Академический Документы
Профессиональный Документы
Культура Документы
The sludge dewatering plant system is designed to handle the sludge generated by the plant. The complete system includes a sludge cake handling system to transfer the dewatered sludge from the mechanical dewatering equipment into bins where it will be transported out from the building storage yard.
The plant consists of the following equipments:Wash water recovery pumpset Decanters Submersible pumpset Submersible mixers Sludge scraper Decanter feed pumps and holding tank feed pump
1.1
OPERATING PRINCIPLES
The plant is designed for 24 hours continuous operation in automatic mode as programmed by the PLC at the respective plant. When required, the plant can also be operated under full manual mode by operator intervention.
VOL. 1 OF 3
1|P age
The plant is designed with the following treatment processes to dewater the sludge prior to transfer out to the landfill:-
1.2.1 -Enhanced flocculation process. Polyelectrolyte is dosed as a flocculent aid. The dosing points are at the pipeline entering into thickener tanks and another at the pipeline entering decanters. The dosing of polymer solution is to aid in sludge thickening and to enhance the dewatering process.
2.0
2.1
DESCRIPTION
Settled sludge from the 10 sedimentation tanks is piped to 2 Nos. sludge balancing tanks (1 duty & 1 standby) while filter backwash waste water is discharged into 2 Nos. washwater recovery tanks (WWRT) (1 duty & 1 standby). One WWRT is designed to hold the waste water from 2 filter backwashing. After the WWRT has collected 2 lots of wastewater, the inlet penstock is closed and the content is settled. The supernatant is pumped back to the inlet of aerator through a floating suction. The sediment from the WWRT is pumped to the sludge balancing tank. Settling operation at WWRT is carried out batch-wise. The sludge balancing tank (SBT) receives sludge transferred from the WWRT as well as sludge and chemical waste discharged directly from the 10 sedimentation tanks and chemical building respectively. Sludge particles are kept suspended in SBT by 2 submersible mixers. Sludge from SBT is fed to the sludge thickener tank (STT) by 2 Nos. submersible thickener feed pumps (TFP). In operation, either 1 or 2 feed pumps will run, depending on level at the
PROCESS PLANT O&M MANUAL VOL. 1 OF 3
2|P age
2.2
2.2.1 FUNCTION The WWRT serves as a holding & sedimentation tank for filter wash-water. It enables the supernatant to be returned to inlet of the aerator and settled sludge to be transferred to SBT.
VOL. 1 OF 3
3|P age
VOL. 1 OF 3
4|P age
After the first WWRT has completed its Settling, it moves on to the Disposal state. In Disposal state, the dedicated wash-water recovery pump (WWRP) will start and the discharge valve of the WWRP open. Status of WWRP & its discharge valve are monitored, and alarm is raised when unusual condition arises. The supernatant from the WWRT is recycled back to the inlet of the aerator. The recycle flow rate is monitored by a magnetic flow-meter & display on the system. The recycle flow is manually pre-set by throttling a valve. In case the recycle wash-water flow exceeds a pre-set high flow value (SCADA adjustable) for more than 5 sec, an alarm Recycle Flow High will be raised. Pumping shall still continue even in Hi Flow condition. Auto-stopping of WWRP is by level electrode. When the low limit contact is activated, the WWRP stops and the discharge valve is close. If WWRP fails before the water reaching low level, the No WWRP Available alarm will be raised and the control sequence will be suspended. Operator interference is required to rectify and normalise the situation. [One unit of WWRP is dedicated to each WWRT, there is no standby unit.] Under normal condition when the WWRP has stopped, the duty submersible sludge transfer pump (STP) will automatically start run until the low-low limit contact (of level electrode) is activated. Status of the STP is monitored. The stand-by STP will run if the duty pump were to fail. After the STP has auto stopped (when WWRT has been emptied), Disposal stage is completed and the WWRT is put to Stand-by (inlet penstock continues to remain close). It will remain in this state until the other WWRT is
PROCESS PLANT O&M MANUAL VOL. 1 OF 3
5|P age
2.2.3 Process Interlocks & Alarms / Failure Conditions: A. The WWRP is dedicated to one unit of WWRT. The 2 STP from the same WWRT may run together automatically (by manually switching both STP to 'Available to start'). B. Control sequence will normally continue even when there is an active alarm (except as in (C) below). C. Process control sequence is suspended with alarm raised when the WWRP or both the STP fail together. In this case, manual intervention is required. D. WWRT is not available when : (a) Inlet penstock or valve is not remote selected at actuator; or (b) The associated WWRP or both STP are not available, fail/fault. E. Alarm to be raised when : (a) Any pump, valve or penstock fails during operation. (b) Alarm is raised when both duty & standby pump fail. (c) Alarm is raised when both the WWRT are NOT available.
