Вы находитесь на странице: 1из 150

Programming Troubleshooting Guide

IntelliPak I and II
Commercial Single Zone Rooftop Air Conditioner with Variable Air Volume (VAV) Controls

Model Number

IntelliPak I models

S*HF*20-75, S*HL*20-75, S*HG*90-130, S*HK*90-130 Ton W*HB, W*HE S*HJ090-162, W*HCA-C

IntelliPak II models

April 2010

RT-SVP04F-EN

Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Commonly Used Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 UCM Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)

10 Unit Operation Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Password Protected Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

System Operating Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25


STATUS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

System Programming SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53


SETUP Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Ventilation Override Definitions (with VOM installed) . . . . . . . . . . . . . . . . . . 66 Temperature Input Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

System Programming SETPOINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89


SETPOINT Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101


CONFIGURATION Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

System Testing & Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108


SERVICE MODE Menu (Local Human Interface only) . . . . . . . . . . . . . . . . . . . 108 DIAGNOSTICS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116 Failure Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Communication Link Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

RT-SVP04F-EN

2010 Trane All rights reserved

General Information
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.

Table 1.
Act = active

Acronyms
HGBP = Hot Gas Bypass HGP = Hot Gas Bypass Hi = high HI = where all caps Human Interface HO = History Only (Diagnostic) HVAC = heating, ventilation and air conditioning ICS = Integrated Comfort System IGV = inlet guide vanes INFO = Information Only (Diagnostic) I/O = input/output Indep = Independent IOM = installation/operation/ maintenance manual IPC = interprocessor communications IPCB = interprocessor communications bridge (module) IWC = inches water column LH = left-hand Lo = low
LCI = LonTalk Communication Interface

AH = Air Handler Annunc = Annunciator AS = AirSide Aux = auxiliary BAS = building automation systems BCI = BACnet Communication Interface CCFM = hundreds of cubic-feet-per-minute CCW = counterclockwise cfm = cubic-feet-per-minute Cfg = Configured, configuration ckt = circuit Cmd = command Comp (s) = compressor, compressors Cond = condenser, condensers Config = configured, configuration Ctrl = control CV = constant volume Cy = cycle

LCI-I = LonTalk Communication Interface for IntelliPak Module

CVDA = Constant Speed Fan (CV)/Discharge Air Temp Control Manif = manifolded CVZT = Constant Speed Fan (CV)/Zone Temperature Control Max = maximum CW = clockwise DCV = Demand Control Ventilation Dflt = default Diag = diagnostic Dmpr = damper DWU = Daytime Warm-up E/A = exhaust air ECEM = exhaust control/enthalpy module Econ = economizer, economizing Ent = entering Evap = evaporator F/A = fresh air Funct = function GBAS = generic building automation system (module) Min = minimum Misc = miscellaneous MCM = Multiple Compressor Module MDM = Modulating Dehumidification Module Mod = modulating MPM = Multi-Purpose Module MWU = morning warm-up NSB = night setback panel Num = number O/A = outside air Occ = occupied OVRD = override PAR = Partial System Disable, Auto Reset (Diagnostic) PMR = Partial System Disable, Manual Reset (Diagnostic) Pos = position

RT-SVP04F-EN

General Information

Pot = potentiometer PPM = parts per million HEAT = where all caps HEAT (module) Propor = proportional psig = pounds-per-square-inch gauge pressure PWS = part-winding start R/A = return air Refrig = refrigerant RH = right-hand RHI = Remote Human Interface rpm = revolutions-per-minute RT = rooftop unit RTM = rooftop module SA = supply air SAP = supply air pressure Sat = saturated SCM = Single Compressor Module Setpt = SETPOINT SF = supply fan SRC = source Stg = stage Stnd = standard STP = SETPOINT Sw = switch

SZ = single-zone (unit airflow) TCI = Tracer communications interface (module) Press = pressure Temp = temperature UCM = Unit Control (Module) Unocc = unoccupied VAV = variable air volume VCM = ventilation control module VDC = volts DC Ventil = ventilation VFD = variable frequency drive VOM = ventilation override module VVDA=Variable Speed Fan (VAV)/Discharge Air Temp Control W/ = with w.c. = water column WU = warmup XL = across-the-line start

Note: Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are trademarks of Echelon Corporation. Note: BACnet is a registered trademark of the American Society of Heating, Refrigeration and Air-conditioning Engineers Inc. (ASHRAE.)

Glossary of Terms
Carefully review these definitions since they are used throughout this document and the Installation, Operation, Maintenance Guide (IOM). Knowledge of these terms is essential in gaining an understanding of how these units operate. Active SETPOINT. The SETPOINT which is currently being used for control by the SETPOINT source selection. BACnet. An open, device networking communications protocol for controls. This protocol utilizes BACnet and ANSI/ASHRAE Standard 135-2004 protocol which provides building owners the capability to connect various types of building control systems or subsystems together.

RT-SVP04F-EN

General Information

Comparative Enthalpy. An economizer control strategy which compares return air enthalpy with outdoor enthalpy. The air with the least heat content (enthalpy) is used for cooling. Compressor Protection Switch. A pressure switch installed on the suction line that prevents compressor operation below the switchs SETPOINT. The purpose is to prevent no-flow scroll compressor operation. Comm3/4. Trane proprietary network communication protocol. Comm5. Trane's implementation of LonTalk or BACnet (an open network communication protocol). Condenser Pressure. The saturated condenser pressure measured on each circuit's(2) condenser section on Evaporative Condenser units. Condenser pressure is converted to Saturated Condenser Temperature for display on the Human Interface. The data from these sensors is used in head pressure control. Control Band. The range of temperatures or pressures which would normally be maintained by the various control functions. Control Point. The value of a SETPOINT that an algorithm is using at any given time. Deadband. As applied to SA temp control, this refers to a range of temperatures equally spaced above and below the SA temp control point in which the control algorithm is satisfied. Dehumidification Override High Zone Temp. The temperature in the critical zone on VAV units where Dehumidification is disabled to prevent over-heating the space due to excess reheat. Dehumidification Override Low Zone Temp. The temperature in the critical zone on VAV units where Dehumidification is disabled to prevent sub-cooling the space due to insufficient reheat. Demand Control Ventilation (DCV). An ASHRAE compliant ventilation scheme that varies the Outside Air Damper minimum position or Fresh Air Flow (TRAQs) between minimum and maximum ventilation SETPOINTs based on CO2 level. Dry Bulb. An outdoor temperature above which economizing will be disabled (unless comparative enthalpy is the economizer control type being used.) Economizer Zone Temp SETPOINT Suppression. a parameter used for setting the Zone Temp SETPOINT at a lower value than the mechanical cooling zone temp SETPOINT. Emergency Stop. A binary input on the RTM which allows unit shutdown with manual reset when connected to a field-supplied switch. Energy Recovery Wheel. A device incorporating a specially coated rotating disc that spins across both outdoor and exhaust air streams transferring to or removing energy from the incoming outdoor air prior to mixing with return air to increase unit efficiency.
RT-SVP04F-EN 5

General Information

Evap Diff. Evap Diff is a calculated value indicating performance of a refrigeration system. It is calculated by determining the difference between the Entering and Leaving temperatures of the evaporator. If this value rises too high it may indicate a problem with the system. External Stop. A binary input on the RTM that allows unit shutdown, with automatic reset, when connected to a field-supplied switch. Hot Gas Bypass. A feature to reduce a refrigeration circuit's cooling capacity by bypassing hot discharge line refrigerant directly to the evaporator coil of the system to more effectively operate in low load conditions. Humidification Control. During modes of continuous fan operation a relay is energized when the Humidity measured in the controlled space drops below an adjustable Humidification SETPOINT. The humidifier device is a user supplied device placed in the supply air stream. LonTalk. An open, device networking communications protocol for controls. This protocol is defined in ANSI approved standard EIA/CEA-709.1-A-1999. Low Ambient Compressor Lockout. A function which prevents compressor operation at low outdoor ambient temperatures. Night SetBack (NSB). Applies to the control of the rooftop unit during unoccupied periods. Also refers to the NSB panel, a communicating wall sensor with night setback capability. Reference Enthalpy. An outdoor enthalpy value above which economizing will be disabled. Remote Human Interface. A human interface module designed to be mounted remotely from the unit. There are some functional differences between a unit mounted and a remote mounted human interface module. Reset Amount Maximum. The maximum amount of reset allowed. Reset End Temperature. The temperature at which the maximum reset amount will occur. Reset Start Temperature. The temperature at which reset will begin. Return Fan Control. Return Fan Control is a feature which allows units to operate at a higher external or duct system static pressure, or to reduce the load (horsepower requirement) on the supply fan motor. The fan is placed in the return air path. Return Fan Plenum Pressure. The area between the Exhaust and Return Dampers and the outlet of the Return Fan defines the return plenum. The absolute static pressure measured in this area is the Return Fan Plenum Pressure.

RT-SVP04F-EN

General Information

Return Plenum Pressure High Limit. This control feature, available on all return fan options, shuts the supply fan and return fan off if the pressure in the return plenum exceeds a non-adjustable SETPOINT of 3.5 iwc. Space Pressure. The pressure in the building as measured by the Space Pressure Transducer, referenced to outside (atmospheric) pressure. Supply Air Pressure High Limit. A pressure limit to prevent unit casing and/or ductwork over pressurization. Statitrac. A trademark for control of space pressurization. Supply Air Pressure. The pressure in inches water column (IWC) of the supply duct plenum or outlet as measured by the Supply Air Pressure Transducer, referenced to local outside (atmospheric) pressure. Supply Air Tempering. Turning on heat when the supply air temperature drops below a preset value usually due to cold outside air being brought in to provide building ventilation. Supply Air Temperature Control Point. The revised value of supply air temperature SETPOINT after supply air temp reset has been applied. Supply Air Temperature Reset. A function that shifts the SA Temp SETPOINT an amount based on the value of another parametertypically Zone Temp or Outdoor Air Temp. The purpose of this function is to lower unit capacity to better meet load requirements. Target. Dynamic control point the unit is controlling to at any given time.

UCM Control System


Trane Large Commercial Rooftop Units are controlled by a microelectronic control system that consists of a network of modules and are referred to as Unit Control Modules (UCM). The unit size, type (CV or VAV), heating functions, peripheral devices, options, exhaust capabilities, etc. determine the number and type of modules that a particular rooftop unit may employ. The UCM receives analog and binary inputs, then processes this information and supplies outputs in the form of modulating voltages, contact closures, etc. to control damper actuators, fan motors, compressors, valves, electric heating coils and other electrical devices in the unit to maintain set comfort levels. The UCM provides some equipment protection functions both directly and indirectly, such as duct pressure limits and compressor lockouts. Listed below are the various modules that may be employed in a UCM control system.

RT-SVP04F-EN

General Information

Rooftop Module (1U1 IntelliPak II) (1U48 IntelliPak I)


(Standard on all units) The RTM is the central processor of the system. It continuously receives information from the other unit modules, sensors, the remote control panel, and customer supplied relays. It then interprets this information and responds to cooling, heating, and ventilation requests by directing the other modules in the system to energize the proper unit components. It also directly initiates supply and exhaust fan operations, and economizer operation.

Compressor Module (SCM/MCM) (IU3 IntelliPak II) (1U49 IntelliPak I)


The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the compressor operation through feedback information it receives from various protection devices.

Heat Module (1U6 IntelliPak II) (1U50 IntelliPak I)


(Standard on all heating units) The Heat module directs the units heater to stage up and down to bring the temperature in the controlled space to within the applicable heating SETPOINT.

Exhaust/Comparative Enthalpy Module (1U5 IntelliPak II) (1U52 IntelliPak I)


(Option - used with Statitrac and/or comparative enthalpy) The ECEM receives data from the return air humidity sensor, the return air temperature sensor, and the return air space pressure transducer to control the economizer, exhaust fan and the exhaust dampers to maintain set space pressure.

Ventilation Control Module (7U14 IntelliPak II) (3U218 IntelliPak I)


(Option - used with TRAQ dampers, DCV, and Outdoor Air Preheat) The VCM receives data from two velocity pressure sensors associated with front and back TRAQ assemblies to measure fresh air flow entering the unit. These measurements are converted to CFM and added to give total fresh air flow. This value can be used for monitoring purposes, to maintain flow to a minimum fresh air flow SETPOINT, or to maintain appropriate CO2 levels in the controlled space using its space CO2 sensor input and the DCV feature. Without TRAQ assemblies installed the VCM can use DCV and the CO2 sensor input to control OA Damper minimum position to maintain CO2 levels in the space. A preheat control relay output is also provided on this module to maintain tempered outdoor air during ventilation using the VCM Auxiliary Temperature input. The preheat unit is user-supplied.

Multi Purpose Module (1U9 IntelliPak II) (1U105 IntelliPak I) (Optional - used with Return Fan Control)
The MPM supports the function of return plenum pressure control by providing inputs for measuring return plenum pressure, calibrating that reading, and providing an output to control the return fan speed (if variable speed configured) in response to control algorithm requests.

RT-SVP04F-EN

General Information

Modulating Dehumidification Module (1U15 IntelliPak II) (1U107 IntelliPak I) (Optional - used with Dehumidification Control)
The MDM supports specific control inputs and outputs for Modulating Dehumidification control including modulating Reheat and Cooling valve control as well as the Reheat Pumpout Coil Relay output.

Generic Building Automation System Module (1U10 = GBAS 0-5V, 1U11 = GBAS 0-10V IntelliPak II) (1U51 = GBAS 0-5V/0-10V IntelliPak I) (Optional - used with Non-Trane Building Control System)
The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the unit and accepts external SETPOINTs in form of analog inputs (0 - 5 V or 0 - 10 V depending on the module selected) and a binary Input for demand limit. Five (5) binary outputs are available on 0 - 5 V modules. One (1) binary output and four (4) analog outputs are available on the 0 - 10 V modules. Refer to the Field Installed Control Wiring section of the Unit Installation, Operation, Maintenance Manual (IOM) for the control wiring to the GBAS module and the various desired SETPOINTs with the corresponding DC voltage inputs.

Ventilation Override Module (VOM) (1U8 IntelliPak II) (1U53 IntelliPak I) (Optional - used on units with special ventilation requirements)
The Ventilation Override module can control the units air handling functions to perform customer specified functions such as space pressurization, exhaust, purge, unit off, etc.

Interprocessor Communications Board (IPCB) (1U12 IntelliPak II) (1U55 IntelliPak I) (Optional - used with Optional Remote Human Interface)
The Interprocessor Communication Board expands communications from the unit UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2 Off , Switch 3 On .

BACnet Communication Interface Module (BCI) (1U66 IntelliPak II) (1U104 IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building Automation Systems)
The BACnet Communication Interface module expands communications from the unit UCM network to a Trane Tracer Summit, or a 3rd party building automation system that utilizes BACnet, and allows external SETPOINT and configuration adjustment and monitoring of status and diagnostics.

Lontalk Communication Interface Module (LCI) (1U7 IntelliPak II) (1U65 IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building Automation Systems)
The LonTalk Communication Interface module expands communications from the unit UCM network to a Trane Tracer Summit, or a 3rd party building automation system that utilizes LonTalk, and allows external SETPOINT and configuration adjustment and monitoring of status and diagnostics.
RT-SVP04F-EN 9

General Information

Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)
The Human Interface (HI) Module illustrated in Figure 1 is the device which enables the customer, building owner, or contractor, to communicate to the Rooftop unit the necessary parameters for unit operation such as cooling and heating SETPOINTs, demand limiting, ventilation override modes, etc. The local (unit mounted) Human Interface and the Remote Human Interface Panel functions are identical, except for Service mode which is not available on the Remote Human Interface Panel. The local HI Module is located in the units main control panel. A small door located in the units control panel door allows access to the HI Modules keypad and display window. There is a 2 line by 40 character LCD screen which provides status information for the various unit functions as well as menus used to set or modify the operating parameters. There is a 16 key keypad adjacent to the LCD screen, which allows the operator to scroll through the various menus and make adjustments to the SETPOINTs, etc. The information displayed in the LCD window will be top-level status information unless the operator initiates other displays. At power-up, the Human Interface LCD will display one of four initial screens illustrated in the General Status section. 1. Unit Status (Unit Off or Stopped) (The unit is configured and operational, but is not running). This screen shows state, mode, and function information when the unit is off or stopped.

2. Unit Status (Unit On) (The unit is configured and operational, and is running). This screen shows state, mode, and function information when the unit is on. 3. VOM Active (a ventilation override command was received) This screen shows that the unit is in a Ventilation Override Mode. 4. No Configuration (the unit needs to be configured). This screen shows that required configuration data is missing. The LCD screen has a backlight that makes the information easier to read. The light will go out if no keys are pressed for 30 minutes. If it goes out, simply press the STATUS key.

10

RT-SVP04F-EN

General Information

Figure 1.

Human Interface Module

Menu Keys
The six keys illustrated in Figure 2 in the MENU area (STATUS, SETPOINTS, SETUP , CONFIGURATION, DIAGNOSTICS, and SERVICE MODE) are used to bring up the various interactive menus where the user inputs and accesses unit operating data. Pressing these keys will display the initial screen for the menu designated by the keys name. The following information describes the keys and their functions when viewing the various menus. If no key is pressed for 30 minutes while the LCD is displaying a menu screen, it will revert back to the unit operating status screen.

STATUS Key
Pressing the STATUS key causes the LCD to display the operating status screen; i.e. On , Unit Stop , External Stop , Emergency Stop , Service Mode . Pressing the NEXT key allows the operator to scroll through the screens which provide information such as air and refrigerant temperatures, humidity levels, fan operation, compressor operation, heater operation, economizer positioning, exhaust operation, as well as heating, cooling, and compressor lockout SETPOINTs. Pressing the STATUS key while viewing any of the data screens will cause the LCD to go back to the operating status screen.
RT-SVP04F-EN 11

General Information

SETPOINTS Key
Pressing the SETPOINTS key will cause the LCD screen to display the first of the SETPOINT screens where the operator will designate default temperature and pressure SETPOINTs. While scrolling through the SETPOINT screens, pressing this key again will cause the LCD to display the first SETPOINT screen.

DIAGNOSTICS Key
Pressing the DIAGNOSTICS key at any time will allow the operator to view any unit function failures. The LCD screen will display one of the diagnostic screens (depending on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the screen is displaying diagnostic information, it will revert back to the operating status display.

CONFIGURATION Key
Pressing the CONFIGURATION key will cause the LCD screen to display the first of the configuration screens where the operator will designate unit configuration data such as unit type, capacity, system control, etc.... This information was programmed at the factory. Pressing the configuration key at any level in the configuration menu will display the first configuration screen. Note: This key should be used if the units configuration data is lost or new options are added in the field, and to view current configuration.

SETUP Key
Pressing the SETUP key will cause the LCD screen to display screens where the operator will designate various operating parameters such as temperature and pressure ranges, limits, percentages, SETPOINT source selections, and sensor input definitions for the control of the rooftop units various operating modes. Pressing the SETUP key at any level in the SETUP menu will display the first SETUP screen.

SERVICE MODE Key


Pressing the SERVICE MODE key causes the LCD to display the first of the service test mode screens showing various unit components which may be turned on or off for the particular test being performed. Once the status of these components is designated, the LCD will display screens that allow the operator to designate the TEST START time delay for each test.

Data Manipulation Keys


The six data manipulation keys illustrated in Figure 2, (ENTER, CANCEL, + (Plus), (Minus), PREVIOUS, and NEXT are used to modify the data within the screens (change values, move the cursor, confirm choices, etc....)

12

RT-SVP04F-EN

General Information

ENTER Key
This key will confirm the new values that were designated by pressing the + (Plus) or (Minus) keys at all edit points. When viewing status and diagnostics screens, it has no function.

CANCEL Key
After changing data, at an editable screen, but before confirming it with the ENTER key, pressing the CANCEL key will return the data to its previous value. This key shall also function to clear active diagnostics.

+ (Plus) Key
When viewing a SETPOINT screen, this key will increase the temperature or pressure value of the SETPOINT. When working with a status menu, it will add the current status display to the custom menu. When viewing the SETUP or service test screens, it will increase SETPOINTs or toggle choices On or Off at each edit point.

- (Minus) Key
This key when viewing the SETPOINT screen will decrease the temperature or pressure value of the SETPOINT. When viewing the SETUP or service test screens, it will decrease SETPOINTs or toggle choices On or Off at each edit point. When viewing the custom menu, pressing the - (Minus) key will remove the status screen from the custom menu. When viewing diagnostics screens it has no function.

PREVIOUS Key
Pressing the PREVIOUS key causes the LCD to scroll backwards through the various displays for each menu. At displays with multiple edit points, it moves the cursor from one edit point to another.

NEXT Key
Pressing the NEXT key causes the LCD to scroll forward through the various displays for each menu. At displays with multiple edit points it moves the cursor from one edit point to another.

Unit Operation Keys


AUTO Key
Pressing the AUTO key at any time will cause the display to go to the top level status display and, if the unit is shutdown, will cause the unit to begin operation in the appropriate mode no matter what level in the menu structure is currently being displayed. If the current display is an editable display, the AUTO key will confirm the desired edit.

RT-SVP04F-EN

13

General Information

STOP Key
Pressing the STOP key will cause the unit to transition to the stop state. If the current display is editable, pressing the STOP key will cancel the desired edit.

TEST START Key (SERVICE)


Pressing this key while viewing any screen in the SERVICE Mode menu will start the service test. When viewing status, SETUP , SETPOINT, and diagnostics screens, it has no function.

CUSTOM Key
The Custom menu is simply a status menu that contains screens that the user monitors most frequently. The Custom menu can only contain five status screens. To create the Custom menu, press the STATUS key, followed by the NEXT key (this brings up the initial status screen). If you want to add this screen to the Custom menu, press the + (Plus) key, if not, press the Next key again until a status screen appears that you would like to add to the Custom menu. Pressing the + (Plus) key while viewing any of the various status screens will add that screen to the Custom menu. Once the Custom menu is programed it can be accessed by pressing the CUSTOM key. To remove a status screen from the Custom menu, press the CUSTOM key, then press the NEXT key until the status screen that you want to remove appears, then press the - (Minus) key.

14

RT-SVP04F-EN

General Information

General Status Display


Anytime the rooftop unit is powered up, or the STATUS, AUTO, or STOP keys are pressed, the unit mounted Human Interface will display one of the following four general status display screens. The operator will then be able to enter keystrokes which will allow him to navigate through a set of menus and submenus in order to provide/ access various monitoring, SETUP , and configuration information. The Human Interface will not display screens or parts of screens for which the unit is not configured.

Figure 2.

Human Interface Keypad

Unit Off or Stopped


If at power up the unit is not running, the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP , CONFIGURATION, and SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.

RT-SVP04F-EN

15

General Information

Stop by Network Initializing

Supply Fan ON Diagnostics

Used With: Top Status Display (Shown when unit is off or stopped) Possible Values: Top/Left field: Unit Off, Unit Stopped, External Stop, Emergency Stop, Stop by Network, Unit Starting, Service Mode Off; Top/Right field: Supply Fan OFF, Supply Fan ON; Bottom/Left field: (Blank), Shutdown, Initializing, Freeze Avoidance Active; Bottom/Right: (Blank), (Diagnostics)

Unit Off Unit Stopped External Stop Emergency Stop Stop by Network Unit Starting Service Mode Off

(Blank) Shutdown Initializing Freeze Avoidance Active

(Blank) (Diagnostics)

Unit On
If the unit has entered an operating state (running), the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional keys are the six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP , CONFIGURATION, and SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.

16

RT-SVP04F-EN

General Information

Freeze Avoidance OA Flow (Blank) CVZT VVDA CVDA Range 0-5980 CCFM (Blank)

ON OFF

VVDA
___________

OA Flow ___ CCFM Supply Fan ________ ____ ______

Occupied Unoccupied Morning WU Daytime WU Standby Shutdown Occupied TOV Initializing (Blank) Tempering

Heat Cool OA Dmpr Dehumid Purge Humidify (Blank)

1-6 1-6 0-100%

(Blank) Diagnostics

Emergency Override Active (units with LCI or BCI module)


If the unit has entered an Emergency Override mode of operation, one of the following displays will appear on the Human Interface LCD screen.

Ventilation Override Mode PRESSURIZE Ventilation Override Mode DEPRESSURIZE Ventilation Override Mode PURGE Ventilation Override Mode SHUTDOWN Ventilation Override Mode FIRE

RT-SVP04F-EN

17

General Information

VOM Active
If at power up the unit is running and has entered a Ventilation Override mode of operation, the following display will appear on the Human Interface LCD screen.
VO Mode in Operation (A,B,C,D,E)

Ventilation Override Mode ______ _____________

Trouble Indicator (Blank) (Diagnostics)

No Configuration
If at power up the unit has not been programmed with the necessary configuration data for normal unit operation, the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional key is the CONFIGURATION key. Note: This screen will only appear when the RTM has been field replaced. Refer to the Configuration Menu.

No Configuration Present Press Configuration Key

Factory Presets
The UCM controlled unit has many operating functions which are preset at the factory, but may be modified to meet the unique requirements of each job. The following list identifies each of the units adjustable functions and the value assigned to it. If these factory presets match the applications requirements, simply press the AUTO key at the Human Interface module to begin unit operation (after completing the Pre-Start and Start-Up procedures in the Installation, Operation, and Maintenance manual). If the application requires different settings, turn to the listed page beside the function, press the designated function menu key, then press and hold the NEXT or PREVIOUS key until its screen appears on the LCD. Once the proper screen appears, simply follow the programming instructions given below the applicable screen in this manual. Note: Record any changes made to the factory-preset values in the corresponding space provided.

