(in applications such as rail networks, airports and major construction developments), our state-ofthe-art manufacturing techniques ensure the highest calibre cables and deliver unrivalled longevity and reliability. Added to the numerous industrial projects currently in progress throughout the UK, the energy network is
also being constantly refurbished, upgraded and maintained to cope with the increased electrical consumption. This has in turn created an increased demand for high quality medium voltage cables that will stand the test of time. Draka has the technical capability to meet this demand. Not only for the excellence of our products but also for the technical guidance and support that we offer. For the utilities sector, the range includes 11, 22 and 33 kV rated versions with solid aluminium or stranded copper cores, in both singles and triplex, normally with polyethylene outer sheaths. In addition to these variants, a stranded aluminium version is
available in singles. For the industrial sector, there are 11, 22 and 33 kV versions with PVC or Zero Halogen, Low Smoke (OHLS) sheathing with stranded copper or stranded aluminium conductors dependent on the application.
Drakas medium voltage product range has been developed with leading edge technology and is backed by the resources of one of the worlds major specialist cable companies. Draka Holding NV is an international cable manufacturer with a turnover of 2 billion Euros and 9,000 employees.
Potential Risks
One of the biggest threats to the effective performance of medium voltage cables are defects in the insulation system caused by gas voids or impurities during the insulation of the cable. The impact of these defects is magnified with increasing voltage as the electrical stresses increase and can lead to degradation of the insulation and in the end a breakdown of the cable. Given the vast volume of medium voltage cabling required in UK infrastructure, and the number of people, businesses and services that are totally reliant on a continued supply of power, any failings requiring replacement can be severe and bring major cost implications. The range is produced at the Nssj factory in Sweden which since Draka acquired the site from ABB in 1999, has seen huge investment as part of a major refurbishment and extension programme. It now has the very latest plant and equipment which means it can be classed amongst the worlds most advanced Medium Voltage manufacturing factories. Already the leading medium voltage supplier to the Scandinavian utilities market, Draka has established a proven pedigree in the development of high quality products which are built to last. It is of course to ISO14001 and ISO9001 certified.
Built to last
Through the sophistication of the manufacturing techniques involved, Draka medium voltage cable limits the exposure to impurities during the compound handling process in production and as a result, its durability is unrivalled.
CLEAN MANUFACTURIN
1 Fundamental to the development of high quality, trusted medium voltage cable at Drakas facility in Sweden has been the introduction of R3 technology including clean rooms and closed systems for materials handling processes usually reserved for high voltage cable manufacture. Here, the crucial areas of the factory are contamination-controlled to eradicate the risk of environmental pollutants such as dust, airborne microbes, aerosol particles and chemical vapours from jeopardising the purity of the cable construction.
Extruder platform
Drum take up
Curing Line
Capstan
1 CORE ARMOURED
CU-XLPE 11 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
10
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
16.0 17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8
1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5
30 32 35 36 38 40 42 46 50 53 57
140 160 210 240 270 220 380 480 570 690 840
0.43 0.40 0.38 0.37 0.36 0.35 0.33 0.32 0.31 0.30 0.29
0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68
0.14 0.13 0.12 0.12 0.11 0.11 0.10 0.10 0.10 0.09 0.09
0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.1 1.2 1.4
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4
205 255 295 335 380 425 485 545 625 695 755
205 240 300 335 380 435 505 575 680 765 845
250 295 355 410 485 535 620 705 835 940 1035
*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
11
1 CORE ARMOURED
CU-XLPE 22 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
12
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
18.2 19.8 21.5 22.8 24.4 26.0 28.3 30.6 33.4 36.4 40.0
1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5
36 38 39 41 42 44 48 50 54 58 62
170 200 240 300 350 440 510 610 730 890 1080
0.46 0.43 0.41 0.40 0.38 0.37 0.36 0.34 0.33 0.32 0.31
0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44
0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10
0.3 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4
205 255 295 335 380 425 485 545 625 695 755
205 240 300 335 380 435 505 575 680 765 845
250 295 355 410 485 535 620 705 835 940 1035
Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.
