Central Battery System Typ CPS 220/64/SV

Catalogue CPS 220/64

Sicherheitstechnik GmbH

New standards allow new ideas!

CPS 220/64/SV

INOTEC Sicherheitstechnik GmbH is a company with the target to create innovative and customer oriented solutions for the Emergency Lighting market. A dynamic team of highly professional and exible employees covers all aspects regarding products, engineering and standards. Modern, technical advanced products set new standards world wide, i.e. JOKER technology for Emergency Lighting Systems or the Dynamic Escape Routing concept realised in the D.E.R.System. This catalogue contains the INOTEC Standard Central Battery Emergency Lighting Systems CPS 220/64/SV and some complementing products. Should you require additional functions or special features please do not hesitate to ask our regional technical sales team for support.

Content Function, design and features Central monitoring Technical data / system overview Joker - Technique System - components and options Page 3-5 8-9 10 - 12 13 14 - 21

System planing and technical tables 22 - 23

Copyright: INOTEC Sicherheitstechnik GmbH, Ense Publications and copies, even partial, only with manufacturers permission. Subject to technical changes. The emergency systems in this catalogue are not compatible to monitoring systems of type INOTEC SVPC, SV-central or multifunctional controller. .

CPS 220/64/SV

Function, design and features


The CPS 220 series covers various load requirements and housing sizes. Joker-Technology, individual lamp- and circuit monitoring are our standard System features ` Modular design, various enclosure sizes for main-, substations, battery-racks and battery enclosures

` Up to 128 circuits (64 out of the main system


/ 64 out of substations) with 20 addresses can be supplied

` Low maintenance and service costs due


to central monitoring of stations and all connected luminaires

` Automated or manually releasing function


test facility with logbook for status and failure information

` Earth failure measurement and test facility ` Isolation terminals for easy earth failure
measurements

` Sealed lead acid gas recombination OGIbatteries with >10 year design life

` Galvanically isolated internal- and external


bus-system

` Separated monitoring- and change-over


devices for maintained-/non-maintained light

` Patented Joker-Technology function for


mixed operation of maintained, non-maintained and switched luminaires on one line Network-compatible, graphics based controller ` 5,6 TFT- Display

` Intuitive, single button operation ` Password protected programming ` Integrated network connection interface
(InoWeb)

` USB-interface to load / save the system conguration load / save the circuit conguration (operation
mode, monitoring depth, destination texts)

connect a standard printer (PCL-compatible) or key-board ` Administration of up to 128 circuits (max. 2.560 luminaires 20 addresses per circuit) ` Automatic function monitoring of system including single luminaire- and circuit failures without
additional data-line

` Integrated logbook for central compilation and > 2 year storage of all system related data ` Circuit-/luminaire function modes free programmable ` Various languages available

Function, design and features


Modular central power supply systems allow, depending on the building layout, the local building standards and the purpose/usage of the building, various design approaches for optimal cost efciency. Basically two different main versions are exsists. The classic Central Battery System: Supplies the complete building via lighting circuits Staircase running into every re zone. All circuits are connected to one central system only. This 1 . . . 20 is an advantage in smaller objects but might not be the best solution as long cable runs and function preserva1 . . . 20 tion of the circuits create higher costs.
E0

CPS 220/64/SV

Staircase

3. floor

1 . . . 20

2. floor

1 . . . 20

1. floor

1 . . . 20 E0 E30

1 . . . 20

Basement

CPS220
E30

E30

MDB
E30

Staircase
1 . . . 20
Sub DB Sub DB

CPUSB

CPUSB

1 . . . 20

Sub DB

Sub DB

CPUSB

CPUSB

The advanced Central Battery System: One central battery sysStaircase tem supplies individually adapted (BUS-) substations, 1 . . . 20 CPUSB, located in every oor or building segment. The combination of fully monitored 220V and 24V circuits/luminaires lead to 1 . . . 20 new, state-of-the-art, central battery system concepts.

1 . . . 20

Sub DB

Sub DB

CPUSB

CPUSB

1 . . . 20

Sub DB

CPS220 MDB
bus line
E30

Sub DB

CPUSB

CPUSB

1 . . . 20

Sub DB

CPUSB

CPS 220/64/SV

Function, design and features


Substation CPUSB 220 / 64 / 24V for 24V INOTEC LED - Safety- and Exit luminaires ` Automatic function monitoring of all connected luminaires

` Independent system with Joker-Technique


function: mixed operation of maintained, non-maintained and switched luminaires

` 24V luminaires individually programmable,


dimmable and addressable via controller

` Controller with 4 x 20 characters; various


languages settable

` Control, administration and failure display


for 20 luminaires addresses per output

` 4 output circuits in protection class III (SELV)


for 20 luminaires / each output

` Two programmable switch inputs for each


luminaire

` Dimmlevel setting for each individual luminaire or single circuits

` Luminaire addressing via search-and-store


controller function or manually

` Statusinfo for system and luminaires via


display and LEDs

` Voltfree contacts for external status display ` Switch contact for remote blocking facility

Substation CPUSB 220 / 64 / 1 Decentral substation for standard LED- / FL - Safety- and Exit luminaires

` Substations for 230V AC / 220V DC luminaires ` Standardised panel sizes ` For local AC supply ` Outputs for 4x2A and 2x4A ` Joker Technique, mixed operation maintained, non-maintained and switched programmable

` Three switch input per circuit ` Modular, allowing exibility for special
applications Emergency lighting bus-substation without controller

Function, design and features


The benets of 24V technology are now integrable to a CPS 220/64 (TFT) 230V system with the new change over device CP 24V 2x2.5A.