18

RT-SVP04F-EN

General Information

Adjustable Function Control Parameters Default system mode Demand limit definition for cooling Demand limit definition for heating Economizer control enable type Exhaust enable point Morning Warmup type Supply air low limit Unit Control Coil Frost Cutout Temp Evap Temperature Limit OA Flow Calibration Gain (Front) OA Flow Calibration Offset (Front) OA Flow Calibration Gain (Back) OA Flow Calibration Offset (Back) OA Flow Calibration Data - Altitude: Unit Address (Comm3/Comm4 only) Default SETPOINTs Economizer drybulb enable SETPOINT Low ambient compressor lockout (Std. units) Low ambient compressor lockout (Low ambient units) Occupied zone temp SETPOINT - cooling Occupied zone temp SETPOINT - heating Space pressure - deadband Space pressure - SETPOINT Occ Dehumidification Occ Dehumid Hysteresis Offset Unocc Dehumidification Unocc Dehumid Hysteresis Offset Supply Air Reheat Setpoint Supply Air Reheat Deadband Maximum Reheat Valve Limit Dehumid Ovrd High Zone Temp Stpt Dehumid Ovrd Low Zone Temp Stpt Cond Coil Purge Interval Unoccupied zone temp - cool Unoccupied zone temp - heat Unoccupied zone temp - morn warmup Min OA Flow - SETPOINT w\VCM Min OA Flow - deadband Preheat actuate temp

Factory Preset Auto None None Drybulb 25% Full 50 deg F Local 30 deg F 35 deg F 1.0 0 CFM 1.0 0 CFM 0 feet 1

Changed To

To adjust Press... SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP

75 deg F 50 deg F 0 deg F 74 deg F 71 deg F .04 iwc 0.08 iwc 60% 5% 60% 5% 70 F 4F 85% 75 F 68F 90 min 85 deg F 60 deg F 72 deg F Set per unit size Set per unit size 35 deg F

SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS

RT-SVP04F-EN

19

General Information

Design Min CO2 (DCV) DCV Min CO2 DCV Min OA Flow Deadband Design Min OA Flow (DCV) DCV Min OA Flow Design Min OA Damper Position(DCV) DCV Min OA Damper Position OA Damper Min Position (non-DCV) Hydronic Heat Freeze Avoidance Open To: Recovery Frost Avoidance Setpoint Functions enable/disable Compressor lead/lag Adjustable Function Morning warmup Supply air tempering Unoccupied economizer Unoccupied mechanical cooling Unoccupied heating Occupied Dehumidification Unoccupied Dehumidification Demand Control Ventilation Occupied Humidification Unoccupied Humidification GBAS Input/Output Definitions... GBAS analog input definitions GBAS output definitions Information format Text displays Unit displays RTM alarm output definitions Sensor source selection for... Monitor Morning warmup Occupied zone control Unoccupied zone control Space Humidity Control Dehumid OVRD Zone Temp SETPOINT source selection for... Morning warmup Occupied zone cooling 20

1000 PPM 8001/4002 PPM 5 CCFM 220 CCFM 67 CCFM 15% 5% 15% 0% 27F Enable Factory Preset Enable Enable Enable Enable Enable Enable Enable Disable Disable Disable Changed To

SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETPOINTS SETUP To adjust Press... SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP

Not Assigned

SETUP SETUP

English English Any Active Diagnostic

SETUP SETUP SETUP

RTM Zone Temp RTM Zone Temp RTM Zone Temp RTM Zone Temp RTM Space Humidity RTM Zone Temp

SETUP SETUP SETUP SETUP SETUP SETUP

Default Default

SETUP SETUP RT-SVP04F-EN

General Information

Occupied zone heating Space Pressure Unoccupied zone cooling Unoccupied zone heating Economizer Dry Bulb Enable Occupied Dehumidification Unoccupied Dehumidification Supply Air Reheat OA Damper Actuator (if equipped) Actuator SETUP Max stroke time Max voltage Min voltage Exhaust Damper Actuator (if equipped) Actuator SETUP... (Direct/reverse action) Max stroke time Max voltage Min voltage

Default Default Default Default Default Default Default Default

SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP

DIRECT 30 sec 10 VDC 2 VDC

SETUP SETUP SETUP SETUP

DIRECT 30 sec 10 VDC 2 VDC Factory Preset Direct Acting 60 seconds 10 VDC 2 VDC

SETUP SETUP SETUP SETUP To adjust Press... SETUP SETUP SETUP SETUP

Adjustable Function Hydronic Heat Actuator (if equipped) Actuator SETUP... (Direct/reverse action) (Max stroke time) (Max voltage) (Min voltage) Lo Ambient Damper Actuator Ckt#1 and Ckt #2 (if equipped) Actuator SETUP... (Direct/reverse action) (Max stroke time) (Max voltage) (Min voltage) Cond Fan VFD Ckt #1 Actuator SETUP Max Stroke Time Max Voltage Min Voltage Cond Fan VFD Ckt #2 Actuator SETUP Max Stroke Time Max Voltage Min Voltage

Changed To

Direct Acting 60 seconds 10 VDC 2 VDC Direct Acting 60 sec 10 VDC 0 VDC Direct Acting 60 sec 10 VDC 0 VDC

SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP SETUP

RT-SVP04F-EN

21

General Information

Supply Fan IGV/VFD (if equipped) Actuator SETUP Max Stroke Time Max Voltage Min Voltage Exhaust Damper/VFD (if equipped) Actuator SETUP Max Stroke Time Max Voltage Min Voltage Return Fan VFD (if equipped) Actuator SETUP Max Stroke Time Max Voltage Min Voltage Exhaust bypass damper Actuator SETUP Max Stroke Time Max Voltage Min Voltage Outdoor air bypass damper Actuator SETUP Max Stroke Time Max Voltage Min Voltage Modulating Gas Heat Actuator (if equipped) Actuator SETUP... (Direct/reverse action) Max stroke time Max voltage Min voltage Head Pressure Control Temporary low limit suppression Upper limit Low limit Efficiency check point Low ambient control point Sump Drain Relay Control (on power loss)2 Sump Purge Interval Time2 22 10 deg F 120 deg F 80 deg F 105 deg F 90 deg F Drain 3 hours SETUP SETUP SETUP SETUP SETUP SETUP SETUP RT-SVP04F-EN Direct2/Reverse1 Acting 90 seconds 10 VDC 2 VDC2/5 VDC1 SETUP SETUP SETUP SETUP Direct Acting 60 sec 10 VDC 2 VDC SETUP SETUP SETUP SETUP Direct Acting 60 sec 10 VDC 2 VDC SETUP SETUP SETUP SETUP Direct Acting 60 sec 10 VDC 2 VDC SETUP SETUP SETUP SETUP Direct Acting 60 sec 10 VDC 0 VDC SETUP SETUP SETUP SETUP Direct Acting 30 sec 10 VDC 2 VDC SETUP SETUP SETUP SETUP

General Information

Sump Purge Duration Time2 Sump Water Heater Setpoint2 Temperature Input Offset for... Heat morning warmup Return air RTM zone temperature RTM aux temperature Outdoor air Ventilation override definition
Note 1. Note 2. Reference note Reference note
1 2

60 sec. 38 F

SETUP SETUP

0 deg F 0 deg F 0 deg F 0 deg F 0 deg F See Definitions

SETUP SETUP SETUP SETUP SETUP SETUP

applies to IntelliPak I units only. applies to IntelliPak II units only.

Password Protected Screens


Some of the operating displays on the Human Interface LCD screens and require a password to change. The following screens display the various programming sections that require a password in order to view or to modify the preset operating parameters. The password for each screen is a different series of + (Plus) or - (Minus) key strokes in a predefined sequence. Shown below are the password protected screens, and the passwords for accessing them. The following screens display the various programming sections that require a specific PASSWORD to be entered by a qualified operator in order to modify the operating parameters. The following screen will appear if the PASSWORD is not entered within approximately 15 seconds.
Password Entry Time Limit Exceeded

1.

Press the NEXT key until the following screen is displayed.

Configuration is Password Protected Please Enter Password: __________

2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen. 3. Press the ENTER key to confirm the password and enter the menu. 4. Press the NEXT key until the following screen is displayed.
Ventilation Override Mode _______ Enter Password to Lock Definition:

1.

Press the + or - keys in this sequence ( + - - + ) to lock each VO Mode.

2. Press the ENTER key to confirm the password and Lock the definitions. 3. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

23

General Information

Diagnostic Reset is Password Protected Please Enter Password: ____________

1.

Press the + or - keys in this sequence ( - + + ) to access this restricted screen.

2. Press the ENTER key to confirm the password and Lock the definitions. 3. Press the NEXT key until the following screen is displayed.
Diagnostic Log is Password Protected Please Enter Password: __________

1.

Press the + or - keys in this sequence ( - + + -) to access this restricted screen.

2. Press the ENTER key to confirm the password and Lock the definitions. 3. Press the NEXT key until the following screen is displayed.

24

RT-SVP04F-EN

System Operating Status


STATUS Menu
The STATUS menu is used to view various operating conditions such as temperatures and humidity levels. Its used to view unit component status such as fan, compressor, heater, and economizer operation, as well as SETPOINT status. The screens shown in this section are for example only. Pressing the + (Plus) key while viewing any of the status display screens will add that screen to the Custom menu. When a status screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the STATUS key again to return to the status menu. The following are examples of status screens that may be viewed by pressing the STATUS key. Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. Press the STATUS key to begin viewing the status screens. Note: The range for all temperature inputs is 40 to 200 F . ERR will appear if the temperature is out of range.
VAV OA FLOW OCCUPIED *350.0 CCFM OA DMPR 0% SUPPLY FAN ON DIAGNOSTICS
Notes: *VCM only - if the unit does not have a VCM this section of the screen is blank.

1. Press the NEXT key until the following screen is displayed.

GENERAL SYSTEM STATUS SUBMENU SCREENS


General System Status Submenu Press ENTER to View Data in this Submenu 1. Pressing the NEXT key will bypass this section. Used With: All Units

Active Unit Control Source: Active Cluster Member Role:

XXXXXXXXXXXX XXXXXXXXXX

Used With: All Units Possible Values: Source = Local, BAS/Network Role = Standalone, Slave, Master

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

RT-SVP04F-EN

25

System Operating Status

RTM Supply Fan Relay: RTM Supply Airflow Proving:

OFF FLOW

Used With: All Units Possible Values: Fan = ON, OFF Airflow = FLOW, NO FLOW

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Supply Fan IGV/VFD Cmd Active Supply Air Pressure Opening To 30% 2.0 IWC Used With: All units with IGV/VFD. Active SAP only shown if SAP is present. Possible Values: Opening to/ Closing to: 0-100%; Active Supply Air Pressure= 0.0 -7.9 IWC Used With: Rooftop units and Air Handlers when IGV/VFD is not installed and valid SAP sensor is present. Possible Values: IWC 0.0 IWC - 7.9

1. Press the NEXT key until the following screen is displayed.

OR Active Supply Air Pressure 2.0 IWC

1. Press the NEXT key until the following screen is displayed.

Exhaust Fan OFF 1. Press the NEXT key until the following screen is displayed. OR Exhaust Fan ON Space Pressure Exhaust Damper/VFD Opening to 0.00 IWC 32 %

Used With: All units when Power Exhaust without Statitrac is installed without Return Fan Possible Values: Fan= ON/OFF,

1. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units when Power Exhaust with Statitrac is installed without Return Fan Possible Values: Fan= ON, OFF, Damper/VFD = 0 to 100%

Note: "Exhaust Fan" and "Exhaust Damper/VFD" is shown only if "Power Exhaust Config" is not = NONE "Exhaust Fan" is not shown if Return Fan is installed "Space Pressure" is shown only if Power Exhaust or Return Fan with Statitrac is installed

26

RT-SVP04F-EN

System Operating Status

Electric Heat: ENABLED Stage: 6 K11: ON

K12: ON

K1: ON

1. Press the NEXT key until the following screen is displayed. (If applicable)

Used With: All units with Electric Heat installed. Possible Values: Electric Heat: ENABLED, DISABLED By Setup, LIMITED By Demand Limit Stage: 0,1,2,3,4,5,6 K*: ON, OFF

OR

Note: Enabled indicates OK to heat; disabled indicates NOT OK to heat, such as during cooling.
K1: ON Used With: All units with Staged Gas Heat Installed. Possible Values: ENABLED, DISABLED By Setup, LIMITED By Demand Limit Stage: 0,1,2 K*: ON, OFF Used With: All units with hydronic heat is installed Possible Values: ENABLED, DISABLED By Setup, LIMITED By Demand Limit, LIMITED By Low Air Temp; Valve Position: Opening to/ Closing to 0-100% Used With: All units with modulating gas heat is installed Possible Values: ENABLED, DISABLED By Setup, LIMITED By Demand Limit; Valve Position: Opening to/Closing to 0-100% Used With: Air Handler Units with Chilled Water Installed Possible Values: Chilled Water: ENABLED, DISABLED By SETUP, LIMITED By Demand Limit, LIMITED By Low Air Temp; Valve Position Field One: Opening To, Closing To Field Two: 0-100%

Gas Heat: ENABLED Stage: 2 K11: ON

K12: ON

1. Press the NEXT key until the following screen is displayed. (If applicable)

OR Hydronic Heat Valve Position: ENABLED Opening To: 100%

1. Press the NEXT key until the following screen is displayed. Low temp air may be OK or tripped (If applicable)

OR Mod Gas Heat Valve Position: ENABLED Opening To: 100%

1. Press the NEXT key until the following screen is displayed. (If applicable)

Chilled Water: Valve Position:

Opening To

ENABLED 100%

RT-SVP04F-EN

27

System Operating Status

Dehumidification Status: by Comfort Control Override is Active

DISABLED

Used With: All IntelliPak with Dehumidification option installed. Top Line Possible Values: ENABLED, DISABLED Bottom line Possible Values: See below

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) by Call for Cooling Demand Limit by Compressor Lockout Sources by Occ Dehumid Function Disable by Dehumid Override Zone Temp High by OA Temperature Out Of Range by Unocc Dehumid Function Disable by Comfort Control Override is Active by Required Sensor Failure Condition by Insufficient Airflow Condition by Sat Reheat Cond Temp Sensor Fail By Reheat Head Pressure High Limit (Blank) Condenser Coil Purge is Active Humidification Status: 1. 2. 3. 4. Humidification is Active If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "DISABLED" If 1st line is "ENABLED" If 1st line is "ENABLED" ENABLED

Used With: Used With: All units with Humidification option installed. Possible Values: ENABLED, DISABLED by Occ Humidification Function Disable (If 1st line is "DISABLED"), by Unocc Humidification Function Disable (If 1st line is "DISABLED"), Humidification is Inactive (If 1st line is "ENABLED" and output is deenergized, Humidification is Active (If 1st line is "ENABLED" and output is energized)

Key Stroke Operation (1) by Occ Humidification Function Disable by Unocc Humidification Function Disable Humidification is Inactive Humidification is Active

1. Press the NEXT key until the following screen is displayed. (If applicable)

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

28

RT-SVP04F-EN

System Operating Status

Compressor Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Compressor Relay KXX XXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Ckt 1 Compr Relay K11: ON Enabled............................................

Used With: All Rooftop Units and Air Handlers with DX Cooling installed.

Used With: IntelliPak I Rooftop Units and Air Handlers with DX Cooling installed. Possible Values: K10, K11 Second Field: ON, OFF, LOCKED Bottom Field: Enabled or any item from Lockout Sources List.

(MORE)

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Compressor Relay KXX XXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Ckt 1 Compr Relay K12: LOCKED Disabled By Evap Temp Sensor Fail (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All IntelliPak II Rooftop units or Air Handlers with DX Cooling. Possible Values: K11: ON, OFF, LOCKED; Second Field: Enabled or any item from Lockout Sources List

Used With: IntelliPak I Rooftop Units and Air Handlers with DX Cooling installed. Possible Values: K11, K12 Second Field: ON, OFF, LOCKED Bottom Field: Enabled or any item from Lockout Sources List.

Used With: All IntelliPak II Rooftop units or Air Handlers with DX Cooling. Possible Values: K12: ON, OFF, LOCKED; Second Field: Enabled or any item from Lockout Sources List

RT-SVP04F-EN

29

System Operating Status

Compressor Relay K3 XXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Ckt 2 Compr Relay K3: OFF Enabled.............................................

Used With: All IntelliPak I Rooftop Units and Air Handlers with DX Cooling installed. Possible Values: Second Field: ON, OFF, LOCKED Bottom Field: Enabled or any item from Lockout Sources List.

(MORE)

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Compressor Relay K4 XXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Ckt 2 Compr Relay K4: LOCKED Disabled By Evap Temp Sensor Fail (MORE) 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All IntelliPak II Rooftop units or Air Handlers with DX Cooling. Possible Values: K3: ON, OFF, LOCKED; Second Field: Enabled or any item from Lockout Sources List

Used With: All IntelliPak I Rooftop Units and Air Handlers with DX Cooling installed. Possible Values: Second Field: ON, OFF, LOCKED Bottom Field: Enabled or any item from Lockout Sources List.

Used With: All IntelliPak II Rooftop units or Air Handlers with DX Cooling. Possible Values: K4: ON, OFF, LOCKED; Second Field: Enabled or any item from Lockout Sources List

30

RT-SVP04F-EN

System Operating Status

Disable or Lockout Sources Disabled By Compressor Protection (Compressor proving input did not close) Disabled By Contactor Failure (Compressor proving input stuck closed) Disabled By Low Pressure Cutout (Low pressure cutout input to MCM) Disabled By Bad Cond Temp Sensor (Temp Sensor is out of -40 F to 200 F range) Disabled By Demand Limit (From GBAS or BAS/Network) Disabled By Frost Protection (Leaving evap temp sensor colder than coil frost temp setpoint (25 F to 35 F) Disabled By BAS/Network Lockout Disabled By Minimum Off Time (3 minutes) Disabled By Low Ambient Lockout (setpoint range -20 F to 80 F) Disabled By Ventilation Override (VOM input A-E or BAS/Network) Disabled By LPC Delay (3 minutes) Disabled By Water Flow Status Disabled By Cond Coil Purge Request Disabled By Sump Temp Sensor Fail Disabled By Low Refrig Charge (Evap temp limit setpoint (24-45 F) has been exceeded for 10 minutes Disabled By Evap Temp Sensor Fail Disabled By Sump Min Level Sensor Fail Disabled By Sump Pump Failure Disabled By Sump Min Level Control * These entries apply to the following 4 screens.

Note: If a compressor output is disabled or locked, these lockout sources will be found in the bottom field for IntelliPak I, or in the second field for IntelliPak II.

Circuit 1 Enter Evap: 48.5

Evap Diff: 5.0 Leave Evap: 53.5

1. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All Rooftop Units and Air Handlers when DX cooling is installed. Possible Values: Evap Diff. = 0.0 to 200.0 F, Enter Evap= -40.0 to 200.0 F, Leave Evap: -40 to 200.0 F

Note: "Evap Diff" and associated value not displayed on inactive circuit or for first ten minutes of circuit operation or if HGBP is installed. Note: "Enter Evap" and associated value not displayed if HGBP is installed
1. Press the NEXT key until the following screen is displayed. Circuit 1 Saturated Condensing Temp: Used With: All Rooftops or Air Handlers with DX Cooling. Possible Values: Saturated Condensing Temp= -40.0 to 200.0 F

100.0

1. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

31

System Operating Status

Circuit 2 Enter Evap: 40.0

Evap Diff: 12.0 Leave Evap: 52.0

1. Press the NEXT key until the following screen is displayed.

Note: "Evap Diff" and associated value not displayed on inactive circuit or for first ten minutes of circuit operation or if HGBP is installed. Note: "Enter Evap" and associated value not displayed if HGBP is installed
1. Press the NEXT key until the following screen is displayed. Circuit 2 Saturated Condensing Temp:

Used With: All Rooftops or Air Handlers with DX Cooling. Possible Values: Evap Diff. = 0.0 to 200.0 F, Enter Evap= -40.0 to 200.0 F, Leave Evap: 40.0 to 200.0 F

97.0

1. Press the NEXT key until the following screen is displayed. Circuit 1 K1: ON K2: ON Cond Fan Staging Stage 4

Used With: All Rooftops or Air Handlers with DX Cooling. Possible Values: Saturated Condensing Temp= -40.0 to 200.0 F Used With: All units except Air Handlers. Possible Values: K1= ON, OFF; K2= ON, OFF; Cond Fan Staging= OFF, Stage 1, Stage 2, Stage 3, Stage 4

1. Press the NEXT key until the following screen is displayed.

Note: K2 status not displayed and maximum stage is 1 on watercooled condenser units.
Circuit 2 K5: ON K6: ON Cond Fan Staging Stage 4 Used With: All units except Air Handlers. Possible Values: K5= ON, OFF; K6= ON, OFF; Cond Fan Staging= OFF, Stage 1, Stage 2, Stage 3, Stage 4

Note: K6 not displayed and maximum stage is 1 on water-cooled condenser units.

1. Press the NEXT key until the following screen is displayed. Condenser Fan Speed: Circuit 1: 100% Circuit 2: 100% 1. Press the NEXT key until the following screen is displayed. Used With: All IntelliPak II units configured with low ambient control or water-cooled condensers Possible Values: Circuit 1= 0 to 100%; Circuit 2= 0 to 100% Used With: All IntelliPak II units with water-cooled condensers installed. Sump Heater Relay is displayed if sump heater installed Possible Values: Sump Water Temp: 0.0 to 200.0 F; Sump Heater Relay: ON, OFF

Condenser Sump Water Temp: Condenser Sump Heater Relay:

73.1F OFF

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable)

32

RT-SVP04F-EN

System Operating Status

Condenser Sump Pump Relay Command: Condenser Sump Pump Proving:

ON FLOW

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Condenser Water Valve Relay Ckt1: Condenser Water Valve Ckt1: OFF OPEN

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Sump Pump Relay: ON, OFF; Sump Proving: FLOW, NO FLOW

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Condenser Water Valve Relay Ckt2: Condenser Water Valve Ckt2: ON CLOSED

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Water Valve Relay: ON, OFF; Water Valve: CLOSED, OPEN

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Condenser Sump Fill Relay: Condenser Sump Fill Valve: OFF OPEN

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Water Valve Relay: ON, OFF; Water Valve: CLOSED, OPEN

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Condenser Sump Drain Relay: Condenser Sump Drain Valve: ON CLOSED

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Sump Fill Relay: ON, OFF; Sump Fill Valve: CLOSED, OPEN

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Sump Drain Relay: ON, OFF; Sump Drain Valve: CLOSED, OPEN

Note: Valve position with Relay ON is configurable based on if need to hold water in the sump or drain it on power loss. See Installation and Operations Manual.

RT-SVP04F-EN

33

System Operating Status

Cond Sump Water Level Max Input: Cond Sump Water Level Min Input:

OPEN CLOSED

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) External Sump Drain Request: INACTIVE

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: Max Input: CLOSED, OPEN; Min Input: CLOSED, OPEN

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Reheat Coil Pumpout Relay: Reheat Coil Pumpout Valve: OFF CLOSED

Used With: All IntelliPak II units with water-cooled condensers installed. Possible Values: ACTIVE, INACTIVE

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Dehumid Reheat Valve Position: Dehumid Cooling Valve Position: 0% 100%

Used With: All IntelliPak units with Dehumidification installed. Possible Values: Coil Pumpout Relay: ON, OFF; Coil Pumpout Valve: CLOSED, OPEN

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Active Outside Air Temperature Low Ambient Comp Lockout Temp: 70.0F 50F

Used With: All IntelliPak units with Dehumidification installed. Possible Values: Reheat Valve: 0Max Reheat Valve Position Setpoint; Cooling Valve: 10-100%

1. Press the NEXT key until the following screen is displayed.

Used With: All Rooftops or Air Handlers with DX Cooling. Possible Values: Active Outside Air Temp= -40 to 200.0F; Low Ambient Comp Lockout Temp= -20 to 80F (Default: 50 F Standard, 0 F Lowambient with Hot Gas Bypass, 10 F Low-ambient without Hot Gas Bypass)

34

RT-SVP04F-EN

System Operating Status

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

ECONOMIZER STATUS SUBMENU SCREENS


Economizer Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass the next section. Air Economizing: ENABLED Outside Air Damper Pos: Used With: All units when an Economizer is installed. Possible Values: Economizing: ENABLED/DISABLED Outside Air: Opening To/Closing To 0 - 100% Used With: All Units when an economizer is installed

10%

1. Press the NEXT key until the following screen is displayed.

Note: Enabled = OK to economize Disabled = Not OK to economize


Active Outside Air Enthalpy ECEM Return Air Enthalpy 29.5 BTU/LB 34.0 BTU/LB Used With: All Units when an Economizer is installed. "RA Enth" is displayed if Comparative Enthalpy or Energy Recovery is installed. Possible Values: 10 to 35 BTU/LB Used With: All Units when an Economizer is installed. "RA Temp" is displayed if Comparative Enthalpy or Energy Recovery is installed.

1. Press the NEXT key until the following screen is displayed. Active Outside Air Temperature ECEM Return Air Temperature 86.0 78.0 F F

1. Press the NEXT key until the following screen is displayed. (if applicable) Active Outside Air Humidity ECEM Return Air Humidity 30 % 62 %

Used With: All Units when an Economizer is installed. "RA Humidity" is displayed if Comparative Enthalpy or Energy Recovery is installed. Possible Values: 10 to 90 %

1. Press the NEXT key until the following screen is displayed.

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RT-SVP04F-EN

35

System Operating Status

OUTSIDE AIR VENTILATION STATUS SUBMENU SCREENS Outside Air Ventilation Status Submenu Press ENTER to View Data in this Submenu 1. Press the NEXT key until the following screen is displayed. Demand Control Ventilation is Space CO2 Level: ENABLED 600 PPM Used With: All Units with fresh air configuration set to any option other than NONE

1. Press the NEXT key until the following screen is displayed.

Used With: All Units Possible Values: ENABLED, DISABLED; Space CO2 Level= 50 to 2200 PPM

Note: "Space CO2 Level" is shown only if "Demand Control ventilation" is ENABLED
DCV Min OA Flow Target: Deadband: 5.0 CCFM OR 80.5 CCFM OA Flow XXX CCFM Used With: All units with Fresh Air Measurement w/DCV (VCM) installed and Demand Control Ventilation Enabled Possible Values: 0 to 65546 CCFM; Deadband= 5.0 to 200 CCFM Used With: All units with Fresh Air Measurement w/DCV (VCM) installed and Demand Control Ventilation Disabled Possible Values: 0 to 65546 CCFM; Deadband= 5.0 to 200 CCFM Used With: All units with Fresh Air Measurement w/DCV (VCM) installed. Possible Values: 0 to 65546 CFM Used With: All units where Fresh Air Configuration is set to any option other than NONE. Possible Values: 0 to 100% Used With: All units with Fresh Air Measurement w/DCV (VCM) or OA Damper Min Position w/DCV (VCM) installed and Preheat enabled. Possible Values: VCM Module= -40.0 to 200.0F

Active Min OA Flow SETPOINT: Deadband: 6.8 CCFM

1400 CCFM OA Flow XXX CCFM

1. Press the NEXT key until the following screen is displayed.

Outside Air Flow Front: 0 CCFM

Total: 0 CCFM Back: 0 CCFM

1. Press the NEXT key until the following screen is displayed.

Outside Air Damper Target: Outside Air Damper Position:

27% 24%

1. Press the NEXT key until the following screen is displayed.

VCM Preheater Output Control: VCM Module Aux Temp Input:

OFF 47.2F

1. Press the NEXT key until the following screen is displayed.

36

RT-SVP04F-EN

System Operating Status

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RETURN FAN STATUS SUBMENU SCREENS


Note: Return Fan and Energy Recovery are mutually exclusive features. Only one of the following two status submenus will be displayed.
Return Fan Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Return Fan Relay: Return Airflow Proving: ON ON Used With: All units with Return Fan installed. Possible Values: ON, OFF Used With: All units with Return Fan installed.

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Return Fan VFD Command: Return Plenum Pressure: 45% 0.8 IWC

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units with Return Fan installed. Possible Values: 0 to 100%; -0.7 to 3.5 IWC

Note: Top line shown only if Return Fan VFD is installed.

RT-SVP04F-EN

37

System Operating Status

Return Plenum Pressure Target: Return Fan VFD Pos: Opening to

0.8 IWC 45%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Max Return Plenum Pressure Stp: 1.2 IWC High Limit: 3.5 IWC Deadband: 0.2 IWC 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units with Return Fan installed. Possible Values: 0.1 to 2.5 IWC; Return Fan VFD= Opening to/Closing to 0 to 100%

Used With: All units with Return Fan installed. Possible Values: Max Return= 0.1 to 2.5 IWC (Default 1.2 IWC); Deadband = 0.1 to 1.0 IWC (Default 0.2 IWC) Note: High limit is 3.5 IWC and is not adjustable.

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Energy Recovery Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Energy Wheel Relay: Energy Wheel Proving: ON ON Used With: All IntelliPak II units with Energy Recovery installed. Possible Values: ON, OFF Used With: All IntelliPak II units with Energy Recovery installed.

