Medium Voltage Cable Range

THE CABLE RANGE THAT DELIVERS DURABILITY AND TRUST


Over many years Draka has established a deserved reputation in the UK as the most trusted and reliable manufacturer in the Low Voltage cable sector. This reputation was earned through our constant commitment to our brand values. We are capitalising on this vast experience and expertise to extend the offering of the worlds most trusted cable brand into the UK medium voltage market, with products founded on the same core principles customer focus, safety, performance and durability. Draka UK is introducing a medium voltage cable range to provide the UKs leading contractors and distributors with the highest quality cables for the industrial and utilities sectors. Our cable exceeds specification requirements to ensure a life expectancy in excess of industry standards. Whether it is utilised for power distribution; (from wind farms and nuclear power stations through to substations), or in the industrial sector

(in applications such as rail networks, airports and major construction developments), our state-ofthe-art manufacturing techniques ensure the highest calibre cables and deliver unrivalled longevity and reliability. Added to the numerous industrial projects currently in progress throughout the UK, the energy network is

also being constantly refurbished, upgraded and maintained to cope with the increased electrical consumption. This has in turn created an increased demand for high quality medium voltage cables that will stand the test of time. Draka has the technical capability to meet this demand. Not only for the excellence of our products but also for the technical guidance and support that we offer. For the utilities sector, the range includes 11, 22 and 33 kV rated versions with solid aluminium or stranded copper cores, in both singles and triplex, normally with polyethylene outer sheaths. In addition to these variants, a stranded aluminium version is

available in singles. For the industrial sector, there are 11, 22 and 33 kV versions with PVC or Zero Halogen, Low Smoke (OHLS) sheathing with stranded copper or stranded aluminium conductors dependent on the application.

Drakas medium voltage product range has been developed with leading edge technology and is backed by the resources of one of the worlds major specialist cable companies. Draka Holding NV is an international cable manufacturer with a turnover of 2 billion Euros and 9,000 employees.

BUILT TO OUTPERFORM DECADE AFTER DECADE AFTER DECADE


Draka as an organisation is passionate about developing world leading products which deliver exceptional value. Customer focus, quality and innovation are at the heart of everything we do. Our technical experts, research and development and state-of-the-art manufacturing facility enables the production of the highest quality cabling systems.

Potential Risks
One of the biggest threats to the effective performance of medium voltage cables are defects in the insulation system caused by gas voids or impurities during the insulation of the cable. The impact of these defects is magnified with increasing voltage as the electrical stresses increase and can lead to degradation of the insulation and in the end a breakdown of the cable. Given the vast volume of medium voltage cabling required in UK infrastructure, and the number of people, businesses and services that are totally reliant on a continued supply of power, any failings requiring replacement can be severe and bring major cost implications. The range is produced at the Nssj factory in Sweden which since Draka acquired the site from ABB in 1999, has seen huge investment as part of a major refurbishment and extension programme. It now has the very latest plant and equipment which means it can be classed amongst the worlds most advanced Medium Voltage manufacturing factories. Already the leading medium voltage supplier to the Scandinavian utilities market, Draka has established a proven pedigree in the development of high quality products which are built to last. It is of course to ISO14001 and ISO9001 certified.

Built to last
Through the sophistication of the manufacturing techniques involved, Draka medium voltage cable limits the exposure to impurities during the compound handling process in production and as a result, its durability is unrivalled.

CLEAN MANUFACTURIN
1 Fundamental to the development of high quality, trusted medium voltage cable at Drakas facility in Sweden has been the introduction of R3 technology including clean rooms and closed systems for materials handling processes usually reserved for high voltage cable manufacture. Here, the crucial areas of the factory are contamination-controlled to eradicate the risk of environmental pollutants such as dust, airborne microbes, aerosol particles and chemical vapours from jeopardising the purity of the cable construction.

Extruder platform

Drum take up

NG. THE SECRET BEHIND


2 Not only does the closed system ensure that the materials used are not contaminated, those specified are all of the highest quality. The conductive cores are formed from copper or aluminium in a comprehensive range of cross sections. Another major component is XLPE (cross-linked polyethylene) a thermosetting material which is able to perform in temperatures of up to 90C without prematurely degrading. This contributes considerably to the resilience of the product.

