Data sheet

Manual motor starter MS132

Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse less against short-circuit, overload and phase failures. Fuse less protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Fuse less starter combinations are setup together with contactors.

Description - Overload protection trip class 10 - Phase loss sensitivity - Disconnect function - Temperature compensation from -25 +60 C - Adjustable current setting for overload protection - Suitable for three- and single-phase application - Trip-free mechanism - Trip indication - Clear switch position indication ON/OFF/TRIP - Lockable handle

Ordering details MS132 screw terminal


Setting range Type Trip 10A 10 10 10 10 10 10 10 10 10 10 10 10 10 10 Order code 1SAM350000R1001 1SAM350000R1002 1SAM350000R1003 1SAM350000R1004 1SAM350000R1005 1SAM350000R1006 1SAM350000R1007 1SAM350000R1008 1SAM350000R1009 1SAM350000R1010 1SAM350000R1012 1SAM350000R1011 1SAM350000R1013 1SAM350000R1014 1SAM350000R1015 Packing unit [Pcs] 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Weight [g] 215 215 215 215 215 265 265 265 265 265 310 310 310 310 310

[A] 0.10 ... 0.16 MS132-0.16 0.16 ... 0.25 MS132-0.25 0.25 ... 0.40 MS132-0.4 0.40 ... 0.63 MS132-0.63 0.63 ... 1.00 MS132-1.0 1.00 ... 1.60 MS132-1.6 1.60 ... 2.50 MS132-2.5 2.50 ... 4.00 MS132-4.0 4.00 ... 6.30 MS132-6.3 6.30 . .. 10.00 MS132-10 8.00 ... 12.00 MS132-12 10.00 . .. 16.00 MS132-16 16.00 . .. 20.00 MS132-20 2 0.00 . .. 25.00 MS132-25 2 5.00 . .. 32.00 MS132-32

class

Note: MS132 with pre-assembled auxiliary contact HKF1-11, please order as follow 1SAM350005Rxxxx

Application The manual motor starters protect the load and the installation against short-circuit and overload. They are three pole protection devices with thermal tripping elements for overload protection and electro-magnetic tripping elements for shortcircuit protection. Furthermore, they provide a disconnect function for safely isolation of the installation and the supply and can be used for the manual switching of loads. Operation mode
Single-phase operation Three-phase operation

The manual motor starters have a setting scale in Amperes, which allows the direct adjusting of the device without any additional calculation. In compliance with international and national standards, the setting current is the rated current of the motor and not the tripping current (no tripping at 1.05 x I, tripping at 1.2 x I; I = setting current).

Connections Terminals 1L1, 3L2, 5L3

Switch position TRIP Trip indication for short-circuit Current setting range

Lockable handle Test function

Terminals 2T1, 4T2, 6T3

Resistance and power losses per phase


Type MS132-0.16 MS132-0.25 MS132-0.4 MS132-0.63 MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 Lower value setting range [A] 0.10 0.16 0.25 0.40 0.63 1.00 1.60 2.50 4.00 6.30 8.00 10.0 16.0 20.0 25.0 Upper value setting range [A] Resistance per phase [ ] Power loss per Phase [W] at Lower value of setting range 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.9 1.0 1.1 1.5 1.8 1.9 Upper value of setting range 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.4 2.3 2.8 2.3 2.8 3.1

0.16 66.00 0.25 25.50 0.40 10.38 0.63 4.36 1.00 1.605 1.60 0.648 2.50 0.272 4.00 0.106 6.30 0.046 10.0 0.024 12.0 0.016 16.0 0.011 20.0 0.0057 25.0 0.0045 32.0 0.0030

2 2CDC131021D0201

Dimensions
MS132 10 A MS132 > 10 A
81,05 / 3,19" 81,25 / 3,2" 72,4 / 2,85" 1,5 / 0,06" 5,5 / 0,22" 43,5 / 1,71" 1,5 / 0,06" 5,5 / 0,22" 72,2 / 2,84" 43,3 / 0,22"

1,7 / 0,1"

35 / 1,38"

45 / 1,77"

1,7 / 0,1"

97,8 / 3,85"

35 / 1,38"

90 / 3,54"

75 / 2,95"

14 / 0,55" 45 / 1,77"

14 / 0,55"

mm / inch

14 / 0,55" 45 / 1,77"

14 / 0,55"

75 / 2,95"

mm / inch

2CDC242015F0009

2CDC242016F0009

MS132 10 A + screw fixing kit

MS132 > 10 A + screw fixing kit

4,5 / 0,18"

9 / 0,35"

5,4 / 0,21"

4,5 / 0,18"

9 / 0,35"

5,4 / 0,21"

110 / 4,33"

122 / 4,8"

mm / inch
17,5 / 0,69" 17,5 / 0,69"

110 / 4,33"

122 / 4,8"

mm / inch

2CDC242017F0009

2CDC242018F0009

Wiring diagram

Approvals

Markings

cULus UL 508

ABS

E
GOST-F

GL

P
2CDC131021D0201 3

CE

GOST-R

45 / 1,77"

Data at TA = 40 C and at rated values, if nothing else indicated


Type Technical data Main circuit Rated operational voltage Ue acc. to IEC/EN 60947-1 Terminals 1L1-3L3-5L5 2T1-4T2-6T3 690 V 250 V see separate table see Rated operational current see Rated operational current see ordering data see separate table see separate table see separate table 10 kA see ordering data 50 / 60 Hz 3 see separate table see separate table see separate table MS132

a.c. d.c.