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

38

RT-SVP04F-EN

System Operating Status

Outside Air Bypass Damper Pos: Exhaust Air Bypass Damper Pos:

0% 15%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Energy Wheel Frost Avoidance: Leaving Recovery Exhaust Temp: INACTIVE 45.0F

Used With: All IntelliPak II units with Energy Recovery installed. Possible Values: 0-100%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Energy Wheel Preheat Relay: OFF

Used With: All IntelliPak II units with Energy Recovery installed. Possible Values: Frost Avoidance: ACTIVE, INACTIVE; Recovery Exhaust Temp: -40.0 to 200.0 F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All IntelliPak II units with Energy Recovery Preheat installed. Possible Values: ON, OFF

CONTROLLING SETPOINT STATUS SUBMENU SCREENS


Controlling SETPOINT Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Active Supply Air Cooling STP From HI (KEYPAD) SETPOINT MENU Is Used With: 55 F Possible Values: HI (Keypad) SETPOINT Menu, Zone Sensor SETPOINT Input, NSB Panel SETPOINT Input, GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module All Units Used With: All Units

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

RT-SVP04F-EN

39

System Operating Status

Active Supply Air Heating STP From HI (KEYPAD) SETPOINT MENU Is

100 F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Daytime Warmup SETPOINTs Initiate: 67 F

Used With: All Units when Hydronic Heat, Electric Heat, or Modulating Gas Heat is installed. Possible Values: HI (Keypad) SETPOINT Menu, Zone Sensor SETPOINT Input, GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module

Terminate:

71 F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Occupied Zone Heating STP From HI (KEYPAD) SETPOINT MENU Is

Used With: All Units when Gas, Electric, Hydronic or External Heat is installed. Possible Values: HI (Keypad) SETPOINT Menu; Initiate= 50-87F; Terminate= 53-90 F (This SETPOINT source is HI (keypad) or BAS/ Network

71 F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Unoccupied Zone Cooling STP From HI (KEYPAD) SETPOINT MENU Is 85 F 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All Units when Gas, Electric, Hydronic or External Heat is installed and Daytime Warmup enabled. Possible Values: HI (Keypad) SETPOINT Menu Zone Sensor Setpnt Input, NSB Panel SETPOINT Input, GBAS 0-5 VDC Module, BAS/ Network, GBAS 0-10 VDC Module; Range 50 - 88F

Used With: All Units Possible Values: HI (KEYPAD) enabled. Possible Values: HI (Keypad) SETPOINT Menu Zone Sensor Setpnt Input, NSB Panel SETPOINT Input, GBAS 0-5 VDC Module, BAS/ Network, GBAS 0-10 VDC Module; Range: 52 - 90 F

40

RT-SVP04F-EN

System Operating Status

Active Unoccupied Zone Heating STP From HI (KEYPAD) SETPOINT MENU Is 60 F 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Morning Warmup SETPOINT From HI (KEYPAD) SETPOINT MENU Is

Used With: All Units when Gas, Electric, Hydronic or External Heat is installed Possible Values: HI (Keypad) SETPOINT Menu, NSB Panel SETPOINT Input, GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module; Range 50 - 88F

72 F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Occ Dehumidification Setpt From HI (KEYPAD) SETPOINT MENU is 60% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Active Unocc Dehumidification Setpt From HI (KEYPAD) SETPOINT MENU is 60% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable) Active Supply Air Reheat Setpoint From HI (KEYPAD) SETPOINT MENU is

Used With: All Units when Gas, Electric, Hydronic or External Heat is installed Possible Values: HI (Keypad) SETPOINT Menu Zone Sensor Setpnt Input, NSB Panel SETPOINT Input, GBAS 0-5 VDC Module, BAS/ Network, GBAS 0-10 VDC Module; Range: 52 - 90 F

Used With: All IntelliPak units with Dehumidification installed. Possible Values: HI (KEYPAD) SETPOINT MENU, BAS/NETWORK, GBAS 0-5VDC Module, BAS/ Network, GBAS 0-10 vdc Module; Range= 40 to 65%

Used With: All IntelliPak units with Dehumidification installed. Possible Values: HI (KEYPAD) SETPOINT MENU, BAS/NETWORK, GBAS 0-5VDC Module, BAS/ Network, GBAS 0-10 vdc Module; Range= 40 to 65%

70.0F

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All IntelliPak units with Dehumidification installed. Possible Values: HI (KEYPAD) SETPOINT MENU, BAS/NETWORK, GBAS 0-5VDC Module, BAS/ Network, GBAS 0-10 vdc Module; Range= 60 to 80 F

RT-SVP04F-EN

41

System Operating Status

Active Occ Humidification Setpt From HI (Keypad) Setpoint Menu is _________ 40% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Unocc Humidification Setpt From HI (Keypad) Setpoint Menu is_____________ 20% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Econ DB Enable SETPOINT From HI (Keypad) Setpoint Menu is__________

Used With: All units with Occupied Humidification option enabled. Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module; Range= 20 to 50%

Used With: All units with Unoccupied Humidification option enabled. Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module; Range= 20 to 50%

Used With: All Units when an Economizer is installed 75 F 1. Press the NEXT key until the following screen is displayed. (if applicable) Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module; SETPOINT range: 40 F to 90 F Active OA Damper Min Position STP From HI (Keypad) Setpoint Menu is_________ 25% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Used With: All units with 0-25% Motorized Damper or 0-100% Air Economizer and i) OA CFM Compensation function is DISABLED or ii) OA Damper Min Position SETPOINT source selection is other than HI (KEYPAD) SETPOINT Possible Values: HI (KEYPAD) SETPOINT MENU, RTM Min Position Pot, GBAS 0-5VDC Module, GBAS 010VDC Module, BAS/Network; Range from 0 to 100%

42

RT-SVP04F-EN

System Operating Status

Active Min OA Flow SETPOINT From HI (KEYPAD) SETPOINT MENU

Used With: All Units when Fresh Air Measurement VCM is installed Possible Values: HI (Keypad) SETPOINT Menu, GBAS 0 - 5 VDC 1. Press the NEXT key until the following screen is displayed. (if applicable) Module, BAS Network GBAS 0-10 VDC Module SETPOINT range: 0 to Max Unit Airflow Refer to the table in the SETPOINT section, "Default Min OA Flow SETPOINT Screen" for max airflow SETPOINTs. 34.2 CFM Active Design Min OA Flow SETPOINT From HI (KEYPAD) SETPOINT MENU Used With: All Units when Fresh Air Measurement VCM is installed Possible Values: HI (Keypad) SETPOINT Menu, GBAS 0 - 5 VDC 1. Press the NEXT key until the following screen is displayed. (if applicable) Module, BAS Network GBAS 0-10 VDC Module SETPOINT range: 0 to Max Unit Airflow Refer to the table in the SETPOINT section, "Default Min OA Flow SETPOINT Screen" for max airflow SETPOINTs. 34.2 CFM Active Min OA Flow Stp DCV Disabled Used With: All Units when Fresh Air Measurement VCM is installed Possible Values: HI (Keypad) 1. Press the NEXT key until the following screen is displayed. (if applicable) SETPOINT Menu, GBAS 0 - 5 VDC Module, BAS Network GBAS 0-10 VDC Module SETPOINT range: 0 to Max Unit Airflow Refer to the table in the SETPOINT section, "Default Min OA Flow SETPOINT Screen" for max airflow SETPOINTs. Active Supply Air Pressure STP From HI (KEYPAD) SETPOINT MENU is Used With: Rooftop units and Air Handlers when IGV/VFD is installed. Possible Values: HI (Keypad) SETPOINT Menu, GBAS 0-5 VDC Module, GBAS 0-10 VDC Module, BAS/Network SETPOINT Range: 0.7=5.1 IWC Used With: Rooftop units and Air Handlers with IGV/VFD installed or with SAP present. Possible Values: High Limit: 1.2 4.7 IWC Deadband: 0.1 - 2.0 IWC

2.0 IWC

1. Press the NEXT key until the following screen is displayed.

Active Supply Air Pressure SETPOINTS High Limit: 4.0 IWC Deadband:

0.5 IWC

1. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

43

System Operating Status

Active Space Pressure SETPOINT From HI (KEYPAD) SETPOINT MENU is

Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan with Statitrac installed 1. Press the NEXT key until the following screen is displayed. (if applicable) Possible Values: HI (Keypad) SETPOINT Menu, GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module; SETPOINT range: -0.2 to 0.30 IWC 0.08 IWC Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan with Statitrac Installed Possible Values: HI (KEYPAD) SETPOINT MENU, SETPOINT range: 0.02 to 0.20 IWC

Active Space Pressure Deadband

0.10

IWC

1. Press the NEXT key until the following screen is displayed.

End of Submenu (NEXT) to Enter SETUP Status 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

CONTROLLING SENSOR STATUS SUBMENU SCREENS


Controlling Sensor Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Active Supply Air Temp Sensor Input From SUPPLY AIR is 50.0 F 1. Press the NEXT key until the following screen is displayed. Active Daytime WU Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0 F 1. Press the NEXT key until the following screen is displayed.(if applicable) Used With: All Units Possible Values: RTM Supply Air Temp Input, BAS/Network Used With: All Units

Used With: All units when Gas, Electric, Hydronic or External Heat is installed and DWU is enabled Possible Values: RTM Zone Temp Input, NSB Panel Temp Sensor Input, RTM Aux Temp Input, Heat Module Aux Temp Input, ECEM Return Air Temp Input, BAS/Network Sensor range: -40 F to 200 F Used With: All Units Possible Values: RTM Zone Temp Input, NSB Panel Temp Sensor Input, RTM Aux Temp Input, Heat Module Aux Temp Input, ECEM Return Air Temp Input, BAS/ Network, Sensor range: -40 F to 200 F
RT-SVP04F-EN

Active Unocc Zone Temp Sensor Input From RTM ZONE TEMP INPUT is 75.0 F 1. Press the NEXT key until the following screen is displayed. (if applicable)

44

System Operating Status

Active Morning WU Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0 F

Used With: All Units when Gas, Electric, Hydronic or External Heat is installed and Morning Warmup is enabled Possible Values: RTM Zone Temp Input, NSB Panel Temp Sensor Input, RTM Aux Temp Input, Heat Module Aux Temp Input, ECEM Return Air Temp Input, BAS/ Network, Sensor range: -40 F to 200 F Used With: All units with Humidification option enabled. Possible Values: RTM Space, Humidity Input, BAS/Network, ECEM RA Humidity Input; Range 10-90%

1. Press the NEXT key until the following screen is displayed. (if applicable)

Active Space Humidity Sensor Input From RTM space Humidity Input is 55% 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Space CO2 Sensor Input From VCM Space CO2 Input is 600 ppm 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) Active Dehumid OVRD Temp Input From RTM ZONE TEMP INPUT is 73.5F 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units with VCM installed. Possible Values: VCM SPACE CO2 INPUT, BAS/Network; Range 502000 ppm

Used With: All units with Dehumidification installed. Possible Values: RTM Zone Temp input, NSB Panel Temp Sensor input, RTM Aux Temp input, Heat Module Aux Temp input, BAS/Network, ECEM Return Air Temp input; Range: -40.0 to 200.0 F

RT-SVP04F-EN

45

System Operating Status

Active Zone Reset Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0 F 1. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All Units with Reset Select not selected as None. Possible Values: RTM Zone Temp Input NSB Panel Temp Sensor Input, RTM Aux Temp Input, Heat Module Aux Temp Input, ECEM Return Air Temp Input, BAS/Network Sensor range: -40 F to 200 F Used With: All Units Possible Values: RTM Outside Air Temp Input, BAS/Network

Active OA Temperature Sensor Input From RTM OUTSIDE AIR TEMP INPUT is 86.0 F 1. Press the NEXT key until the following screen is displayed. (if applicable) Active Outside Air Humidity Input From OA HUMIDITY SENSOR INPUT is 30 %

Used With: All Units when an Economizer is installed 1. Press the NEXT key until the following screen is displayed. (if applicable) Possible Values: OA Humidity Sensor Input BAS/Network Sensor range: 10 to 90% Active Supply Air Press Input From RTM SA PRESSURE INPUT is Used With: All units when IGV/VFD is installed or when the SAP Sensor is enabled Possible Values: RTM SA Pressure 1. Press the NEXT key until the following screen is displayed. (if applicable) Input, BAS/Network; Range: 0 to 7.9 IWC 2.1 IWC Active Space Pressure Input From ECEM SPACE PRESSURE INPUT is Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan with Statitrac installed. 1. Press the NEXT key until the following screen is displayed. (if applicable) Possible Values: ECEM Space Pressure Input, BAS/Network, Sensor range: -0.67 to 0.67 IWC 0.08 IWC Temp Sensor Input Being Monitored: RTM ZONE TEMP INPUT is Used With: All Units Possible Values: RTM Zone Temp Input, NSB Panel Temp Sensor Input, RTM Aux Temp Input, HEAT Module Aux Temp Input, ECEM Return Air Temp Input, No Sensor Selected, Sensor range: -40 F to 200 F

82.0 F

1. Press the NEXT key until the following screen is displayed.

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Temperature Input Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. Used With: All Units

46

RT-SVP04F-EN

System Operating Status

Temp Measured By Sensor Connected To RTM SUPPLY AIR TEMP INPUT 50.0

Used With: All UnitsEER = No sensor connected or sensor failure

1. Press the NEXT key until the following screen is displayed. (if applicable) Temp Measured By Sensor Connected To RTM ZONE TEMP INPUT 82.0 F 1. Press the NEXT key until the following screen is displayed. Temp Measured By Sensor Connected To NSB Panel Temp Sensor Input 79.5 Used With: All Units when Night Setback (NSB) is installed Used With: All UnitsEER = No sensor connected or sensor failure

1. Press the NEXT key until the following screen is displayed. Temp Measured By Sensor Connected To RTM AUX TEMP INPUT 62.0 F 1. Press the NEXT key until the following screen is displayed. Temp Measured By Sensor Connected To RTM OUTSIDE AIR TEMP INPUT 86.0 F 1. Press the NEXT key until the following screen is displayed. (if applicable) Temp Measured By Sensor Connected To HEAT MODULE AUX TEMP INPUT 82.0 F 1. Press the NEXT key until the following screen is displayed. Used With: All Units when Gas, Electric, Hydronic or Modulating Heat is installedEER = No sensor connected or sensor failure Used With: All UnitsEER = No sensor connected or sensor failure Used With: All UnitsEER = No sensor connected or sensor failure

Temp Measured By Sensor Connected To ECEM RETURN AIR TEMP INPUT 78.0 F

Used With: All Units when Comparative Enthalpy is installed EER = No sensor connected or 1. Press the NEXT key until the following screen is displayed. (if applicable) sensor failure Temp Measured By Sensor Connected To VCM MODULE AUX TEMP INPUT 50.0 F 1. Press the NEXT key until the following screen is displayed. Used With: All Units when VCM is installed and OA Preheater is enabledEER = No sensor connected or sensor failure Used With: All Rooftop Units and Air Handlers when DX cooling is installed

Compressor Module Ckt 1 Evap Temp 49.4 F Sat Cond Temp

95.0 F

1. Press the NEXT key until the following screen is displayed. (if applicable) Compressor Module Ckt 2 Evap Temp 50.6 F Sat Cond Temp

97.0 F

1. Press the NEXT key until the following screen is displayed.

Used With: All Rooftop Units and Air Handlers when DX cooling is installed

RT-SVP04F-EN

47

System Operating Status

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Local Hardwired Input Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. IntelliPak II Config Input: Dehumidification Config Input: CLOSED OPEN Used With: All IntelliPak units Possible Values: OPEN/CLOSED Used With: All Units

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) RTM Supply Airflow Proving: ______________________ FLOW FLOW Used With: All Units Possible Values: RTM Exhaust Airflow Proving Flow, RTM Return Airflow Proving Flow; Flow, No Flow

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

RTM Remote Min Position Pot Input

0%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units where Min Pos Pot input is valid(0-100%) or if Air Economizer is installed and assigned as OA Damper Min Pos SETPOINT Source. Possible Values: 0 to 100%

Note: If input is out of range (30 240 ohms) (if applicable) this screen will not appear.

RTM Supply Air Pressure Input

2.1

IWC

1. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units when IGV/VFD is installed or without IGV/VFD but Supply Air Pressure is present.

48

RT-SVP04F-EN

System Operating Status

RTM Outside Air Humidity ECEM Return Air humidity

55% 46%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) RTM Space Humidity 10%

Used With: All units with AS Economizer installed. "RA Humidity" shown only if Comparative Enthalpy is installed Possible Values: 10 - 90%

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable) ECEM Space Pressure Input 0.08 IWC

Used With: All units with DeHumidification or Humidification options installed. Possible Values: 10 - 90%

1. Press the NEXT key until the following screen is displayed. (if applicable) VCM Outside Air Flow Input 350.0 CCFM

Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan with Statitrac installed. Possible Values: -0.67 to 0.67 IWC

1. Press the NEXT key until the following screen is displayed.

Used With: All Units when VCM is installed Possible Values: 0 to Max Unit Air Flow Refer to the table in the SETPOINT section, "Default Min OA Flow SETPOINT Screen" for max airflow SETPOINTs. (if applicable) Used With: All Units when VCM is installed and C02 Reset is enabled or DCV is enabled Possible Values: 50 to 2000 PPM

VCM CO2 Level Input

1512 PPM

1. Press the NEXT key until the following screen is displayed

RT-SVP04F-EN

49

System Operating Status

MPM Return Plenum Pressure Input

0.0 IWC

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Screen shown only if unit with Return Fan installed Possible Values: -0.7 to 3.5 IWC

End of Submenu (NEXT) to Enter STATUS 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

GBAS 0-5 VDC MODULE STATUS SUBMENU SCREENS


GBAS 0 - 5VDC Module Status Submenu Press ENTER to View Data in This Submenu 1. Pressing the NEXT key will bypass this section. GBAS 0-5VDC Module Assigned: Input 1 0.00 VDC Not Assigned Used With: All Units when GBAS 05 VDC is installed Possible Values: Not Assigned, Input=0.0-5 VDC Assignment, Unocc Zone Cooling SETPOINT, Occ Zone Heating SETPOINT, Unocc Zone Heating SETPOINT, Supply Air Cooling SETPOINT, Supply Air Heating SETPOINT, Space Pressure SETPOINT, SA Pressure SETPOINT, Min OA Flow SETPOINT, MWU SETPOINT, Econ Dry Bulb Enable SETPOINT, Minimum Position SETPOINT, Occ Dehumidification Setpoint, Unocc Dehumidification Setpoint , Supply Air Reheat Setpoint, Occ Humidification SETPOINT, Unocc Humidification SETPOINT Used With: All Units when GBAS 05 VDC is installed Possible Values: OPEN, CLOSED Used With: All Units when GBAS 05 VDC is installed

1. Press the NEXT key to display GBAS 0-5 VDC inputs 2, 3 and 4. 2. Press the NEXT key until the following screen is displayed.

GBAS (0-5 VDC) Demand Limit Input Status OPEN 1. Press the NEXT key until the following screen is displayed.

50

RT-SVP04F-EN

System Operating Status

GBAS 0-5 VDC Module Relay Output Status Output 1 OFF 1. Press the NEXT key to display GBAS 0-5 VDC Outputs 2, 3, 4 and 5. 2. Press the NEXT key until the following screen is displayed. End of Submenu (Next) to enter Status 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

Used With: All Units when GBAS 05 VDC is installed Possible Values: ON, OFF

GBAS 0-10 VDC Module STATUS submenu screens


GBAS 0 - 10 VDC Module Status Submenu Press ENTER to View Data in This Submenu 1. Press the NEXT key to bypass this menu and advanced to "General Status" Display screen. GBAS 0-10 VDC Module Analog Input 0.00 VDC Assigned: NOT ASSIGNED 1. Press the NEXT key to display Generic BAS Analog Input screens 2, 3 & 4. 2. Press the NEXT key to advance to the following Used With: With GBAS 0-10 VDC Module Possible Values: Input = 0.00 to 10.0 VDC Assigned: NOT ASSIGNED, Unocc Zone Cooling SETPOINT, Occ Zone Heating SETPOINT, Unocc Zone Heating SETPOINT, Supply Air Cooling SETPOINT, Supply Air heating SETPOINT, Space Pressure SETPOINT, SA Pressure SETPOINT, Min OA Flow SETPOINT, MWU SETPOINT, Econ Dry Bulb Enable SETPOINT, Minimum Enable SETPOINT, Occ Dehumidification Setpoint, Unocc Dehumidification Setpoint, Supply Air Reheat Setpoint, Occ Humidification SETPOINT, Unocc Humidification SETPOINT Used With: With GBAS 0-10 VDC Module Possible Values: Open, Closed Used With: All Units when GBAS 010 VDC is installed

GBAS 0-10 VDC Demand Limit Input Status Open 1. Press the NEXT key until the following screen is displayed. GBAS 0-10 VDC Binary Output OFF Assigned: OUTPUT IS NOT ASSIGNED

Used With: With GBAS 0-10 VDC Module Possible Values: Output= ON, OFF Output is not assigned, Indicate selected diag alarms*, Any Active Diagnostic

Note: *See Alarm Listing under RTM Alarm Output

RT-SVP04F-EN

51

System Operating Status

GBAS 0-10 VDC Analog Output 1 Assigned:

0.00 VDC NOT ASSIGNED

1. Press the NEXT key to display Generic BAS Analog Output screens 2, 3 & 4. 2. Press the NEXT key to advance to the following

Used With: With GBAS 0-10 VDC Module Possible Values: 0.0 to 10.0 VDC Assignment: Outdoor air Temperature, Zone Temperature, Supply Air Temperature, Supply Air Pressure, Space Pressure, Space Relative Humidity, OA Relative Humidity, Space CO2 Level, Cooling Capacity, Heating Capacity, Outdoor Air Damper Position, Outdoor Airflow

End of Submenu (NEXT) to Enter STATUS 1. Press the STATUS key to return to the top status level information. 2. Pressing the NEXT will advanced to "General Status" Display screen.

52

RT-SVP04F-EN

System Programming SETUP


After the unit is installed, the control module must be programmed with certain SETUP information in order to operate and function properly. The data necessary for unit operation will vary depending on certain factors such as unit size, type, and installed options. This section of the manual provides step by step instructions for programming this information. Also provided are instructions for checking unit operating status, accessing and clearing diagnostics, and performing service tests. Some of the displays shown in this manual may not appear on the Human Interface (HI) LCD screen during programming. Only the applicable screens for the specific unit options and operating parameters will be displayed. Start with the first SETUP screen in the SETUP menu and program the necessary information by completing the steps located below each illustrated window. Information that pertains to when the screens are applicable, the factory preset values, and the possible values that may be designated is located to the right of each programmable screen. Ignore the steps that do not apply to your unit and application, and move on to the next applicable set of instructions in the manual. Continue this process until all applicable screens are programmed with the required information.

SETUP Menu
The SETUP menu is used to input initial operating information such as control parameters, SETPOINT source selection, sensor source selections, ventilation override definitions, functions enable/disable, status, text display (language), temperature display (C or F), and system tuning parameters. When a SETUP screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press the SETUP key again to return to the SETUP menu. Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. Press the SETUP key to begin viewing or modifying the SETUP screens. If a screen is not visible on the Unit Human Interface Module, refer to the Used With information listed to the right of each screen in this book. Press the SETUP key to display the following screen.

RT-SVP04F-EN

53

System Programming SETUP

Display Text in: ENGLISH LANGUAGE Display Units Using: ENGLISH NOTATION 1. Press the + or - key until the proper value is displayed. ENGLISH, SI 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). General Unit Functions Setup Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. If Remote Panel Mode Input Not Present: System Mode: AUTO 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Reduce Multi-Unit Startup Power Demand After Power-Up, Delay Unit Start 0 Sec 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Daytime Warmup Function: ENABLED

Used With: All Units Factory Presets: Text and Units: ENGLISH Language, ENGLISH Notation Possible Values: Text: ENGLISH, FRENCH, SPANISH Units: ENGLISH NOTATION, SI NOTATION

Used With: All Units

Used With: All Units Possible Values: System Mode = OFF/AUTO

Used With: All units. Possible Values: Range 0-255 Sec (Default 0 Sec)

Used With: All Units when gas, electric, or hydronic heat is installed. Possible Values: ENABLED, DISABLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. (if applicable)

54

RT-SVP04F-EN

System Programming SETUP

Morning Warmup Function: Morning Warmup Type:

ENABLED FULL CAPACITY

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All Units when Gas, Electric, or Hydronic Heat is installed. Factory Presets: Function: ENABLED, MWU Type: Full Capacity Possible Values: Function: ENABLED, DISABLED MWU Type: FULL CAPACITY, CYCLING CAPCITY Used With: All Units when Modulating Gas, Electric or Hydronic Heat is installed Factory Preset: ENABLED

Supply Air Tempering Function: ENABLED Warm Up Outside Air Used For Ventilation 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: Possible Values: ENABLED, DISABLED* (Note: Supply Air Tempering is not used with staged gas heat)
Used With: All Rooftop Units and Air Handler Units when DX Cooling is installed or Air Handler with chilled water installed. Factory Preset: ENABLED Possible Values: Cooling: ENABLED, DISABLED Used With: All Units when Gas, Electric, Hydronic, or External Heat is installed Factory Presets: Cooling & Heating: ENABLED Possible Values: Cooling & Heating: ENABLED, DISABLED

Unocc Mech Cooling Function:

ENABLED

OR

Unocc Mech Cooling Function: Unocc Heating Function:

ENABLED ENABLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Occupied Dehumid Function: Unoccupied Dehumid Function:

ENABLED ENABLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with Dehumidification installed. Possible Values: ENABLED, DISABLED

RT-SVP04F-EN

55

System Programming SETUP

Occ Humidification Function: Unocc Humidification Function:

DISABLED DISABLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). VCM Preheater Output Control: ENABLED Activate If Preheat Temp Below SETPOINT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Demand Limit Definition: Cooling: None 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All units with Humidification option enabled. Factory Presets: ENABLED Possible Values: ENABLED, DISABLED

Used With: All Units when VCM is installed Factory Preset: DISABLED Possible Values: ENABLED, DISABLED

Used With: All Rooftop units (or Air Handler with DX Cooling) with GBAS or LCI or BCI installed Factory Presets: NONE Possible Values: Cooling: 25, 50, 75, 100%

Note: NONE=No Limit to Cooling; 100% = 100% of Cooling Capacity is Limited


Demand Limit Definition: Cooling: None ......................................Heating: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Used With: All units with Gas, Electric, or Hydronic heat with GBAS or LCI or BCI installed Factory Presets: None Possible Values: Cooling: 25, 50, 75, 100% Heating: 50% or 100%

None

1. Press the + or - key until the proper value is displayed.

Note: NONE=No Limit to Cooling; 100% = 100% of Cooling Capacity is Limited


Compressor Lead/Lag Function: ENABLED Vary Staging Order To Distribute Runtime 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Used With: All Rooftop Units and Air Handlers when DX Cooling is installed Factory Preset: ENABLED Possible Values: ENABLED, DISABLED = Stage Comp(s) Up/ Down In Fixed Sequence

56

RT-SVP04F-EN

System Programming SETUP

Evap Temperature Limit. Shut Off Circuit if (Leaving - Entering) Exceeds: 35F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All Units Factory Preset: 35 F Possible Values: 25-40 F

Note: On units with Dehumidification installed a non-adjustable Evap Temperature Limit of 40 F is used for the Reheat Circuit only.
Coil Frost Cutout Temperature. Shut off Compressors If Evap Temp Is Below: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Used With: All Rooftop Units and Air Handlers when DX Cooling is installed Factory Preset: 30 F Possible Values: 25 F to 35 F

30 F

1. Press the + or - key until the proper value is displayed.

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. VAV Control Functions Submenu Press ENTER to Review or Adjust 1. Press the NEXT key until the following screen is displayed. Supply Air Temp Reset Type: Cooling: NONE 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Supply Air Temp Reset type: Cooling: NONE Heating: NONE 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Used With: All Units when Hydronic, Electric, or Modulating Gas Heat installed Possible Values: Cool/Heat: NONE, ZONE, OA Used With: Rooftops and Air Handlers when no cooling is installed Possible Values: Cool: NONE, ZONE, OA Used With: All Units

RT-SVP04F-EN

57

System Programming SETUP

Supply Air Temp Zone Start Temp: 72 F

Reset For Cooling: End Temp: 69 F

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when Zone Cooling Reset is selected. Factory Presets: StartTemp= 78F EndTemp= 75F Possible Values: Start: 67 - 81 F End: 60 - 80 FF

Supply Air Temp Outside Air Start Temp: 90 F

Reset For Cooling: End Temp: 70 F

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when Outside Air Reset is selected. Factory Presets: StartTemp= 90F EndTemp= 70F Possible Values: Start: 46 - 125 F End: 45 - 124 F

Supply Air Temp Zone

Reset For Cooling: 5F

Maximum Amount of Reset Applied: 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice.

Used With: All Units when Zone Reset is selected. Factory Presets: 5 F Possible Values: 0 - 20 F

3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Supply Air Temp Outside Air

Reset For Cooling: 5F

Maximum Amount of Reset Applied: 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice.

Used With: All Units when Outside Air Cooling Reset is selected. Factory Presets: 5 F Possible Values: 0 - 20 F

3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

58

RT-SVP04F-EN

System Programming SETUP

Supply Air Temp Zone Start Temp: 65 F

Reset For Heating: End Temp: 68 F

1. Press the NEXT key until the following screen is displayed.

Used With: All Units when Zone Heating reset is selected. Factory Presets: Start Temp: 65 F, End Temp: 68 F Possible Values: Start: 50 - 89 F End: 51 - 90 F

Supply Air Temp Outside Air Start Temp: 10 F

Reset For Heating: End Temp: 60 F

1. Press the NEXT key until the following screen is displayed.

Used With: All Units when Outside Air Heating Reset is selected. Factory Presets: Start Temp: 10 F, End Temp: 60 F Possible Values: Start: 0 - 94 F End: 1 - 95 F Used With: All Units when Zone Heating is selected. Factory Presets:10F Possible Values: 10 - 90 F Used With: All Units when Outside Air Heating is selected. Factory Presets:10F Possible Values: 10 - 90 F Used With: All Units Factory Presets: 6 Min Possible Values: 0 to 100%

Supply Air Temp ZONE

Reset For Heating: 10 F

Maximum Amount of Reset Applied:

1. Press the NEXT key until the following screen is displayed.

Supply Air Temp OA

Reset For Heating: 10 F

Maximum Amount of Reset Applied:

1. Press the NEXT key until the following screen is displayed.

VAV Box Max Stroke Time:

6 Min

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Max Occupied IGV/VFD Command: 100%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units when IGV/VFD is installed Factory Presets: 100% Possible Values: 0 to 100%

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RT-SVP04F-EN

59

System Programming SETUP

Economizer Control Functions Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Economizer Cntrl Enable Type: When Comparative Enthalpy Not Available 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Unocc Air Economizer Function: ENABLED REFERENCE

Used with: All Units when an economizer is installed.

Used With: All Units when an economizer is installed Factory Presets: REFERENCE Possible Values: REFERENCE, DRYBULB

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Head Pressure Ctrl Setup Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Sump Drain Valve Relay Control is: DRAIN During Unit Power Loss Conditions 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Sump Purge Interval Timer: Sump Purge Duration Timer: 3 Hrs. 60 Sec.

Used With: All Units when an economizer is installed Factory Presets: ENABLED Possible Values: ENABLED, DISABLED

Used with: Rooftops and Air Handlers when DX cooling is installed

Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: DRAIN Possible Values: HOLD, DRAIN

Note: Sump Purge Duration Timer: only shown if Interval Timer not DISABLED
1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)
60

Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: Interval Timer: 3 hours. Possible Values: Interval Timer: 112 hours; Duration Timer: 30-60 sec., default is 30 sec.