CPS 220/64/SV

` Functions of connected luminaires are automatically monitored

` Each luminaire can be programmed individually via the comfort TFT-controller

` Up to two input switches can be assigned to


each luminaire ` Luminaires can be dimmed separately ` Two output circuits in protection class III (SELV) for up to 20 luminaire addresses per circuit ` Luminaires are addressed without an address switch

In the event of a re, escape routes can be dynamically rerouted by the 24V change-overdevice in combination with D.E.R luminaires. Therefore a separate escape route D.E.R controller is no longer necessary.

Also available as BUS substation featuring the following additional functions:

` Integrated circuit separating module (SKW) ` Current loop input ` Ideal for a re compartment

CPS 220/64/SV

Function, design and features


The battery control system (BCS) monitors the battery blocks and provides a temperature controlled charging process. Detailed information like temperature and voltage of each individual battery block is measured and logged. In the event of an emergency, each emergency lighting system is assigned to the emergency power supply. For battery-backed systems, this emergency power supply is the battery, which in the event of a fault will not achieve the required operating duration, thereby compromising safety aspects in the building. Detecting faulty battery blocks at an early stage increases safety and reduces costs as it often sufces to replace the faulty block before it damages the remaining blocks. Therefore, the INOTEC BCS system does not monitor the battery symmetry; instead it uses a sensor to monitor each individual battery block, displaying the voltage and temperature on the comfort TFT-controller.

The charging process is automatically controlled if the temperature deviates from the usual operating temperature. If the temperature or battery block voltage exceeds a specied threshold, a failure notication will be issued and the charging process will be disconnected. The charging process will not start again until a manual reset is done. The BCS system controller includes RIF 5 functionalities. The battery management system is only available in combination with the comfort TFT-controller.

Function, design and features


The central monitoring system, INOMASTER, monitors up to 192 INOTEC emergency systems on 6 RTG data lines.

CPS 220/64/SV

max. 500m

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

CP 4x2A
2

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

CPS 220 / 64

CPS 220 / 64

CPS 220 / 64

Netz

Batterie

Netz

Batterie

16AT Ein

10AT

16AT Ein

10AT

Ladeteil 220V/7,5A

Ladeteil 220V/7,5A

CPS 220/64/11KW

CLS

Strung Failure

Batt.-Betrieb Bat.-Operation

Betrieb Operation

CPS 220/64/11KW - 1

CPS 220/64/11KW - 1

max. 500m

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

CPS 220 / 64

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

CLS

CLS

By using web technology the central monitoring solution is platform-independent and its no longer necessary to install additional software. All systems can be checked with any html-browser, even by portable devices such as smartphones or PDAs Additional functions: ` Monitoring of up to 491,520 luminaires (CPS 220/64 with 128 2-A circuits and 20 luminaires)

CPS 220/64/11KW - 1

` Test for function and battery


duration automatically activated at freely denable intervals

` Failure printout for all connected


devices

` Supports of CPS 220/64, CPS


220/48.1 and CLS 24

` Conguration software (installation required) for system programming available soon

` Possible to set password to


protect access rights

` Overall status is displayed in


INOMASTER

CPS 220/64/SV

Function, design and features


Comfort TFT-controller with integrated INOWEB function for centralised monitoring of the CPS 220/64 emergency lighting device via the Intranet/Internet. An existing network is used for connection purposes. The emergency lighting devices are monitored by accessing the controllers INOWEB functionality (by means of the web browser). Every system, circuit and luminaire status can be checked by the password-protected (optional) website. It is also possible to monitor systems on a PC with Internet access if an Internet connection is already in place. For demonstration purposes, please contact your regional technical sales team. Functions:

` Starting a function test ` Blocking / Unblocking ` Failure printout ` Static building layout visualisation by linking
local les or urls

Using the INOWEB Control software, it is also possible to monitor complex installations containing a range of system types from a single centralised location. To perform this process, the comfort TFT-controller must be connected to the available network.
Intranet / Firmennetzwerk
CPS 220/64/11KW mit TFT incl. InoWeb
CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A

CPS 220/64/11KW mit TFT incl. InoWeb


CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

1 UG Verteilerraum EG Verteilerraum 1OG Verteilerraum [kein Zielort vergeben]

Betrieb Test Strung blockiert

Systemfehler: keiner Systemfehler Strung Stromkreis [DL und NL]

CPS 220 / 64

CPS 220 / 64

Netz

Batterie

Netz

Batterie

16AT Ein

10AT

16AT Ein

10AT

Ladeteil 220V/7,5A

Ladeteil 220V/7,5A

Switch Router

Switch

Internet

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

CPS 220 / 64

CPS 220 / 64

Netz

Batterie

Netz

Batterie

INOWEB Control functionalities:

16AT Ein

10AT

16AT Ein

10AT

Ladeteil 220V/7,5A

Ladeteil 220V/7,5A

` Monitoring of up to 32 INOTEC emergency lighting devices (expansion on request)