Curing Line

220m in length with a

THE QUALITY AND LONGE


3 In 2007, Draka made a 6 million investment to refurbish and extend the Nssj site. The most significant development was the incorporation of a new peroxide cure CCV-Line for the insulation of our medium voltage cores. The line has doubled the capacity of the factory to meet the growing global demands for 10-36 kV medium voltage cable. 4 Fed from an extruder platform, the CCV-Line is 220m long with a vertical drop of 20m. It features a 200mm diameter tube through which the cable is cross linked at high temperature and high pressure. 5 Quality control extends across all aspects of the manufacturing process and includes stringent testing

vertical drop of 20m

ER LIFE OF OUR CABLES


procedures including X-rays during production to confirm the structural integrity of the cable. In accordance with European and country specific standards, Draka medium voltage cable is continuously put through long-term water immersion tests, followed by high voltage electrical breakdown testing to ensure the cables will be fully reliable throughout their expected operational life-span. All of the above is to ensure that Draka produces the highest quality medium voltage cables.

Taping machine measurement gauge Caterpillar

Capstan

1 CORE ARMOURED
CU-XLPE 11 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

10

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 23 25 27 29 30 32 34 37 41 43 47

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

16.0 17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8

1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5

30 32 35 36 38 40 42 46 50 53 57

140 160 210 240 270 220 380 480 570 690 840

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC conductor resistance at 90C /km 0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080 0.064 0.051 0.042 Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.43 0.40 0.38 0.37 0.36 0.35 0.33 0.32 0.31 0.30 0.29

0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68

0.14 0.13 0.12 0.12 0.11 0.11 0.10 0.10 0.10 0.09 0.09

0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.1 1.2 1.4

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4

205 255 295 335 380 425 485 545 625 695 755

205 240 300 335 380 435 505 575 680 765 845

250 295 355 410 485 535 620 705 835 940 1035

*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

11

www.drakauk.com 01332 345431

1 CORE ARMOURED
CU-XLPE 22 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

12

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 29 30 32 33 34 36 39 40 44 48 52

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

18.2 19.8 21.5 22.8 24.4 26.0 28.3 30.6 33.4 36.4 40.0

1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5

36 38 39 41 42 44 48 50 54 58 62

170 200 240 300 350 440 510 610 730 890 1080

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 AC conductor resistance at 90C /km 0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080 0.064 0.051 0.042 Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.46 0.43 0.41 0.40 0.38 0.37 0.36 0.34 0.33 0.32 0.31

0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44

0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10

0.3 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4

205 255 295 335 380 425 485 545 625 695 755

205 240 300 335 380 435 505 575 680 765 845

250 295 355 410 485 535 620 705 835 940 1035

Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.

13

www.drakauk.com 01332 345431

1 CORE ARMOURED
CU-XLPE 33 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

14

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 34 36 38 39 40 42 44 47 51 53 58

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

25.2 26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0

2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5

42 44 47 48 50 52 54 57 61 64 69

210 240 300 340 380 420 490 580 680 800 960

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080 0.064 0.051 0.042

0.46 0.45 0.44 0.42 0.41 0.40 0.38 0.37 0.35 0.34 0.33

0.16 0.18 0.21 0.23 0.25 0.27 0.229 0.32 0.36 0.40 0.44

0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.10

0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4

205 255 295 335 380 425 485 545 625 695 755

205 240 300 335 380 435 505 575 680 765 845

250 295 355 410 485 535 620 705 835 940 1035

*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

15

www.drakauk.com 01332 345431

3 CORE ARMOURED
CU-XLPE 11 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

16

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 44 47 51 55 58 61 69 72

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

16.0 17.5 19.3 20.8 22.2 24.1 26.3 28.6

2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15

54 58 62 67 69 73 82 86

600 750 800 850 950 1100 1425 1700

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080

0.34 0.33 0.31 0.30 0.29 0.28 0.27 0.26

0.24 0.27 0.31 0.33 0.36 0.40 0.49 0.55

0.11 0.10 0.10 0.09 0.09 0.09 0.09 0.08

0.5 0.6 0.7 0.7 0.8 0.8 0.9 1.0

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3 42.9

3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

175 210 250 285 325 360 415 470

165 205 240 280 320 360 420 480

205 250 295 340 390 435 515 590

*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

17

www.drakauk.com 01332 345431

3 CORE ARMOURED
CU-XLPE 22 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under the copper tape Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