RT-SVP04F-EN

System Programming SETUP

Sump Water Heater Setpoint:

38F

Low Sump Temp Activates Heater Output 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Cond Temp Control Band Lower Limit: 80 F Upper Limit: 120 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All IntelliPak II units with water-cooled condensers and sump heat installed. Factory Preset: 38 F Possible Values: 38-43 F

Used With: All Rooftop Units and Air handlers when DX Cooling is installed. Factory Presets: Upper: 120 F, Lower: 80 F Possible Values: Lower: 70 F to 90 F, Upper: 110 F to 130 F

Cond Temp Control Band Temporary Low Limit Suppression: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Temp Efficiency Check Point: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Temp Low Ambient Control Point: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 90 F 1. Press the + or - key until the proper value is displayed. 105 F 1. Press the + or - key until the proper value is displayed. 10 F 1. Press the + or - key until the proper value is displayed.

Used With: All Rooftop Units and Air handlers when DX Cooling is installed. Factory Presets: 10 F Possible Values: 0 to 20 F

Used With: All Rooftop Units and Air handlers when DX Cooling is installed. Factory Presets: 105 F Possible Values: 95 to 115 F

Used With: All Rooftop Units and Air handlers when DX Cooling and low ambient dampers are installed. Factory Presets: 90 F Possible Values: 80 F to 100 F

Note: All low ambient dampers control to this condensing temperature

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RT-SVP04F-EN

61

System Programming SETUP

Sensor Source Selections Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. For Daytime Warmup Temp Crtl, Use sensor Connected to: RTM ZONE TEMP INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used with: All Units.

Used With: All Units Gas, electric, Hydronic or External Heat is installed. Possible Values: RTM ZONE TEMP INPUT, NSB PANEL TEMP SENSOR INPUT, RTM AUX TEMP INPUT, HEAT MODULE AUX TEMP INPUT, ECEM RETURN AIR TEMP INPUT Used With: All Units Factory Preset: RTM ZONE TEMP INPUT Possible Values: RTM ZONE TEMP INPUT, NSB PANEL TEMP SENSOR INPUT, RTM AUX TEMP INPUT, HEAT MODULE AUX TEMP INPUT, ECEM RETURN AIR TEMP INPUT Used With: All Units when Gas, Electric, Hydronic or External Heat is installed. Factory Preset: RTM ZONE TEMP INPUT Possible Values: RTM ZONE TEMP INPUT, NSB PANEL TEMP SENSOR INPUT, RTM AUX TEMP INPUT, HEAT MODULE AUX TEMP INPUT, ECEM RETURN AIR TEMP INPUT Used With: All units with DeHumidification or Humidification options installed. Factory Preset: RTM Space Humidity Input Possible Values: RTM Space Humidity Input, ECEM RA Humidity Input

For Unoccupied Zone Temp Ctrl, Use Sensor Connected To: RTM ZONE TEMP INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

For Morning Warmup Temp Control, Use Sensor Connected To: RTM ZONE TEMP INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

For Space Humidity Control, Use Sensor Connected To: RTM SPACE HUMIDITY INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

62

RT-SVP04F-EN

System Programming SETUP

For Dehumid OVRD Zone Temp, Use Sensor Connected To: RTM ZONE TEMP INPUT

Used With: All units with Dehumidification installed. Factory Preset: RTM Zone Temp input Possible Values: RTM Zone Temp input, NSB Panel Temp Sensor input, RTM Aux Temp input, Heat Module Aux Temp input, ECEM Return Air Temp input (See below for detail) Used With: All Units Factory Preset: RTM Space Humidity Input Possible Values: RTM Zone Temp, NSB Panel Temp Sensor Input, RTM Aux Temp Input, Heat Module Aux Temp Input, ECEM Return Air Temp Input Used With: All Units Factory Preset: RTM ZONE TEMP INPUT Possible Values: RTM ZONE TEMP INPUT, NSB PANEL TEMP SENSOR INPUT, RTM AUX TEMP INPUT, HEAT MODULE AUX TEMP INPUT, ECEM RETURN AIR TEMP INPUT, NO SENSOR SELECTED

For Zone Reset Function, Use Sensor Connected To: RTM ZONE TEMP INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Monitor Specific Temp Input, Use Sensor Connected To: RTM ZONE TEMP INPUT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Outside Air Ventilation Setup Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Demand Controlled Ventilation: _________________________ 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). DISABLED Used With: All units with Fresh Air Measurement w/DCV (VCM) or OA Damper Min Position w/DCV installed. Factory Preset: Disabled Possible Values: DCV SETPOINT Modified By Space CO2 Level (If Enabled), BLANK (If Disabled) Used with: All Units when Fresh Air is configured other than NONE

RT-SVP04F-EN

63

System Programming SETUP

OA flow Compensation Function: Use fixed OA Damper Minimum Position

DISABLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units without Fresh Air measurement (VCM) with an economizer when IGF/VFD is installed Factory Preset: Disabled Possible Values: ENABLED, DISABLED Enabled 2nd line= "OA Damper Min Pos Depends on IGV/VFD Pos" Disabled 2nd line= "Use Fixed OA Damper Minimum Position" Used With: All units with Fresh Air Measurement w/DCV (VCM) installed. Factory Preset: Gain 1.0, Offset 0 CCFM Possible Values: Gain= 0.5 to 1.5 (Default 1.0); Offset= -250 to 250 CCFM (Default 0 CFM)

OA Flow Calibration Data Gain 1.0

(Front) Offset 0 CCFM

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Note: Front refers to the flow station on the "Front" of the unit (See Installation, Operation, Maintenance Manual)
Used With: All units with Fresh Air Measurement w/DCV (VCM) installed. Factory Preset: Gain 1.0, Offset 0 CCFM Possible Values: Gain= 0.5 to 1.5 (Default 1.0); Offset= -25 to 25 CCFM

OA Flow Calibration Data Gain 1.0

(Back) Offset 0 CCFM

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Note: Back refers to the flow station on the "Back" of the unit (See Installation, Operation, Maintenance Manual)

64

RT-SVP04F-EN

System Programming SETUP

Maximum OA Flow at Design Conditions

XXX CCFM

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. 3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance of customized menus. 4. Press the NEXT key until the following screen is displayed. (if applicable)

Used With: All units with OA Normalization: Return Fan and units with Fresh Air Measurement w/DCV (VCM) installed.

OA Flow Calibration Data Altitude: 0 Ft. 1. Press the + or - key until the proper value is displayed 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed OA Flow Calibration Data Altitude Values & Associated Data ENGLISH 0 ft 500 ft 1000 ft 1500 ft 2000 ft 2500 ft 3000 ft 3500 ft 4000 ft 4500 ft ENGLISH 5000 ft 5500 ft 6000 ft 6500 ft 7000 ft 7500 ft 8000 ft 8500 ft 9000 ft 9500 ft 10000 ft SI 0m 150 m 300 m 450 m 600 m 750 m 900 m 1050 m 1200 m 1350 m SI 1500 m 1650 m 1800 m 2000 m 2150 m 2300 m 2450 m 2600 m 2750 m 2900 m 3050 m ENUM CORR FACTOR 1.00 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 ENUM CORR FACTOR 0.91 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.85 0.84 0.83

Used With: All units with Fresh Air Measurement w/DCV (VCM) installed.

RT-SVP04F-EN

65

System Programming SETUP

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

Ventilation Override Definitions (with VOM installed)


Each of the five VOM modes have factory presets, that when initiated by a VOM contact closure, will accomplish five predefined operations (listed below). Any of the five sequences may be user-redefined by changing the factory presets at the unit mounted Human Interface or through Tracer.

Ventilation Override Mode A - (Unit Off)


Supply Fan - Off Inlet Vanes / VFD - Closed/0% Return Fan VFD - Min Return Fan/Exhaust Damper - Off/Closed (if equipped) OA Dampers - Closed Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output-Deenergized VO Relay - Energized VCM Preheater State - Off (with VCM installed)

Ventilation Override Mode B - (Pressurize)


Supply Fan - On Inlet Vanes / VFD - Open/100% Return Fan VFD - Min Return Fan/Exhaust Damper - Off/Closed (if equipped) OA Dampers - Open Heat - All heat stages Off (staged gas & elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output-Energized VO Relay-Energized VCM Preheater State - Off (with VCM installed)

66

RT-SVP04F-EN

System Programming SETUP

Ventilation Override Mode C - (Exhaust)


Supply Fan - Off Inlet Vanes - Closed (if equipped) Return Fan/Exhaust Damper - On/Open (if equipped) Return Fan VFD - Max OA Dampers - Closed Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output-Deenergized VO Relay-Energized VCM Preheater State - Off (with VCM installed)

Ventilation Override Mode D- (Purge)


Supply Fan - On Inlet Vanes / VFD - Open/100% Return Fan VFD - Max Return Fan/Exhaust Damper - On/Open (if equipped) OA Dampers - Open Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output-energized VO Relay - Energized VCM Preheater State - Off (with VCM installed)

Ventilation Override Mode E- (Purge with Duct Pressure Control)


Supply Fan - On Return Fan VFD - Max Inlet Vanes / VFD - Open/100% (Controlled by SA Pressure Control function, SA Pressure High Limit is disabled) Return Fan/Exhaust Damper - On/Open (if equipped) OA Dampers - Open Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - Energized VO Relay - Energized VCM Preheater State - Off (with VCM installed) OFF - will appear in the Ventilation Override screen after all VOM binary inputs have been reset (opened).

Emergency Override Definitions (with LCI or BCI module installed)


When an LCI or BCI module is installed, the user can initiate one of five (5) Emergency Override sequences that have the following predefined unit operation via LonTalk or BACnet Communication:

RT-SVP04F-EN

67

System Programming SETUP

PRESSURIZE Supply Fan - On Inlet Vanes - Open (if equipped) Return Fan VFD - Min Return Fan/Exhaust Damper - Off/Closed (if equipped) OA Dampers - Open Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - Energized VO Relay - Energized (with VOM module installed) VCM Preheater State - Off (with VCM installed) DEPRESSURIZE Supply Fan - Off Inlet Vanes - Closed (if equipped) Return Fan VFD - Max Return Fan/Exhaust Damper - On/Open (if equipped) OA Dampers - Closed Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized VO Relay - Energized (with VOM module installed) VCM Preheater State - Off (with VCM installed) PURGE Supply Fan - On Inlet Vanes - Open (if equipped) Return Fan/Exhaust Damper - On/Open (if equipped) Return Fan VFD - Max OA Dampers - Open Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - Energized VO Relay - Energized (with VOM module installed) VCM Preheater State - Off (with VCM installed) SHUTDOWN Supply Fan - Off Inlet Vanes - Closed (if equipped) Return Fan/Exhaust Damper - Off/Closed (if equipped) Return Fan VFD - Min OA Dampers - Closed Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized VO Relay - Energized (with VOM module installed) VCM Preheater State - Off (with VCM installed)
68 RT-SVP04F-EN

System Programming SETUP

FIRE Supply Fan - Off Inlet Vanes - Closed (if equipped) Return Fan/Exhaust Damper - Off/Closed (if equipped) Return Fan VFD - Min OA Dampers - Closed Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized VO Relay - Energized (with VOM module installed) VCM Preheater State - Off (with VCM installed)

Ventilation Override Definitions Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. 2. If the factory preset VOM modes (A, B, C, D, E) need to be modified to meet specific application requirements, press the ENTER key to advance to the following screens Ventilation Override Definition Supply Fan 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition Supply Fan IGV/VFD 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition Exhaust Fan/Dampers 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Mode A ON/OPEN Mode A MIN Mode A ON

Used with: All Units when VOM is installed

1. Press the + or - key until the proper value is displayed.

Used With: All Units when VOM is installed Factory Presets: Refer to Definitions Possible Values: On, OFF

1. Press the + or - key until the proper value is displayed.

Used With: All Units when IGV or VFD is installed Factory Presets: Refer to Definitions Possible Values: IN CONTROL, MIN, or MAX Used With: All Units when VOM and Power Exhaust with Statitrac is installed Factory Presets: Refer to Definitions Possible Values: On/OPEN, OFF/ CLOSED

1. Press the + or - key until the proper value is displayed.

RT-SVP04F-EN

69

System Programming SETUP

Ventilation Override Definition Return Fan/Exhaust Dampers

Mode A OFF/CLOSED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Ventilation Override Definition Exhaust Fan 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition Mode Return Fan VFD Command A Min Mode A ON

Used With: All units with VOM installed with Return Fan. Possible Values: Return Fan/ Exhaust Damper: OFF/CLOSED, ON/ OPEN

1. Press the + or - key until the proper value is displayed.

Used With: All Units when VOM and Power Exhaust without Statitrac is installed Factory Presets: Refer to Definitions Possible Values: ON, OFF Used With: All units with VOM installed and Return Fan with Statitrac installed. Possible Values: Return Fan VFD Command: MIN, MAX

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Ventilation Override Definition Outside Air Dampers 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition VAV Box Relay Mode A DEENERGIZED Mode A OPEN

1. Press the + or - key until the proper value is displayed.

Used With: All Units when VOM and an economizer is installed Factory Presets: Refer to Definitions Possible Values: OPEN/CLOSED

1.Press the NEXT key until the following screen is displayed.

Used With: All Units Factory Presets: Refer to Definitions Possible Values: ENERGIZED/ DEENERGIZED Used With: All Units when VOM and Gas, Electronic or Hydronic Heat is installed Factory Presets: Refer to Definitions Possible Values: OFF, IN CONTROL

Ventilation Override Definition Heat 2. Press the ENTER key to confirm this choice.

Mode A OFF

1. Press the + or - key until the proper value is displayed. 3. Press the NEXT key until the following screen is displayed.

70

RT-SVP04F-EN

System Programming SETUP

Ventilation Override Definition VCM Preheater State 2. Press the ENTER key to confirm this choice.

Mode A IN CONTROL

1. Press the + or - key until the proper value is displayed. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition Ventilation Override Relay 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Ventilation Override Definition Enter Password to Lock Definition: 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Note: After locking a MODE (by entering the password), the display for that MODE becomes "Reporting" only and the definition can not be changed unless the Ventilation Override Module is replaced. If the password was entered, pressing the NEXT key will scroll through the previous screens to confirm the selected choices for each mode as follows: Mode A Mode A ENERGIZED

Used With: All Units when VOM is installed and OA preheater function is enabled Factory Presets: Refer to Definitions Possible Values: OFF, IN CONTROL Used With: All Units when VOM is installed Factory Presets: Refer to Definitions Possible Values: ENERGIZED/ DEENERGIZED Used With: All Units Factory Presets: Not Locked Possible Values: Not Locked, Locked

1. Press the + or - key until the proper value is displayed.

Ventilation Override Supply Fan

Mode A

Is Locked

Key functions for the locked VOM displays are as follows: The ENTER, +, and - keys are disabled. The PREVIOUS and NEXT keys will advance to the previous and next screens respectively. After all of the VOM modes have been viewed or modified, the following screen will be displayed. Ventilation Override Supply Fan 1. Follow the preceding steps used to program MODE "A" to program MODE B", "C", "D", and "E" if modifications are needed. After all of the Ventilation Override Definitions have been programmed, pressing the NEXT key will advance to the following screen. Mode B

Used With: All Units when VO mode is locked Factory Presets: Refer to the Definitions Possible Values: N/A

Used With: All Units Factory Presets: Refer to the Definitions Possible Values: ON, OFF

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RT-SVP04F-EN

71

System Programming SETUP

GBAS 0 - 5 VDC Module I/O Assignments Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. GBAS (0 - 5 VDC) Analog Input 1 NOT ASSIGNED 1. Press the + or - key until the proper selection is displayed for the number 1 assignment. 2. Press the ENTER key to confirm this choice. Only one input definition can be assigned to each input and they can not be duplicated. 3. Press the NEXT key to advance to the number 2 input assignment screen and repeat steps 1 & 2. Follow these steps for input assignments 3 and 4. 4. Press the NEXT key until the following screen is displayed. Assignment

Used with: All Units when GBAS 05 VDC is installed.

Used with: All Units when GBAS 05 VDC is installed. Factory Presets: Not Assigned Possible Values: Not Assigned, Unoccupied Zone Cooling SETPOINT Occupied Zone Heating SETPOINT Unoccupied Zone Heating SETPOINT Space Static Pressure SETPOINT, SA Static Pressure SETPOINT, Min OA Flow SETPOINT, Morning Warmup SETPOINT, Econ Dry Bulb Enable SETPOINT, Minimum Position SETPOINT, Occupied Dehumid SETPOINT, Unoccupied Dehumid SETPOINT, Supply Air Reheat SETPOINT, Occupied Humidification SETPOINT, Unoccupied Humidification SETPOINT Used With: All Units when GBAS 05VDC is installed Factory Presets: Output 1 = Dirty Filters Output 2 = Compressor Trip Compressor Trip - Ckt 1 Compressor Trip - Ckt 2 Low Pressure Control Open Low Pressure Control Open - Ckt 1 Low Pressure Control Open - Ckt 2 Comp Contactor Fail Comp Contactor Fail - Ckt 1 Comp Contactor Fail - Ckt 2 Output 3 = Heat Fail Output 4 = Supply Fan Failure Output 5 = Any Active Diagnostic Possible Values: Refer to the list of active diagnostics that can be assigned to each of the five (5) output definitions in the "Diagnostics Menu" section.

GBAS (0 - 5 VDC) Output 1 Press ENTER to Review or Adjust

Alarm Assignments

1. Pressing the NEXT key will bypass this section. 2. Press the + or - key until the proper selection is displayed for the number 1 assignment. + (Plus) key will assign ALL Diagnostics and (Minus) key will allow diagnostic selection. 3. Press the ENTER key to confirm this choice. If (Yes) was assigned to the Output assignment, the output 2 assignment screen will be displayed. Repeat step 1 for each of the remaining 4 Outputs. If (NO) was assigned, only one output assignment can be assigned to each output assignment and they can not be duplicated. Once the output diagnostics have been defined, press the NEXT key to advance to the number 2 output assignment screen and repeat steps 1 & 2. Note: Assigning "Yes" to a GBAS output definition means that if the assigned diagnostic is present, the output assigned to it will be energized.

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. This screen is displayed when GBAS 0-10 VDC Module is installed
72 RT-SVP04F-EN

System Programming SETUP

GBAS 0-10 VDC Module I/O Assignments Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. GBAS (0-10 VDC) Analog Input 1 Assignment NOT ASSIGNED 2. Press the + or - key until the proper value is displayed. 3. Press the ENTER key to confirm this choice. 4. Press the NEXT key to display Generic BAS Analog Input 2 screen. 5. Press the + or - key until the proper value is displayed. 6. Press the ENTER key to confirm each choice. 7. Repeat steps 1-4 to display Generic BAS Analog Input screens 2, 3 &4 8. Press the NEXT key to advance to the following screen. Used with: All Units when GBAS 010 VDC Module is installed Factory Presets: Not Assigned Possible Values: Not Assigned, Unocc Zone Cooling SETPOINT, Occupied Zone heating SETPOINT, Unoccupied Zone Heating Setpoint, Supply Air Cooling SEPOINT, Supply Air Heating SETPOINT, Space Static Pressure SETPOINT, SA Static Pressure SETPOINT, Min Outside Air Flow SETPOINT, Morning Warmup SETPOINT, Econ Dry Bulb Enable SETPOINT, Minimum Position SETPOINT, Occupied Dehumid SETPOINT, Unoccupied Dehumid SETPOINT, Supply Air Reheat SETPOINT, Occupied Humid SETPOINT, Unoccupied humidity SETPOINT

The following screen will display if "Indicate selected diag alarms" is assigned GBAS (0-10 VDC) Binary Alarm Assignments Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic To Alarm Output Any Active Diagnostic (Yes) 1. Press the + or - key until the proper value is displayed. If "YES" is assigned to "Any Active Diagnostic", pressing the NEXT key will advance to the "End of Submenu" screen. Assigning "NO" to the "Any Active Diagnostic" will advance to the selectable diagnostic screens. See 0-5 active diagnostic list. 2. Press the ENTER key to confirm each choice. 3. Press the NEXT key to scroll through each Active Diagnostic. Used with: All Units when GBAS 010 VDC module is installed Factory Presets: Yes Possible Values: Yes, No--Values: Refer to the list of active diagnostics that can be assigned to each of the five (5) output definitions in the "Diagnostics Menu" section.

RT-SVP04F-EN

73

System Programming SETUP

GBAS (0-10 VDC) Analog Output 1 Assignment NOT ASSIGNED 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. GBAS (0-10 VDC) Analog Output 2 Assignment NOT ASSIGNED 1. 2. 3. 4. 5. 6. 7. 4. 8. Press the + or - key until the proper value is displayed. Press the ENTER key to confirm this choice. Press the NEXT key until the following screen is displayed. Press the NEXT key to display Generic BAS Analog Output 3 screen Press the + or - key until the proper value is displayed. Press the ENTER key to confirm each choice. Repeat steps 1-4 to display Generic BAS Analog Output screens 3 & Press the NEXT key to advance to the following screen. Used with: All units when GBAS 010 VDC Module Factory Presets: Not Assigned Possible Values: ACTIVE COOLING CAPACITY, ACTIVE HEATING CAPACITY, OUTSIDE AIR TEMPERATURE, ACTIVE ZONE TEMPERATURE, ACTIVE SUPPLY AIR TEMPERATURE, ACTIVE SUPPLY AIR PRESSURE, ACTIVE SPACE PRESSURE, ACTIVE SPACE RELATIVE HUMIDITY, ACTIVE OUTDOOR AIR RELATIVE HUMIDITY, ACTIVE SPACE CO2 LEVEL, ACTIVE OUTDOOR AIR DAMPER POSITION, ACTIVE OUTDOOR AIR FLOW

End of Submenu (NEXT) to enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. RTM Alarm Output Diagnostic Assignments Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. RTM Alarm Output Setup Submenu Press ENTER to Review or Adjust 1. Pressing the ENTER key will allow viewing of this Submenu. Assign Diagnostic to Alarm Output? Any Active Diagnostic ____________________ (YES) 1. Press the ENTER key then the NEXT key to display the possible diagnostics that may be assigned to the RTM alarm output definition. 2. Press the + (Plus) key to assign "Yes" to the output definition or (Minus) key to assign "No" to the output definition. 3. Press the ENTER key to confirm each selection. Used with: All Units Possible values: Any Active Diagnostic (YES), Any Active Diagnostic (NO) Screen always shown Used with: All Units

Note: If (NO) is selected, any or all of the diagnostics in the Assignment Submenu-RTM Alarms may be assigned.
All units (if "Any Active Diagnostic" (NO) is selected above)

Assignment Submenu - RTM Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section.

74

RT-SVP04F-EN

System Programming SETUP

Assign Diagnostic to Alarm Output? ____________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Possible values: RTM Zone Temp Sensor Failure Supply Air Temp Sensor Failure RTM Aux Temp Sensor Failure OA Temp Sensor Failure Mode Input Failure Occ Zone Heat SETPOINT Failure Supply Air Pres Sensor Failure OA Humidity Sensor Failure Emergency Stop Supply Fan Failure Exhaust Fan Failure Return Fan Failure Unocc Zone Cool Setpt Failure Unocc Zone Heat Setpt Failure Supply Air Pres Setpt Failure Auto Reset SA Static Pres Limit Manual Reset SA Static Pres Limit NSB Panel Comm Failure RTM Module Data Storage Error Unit HI Communications Failure Supply Air Temp Cool Setpt Fail Supply Air Temp Heat Setpt Fail Dirty Filter NSB Panel Zone Temp Sensor Fail RTM Zone Humidity Sensor Failure Improper Air Flow For Dehumid Occ Dehumid Setpoint Failure Unocc Dehumid Setpoint Failure Unocc Humidity SETPOINT Failure Occ Humidity SETPOINT Failure Mixed Air Proving Failure Final Filter Proving Failure Used With: All units. (if "Any Active Diagnostic" NO selected above)

Assignment Submenu - MCM Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section.

RT-SVP04F-EN

75

System Programming SETUP

Assign Diagnostic to Alarm Output? ________________________ YES

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units. (if ENTER pressed above) Possible values: YES/NO; Lvg Evap Temp Sensor Fail - Ckt 1, Lvg Evap Temp Sensor Fail - Ckt 2, Low Pres Control Open - Ckt 1, Low Pres Control Open - Ckt 2, Cond Temp Sensor Failure - Ckt 1, Cond Temp Sensor Failure - Ckt 2, Compressor Trip - Ckt 1, Compressor Trip - Ckt 2, MCM Communications Failure, Comp, Contactor Fail - Ckt 1, Comp Contactor Fail - Ckt 2, High Super Heat - Ckt 1, Low Refrigerant Charge - Ckt 1, High Super Heat Ckt 2, Low Refrigerant Charge - Ckt 2, Enter Evap Temp Sensor Fail -Ckt 1, Enter Evap Temp Sensor Fail -Ckt 2 Used With: All units with Heat installed. (if "Any Active Diagnostic" NO is selected above)

Assignment Submenu - HEAT Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Assignment Submenu - ECEM Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with Heat installed. (if ENTER pressed above) Possible values: YES/NO; HEAT Aux Temp Sensor Fail, Low Air Temp Limit Trip, Heat Failure, Heat Module Comm Failure

Used With: All units. (if "Any Active Diagnostic" NO is selected above)

Used With: All units with ECEM installed. (if ENTER pressed above) Possible values: YES/NO; Space Static Pres Setpt Failure, Space Pressure Sensor Failure, Return Air Temp Sensor Failure, RA Humidity Sensor Failure, ECEM Communications Failure

76

RT-SVP04F-EN

System Programming SETUP

Assignment Submenu - VOM Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Assignment Submenu - VCM Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Assignment Submenu - GBAS Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? GBAS 0-5VDC Module Comm Failure YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units. (if "Any Active Diagnostic" NO is selected above)

Used With: All units with VOM installed. (if ENTER pressed above) Possible values: YES/NO; VOM Communications Failure, Ventilation Override Mode A, Ventilation Override Mode B, Ventilation Override Mode C, Ventilation Override Mode D, Ventilation Override Mode E

Used With: All units. (if "Any Active Diagnostic" NO is selected above)

Used With: All units with VCM installed. (if ENTER pressed above) Possible values: YES/NO; CO2 Sensor Failure, VCM Aux Temp Sensor Failure, Blocked Return Air, Velocity Pressure Sensor Fail (Back), VCM Communications Failure, Velocity Pressure Sensor Fail (Front)

Used With: All units. (if "Any Active Diagnostic" NO is selected above)

Used With: All units with GBAS 05VDC installed. (if ENTER pressed above) Possible values: YES/NO

RT-SVP04F-EN

77

System Programming SETUP

Assign Diagnostic to Alarm Output? GBAS 0-10VDC Module Comm Failure YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Assignment Submenu - BAS/Network Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Assignment Submenu - BAS/Network Alarms Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Assign Diagnostic to Alarm Output? _________________________ YES 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with GBAS 010VDC installed. (if ENTER pressed above) Possible values: YES/NO

Used With: All units. (if "Any Active Diagnostic" NO is selected above)

Used With: All units with LCI or BCI installed. (if ENTER pressed above) Possible values: YES/NO; BAS Module Comm Failure BAS/Network Comm Failure

Used With: All units with Return Fan installed. (if "Any Active Diagnostic" is not selected above)

Used With: All units with Return Fan installed. (if ENTER pressed above) Possible values: YES/NO (IntelliPak II only); MPM Communications Failure, Auto Reset Return Pressure Limit, Manual Reset Return Pressure Limit, Rtrn Plenum Press Sensor Failure, Energy Recovery Wheel Proof Failure, Lvg Recovery Exh Temp Sensor Fail, Comm Fail, Auto reset Return press. limit, Man limit, Retorn plen. press. failure.

Note: Assigning "Yes" to an Alarm output definition means that if the assigned diagnostic is present, the RTM alarm output will be energized.

78

RT-SVP04F-EN

System Programming SETUP

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

Temperature Input Calibration


The following five (5) Offset screens are used only if calibration of a sensor designated to perform the listed function is necessary. Example: If the temperature sensor for Morning Warm Up (MWU) is checked and a difference between the actual measured room temperature and the corresponding measured sensor value is found, by programming the amount of error into the Temperature Input Offset for Morning Warm Up (MWU) Heat The sensor can be calibrated.

Calibration and Offset Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Temperature Calibration Offset For RTM Zone Temperature Input 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Temperature Calibration Offset For RTM Aux Temperature Input 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 0.0 F 1. Press the + or - key until the proper value is displayed. 0.0 F 1. Press the + or - key until the proper value is displayed.

Used with: All Units

Used With: All Units Factory Presets: 0.0 F Possible Values: Plus or Minus 5.0 F

Used With: All Units Factory Presets: 0.0 F Possible Values: Plus or Minus 5.0 F

Temperature Calibration Offset For RTM Outside Air Temperature Input 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 0.0 F 1. Press the + or - key until the proper value is displayed.