13
1 CORE ARMOURED
CU-XLPE 33 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
14
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
25.2 26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0
2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5
42 44 47 48 50 52 54 57 61 64 69
210 240 300 340 380 420 490 580 680 800 960
0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283
0.494 0.343 0.248 0.196 0.159 0.128 0.098 0.080 0.064 0.051 0.042
0.46 0.45 0.44 0.42 0.41 0.40 0.38 0.37 0.35 0.34 0.33
0.16 0.18 0.21 0.23 0.25 0.27 0.229 0.32 0.36 0.40 0.44
0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.10
0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.8
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.8 11.0 14.9 18.9 23.6 29.1 47.2 46.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 43.0 43.0 57.4 71.7 90.4
205 255 295 335 380 425 485 545 625 695 755
205 240 300 335 380 435 505 575 680 765 845
250 295 355 410 485 535 620 705 835 940 1035
*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
15
3 CORE ARMOURED
CU-XLPE 11 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
16
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300
54 58 62 67 69 73 82 86
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3 42.9
*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
17
3 CORE ARMOURED
CU-XLPE 22 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under the copper tape Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
18
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300
64 68 74 77 80 84 88 95
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3 42.9
Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
19
3 CORE ARMOURED
CU-XLPE 33 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
20
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240
83 87 90 92 94 97 101
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 7.1 10.0 13.6 17.2 21.5 26.5 34.3
3x50 3x70 3x95 3x120 3x150 3x185 3x240 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
21
1 CORE ARMOURED
AL -XLPE 11 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
22
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
16.0 17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8
1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.5 2.5
30 32 35 36 38 40 42 46 50 53 57
110 120 150 170 180 210 240 280 330 380 440
0.43 0.40 0.38 0.37 0.36 0.35 0.33 0.32 0.31 0.30 0.29
0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68
0.14 0.13 0.12 0.12 0.11 0.11 0.10 0.10 0.10 0.09 0.09
0.5 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.1 1.2 1.4
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
155 200 235 265 300 330 385 435 510 570 635
160 190 230 265 300 345 400 460 555 635 720
195 235 280 325 370 425 490 565 680 775 880
*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.
23
1 CORE ARMOURED
AL -XLPE 22 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
24
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
18.2 19.8 21.5 22.8 24.4 26.0 28.3 30.6 33.4 36.4 40.0
1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5
36 38 39 41 42 44 48 50 54 58 62
140 160 180 200 210 240 290 320 370 420 490
0.46 0.43 0.41 0.40 0.38 0.37 0.36 0.34 0.33 0.32 0.31
0.17 0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44
0.15 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.11 0.10
0.3 0.4 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
155 200 235 265 300 330 385 435 510 570 635
160 190 230 265 300 345 400 460 555 635 720
195 235 280 325 370 425 490 565 680 775 880
Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.
25
1 CORE ARMOURED
AL -XLPE 33 kV
Application fields 1-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Metallic screen Metallic layer, copper tape Inner sheath PVC or PE, black Armour Galvanized aluminium wires Outer sheath PVC or halogen free compound, red or black
26
Number of cores x cross-section of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630
25.2 26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0
2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5
42 44 47 48 50 52 54 57 61 64 69
180 200 240 260 290 310 340 380 440 490 560
0.46 0.45 0.44 0.42 0.41 0.40 0.38 0.37 0.35 0.34 0.33
0.16 0.18 0.21 0.23 0.25 0.27 0.229 0.32 0.36 0.40 0.44
0.15 0.14 0.14 0.13 0.13 0.13 0.12 0.12 0.11 0.11 0.10
0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.6 1.8
Current rating
Number of cores x crosssection of conductor mm2 1x50 1x70 1x95 1x120 1x150 1x185 1x240 1x300 1x400 1x500 1x630 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 5.2 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
155 200 235 265 300 330 385 435 510 570 635
160 190 230 265 300 345 400 460 555 635 720
195 235 280 325 370 425 490 565 680 775 880
*Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Trefoil grounded at both ends. Nominal values unless otherwise specified.
27
3 CORE ARMOURED
AL -XLPE 11 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 6.35/11 (12) kV Impulse voltage 95 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 3.4 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
28
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300
54 58 62 67 69 73 82 86
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3
3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
29
3 CORE ARMOURED
AL -XLPE 22 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 12.7/22 (24) kV Impulse voltage 144 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 5.5 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under the copper tape Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
30
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300
64 68 74 77 80 84 88 95
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3
3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
31
3 CORE ARMOURED
AL -XLPE 33 kV
Application fields 3-core armoured power cable. Standard BS6622/BS7835 Rated voltage 19/33 (36) kV Impulse voltage 194 kV Fire propagation class BS EN 50266-2-4. Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Bending radius At laying: 12 x D. When installed: 8 x D D = Overall diameter of cable
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nominal thickness = 8.0 mm Insulation screen Extruded, bonded or strippable Core identification coloured phasetape under screen Metallic screen Metallic layer, copper tape, over each individual core Filler PP yarn Inner sheath PVC or PE, black Armour Galvanized steel wires Outer sheath PVC or halogen free compound, red or black
32
Number of cores x cross-section of conductor mm2 3x50 3x70 3x95 3x120 3x150 3x185 3x240
83 87 90 92 94 97 101
Current rating
Number of cores x crosssection of conductor mm2 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 4.7 6.6 8.9 11.3 14.2 17.5 22.7 28.3
3x50 3x70 3x95 3x120 3x150 3x185 3x240 3x300 *Installation conditions Ground temperature: 15C Depth of laying: 0.65 m Ground resistivity: 1.0 m x K/W
Air temperature 25C Screen grounded at both ends. Nominal values unless otherwise specified.