CPS 220/64/11KW mit TFT incl. InoWeb CPS 220/64/11KW mit TFT incl. InoWeb

` Automatic function/battery duration test ` Logbook function for all connected devices ` Email automatically sent at denable intervals in
the event of tests or faults

` Overall status displayed (of all systems) by an icon


in the task bar

Technical data, systems overview

CPS 220/64/SV

Technical data:

CPS 220 / 64 / 11kW-1 CPS 220 / 64 / 11kW-2 CPS 220 / 64 / 11kW-1 CPS 220 / 64 / 11kW 3-phase 3-phase

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

1030 mm

1030 mm

CP 4x2A
3

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

830 mm

2
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

3
3,15 A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

INOTEC
Betrieb Batt.-Betrieb

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

Strung

La deStrung

Drucker Centronics
Reset

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

CPS 220 / 64

Key-Boa rd

INOTEC
Betrieb Batt.-Betrieb

INOTEC
Betrieb Batt.-Betrieb

Strung

La deStrung

Strung

Drucker Centronics
Reset

CPS 220 / 64
INOTEC
Betrieb Batt.-Betrieb

Key-Boa rd

La deStrung

Drucker Centronics
Reset

CPS 220 / 64

Key-Boa rd

Strung

La deStrung

Drucker Centronics
Reset

CPS 220 / 64

Key-Boa rd

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A
Netz Batterie
Netz Batterie

16AT Ein

10AT

Netz

Batterie

16AT
16AT Ein 10AT

10AT Ein

Ladeteil 220V/7,5A
Ladeteil 220V/7,5A

Ladeteil 220V/7,5A

2030 mm

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

Protection class: I Protection category: IP20 Perm. ambient temperature for system: -5C bis +35C for battery: see battery data sheet Battery voltage: 220V DC Housing color: RAL 7035 Plinth (optional) 100mm or 200mm Rated voltage: System current: internal total max. Load Max. installed battery capacity Charger Circuit modules 4x2 A, 2x4 A, 1x6 A max. intern/extern 2x2,5 A 24V max. intern/extern Conductor cross section, max. (mm): Mains supply Battery supply Outgoing to luminaires Data line (RTG) 24V monitoring Supply cable BUS-line IB2 Mains to CPUS Battery to CPUS Dimensions H x W x D (mm) With function preservation (optional) - with function preservation Cable inlets

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

1200 mm

Netz

Batterie

1200 mm

1200 mm

16AT Ein

10AT

Ladeteil 220V/7,5A

Depth 400 mm 800 mm

Depth 400 mm 800 mm

Depth 400 mm 800 mm

Depth 400 mm 800 mm

1~N/PE, 230V AC 10%, 50/60Hz 50 A 50 A 11 kW 75 Ah 1 x 3 A or 7,5 A 16/16 8/16 35 35 4 4 4 35 4 35 35 2030 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 4 Outgoings *1 1 Outgoing *1 2 x 8 TE 1 x 4 TE top

1~N/PE, 230V AC 10%, 50/60Hz 50 A 50 A 11 kW 75 Ah 2 x 3 A or 7,5 A 16/16 8/16 35 35 4 4 4 35 4 35 35 2230 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 4 Outgoings *1 1 Outgoing *1 2 x 8 TE 1 x 4 TE top

3~N/PE, 400V AC 10%, 50/60Hz 50 A 50 A 11 kW 75 Ah 1 x 3 A or 7,5 A 16/16 8/16 35 35 4 4 4 35 4 35 35 2230 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 in option slot 1 Outgoing *2 8 TE top

3~N/PE, 400V AC 10%, 50/60Hz 50 A 50 A 11 kW max. 4 x 3A or 7,5A 16/16 8/16 35 35 4 4 4 35 4 35 35 2030 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 in option slot 1 Outgoing *2 1 x 27 TE *3 1 x 6 TE 2 TE top or bottom

Termination box US-BUS Neozed NH00 fuse Space for options Space required for battery fuses NH00 Cable inlets

10

CPS 220/64/SV

Technical data, systems overview

CPS 220 / 64 / 22kW CPS 220 / 20 / 1,2A CPS 220 / 20 / 3A 3-phase

CPS 220 / 20 / 5,5kW CPS 220 / 20 / 5,5kW CPUS 220 / 64 / 11kW / 3A / 7,5A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

CPS 220/20
CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A

CPS 220/20
1
3,15 A

830 mm

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

INOTEC

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

800 mm

800 mm

Betrieb

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

600 mm

Batt.-Betrieb

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

Strung

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

La deStrung

Drucker Centronics
Reset

CPS 220 / 64

Key-Boa rd

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

CPS 220/20
CP 4x2A CP 4x2A CP 4x2A CP 4x2A CP 4x2A AIF CPS 220/20 LT 220V / 1,2A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

DC

Netz

Batterie

Netz

Batterie

3,15A

2030 mm

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

16AT Ein

10AT

16AT Ein

10AT

CPS 220 / 64

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

AC ~
F
I

DC 4

Ladeteil 220V/7,5A

Ladeteil 220V/7,5A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

AC ~

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

3,15A

Netz

Batterie

16AT

10AT Ein

Achtung!! Sicherungen im Gert nicht unter Last ziehen. Anlage blockieren.