2.3
2.3.1 FUNCTION Sludge Balancing Tank (SBT) acts as a buffer tank for storage of sludge from clarifier, chemical waste from chemical building and sludge transferred from WWRT before it is fed to the thickener tank. This serves to even out the sludge feed rate to the 2 sludge thickening tanks. Dimension of a SBT = 9.00mW x 10.685mL x 2.80m Depth
VOL. 1 OF 3
6|P age
7|P age
VOL. 1 OF 3
8|P age
2.4.1 FUNCTION The Sludge Thickener Tank (STT) increases the solids concentration of sludge before it is pumped to the holding tank. The clear supernatant overflows the weir and is returned to WWRT by gravity. The STT can also act as sludge storage tank in case the sludge holding tank is full or temporary out of service.
VOL. 1 OF 3
9|P age
Volume of sludge, 1.0m depth in STT = 750 cu meter. 2.4.2 OPERATION For each STT, there is an Auto/Manual selection switch on the SCADA screen to interlock with the TFP. The position of selector switch (on SCADA screen) will determine how the TFP response. Normally the Auto position is to be selected unless that STT is not available or under manual testing. When the STT is put to Auto from SCADA, the scrapper or rake will run continuously; and corresponding TFP will receive a start permissible i.e. it is free to start & stop depending on level corresponding SBT. sludge the 2 signal; at the
When a STT is put to Manual, the sludge scrapper will retain its last status before the switch-over (i.e. scrapper will be running if it was running before or the scrapper will be stop if it was not running earlier) and the corresponding TFP is NOT start permissive (i.e. the TFP will not auto start/stop with level changes at the corresponding SBT.). However, the TFP can still be manually started if so wishes. There is no In service /Stand-by /Out of Service selection for the STT; the only available selection is Auto or Manual. The sludge feed to STT and discharge from a STT is not controlled by status at the STT itself. When the TFP runs, supernatant from the STT will overflow and return to the WWRT by gravity. When the SHT feed pump (SHTFP) runs, the concentrated sludge will be transferred to the sludge holding tank. The only equipment that is controlled from the STT is the sludge scrapper drive.
VOL. 1 OF 3
10 | P a g e
2.4.3 Process Interlocks & Alarms / Failure Conditions: The Auto/Manual selection state of a STT is interlocked to start permissive-ness of the corresponding TFP as described earlier. Whenever a Sludge scrapper fails or trips, an alarm must be raised. Sludge scrapper shall be provided with a remote mounted emergency stop button station. If the torque switch on the sludge scraper gearbox is activated, Alarm Sludge Scraper Tripped on Over-Torque is raised.
2.5
2.5.1 FUNCTION A Sludge Holding Tank Feed Pump (SHTFP) transfers the concentrated sludge from the bottom of a STT to the sludge holding tank (SHT). There are 2 sets of dedicated STT, SHTFP and SHT; cross-over operation between these 2 sets of equipment is not possible. The SHT stores and provides a steady stream of thicken sludge of fairly uniform solids concentration for feeding to the centrifuge decanters. The 2 submersible mixers (SSMX) at each SHT prevent the sludge particles from settling. Dimension of a SHT: 7.50mL x 7.00mW x 2.35mD
VOL. 1 OF 3
11 | P a g e
12 | P a g e
2.5.3 Process Interlocks & Alarms / Failure Conditions: The Auto/Manual selected state of a SHT will either enable or disable SHT level control of the corresponding SHTFP and SSMX. An equipment (pump, mixer & valve) failure alarm shall be raised whenever such an event arises. Except for SHTFP, the failure of the duty unit shall not cause the standby unit to run. Before a SHTFP stops on auto, the pump and the sludge delivery piping shall be auto-flushed as described.