18

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 53 57 63 65 67 72 76 72

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

20.2 21.8 23.5 24.8 26.4 28.0 30.3 28.6

2.5 2.5 2.5 3.15 3.15 3.15 3.15 3.15

64 68 74 77 80 84 88 95

700 780 900 1100 1200 1400 1600 1850

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601

0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080

0.37 0.35 0.33 0.32 0.31 0.30 0.29 0.28

0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32

0.12 0.11 0.10 0.10 0.10 0.09 0.09 0.09

0.7 0.8 0.8 0.9 1.0 1.0 1.2 1.3

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3 42.9

3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

175 210 250 285 325 360 415 470

165 205 240 280 320 360 420 480

205 250 295 340 390 435 515 590

Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

19

www.drakauk.com 01332 345431

3 CORE ARMOURED
CU-XLPE 33 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

20

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 60 64 67 71 72 75 79

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

25.2 26.8 28.5 29.8 31.4 33.0 35.3

2.5 3.15 3.15 3.15 3.15 3.15 3.15

83 87 90 92 94 97 101

900 1100 1200 1350 1450 1600 1800

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.387 0.268 0.193 0.153 0.124 0.0991 0.0754

0.494 0.343 0.248 0.196 0.159 0.128 0.0988

0.41 0.39 0.37 0.36 0.35 0.33 0.32

0.13 0.14 0.16 0.17 0.18 0.20 0.22

0.13 0.12 0.12 0.11 0.11 0.10 0.10

0.8 0.8 1.0 1.0 1.1 1.2 1.3

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3

3x50 3x70 3x95 3x120 3x150 3x185 3x240 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

175 210 250 285 325 360 415

165 205 240 280 320 360 420

205 250 295 340 390 435 515

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

21

www.drakauk.com 01332 345431

1 CORE ARMOURED
AL -XLPE 11 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

22

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 23 25 27 29 30 32 34 72 41 43 47

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

16.0 17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8

1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5

30 32 35 36 38 40 42 46 50 53 57

110 120 150 170 180 210 240 280 330 380 440

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 AC conductor resistance at 90C /km 0.822 0.568 0.410 0.325 0.265 0.211 0.162 0.130 0.102 0.0825 0.0632 Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.43 0.40 0.38 0.37 0.36 0.35 0.33 0.32 0.31 0.30 0.29

0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68

0.14 0.13 0.12 0.12 0.11 0.11 0.10 0.10 0.10 0.09 0.09

0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.1 1.2 1.4

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

155 200 235 265 300 330 385 435 510 570 635

160 190 230 265 300 345 400 460 555 635 720

195 235 280 325 370 425 490 565 680 775 880

*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.

23

www.drakauk.com 01332 345431

1 CORE ARMOURED
AL -XLPE 22 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

24

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 29 30 32 33 34 36 39 40 44 48 52

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

18.2 19.8 21.5 22.8 24.4 26.0 28.3 30.6 33.4 36.4 40.0

1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5

36 38 39 41 42 44 48 50 54 58 62

140 160 180 200 210 240 290 320 370 420 490

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 AC conductor resistance at 90C /km 0.822 0.568 0.410 0.325 0.265 0.211 0.162 0.130 0.102 0.0825 0.632 Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.46 0.43 0.41 0.40 0.38 0.37 0.36 0.34 0.33 0.32 0.31

0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44

0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10

0.3 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

155 200 235 265 300 330 385 435 510 570 635

160 190 230 265 300 345 400 460 555 635 720

195 235 280 325 370 425 490 565 680 775 880

Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.

25

www.drakauk.com 01332 345431

1 CORE ARMOURED
AL -XLPE 33 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black

26

Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 34 36 38 39 40 42 44 47 51 53 58

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

25.2 26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0

2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5

42 44 47 48 50 52 54 57 61 64 69

180 200 240 260 290 310 340 380 440 490 560

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 DC conductor resistance at 20C /km 0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469 AC conductor resistance at 90C /km 0.822 0.568 0.410 0.325 0.265 0.211 0.162 0.130 0.102 0.0825 0.042 Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.46 0.45 0.44 0.42 0.41 0.40 0.38 0.37 0.35 0.34 0.33

0.16 0.18 0.21 0.23 0.25 0.27 0.229 0.32 0.36 0.40 0.44

0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.10

0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

155 200 235 265 300 330 385 435 510 570 635

160 190 230 265 300 345 400 460 555 635 720

195 235 280 325 370 425 490 565 680 775 880

*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.

