Вы находитесь на странице: 1из 3

U P T I M E I N S T I T U T E , L L C

Accredited Tier Designer Technical Paper Series:


Prepared by Uptime Institute Professional Services, LLC
Copyright 2011 by Uptime Institute, LLC
20 West 37th Street - 6th Floor
New York, NY 10018
All rights reserved.
The Uptime Institutes (Institute) publications are protected by international copyright law. The Institute requires written
requests at each and every occasion that the Institutes intellectual property or portions of the Institutes intellectual property
are reproduced or used. The Institute copyright extends to all mediapaper, electronic, and video contentand includes
use in other publications, internal company distribution, company Web sites and marketing materials, and handouts for
seminars and courses. For more information, please visit www.uptimeinstitute.org/resources to download a Copyright Re-
print Permission Request Form.
, LLC

Continuous Cooling
This Technical Paper supplements Data Center Site Infrastructure Tier Standard: Topology.
UPTIME INSTITUTE ATD Technical Paper Series: Continuous Cooling
2
This technical paper clarifies the requirements for Continuous Cooling in the context of the Uptime Institutes Tier Standard:
Topology. Tier IV is the only Tier that requires Continuous Cooling. Additionally, this paper serves to recommend Continuous
Cooling at densities beyond 4 kilowatts (kW)/rack, regardless of Tier.
As the power densities in the data center increase, the need for Continuous Cooling becomes more profound. The risk of
the loss of cooling during a UPS ride-though event can be catastrophic to a business. IT equipment may fail or become
wounded.
However, depending on the cooling or UPS technology deployed, the definition and requirement for Continuous Cooling
can widely differ. This paper clarifies the definition of Continuous Cooling and details its deployment with varying types of
technology choices.
Regardless of technology, Continuous Cooling is defined as the ability to provide stable cooling to the IT and UPS
environment without any interruption. Continuous Cooling provides this stable cooling capability for the duration of the
UPS ride-through time. For example, for a static UPS system with 15 minutes of battery, the Continuous Cooling will need
to provide stable cooling for 15 minutes. Note, however, that if there are redundant modules and battery strings available,
the 15 minute ride-through time could become 30 minutes or more (depending on redundancies). Careful consideration
should be taken by the owner to determine if the stated ride-through time or the available ride-through time should be the
requirement for the Continuous Cooling solution.
The American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), in concert with major IT
equipment manufacturers, established Thermal Guidelines for Data Processing Environments that includes recommended
computer equipment inlet air temperatures necessary to enable reliable operation of servers, storage, and network devices.
As of 2010, the ASHRAE guideline (accepted on a global basis) recommends that the device inlet be between 66-81F
(18-27C) and 20-80% relative humidity to meet the manufacturers established criteria.
As a point of reference, Uptime Institute conducted a demonstration on a 6-kW/rack average computer room. Intake air
temperatures in computer rooms will exceed the top value in this range within 60 seconds after a loss of cooling or even
air movement.
Consider the scenario of a utility failure, during which the UPS continues to power the IT devices, but mechanical plant
operation is interrupted. Depending on the technology of the cooling deployed, this interruption may continue for several
minutes. During this time, elevated temperatures in the computer room may damage IT equipment. Continuous Cooling
provides the bridge to enable stable cooling to continue until the mechanical or other cooling resumes.
TIER STANDARD: TOPOLOGY REQUIREMENTS
Tier IV is the only Tier that requires Continuous Cooling.
Continuous Cooling for a chilled water system is generally accomplished with thermal energy storage (TES) capability
(also known as chilled water storage). Secondary pumps and computer room air handlers (CRAHs) are required to be on
UPS. This can be the IT UPS or a separate, Concurrently Maintainable and Fault Tolerant, mechanical UPS system. If the
cooling system is in a primary-direct configuration, then the primary pumps are required to be on UPS.
Continuous Cooling for direct exchange (DX) systems requires both the computer room air conditioners (CRACs) and the
external condensers to be on a Concurrently Maintainable and Fault Tolerant UPS system. The same requirement exists for
split- system air conditioning units.
Continuous Cooling for 100% outside air systems that can provide cooling throughout the year require the fans (or the
system that delivers the air to the computer room) to be on UPS.
When rotary UPS systems are deployed as the IT UPS, then the cooling system must be on the no-break bus. This allows
provision of cooling throughout a UPS ride-through event. If there is a chilled water system deployed in tandem with a
rotary UPS with no batteries, typically no TES is required. However, each specific case should be reviewed to ensure stable
cooling is provided during a loss of power event.
Regardless of any of the cooling or UPS technology deployed in a particular data center, consideration must be given to
the time required to restore mechanical cooling. For example, in a chilled water system, although the engine generators
may assume the electrical load within seconds after loss of utility, the result of the momentary loss of power to the chillers
may require a restart cycle lasting up to 15 minutes or even more. Although manufacturers are reducing the restart times,
20 West 37th Street, 6th Floor, New York, NY 10018
+1 206.706.4149 Fax: +1 206.706.3083
uptimeinstitute.org professionalservices.uptimeinstitute.com
2011 Uptime Institute, LLC UI109110-411
, LLC
3
UPTIME INSTITUTE ATD Technical Paper Series: Continuous Cooling
the interval between the loss of power and a resumption of the systems ability to produce stable cooling needs to be
incorporated as a data point in the ride-through time. For example, if a UPS ride-through time is set at 5 minutes, yet it takes
15 minutes to resume stable mechanical cooling after a loss of power, then the TES must be able to provide 15 minutes of
chilled water storage.
Providing thermal stability to the IT and UPS environment during the transition from utility outage to engine-generator
power, Continuous Cooling ensures that a utility event does not result in costly heat damage to IT hardware or critical
equipment. A requirement only for Tier IV, but justifiable for average densities above 4 kW in light of potential damage to
facilities and IT investment.
RELATED PUBLICATIONS
Tier Standard: Topology
Accredited Tier Designer Technical Paper Series: Engine-Generator Ratings
Accredited Tier Designer Technical Paper Series: Makeup Water
Further information can be found at www.uptimeinstitute.com/resources.

Вам также может понравиться