Achtung!! Sicherungen im Gert nicht unter Last ziehen. Anlage blockieren.

Achtung!! Sicherungen im Gert nicht unter Last ziehen. Anlage blockieren.

Ladeteil 220V/7,5A
10A 10A 10A 10A 10A 10A

Batteriesicherung
hin ter d er B lend e

Batteriesicherung
hin ter d er B lend e

Batteriesicherung
hin ter d er B lend e

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

1000 mm

1000 mm

Netz

Batterie

16AT Ein

10AT

Ladeteil 220V/7,5A

1000 mm

1200 mm

830 mm

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

Netz

Batterie

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

16AT Ein

10AT

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

Ladeteil 220V/7,5A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

Depth 400 mm 800 mm

Depth 300 mm 600 mm

Depth 300 mm 600 mm

Depth 300 mm 600 mm

Depth 400 mm 800 mm

CPS 220 / 64

Depth 400 mm 800 mm

3~N/PE, 400V AC 10%, 50/60Hz 63 A 100 A 22 kW max. 4 x 3A or 7,5A 16/16 8/16 35 35 4 4 4 35 4 35 35 2030 x 800 x 400 22 x M 20 64 x M 25 6 x M 32 2 x M 50 in option slot 1 Outgoing *2 1 x 27 TE *3 1 x 6 TE 2 TE top or bottom

1~N/PE, 230V AC 10%, 50/60Hz 7A 7A 1,5 kW 18,1 Ah 1,2 A 5/2/4 35 4 4 1600 x 600 x 300 BRS 10 2460 x 1200 x 595 10 x M 20 33 x M 25 4 x M 32

1~N/PE, 230V AC 10%, 50/60Hz 7A 7A 1,5 kW 27,8 Ah 3A 5/2/4 35 4 4 1800 x 600 x 300 BRS 10 2460 x 1200 x 595 10 x M 20 33 x M 25 4 x M 32

1~N/PE, 230V AC 10%, 50/60Hz 25 A 25 A 5,5 kW 27,8 Ah 3A 5/16 2/16 4 35 4 4 4 2,5 1800 x 600 x 300 BRS 10 2460 x 1200 x 595 10 x M 20 33 x M 25 4 x M 32

1~N/PE, 230V AC 10%, 50/60Hz 25 A 25 A 5,5 kW 75 Ah 7,5 A 5/16 2/16 4 35 4 4 4 2,5 2030 x 800 x 400 BRS 10 2460 x 1200 x 595 22 x M 20 64 x M 25 6 x M 32 2 x M 50 1 Outgoing *2 1 Outgoing *2 24 TE top

1~N/PE, 230V AC 10%, 50/60Hz 50 A 50 A 11 kW 16/16 8/16 35 35 4 4 4 35 4 830 x 800 x 400 BRS 08 1374 x 624 x 434 22 x M 20 64 x M 25 6 x M 32 2 x M 50 in option slot 1 Outgoing *2 2 x 8 TE 1 x 4 TE top

13 TE top

13 TE top

1 Outgoing *2 1 Outgoing *2 13 TE top

*1 not in option slot *2 in option slot *3 1 x 31 TE supply bottom side

11

Technical data, systems overview

CPS 220/64/SV

Technical data:

CPUSB 220 / 64 / 16 CPUSB 220 / 64 / 8-1 CPUSB 220 / 64 CPUSB 220 / CPUSB 220 / / 1 - 2A 64 / 1-2,5A/24V 64 / 24V

600 mm

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

Depth 300 mm 600 mm

Depth 82
181

Protection class: I Protection category: IP20 Perm. ambient temperature for system: -5C bis +35C for battery: see battery data sheet Battery voltage: 220V DC Housing color: RAL 7035 Plinth (optional) 100mm or 200mm Rated voltage: System current: Intern total Circuit separating module Circuit modules CP 4x2 A, 2x4 A, 1x6 A CP 24V 2x2,5 A Conductor cross section, max. (mm): Outgoing to luminaires 24V monitoring BUS-line IB2 Dimensions H x W x D (mm) With function preservation (option) - with function preservation Cable inlets

CPUSB 220 / 64 / 8 - 9 CPUSB...1 - 4A


600 mm
600 mm

378

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

CP 4x2A

378

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

1
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

2
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

3
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

4
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

F
3,15 A

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

= BL / NM = DL / M

Depth 300 mm 600 mm

Depth 300 mm 600 mm

Depth 82
181

Depth 82
181

378

116,5
253

230V AC 10% / 216V DC +10% / -15% (supplied by CPS)


max. 16 max. 8 4 35 4 600 x 600 x 300 BRS 08 1374 x 624 x 434 10 x M 20 33 x M 25 4 x M 35 4 TE max. 8 max. 4 4 35 4 600 x 600 x 300 BRS 08 1374 x 624 x 434 10 x M 20 33 x M 25 4 x M 35 13 TE 8A 8A Ja 1 (4x2A or 2x4A) 5 A (24V) 5 A (24V) Ja 1 4 4 4 4 4 4 12 A (24V) 12 A (24V) 1 4x3A (24V)

4 4 2,5 466 x 253 x 378 x 181 x 82 378 x 181 x 82 116,5 BRS 06 BRS 06 BRS 08 1074 x 624 x 1074 x 624 x 1374 x 624 x 334 334 434 11 x M20 11 x M20 6 x M16 9 x M 20 -

