROM ANY SCREENS DISPLAYED ABORT ENTER

HDLT :
Zero Shift n.nn % #.## HELP DEL ABORT ENTER

CALIBRATE MENU 1 calibration 2 parameters 3 tools HELP SAVE HOME

All ABORT Keys go out the displayed function without modification and return to CALIBRATE MENU

HDLT :
Reduce Span n.nn % #.## HELP DEL ABORT ENTER

39 / 45

HDLT COMMUNICATOR

DIAGNOSTIC MENU
MENU 3
DIANOSTIC MENU

1 diagnostic data nbr of filling up time tank empty time tank full time working internal temp

Read continuous diagnostic data: total filling up, time tank empty, time tank full, time transmitter working Total number of filling tanks. Time in days for tank empty. Time in days for tank full . Time in days for HDLT working. Indicate the internal temperature inside the HDLT head.

2 reset continuous Reset continuous diagnostic data : total filling up, time tank empty, time tank full, time transmitter working. These variables are set to 0. The previous data are lost and must be recorded to be used later. Sensor check procedure. This test must be run ONLY IF THE LIQUID LEVEL IS STABLE to 3 sensor test avoid to go to FAILSAFE MODE. 4 smart filtering This sub menu allow to change manually or automatically the smart filtering variables to suppress noise , waves in the displacer chamber or wave in the tank and accordingly to reduce the current output variation. The user can read and change the parameters value described below one by one . Integration window expressed in seconds.The scale must be between 0.1s and 32.0s . Dead zone expressed in % of zero /span calibration. The scale must be between 0.01% and 10.0% . Validation window expressed in seconds.The scale must be between 0.1s and 32.0s . The three above parameters are found automatically with the target to reduce the current output variation below 0.3% of the full span. The specific gravity meter allow the user to read an unknown specific gravity. Be sure the displacer is fully immersed to avoid wrong measurement. To read all the transmitter tempory faults which have been cleared by the transmitter if not remained. The faults displayed are the same as : INFO / 1 read fault(s).

manual tune W INTG DZ INTG W VAL auto tune 5 SG meter 6 fault historic

40 / 45

HDLT COMMUNICATOR

MENU 3 3
HDLT : DIAGNOSTIC MENU & 1 diagnostic data 2 reset continuous 3 sensor test 4 smart filtering 5 SG meter 6 fault historic HELP SAVE HOME HDLT :
nbr of filling up

HDLT : After resetting, the c u r r e n t v a l u e s wi l l be lost. Press ABORT if you need these values ABORT OK

time tank empty time tank full

= n.n tank = n day = n day

ABORT

OK

HDLT : HDLT : HDLT : NOTE 1 Be sure that the displacer is fully immersed.. ABORT OK RESET CONTINUOUS DATA CORRECTLY EXECUTED ABORT OK
time working internal temp = n day = nn.n C

ABORT

OK

HDLT : SG = n.nnn ABORT HDLT :


make your choice : 1 manual tune 2 auto tune ABORT ENTER

HDLT :

NOTE 2 WAIT SENSOR TEST IN PROGRESS ABORT some seconds

NOTE 1 If the S.G. METER has not been previously calibrated the screen message is: SPECIFIC GRAVITY METER NOT CALIBRATED ABORT OK

HDLT :
W INTG = n.n s DZ INTG = n.nn% W VAL = n.nnn s

HDLT : TEST PASS OK ABORT OK

ABORT

HDLT :
W INTG (s) nn.n s ##.#

HDLT :

NOTE 2 WAIT AUTO TUNE IN PROGRESS ABORT some seconds later

HELP DEL ABORT ENTER

HDLT :
DZ INTG (%) n.nn #.##

NOTE 2 ABORT key dont wait the test result and return to DIAGNOSTIC MENU This take around 15 seconds. The message is: procedure aborted TRY AGAIN

HDLT :

NOTE 3 HDLT :

DEL ABORT

HDLT :
FROM ANY SCREENS DISPLAYED ABORT ENTER

AUTO TUNE CORRECTLY EXECUTED ABORT OK

W VAL (s) n.nn #.##

DEL ABORT NOTE 3 In case of problems to research the parameters, the message below is displayed PROCEDURE STOPPED ABORT OK HDLT :
Record values ? Press : 0K for YES ABORT for NO ABORT OK

All ABORT Keys go out the displayed function without modification and return to CALIBRATE MENU

