Power System Manager (PSM2000)

OPERATING MANUAL PSM2000

Page 1

Power System Manager (PSM2000)


Table of content 1. 2. Introduction.................................................................................................................... 3 Installation ..................................................................................................................... 3 Connecting RS 232 port .......................................................................................... 3 Connection PC - SYS 3000. .................................................................................... 4

2.1. 2.2. 3.

General presentation ..................................................................................................... 5 MENU SELECTION................................................................................................. 5

3.1. 4.

Getting started ............................................................................................................... 6 Connection to the inverter system ........................................................................... 6

4.1. 5.

Using the software......................................................................................................... 7

5.1. Menu Current Connection ................................................................................. 7 5.1.1. Sub-menu Inverters Informations..................................................................... 7 5.1.2. Sub-menu Schema ........................................................................................ 11 5.1.3. Sub-menu Actions.......................................................................................... 12 5.1.4. Sub-menu Alarm Log ..................................................................................... 14 5.1.5. Sub-menu History log..................................................................................... 14 5.1.6. Sub-menu Global Actions .............................................................................. 15 5.2. MENU Connect. ................................................................................................... 16 5.2.1. Sub-menu Dial ............................................................................................... 16 5.2.2. Sub-menu Wait for a call................................................................................ 16 5.3. MENU Configuration. ........................................................................................... 17 5.4. MENU Tools......................................................................................................... 17 5.5. MENU Exit. .......................................................................................................... 17 5.6. MENU Help (?)..................................................................................................... 18 6. Troubleshooting........................................................................................................... 18

This software is based on an ON LINE help menu. Please do not hesitate to consult this help function while you are using the software. This software is protected with a licence number in relation with the serial number of the SYS3000 controller. If you have any communication problem please verify that you are using the appropriate licence number according to the serial number of the controller SYS3000.

Page 2

Power System Manager (PSM2000)


1. Introduction
PSM2000 (Power System Manager) is the remote management software dedicated to work with Inverter system Supervisor SYS3000 controller. PSM2000 is able to monitor and control all generation of inverter modules, static switches and inverter systems based on RDI technology. It operates under Win95, Win98, Win2000, WinXP or WinNT operating system. Basics functions are :

Getting connected with the system locally or through modem line Displaying information on the complete system, each inverter group or each inverter unit individually in a bloc diagram, or text mode format Being informed when any event occurs on the system Having all information and history in a log file which can be saved or printed ...

2. Installation
Installation must be done from Zip file, executable file is PSM2000.EXE After unzipping the file to a specified location, launch PSM2000 Icon in the installation directory. Minimum material for proper software use : VGA screen 32Mb RAM RS 232 serial port Windows 95 or above

2.1. Connecting RS 232 port


Connect a cable between the SYS3000 front plug (DB9) and the computer. CAUTION : You CANNOT connect pin5 (GND) to the RS-232 plug chassis. Never connect A with B as showed on the schematic

Figure 1. : DB9 connection

Page 3

Power System Manager (PSM2000)


2.2. Connection PC - SYS 3000. Use a cable with following characteristics :

Figure 2. : Serial cable for PC connection

Page 4

Power System Manager (PSM2000)


3. General presentation
Main interface of PSM2000 is a graphic window. This window is made of : Drop-down menus you can access with mouse click or via function key F10 + arrows Indicators below this menu line, allowing the user to check the activity on the communication line

Thanks to these indicators, the user can check the proper working of the PSM2000 communication software and if the station is corresponding with the computer.

Figure 3. : Main interface of PSM2000

3.1. MENU SELECTION


PSM2000 (Power System Manager) software offers the following menus :

Current connection

Connect
Configuration Tools Exit Help ( ?)

You can access the sub-menus the following way : Clicking with your mouse on the menu With arrow keys and Enter when you are on the appropriate menu

Page 5

Power System Manager (PSM2000)


4. Getting started
Click on the icon PSM2000 to start the software PSM2000. 4.1. Connection to the inverter system
Be sure that your PC or modem is correctly settled and the system with SYS3000 has been switched ON, modem is configured in PSM2000 and in the controller SYS3000. If configurations in PSM2000 and in the SYS3000 are not correct, communication may not be established. If you are not using a modem, then connect an RS232 cable between your PC and the SYS3000 serial port (DB9 connector). The serial cable is a classic serial communication cable; refer to chapter 2.2. Select the menu Connect in the general toolbar to enter in the connection window.

Figure 4. : Connection window Important notes : 1. Serial number and license number must be properly entered otherwise communication may not be established. 2. To add a new system to the Station List for monitoring, click on Append and complete the informations before establishing the connection. 3. Be sure that SYS3000 and terminal have the same configuration before establishing communication.

Page 6

Power System Manager (PSM2000)


5. Using the software
5.1. Menu Current Connection 5.1.1. Sub-menu Inverters Informations
This sub-menu displays the characteristics / parameters of inverters present in the system. These informations are stored in the memory of the SYS3000. The Sub-menus STATUS & SCHEMA displays system informations but doesnt allow any system operation. To change inverters parameters, the user must use the ACTION Sub-menu. Sub-menu Status - System This window allows checking parameters for the complete inverter system : General informations : SYS 3000 software number Inverter system characteristics : site name, serial number, time and date Configuration : DC nominal voltage Monitored nominal power Percentage of installed power used for the loads Inverters : Number of configured inverters Number of monitored inverters Number of inverters in normal working mode Number of manually stopped inverters Measures : Voltage, current and delivered power from the inverter system Output frequency Loading rate of inverters Static Switch (if present): Working mode if applicable Alarms present on the Static Switch Static switch source used to supply the load Alarms : Alarm stop menu activated or not Total of Urgent / Non urgent alarms present in the system