Space for options

Required space for options 0 TE Mains terminals for substation (single-phase system) 1 TE DP 2 TE DP / B.1 4 TE LSA 8.1 6 TE LSA 8.1 24, incl. 4 terminals 7 TE Fuse protection Battery NH00 Fuse output NH00 for substation

RIF 5 BCS PSU 24 Fuse output Neozed for substation Mains terminals for substation (3-phase system)

12

466

CPS 220/64/SV

Advantages and function of Joker-technology


Joker-technology - a cost saving innovation

``Each INOTEC CPS emergency lighting


system can be built-up to three different supply luminaire switching modes on the same output at the same time. Luminaires with Joker high frequency electronic ballast (common standard on INOTEC-SV lumnaires) or Joker switch modules, for third party electronic ballast, must be used. These components allow an easy setting of the monitoring address and luminaire mode.

Advantages of the Joker - technology

``Simple design and engineering ``Reduced installation material content ``Cut down on installation time ``Higher load level for nal end circuits ``Switching mode settable on each luminaire

``The patented JOKER-technology of INOTEC


reduces the design- and installation time and cuts down on material cost.

`` The sample pictured shows the kind of


installation savings which can be achieved.

``Conventional systems and installations


with the switching modes maintained-, non-maintained- and switched maintained mode, require 6 nal end circuits to feed 9 lumnaires in a part of the building shown.

``The Joker-technology reduces the number


of circuits required. Our sample needs only 2 nal end circuits to feed the same number of luminaires due to the fact that the operation of all switching modes on one circuit is possible.
Circuit 1 Circuit 3 Circuit4 Circuit 2

``The maintained and switched maintained


luminaires are active during mains presence. During mains failure, however, all luminaires, regardless of their operation mode, will be switched on and supplied by the central battery system.

Conventional installation requires 6 nal circuits

Circuit 5 Circuit 6

Circuit 1

Circuit 2

Joker technology with 2 nal circuits

German Patentnumber: DE 19807844 European Patentnumber: EP 0939476

Maintained

Non-maintained

Switched maintained

13

Systemkomponenten und Optionen

CPS 220/64/SV

CPS-comfort TFT-controller

Circuit modules

Graphic user interface Administration of up to 128 circuits (max.


2.560 luminaires 20 addresses per circuit)

Individual slide-in circuit modules with 2 pole Single luminaire- and circuit- monitoring with Monitoring without data-line LEDs in the front for circuit status info and circuit Completely wired to terminals 4mm 4 circuits 2A 2 circuits 4A 1 circuit 6A
Available types: (4x2) (2x4) (1x6) mode JOKER function fuse-protection for every circuit

Intuitive, single button operation Detailed status- and failure display Integrated network interface with webserver
(InoWeb) USB-interface Load / store / change system-, circuit-, luminaire-conguration For standard printer (PCL-compatible) and keyboard Free programmable, non-volatile memory Password protection Automatic time adjustment via network Blocking function for complete system or mains lighting Interface for BMS or other superior monitoring system Helptext for all system functions Various languages available

All available status information for the complete Fault information for every circuit or individual
luminaire with location text-info Achieved battery duration (in minutes) during the last endurance test Available battery capacity Logbook entries > 2 years CPS-system Charger 220 V/3,0 A and 220 V/7,5 A

Accessible display information:

Single luminaire- / circuit monitoring Automatic function test - / duration test cycles Time delay on mains return Deep discharge protection settings with display
Optional: Standard 4-line liquid crystal display with functional limitations available.

Programming possibilities:

For all available 216V lead-acid accumulators Service-friendly 19 - housing Modern, microprocessor controlled design with high efciency low weight Battery charge- and discharge current informa Constant charger- and battery circuit monitoring
with fault display at the CPS controller in case of blown battery fuse missing or defect battery block faulty charger open battery circuit battery voltage to high / low Temperature controlled charging to ensure longer battery life tion is permanently available at the CPS controller

14

CPS 220/64/SV

Systemkomponenten und Optionen

Fully monitored, autarchic 230V Bus-Substation The usage of this autarchic 230V bus-substation allows maximum exibility and gives a high safety standard in combination with cost saving for the installation. Local mains supply / lighting circuit monitoring and the standard INOTEC features like Joker-Technique give the design and planning all technical possibilities. Central programming, monitoring and detailed status-/failure- display of all connected bus-substations is achieved via the TFT-controller. Standard sizes:

Fully monitored, autarchic 24V Bus-Substation The 24V bus-substation, connected to a CPS 220/64 SV system, operates fully autarchic but is fully monitored via the main emergency lighting panel. In addition to the information available on the TFT of the main panel all local status- and luminaire information is available on the LCD of the substation. The station offers the following standard features along with the proven Joker-Technique: Supply of 24V INOTEC LED luminaires 4 output circuits a 3A in protection class III (SELV) for 20 luminaires / each output Controller with 4 x 20 characters; individual luminaire text info Various languages settable Automatic function monitoring of all connected circuits and luminaires without additional data-line 2 individual dimmlevels settable for each individual luminaire on the substation controller Automatic / manual luminaire addressing via substation controller Statusinfo for system and luminaires via display and LEDs Voltfree contacts for external status display Switch contact for remote blocking facility LSA 4 built in for individual luminaire switching Monitoring loop for local mains failure detection Central dimming possibility for individual luminaires or complete circuit via internal pushbutton or external 0-10V interface System for wall mounting / surface mounted Mains operation: 230V AC +/-10% Battery operation: 220V DC +10%/-15% Output voltage: 24V DC +/-20% System protection class: I / IP20