41 / 45

HDLT COMMUNICATOR

CONTROLLER MENU
MENU 5
CONTROLLER MENU

1 controller view

Displays controller parameters like: setpoint (SP) , process variable (PV) and controller output (OUT-C).In addition this windows specifies the controller mode: AUTO or MANUAL mode and the alarms : HIGH or LOW , ABSOLUTE or DEVIATION. Sub-menu to set tuning PID coefficients. Proportionnal gain. It is the ratio of proportionnal controller output to error. Value between 0 and 50. Integral time or reset time expressed in second. Value between 0 and 1000 seconds. Derivative time or rate time. Value between 0 and 5000 milliseconds. Derivative gain to control the derivative action. Value between 0 and 100. Coefficient to change the proportionnal gain . The range is -9 to +9 . When Beta is 0 no action is done on P. When Beta =+9 , P is multiplied by 2 is error is greater than 20% and decrease to P value for error=0. When Beta =-9 , P is divised by 2 is error is greater than 20% and increase to P value for error=0. To change the local controller setpoint.

2 PID setting P I D Kd Beta

3 setpoint

42 / 45

HDLT COMMUNICATOR

HDLT : CONTROLLER MENU 1 controller view 2 PID setting 3 setpoint HELP SAVE HOME

MENU 5
HDLT : CTRL IN xxxxxxx ALARM xxxxxx PV = 49.9% L-SP = 50.0% OUT-C = 10.256 mA ABORT = 5.0 = 0.8 s = 520 ms = 57 =8 ABORT OK Display refreshed every 3 seconds

HDLT : P I D Kd Beta HDLT : setpoint nnn.nn ###.## HELP

DEL ABORT

HDLT : P nn.nn ##.## HELP DEL ABORT

HDLT : I nn.nn s ##.## HELP DEL ABORT ENTER

HDLT : D nn.nn ms ##.## HELP DEL ABORT

HDLT : Kd nn.nn s ##.## HELP DEL ABORT ENTER

HDLT : Beta nn.nn s ##.## HELP DEL ABORT ENTER

HDLT :
Record values ? Press : 0K for YES ABORT for NO ABORT OK

All ABORT Keys go out the displayed function without modification and return to CONTROLLER MENU

43 / 45

HDLT COMMUNICATOR

HDLT 12300 PRINCIPLE OF CALIBRATION


CONFIGURATION IN LEVEL TRANSMITTER

CALIBRATE MODE CAL Z S

CALIBRATE MODE VAR SET MA L / MA H

CALIBRATE MODE VAR SET LEVEL L / LEVEL H

MA H = 20 mA SPAN

LEVEL H = 560 mm

ZERO MA L = 4 mA SG CAL = LEVEL L = 0 mm

CONFIGURATION IN INTERFACE TRANSMITTER

CALIBRATE MODE CAL Z S

CALIBRATE MODE VAR SET MA L / MA H

CALIBRATE MODE VAR SET LEVEL L / LEVEL H

MA H = 20 mA SPAN

LEVEL H = 560 mm

ZERO MA L = 4 mA HSG CAL = 0.96 LSG CAL = 0.56 LEVEL L = 0 mm

44 / 45

HDLT COMMUNICATOR

TRADEMARK INFORMATION

HART

is a Registered trademark of the HART Communication Foundation, Austin, Texas, USA.

Model 275 HART Communicator is a product of Fisher Rosemount Systems, Inc.

45 / 45

TRADEMARK INFORMATION
HART is a Registered trademark of the HART Communication Foundation, Austin, Texas, USA. Model 275 HART Communicator is a product of Fisher Rosemount Systems, Inc.

Sales Offices and Distribution Centers


NETHERLANDS
Dresser Industrial Products B.V. Masoneilan Division Steenhouwerstraat 11 - 3194 AG Hoogvliet P.O. Box 640 3190 AN Hoogvliet RT The Netherlands Telephone 010-4384122 Fax 010-4384443

AUSTRIA
Masoneilan HP+HP GmbH Hans-Kudlich-Str. 35 A 2100 Korneuburg - Austria Telephone/Fax : 02262 63689

GERMANY

(continuation)

BELGIUM
Masoneilan Division of Dresser Europe S.A. 281-283, Chausse de Bruxelles 1190 BRUSSELS - Belgium Telephone 02 344 09 70 Fax 02 344 11 23

Masoneilan - HP+HP GmbH Uhlandstrasse 58 60314 Frankfurt Germany Telephone 49 69 439350 Fax 49 69 4970802 Masoneilan - HP+HP GmbH Goethestrasse 1700 06237 Leuna Germany PhoneFax 49 03461 434443