2.6
DECANTER CONYEVOR
FEED
PUMPS
AND
SCREW
2.6.1 FUNCTION The decanter feed pump (DFP) transfers the sludge from the sludge holding tank to the centrifuge decanter (CD) for dewatering. Dewatered sludge as discharged from decanter is transported by a screw conveyor (SC) to a collecting bin. There are 4 decanter feed pumps and 3 centrifuge decanters in this system. One DFP shall run to supply the feed to one decanter. Each decanter will have its dedicated screw conveyor to transport the sludge cake to an arm-roll bin.
VOL. 1 OF 3
13 | P a g e
2.6.2 2.6.2.1
The suction pipeline is arranged in such that sludge holding tank No.1 (SHT #1) supplies feed to DFP#1 and DFP#2; while SHT#2 serves DFP#3 and DFP#4. Individual discharge pipeline of all DFP will join to a common 'ring main' and then equally distributes the feed to each CD. The provision of 'ring main' allows duty-cycle operation of the decanter feed pumps (DFP) and centrifuge decanters (CD). When only one unit centrifuge decanter need to be run, any available DFP and CD may be selected for the duty. Operator has to ensure the suction and delivery manual valves are open and then the duty DFP and CD are selected to Auto at the LCP or SCADA. The motorised suction valve of the duty selected DFP and the motorised inlet valve to the duty selected CD will auto open. The sludge cake screw conveyor (SC) of the duty selected CD shall be put to Auto as well, to enable remote control by the PLC. When two decanters are required in operation simultaneously, any 2 available DFP may be selected manually for the duty while the 2 duty CD units are automatically selected by PLC (based on available running hours). The setting of running hour is adjustable at SCADA/PLC. The default running hour setting shall be 8 hours per day for each CD. Total running hours for all three CD is 8 x 3 = 24 hours.
VOL. 1 OF 3
14 | P a g e
When 2 sets of DFP and CD are running simultaneously, both DFP supplies feed to a common discharge line (ring main) and then equally distribute into both CD. The respective SC of both duty CD will automatically start via PLC remote control.
2.6.2.2 Operation of centrifuge decanter & related equipment. After the selected DFP, CD and SC are switched to Auto on the LCP and the correct isolation valves are open, the centrifuge decanter may be manually initiated to start from the decanter local control panel by pressing a push-button on the decanter LCP control touch-screen or remote initiation from SCADA. The decanter will start and undergo a normal starting sequence as described later. The motorised valves, feed pump and screw conveyor will be opened and started automatically at the correct sequence. Similarly, the decanter will go through an auto stop sequence when the Stop switch is activated. When the decanter is switched to Manual position, the standard decanter starting and decanter stopping sequences will be both deactivated. The associated motorised valves, feed pump and screw conveyor must be manually started or stopped at the proper sequence. A low level condition (L2) at SHT (sludge holding tank) shall to trigger the centrifuge decanter connected to this SHT to undergo a normal stop sequence on Auto.