4x2A and 2x4A for 230V AC / 220V DC Individual setting of monitoring-/operation Modular, allowing exibility for special Central programming via TFT-controller of main Monitoring loop for local mains failure detection LEDs for local status information on circuit mode
and failures Mains operation: 230V AC +/-10% Battery operation: 220V DC +10%/-15% System protection class: I / IP 20 panel applications mode for every circuit

15

External supervision and display

CPS 220/64/SV

CP 24V 2x2,5A

CPUSB 220 / 64 / 1-2,5 / 24V Independent 24V sub station designed to increase safety standards and save space in the installation area. The comfort TFT-controller is used to programme, monitor and display the status centrally. To supply 24V INOTEC LED luminaires Two output circuits at 2.5 A in protection class III (SELV) Communicates with luminaires without additional data line Up to 20 luminaires can be monitored individually per circuit Two input switches and dimming value can be programmed per luminaire Control of 24V INOTEC D.E.R. luminaires Integrated circuit separating module Current loop assumes switch-on role in event of sub-db failure Only in combination with comfort TFT-controller

To supply 24V INOTEC LED luminaires Two output circuits at 2.5 A in protection class III Communicates with luminaires without additional Up to 20 luminaires can be monitored individually Two input switches and dimming value can be Control of 24V INOTEC D.E.R. luminaires LEDs in front cover are used to display the circuit Completely wired on 4mm terminals Two rack spaces required Only in combination with comfort TFT-controller
status programmed per luminaire per circuit data line (SELV)

Max. wire length for max. voltage drop of 4V Loading condition: worst case (load at the end of the wire) Current Cross-section Length 3A 1,5 mm 56m 2A 1,5 mm 84m 1A 1,5 mm 168m 3A 2,5 mm 93m 2A 2,5 mm 140m 1A 2,5 mm 280m

16

CPS 220/64/SV

System components and options

RIF 5 Interface for remote status indication and system blocking function. Free programmable, in connection to a switch, for maintained and non maintained emergency light ON/OFF maintained emergency light ON/OFF With or without loop monitoring 5 voltfree contacts for operation battery operation failure (general) free programmable 2x Terminals battery sensor for temperature controlled charging With phase monitor (sub-db or main-db), single phase Contacts: 24V / 1A EMC protected to EN 55015 Dimension: H = 59, W = 71.5, D = 90 (mm) System status Operation Sumfailure Failure 1-2 close open Operation 3-4 close open Battery open open operation 5-6 Option 1 selectable Option 2 selectable

BCS Battery control system designed for the individual monitoring of up to 36 battery blocks.

Records (for each battery block) Temperature Voltage Temperature controlled charging of battery
blocks; safety switch-off function for charging if battery block temperature or voltage is exceeded RIF 5 module functionalities integrated Only in combination with comfort TFT-controller EMC protection in acc. with EN 55015 Dimensions: H=59, W=71.5, D=90 (mm) Sensor dimensions: H=19 , W=40, D=38 (mm)

Relay contacts

Battery operation close open close

Remote switch Volt free contacts 24V DC max.100mA 24V Monitoring loop

850 009

single phase supply monitor battery voltage internal wiring

Temp. sensor

17

Systemkomponenten und Optionen

CPS 220/64/SV

LSA 3.1 Light switch monitor, 3 channels


For the common switching (on/off ) of safety luminaires along with the mains lighting Up to three channels can be allocated to every individual, or a number of CPS output circuits. This switch/channel allocation happens during the set-up/commissioning and is programmable on the CPS-controller. Attention: common neutral! Supply voltage: 230V AC 50/60 Hz EMC protected to EN 55015 Dimensions: H = 59, W = 17,5, D = 90(mm)

LSA 8.1 mit DP/BUS Light switch monitor, 8 channels For the common switching (on/off ) of safety luminaires along with the mains lighting and for phase monitoring. Each channel is galvanic separated. Up to three channels can be allocated to every individual, or a number of CPS output circuits. This switch/channel allocation happens during the setup/ commissioning and is programmable on the CPS controller. Three-phase-monitor, DP/BUS free selectable phase connections 1 change-over contact monitoring low voltage and mains failure for single-phase monitoring too voltage 230V AC, 400V AC threshold 0,85 x UN deactivation switch Failure info at the CPS-controller with location Supply voltage: Available in 230V AC 50/60 Hz or 24V DC EMC protected to EN 55015 Dimension: H = 59, W = 71,5, D = 90(mm)

PE N L

PE N L
General lighting

PE N L
General lighting

PE N L
General lighting

850 008

Internal wiring

18

CPS 220/64/SV

Systemkomponenten und Optionen

DP Three Phase Monitor To detect phase- or circuit failures in general lighting sub-distribution panels With volt-free failure indication contact LED-indication for L1, L2, L3 free selectable phase connections monitoring low voltage and mains failure in threephase networks for single-phase monitoring too acc. to IEC 255 for DIN rail mounting For the connection to INOTEC central- and group supply battery systems. Voltage: 230V/400V AC 50/60 Hz Threshold: 0,85 UN Perm. temp.: -20C ... +60C EMC protected to EN 55015 Dimension: H =58, W = 17,5, D = 90(mm)