27

www.drakauk.com 01332 345431

3 CORE ARMOURED
AL -XLPE 11 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

28

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 44 47 51 55 58 61 69 72

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

16.0 17.5 19.3 20.8 22.2 24.1 26.3 28.6

2.5 2.5 2.5 2.5 2.5 2.5 3.15 3.15

54 58 62 67 69 73 82 86

450 500 600 650 750 850 950 1100

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100

0.822 0.568 0.411 0.325 0.265 0.211 0.162 0.130

0.34 0.33 0.31 0.30 0.29 0.28 0.27 0.26

0.24 0.27 0.31 0.33 0.36 0.40 0.49 0.55

0.11 0.10 0.10 0.09 0.09 0.09 0.09 0.08

0.5 0.6 0.7 0.7 0.8 0.8 0.9 1.0

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3

3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

145 175 205 230 260 290 340 380

130 155 190 220 250 280 330 375

160 190 230 265 305 340 400 460

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

29

www.drakauk.com 01332 345431

3 CORE ARMOURED
AL -XLPE 22 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under the copper tape Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

30

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 53 57 63 65 67 72 76 72

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

20.2 21.8 23.5 24.8 26.4 28.0 30.3 28.6

2.5 2.5 2.5 3.15 3.15 3.15 3.15 3.15

64 68 74 77 80 84 88 95

600 650 700 850 900 1000 1150 1300

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.641 0.443 0.320 0.253 0.206 0.164 0.125 0.100

0.822 0.568 0.410 0.325 0.265 0.211 0.162 0.130

0.37 0.35 0.33 0.32 0.31 0.30 0.29 0.28

0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32

0.12 0.11 0.10 0.10 0.10 0.09 0.09 0.09

0.7 0.8 0.8 0.9 1.0 1.0 1.2 1.3

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3

3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

145 175 205 230 260 290 340 380

130 155 190 220 250 280 330 375

160 190 230 265 305 340 400 460

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

31

www.drakauk.com 01332 345431

3 CORE ARMOURED
AL -XLPE 33 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black

32

Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240

Diameter over insulation mm

Diameter over inner sheath (approx.) mm 60 64 67 71 72 75 79

Diameter of steel wires mm

Overall diameter (approx.) mm

Weight (approx.) Kg/100 m

25.2 26.8 28.5 29.8 31.4 33.0 35.3

2.5 3.15 3.15 3.15 3.15 3.15 3.15

83 87 90 92 94 97 101

950 1050 1150 1250 1400 1550 1700

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 DC conductor resistance at 20C /km AC conductor resistance at 90C /km Inductance mH/km Capacitance F/km Reactance at 50 Hz /km Charging current/phase A/km

0.641 0.443 0.320 0.253 0.206 0.164 0.125

0.822 0.568 0.410 0.325 0.265 0.211 0.162

0.41 0.39 0.37 0.36 0.35 0.33 0.32

0.13 0.14 0.16 0.17 0.18 0.20 0.22

0.13 0.12 0.12 0.11 0.11 0.10 0.10

0.8 0.8 1.0 1.0 1.1 1.2 1.3

Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3

3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W

145 175 205 230 260 290 340 380

130 155 190 220 250 280 330 375

160 190 230 265 305 340 400 460

Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.

33

www.drakauk.com 01332 345431

1 CORE
CU-XLPE-CWS-PE 11 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

34

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8

27 29 30 32 34 36 38 43 45 50

125 150 180 215 250 305 370 465 565 700

K14 K14 K14 K14 K16 K16 K18 K20 K20 K22

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.40/0.58 0.38/0.56 0.36/0.55 0.35/0.54 0.34/0.53 0.33/0.51 0.31/0.50 0.31/0.49 0.29/0.48 0.29/0.47

0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68

1.1 1.2 1.3 1.4 1.6 1.8 2.0 2.2 2.4 2.7

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4

255 295 335 380 425 485 545 625 695 755

240 300 335 380 435 505 575 680 765 845

295 355 410 485 535 620 705 835 940 1035

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

35

www.drakauk.com 01332 345431

1 CORE
CU-XLPE-CWS-PE 22 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

36

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

21.8 23.5 24.8 26.4 28.0 30.3 32.6 35.4 38.4 42.0

31 33 34 35 37 39 42 46 49 53

140 165 195 230 265 325 390 490 590 725

K14 K14 K14 K14 K16 K16 K18 K20 K20 K22

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.42/0.61 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.52 0.32/0.51 0.31/0.50 0.30/0.48