2.6.2.3
When a decanter is initiated to start, the standard centrifuge decanter starting sequence is activated. A typical decanter starting sequence is as follows:
(1) Decanter start initiated from the LCP. (after checking manual valve position)
VOL. 1 OF 3
15 | P a g e
(6) Start the associated DFP. (7) Send start signal to duty DPDP (if dosing pump not already in operation), or increase the polymer feed rate according sludge solids loading (when the 2nd decanter is started and the DPDP is already running). (8) Thickened sludge & polymer solution enter the running decanter; dewatering of sludge will take place. (9) Centrate liquid is discharged from the liquid end & the dewatered sludge cake drops from solid discharge port to the screw conveyor. (10) The centrifuge decanter control system will adjust the speed of decanter and monitor the differential speed in response to any variation in torque via automatic torque mode. Torque is affected by feed rate and solids content in feed. The decanter controller will monitor these operating conditions while the unit is running. (11) The decanter would remain in operation when there is a continuous stream of sludge feed and the decanter is healthy. (12) The decanter will undergo a normal stop sequence when the operator initiates the Stop button. The Emergency Stop button shall not be used to stop the unit under normal operating condition, unless it is an emergency. On pressing Emergency Stop, the unit
VOL. 1 OF 3
16 | P a g e
2.6.2.4
When a normal Stop command is received by the decanter controller, a standard stop sequence is activated. A typical decanter stopping sequence is as follows: (1) Decanter Stop is initiated from decanter LCP. (2) The DPDP will immediately stop and the suction valve of DFP is closed. After 5 seconds, the polymer inlet valve to the CD will be closed. (3) The corresponding DFP flushing water inlet valve is open; while the DFP and CD is still running. Flushing water displaces the sludge in DFP & delivery pipe to the decanter when the DFP is running. The DFP & CD flushing duration can be set from the LCP. [Note: If two decanters are running simultaneously, the initiation of "Stop" will cease the feeding of sludge for both DFP and flushing will take place in series for both DFP and CD.] (4) After the DFP & CD flushing duration has elapsed, the DFP will stop. (5) After 5 s, the flushing water inlet valve to the DFP is closed. (6) After a delay of 3 minutes (adjustable from LCP), the CD inlet valve is closed & the motor drive of the CD is stopped. (7) After another delay of 2 minutes (adjustable) when all the sludge cake has been transferred to the arm roll bin, the SC attached of the decanter is stopped. (8) The DC and its feed pump (DFP) are now in the stop position.
VOL. 1 OF 3
17 | P a g e
(1) When two decanters are required in operation, the selection of duty decanter feed pumps (DFP) is done manually. The operator is required to check & confirm the manual valves of selected duty DFP are open before the decanter standard start sequence is operative. (2) An equipment (decanter, feed pump, screw conveyor & motorised valve) failure alarm shall be raised whenever such an event arises. The failure or tripping of an equipment shall not cause the standby unit to run on auto. The operator has to go to the field to investigate, clear the fault and normalise the equipment before starting again. This applies to all motorised equipment in this section, i.e. all equipment related to DCP and CD, except for the decanter polymer dosing pump (DPDP). (3) When sludge holding tank level is at L2 or below (see section 7.5.2 above), the operating centrifuge decanter connected to it will undergo a normal shutdown, with DFP & CD flushing prior to shut down; if the CD is selected to Auto. (4) When the screw conveyor (SC) associated with a running decanter trips, the operating centrifuge decanter connected to it will undergo a normal shutdown, with DFP & CD flushing prior to shut down; if on Auto. (5) When the DFP associated with a running decanter trips or fails, the operating decanter connected to it will stop immediately, without flushing (since flushing cannot be carried out when the DFP fails). At the same time the DPDP will stop or has its output halved if another decanter unit is still running. (6) Motorised valve failure(s) taking place after a decanter has completed its standard starting sequence will not cause the decanter to stop or trigger a CD stopping sequence. If valve failure takes place during a CD
PROCESS PLANT O&M MANUAL VOL. 1 OF 3
18 | P a g e
2.7
2.7.1 DESCRIPTION
Two units of Packaged Raw Water Polymer Batching plant shall be installed for the works. Polyelectrolyte solution is dosed at a proportional to the plant inlet flow (raw common inlet channel of the clarifiers the respective clarifier via the respective controlled rate, water), into the before entering inlet penstock.
Prior to dosing into the raw water clarifier inlet chamber, the liquid polyelectroyte is diluted with carrier water via a common dilution water valve to assist dispersion. The amount of dilution water is regulated by manual valve and indicated locally by rotameter. The dilution water shall remain unaltered when changing the polyelectrolyte dose. From laboratory jar tests and pump calibration curves, the desired polyelectrolyte dose shall be set by the stroke adjustment hand wheel on the duty dosing pump manually. The dosing pump output can be periodically checked by using the portable Calibration Cylinder located at the suction pipework. The control of the polyelectrolyte dosing plant will be manual and automatic. Electrically operated valves shall only be provided for the respective dosing pump on the suction and storage tank outlet.