Used With: All Units Factory Presets: 0.0 F Possible Values: Plus or Minus 5.0 F

RT-SVP04F-EN

79

System Programming SETUP

Temperature Calibration Offset For Heat Module Aux Temp Input 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Temperature Calibration Offset For ECEM Return Air Temperature Input 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 0.0 F 1. Press the + or - key until the proper value is displayed. 0.0 F 1. Press the + or - key until the proper value is displayed.

Used With: All Units when Gas, Electric, or Hydronic Heat is installed Factory Presets: 0.0 F Possible Values: Plus or Minus 5.0 F

Used With: All Units when comparative enthalpy is installed Factory Presets: 0.0 F Possible Values: Plus or Minus 5.0 F

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Device Characteristic Setup Definitions Press ENTER to review or Adjust 1. Pressing the NEXT key will bypass this section. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. OA Damper 10.0 VDC Used With: All Units when an economizer is installed Factory Presets: 10.0 VDC Possible Values: 0.1 to 10.0 Volts DC OA Damper 2.0 VDC Used With: All Units when an economizer is installed Factory Presets: 2.0 VDC Possible Values: 0.0 to 9.9 Volts DC OA Damper 30 Sec Used With: All Units when an economizer is installed Factory Presets: 30 Seconds Possible Values: 1 - 255 Seconds Used with: All Units

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

80

RT-SVP04F-EN

System Programming SETUP

Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice.

OA Damper DIRECT ACTING

1. Press the + or - key until the proper value is displayed. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Supply Fan IGV/VFD cmd 0.0 VDC Supply Fan IGV/VFD cmd 30 Sec

Used With: All Units when an economizer is installed Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING, REVERSE ACTING

1. Press the + or - key until the proper value is displayed.

Used With: All Units when IGV/VFD is installed Possible Values: 1 - 255 Seconds (Default 30 seconds)

1. Press the + or - key until the proper value is displayed.

Used With: All Units when IGV/VFD is installed Factory Presets: 0 VDC Possible Values: 0 to 9.9 Volts DC

Note: For VFD set to 0.0 VDC For IGV set to 2.0 VDC
Used With: All Units when IGV/VFD is installed Factory Presets: 10.0 VDC Possible Values: 0.1 to 10.0 Volts DC

Actuator Setup Max Voltage

Supply Fan IGV/VFD cmd 10.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time Return Fan VFD 30 Sec Supply Fan IGV/VFD cmd DIRECT ACTING

1. Press the + or - key until the proper value is displayed.

Used With: All Units when IGV/VFD is installed Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING, REVERSE ACTING

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with Return Fan installed. Possible Values: 1-255 seconds (Default 30 seconds)

RT-SVP04F-EN

81

System Programming SETUP

Actuator Setup Min Voltage

Return Fan VFD 0.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Actuator Setup Max Voltage Return Fan VFD 10.0 VDC

Used With: All units with Return Fan installed. Factory Presets: 0.0 VDC Possible Values: 0.0 - 9.9 (Default
0.0)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Actuator Setup Direct/Reverse Act Return Fan VFD DIRECT ACTING

Used With: All units with Return Fan installed. Factory Presets: 10.0 VDC Possible Values: 0.0 - 10.0 (Default 10.0)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with Return Fan installed. Factory Presets: Direct Acting Possible Values: Direct, Reverse

Actuator Setup Max Stroke Time

Exhaust Damper/VFD 60 Sec

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Exhaust Damper/VFD 2.0 VDC

Used With: All Units when IGV/VFD is installed or Return Fan is installed Factory Presets: 60 Seconds Possible Values: 1 - 255 Seconds

1. Press the + or - key until the proper value is displayed.

Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan is installed. Factory Presets: 2.0 VDC Possible Values: 0.0 to 9.9 Volts DC

Note: For VFD, set to 0.0 VDC; for damper, set to 2.0 VDC

82

RT-SVP04F-EN

System Programming SETUP

Actuator Setup Max Voltage

Exhaust Damper/VFD 10.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Hydronic DIRECT ACTING Hydronic 10.0 VDC Hydronic 2.0 VDC Hydronic 60 Sec Exhaust Damper/VFD DIRECT ACTING

Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan is installed. Factory Presets: 10.0 VDC Possible Values: 0.1 to 10.0 Volts DC Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan is installed. Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING, REVERSE ACTING Used With: All Units when Hydronic Heat and/or Chilled Water is installed Factory Presets: 60 Seconds Possible Values: 1 - 255 Seconds

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

Used With: All Units when Hydronic Heat and/or Chilled Water is installed Factory Presets: 2.0 VDC Possible Values: 0.0 to 10.0 Volts DC Used With: All Units when Hydronic Heat and/or Chilled Water is installed Factory Presets: 0.0 VDC Possible Values: 0.0 to 9.9 Volts DC Used With: All Units when Hydronic Heat and/or Chilled Water is installed with air-cooled condensers Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING, REVERSE ACTING

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

Note: Only one of the following two screens will be shown

RT-SVP04F-EN

83

System Programming SETUP

Actuator Setup Max Stroke Time

Num 1 Low Ambient 60 Sec

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time Cond Fan VFD Ckt 1 60 Sec

Used With: All Rooftop Units and Air Handlers when DX Cooling is installed with air-cooled condensers. Factory Presets: 60 Seconds Possible Values: 1 - 255 Seconds

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 60 seconds Possible Values: 1-255 seconds

Note: Only one of the following two screens will be shown


Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage Cond Fan VFD Ckt 1 0.0 VDC Num 1 Low Ambient 2.0 VDC Used With: All Rooftop Units and Air Handlers when DX Cooling is installed with air-cooled condensers. Factory Presets: 2.0 VDC Possible Values: 0.0 to 9.9 Volts DC Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 0.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: Only one of the following two screens will be shown


Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage Cond Fan VFD Ckt 1 10.0 VDC Num 1 Low Ambient 10.0 VDC Used With: All Rooftop Units and Air Handlers when DX Cooling is installed with air-cooled condensers. Factory Presets: 10.0 VDC Possible Values: 0.1 to 10.0 Volts DC Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 10.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: Only one of the following two screens will be shown

84

RT-SVP04F-EN

System Programming SETUP

Actuator Setup Direct/Reverse Act

Num 1 Low Ambient DIRECT ACTING

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Fan VFD Ckt 1 DIRECT ACTING

Used With: All Rooftop Units and Air Handlers when DX Cooling is installed with air-cooled condensers. Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: DIRECT Possible Values: DIRECT, REVERSE

1. Press the + or - key until the proper value is displayed.

Note: Only one of the following two screens will be shown


Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Fan VFD Ckt 2 60 Sec Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 60 seconds Possible Values: 1-255 seconds Num 2 Low Ambient 60 Sec Used With: All Units with AirCooled Condensers installed Factory Presets: 60 Seconds Possible Values: 1 - 255 Seconds

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

Note: Only one of the following two screens will be shown


Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Fan VFD Ckt 2 0.0 VDC Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 0.0 VDC Possible Values: 0.0 - 10.0 VDC Num 2 Low Ambient 2.0 VDC Used With: All Units with AirCooled Condensers installed Factory Presets: 2.0 VDC Possible Values: 0.0 to 9.9 Volts DC

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

Note: Only one of the following two screens will be shown

RT-SVP04F-EN

85

System Programming SETUP

Actuator Setup Max Voltage

Num 2 Low Ambient 10.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Cond Fan VFD Ckt 2 10.0 VDC

Used With: All Units with AirCooled Condensers installed Factory Presets: 10.0 VDC Possible Values: 0.1 to 10.0 Volts DC

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: 10.0 VDC Possible Values: 0.0 - 10.0 VDC

Note: Only one of the following two screens will be shown


Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Min Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Modulating Gas Heat 2.0 VDC Used With: All Rooftop Units and Air Handlers when Modulating Gas is installed Factory Presets: 2 VDC Possible Values: 0.0 to 9.9 Volts DC Modulating Gas Heat 90 Sec Used With: All Rooftop Units and Air Handlers when Modulating Gas is installed Factory Presets: 90 Seconds Possible Values: 1 - 255 Seconds Cond Fan VFD Ckt 2 DIRECT ACTING Used With: All IntelliPak II units with water-cooled condensers installed. Factory Preset: DIRECT Possible Values: DIRECT, REVERSE Num 2 Low Ambient DIRECT ACTING Used With: All Units with AirCooled Condensers installed Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed.

86

RT-SVP04F-EN

System Programming SETUP

Actuator Setup Max Voltage

Modulating Gas Heat 10 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time Exh Bypass Damper 60 Sec Modulating Gas Heat DIRECT ACTING

Used With: All Rooftop Units and Air Handlers when Modulating Gas is installed Factory Presets: 10 VDC Possible Values: 0.1 to 10.0 Volts VDC Used With: All Rooftop Units and Air Handlers Modulating Gas is installed Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse Acting Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 60 seconds Possible Values: 1-255 seconds

1. Press the + or - key until the proper value is displayed.

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Actuator Setup Min Voltage

Exh Bypass Damper 2.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Stroke Time 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. OA Bypass Damper 60 Sec Exh Bypass Damper DIRECT ACTING Exh Bypass Damper 10.0 VDC

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 2.0.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 10.0.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: DIRECT Possible Values: DIRECT, REVERSE

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 60 seconds Possible Values: 1-255 seconds

RT-SVP04F-EN

87

System Programming SETUP

Actuator Setup Min Voltage

OA Bypass Damper 2.0 VDC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Max Voltage 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Actuator Setup Direct/Reverse Act 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. OA Bypass Damper DIRECT ACTING OA Bypass Damper 10.0 VDC

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 2.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: 10.0 VDC Possible Values: 0.0 - 10.0 VDC

1. Press the + or - key until the proper value is displayed.

Used With: All IntelliPak II units with Energy Recovery installed. Factory Preset: DIRECT Possible Values: DIRECT, REVERSE

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Control Algorithm Tuning Parameters Press ENTER to Review or Adjust

Note: Contact the Trane Company before making any adjustment to these settings
1. Pressing the NEXT key will bypass this section.

End of Submenu (NEXT) to Enter SETUP 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

88

RT-SVP04F-EN

System Programming SETPOINTS


SETPOINT Menu
The SETPOINT menu is used to designate default zone temperature SETPOINTs, supply air and space pressure SETPOINTs, and low ambient compressor lockout SETPOINTs. These SETPOINTs will be active (in use) for the SETPOINT Source Selection designated as DEFAULT for these inputs. When a SETPOINT screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the SETPOINT key again to return to the SETPOINT menu. Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. Press the SETPOINT key to begin viewing or modifying the unit SETPOINTs.

Default Supply Air Temp SETPOINT Cooling: 55 F OR Default Supply Air Temp SETPOINTS Cooling: 55 F Heating: 100 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units Factory Presets: 55 F Possible Values: 40 F to 90 F

Used With: All Units with Hydronic, Electric, or Modulating Gas Heat. Factory Presets: Heating: 100 F, Cooling: 55 F Possible Values: Cool: 40 F to 90 F, Heat: 40 F to 180 F

Supply Air Temperature Deadband Cooling: 8.0 F OR

Used With: All Units Factory Presets: 8.0 F Possible Values: Cooling: 4 - 20 F

RT-SVP04F-EN

89

System Programming SETPOINTS

Supply Air Temperature Deadband Cooling: 8.0 F Heating: 4.0 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units with Electric, Hydronic, or Modulating Gas


Factory Presets: Cooling: 8 F, heat: 4 F

Possible Values: Cooling:4 F to 20 F, Heat: 2 F to 10 F

Default Daytime Warmup SETPOINTS Cooling: 67 F Terminate: 71 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All units with Gas, Hydronic, Electric, or External Heat installed. Factory Presets: Initiate: 67 F, Terminate: 71 F Possible Values: DWU Initiate: 50 F to 87 F DWU Terminate: 53 F to 90 F

Default Occupied Zone Temp SETPOINTS Heat: 71 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when Gas Electric, Hydronic or External Heat is installed and Daytime warmup is enabled. Factory Presets: Heat: 71 F, Possible Values: Heat: 50 F to 90F This is the SETPOINT to which the heat is controlled during Daytime Warmup mode.

Default Unoccupied Zone Temp SETPOINTS Cool: 85 F OR Default Unoccupied Zone Temp SETPOINTS Cool: 85 F Heat: 60 F Morn Warmup: 72 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units Factory Presets: 85 F Possible Values: 52 F to 90 F

Used With: All Units when Gas Electric, Hydronic or External Heat is installed. Factory Presets: Cool: 85 F, Heat: 60 F, Morning Warmup: 72 F Possible Values: Cool: 52 F to 90F, Heat: 50 F to 88F, Morning Warmup: 50 F to 90 F. Minimum difference of 2 degrees F maintained between Heating & Cooling SETPOINTS. Morning warmup cannot be lower than Heating SETPOINTS.

90

RT-SVP04F-EN

System Programming SETPOINTS

Derived Zone stp Dead:

xx.xF

Used With: CV units w/ one stp only 2.0 -10F DEFAULT 4.0 USED WHEN ONE SETPOINT IS AVAIL.

1. Pressing the NEXT key will scroll forward through the screens. Humidity Control SETPOINT Submenu Used With: All units with Dehumidification or Humidification option installed.

Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Dehumidify if Space Humidity Above Occ Dehumidification Setpoint: 60% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Stop Dehumid if Space RH Below STP Minus Occ Dehumid Hysteresis Offset: 5% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Dehumidify if Space Humidity Above Unocc Dehumidification Setpoint: 60% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Stop Dehumid if Space RH Below STP Minus Unocc Dehumid Hysteresis Offset: 5% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 60% Possible Values: 40-65%

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 5% Possible Values: 3-10%

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 60% Possible Values: 40-65%

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 5% Possible Values: 3-10%

RT-SVP04F-EN

91

System Programming SETPOINTS

Default Supply Air Reheat Stpt: Supply Air Reheat Deadband:

70F 4F

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) In Active Dehumidification Mode, Limit Maximum Reheat Valve Position To: 85% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Dehumid Ovrd High Zone Temp Stpt: Dehumid Ovrd Low Zone Temp Stpt: 75F 68F

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: Reheat Setpoint: 70 F; Reheat Deadband: 4 F Possible Values: Reheat Setpoint: 60-80 F; Reheat Deadband: 2-10 F

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 85% Possible Values: 50-85%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Cond Coil Purge Interval Setpt: 90 Min

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: Ovrd High Temp: 75 F; Ovrd Low Temp: 68 F Possible Values: Ovrd High Temp: 70-85 F; Ovrd Low Temp: 60-75 F

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Humidify if Space Humidity Below Occ Humidification SETPOINT: 30% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) Stop Humid if Space RH Above STP Plus Occ Humid Hysteresis Offset: 5% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All IntelliPak units with Dehumidification option installed Factory Preset: 90 Minutes Possible Values: 60-120 Minutes

Used With: All units with Occupied Humidification option installed. Factory Preset: 30% Possible Values: 20-50%

Used With: All units with Occupied Humidification option installed. Factory Preset: 5% Possible Values: 3-10%

92

RT-SVP04F-EN

System Programming SETPOINTS

Humidify if Space Humidity Below Unocc Humidification SETPOINT: 30% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All units with Unoccupied Humidification option installed. Factory Preset: 30% Possible Values: 20-50%

Stop Humid if Space RH Above STP Plus Unocc Humid Hysteresis Offset: 5% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All units with Unoccupied Humidification option installed. Factory Preset: 5% Possible Values: 3-10%

End Of Submenu (NEXT) to Enter SETPOINT 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

Used With: All units Screen shown if in this submenu

Outside Air Control SETPOINT(S) Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. WHEN ECON COOL, SPACE REDUCE ZONE TEMP COOL STP BY X.Xf 0-3.0 DEFAULT 1.5 1. Pressing the NEXT key will scroll forward through the screens. Reference Enthalpy: Enable Air econ 25 BTU/LB

Used With: All units with Fresh Air Configuration set to any option other than NONE.

When OA Enthalpy is below: 2. Press the ENTER key to confirm this choice.

1. Press the + or - key until the proper value is displayed. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units when an economizer is installed and Reference Enthalpy is engaged Factory Presets: 25 BTU/LB Possible Values: 19 to 28 BTU/LB

Note: This Setpoint is used when comparative enthaltpy is not installed or is invalid.
Used With: All units when an economizer is installed and Dry bulb Control is enabled--Configuration set to any option other than NONE. Possible Values: 50-140 F (Default 75 F)

Default Econ Drybulb Enable SETPOINT Enable Economizer Below: 75 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Note: This Setpoint is used when comparative enthaltpy is not installed or is invalid.
93

RT-SVP04F-EN

System Programming SETPOINTS

Supply Air Low Limit - Modulate Economizer Toward Min Pos if SA Temp below: 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. VCM Preheat ON If VCM Aux Temp Below Ventilation Preheat SETPOINT: 35 F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) 50 F 1. Press the + or - key until the proper value is displayed.

Used With: All Units when an economizer is installed Factory Presets: 50 F Possible Values: 40 to 65 F

Used With: All units with Fresh Air Measurement w/DCV or OA Damper Min Position w/DCV installed and Preheat is enabled. Possible Values: 35-75 F (Default 35 F)

Default Design Min CO2 Setpt: Default DCV Min CO2 SETPOINT:

1000 PPM 400 PPM

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Default Design Min OA Flow Stp: Default DCV Min OA Flow Setpt: OR 855 CCFM 652 CCFM

Used With: All units with DCV enabled. Possible Values: Default Design Min 150-2000 PPM (Factory Default 1000 ppm); Default DCV Min 501900 PPM (Factory Default 400)

Used With: All units with Fresh Air Measurement w/DCV and DCV enabled. Factory Preset: 112 CCFM or 146 CCFM (based on unit size) Possible Values: Default Design= 0-585 CCFM Default DCV=0-585 CCFM Used With: All units with Fresh Air Measurement w/DCV and DCV enabled. Factory Preset: 5 CCFM Possible Values: 50-200

Demand Controlled Ventilation Min OA Flow deadband: OR 5 CCFM

Default Min OA flow SETPOINT: Min OA Flow Deadband: OR

40 CFM 10.0 CFM

Used With: All Units when VCM is installed with TRAQs installed and DCV disabled. Factory Presets: See Airflow Deadband below Possible Values: SETPOINT: 0 to Max Unit Airflow, Max Unit Airflow: 0-585 CCFM Deadband: 500 - 2000 CFM

94

RT-SVP04F-EN

System Programming SETPOINTS

Default Design Min OA Damper Pos: Default DCV Min OA Damper Pos Stp: OR

15% 10%

Used With: All units with DCV enabled and 0-100% OA Damper installed. Possible Values: Default Design= 0-100% (default 15%); Default DCV= 0-100% (Default 10%) Used With: VAV units with IGV/VFD and 0-100% OA Damper and OA CFM Compensation is enabled. Possible Values: 0-100% (Default 15%)

Default OA Damper Min Position: With IGV/VFD Command At Minimum

15% (0%)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Note: OA Damper Min Pos with IGV at Min MUST BE > OA Damper Min Pos with IGV at Max
Default OA Damper Min Position: With IGV/VFD Command At Maximum 15% (100%) Used With: VAV units with IGV/VFD and 0-100% OA Damper and OA CFM Compensation is enabled. Possible Values: 0-100% (Default 10%)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Note: OA Damper Min Pos with IGV at Min MUST BE > OA Damper Min Pos with IGV at Max
OR Default OA Damper Min Position: 15% Used With: Screen shown only if 0-25% Damper installed, or unit is configured with 0-100% Damper with DCV disabled and OA CFM Compensation function disabled. Possible Values: 0-100% (Default 15%)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Note: If unit has TRAQ, this setpoint is not used.


Used With: All units

End Of Submenu (NEXT) To Enter SETPOINT 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

RT-SVP04F-EN

95

System Programming SETPOINTS

Default Supply Air Pressure: High Limit: 4.0 IWC Deadband:

2.0 IWC 0.5 IWC

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when IGV/VFD is installed. High Limit shown when VAV without IGV/VFD & Supply Air Pressure Sensor is installed. Factory Presets: SETPOINT: 2.0 IWC High Limit: 4.0 IWC Deadband: 0.5 IWC Possible Values: SETPOINT 0.7 5.1 IWC High Limit 1.2 - 5.7 IWC Deadband 0.1 - 2.0 IWC

Note: SETPOINT cannot be adjusted above: High Limit = Deadband divided by 2 minus 0.1
Max Return Plenum Pressure Stp: Deadband: 0.2 IWC 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Default Space Pressure SETPOINT: Space Pressure Deadband: 0.08 IWC 0.10 IWC 1.2 IWC Used With: All units with Return Fan VFD installed. Possible Values: Max Return= 0.1 - 2.5 IWC (Default 1.2 IWC) Deadband= 0.1 - 1.0 IWC (default 0.2 IWC)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Exhaust Enable Point. Enable Exhaust Fan 25%

Used With: All Units when Power Exhaust with Statitrac is installed or Return Fan with Statitrac installed Factory Presets: SETPOINT: 0.08 IWC, Deadband: 0.04 IWC Possible Values: SETPOINT: -0.2 to 0.3 IWC, Deadband 0.02 - 0.2 IWC

When Outside Air damper is Above: 2. Press the ENTER key to confirm this choice.

1. Press the + or - key until the proper value is displayed. 3. Press the NEXT key until the following screen is displayed. Low Ambient Comp Lockout Temp: 50 F

Used With: All Units when Power Exhaust with or without Statitrac installed, but without Return Fan. Factory Presets: 25% Possible Values: 0 to 100%

Comp(s) OFF if OA Temp Below This Value 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units with DX Cooling Factory Presets: 50 F Possible Values: -20 F to 80 F

96

RT-SVP04F-EN

System Programming SETPOINTS

For Standby Freeze Avoidance, Open the Hydronic Heat Valve (s) To: 0% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Frost Avoidance ON When LRE Temp Below Recovery Frost Avoidance Setpoint: 27F 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable) SETPOINT Source Selections Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section For Supply Air Temp Cooling Control, SETPOINT From: Use

Used With: All units with Hydronic Heat installed. Factory Preset: 0% Possible Values: 0-100%

Note: When the active outside air temperature drops below 45 F , this output is active.

Used With: All units with Energy Recovery option installed Factory Preset: 27 F Possible Values: 0-60 F

Used With: All Units

HI (KEYPAD) SETPOINT MENU

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (KEYPAD) SETPOINT MENU, ZONE SENSOR SETPOINT INPUT, NSB PANEL SETPOINT INPUT, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module Used With: All Units when hydronic Heat or Modulating Gas Heat is installed with GBAS 0-5VDC or GBAS 0-10 VDC module Factory Presets: HI (Keypad) Setpoint Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module Used With: All Units when Gas, Electric or Hydronic Heat is installed with Daytime Warmup Enabled Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, ZONE SENSOR SETPOINT INPUT, NSB PANEL SETPOINT INPUT, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module

For Supply Air Temp Heating Control, SETPOINT From:

Use

HI (KEYPAD) SETPOINT MENU

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

For Occ Zone Temp Heating Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

97

System Programming SETPOINTS

For Unocc Zone Temp Cooling Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, ZONE SENSOR SETPOINT INPUT, NSB PANEL SETPOINT INPUT, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module Used With: All Units when Gas, Electric or Hydronic Heat or external Heat is installed Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, ZONE SENSOR SETPOINT INPUT, NSB PANEL SETPOINT INPUT, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module Used With: All Units when Gas, Electric or Hydronic Heat is installed Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, NSB PANEL SETPOINT INPUT GBAS 0-5VDC Module GBAS 0-10VDC Module Used With: All units with Economizer installed. Factory Presets: HI (Kyepad) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module

For Unocc Zone Temp Heating Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

For Morning Warmup Temp Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

For Economizer Dry Bulb Enable, Use SETPOINT From: HI (Keypad) Setpoint Menu_____________ 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) For Default OA Damper Min Position, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units when an economizer or VCM is installed and Remote Min Position Pot or GBAS 05VDC or GBAS 0-10VDC is installed. Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, REMOTE MIN POS POT INPUT, GBAS 0-5VDC Module, GBAS 0-10VDC Module

98

RT-SVP04F-EN

System Programming SETPOINTS

Humidity Ctrl Stpt Source Select Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. For Occ Dehumidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT Menu 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units

Used With: All IntelliPak units with Dehumidification option installed and GBAS 0-5Vdc or GBAS 0-10Vdc installed Factory Preset: HI (KEYPAD) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT Menu, GBAS 0-5VDC Module, GBAS 0-10VDC Module Used With: All IntelliPak units with Dehumidification option installed and GBAS 0-5Vdc or GBAS 0-10Vdc installed Factory Preset: HI (KEYPAD) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT Menu, GBAS 0-5VDC Module, GBAS 0-10VDC Module Used With: All units with Occupied Humidification enabled and GBAS 05VDC or 0-10VDC installed. Factory Presets: HI (KEYPAD) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module Used With: All units with Unoccupied Humidification enabled and GBAS 0-5VDC or 0-10VDC installed. Factory Presets: HI (KEYPAD) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module Used With: All IntelliPak units with Unoccupied Humidification enabled and GBAS 0-5VDC or 0-10VDC installed. Factory Presets: HI (KEYPAD) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC Module, GBAS 0-10VDC Module
99

For Unocc Dehumidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT Menu 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

For Occ Humidification Control, Use SETPOINT From: _____________________ 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

For Unocc Humidification Control, Use SETPOINT From: _____________________ 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

For Supply Air Reheat Control, Use Setpoint From: HI(KEYPAD) SETPOINT Menu 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable)

RT-SVP04F-EN

System Programming SETPOINTS

Used With: All units. End Of Submenu (NEXT) To ENTER SRC SEL 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

For Min Outside Air Flow Rate Ctrl, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units when VCM and GBAS is installed Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module

For Supply Air Pressure Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units when IGV/VFD and GBAS 0-5 VDC Module is installed or GBAS 0-10VDC is installed Factory Presets: Factory Presets: HI (Keypad) SETPOINT Menu Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5VDC GBAS 0-10VDC Used With: All Units when Power Exhaust with Statitrac is installed and GBAS 0-5VDC or GBAS 010VDC Factory Presets: HI (KEYPAD) SETPOINT MENU Possible Values: HI (KEYPAD) SETPOINT MENU, GBAS 0-5 VDC MODULE, GBAS 0-10VDC Module

For Space Pressure Control, Use SETPOINT From: HI (KEYPAD) SETPOINT MENU 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

End Of Submenu (NEXT) To Enter SETPOINT 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu.

100

RT-SVP04F-EN

System Configuration
CONFIGURATION Menu
The electronically controlled unit has many operating functions whose settings are preset at the factory. The following configuration programming steps are provided for those cases where the Human Interface module has been replaced after the unit has been in operation and must be reconfigured. Refer to the Model number stamped on the unit nameplate located on the control panel door while scrolling through the configuration screens. Certain digits of this alpha/ numeric model number provide information that must be entered at the Human Interface (HI) in order for the UCM network to operate properly. Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. Press the CONFIGURATION key to begin viewing or modifying the configuration screens. Note: Pay close attention to the notes throughout this section of the document. The notes describe additional essential messages and other intermediate screen information.