Rated operational current Ie Rated operational current DC-5 Ie 3 conducting paths in series up to 250 V Rated current I n / Conventional free-air thermal current Ith Setting range - thermal overload protection Rated instantaneous short-circuit current setting Ii Rated service short-circuit breaking capacity Ics Rated ultimate short-circuit breaking capacity Icu Rated service short-circuit breaking capacity d.c. Ics 3 conducting paths in series up to 250 V

Trip class acc. to IEC/EN 60947-4-1 Rated frequency acc. to IEC/EN 60947-1 Number of poles Resistence per phase Power loss per phase lower value of setting range upper value of setting range

Isolation data Rated impulse withstand voltage U imp acc. to IEC/EN 60947-1 Rated insulation voltage Ui acc. to IEC/EN 60947-1 Pollution degree acc. to IEC/EN 60664 Electrical connection MS132 10A Connecting capacity solid flexible with ferrule flexible with ferrule isolated flexible without ferrule Stripping length Tightening torque Connection screw MS132-12, -16 Connecting capacity solid flexible with ferrule flexible with ferrule isolated flexible without ferrule Stripping length Tightening torque Connection screw MS132-20, -25, -32 Connecting capacity solid flexible with ferrule flexible with ferrule isolated flexible without ferrule Stripping length Tightening torque Connection screw 1/2 x 2.5 ... 6 mm 2 1/2 x 1 ... 6 mm2 1/2 x 1 ... 6 mm2 1/2 x 2.5 ... 6 mm 2 10 mm 2 Nm M4 (Pozidrive 2) 1/2 x 1 ... 4 mm2 1/2 x 0.75 ... 2.5 mm 2 1/2 x 0.75 ... 2.5 mm2 1/2 x 0.75 ... 2.5 mm 2 10 mm 1.5 Nm M4 (Pozidrive 2) 1/2 x 1 ... 4 mm 2 1/2 x 0.75 ... 2.5 mm 2 1/2 x 0.75 ... 2.5 mm2 1/2 x 0.75 ... 2.5 mm2 9 mm 0.8 ... 1.2 Nm M3.5 (Pozidrive 2) 6 kV 690 V 3

4 2CDC131021D0201

Type General Data Mechniacl durability Electrical durability Duty time Dimensions (W x H x D) Weight Mounting Mounting positions Group Mounting Minimum distance to other units same type Minimum distance to electrical conductive wall (earthed) Degree of protection acc. to IEC/EN 60947-1 horizontal vertical horizontal - up to 400 V horizontal - up to 690 V vertical enclosure / terminals

MS132

10 5 5 x 10 4 100% see dimension drawing see ordering data DIN-rail (EN 60715) optional for single mounting (position 1-6) on request 0 mm 150 mm 0 mm > 1.5 mm 75 mm IP20 A up to 2000 m

Utilization Category acc. to IEC/EN 60947-2 Altitude Environmental data Ambient air temperature range Operation open - compensated without derating open Storage Temperature compensation Vibration (sinusoidal) acc. to IEC/EN 60068-2-6 (Fc) Shock (half-sine) acc. to IEC/EN 60068-2-27 (Ea)

-25 C ... +60 C -25 C ... +70 C -50 C ... +80 C continuous 5 g / 3 - 150 Hz 25 g / 11 ms

Standards / Directives Standard Low Voltage Directive EMC Directive RoHS Directive Electromagnetic compatibility Approvals, markings Approvals Markings UL/CSA Max. operational voltage Manual Motor Controller ratings Motor ratings Horse power Full load amps (FLA) Locked rotor amps (LRA) Short-Circuit Protective devices see separate table see separate table see separate table see separate table 600 V see separate table see page 3 see page 3 not applicable IEC/EN 609472, ICE/EN 60947-4-1, IEC/EN 60947-1, UL 508; CSA 22.2 No. 14 2006/95/EC 2004/108/EC 2002/95/EC

2CDC131021D0201 5

Type Technical data Electrical connection MS132 10A Connecting capacity solid stranded flexible without ferrule Stripping length Tightening torque Connection screw MS132-12, -16 Connecting capacity solid stranded flexible without ferrule Stripping length Tightening torque Connection screw MS132-20, -25, -32 Connecting capacity stranded flexible without ferrule Stripping length Tightening torque Connection screw