0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44

0.8 0.8 0.9 1.0 1.0 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4

255 295 335 380 425 485 545 625 695 755

240 300 335 380 435 505 575 680 765 845

295 355 410 485 535 620 705 835 940 1035

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

37

www.drakauk.com 01332 345431

1 CORE
CU-XLPE-CWS-PE 33 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-1.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

38

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0

36 38 39 40 42 44 47 51 55 58

180 225 250 280 295 375 430 525 635 775

K16 K18 K18 K18 K20 K20 K22 K22 K22 K24

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.46/0.66 0.44/0.62 0.42/0.60 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.49 0.32/0.48

0.14 0.16 0.17 0.18 0.20 0.22 0.24 0.26 0.29 0.32

0.8 1.0 1.0 1.1 1.2 1.3 1.4 1.6 1.7 1.9

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4

255 295 335 380 425 485 545 625 695 755

240 300 335 380 435 505 575 680 765 845

295 355 410 485 535 620 705 835 940 1035

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

39

www.drakauk.com 01332 345431

3 CORE
CU-XLPE-CWS-PE TRIPLEX 11 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round copper acc. to IEC 60228 class 22 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

40

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

17.6 19.3 20.6 22.2 23.8 26.1

27 29 30 32 34 36

59 63 65 69 74 78

375 450 540 645 750 915

500 500 500 500 500 500

K24 K24 K24 K26 K28 K28

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance mH/km Capacitance F/km Charging current/ phase A/km

0.268 0.193 0.153 0.124 0.0991 0.0754

0.542 0.542 0.542 0.542 0.542 0.542

0.40 0.38 0.36 0.35 0.34 0.33

0.27 0.31 0.33 0.36 0.40 0.44

1.1 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4

3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

255 295 335 380 425 485

240 300 335 380 425 505

295 355 410 485 535 620

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

41

www.drakauk.com 01332 345431

3 CORE
CU-XLPE-CWS-PE TRIPLEX 22 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

42

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

21.8 23.5 24.8 26.4 28.0 30.3

31 33 34 35 37 39

67 72 74 76 80 85

285 315 345 405 450 510

500 500 500 500 500 500

K26 K26 K26 K26 K28 K28

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance mH/km Capacitance F/km Charging current/ phase A/km

0.268 0.193 0.153 0.124 0.0991 0.0754

0.542 0.542 0.542 0.542 0.542 0.542

0.42 0.40 0.39 0.37 0.36 0.34

0.19 0.21 0.22 0.24 0.26 0.29

0.8 0.8 0.9 1.0 1.0 1.2

Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4

3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

255 295 335 380 425 485

240 300 335 380 425 505

295 355 410 485 535 620

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

43

www.drakauk.com 01332 345431

3 CORE
CU-XLPE-CWS-PE TRIPLEX 33 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 19/33 (36) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

44

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

26.8 28.5 29.8 31.4 33.0 35.3

36 38 39 40 42 44

78 82 85 87 91 95

540 675 750 840 885 1125

500 500 500 500 500 500

K28 K30 K30 K30 K30 K30

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance mH/km Capacitance F/km Charging current/ phase A/km

0.268 0.193 0.153 0.124 0.0991 0.0754

0.542 0.542 0.542 0.542 0.542 0.542

0.46 0.44 0.42 0.40 0.39 0.37

0.14 0.16 0.17 0.18 0.20 0.22

0.8 1.0 1.0 1.1 1.2 1.3

Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4

3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

255 295 335 380 425 485

240 300 335 380 425 505

295 355 410 485 535 620

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

45

www.drakauk.com 01332 345431

1 CORE
AL -XLPE-CWS-PE 11 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

46

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8

27 29 30 32 34 36 38 43 45 50

80 90 100 120 135 150 175 220 255 300

K14 K14 K14 K14 K16 K16 K18 K20 K20 K22

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.40/0.58 0.38/0.56 0.36/0.55 0.35/0.54 0.34/0.53 0.33/0.51 0.31/0.50 0.31/0.49 0.29/0.48 0.29/0.47

0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68

1.1 1.2 1.3 1.4 1.6 1.8 2.0 2.2 2.4 2.7

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

200 235 265 300 330 385 435 510 570 635

190 230 265 300 345 400 460 555 635 720

235 280 325 370 425 490 565 680 775 880

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

47

www.drakauk.com 01332 345431

1 CORE
AL -XLPE-CWS-PE 22 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

48

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

21.8 23.5 24.8 26.4 28.0 30.3 32.6 35.4 38.4 42.0

31 33 34 35 37 39 42 46 49 53

95 105 115 135 150 170 195 245 280 325

K14 K14 K14 K14 K16 K16 K18 K20 K20 K22

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.42/0.61 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.52 0.32/0.51 0.31/0.50 0.30/0.48