Unit Product family is: Press (NEXT) or

IntelliPak II

(Previous) to Continue

Possible Values: IntelliPak I, IntelliPak II

Note: This screen is not adjustable. Configuration is based on the presence (IntelliPak II) or absence (IntelliPak I) of a configuration jumper on the RTM.
Configuration - Model Num Digit 1 Unit Type: ROOFTOP UNIT 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Used With: All Units Possible Values: CONFIG REQD, ROOFTOP UNIT, AIR HANDLER

Note: For IntelliPak II products, if "Unit Type" is changed from Air Handler to Rooftop, then "Unit Capacity" is set to CONFIG REQD. If "Heating Type" is Electric Heat, the "Electric Heat Capacity" is also set to CONFIG. REQD.
Configuration - Model Num Digit Heating Type: 2 GAS Used With: All Units. Possible Values: CONFIG REQD, ELECTRIC, GAS, HYDRONIC, EXTERNAL HEAT, NONE (COOLING ONLY)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

101

System Configuration

Configuration - Model Num Digit Unit Capacity: OR Configuration - Model Num Digit Unit Capacity CFM:

5, 6, 7 90

Used With: Rooftop Units and Air Handlers with DX Cooling Possible Values: 20-162 Tons

5, 6, 7 16100-45000

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Cooling Type: OR 6 NO COOLING

Used With: Screen shown only for RT AH units with None or Chilled Water Cooling Possible Values: CONFIG REQD, 4000-45000

Used With: Screen shown only if Air Handler Unit Possible Values: CONFIG REQD, No Cooling, DX Cooling, Chilled Water Used With: Units with Electric Heat installed Possible Values: Not CONFIG, CONFIG, 30, 50, 70, 110, 130, 150, 170, 190 kW

Configuration - Model Num Digit Electric Heat Capacity:

9 90 KW

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. OR Configuration - Model Num Digit Gas Heat Type: 9 STAGED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Exhaust/Return: 17 or 11 NONE

Used With: Screen shown only if Gas Heat installed Possible Values: Staged, Modulating

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All Units Possible Values: CONFIG REQD, None, EXH FAN_W/ STATITRAC, EXH FAN_W/O STATITRAC, RET FAN W/ STATITRAC, RET FAN W/O STATITRAC

Note: Return Fan selection not permitted to be installed if Energy Recovery option is already installed.
Configuration - Model Num Digit System Control: 20 or 17 ZONE TEMP CTRL (CV) Used With: All Units Possible Values: CONFIG REQ'D, ZONE TEMP CTRL (CV), DISCH TEMP CTRL (VAV), DISCH TEMP CTRL (CV)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

102

RT-SVP04F-EN

System Configuration

Note: For DISCH TEMP CTRL (VAV) possible value, this indicates with IGV/VFD. Note: For DISCH TEMP CTRL (CV) possible value, this indicates without IGV/VFD.
Configuration - Model Num Digit Fresh Air Section: 21 or 16 No Fresh Air Used With: All Units Possible Values: CONFIG REQ'D, NO FRESH AIR, 0-100% ECONOMIZER, 025% MOTORIZED DAMPER

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Ventilation Ctrl (VCM) CONFIG REQ'D 21 or 31

Used With: All Units Possible Values: * Ventilation Ctrl (VCM) CONFIG REQ'D, * Ventilation Ctrl (VCM) NOT INSTALLED * Fresh Air Measurement(VCM) W/ DCV OPTION * OA Damper Min Pos (VCM) W/ DCV OPTION

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: For Ventilation Ctrl (VCM) NOT INSTALLED possible value, this screen used to indicate Ventilation Ctrl module NOT INSTALLED. There are two possible VCM "installed" options.
Configuration - Model Num Digit Comparative Enthalpy: 21 or 23 INSTALLED Used With: Screen always shown Possible Values: CONFIG REQ'D, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Final Filters: 24 INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Energy Recovery: 25 NOT INSTALLED

Used With: All IntelliPak II Units Possible Values:CONFIG REQ'D, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All IntelliPak II Units with Energy Recovery installed Possible Values: CONFIG REQ'D, NOT INSTALLED, INSTALLED W/O PREHEAT, INSTALLED W/ PREHEAT

Note: This feature not permitted to be installed if Return Fan is already installed.

RT-SVP04F-EN

103

System Configuration

Configuration - Model Num Digit Condenser Type:

27 Air-Cooled

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Used With: All IntelliPak II Units Possible Values: CONFIG REQ'D, AIRCOOLED, WATER-COOLED W/O SUMP HT, WATER-COOLED WITH SUMP HT

Note: For WATER-COOLED possible values the unit must be physically configured with water-cooled condensers or improper operation and possible unit damage may occur.
Configuration - Model Num Digit Dehumid w/ Hot Gas Reheat: 30 or 22 NOT INSTALLED Used With: All IntelliPak Units Possible Values: NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: This feature uses a hardware configuration jumper and is not HI adjustable.
Configuration - Model Num Digit Hot Gas Bypass: 30 or 22 INSTALLED Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: If Hot Gas Bypass is installed Low Charge Protection and Lead/Lag functions will be automatically disabled.
Configuration - Model Num Digit Ambient Control: 31 or 19 STANDARD Used With: All Units Possible Values: CONFIG REQD, STANDARD, 0 DEGREE F

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

Note: When set to "STANDARD" the Low Abient Compressor Lockout setpoint may not be set less than 40 F . When set to "0 DEGREE F" the setpoint can be set down to -20 F .
Configuration - Model Num Digit Remote Human Interface 33 or 30 INSTALLED Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed.

104

RT-SVP04F-EN

System Configuration

Configuration - Model Num Digit BAS Communication Module

34 or 35 INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit GBAS 0-5 VDC Module 34 or 28 INSTALLED

Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit GBAS 0-10 VDC Module 34 or 28 INSTALLED

Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Configuration - Model Num Digit Ventilation Override (VOM) 34 or 31 INSTALLED

Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. Unit Model Number 1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: RTM INVALID 24.00

Used With: All Units Possible Values: CONFIG REQD, NOT INSTALLED, INSTALLED

Used With: All units unless RTM has been changed. Possible Values: Model Number

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

Used With: Screen always shown Possible Values: Software Revision Number: See note below; RTM (before the period): 0-255; RTM (after the period): 00-99

Note: "INVALID" shown in upper right corner if s/w version not valid for unit w/IntelliPak II config jumper.

RT-SVP04F-EN

105

System Configuration

Software Revision Number: Multiple Compressor Module (MCM)

INVALID 15.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

Used With: Screen always shown on Ipak II and MCM Installed (DX Cooling) Possible Values: Software Revision Number: See note below; MCM (before the period): 0-255; MCM (after the period): 00-99

Note: "INVALID" shown in upper right corner if software version not valid for unit w/IntelliPak II config jumper (All following version screens).
Software Revision Number: GBAS 0-5 VDC Module INVALID 5.0 Used With: Screen shown only if GBAS 0-5 VDC Module installed Possible Values: Software Revision Number: See note below; Module (before the period): 0-255; Module (after the period): 00-99 Used With: Screen shown only if GBAS 0-10 VDC Module installed Possible Values: Software Revision Number: See note below; Module (before the period): 0-255; Module (after the period): 00-99 Used With: Screen shown only if VOM module installed Possible Values: Software Revision Number: See note below; VOM (before the period): 0-255; VOM (after the period): 00-99 Used With: Screen shown only if Comparative Enthalpy, Power Exhaust with Statitrac installed Possible Values: Software Revision Number: See note below; Module (before the period): 0-255; Module (after the period): 00-99 Used With: Screen shown only if unit is not Cooling Only and unit is not External Heat Possible Values: Software Revision Number: See note below; Module (before the period): 0-255; Module (after the period): 00-99

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: GBAS 0-10 VDC Module INVALID 2.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: Ventilation Override (VOM) INVALID 3.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: Exhaust/Comp Enthalpy Module INVALID 11.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

Software Revision Number: Heat Module

INVALID 11.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

106

RT-SVP04F-EN

System Configuration

Software Revision Number: Unit Human Interface (HI)

INVALID 32.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: Remote Human Interface (RHI) INVALID 32.00

Used With: Screen always shown Possible Values: Software Revision Number: See note below; HI (before the period): 0-255; HI (after the period): 00-99

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

Used With: Screen shown only if Remote Human Interface Module installed Possible Values: Software Revision Number: See note below; RHI (before the period): 0-255; RHI (after the period): 00-99 Used With: Screen shown only if VCM Module installed Possible Values: Software Revision Number: See note below; VCM (before the period): 0-255; VCM (after the period): 00-99 Used With: Screen shown only if LCI or BCI Module installed Possible Values: Software Revision Number: See note below; Comm5 (before the period): 0-255; Comm5 (after the period): 00-99 Used With: Screen shown only on IntelliPak II unit with MPM (Return Fan or Energy Wheel) installed Possible Values: Software Revision Number: See note below; MPM (before the period): 0-255; MPM (after the period): 00-99 Used With: All units with Dehumidification installed Possible Values: 0-255 before the period; 0-99 after the period.

Software Revision Number: Ventilation Control Module (VCM)

INVALID 4.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: BAS Communications: Comm5 INVALID 14.00

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen. Software Revision Number: Multi-Purpose Module (MPM) INVALID 1.0

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

Software Revision Number: Modulating Dehumid Module (MDM)

INVALID 1.0

1. Pressing the NEXT key will scroll forward through the screens. 2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

RT-SVP04F-EN

107

System Testing & Troubleshooting


SERVICE MODE Menu (Local Human Interface only)
The SERVICE MODE menu is used to input operating parameters for unit operation during a service test. Depending on the particular test being conducted, the user will cycle through all unit outputs (compressors, fans, dampers, heaters, etc.) and selectively turn them On or Off for the test. After designating the operating status for each unit component, the operator will designate the TEST START delay time. When a service mode screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general operating status display. If this happens, press the SERVICE MODE key again to return to the service menu. Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. To operate the system in the TEST MODE, press the SERVICE MODE key to enter into the service mode menu and scroll through all of the system outputs and selectively turn them On or Off .

Supply Air Controls Supply Fan OFF OR Supply Air Controls Supply Fan OFF IGV/VFD Cmd OR 35%

Used With: All Units without IGV/ VFD without Return Fan Possible Values: ON, OFF, AUTO Used With: All Units when IGV/VFD is installed without Return Fan Possible Values: ON, OFF, AUTO IGV/VFD Cond: 0 - 100% 0% Used With: All units with Return Fan installed. Possible Values: Supply Fan= OFF, ON, AUTO IGV/VFD= 0-100% Return Fan= OFF, ON, AUTO VFD Cmd= 0-100%

Supply Fan Return Fan

OFF OFF

IGV/VFD Cmd VFD Cmd 0%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Note: IGV/VFD command must be 100% if 2 stage gas is being tested.

Note: Supply Fan and Return Fan modifications will change a common SETPOINT (if one is changed, the other automatically changes.)
RTM VAV Box Relay RTM Alarm Output 1. Press the NEXT key until the following screen is displayed. Used With: All Units Possible Values: RTM VAV Box relay, Drive Max Auto, Alarm Output On/Off
RT-SVP04F-EN

108

System Testing & Troubleshooting

Humidification Relay

ON

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All units with RTM, MCM, and HI. Possible Values: ON, OFF

Note: Humidification Relay can only be set ON if Supply Fan Output is set ON. A message will display indicating such and operation will be prevented
Energy Recovery Control Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Energy Recovery Wheel Operation: Energy Recovery Preheat Relay: OFF OFF Used With: All IntelliPak II units with Energy Recovery installed Factory Preset: Wheel Operation: OFF; Preheat Relay: OFF Possible Values: ON, OFF Used With: All IntelliPak II units with Energy Recovery installed

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Note: Attempting to set the ER Preheat relay to the ON state without the Supply Fan Output being in the ON state first will generate an informational message and the operation will be prevented.
Exhaust Air Bypass Damper Pos: Outside Air Bypass Damper Pos: 0% 0% Used With: All IntelliPak II units with Energy Recovery installed Factory Preset: 0% Possible Values: 100%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

RT-SVP04F-EN

109

System Testing & Troubleshooting

End Of Submenu (NEXT) For Service Mode 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Compressor and Condenser Fan Submenu Press ENTER to Review or Adjust 1. Pressing the NEXT key will bypass this section. Head Pressure Control: Enables Automatic Sump and Fan Control 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable). AUTO

Used With: All IntelliPak II units with Energy Recovery installed

Used With: All Rooftops or Air Handlers with DX Cooling.

Used With: All IntelliPak II units with water-cooled condensers installed Factory Preset: AUTO Possible Values: AUTO, MANUAL; Second Line: Enables Automatic Sump and Fan Control, Manual Sump and Fan Control Allowed Used With: All IntelliPak II units with water-cooled condensers installed Factory Preset: Fan Relay: OFF; Fan Speed: 0% Possible Values: Fan Relay: ON, OFF; Fan Speed: 0-100%

Condenser Fan Relay

K1:

OFF 0%

Condenser Fan Speed Ckt1:

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Condenser Fan Relay K5: OFF 0%

Condenser Fan Speed Ckt2:

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Condenser Sump Pump Relay: OFF

Used With: All IntelliPak II units with water-cooled condensers installed Factory Preset: Fan Relay: OFF; Fan Speed: 0% Possible Values: Fan Relay: ON, OFF; Fan Speed: 0-100%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All IntelliPak II units with water-cooled condensers installed Factory Preset: OFF Possible Values: ON, OFF

110

RT-SVP04F-EN

System Testing & Troubleshooting

Sump Fill Relay: Sump Drain Relay:

OFF OFF

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Sump Heater Relay: OFF

Used With: All IntelliPak II units with water-cooled condensers installed Factory Preset: OFF Possible Values: ON, OFF

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed (if applicable). Condenser Fan Outputs (MCM 1) K1 OFF K2 OFF K5 OFF K6 OFF 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: All IntelliPak II units with water-cooled condensers and sump heat installed Factory Preset: OFF Possible Values: ON, OFF

Used With: All Rooftops or Air Handlers with DX Cooling and Airside Condensers. Possible Values: ON, OFF, AUTO

Note: If either 1A or 1B (Ckt 1) is set to AUTO, the other will automatically be changed to AUTO. The same is true of 2A and 2B (Ckt 2). If either is set to AUTO, the other will be changed also
Condenser Fan Speed (MCM) Ckt 1 0% Ckt 2 0% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Used With: All Rooftops and Air Handlers with DX Cooling and Airside Condensers. Possible Values: AUTO, 0-100% (default 0%)

RT-SVP04F-EN

111

System Testing & Troubleshooting

Compressor Relays (MCM 1) K11 OFF K12 OFF K3 OFF K4 OFF 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Reheat Pumpout Coil Relay: Reheat Valve: CLOSED 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). ON

Used With: All Rooftops or Air Handlers with DX Cooling. Possible Values: OFF, ON

Used With: All IntelliPak units with Dehumidification installed Factory Preset: ON; Reheat Valve: CLOSED (Status Only); Cool Valve: OPEN (Status Only) Possible Values: Coil Relay: ON, OFF; Reheat Pumpout: OPEN, CLOSED; Cooling Pumpout: OPEN, CLOSED

Note: This parameter may be adjusted manually only when compressors are set to OFF . Otherwise the value is set automatically as a function of Reheat Valve position.
Dehumid Reheat Valve Position: Dehumid Cooling Valve Position: 0% 100% Used With: All units with Dehumidification installed Factory Preset: Reheat Valve: 0%; (Cooling Valve: 100% as status only) Possible Values: Reheat Valve: 0, 10-90%; Cooling Pumpout: 100%, 10-90% (Status only)

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

End Of Submenu (NEXT) For Service Mode 1. Press the NEXT key to leave the submenu and show following screen. 2. Press PREVIOUS to page back through the submenu. Relay State = Hydro Heat/Chilled Water Output HEAT ON 0%

Used With: All Rooftops or Air Handlers with DX Cooling.

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable).

Used With: Air Handlers with Chilled Water Cooling and Hydronic Heat. Possible Values: Relay State= HEAT ON, COOL ON, OVERRIDE; 0100%

112

RT-SVP04F-EN

System Testing & Troubleshooting

Relay State = Mod Gas Heat/Chilled Water Output

HEAT ON 0%

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). CHILLED WATER Actuator 0% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key to advance the cursor. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable). Hydronic Heat Actuator 0% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed. Modulating Gas Heat Actuator 0% 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed. Heat Stages: K11: OFF 0 K12: OFF K1: OFF

Used With: Air Handlers with Chilled Water Cooling and Modulating Gas Heat installed. Possible Values: Relay State= HEAT ON, COOL ON; 0-100%

Used With: Air Handlers with Chilled Water Cooling and Heat type is not Hydronic or Mod Gas Heat. Possible Values: 0-100%

Used With: All Rooftop Units when Hydronic heat is installed and Air Handlers when DX Cooling is installed Factory Presets: 0% Possible Values: 0 - 100% Used With: All Rooftop Units when Modulating Gas is installed and Air Handlers when DX Cooling is installed Factory Presets: 0% Possible Values: 0 - 100% Used With: All Units when Staged Gas Heat or electric Heat is installed Factory Presets: OFF Possible Values: OFF, ON, Heat Stages: 0-6

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed.

RT-SVP04F-EN

113

System Testing & Troubleshooting

OA Damper Pos

0%

Exhaust Damper: 0% Exhaust Fan: OFF

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All units; OA Damper Pos (Fresh Air) shown if 100% Economizer* or 25% Motorized OA Damper installed Exhaust (Damper) shown only if Power Exhaust or Return Fan with Statitrac is installed Exhaust Fan shown only if Power Exhaust (no Return Fan) is installed (with or without Statitrac) Possible Values: OA Damper: 0 to 100% (Economizer installed) or 025% (Motorized OA Damper installed); Exhaust Damper= 0100%; Exhaust fan= OFF, ON

Ventilation Override Module Output Relay OFF 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed. VCM Preheater State OFF

Used With: All Units when VOM is installed Factory Presets: OFF Possible Values: ON, OFF

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice 3. Press the NEXT key until the following screen is displayed. GBAS 0-5 VDC Module Relay Outputs #1 OFF #2 OFF #3 OFF #4 OFF #5 OFF 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when VCM is installed Factory Presets: OFF Possible Values: ON, OFF

Used With: All Units when GBAS 05 VDC is installed Factory Presets: OFF Possible Values: 1, 2, 3, 4, 5 = ON, OFF

GBAS 0-10 VDC Module Relay Outputs #1 OFF 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units when GBAS 010 VDC is installed Possible Values: OFF, ON

114

RT-SVP04F-EN

System Testing & Troubleshooting

GBAS 0-10 VDC Module Analog Outputs #1 0v #2 0v #3 0v #4 0v 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable) Status/Annunc Test Heat: OFF Cool: OFF Sys On (Blinking) Service: OFF

Used With: All Units when GBAS 010 VDC is installed Possible Values: 0-10.0 v

1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units Factory Presets: OFF Possible Values: HEAT = ON, OFF COOL = ON, OFF SERVICE = ON, OFF

Start Test In Press TEST START To Begin, STOP To Halt 1. Press the + or - key until the proper value is displayed. 2. Press the ENTER key to confirm this choice. 3. Press the NEXT key until the following screen is displayed. 4. Repeat steps 1 and 2 for the next value. 5. Press the NEXT key until the following screen is displayed (if applicable)

Used With: All Units Factory Presets: 5 Seconds Possible Values: 0 to 120 Seconds

RT-SVP04F-EN

115

System Testing & Troubleshooting

DIAGNOSTICS Menu
The DIAGNOSTICS menu is used to view diagnostics that have resulted from system failures within the unit. There are two lists where diagnostics reside; the Active list, and the Diagnostic Event Log. The Active list is used for viewing all active diagnostics and for clearing diagnostics that can be manually reset. These lists of diagnostics are displayed after pressing the DIAGNOSTICS key if active diagnostics are present. Active manual diagnostics can be cleared in batch form at the unit mounted Human Interface. When an Active diagnostic is manually or automatically cleared, it is removed from this buffer. Automatically resetting diagnostics can not be reset by the Human Interface, because the condition that caused the diagnostic has to be corrected for the diagnostic to clear. The word MORE is displayed on all screens if more than one diagnostic exist, except for the last diagnostic. Upon reaching the last diagnostic, the word MORE disappears. Pressing the NEXT key at this point causes the display to advance to the first diagnostic in the Diagnostic Event Log. The Diagnostic Event Log screens are displayed after scrolling through the Active list or after pressing the DIAGNOSTICS key when no active diagnostics are present. Its used to view the past 20 diagnostics. Diagnostics in this log are stacked in inverse chronological order, with the first diagnostic screen being the most recently reported diagnostic. When a new diagnostic is displayed, the words NOT VIEWED are displayed with it. After viewing the last not viewed diagnostic, the words NOT VIEWED change to VIEWED for every diagnostic in the log. The diagnostic will remain this way as long as it is in the log. This allows the operator to distinguish between old and new diagnostics in the Event Log. Pressing the NEXT key after reaching the last diagnostic in the Event Log advances the display to the first diagnostic in the Active list if any exist. If not, the display reverts back to the first Event Log diagnostic. If the Diagnostic Event Log is full (20 events), and another diagnostic occurs, the oldest diagnostic is pushed off the end of the list. If all 20 diagnostics in the list are active when the 21st occurs, then the oldest Active diagnostic is pushed off the end of the list. When an Active diagnostic is automatically or manually cleared in the Active buffer, its status in the Diagnostic Log changes from Active to History. If the operator does not clear an active diagnostic in the Active log, its status will still show as active in the Diagnostic Log. When a diagnostic screen is displayed for more than four hours without a key being pressed, the screen will return to the operating status display.

116

RT-SVP04F-EN

System Testing & Troubleshooting

One of the following screens will be the first screen displayed when the DIAGNOSTIC" key is pressed Diagnostic Menu ---- Info No Active Diagnostics (NEXT) History Log OR Press CANCEL to Clear All Active Manual Diagnostics, or Press NEXT to View 1. Pressing the "CANCEL" key to clear the diagnostics will prompt the following screen.

Diagnostic Reset Is Password Protected Please Enter Password: _____________ 1. Press the + (plus) or - (minus) keys to enter the password 2. Press the ENTER key to confirm this choice. When the correct password is entered, the following screen will be displayed. Resetting Active Manual Diagnostics Sending Reset Request and then the following screen will be displayed Resetting Active Manual Diagnostics Updating Unit Data, Please wait and then the following screen will be displayed Active Diagnostic -- Info Please Wait, Unit Is In Reset Mode OR 1. Pressing the "NEXT" key to view the diagnostics will prompt the following screen if a "MANUAL RESET" failure has occurred.

Used With: All Units Factory Presets: N/A Possible Values: + (plus) and (Minus)

RT-SVP04F-EN

117

System Testing & Troubleshooting

Active Diagnostic -- Manual Reset ___________________ More The word MORE will only appear if more than one failure has occurred.

Used With: All units Factory Presets: N/A

Possible Values: Blocked Air Return Compressor Contactor Fail - Ckt 1 Compressor Contactor Fail - Ckt 2 Compressor Trip - Ckt 1 Compressor Trip - Ckt 2 Cond Sump Pump Manual Fail Low Air Temperature Limit Trip Low Pressure Control Open - Ckt 1 Low Pressure Control Open - Ckt 2 Low Refrigerant Charge - Ckt 1 Low Refrigerant Charge - Ckt 2 Cond Sump Heater Failure Emergency Stop Energy Recovery Wheel Proof Failure Exhaust Fan Failure Improper Airflow for Dehumid Cond Sump Heater Failure
OR Pressing the "NEXT" key to view the diagnostics will prompt the following screen if a "AUTO RESET" failure has occurred.

Manual Reset Return Pressure Limit Manual Reset SA Static Pressure Limit Return Fan Failure Supply Fan Failure Cond Sump Heater Failure

Active Diagnostic -- Auto Reset ___________________ More The word MORE will only appear if more than one failure has occurred.

Used With: All units Factory Presets: N/A

118

RT-SVP04F-EN

System Testing & Troubleshooting

Possible Values

Auto Reset SA Static Pres Limit CO2 Sensor Failure

RA Humidity Sensor Failure,

Velocity Pressure Sensor Failure

Return Air Temp Sensor Failure, VOM Communications Failure, Entering Evap Temp Sensor Fail - Ckt 2

Cond Temp Sensor Failure - Ckt 1, RTM AUX Temp Sensor Failure, Entering Evap Temp Sensor Fail - Ckt 1 Cond Temp Sensor Failure - Ckt 2, RTM Zone Temp Sensor Failure, ECEM Communications Failure,

Space Pressure Sensor Failure, GBAS 0-10VDC Module Comm Failure

Evap Temp Sensor Failure - Ckt 1, Space Static Pres Setpt Failure, Min OA Flow SETPOINT Fail Evap Temp Sensor Failure - Ckt 2, Supply Air Pres Sensor Failure, Min Position SETPOINT Fail GBAS 0-5VDC Module Comm Failure, Heat AUX Temp Sensor Fail, Heat Module Comm Failure, MCM Communications Failure, Mode Input Failure, NSB Panel Comm Failure, Supply Air Pres Setpt Failure, Supply Air Temp Cool Setpt Fail, Supply Air Temp Heat Setpt Fail, Supply Air Temp Sensor Failure, BAS Module Comm Failure, BAS/Network Comm Failure MPM Communications Fail Occ Humid SETPOINT Fail Return Plenum Press Sensor Fail RTM Zone Humidity Sensor Fail Velocity Press Sensor (Front) Fail Velocity Press Sensor (Rear) Fail Cond Sump Min Level or Drain Fail2

NSB Panel Zone Temp Sensor Fail Unit HI Communications Failure, OA Humidity Sensor Failure, OA Temp Sensor Failure, Occ Dehumidification Setpoint Failure Leaving Recovery Exhaust Temp Failure2 Cond Pressure Sensor Fail Ckt #1

Unocc Zone Cool Setpt Failure, Cond Sump Max Level Failure2 Cond Sump Temp Sensor Fail2 Cond Sump Temp Sensor Failure2 Cond Sump Min Level or Drain Fail2

Unocc Dehumidification Setpoint Cond Pressure Sensor Fail Ckt Failure #2 SA Reheat Setpoint Failure MDM Communications Failure Unocc Zone Heat Setpt Failure, VCM Aux. Temp Sensor Failure

Occ Zone Heat SETPOINT Failure, VCM Module Comm Failure


2 IntelliPak II only

RT-SVP04F-EN

119

System Testing & Troubleshooting

OR Pressing the "NEXT" key to view the diagnostics will prompt the following screen if a "Information Only" failure has occurred. Active Diagnostic -- Info ___________________ More The word MORE will only appear if more than one failure has occurred. Used With: All units Factory Presets: N/A Possible Values: Heat Fail, Dirty Filter, Ventilation Override Mode A, B, C, D, or E, Rooftop Module Data Storage Error, Dirty Final Filter, Dirty Recovery Filter, High Superheat Ckt 1, High Superheat - Ckt 2

Note: Activation of any VOM Mode can be viewed within the "Active Diagnostic" screen.
and the following screen will be displayed Log 1 ________________________ ____________ Used With: All units Factory Presets: N/A Possible Values: Log Number 120, Viewed or Not Viewed, Active or History, Manual, Auto, or Info., Any diagnostic listed under the previous screens associated with the type of diagnostic including VOM activated Mode. Used With: All units Factory Presets: N/A Possible Values: + (Plus) and (Minus)

1. Pressing the "CANCEL" key to clear the diagnostics will prompt the following screen.

Diagnostic Log Is Password Protected Please Enter Password: _______________ 1. Press the + (Plus) or - (Minus) keys to enter the password 2. Press the ENTER key to confirm this choice. When the correct password is entered, the following screen will be displayed.

Active Diagnostics __________________ Please Wait, Updating Diagnostic Log If the "DIAGNOSTIC LOG" is empty when the "CANCEL" key is pressed, the following screen will be displayed.

Used With: All units Factory Presets: N/A Possible Values: Manual, Auto, or Info

Active Diagnostics ---- Info "Diagnostic Buffer Is Already Empty!" Press the AUTO or STOP key to return to the top level status screen.

Used With: All units Factory Presets: N/A Possible Values: Manual, Auto, or Info

120

RT-SVP04F-EN

System Testing & Troubleshooting

Failure Modes
When any condition results in the rooftop units inability to perform a normal function, it is said to have entered a failure mode. There are two types of failure modes. 1. An Analog input out of range failure mode. This failure mode occurs when a sensing device such as a zone temperature sensor or a humidity sensor begins to transmit information that is outside its allowable range. 2. A Fault recognition by input logic failure mode. This failure mode occurs when the UCM receives information that does not make sense or does not conform to its predefined logic.

Communication Link Problems


If one of these messages appear on the Human Interface screen, that Human Interface is not communicating with the unit.

LOCAL HI COMMUNICATIONS LOSS CHECK COMM LINK WIRING BETWEEN MODULES

OR

Used With: All Units with Local HI Problem: The Unit Mounted (Local) Human interface has lost communications with the RTM. See "Fail Diagnostic" for additional information. Check: Wiring between Unit Mounted (Local) Human Interface and RTM. Verify crimping and polarity of communications wiring. There should be no loose connections or crimps on wire insulation.

RT-SVP04F-EN

121

System Testing & Troubleshooting

REMOTE HI COMMUNICATIONS LOSS CHECK COMM LINK WIRING TO UNIT NUMBER 3

Used With: All Units with Remote Human Interface Possible Values: Unit Number 1 through 4 Problem: The Remote Human Interface has lost communications with the unit whose number is specified (#3 in this example). Check: Field/unit wiring between Remote Human Interface and the IPCB on the unit number specified. Also, verify wiring between the IPCB and RTM of the unit whose number is specified. Verify crimping and polarity of communications wiring. There should be no loose connections or crimps on wire insulation.

If one of these messages appear on the Human Interface screen, the link is noisy or there is another Human Interface of the same type on the link. IMPROPER HUMAN INTERFACE CONFIGURATION MORE THAN ONE LOCAL HI ON LINK Used With: All Units with Local HI Problem: Noisy Communications link or a second Local HI has been installed on the link. Check: Wiring between Unit Mounted (Local) Human Interface and RTM. Verify crimping of communications wiring. There should be no loose connections or crimps on wire insulation. If a Remote HI was installed, verify that a Local HI was not installed by mistake. Used With: All Units with Remote Human Interface Problem: Noisy Communications link or a second Remote HI has been installed on the link. Check: Field/Unit wiring between Remote Human Interface and the IPCB and RTM. Verify crimping of communications wiring. There should be no loose connections or crimps on wire insulation. Verify that no other Remote HI's have been connected to the same communications link/unit.