MS132

1/2 x AWG16 ... AWG12 1/2 x AWG16 ... AWG12 1/2 x AWG16 ... AWG12 9 mm 10 - 12 lb-in M3.5 (Pozidrive 2) 1/2 x AWG16 ... AWG12 1/2 x AWG16 ... AWG12 1/2 x AWG16 ... AWG12 10 mm 14 lb-in M4 (Pozidrive 2 / 6.5 mm) 1/2 x AWG12 ... AWG8 1/2 x AWG12 ... AWG8 10 mm 18 lb-In M4 (Pozidrive 2)

Type

Rated instantaneous short-circuit current setting li [A]

Rated current ln / Conventional free-air thermal current lth [A] 0.16 0.25 0.40 0.63 1.00 1.60 2.50 4.00 6.30 10.0 12.0 16.0 20.0 25.0 32.0

MS132-0.16 1.25 1.87 MS132-0.25 1.95 2.92 MS132-0.4 3.12 4.68 MS132-0.63 4.91 7.37 MS132-1.0 9.20 13.8 MS132-1.6 14.7 22.1 MS132-2.5 23.0 34.5 MS132-4.0 40.0 60.0 MS132-6.3 63.0 94.5 MS132-10 120 180 MS132-12 144 216 MS132-16 192 288 MS132-20 240 360 MS132-25 300 450 MS132-32 384 576

Short-Circuit protection
Type MS132-0.16 MS132-0.25 MS132-0.4 MS132-0.63 MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 I CS [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 50 25 230 V AC I CU [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 50 50 gG [A] 100 125 I CS [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 50 25 400 V AC I CU [kA] 100 100 100 100 100 100 100 100 100 100 100 100 100 50 50 gG [A] 100 125 I CS [kA] 100 100 100 100 100 100 100 3 3 3 3 3 3 3 3 690 V AC ICU [kA] 100 100 100 100 100 100 100 3 3 3 3 3 3 3 3 gG [A] on request on request on request on request on request on request on request on request
lCS = Rated service short-circuit breaking capacity lCU = Rated ultimate short-circuit breaking capacity o = No back-up fuse required, because short-circut proof up to 100 kA

6 2CDC131021D0201

UL / CSA ratings
Type MS132-0.16 MS132-0.25 MS132-0.4 MS132-0.63 MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 hp - - - - - 1/10 1/6 1/3 1/2 1-1/2 2 2 3 3 5 FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 12 12 17 17 28 Motor rating, single phase 220 - 240 V AC LRA 0.96 1.5 2.4 3.78 6 9.6 15 24 37.8 60 72 72 92 127 162 hp - - - - - - 1/2 1/2 1 3 3 5 5 7-1/2 10 440 - 480 V AC FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 8.5 8.5 14 14 21 26 LRA 0.96 1.5 2.4 3.78 6 9.6 15 24 37.8 46 64 81 81 116 145

Type MS132-0.16 MS132-0.25 MS132-0.4 MS132-0.63 MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 hp - - - - - - - - 1/2 3/4 1-1/2 2 3 3 5 110 - 120 V AC FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 12 16 19.2 19.2 30.4 LRA 0.96 1.5 2.4 3.78 6 9.6 15 24 37.8 60 72 84 128 128 184 hp - - - - - - 1/2 1 1-1/2 3 3 5 5 7-1/2 10

Motor rating, three phase 220 - 240 V AC FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9.6 9.6 15.2 15.2 22 28 LRA 0.96 1.5 2.4 3.78 6 9.6 15 24 37.8 64 64 92 92 127 162 hp - - - - - 3/4 1 2 3 5 7-1/2 10 10 15 20 440 - 480 V AC FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 4 4.8 7.6 11 14 14 21 27 LRA 0.96 1.5 2.4 3.78 6 9.6 15 24 32 46 64 81 81 116 145 hp - - - - 1/2 3/4 1-1/2 3 5 7-1/2 10 10 15 20 25 500 - 600 V AC FLA 0.16 0.25 0.4 0.63 1 1.6 2.5 3.9 6.1 9 11 11 17 22 27 LRA 0.96 1.5 2.4 3.78 6 9.6 15 26 37 51 65 65 93 116 146

Type MS132-0.16 MS132-0.25 MS132-0.4 MS132-0.63 MS132-1.0 MS132-1.6 MS132-2.5 MS132-4.0 MS132-6.3 MS132-10 MS132-12 MS132-16 MS132-20 MS132-25 MS132-32 Max. Circuit Breaker per UL/NEC 480 V / 600 V [A] 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 Max. Fuse type K5 o. RK5 per UL/NEC 480 V / 600 V [A] 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250

UL 508 Manual Motor Controller for Motor D isconnect Max. Short Circuit Current [kA] 480 V 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 600 V 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 for Group Installation Max. Short Circuit Current [kA] 480 V 600 V 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - 30 - for Tap Conductor Max. Short Circuit Current [kA] 480 V 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 600 V -

2CDC131021D0201 7

Contact us

You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage products

We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2010 ABB All rights reserved

Order Number 2CDC 131 021 D0201 Printed in Germany (07.10)

ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-Mail: info.desto@de.abb.com

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.