33
1 CORE
CU-XLPE-CWS-PE 11 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
34
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8
27 29 30 32 34 36 38 43 45 50
125 150 180 215 250 305 370 465 565 700
K14 K14 K14 K14 K16 K16 K18 K20 K20 K22
0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.40/0.58 0.38/0.56 0.36/0.55 0.35/0.54 0.34/0.53 0.33/0.51 0.31/0.50 0.31/0.49 0.29/0.48 0.29/0.47
0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68
1.1 1.2 1.3 1.4 1.6 1.8 2.0 2.2 2.4 2.7
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4
255 295 335 380 425 485 545 625 695 755
240 300 335 380 435 505 575 680 765 845
295 355 410 485 535 620 705 835 940 1035
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
35
1 CORE
CU-XLPE-CWS-PE 22 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
36
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
21.8 23.5 24.8 26.4 28.0 30.3 32.6 35.4 38.4 42.0
31 33 34 35 37 39 42 46 49 53
140 165 195 230 265 325 390 490 590 725
K14 K14 K14 K14 K16 K16 K18 K20 K20 K22
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.42/0.61 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.52 0.32/0.51 0.31/0.50 0.30/0.48
0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44
0.8 0.8 0.9 1.0 1.0 1.2 1.3 1.4 1.6 1.8
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4
255 295 335 380 425 485 545 625 695 755
240 300 335 380 435 505 575 680 765 845
295 355 410 485 535 620 705 835 940 1035
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
37
1 CORE
CU-XLPE-CWS-PE 33 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-1.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -10C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
38
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0
36 38 39 40 42 44 47 51 55 58
180 225 250 280 295 375 430 525 635 775
K16 K18 K18 K18 K20 K20 K22 K22 K22 K24
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.46/0.66 0.44/0.62 0.42/0.60 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.49 0.32/0.48
0.14 0.16 0.17 0.18 0.20 0.22 0.24 0.26 0.29 0.32
0.8 1.0 1.0 1.1 1.2 1.3 1.4 1.6 1.7 1.9
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 11.0 14.9 18.9 23.6 29.1 37.7 47.2 62.9 78.7 99.1 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 10.0 13.6 17.2 21.5 26.5 34.4 43.0 57.4 71.2 90.4
255 295 335 380 425 485 545 625 695 755
240 300 335 380 435 505 575 680 765 845
295 355 410 485 535 620 705 835 940 1035
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
39
3 CORE
CU-XLPE-CWS-PE TRIPLEX 11 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round copper acc. to IEC 60228 class 22 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
40
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
27 29 30 32 34 36
59 63 65 69 74 78
Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
41
3 CORE
CU-XLPE-CWS-PE TRIPLEX 22 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
42
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
31 33 34 35 37 39
67 72 74 76 80 85
Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
43
3 CORE
CU-XLPE-CWS-PE TRIPLEX 33 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 19/33 (36) kV Fire propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round copper acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
44
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
36 38 39 40 42 44
78 82 85 87 91 95
Current rating
Number of cores x cross-section of conductor mm2 Current rating at core temp. 65 C in ground A Current rating at core temp. 65 C in air A Current rating at core temp. 90 C in air A Max. short-circuit Max. short-circuit current on the current on the conductor during 1 s conductor during 1 at initial temp. s at initial 65 C kA temp. 90 C kA 11.0 14.9 18.9 23.6 29.1 37.7 10.0 13.6 17.2 21.5 26.5 34.4
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
45
1 CORE
AL -XLPE-CWS-PE 11 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
46
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
17.6 19.3 20.6 22.2 23.8 26.1 28.4 31.2 34.2 37.8
27 29 30 32 34 36 38 43 45 50
K14 K14 K14 K14 K16 K16 K18 K20 K20 K22
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.40/0.58 0.38/0.56 0.36/0.55 0.35/0.54 0.34/0.53 0.33/0.51 0.31/0.50 0.31/0.49 0.29/0.48 0.29/0.47
0.27 0.31 0.33 0.36 0.40 0.44 0.49 0.55 0.60 0.68
1.1 1.2 1.3 1.4 1.6 1.8 2.0 2.2 2.4 2.7
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
200 235 265 300 330 385 435 510 570 635
190 230 265 300 345 400 460 555 635 720
235 280 325 370 425 490 565 680 775 880
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
47
1 CORE
AL -XLPE-CWS-PE 22 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
48