0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44

0.8 0.8 0.9 1.0 1.0 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

200 235 265 300 330 385 435 510 570 635

190 230 265 300 345 400 460 555 635 720

235 280 325 370 425 490 565 680 775 880

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

49

www.drakauk.com 01332 345431

1 CORE
AL -XLPE-CWS-PE 33 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-1.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black

50

Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35

Diameter over insulation mm

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m 500 500 500 500 500 500 500 500 500 500

Standard drum size

26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0

36 38 39 40 42 44 47 51 55 58

120 145 155 165 180 220 235 280 325 375

K16 K18 K18 K18 K20 K20 K22 K22 K22 K24

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469

0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542

0.46/0.66 0.44/0.62 0.42/0.60 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.49 0.32/0.48

0.14 0.16 0.17 0.18 0.20 0.22 0.24 0.26 0.29 0.32

0.8 1.0 1.0 1.1 1.2 1.3 1.4 1.6 1.7 1.9

Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5

200 235 265 300 330 385 435 510 570 635

190 230 265 300 345 400 460 555 635 720

235 280 325 370 425 490 565 680 775 880

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.

51

www.drakauk.com 01332 345431

3 CORE
AL-XLPE-CWS-PE TRIPLEX 11 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

52

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

17.6 19.3 20.6 22.2 23.8 26.1

27 29 30 32 34 36

59 63 65 69 74 78

240 270 300 360 405 450

500 500 500 500 500 500

K24 K24 K24 K26 K28 K28

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125

0.542 0.542 0.542 0.542 0.542 0.542

0.40 0.38 0.36 0.35 0.34 0.33

0.27 0.31 0.33 0.36 0.40 0.44

1.1 1.2 1.3 1.4 1.6 1.8

Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7

200 235 265 300 330 385

190 230 265 300 345 400

235 280 325 370 425 490

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

53

www.drakauk.com 01332 345431

3 CORE
AL-XLPE-CWS-PE TRIPLEX 22 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

54

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

21.8 23.5 24.8 26.4 28.0 30.3

31 33 34 35 37 39

67 72 74 76 80 85

285 315 345 405 450 510

500 500 500 500 500 500

K26 K26 K26 K26 K28 K28

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125

0.542 0.542 0.542 0.542 0.542 0.542

0.42 0.40 0.39 0.37 0.36 0.34

0.19 0.21 0.22 0.24 0.26 0.29

0.8 0.8 0.9 1.0 1.0 1.2

Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7

200 235 265 300 330 385

190 230 265 300 345 400

235 280 325 370 425 490

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

55

www.drakauk.com 01332 345431

3 CORE
AL-XLPE-CWS-PE TRIPLEX 33 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90 C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D

Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation

56

Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35

Diameter over insulation mm

Diameter over sheath (approx)

Overall diameter (approx.) mm

Weight (approx.) kg/100 m

Standard delivery length m

Standard drum size

26.8 28.5 29.8 31.4 33.0 35.3

36 38 39 40 42 44

78 82 85 87 91 95

360 435 465 495 540 660

500 500 500 500 500 500

K28 K30 K30 K30 K30 K30

Electrical data at +20 C


Number of cores x cross-section of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Conductor resistance /km Screen resistance /km Inductance in trefoil/in plane* mH/km Capacitance F/km Charging current/phase A/km

0.443 0.320 0.253 0.206 0.164 0.125

0.542 0.542 0.542 0.542 0.542 0.542

0.46 0.44 0.42 0.40 0.39 0.37

0.14 0.16 0.17 0.18 0.20 0.22

0.8 1.0 1.0 1.1 1.2 1.3

Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7

200 235 265 300 330 385

190 230 265 300 345 400

235 280 325 370 425 490

*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m

Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.

57

www.drakauk.com 01332 345431

THE WORLDS MOST TRUSTED CABLE BRAND


At Draka we work hard to drive standards of design and manufacture higher so that our customers can enjoy the benefits of products they can rely on, totally. If you share the same high standards, always specify the brand you can trust Draka.

Draka UK Limited, P.O. Box 6500, Alfreton Road, Derby, DE21 4ZH, UK Tel: +44 (0)1332 345431 Fax: +44 (0)1332 331237 email: cableuk@draka.com