Вы находитесь на странице: 1из 2

Air Light Troffer

Identification * NF/LAG/ALT-S (Single Sided) * NF/LAG/ALT-D (Double Sided)

60

mm 47 6m m

Material - Electrode Galvanised / Galvanised Iron Material Thickness - 0.5mm Insulation Material - Polyethylene (P.E)

17

m 8m 5 mm 08

168mm

Insulation Thickness - 3mm


152mm

89mm

42mm
13 mm

External Finish - Natural Width of Each Slot Opening - 19mm / 25mm / 38mm Note: Dimension of Light Troffer varies, depend on the size of light box

35

mm

13

mm

PRODUCT INFORMATION
NF/LAG/ALT offers in a single or double air diffusion. Troffers are designed to provide a maximum air flows at a minimum sound levels. Sizes are fabricated accordingly to project requirement.

NAM FOONG (M) SDN BHD (8070-T)

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR DIFFUSERS SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Single Sided Light Troffer Dedicated Vertical Throw Slot Size : 1108mm long, 38mm wide, with damper blade in centre, damper blade fully open Overall Unit Length : 1140mm SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 97 115 135 160 205 Ps (Pa) 22 31 42 58 99 T (m) 3 3.5 3.5 4 4 NR

4000

8000

21 27 31 35 42

<46.6 <47.4 <48.3 <50.3 55.9

<38.7 42.8 46.8 50.6 57.0

35.7 40.7 44.7 48.8 55.3

25.6 32.5 37.0 41.8 49.2

19.4 27.5 32.6 38.0 46.0

<15.4 20.5 27.0 33.7 42.9

<17.1 <17.4 <18.5 22.9 34.8

ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR DIFFUSERS SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 30/9/99 NAM FOONG (M) SDN BHD (8070-T) Double Sided Light Troffer Dedicated Vertical Throw Slot Size : 1108mm long, 38mm wide, with damper blade in centre, damper blade fully open Overall Unit Length : 1140mm SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000

TEST CONDITIONS Qs (l/s) 115 140 173 227 280 Ps (Pa) 11 16 22 37 55 T (m) 4 4.5 >5 >5 >5 NR

4000

8000

<18 23 28 35 41

<47.5 <48.8 <50.2 54.4 58.9

<39.2 43.0 47.7 54.5 59.4

<31.9 37.5 42.2 49.4 54.6

23.5 30.9 36.9 44.8 50.4

<15.6 21.7 29.0 37.8 44.1

<14.6 <16.4 22.2 32.9 40.1

<17.1 <17.2 <17.8 23.4 31.9

LEGEND Qs Ps < > NR T Primary Air Flow Rate (l/s) Supply Static Pressure (Pa) Insufficient margin above background noise to allow accurate determination Length of throw greater than that able to be measured Noise Rating number based upon room absorption of 10 dB Throw in meters to a terminal velocity of 0.25 m/s