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
21.8 23.5 24.8 26.4 28.0 30.3 32.6 35.4 38.4 42.0
31 33 34 35 37 39 42 46 49 53
K14 K14 K14 K14 K16 K16 K18 K20 K20 K22
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.42/0.61 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.52 0.32/0.51 0.31/0.50 0.30/0.48
0.19 0.21 0.22 0.24 0.26 0.29 0.32 0.36 0.39 0.44
0.8 0.8 0.9 1.0 1.0 1.2 1.3 1.4 1.6 1.8
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
200 235 265 300 330 385 435 510 570 635
190 230 265 300 345 400 460 555 635 720
235 280 325 370 425 490 565 680 775 880
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
49
1 CORE
AL -XLPE-CWS-PE 33 kV
Application fields Single-core, distribution cable for outdoors use in 3-phase formation. Installation in pipes and ground/water. Standard BS 7870-1.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Stranded, round and compacted aluminium acc. to IEC 60228 class 2 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black
50
Number of cores x cross-section of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35
Standard delivery length m 500 500 500 500 500 500 500 500 500 500
26.8 28.5 29.8 31.4 33.0 35.3 37.6 40.4 43.4 47.0
36 38 39 40 42 44 47 51 55 58
120 145 155 165 180 220 235 280 325 375
K16 K18 K18 K18 K20 K20 K22 K22 K22 K24
0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 0.0605 0.0469
0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542 0.542
0.46/0.66 0.44/0.62 0.42/0.60 0.40/0.59 0.39/0.57 0.37/0.55 0.36/0.54 0.34/0.53 0.33/0.49 0.32/0.48
0.14 0.16 0.17 0.18 0.20 0.22 0.24 0.26 0.29 0.32
0.8 1.0 1.0 1.1 1.2 1.3 1.4 1.6 1.7 1.9
Current rating
Number of cores x crosssection of conductor mm2 1x70/35 1x95/35 1x120/35 1x150/35 1x185/35 1x240/35 1x300/35 1x400/35 1x500/35 1x630/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 31.2 41.6 52.0 65.6 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7 28.3 37.8 47.2 59.5
200 235 265 300 330 385 435 510 570 635
190 230 265 300 345 400 460 555 635 720
235 280 325 370 425 490 565 680 775 880
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Trefoil with screen grounded at both ends Nominal values unless otherwise specified.
51
3 CORE
AL-XLPE-CWS-PE TRIPLEX 11 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 6.35/11 (12) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during installation: -20C. Below 0C special precautions must be taken. Impulse voltage 95 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 3.4 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
52
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
27 29 30 32 34 36
59 63 65 69 74 78
Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
53
3 CORE
AL-XLPE-CWS-PE TRIPLEX 22 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 12.7/22 (24) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 144 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 5.5 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
54
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
31 33 34 35 37 39
67 72 74 76 80 85
Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
55
3 CORE
AL-XLPE-CWS-PE TRIPLEX 33 kV
Application fields 3-core cable. distribution cable for outdoors use. Installation in pipes and ground. Standard BS 7870-4.10 Rated voltage 19/33 (36) kV Flame propagation class The PE sheath is not flame-retardant Temperature range In continuous operation max. conductor temp 90 C. Lowest cable temperature during laying -20C. Below 0C special precautions must be taken. Impulse voltage 194 kV Bending radius At fixed mounting: 10 x D. At laying: 15 x D
Design
Conductor Solid, round aluminium acc. to IEC 60228 class 1 Conductor screen Extruded Insulation XLPE, nom. thickness = 8.0 mm Insulation screen Extruded bonded Concentric conductor Annealed copper wires Sheath MDPE, black Laying up Three stranded single-core cables in triplex formation
56
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35
36 38 39 40 42 44
78 82 85 87 91 95
Current rating
Number of cores x crosssection of conductor mm2 3x1x70/35 3x1x95/35 3x1x120/35 3x1x150/35 3x1x185/35 3x1x240/35 Current rating at core temp. 65 C in ground* A Current rating at core temp. 65 C in air* A Current rating at core temp. 90 C in air* A Max. short-circuit current on the conductor during 1 s at initial temp. 65 C kA 7.2 9.9 12.4 15.6 19.2 25.0 Max. short-circuit current on the conductor during 1 s at initial temp. 90 C kA 6.6 8.9 11.3 14.2 17.5 22.7
*Current ratings conditions Ambient temperature air: 25C Ground temperature: 15C Depth of burial: 0.7 m
Thermal resistance of soil: 1.0 Km/W Screen grounded at both ends. Nominal values unless otherwise specified.
57