Volume of Nitrogen Required For Testing & Purging Containers **


Insert Pertinent Information In Yellow Boxes

Pressure Testing PIPE with Nitrogen


Length In Ft. =

50
Dia. In Inches. =

8
0.667

=L =D Dia. In Ft. =

Nitrogen Volume Required

High Pressure 'T' Cylinders Required

Volume of Gas @

125

PSIG:

166

CF

T Cyl.s 0.6

The Nitrogen volumes shown are for pressurizing a pipe to the selected pressure only. Additional Nitrogen would be required for any additional purging or volume changes. See below for purging calculations. It is always recommended to have additional Nitrogen available to compensate for any leaks or un-foreseen requirements.

Purging or Pressure Testing TANKS with Nitrogen


Length or Height In Ft. = =L =D Diameter In Ft. =

20

8
T' Cyl.s Req. to Achieve Volume Changes

Volume of Gas @ 1 Atm. To Obtain:

Nitrogen Volume Required 1,005 CF 3,014 7,034 5,024


CF CF CF

Appr. Residual Oxygen Approximate Vol. Levels Changes Rqd.

Purging Data

Volume Required for Air Purge @ 1 Atm: Volume Required for Food Purge @ 1 Atm.: Volume Required for 100 % Purge @ 1 Atm.:

1.0% O2 Bal. .02% O2 Bal. .14% O2 Bal.

3 7 5

9.9 23.1 16.5

Purging does not require pressurization. The results shown are for the number of 'T' cylinders to provide the appropriate number of volume changes at very low flow with no pressurization. Note: NEVER enter a vessel that has been purged with Nitrogen, or any other gas unless you have tested that atmosphere for proper levels of oxygen.

For Pressure Test of Vessel, Add Test Pressure Required. Volume of Gas @

25

PSIG:

2,714

CF

Pressure Testing Data

High Pressure Cylinders Required

T Cyl.s 9.0

www.weldspecialty.com

Page 1 of 2

Printed: 11/6/2013

Volume of Nitrogen Required For Testing & Purging Containers **


Insert Pertinent Information In Yellow Boxes

Purging or Pressure Testing FURNACES with Nitrogen

Length In Ft. =

12

Height In Ft. =

Width In Ft. =

6
Appr. Residual Oxygen Approximate Vol. Levels Changes Rqd.

Volume of Gas @ 1 Atm. To Obtain:

Nitrogen Volume Required 360 CF 1,080 2,520 1,800


CF CF CF

T' Cyl.s Req. to Achieve Volume Changes

Purging Data

Volume Required for Air Purge @ 1 Atm: Volume Required for Food Purge @ 1 Atm.: Volume Required for 100 % Purge @ 1 Atm.:

1.0% O2 Bal. .02% O2 Bal. .14% O2 Bal.

3 7 5

3.6 8.3 5.9

Purging does not require pressurization. The results shown are for the number of 'T' cylinders to provide the appropriate number of volume changes at very low flow with no pressurization. Note: NEVER enter a vessel that has been purged with Nitrogen, or any other gas unless you have tested that atmosphere for proper levels of oxygen.

For Pressure Test of Vessel, Add Test Pressure Required. Volume of Gas @

50

PSIG:

1,584

CF

Pressure Testing Data

High Pressure Cylinders Required

T Cyl.s 5.3

** This information is used to determine volumes of N2 requirements for purging pipelines and vessels, and is not intended to replace proper monitoring of oxygen levels with proper equipment.