OR

IMPROPER HUMAN INTERFACE CONFIGURATION MORE THAN ONE REMOTE HI ON LINK

122

RT-SVP04F-EN

System Testing & Troubleshooting

MODULE SOFTWARE VERSION MISMATCH PRESS CONFIG TO REVIEW, SEE LITERATURE

Used With: All Units with Local HI Problem: One or more control modules are installed that have a version of software that does not match the required versions for the installed features. Check: Use the HI Configuration Menu to check the software versions of the required modules. The ones that do not match will have the word "INVALID" in the upper right corner of the screen. Replace the software in those modules with the latest version.

RT-SVP04F-EN

123

System Testing & Troubleshooting

Diagnostics
There are four types of diagnostics: 1. (PMR) Partial System Disable, Manual Reset

2. (PAR) Partial System Disable, Auto Reset 3. (INFO) Information Only 4. (HO) History Only The following Troubleshooting chart list possible Failure Modes and: 1. The Diagnostic Displayed on the Human Interfaces LCD screen and if it is a PMR, PAR, INFO or HO diagnostic.

2. The condition which caused the failure mode to occur or the Reason for Diagnostic. 3. The UCMs Reaction to the failure mode. 4. The Reset Required to remove the diagnostic.

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION A "Return Pressure Shutdown" signal is sent to the following functions: Compressor Staging Control; Economizer Actuator Control; Heat Operation; Supply Fan Control and Proof of Operation; IGV Actuator Control; Return Fan and Proof Operation. The Return Pressure High Limit trip counter is incremental. A "Supply Air Pressure Shutdown" signal is sent to the following functions; a. Compressor Staging Control, b. Economizer Actuator Control, c. Heat Operation, d. Supply Fan Control, e. Return Fan Control, f. IGV / VFD Control, g. Exhaust Fan Control, h. Exhaust Actuator Control

RESET REQUIRED (PAR) An automatic reset occurs when the Return Plenum Pressure drops below the Return Plenum Pressure High Limit, the VFD closes completely, and 15 seconds have elapsed since the shutdown command was issued.

Auto Reset Return Pressure Auto Reset Return Pressure Limit Trip. Limit Trip. Problem: Return Plenum Pressure exceeds the return Plenum Pressure High Limit (single Trip). Problem: Return Plenum Pressure exceeds the return Plenum Pressure High Limit (3.5 iwc non-adjustable) continuously for 1 second

The SA static pressure exceeded the SA static pressure limit SETPOINT for at Problem: The Supply Air Static least one second continuously. Pressure went too high. Auto Reset SA Static Pressure Limit

(PAR) An automatic reset occurs after the Inlet Vanes have closed. The Supply Fan will not be allowed to restart for 15 seconds after the diagnostic has occurred.

BACnet Communications Interface (BCI) Module

None

None

None

124

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED BAS Module Communications Failure Problem: The RTM has lost communications with the LCI or BCI. Check: Check field/ unit wiring between RTM and LCI or BCI Module. BAS/Network Comm Failure Problem: The LCI or BCI has lost communications with Tracer. Check: Network (Tracer or 3rd party building control panel) is powered up and running properly. If so, check unit wiring between LCI or BCI and network (Tracer or 3rd party building control panel). Blocked Air Return Failure

REASON FOR DIAGNOSTIC The RTM has lost communications with the LCI or BCI Module.

UCMS REACTION All active commands and SETPOINTs provided by the network through the LCI or BCI will be cancelled and/ or ignored. Where the network has been designated as SETPOINT source, local HI default SETPOINTs will be used.

RESET REQUIRED (PAR) An automatic reset occurs after communication has been restored.

The LCI or BCI has lost communications with the Network for > 15 minutes.

All active commands and SETPOINTs provided by the network through the LCI or BCI will be cancelled and/ or ignored. Where the network has been designated as SETPOINT source, local HI default SETPOINTs will be used.

(PAR) An automatic reset occurs after communication between the network and LCI or BCI has been restored.

The low pressure limit on the A "Supply Air Pressure VCM module is detected closed Shutdown" signal is sent to the following functions; Problem: There is no return air for 1 second. a. Compressor Staging flow indication. Control, Check: Mixed air section damper linkages and actuators for proper travel and operation and return duct for impediments to airflow. Check wiring between mixed air pressure sensor and VCM module. Check wiring between all damper actuators and control box. Compressor Contactor Fail The circuit #1 compressor proving input is detected Circuit 1 closed continuously for more Compressor Contactor Fail than 3 seconds while neither Circuit 1 compressor output on circuit Problem: The Compressor Contactor for Circuit. #1 has #1 is closed. malfunctioned. Comp Contactor Fail Circuit 2 Problem: The Compressor Contactor for Circuit. #2 has malfunctioned. The circuit #2 compressor proving input is detected closed continuously for more than 3 seconds while neither compressor output on circuit #2 is closed. A "Lockout circuit #2 request is issued to the Compressor Staging Control function. b. Economizer Actuator Control, c. Heat Operation, d. Supply Fan Control e. IGV Actuator Control f. Return Fan Control g. Exhaust Fan Control h. Exhaust Actuator Control

(PMR) A manual reset is required after the diagnostic is set. It can be reset by the HI or Tracer, or by cycling power to the RTM.

A "Lockout Circuit #1 request (PMR) A manual reset is required after the diagnostic is is issued to the Compressor set. It can be reset by the HI Staging Control function. or Tracer, or by cycling power to the RTM.

PMR) A manual reset is required after the diagnostic is set. It can be reset by the HI or Tracer, or by cycling power to the RTM.

RT-SVP04F-EN

125

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (PMR) A manual reset is required after this diagnostic occurs. The Diagnostic can be reset by the unit mounted Human Interface Module or Tracer, or by cycling power to the RTM. (PMR) A manual reset is required after this diagnostic occurs. The Diagnostic can be reset by the unit mounted Human Interface Module or Tracer, or by cycling power to the RTM. (PAR) An automatic reset occurs after the #1 Condenser Temp input returns to its allowable range within 10 seconds.

A Lockout circuit #1 request Compressor Trip - Circuit 1 The circuit #1 compressor proving input is detected open is issued to the Compressor Problem: The Compressor continuously for more than 3 Staging Control function. Circuit #1 has tripped. seconds when either or both compressor outputs on circuit #1 are energized (as described in the Compressor Protection function). A Lockout circuit #2 request Compressor Trip - Circuit 2 The circuit #2 compressor proving input is detected open is issued to the Compressor Problem: The Compressor continuously for more than 3 Staging Control function. Circuit #2 has tripped. seconds when either or both compressor outputs on circuit #2 are energized (as described in the Compressor Protection function). Cond Temp Sensor Failure - The unit is reading a signal that is out of range for the Circuit 1 circuit #1 Saturated Condenser Temperature Problem: The Saturated Condenser Temperature Input sensor. (Temp < -55 F or Temp > 209 F). is out of range for Circuit #1. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and MCM/SCM. A Lockout Circuit #2 request Cond Temp Sensor Failure - The unit is reading a signal is issued to the Compressor that is out of range for the Circuit 2 Staging Control function. Problem: The Saturated Cond. circuit #2 Saturated Temp Input is out of range for Condenser Temperature sensor. (Temp < -55 F or Temp Circuit #2. > 209 F). Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and MCM. Condenser Pessure Sensor Input voltage is out of range: Compressor and condenser operation for Circuit-1 is Input < 0.625 V or Input > Failure Ckt #1 locked out until sensor value 4.80 V. returns in range. Problem:The Circuit-1 Condenser Pressure input voltage is out of range. Check wiring between Circuit1 Condenser Pressure sensor and MPM. If correct verify correct voltage on sensor input on MPM. A Lockout Circuit # 1 request is issued to the Compressor Staging Control function.

(PAR) An automatic reset occurs after the #2 Condenser Temp input returns to its allowable range within 10 seconds.

(PAR) An automatic reset occurs after the Circuit-1 Condenser Pressure input returns to within range for 10 continuous seconds.

126

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (PAR) An automatic reset occurs after the Circuit-2 Condenser Pressure input returns to within range for 10 continuous seconds.

Condenser Pessure Sensor Input voltage is out of range: Compressor and condenser operation for Circuit -2 is Input < 0.625 V or Input > Failure Ckt #2 locked out until sensor value 4.80 V. returns in range. Problem:The Circuit-2 Condenser Pressure input voltage is out of range. Check wiring between Circuit2 Condenser Pressure sensor and MPM. If correct verify correct voltage on sensor input on MPM. Cond Sump Min Level or Drain Fail Problem: The Cond Water Sump Fill Relay is energized, the 30-minute fill timer expires and the Cond Water Sump Min Level Input is not closed. Anytime there is an acitve Cond Sump Drain request and the Cond Sump Min Level Input is closed a 5 minute timer is started. This timer is continually reset whenever the Cond Sump Min Level Input is open. Check: wiring from the MCM to the Sump Fill valve, water flow to the sump, sump min level switch and associated wiring. A compressor lockout is Sump Pump contactor auxiliary contacts do not close generated on all circuits. (state change), within 6 seconds, when the pump is Problem: Sump pump possibly requested ON for mechanical not operative. cooling, or are open for 6 continuous seconds during Check: wiring to sump pump, compressor operation. contactor, and auxillary contacts. Condenser Sump Pump Manual Fail The condenser sump pump water level reaching the Cond Sump Max Level switch is Problem: The condenser sump considered an undesirable condition indicating a problem water is reaching an with the mechanical float valve undesirable level and is reaching the maximum level or some other water control mechanism. sensor. Cond Sump Max Level Failure Generate a Cond Sump Max Level Failure auto reset diagnostic. De-energize the Cond Sump Fill Relay. The Cond Water Sump Fill Relay is energized, the 30minute fill timer expires and the Cond Water Sump Min Level Input is not closed. When the Cond Water Sump Fill Relay is energized, a 30minute timer is started. This timer is continually reset whenever the Cond Water Sump Min Level input is closed. All compressor circuits are locked out due to inability to determine if the sump has sufficient water level. De-energize the Heat relay.

(PAR) An automatic reset occurs after the Cond Water Sump Min Level Input is closed for 10 continuous seconds. Once the Cond Sump Min Level is open for 10 continuous seconds clear diagnostics and compressor lockouts.

(PMR) A manual reset is required anytime after the Diagnostic is set to re-enable compressor operation. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

(PAR) Once the Cond Sump Max Level input is open for 120 continuous seconds the diagnostic will be cleared and the fill relay will be energized.

RT-SVP04F-EN

127

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Condenser Sump Temp Sensor Failure

REASON FOR DIAGNOSTIC

UCMS REACTION A compressor lockout is generated on all circuits and the Condenser Sump is drained completely if the Outdoor Air Temp is below 35F or failed. The Sump will be allowed to fill again if the Outdoor Air Temp rises above 40F.

RESET REQUIRED (PAR) An automatic reset occurs and the sump is allowed to fill after the Condenser Sump Temp input returns to within range for 10 seconds.

The unit is reading a signal that is out of range for this input (Temperature < -40F or Problem: The condenser sump Temperature > 200 F). temperature sensor data is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and VCM.

Condenser Sump Minimum The Minimum level input has A compressor lockout is opened three times without 60 generated on all circuits. level Short Cycle Failure seconds of continous sump Problem: The minimum water pump operation. level is not being maintained.

(PMR) A manual reset is required anytime after the Diagnostic set to re-enable compressor operation. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM. (PAR) An automatic reset occurs after the CO2 Sensor transducer input receives a signal that is within range for 10 continuous seconds.

The unit is reading a signal The CO2 Reset Function is that is out of range for the CO2 disabled. Problem: The VCM CO2 sensor Sensor transducer input. input signal is out of range. Check: Check field/unit wiring between Sensor and VCM. Dirty Filter Problem: There is a Dirty Filter. Dirty Recovery Filter Problem: Recovery Filter proving switch is closed. Check: Status of Recovery Filters Economizer DryBulb SETPOINT Failure Problem: The input for Drybulb SETPOINT is out of range. Check: Wiring to the GBAS input designated for Minimum Outdoor Air Flow SETPOINT or check BAS/Network interface card status and wiring. Economizer DryBulb SETPOINT is out of range: Temperature <50 F or Temperature > 140 F The active Economizer DryBulb SETPOINT reverts to the default Economizer DryBulb Enable SETPOINT. The filter switch input on the An Information Only RTM is closed for more than 60 Diagnostic is set. seconds continuously. Recovery Filter proving switch An Information Only diagnostic is set. is closed for more than 60 seconds continuously.

CO2 Sensor Failure

(INFO) An automatic reset occurs after the Dirty Filter input reopens for 60 continuous seconds. (PAR) An automatic reset occurs after the Recovery Filter proving switch input reopens for 60 continuous seconds.

(PAR) An automatic reset occurs after the Economizer DryBulb Enable SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Economizer DryBulb Enable SETPOINT selection source is user-defined.

128

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED ECEM Communications Failure Problem: The RTM has lost communications with the ECEM. Check: Check field/unit wiring between RTM and ECEM Module.

REASON FOR DIAGNOSTIC The RTM has lost communications with the ECEM.

UCMS REACTION

RESET REQUIRED

(PAR) An automatic reset If the unit has the Comparative Enthalpy option, occurs after communication has been restored. the Economizer Enable r.e. Enthalpy function will revert to Level 2 enthalpy comparison. On units with Statitrac; a. Space pressure control is deactivated, b. the Exhaust Fan Control function receives an "Exhaust Fan Fail" command, c. the Exhaust Damper control function receives a "Close Damper" request, and d. The Outside Air Damper is limited to minimum position.

An open circuit has occurred on the Emergency Stop input caused either by a High Duct Problem: The Emergency Stop Temp T-stat trip, or the input is open. opening of field-provided contacts, switch, etc.... Emergency Stop

OFF or Close requests are issued as appropriate to the following functions;

(PMR) A manual reset is required after the Emergency Stop input recloses. The a. Compressor staging/Chilled Diagnostic can be reset by the Human Interface or Tracer or Water Cooling control by cycling power to the RTM. b. Heat operation c. Supply fan control and proof of operation d. Exhaust fan control and proof of operation. e. Exhaust actuator control f. Outside Air Damper Control g. On VAV units, IGV/VFD control h. Return fan control and proof of operation.

Energy Recovery Wheel Proof Failure Problem:Temperature input comparison indicates the energy recovery wheel may not be turning. Check for wheel operation (relay/contactor closure, motor, wheel turning) Entering Evaporator Temperature Sensor Failure (Ckt 1 and Ckt 2) Problem: The Entering Evap Temp Sensor is out of range. Check wiring from MCM to sensor. If wiring is correct check voltage on sensor input.

Comparison of the Leaving Recovery Exhaust Temp and Return Air Temp doesn't indicate adequate differential between entering and leaving exhaust air across the energy recovery wheel.

Energy Wheel output is deenergized and associated dampers closed while in heat mode. In cooling mode the dampers will still open during economizing operation.

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

Entering Evaporator Temperature Sensor Failure Temperature <-55 F or Temperature > 209 F

For units with Low Charge Protection, the Low Charge Protection function (either Ckt1 or Ckt2) is disabled. For units with Low Charge Protection, a "Lockout (Ckt1 or Ckt2)" request is issued to the compressor Staging Control Function.

(PAR) An automatic reset occurs after the Entering Evaporator Temperature Sensor input returns to within range continuously for 10 seconds.

RT-SVP04F-EN

129

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Evaporator Temperature Sensor Failure - Circuit 1 Evaporator Temperature Sensor Failure - Circuit 1 Problem: The Evaporator Temperature Sensor (Circuit #1) is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and MCM/SCM. Evaporator Temperature Sensor Failure - Circuit 2 Problem: The Evaporator Temperature Sensor (Circuit #2) input is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and MCM.

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (PAR) An automatic reset occurs after the #1 Evaporator Temperature input returns to its allowable range for 10 seconds.

The Coil Frost Protection The unit is reading a signal function for refrigeration that is out of range for the circuit #1 only is disabled. circuit #1 Evaporator Temperature sensor input (Temp < -55 F or Temp > 209 F).

The Coil Frost Protection The unit is reading a signal function for refrigeration that is out of range for the circuit #2 only is disabled. circuit #2 Evaporator Temperature sensor. (Temp < -55 F or Temp > 209 F).

(PAR) An automatic reset occurs after the #2 Evaporator Temperature input returns to its allowable range for 10 seconds.

The unit has power exhaust and the Exhaust Proving input Problem: There is no exhaust is detected OPEN for 40 continuous seconds during any airflow indication after the period of time in which the exhaust fan has been Exhaust Fan binary output is requested on. ON. Exhaust Fan Failure Check: Check belts, linkages, etc. on the Exhaust Fan assembly. If these are ok, check field/unit wiring between RTM and Exhaust Fan. If Exhaust Fan will run in service mode, then verify airflow proving switch and wiring.
Notes: If StatiTrac or an ECEM is installed but not communicating, Exhaust Fan Failure will appear as an active diagnostic at all times.

A minimum position request is issued to the Economizer Actuator Control function. And a Fan off request is issued to the Exhaust Fan Control function.

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

Final Filter Proving Failure "Final Filter switch is closed for An Information Only diagnostic is set. more than 60 seconds continuously. Problem: Final Filter switch is closed. Check: Status of Final Filters

(PAR) An automatic reset occurs after the Final Filter switch input reopens for 60 continuous seconds.

130

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED GBAS 0-5VDC Module Communications Failure Problem: The RTM has lost communications with the GBAS Module. Check: Check field/unit wiring between RTM and GBAS.

REASON FOR DIAGNOSTIC The RTM has lost communications with the GBAS Module.

UCMS REACTION The UCM will initiate the following actions; a. If the Demand Limit input was closed prior to the communications loss, then the Demand Limit commands issued to the Heat Operation function (if applicable) and the Compressor Staging/Chilled Water Cooling function will be cancelled. b. If any of the GBAS SETPOINT control parameters are the HI-selected SETPOINT sources, then those SETPOINTS will revert to the default HI SETPOINTs. c. Any active GBAS output control parameters will be ignored. d. A fail safe function in the GBAS module will cause all GBAS outputs to be zeroed and de-energized.

RESET REQUIRED (PAR) An automatic reset occurs after communication has been restored.

(PAR) An automatic reset RTM lost communication with If Demand Limit input was occurs after one complete set GBAS 0-10VDC module for 60 closed previous to the communications loss, then the of the required IPC packets seconds. has been received. Demand Limit commands Problem: RTM lost issued to the Heat Operation communications with GBAS 0function (If applicable) and the 10 VDC module. Compressor Staging function will be canceled. If any of the Check wiring from GBAS 0-10 GBAS 0-10 vdc SETPOINT VDC module to RTM. Control Parameters are the HIselected SETPOINT source, then those SETPOINTs will revert to the default HI SETPOINTs. Any active GBAS 0-10 vdc Output Control Parameters will be ignored. A fail-safe function in the GBAS 0-10vdc module will cause all GBAS 0-10vdc outputs to be zeroed and de-energized. GBAS 0-10 VDC Module Communications Failure Heat Failure The Heat Fail input on the Heat module was closed: An Information Only diagnostic is set. (INFO) An automatic reset occurs after the Heat Fail input remains open for 210 seconds continuously.

Problem: The Heat has Failed. a. for more than 80 seconds, b. for 10 consecutive (Gas or Electric heat unit) Typically, this is because the occurrences (each lasting 5 seconds or more) within a 210 gas heater's ignitor failed to light the gas, or because the second period. electric heat section became too hot.

RT-SVP04F-EN

131

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION The functions that designated the Heat Module Auxiliary Temperature Input as their input are disabled.

RESET REQUIRED (PAR) An automatic reset occurs after the Heat Module Auxiliary Temperature input returns to its allowable range for 10 seconds.

At least one enabled unit HEAT Mod Aux Temp Sensor Fail (formerly: MWU function has the HEAT Module Auxiliary Temperature input Zone Sensor Fail) designated as its sensor, and the unit is reading a signal Problem: The HEAT Mod Aux that is out of range for this Temp Sensor Input is out of input (Temp < -55 F or Temp range. > 209 F). Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and HEAT Module. Heat Module Communication Failure Problem: The RTM has lost communications with the Heat Module. Check: Check field/unit wiring between RTM and Heat Module.

An All Heat Off request is The RTM has lost communications with the Heat sent to the Heat Operation function. Module. If the unit has staged gas or electric heat, all Heat Module outputs will be zeroed and de energized. If the unit has Hydronic Heat or Chilled Water installed, the unit will turn off the Supply fan and close the Outside Air Damper upon the occurrence of a HEAT Module comm failure. A fail-safe function in the Heat Module will cause all water valves to be set to 100% to provide full water flow. Unless used for switching purposes (Air Handlers with Chilled Water and Mod Gas, or Chilled Water and Hydronic Heat) all binary outputs will be de energized. High Superheat (Ckt1 and/or Ckt2) An Information Only diagnostic is set.

(PAR) An automatic reset occurs after communication has been restored.

High Superheat (Ckt1 and/ High Superheat (Ckt1 and/or Ckt2) The cooling circuit has or Ckt2) been active for 10 minutes and the difference in the Problem: Evaporator entering and leaving Temperature Differential is evaporator temperatures is greater then the Evaporator greater than the Evaporator Temperature Differential Temperature Differential SETPOINT minus 5 F. SETPOINT minus 5 F but less than the Evaporator Temperature Differential SETPOINT for a period of ten minutes.

(PAR) An automatic reset occurs after the difference in the entering and leaving evaporator temperature is less than the Evaporator Temperature Differential SETPOINT minus 5 F

132

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Improper Airflow for Dehumidification

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED

The Dehumidification function (PMR) A manual reset is IGV/VFD control output did required not increase above 80% within is disabled the VAV Box Drive Open stroke anytime after the Diagnostic is time + 5 minutes. The supply set to re-enable Problem: The unit air static pressure control Dehumidification control. The transitioned into function remains active Diagnostic can be reset by the Dehumidification mode during Human Interface or Tracer, or occupied mode and the IGV/ through a transition into Dehumidification and the VAV by cycling power to the RTM. VFD output did not reach 80% Box Drive Open signal is set within the designated timeout during Dehumid mode. period after the transition. Dehumidification mode requires unit to be at full Check: Wiring from the VAV airflow for proper Box Drive Open relay to VAV performance. Boxes or check that the VAV Box Drive Open relay on the RTM is energizing during Dehumid mode. If VAV Boxes are driving open in response to the command check that the Supply Air Pressure sensed decreases and the IGV/VFD output signal from the RTM is increasing to compensate. Also check that the supply air pressure sensor is valid and no diagnostic conditions exist related to Supply Air Static Pressure control. Leaving Recovery Exhaust Temp Failure Problem: The Leaving Recovery Exhaust Temp is out of range. Check wiring from MPM to sensor. If wiring is correct check voltgae on sensor input. LonTalk Communications Interface (LCI) Module None Leaving Recovery Exhaust Temperature signal input voltage is out of normal range (< -55 F or > 209 F) Exhaust Air Bypass Damper modulated fully closed if energy recovery for heating is active or if energy recovery is not active. If OA Damper is fully open Exhaust Air Bypass and Outside Air Bypass dampers modulated fully open when Outside Air Temp is 10F or less. None (PAR) An automatic reset occurs after the Leaving Recovery Exhaust Temp input returns to within range continupusly for 10 seconds

None

RT-SVP04F-EN

133

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION The UCM will initiate the following actions;

RESET REQUIRED

Low Air Temperature Limit A Low Air Temperature Limit Trip is detected continuously Trip(formerly: Freezestat for more than one second. Trip) This can occur if the Hydronic Heat Low Air Temperature Problem: The Low Air Limit input closes for > 1 Temperature Limit has Tripped. (Units with Steam or second, or if the Chilled Water Low Air Temperature Limit Trip Hot Water heating, or Air input opens for > 1 second. Handlers with Chilled Water On units with both Hydronic Cooling) Heat and Chilled water, both Low Air Temperature Limit inputs are active, and the unit will respond in the same manner regardless of which input is used.

(PMR) A manual reset is required after the Low Air a. An Open All Water Valves Temperature Limit Trip condition clears. The request is issued to the Diagnostic can be reset at the Heat Module function, unit mounted Human causing any Steam, Hot Interface, by Tracer, or by Water, or Chilled Water cycling power to the RTM. valves on the unit to open. b. An All Heat OFF request is issued to the Heat Control function. c. A Fan Off request is sent to the Supply Fan Control function and the Return Fan Control function. d. A Close Damper request is sent to the Economizer Actuator Control function.

Low Pressure Control Open The Circuit # 1 LPC input is detected open as described in - Circuit 1 the Compressor Protection Problem: The Low Pressure Control (LPC) for Circuit #1 is function. open. Check: State of refrigerant charge for circuit #1. Low Pressure Control Open The Circuit # 2 LPC input is detected open as described in -Circuit 2 the Compressor Protection Problem: The Low Pressure Control (LPC) for Circuit #2 is function. open. Check: State of refrigerant charge for circuit #2. Low refrigerant Charge (Ckt1 and/or Ckt2). The cooling circuit has been active for 10 minutes and the difference in Problem: The difference the entering and leaving between entering and leaving evaporator temperatures is evaporator temperatures is greater than the Evaporator greater then Evaporator Temperature Differential Temperature Differential SETPOINT for 10 continuous SETPOINT for 10 minutes. minutes. Low Refrigerant Charge (Ckt1 and/or Ckt2) Check: Status of refrigerant charge and running pressures on affected circuit.

A Lockout Circuit # 1 request is issued to the Compressor Staging Control function.

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

A Lockout Circuit # 2 request is issued to the Compressor Staging Control function.

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM. (PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM."

A "Lockout (Ckt1 and/or Ckt2)" request is issued to the compressor Staging Control Function.

134

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Manual Reset Supply Air Static Pressure Limit

REASON FOR DIAGNOSTIC

UCMS REACTION A "Supply Air Pressure Shutdown" signal is sent to the following functions; a. Compressor Staging Control, b. Economizer Actuator Control, c. Heat Operation, d. Supply Fan/Return Fan Control, e. IGV / VFD Control, f. Exhaust Fan Control g. Exhaust Actuator Control

RESET REQUIRED (PMR) A manual reset is required and can be accomplished at the Human Interface or by Tracer, or by cycling the power to the RTM.

The Auto Reset Supply Air Static Pressure Limit diagnostic has occurred for the Problem: The Supply Air static 3rd time while the unit is operating in any mode. pressure went too high for the third consecutive time.

The RTM has lost communications with the Problem: The RTM has lost MCM. communications with the MCM. MCM Communications Failure Check: Check field/unit wiring between RTM and MCM. Minimum Outdoor Air Flow Minimum Outdoor Air Flow SETPOINT out of range: OA SETPOINT Failure flow is < 0 or > Max Unit Problem: The input designated Airflow as the SETPOINT is out of range. Check: Wiring to the GBAS input designated for Minimum Outdoor Air Flow SETPOINT or check BAS/Network interface card status and wiring. The mode input signal on the Problem: The RTM Mode input RTM is out of range (R < 1k ohm or R > 40k ohm). is out of range. MODE Input Failure Check: Mode input resistance should be between 1 Kohm and 40 Kohms. If so, check field/unit wiring between Sensor and RTM.

A Lockout request is sent to (PAR) An automatic reset occurs after communication the Compressor Staging has been restored. Control function. And a failsafe function in the MCM will cause all MCM outputs to be zeroed and de energized. The active Minimum OA Flow SETPOINT reverts to the default Minimum OA Flow SETPOINT. (PAR) An automatic reset occurs after the Minimum OA Flow SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Minimum OA Flow SETPOINT selection source is user-defined.

The system mode reverts to the default (HI set) System Mode.

(INFO) An automatic reset occurs after the Mode input returns to its allowable range for 10 seconds.

The RTM lost communications All active commands and to the MDM for 60 seconds. setpoints provided by the MDM module will be canceled and/ or ignored. All binary outputs Problem: RTM lost will be de-energized and communication to the MDM analog output set to fail-safe. module. Dehumidification control function is disabled and a Check wiring between the compressor lockout request is MDM and RTM. Check for issued for the Reheat Circuit properly powered MDM board. (Circuit #1) MDM Communications Failure

(PAR) An automatic reset occurs after one complete set of the required IPC packets has been received.

RT-SVP04F-EN

135

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED MPM Communications Failure

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (PAR) An automatic reset occurs after one complete set of the required IPC packets has been received.

MPM Communications Failure. MPM Communication Failure. The RTM lost communications All active commands and SETPOINTs provided by the to the MPM for 60 seconds. MPM module will be canceled Problem: RTM lost and/or ignored. Return Fan communication to the MPM control function is disabled. module. For evaporative Condensing units, a lockout request is Check wiring between the issued, for all circuits, to the MPM and RTM. Check for compressors Staging Control properly powered MPM board. Function. NSB Panel Zone Temp Sensor Failure Problem: The NSB panel's zone temp sensor input is out of range. (This input is at the NSB Panel, not on the Rooftop unit itself). Check: If have an external sensor connected to the NSB Panel Zone Sensor input, then the internal NSB Panel zone sensor should be disabled. Verify sensor resistance. If in valid range, check wiring between Sensor and NSB Panel.