DP/B.1 Three Phase Monitor with BUS, addressable To detect phase- or circuit failures in general lighting sub-distribution panels. With location info at CPS-controller of monitored sub-distribution panel in case of phase failure. With volt-free failure indication contact. LED-indication for L1, L2, L3 free selectable phase connections 2 x n/o contacts monitoring low voltage and mains failure in three -phase networks for single-phase monitoring too acc. to IEC 255 for DIN rail mounting Detailed phase failure with location info of the sub-db at CPS controller For the connection to INOTEC central- and group supply battery systems. Voltage: 230V/400V AC 50/60 Hz Threshold: 0,85 UN Perm. temp.: -15C ... +40C EMC protected to EN 55015 Dimension: H = 58, W = 36, D = 90(mm)

L1 L2 L3 N PE

SUB DB 1

SUB DB 2
L1 L2 L3 N PE

L1 L2 L3 N PE

SUB DB ...

L1

L2

L3

L1

L2

L3

L1

L2

L3

Einer

Einer

890 414

890 414

890 414

Zehner

Zehner

4
3

4
3

4
3

EMC: gem. EN 55015

Address setting is mandatory for full functionality

850 009

RIF5

or

terminal rail

+24V IB 2

1 3

2 4

+24V BUS

EMC: gem. EN 55015

1 3

2 4

+24V BUS

EMC: gem. EN 55015

1 3

2 4

+24V BUS

gem. VDE 0108 ta: -15 bis 40C

gem. VDE 0108 ta: -15 bis 40C

gem. VDE 0108 ta: -15 bis 40C

Zehner

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

Kontakte (1 / 2) + (3 / 4) ffnen bei Netzausfall

6
7

INOTEC

INOTEC

INOTEC

Einer

DP / B.1

L1 L2 L3

Adresse 1 bis 31
4
5

6
7

DP / B.1

L1 L2 L3

Adresse 1 bis 31
4
5

6
7

DP / B.1

L1 L2 L3

Adresse 1 bis 31
4
5

6
7

8 8

8 8

8 8

19

System components and options

CPS 220/64/SV

MTB The MTB-remote mimic panel (MTB/AP = wall mounting, MTB/UP = recessed wall-/panel mounting) are used for external status- and failure indication of emergency lighting systems. Furthermore it allows to block the system via the integrated key-switch. Functions: Key-switch free programmable for: maintained and non maintained light ON / OFF maintained light ON / OFF

CPS-MTB For external status and failure indication of up to 16 connected CPS 220/64 systems using a threeconductor RTG-BUS (system- / circuit- / luminairestatus). Manual and automatic function and battery duration test is activated centrally at freely denable intervals. The status of the emergency lighting systems is displayed via three status LEDs and on the OLED graphic display in clear text. It is also indicated acoustically by the integrated buzzer. Functional displays: Green LED Operation Yellow LED Battery operation Red LED Fault (general) The status of the emergency lighting devices can also be signalled by four volt-free outputs: Operation Battery operation Failure Free programmable Current loop to block or unblock the connected emergency lighting systems. EMC protection in acc. with EN 55015

Green LED - operation Yellow LED - battery operation Red LED - failure (battery / luminaire)
Connection to RIF-module of CPS-system; max cable length with 0,5mm 500m Voltage: UN= 24V DC +/-10% Mode: Permanent operation Temp.-range: -15C ... +40C Protection: IP30 Housing: Stainless steel/polycarbonate EMC protection to EN 55015

Displayed:

Wall mounting:
43
Betrieb Operation

90

Ein/On

Aus/Off

INOTEC

58

Strung Failure

-Betrieb -Operation

Recessed wall mounting:

Notlicht
Betrieb Batt.-Betrieb Ein Aus INOTEC

230

38

186
58 74

Strung

20

90

CPS 220/64/SV

Luminaire monitoring and supply modules

INOSTICK For programming and saving the CPS device conguration. This conguration is simple to create or change in Microsoft Windows using the programming software provided. System requirements: Microsoft Windows XP, Microsoft Windows Vista Min. Microsoft.NET Framework 2.0 Min. resolution: 1024 x 768 pixel INOPRINT available at the parallel port of a CPS-system can be stored as a text le on INOPRINT. Via PC / USB-interface the information can be stored and printed.