VOL. 1 OF 3
19 | P a g e
Preparation of the polyelectrolyte solution is designed for automatic batching, with control by the main PLC. The polyelectrolyte batching plant comprise of a storage hopper of about 100 kg c/w a feeder mounted at the bottomed. A vacuum powder loader is provided at the hopper for loading bagged powder into the hopper. The hopper shall be equipped with loadcells weigher for display of content weight. Two nos. of SS316 mixing tanks of approximately 5 m3 are constructed. A dedicated top mounted stirrer is provided for the mixing tank. The plant offered is designed for batch preparation of stock solution. A fixed speed dry feeder is provided to deliver a predetermined quantity of Polyelectrolyte powder into the mixing and mix with the incoming service water. The batching plant comprise of a hopper to store the required Polyelectrolyte powder. The powder storage capacity shall be 100 kg. The hopper is equipped with a vacuum powder for loading bagged powder into the hopper. A weighing system comprising of loadcells shall display the hopper content weight at the LCP. The operator will be able to select the required polymer batch strength (0.1 to 0.4% w/v). Upon selection of the strength to batch, the PLC shall compute the quantity of powder required and the feeder shall deliver accordingly to achieve the selected strength. The powder Polymer hopper shall fill by operating the vacuum powder loader with a local controlled switch at the hopper. The conveyor nozzle is manually inserted into a 25kg powder bag to effect the transfer.
VOL. 1 OF 3
20 | P a g e
The preparation of polymer solution, at a pre-selected strength is automatically controlled by the PLC. The preparation sequence is initiated on low level only in the Mixing Tank as detected by a level switch. Upon manual initiation and a low level signal is detected, the sequence shall proceed as follows:Service water inlet valve opens to fill the Tank via a wetting device. The stirrer shall start when the feed commence feeding powder into the mixing tank. When a predetermined quantity is delivered into the mixing tank, the feeder shall stop. Service water continues to fill the mixing tank until the required level is achieved.
FAILURE CONDITION On power failure, the preparation sequence is interrupted. On restoration of power the batching sequence shall be restarted manually to continue.
Two nos. of Polymer Dosing Pumps are provided with one duty and one standby for the works. Control of pumps and electrically operated valves are at the LCP. Two units of dedicated VSD are provided at the LCP to vary the pumping speed of the dosing pump via flow pacing control through a central PLC. The pump stroke setting shall be manually selected at the pump to suit. One no. of Polymer Dosing Pumps is a duty pump and the 2nd pump is served as a 100% standby dosing pump. In manual mode i.e. Local Manual, the duty tank outlet valve and the duty pump suction valve are operated at the LCP. The stroking speed of the dosing pump is directed
PROCESS PLANT O&M MANUAL VOL. 1 OF 3
21 | P a g e
VOL. 1 OF 3
22 | P a g e
FAILURE CONDITION On power failure the Polymer Dosing Pumps will stop and all valves position will maintain. On restoration of power supply, operation of the plant is reinitiated manually. When a duty dosing pump fails during operation under Local Auto or Remote Auto mode, the standby dosing pump will automatically take over the failed pump. The appropriate valves will automatically open or close respectively to correspond the operation requirement. On dosing pump failure, an appropriate alarm is raised at the LCP. Electrically operated valve failure (fail to open and fail to close), an amber failed light will be lighted on the respective valve status lights and the operator shall investigate and take appropriate action (to rectify or to switch over to next tank or pump). On VSD failure the appropriate alarm is raised at the LCP. The VSD shall be manually changeover.
2.7.2.3 POLYMER PLANT LCP The facilities for Manual Control and Local Auto are located at the LCP and complete with indication lights. The LCP have the following control functions and indications: 1) Power On status indicator lamp 2) Alarm Accept and Lamp Test push-button. 3) Hopper Weight Indicator 2 nos. 4) Running/Stopped/Tripped status indicating lights & Run and Stop buttons for :-
VOL. 1 OF 3
23 | P a g e
5) Open/Close/Fault status indicator lights & Open and Close push buttons for :a. Pump Suction Valves 2 nos. b. Mixing Tank Outlet Valves 2 nos. c. Pump Flushing Valve 2 nos. d. Common Carrier Water Valve 1 no. e. Mixing Tank Inlet Valves 2 nos.