(PAR) An automatic reset The unit reverts to the next NSB Panel Communication The RTM has lost communications with the NSB lower priority mode switching occurs after communication Failure source (typically the HI default has been restored. panel. mode). If the NSB Panel Zone Problem: The RTM has lost Sensor is the designated communications with the sensor source for any Night SetBack Panel functions, those functions are (programmable zone sensor). disabled. Check: Field/unit wiring between RTM and NSB Panel. OA Humidity Sensor Failure The unit is reading a signal that is out of range for the Outside Air humidity sensor Problem: The Outside Air Humidity sensor data is out of (Humidity < 5% or Humidity > 100%). range. Check: Check field/unit wiring between Sensor and RTM. The Economizer Enable r.e Enthalpy function reverts to Dry-Bulb Temperature changeover (Level 1) control. (PAR) An automatic reset occurs after the OA Humidity input returns to its allowable range for 10 seconds.

136

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED OA Temperature Sensor Failure Problem: The Outside Air Temperature sensor input is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and RTM.

REASON FOR DIAGNOSTIC The unit is reading a signal that is out of range for the Outside Air Temperature sensor input on the RTM. (Temp < -55 F or Temp > 209 F).

UCMS REACTION Unit functions that are disabled include;

RESET REQUIRED

(PAR) An automatic reset occurs after the OA Temp input returns to its allowable a. Low Ambient Compressor range. In order to prevent Lockout rapid cycling of the Diagnostic, b. The Outside Air Damper there is a 10 second delay drivesto minimumposition. c. On VAV units with SA Temp before the automatic reset. Reset type selected as OA Temp Reset, the Reset type reverts to NONE for the duration of the failure.

Occupied Dehumidification Occupied Dehumidification SETPOINT Failure SETPOINT input is out of range: Humidity <40% or Problem: The input designated Humidity >65% as Occupied Dehumidification SETPOINT source is out of range. Check: Wiring to the GBAS input designated for Occupied Dehumidification SETPOINT or check BAS/Network interface card status and wiring. Occupied Humidification SETPOINT Failure Problem: The input designated as Occupied Humidification SETPOINT source is out of range. Check: Wiring to the GBAS input designated for Occupied Humidification SETPOINT or check BAS/Network interface card status and wiring. Occupied Zone Cool SETPOINT Failure Problem: The Occupied Zone Cooling SETPOINT Input out of range. The input designated as Occupied Zone Cooling SETPOINT source is out of range (Temperature < 45 F or Temperature > 94 F). Occupied Humidification SETPOINT input is out of range: Humidity <20% or Humidity >50%

The active Occupied Dehumidification SETPOINT reverts to the default Occupied Dehumidification SETPOINT.

(PAR) An automatic reset occurs after the Occupied Dehumidification SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Occupied Dehumidification SETPOINT selection source is user defined.

The active Occupied Humidification SETPOINT reverts to the default Occupied Humidifications SETPOINT.

(PAR) An automatic reset occurs after the Occupied Humidification SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Occupied Humidification SETPOINT selection source is userdefined.

The active Occupied Zone Cooling SETPOINT reverts to the default Occupied Zone Cooling SETPOINT.

(PAR) An automatic reset occurs after the designated Occupied Zone CSP input returns to its allowable range for 10 continuous seconds, or after a different, valid Occupied Zone CSP selection source is user-defined. (PAR) An automatic reset occurs after the designated Occupied Zone HSP input returns to its allowable range for 10 continuous seconds, or after a different, valid Occupied Zone HSP selection source is user-defined.

Occupied Zone Heat SETPOINT Failure Problem: The Occupied Zone Heating SETPOINT Input is out of range.

The input designated as Occupied Zone Heating SETPOINT source is out of range (Temperature < 45 F or Temperature > 94 F).

The active Occupied Zone Heating SETPOINT reverts to the default Occupied Zone Heating SETPOINT.

RT-SVP04F-EN

137

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION The Economizer Enable r.e. Enthalpy function reverts to Reference Enthalpy changeover (Level 2) control.

RESET REQUIRED (PMR) An automatic reset occurs after the RA Humidity input returns to its allowable range continuously for 10 seconds.

RA Humidity Sensor Failure The unit is reading a signal that is out of range for the Problem: On units with both Return Air humidity sensor Air Economizer and (Humidity < 5% or Humidity > Comparative Enthalpy 100%). Installed: The Return Air Humidity sensor input is out of range. Check: Check field/unit wiring between Sensor and ECEM. The unit is reading a signal that is out of range for the Return Air humidity sensor (Temperature < -55 F or Problem: On units with the Comparative Enthalpy option, Temperature > 209 F). the Return Air Temperature sensor input is out of range. Return Air Temperature Sensor Failure Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and ECEM. Return Fan failure

The Economizer Enable r.e. Enthalpy function reverts to Reference Enthalpy changeover (Level 2) control.

(PAR) An automatic reset occurs after the RA Temperature input returns to its allowable range continuously for 10 seconds.

A fan off request is sent to the Return Fan Proving input is return fan control functions. detected OPEN for 40 continuous seconds during any Problem: There is no return air flow indication after the return period of time in which the Return Fan binary output is fan has been requested on. ON. Check: Check belts, linkages, etc. on the Return Fan assembly. If these are ok, check field/unit wiring between RTM and Return Fan. Also check wiring on MPM. (Note: A communications error
from the MPM can also cause a return fan failure lockout.) If Return Fan will run in service mode, then verify airflow proving.

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

Return Plenum Pressure Sensor Failure Problem: The Return Plenum Pressure input voltage is out of range. Check wiring between Return Plenum Pressure sensor and MPM. If correct verify correct voltage on sensor input on MPM.

Return Plenum Pressure Sensor Failure. Input voltage is out of range: Input < 0.625 V or Input > 4.80 V.

Return Plenum Pressure Sensor Failure. The supply fan and return fan are requested OFF. The outside air damper is requested to close. The exhaust damper is requested to close.

(PAR) An automatic reset occurs after the Return Plenum Pressure input returns to within range for 10 continuous seconds.

138

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Rooftop Module Data Storage Error

REASON FOR DIAGNOSTIC

UCMS REACTION A manuel reset diagnostic will be displayed at the Human Interface and unit operation will be prevented until reset.

RESET REQUIRED (PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

An error occurred while the RTM was writing data to its internal non-volatile memory (EEPROM). The RTM detects Problem: There was a data an Human Interface software transmission error or an older version less than 32.xx version Human Interface (prior to 32.xx) is connected to the control system. (Intellipak II RTM requires compatible Human Interface ver 32.xx or higher) Check: This can be caused by an intermittent power loss. Turn the unit off for 1-2 minutes, then back on again. If diagnostic persists, then the RTM may need to be replaced. RTM and Human Interface software versions. RTM Auxiliary Temperature At least one enabled unit function has the RTM Auxiliary Sensor Failure Temperature input designated as its sensor, and the unit is Problem: The RTM Auxiliary reading a signal that is out of Temperature sensor data is range for this input out of range. (Temperature < -55 F or Temperature > 209 F). Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and RTM. RTM Space Humidity Sensor Failure Problem: Humidity sensor out of range. Check wiring from Humidity Sensor to RTM module. Check for proper voltage range on RTM Humidity Sensor input if wired correctly. RTM Zone Temperature Sensor Failure Problem: The RTM Zone Temperature sensor input is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and RTM. At least one enabled unit function has the RTM Zone Temperature input designated as its sensor, and the unit is reading a signal that is out of range for this input (Temperature < -55 F or Temperature > 150 F). RTM Zone Humidity input out of range: Humidity <1% or Humidity >100%.

The functions with the RTM Aux Temperature input designated as their sensor are disabled.

(PAR) An automatic reset occurs after the designated Zone Temperature input returns to its allowable range. In order to prevent rapid cycling of the Diagnostic, there is a 10 seconds delay before the automatic reset.

The Dehumidification and Humidification functions are disabled if the RTM Space Humidity Sensor is selected as sensor source for these functions.

(PAR) An automatic reset occurs after the RTM Zone Humidity input returns to within range continuously for 10 seconds.

The functions with the RTM Zone Temperature input designated as their sensor are disabled.

(PAR) An automatic reset occurs after the designated Zone Temperature signal returns to its allowable range. In order to prevent rapid cycling of the Diagnostic, there is a 10 second delay before the automatic reset.

RT-SVP04F-EN

139

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED SCM Communications Failure

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED

The RTM has lost A Lockout request is sent to (PAR) An automatic reset occurs after communication communications with the SCM. the Compressor Staging has been restored. Control function. And a failProblem: The RTM has lost safe function in the SCM will communications with the cause all SCM outputs to be SCM. zeroed and de-energized. Check: Check field/unit wiring between RTM and SCM. The unit is reading a signal that is out of range for the Space Pressure transducer Problem: The Space Pressure input (During calibration: V < 40 mV or V > 420 mV, During input signal is out of range. operational times: V < 40 mV or V > 0.75 V). Check: Check field/unit wiring between Sensor and ECEM. Space Pressure Sensor Failure Space Static Pressure SETPOINT Failure Problem: The active Space Static pressure SETPOINT is out of range. Check: Check SETPOINT value. Also, if Space Pressure SETPOINT source is GBAS, but this SETPOINT has not been assigned to any of the 4 analog inputs on GBAS, this message will occur. Supply Air Pressure Sensor The unit is reading a signal that is out of range for the Failure Supply Air Pressure sensor voltage input (Input < 40mV Problem: The Supply Air or Input > 4.75V) Pressure sensor voltage input is out of range. Check: Check field/unit wiring between Sensor and RTM. Supply Air Pressure SETPOINT Failure Problem: The Supply Air pressure input signal is out of range. The Supply Air Pressure SETPOINT input is sending a signal that is out of range (Input < 1.0 IWC or Input > 4.3 IWC) The default Supply Air Pressure SETPOINT will become the active Supply Air Pressure SETPOINT. (PAR) An automatic reset occurs after the designated SA Pressure SETPOINT source sends a signal within range for 10 continuous seconds, or after a different SA Pressure SETPOINT source is userdefined. The IGVs will drive closed, and the following functions are disabled; a. SA Pressure Control b. SA Static Pressure Limit The unit is reading a signal that is out of range for the Space Static Pressure SETPOINT (Input < 0.03 IWC or Input > 0.20 IWC). The Space Pressure Control function is disabled, and the exhaust fan and the exhaust damper actuator are controlled as if the unit did not have Statitrac. Default exhaust enable point is used. (PAR) An automatic reset occurs after the designated Space Pressure transducer sends a signal within range for 10 continuous seconds.

The default Space Pressure SETPOINT will become the active Space Pressure SETPOINT.

(PAR) An automatic reset occurs after the designated Space Pressure SETPOINT source sends a signal within range for 10 continuous seconds, or after a different Space Pressure SETPOINT source is user-defined.

(PAR) An automatic reset occurs after the SA Pressure input returns to its allowable range for 10 seconds.

140

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (PAR) An automatic reset occurs after the Supply Air Reheat SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Supply Air Reheat SETPOINT selection source is user defined.

Supply Air Reheat Setpoint Supply Air Reheast SETPOINT The active Supply Air Reheat is out of range: SETPOINT Failure Temperature < 60 F or Problem: The input designated Temperature > 90 F as Supply Air Reheast SETPOINT source is out of range. Check: Wiring to the GBAS input designated for Supply Air Reheat SETPOINT or check BAS/Network interface card status and wiring. The input designated as the Supply Air Temperature Cooling SETPOINT is out is out of range (Temperature < 35 F Problem: The active Supply Air or Temperature > 95 F). Temperature Cooling Supply Air Temperature Cool SETPOINT Failure SETPOINT is out of range. The default HI-set Supply Air Temperature Cooling SETPOINT becomes the active Supply Air Temperature Cooling SETPOINT. reverts to the default Supply Air Reheat SETPOINT.

(PAR) An automatic reset occurs after the SA Temp Cooling SETPOINT input returns to within range for 10 continuous seconds, or after a different SA temp cooling SETPOINT selection source is user-defined. (PAR) An automatic reset occurs after the SA Temp Heating SETPOINT input returns to within range for 10 continuous seconds, or after a different SA temp heating SETPOINT selection source is user-defined. (PAR) An automatic reset occurs after the designated Supply Air Temperature input returns to its allowable range. In order to prevent rapid cycling of the Diagnostic, there is a 10 second delay before the automatic reset.

The input designated as the Supply Air Temperature Heating SETPOINT is out is out of range (Temperature < 35 F Problem: The active Supply Air or Temperature > 185 F). Temperature Cooling SETPOINT is out of range. Supply Air Temperature Heat SETPOINT Failure

The default HI-set Supply Air Temperature Heating SETPOINT becomes the active Supply Air Temperature Heating SETPOINT.

These unit functions are The unit is reading a signal disabled; that is out of range for the Supply Air Temperature input a. Supply Air Tempering on the RTM (Temperature < - b. Economizing Problem: The Supply Air 55 F or Temperature > 209 F). c. On CV units, the Supply Air Temperature sensor input is Temperature low limit function out of range. is disabled. d. On VAV units, the Supply Check: Sensor resistance Air Temperature Control should be between 830 ohms heating and cooling functions (200 F) and 345.7Kohms (-40 are disabled. F). Check field/unit wiring between Sensor and RTM. Supply Air Temperature Sensor Failure The supply airflow input is detected OPEN for 40 continuous seconds during any Problem: There is no supply period of time in which the airflow indication after the supply fan binary output is supply fan has been requested ON. This input is ignored for on. up to 5 minutes after the supply fan is first started, until Check: Check belts, linkages, airflow is first detected. etc. on the Supply Fan assembly. If these are ok, check field/unit wiring between RTM and Supply Fan. Supply Fan Failure If Supply Fan will run in service mode, then verify airflow proving switch and wiring. OFF or Close requests are issued as appropriate to the following functions; a. Compressor staging /Chilled Water control b. Heat operation c. Supply fan control and proof of operation. d. Return fan control and proof of operation. e. Exhaust fan control and proof of operation f. Exhaust actuator control g. Economizer actuator control h. IGV / VFD control

(PMR) A manual reset is required anytime after the Diagnostic is set. The Diagnostic can be reset by the Human Interface or Tracer, or by cycling power to the RTM.

RT-SVP04F-EN

141

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Unoccupied Dehumidification SETPOINT Failure

REASON FOR DIAGNOSTIC Unoccupied Dehumidification SETPOINT input is out of range: Humidity <40% or

UCMS REACTION The active Unoccupied Dehumidification SETPOINT reverts to the default Unoccupied Dehumidification SETPOINT.

RESET REQUIRED (PAR) An automatic reset occurs after the Unoccupied Dehumidification SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Unoccupied Dehumidification SETPOINT selection source is user defined.

Problem: The input designated Humidity >65% as Unoccupied Dehumidification SETPOINT source is out of range. Check: Wiring to the GBAS input designated for Unoccupied Dehumidification SETPOINT or check BAS/Network interface card status and wiring.

Unoccupied Humidification Unoccupied Humidification SETPOINT input is out of SETPOINT Failure range: Humidity <20% or Humidity >50% Problem: the input designated as Unoccupied Humidification SETPOINT source is out of range. Check: Wiring to the GBAS input designated for Unoccupied Humidification SETPOINT or check BAS/ Network interface card status and wiring. Unoccupied Zone Cool SETPOINT Failure Problem: The Unoccupied Zone Cooling SETPOINT Input out of range. The input designated as Unoccupied Zone Cooling SETPOINT source is out of range (Temperature < 45 F or Temperature > 94 F).

The active Unoccupied Humidification SETPOINT reverts to the default Unoccupied Humidifications SETPOINT.

(PAR) An automatic reset occurs after the Unoccupied Humidification SETPOINT input returns to within range for 10 continuous seconds, or after a different, valid Unoccupied Humidification SETPOINT selection source is userdefined.

The active Unoccupied Zone Cooling SETPOINT reverts to the default Unoccupied Zone Cooling SETPOINT.

(PAR) An automatic reset occurs after the designated Unoccupied Zone CSP input returns to its allowable range for 10 continuous seconds, or after a different, valid unoccupied Zone CSP selection source is user-defined. (PAR) An automatic reset occurs after the designated Unoccupied Zone HSP input returns to its allowable range for 10 continuous seconds, or after a different, valid unoccupied Zone HSP selection source is userdefined.

Unoccupied Zone Heat SETPOINT Failure Problem: The Unoccupied Zone Heating SETPOINT Input is out of range.

The input designated as Unoccupied Zone Heating SETPOINT source is out of range (Temperature < 45 F or Temperature > 94 F).

The active Unoccupied Zone Heating SETPOINT reverts to the default Unoccupied Zone Heating SETPOINT.

142

RT-SVP04F-EN

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Unit HI Communications Failure Problem: The RTM has lost communications with the Unit mounted (local) Human Interface (HI). Check: Field/unit wiring between RTM and Local HI.

REASON FOR DIAGNOSTIC

UCMS REACTION

RESET REQUIRED (INFO) An automatic reset occurs after communication has been restored between the RTM and the HI. When the failure screen is cleared, the General display is restored and HI interaction with the interaction with the RTM is again permitted.

A fail-safe function in the HI The RTM has lost communications with the unit- will; mounted Human Interface. a. disallow any interaction between the HI and the RTM (or any other modules), b. render all HI keystrokes ineffective, and c. cause the following to be displayed on the unitmounted HI display: LOCAL HI COMMUNICATIONS LOSS CHECK COMM LINK WIRING BETWEEN MODULES (If the unit has a remote HI option, then on the remote HI module, this diagnostic will be reported and displayed as any other automatic reset diagnostic.

VCM Aux Temp. Sensor Failure. Problem: The VCM Auxiliary Temperature sensor data is out of range. Check: Sensor resistance should be between 830 ohms (200 F) and 345.7Kohms (-40 F). If so, check field/unit wiring between Sensor and VCM. VCM Communications Failure. Problem: There has been a loss of communications between the VCM and the RTM. Check wiring between VCM and RTM.

At least one enabled unit function has the VCM Auxiliary Temperature input designated as its sensor, and the unit is reading a signal that is out of range for this input (Temperature < -40F or Temperature > 200 F).

The functions with the VCM Aux Temperature input designated as their sensor are disabled.

PAR) An automatic reset occurs after the designated Zone Temperature input returns to its allowable range. In order to prevent rapid cycling of the Diagnostic, there is a 10 seconds delay before the automatic reset.

There has been a loss of communications between the VCM and the RTM.

Fresh Air Management with DCV or OA Damper Min. Position with DCV will be disabled.

PAR) An automatic reset occurs after communication has been restored.

The unit is reading a signal that is out of range for the Velocity Pressure transducer input (During calibration: V < Problem: The Velocity 40 mV or V > 420 mV, During Pressure input signal is out of operational times: V < 40 mV range. or V > 0.75 V). Velocity Pressure Sensor Failure Check: Check field/unit wiring between Sensor and VCM.

The Minimum Airflow Control Function is disabled. The Outside Air Damper Minimum Position function will revert to using the OA Flow compensation function if OA Flow Compensation is ENABLED or to the default minimum position function if OA Flow Compensation is DISABLED or not available.

(PAR) An automatic reset occurs after the designated Space Pressure transducer sends a signal within range for 10 continuous seconds.

RT-SVP04F-EN

143

System Testing & Troubleshooting

DIAGNOSTIC DISPLAYED Velocity Pressure Sensor Failure (Front or Back) Problem: The Velocity pressure voltage input is out of range. Check wiring from VCM and sensor. VOM Communications Failure Problem: The RTM has lost communications with the VOM. Verify: Check field/unit wiring between RTM and VOM.

REASON FOR DIAGNOSTIC The Velocity pressure voltage input is out of range. During the calibration cycle if the voltage is less than 40mV or greater than 420 mV. During Operational time if the Voltage is less than 40mV or greater than 0.75V. Time to react is greater than 10 seconds but less than 20 seconds. The RTM has lost communications with the VOM.

UCMS REACTION Minimum air flow and Demand Control Ventilation functions revert to OA Damper Min Position DCV functionality. Economizer Min. Pos. reverts to the position provided by the OA Damper Min Position DCV function.

RESET REQUIRED (PAR) An automatic reset occurs after the Velocity Pressure input returns to within range continuously for 10 seconds.

(PAR) An automatic reset Ventilation override actions will not be allowed, and the VO occurs after communication has been restored. Output relay will be de energized.

UNIT MODULE Multiple Circuit Compressor Module (MCM)

ANALOG INPUTS Leaving Evap Temperature Sensor (Ckt #1) Leaving Evap Temperature Sensor (Ckt #2) Entering Evap Temperature Sensor (Ckt #1) Entering Evap Temperature Sensor (Ckt #2) Saturated Condenser Temperature Sensor (Ckt #1) Saturated Condenser Temperature Sensor (Ckt #2) Sump Water Temp (Ckt #1)

ANALOG OUTPUTS

BINARY INPUTS

BINARY OUTPUTS Compressor Relay (K11) Compressor Relay (K12) Compressor Relay (K3) Compressor Relay (K4) Condenser Fan 1A Condenser Fan 1B Condenser Fan 2A Condenser Fan 2B Condenser Water Valve Ckt #1 Condenser Water Valve Ckt #2 Sump Pump ON/OFF Sump Heat ON/OFF Sump Fill Sump Drain

Condenser Fan Speed Low Pressure Control (Low Ambient Ckt #1) (Ckt #1) Condenser Fan Speed Low Pressure Control (Ckt #2) (Low Ambient Ckt #2) Compressor Proving (Ckt #1) Compressor Proving (Ckt #2) Water Level Min Water Level Max Sump Pump Proving External Sump Drain Request

144

RT-SVP04F-EN

System Testing & Troubleshooting

UNIT MODULE Rooftop Module

ANALOG INPUTS Zone Temperature Sensor S/A Temperature Sensor O/A Temperature Sensor Mode Input Channel (from the remote panel) Cooling SETPOINT (from the remote panel) Heating SETPOINT (from the remote panel) Supply Air Pressure Transducer Outdoor Air Humidity Sensor Auxiliary Temperature Sensor Economizer Minimum Position Space Humidity Sensor Address

ANALOG OUTPUTS Outside Air Damper Output IGV/VFD Outputs

BINARY INPUTS Emergency Stop Dehumidification Configuration Input External Auto/Stop

BINARY OUTPUTS Occupied/Unoccupied Relay Alarm Relay

Supply Fan Relay Occupied/Unoccupied LED 1-4 Transistor Supply Airflow Proof Exhaust/return Fan Dirty Filter Relay VAV Changeover IntelliPak II configuration Input Dirty Final Filter Exhaust/Return Airflow Humidification Relay

Ventilation Override Module

Address

None

VOM Mode A Contacts VOM Relay VOM Mode B Contacts VOM Mode C Contacts VOM Mode D Contacts VOM Mode E Contacts

Exhaust/Comparative Return Air Temperature Sensor Enthalpy Module (ECEM) Return Air Humidity Sensor Space Pressure Address Generic BAS Module 5V

Exhaust Fan SpeedDamper

None

Space Pressure Calibration Solenoid

None There are 4 analog inputs. Each input can be configured as one of the following definitions: the inputs 1, 2, 3, & 4 may be assigned to: Occupied Zone Cooling SETPOINT, Occupied Zone, Heating SETPOINT, Unoccupied Zone, Cooling SETPOINT, Unoccupied Zone, Heating SETPOINT, Space Static, Pressure SETPOINT, or Minimum OA Flow SETPOINT. No 2 inputs can be assigned to the same definition. Address

GBAS Demand Limit Input

GBAS Binary Output 5 GBAS Binary Output 4 GBAS Binary Output 3 GBAS Binary Output 2 GBAS Binary Output 1

RT-SVP04F-EN

145

System Testing & Troubleshooting

UNIT MODULE Generic BAS Module 10V

ANALOG INPUTS There are 4 analog inputs. Each input can be configured as one of the following definitions: the inputs 1, 2, 3, & 4 may be assigned to: Occupied Zone Cooling SETPOINT, Occupied Zone, Heating SETPOINT, Unoccupied Zone, Cooling SETPOINT, Unoccupied Zone, Heating SETPOINT, Space Static, Pressure SETPOINT, or Minimum OA Flow SETPOINT. No 2 inputs can be assigned to the same definition. Address

ANALOG OUTPUTS

BINARY INPUTS

BINARY OUTPUTS Active Diagnostic Output

GBAS Demand Limit There are 4 analog Input outputs--each output can be configured as defined in GBAS Analog output assignments.

Heat Module

Morning Warmup Temperature Sensor Address None

Modulating Heat Actuator (Hydronic) None None

HW Freeze Status Heat Fail CW Freeze Status None None

Heat 1 (K1) Relay Heat 2 (K2) Relay Heat 3 (K3) Relay None None

Human Interface Module

None Interprocessor Communications Bridge (IPCB) Module Multi-Purpose Module Return Air Plenum Pressure Liquid Line Pressure Ckt 1 Liquid Line Pressure Ckt 2 Address VCM

Outdoor Air Bypass Damper Exhaust Air Bypass Damper/Return Fan Speed Energy Recovery Preheat

Dirty Recovery Filter

Energy Recovery Wheel Return Air Plenum Pressure Calibration Energy Recovery Preheat Preheater Relay Pressure Calibration

Front Velocity Pressure Outside Air CFM (PCB None Transducer Only) Back Velocity Pressure Transducer Auxiliary Temperature Space CO2 Sensor Address

MDM

Reheat Valve Output (Phase A & B) Cooling Valve Output (Phase A & B)

Reheat Pumpout Relay

146

RT-SVP04F-EN

A
Active Setpoint 4, 5 AUTO Key See Figure 2 13

B
BACnet 3, 4, 5, 9 BCI 3, 9, 17

C
CANCEL Key See Figure 2 13 central processor of the system See Rooftop Module 8 Comm3/4 5 Comm5 5 Commonly 3 Compressor lead/lag 20 Compressor Module See SCM and MCM Communication Failure 8 Compressor Protection Switch See Low Pressure Control 5 CONFIGURATION 12 CONFIGURATION Key 12 CONFIGURATION Menu 101 Configuration password 23 Control Band 5 Control Parameters 19 Control Point 5 CUSTOM Key See figure 2 14

D
Data Manipulation Keys 12 Deadband 5 designate 89 Diagnostics 124 DIAGNOSTICS Key See Figure 2 12

E
Economizer Zone Temp Setpoint Suppression 5 Emergency Override Definitions (with LCI-I module installed) 67 Emergency Override modes 17 ENTER Key See Figure 2 13 Exhaust/Comparative Enthalpy Module (1U52) 8 External Stop 6

F
Figure 1 11 Figure 2 15

G
GBAS Input/Output Assignments 20

RT-SVP04F-EN

147

Index
Generic BAS Module (1U51) 9

H
Heat Module (1U50) 8 Human Interface Keypad See Figure 2 15 Human Interface Module See Figure 1 11

I
Interprocessor Communications Bridge Module 9

L
LCI, LCI-I 9 LonTalk 67, 133 Low Ambient Compressor Lockout 6

M
Menu Keys See Figure 2 11

N
NEXT Key See Figure 2 13 Night SetBack (NSB) 6 No Configuration 18

P
PREVIOUS Key 13

R
Reference Enthalpy 6 Remote Human Interface See Interprocessor Communication Module 6 Reset Amount Maximum 6 Reset End Temperature 6 Reset Start Temperature 6 Rooftop Module 8

S
SERVICE MODE Key See Figure 2 12 Setpoint Source Selection 20 SETPOINTS Key See Figure 2 12 SETUP Key See figure 2 12 Space Pressure 7 special ventilation requirements See Ventilation Override Module 9 stage heat up and down See Heat Module 8 Statitrac 7 STATUS Key See Figure 2 11 STOP Key

148

RT-SVP04F-EN

See Figure 2 14 Supply Air Pressure 7 Supply Air Temperature Control Point 7 Supply Air Temperature Reset 7 Supply Air Tempering 7

T
TEST START Key (SERVICE) See Figure 2 14

U
UCM Control System 7 Unit Operation Keys See Figure 2 13 Unit Status (Unit Off or Stopped) 10 Unit Status (Unit On) 10

V
Ventilation Override Mode A - (Unit Off) 66 Ventilation Override Mode B - (Pressurize) 66 Ventilation Override Mode C - (Exhaust) 67 Ventilation Override Mode D- (Purge) 67 Ventilation Override Mode E- (Purge with Duct Pressure Control) 67 Ventilation Override Module (1U53) 9 VOM Active 10, 18

RT-SVP04F-EN

149

Literature Order Number Date Supersedes www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com

RT-SVP04F-EN April 2010 RT-SVP04F-EN (December 2009)

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

Вам также может понравиться