Page 7

Power System Manager (PSM2000)

Figure 5. : Inverters informations window (System)

Page 8

Power System Manager (PSM2000)


Sub-menu Status - Group This window allows the user to check informations per inverter group : Each group is selectable by accessing the dedicated menu (Group 1 Group 4) Configuration : Nominal DC input voltage Monitored nominal power Stopping voltage value on DC input Status of inverters : Number of configured inverters Number of monitored inverters Number of inverters working properly Number of inverters manually stopped Measures : Voltage, current and delivered power from the inverter system DC input voltage of inverter group

Figure 6. : Inverters informations window (Group)

Page 9

Power System Manager (PSM2000)


Sub-menu Status - Module This window allow the user to check informations per inverter : Modules configuration : Nominal power of each inverter Inverter status Measures : Output current and power for each inverter Heatsink temperature of each module

Figure 7. : Inverters informations window (Module)

Page 10

Power System Manager (PSM2000)


5.1.2. Sub-menu Schema
This window is a graphical representation of the inverter system, showing the configuration of the connected system. Schematic is composed of following elements : DC input breakers Inverter modules Inverter groups Complete inverter system Static switch Manual By-pass Auxiliary AC back-up source (with or without breakers) Output fuses / breakers Clicking on the objects will show the statues of measurements. Alarms are color-represented : Yellow for Non-Urgent Red for Urgent

Figure 8. : Schema window

Page 11

Power System Manager (PSM2000)


5.1.3. Sub-menu Actions
The action window allows the user to make operations on the connected system. 'System' allows to start/stop the system with the buttons Start / Stop

Figure 9. : Inverters actions window (System) 'Groups' allows to start / stop inverters groups, selected with clicking boxes, with the Start / Stop buttons.

Figure 10. : Inverters actions window (Groups)


Page 12

Power System Manager (PSM2000)


'Modules' allows to start / stop inverters, selected with clicking boxes, with the Start / Stop buttons. Additional informations are available : Group number and module status.

Figure 11. : Inverters actions window (Modules) 'Static Switch' allows to know the working mode (On-Line or Off-line) if static switch is present. The button apply allows to validate the new working mode.

Figure 12. : Inverters actions window (Static switch)

Page 13

Power System Manager (PSM2000)


5.1.4. Sub-menu Alarm Log
This menu allows the user to see the alarm log file for the inverter system. A counter indicates the number of Urgent and Non-urgent alarms present in the system.

Figure 13. : Alarm log window

5.1.5. Sub-menu History log


This sub-menu displays the events recorded in the SYS3000 (100 events maximum). For each message following informations are available : Number, Date, Time, Label and Alarm type (UA NUA - No Alarm)

Figure 14. : History log window

Page 14

Power System Manager (PSM2000)


Messages are displayed with time/date classification. The newer message appears on top. The print button allows to print the events. The Save button allows to save the event log in the specified location.

5.1.6. Sub-menu Global Actions Sub-menu Date & time


This sub-menu allows setting up the SYS3000 time and dating from the computer. It is necessary to have correct parameters on the computer before sending the informations.

Figure 15. : Global actions window (Date & Time)

Sub-menu History log


This Sub-menu shows the events applied to the system. It is also possible to clear the changes made to the system (Clear button)

Figure 16. : Global actions window (History log)

Page 15

Power System Manager (PSM2000)


5.2. MENU Connect.
This menu allows to make connection between computer / SYS3000 device.

5.2.1. Sub-menu Dial


Station list & description : This menu shows the registered stations on the computer software. To connect to inverter system, choose SYS3000. In the description menu, it is necessary to enter the Serial Number and the License number. Serial number is available on the SYS3000 (6-Number digit), please refer to SYS3000 manual. The License number is given by your inverter system supplier. Protocol to use is J-Bus Connection must be made in Terminal mode to connect direct from computer. To connect remotely via modem, choose Modem in the connection menu. Enter the phone number of the modem installed in the system in the appropriate Phone number box. In the terminal configuration menu, you must enter your computer parameters for connection. Here are standard parameters to use : Port : depends on your system Baud rate : 9600 Stop bits : 1 Parity : none Flow control : None Data bits : 8

Click on Connect to start connection.

5.2.2. Sub-menu Wait for a call


Select the appropriate device (Modem) on your computer to use for connection and press OK. When this is done, the computer will wait for incoming call from the inverter system. (The phone number to call the computer must be set up in the SYS3000, see related manual).

Page 16

Power System Manager (PSM2000)


5.3. MENU Configuration.
This menu allows to set up parameters : Password to restrict access to PSM2000 software Callback number for the modem in case of callback Default language

Figure 17. : Configuration window

5.4. MENU Tools.


This menu allows to configure the modem installed in the system and connected to SYS3000.

Figure 18. : Device selection window

5.5. MENU Exit.


This menu allows to exit from PSM2000.

Figure 19. : Exit window Yes button will exit. No button will come back to the PSM2000 Software
Page 17

Power System Manager (PSM2000)


5.6. MENU Help (?).
This menu enters the On-line help from the PSM2000

6. Troubleshooting
This section will help you in case you cannot operate the software properly. An ON-Line help is also available with the software; please do not hesitate to consult it. Connection/communication problem Check your licence number is correct with reference to the controller serial number. If you do not have the licence number please note the last 6 digits of the serial number and ask support team to provide you with the proper licence number. If you are using a modem please verify that PSM2000 and SYS3000 have the same configuration parameters. If a password has been installed in the SYS3000 you must install it in the PSM2000 because each command you are sending is checked by verifying both password.