6) Running/Stopped/Tripped status indicating lights & Run and Stop buttons for :a. Dosing Pump No. 1 b. Dosing Pump No. 2 c. Dosing Pump Starter 2 nos. 7) Dosing Pump Starters 2 nos. 8) Variable Speed Drive Units 4 nos. 9) Local /Remote Selector Switch. 10) 11) Auto/Manual Selector Switch Local Start/Stop initiation push button
2.7.2.4 ALARM SUMMARY The following alarms shall be provided for Raw Water Polymer Dosing Pump LCP:1) 2) 3) 4) 5) Hopper Weight Low Hopper Weight High Mixing Tank Level High Mixing Tank Level Low Common Failed for Pump/Valve/VSD
VOL. 1 OF 3
24 | P a g e
2.7.3 POLYMER DOSING PLANT START UP BATCHING PLANT START UP The batching plant is only operated in automatic mode. The initiation of the batching done manually at the local panel mounted on the skid. Selection of solution strength is also done on the local panel.
POLYMER DOSING PUMP START UP AUTOMATIC MODE Start-up of the plant in the automatic mode is initiated manually by a Start button at the LCP or at the control centre MMI. Upon initiation of Start button, the auto sequence commences when raw water flow is detected and stop when raw water flow ceases. Unless Stop is initiated, sequence will resume when raw water flow is re-established after the raw water flow ceased.
MANUAL MODE
The Polymer plant is designed to run only in Local Manual and Remote Manual is therefore not used. Start-up of the plant in the manual mode is done at the local control panel. The following steps shall be followed to commence the operation in manual mode:At the LCP under Preparation System, please select the switch to Local for duty tank Then select the selector switch next to it to Manual At the LCP under Dosing System section, please select the switch to Local
VOL. 1 OF 3
25 | P a g e
2.7.4 POLYMER DOSING PLANT SHUTDOWN AUTOMATIC MODE Shutdown of the plant in auto mode is initiated manually by an Initial Stop button at the LCP or at the control centre. Upon initiation of Initial Stop button, the auto stop sequence commences with the duty pump stopping and follows by the respective closing of motorized valves. When raw water flow ceases or not detected, the plant will also stop. Unless Initial Stop is initiated,
VOL. 1 OF 3
26 | P a g e
MANUAL MODE Shutdown in manual mode is done at the LCP by pressing the Initial Stop button or at the control centre. The following steps shall stop the plant operated in manual mode:After pressing the Initial Stop button, the duty pump suction valve shall be selected to Close to isolate the pump Select the duty tank outlet valve to Close to isolate the tank Then, select the common carrier water valve to Close to stop the carrier water The dosing pumps shall be manually flushed by selecting Open on the respective flushing valve located at the pump suction for about 10 to 15 seconds and Close after that
2.7.5 POLYMER DOSING PLANT MAINTENANCE The Polymer dosing plant basically consists of the batching plant complete with mixing and storage tanks, level sensors, motorized valves, a transfer pump and metering pumps. Manufacturers equipment manuals are included in this O&M manual for reference. The operators are advised to refer to the specific manual for proper maintenance procedure described in the relevant manual.
VOL. 1 OF 3
27 | P a g e
- On a monthly basis, the metering pump should be recalibrated to ensure the pumping rate is maintained. If flow rate is noticeably different from previous calibration, refer to manufacturer manual for pump fault. - On a monthly basis, the motorized valves should be tested to ensure they are able to close and open fully and the respective signal feedback status is displayed at the SCADA. - On a monthly basis, the mixing tank level probes should be tested to trigger the high-high, high and low level indication at the SCADA.
VOL. 1 OF 3
28 | P a g e
1. Restart raw water pump. 2. Check flow meter and 2. Raw water flow signal rectify. loss. 3. Service tank sensor detected low-low. level 3. Initiate batching of polymer solution. level
4. Switch on the power 4. MCC power to pumps to the pumps at the isolated. MCC. 5. Pump emergency switch 5. Reset pump operated. emergency switch. 6. Check for pump 6. Pump tripped/faulted. overload or possible short circuit.
VOL. 1 OF 3
29 | P a g e
1. Inspect pump diaphragm and replace if necessary. 2. Check suction valve and pipe for blockage and clean.
3. Check pump stroke and VSD setting. 3. Readjust setting or recalibrate pump if necessary.
1. Inspect dampener air pressure, inflate or replace where necessary. 2. Check suction valve and pipe for blockage and clean.
2. Pump choked.
suction
VOL. 1 OF 3
30 | P a g e