J-SV-Modul/S J-SV-Modul.2/S J-SV-Modul.3/S J-SV-Modul.4/S J-SV-Modul.L/S Single luminaire monitoring module for uorescent- (T16/T5) compact uorescent, halogen and incandescent lamps. With easy accessible address switch, JOKER function and individual lamp monitoring. This module features a sense-input or an inverted phase monitor too. The JOKER/S function allows luminaires to be operated via these J-SV-modules in maintained, non-maintained and switched mode on the same nal end circuit. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems. Voltage: 230 V AC, 50/60 Hz 220 V DC, 20 % Perm. temp.: -15C ... +65C EMC protected to EN 55015 Dimension: H = 28, W = 90, D = 40 (mm) (JSV-Modul/S, J-SV-Modul.2/S, J-SVModul.3/S, J-SV-Modul.4/S) H = 17,9, W = 240,4, D = 26,4 (mm) (J-SVModul.L/S)

PE N L

General lighting

Light switch J-SV-Modul.2/S NS L+ J-SV-Modul.3/S NL+ J-SV-Modul.4/S L+


N- J-SV-Modul/S NLS

Fluorescent lamps with high frequency electronic ballast standard bulbs or halogen lamps

Input

NS LS NL+

J-SV-Modul.L/S

NL+

From CPS 220

Fluorescent lamps with high frequency electronic ballast standard bulbs or halogen lamps

21

Function, design and features


Battery current for lamps used for emergency / safety lights Table 1 Data for INOTEC high frequency ballasts during mains- and battery operation. Lamp type T 16 Base G5 INOTEC EVG 4-6W / 4-13W 4-6W / 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 4-13W 18W 13W 18W 18W 36W 58W Lamp 4W 6W 8W 13W 5W 7W 9W 11W 10W 13W 18W 13W 18W 18W 36W 58W 18W 18W IBat. Mains [mA] load [VA] 20 4,2 25 6,3 33 8,4 44 14 24 5,3 26 7,4 33 10 44 12 35 11 44 14 90 19 44 14 90 19 90 19 100 / 150 37 140 / 235 90 90 60 19 19

CPS 220/64/SV

TC-SEL

2G7

TC-DEL

G 24 q1 G 24 q2 GX 24 q1 GX 24 q2 G 13

TC-TEL T 26

(50% / 100% Light output) (50% / 100% Light output)

TC-F TC-L

2 G 10 2 G 11

18W 18W

Table 2 Data for INOTEC LED luminaire with Power LED. (J-ET 9/24 ... SV) For specic luminaire details see luminaire catalogues. Qty. LED 24V 6x0,5W 4x0,5W 4x1W 3x1W 2x1W 1x1W IBat. [mA] 125 100 200 150 115 80 Qty. LED 230V 1 2 3 4 5 6 IBat. [mA] 12 17 32 25 18 20 Mainload [VA] 4,8 8,3 9,5 81 6,3 7,2

Table 3 Data for glow wire lamps (AGL) and halogen lamps with electronic transformer. 220V Glow wire lamp 7W 15 W 25 W 40 W 60 W 75 W 100 W IBat. [mA] 30 70 110 180 270 340 450 Halogen lamp 20 W 35 W 50 W 75 W 100 W IBat. [mA] 115 210 285 420 560

22

CPS 220/64/SV

Function, design and features


Table 4 Battery data Housings, dimensions and discharge currents Capacity 12,0 16,6 24,1 40,0 55,0 56,0 65,9 85,1 100,0 102,0 115,0 153,6 205,2 Weight [kg] Housing Max. discharge current [A] Blocks Block Total 8h 3h 2h 1h 1,42 2,95 4,14 7,26 18 3,6 64,8 1*1 2,05 5,20 7,60 13,80 18 5,9 106,2 1*1 2,95 7,20 9,76 17,00 18 9,4 169,2 1*1 1 4,71 9,82 13,78 24,16 18 13,3 239,4 1* 6,49 13,52 18,96 33,24 18 17,5 315,0 1*1 6,70 15,70 21,40 38,70 18 19,5 351,0 1*1 8,06 19,10 28,30 53,20 18 23,7 426,6 1*1 10,30 23,90 34,50 63,50 18 30,0 540,0 2*2 11,79 24,58 34,49 60,45 18 30,5 549,0 2*2 2 12,29 28,60 38,80 69,80 18 33,1 596,0 2* 13,80 34,00 50,20 91,00 18 39,6 712,8 2*2 46,4 835,2 Rack 18,29 41,40 56,50 102,20 18 67,2 1.209,6 Rack 24,79 58,20 79,20 143,20 18

*1 Battery housing included in CPS assembly *2 1 Battery housing included in CPS assembly

Table 5 Chargers and ventilation Recharging 12 hours / 80% Capacity C10 -1,8V/Z 12 16,6 24,1 40,0 55,0 56,0 65,9 85,1 100,0 102,0 115,0 153,6 205,2 Qty. charger (3h- discharge) 3,0A 7,5A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 Free airow [m/h] 0,06
0,09 0,13 0,22 0,30 0,30 0,36 0,46 0,54 0,55 0,62 0,83 1,11

Ventilation [cm]
1,70 2,60 3,70 6,20 8,40 8,40 10,10 12,90 15,20 15,40 17,40 23,30 31,10

Table 6 Fuse protection mains supply Over all connection power Fuse protection Min. conductur cross-section to 8 kVA 35A 6mm 8 - 11 kVA 11 - 14 kVA 14 - 18 kVA 18 - 22 kVA 50A 63A 80A 100A 10mm 16mm 25mm 35mm

The specication are min. conductur cross-sections. For the max. permissible line drop the dimensioning of the conductor is to be made according to the distance and the connection power. (max. line drop: 3%)

23

INOTEC Sicherheitstechnik GmbH Am Buschgarten 17 D - 59 469 Ense Tel +49 29 38/97 30-0 Fax +49 29 38/97 30-29 info@inotec-licht.de www.inotec-licht.de

24

Sicherheitstechnik GmbH

707 075