SINGAPORE
Dresser Valve & Controls Far East 16, Tuas Ave 8 - Singapore 639231 Telephone 65-861-6100 Fax 65-861-7172

BRAZIL
Dresser Idustria E Comercio Ltda Divisao Masoneilan Rua Senador Vergueiro, 433 09521-320 Sao Caetano Do Sul Sao Paulo - Brazil Telephone 55 11 453 5511 Fax 55 11 453 5565

ITALY
Masoneilan - Division of Dresser Italia S.p.A. Headquarters, Sales Office, Plant and After Sales : Via Cassano 77 80020 Casavatore (Naples) - Italy Telephone (081) 7892111 Fax (081) 7892208 North Italy Sales Office : C.soGaribaldi 113 20121 Milan - Italy Telephone (02) 29005683/84 Fax (02) 29005660

SOUTH AFRICA
Dresser Limited Valve & Controls Division P.O. Box 2234 - 16 Edendale Road Eastleigh, Edenvale 1610 Transvaal, Republic of South Africa Telephone 27-11-452-1550 Fax 27-11-452-2903

CANADA
Dresser Canada, Inc. Valve & Controls Division 5010 North Service Road Burlington, Ontario, L7L 5R5 - Canada Telephone 1-905-335-3529 Fax 1-905-336-7628 Dresser Canada, Inc. Valve & Controls Division 3530 78 th Avenue Edmonton, Alberta T6B 2X9 - Canada Telephone 1-403-465-7882 Fax 1-403-468-0934

SPAIN JAPAN
Niigata Masoneilan Valve Service Company 26th fl., Marive East Tower WBG 2-6 Nakase, Mihama-ku Chiba-shi, Chiba, 261-71 - Japan Telephone 81-43-297-9242 Fax 81-43-299-1115 Masoneilan S.A. Zona Franca, Sector M, Calle Y 08040 Barcelona - Spain Telephone 3 223 41 75/223 41 28 Fax 3 223 47 54

UNITED KINGDOM
Valve & Controls - Dresser U.K. Ltd Trevithick Works Gillibrands Estate, Skelmersdale Lancashire WN8 9TU - England Telephone 44-1695-52600 Fax 44-1695-720175 Valve & Controls - Dresser U.K. Ltd U.K. Sales Office : Unit 5, Brook Business Centre Cowley Mill Road, Uxbridge Middx UB8 2FX - England Telephone 44-1895-454900 Fax 44-1895-454919

LATIN AMERICA
Dresser Valve & Controls Division 10556 NW 26th Street, Suite D-201 Miami, Florida 33172 - U.S.A. Telephone 1-305-470-2766 Fax 1-305-470-2743

FRANCE
Dresser Produits Industriels Division Masoneilan 4, place de Saverne 92971 Paris La Dfense Cedex France Telephone 33 1 49 04 90 00 Fax 33 1 49 04 90 10 Lyon Distribution Center 55, rue de la Mouche 69540 Irigny - France Telephone 33 4 72 39 06 29 Fax 33 4 72 39 21 93

MEXICO
Masoneilan Internacional, S.A. de C.v. Henry Ford n 114, Esq. Fulton Fraccionamiento Industrial San Nicolas 54030 Tlalnepantla, Mexico Telephone 52-5-310-9863 Fax 52-5-310-5584

UNITED STATES
Dresser Valve & Controls Division Masoneilan North America Operations 85 Bodwell Street Avon, Massachusetts 02322-1190 Telephone 1-508-586-4600 Fax 1-508-941-5497 Dresser Valve & Controls Division 15112 Morales Road (77032) P.O. Box 60078 Houston, Texas 77205-0078 Telephone 1-281-871-6500 Fax 1-281-871-6569

MIDDLE EAST REGION


Dresser Valve & Controls Division Middle East Operations Unit JAO1 and JAO2 Roundabout 8 Jebel Ali Free Zone United Arab Emirates Telephone 971-4-838-752 Fax 971-4-838-038

GERMANY
Masoneilan - HP+HP GmbH Head Office : 47860 Willich Postfach 1208 47877 Willich Klein-Kollenburg Strasse 78-80 Germany Telephone 49 2156 9189-0 Fax 49 2156 41058

PLANTS, SPARE PARTS and AFTER SALES DEPARTMENTS: 3, rue SaintPierre 14110 CondsurNoireau Telephone : 33 2 31 59 59 59 - Fax : 33 2 31 59 59 60 - E-mail : service.clients@dpi.fr

Вам также может понравиться