Вы находитесь на странице: 1из 177

EERL 2005-01 Earthquake Engineering Research Laboratory

Performance of 18-Story Steel Moment-Frame Buildings During a Large San Andreas Earthquake A Southern California-Wide End-to-End Simulation

by

Swaminathan Krishnan, Chen Ji, Dimitri Komatitsch, and Jeroen Tromp


This study was conducted at the Seismological Laboratory

ST

IT U T E O F
T
EC

IF O R NIA

HNOLOG

1891

AL

California Institute of Technology Pasadena, California 2005

ii

c 2005 Swaminathan Krishnan, Chen Ji, Dimitri Komatitsch, and Jeroen Tromp All Rights Reserved

iii

Acknowledgements
We wish to gratefully acknowledge the funding provided by the Seismological Laboratory at the California Institute of Technology. We also wish to thank Professors John F. Hall, Thomas Heaton, and Hiroo Kanamori of the California Institute of Technology for their insights and advice during the course of this study. The numerical simulations were performed on the Division of Geological & Planetary Sciences Dell cluster at the California Institute of Technology, USA, and the Seawulf cluster at the University of Toronto, Canada.

iv

Summary
The mitigation of seismic risk in urban areas in the United States and abroad is of major concern for all governments. Unfortunately no comprehensive studies have attempted to address this issue in a rigorous, quantitative manner. This study tackles this problem head-on for two 18-story steel moment-frame buildings in southern California. The approach adopted here can be used as a template to study earthquake risk in other seismically sensitive regions of the world, such as Taiwan, Japan, Indonesia, China, South American countries (Chile, Bolivia, etc.), and the west coast of the United States (in particular, Seattle). In 1857 a large earthquake of magnitude 7.9 [1] occurred on the San Andreas fault with rupture initiating at Parkeld in Central California and propagating in a southeasterly direction over a distance of more than 360 km. Such a unilateral rupture produces signicant directivity toward the San Fernando and Los Angeles basins. Indeed, newspaper reports (Los Angeles Star [2, 3]) of sloshing observed in the Los Angeles river point to long-duration (12 min) and long-period (28 s) shaking which could have a severe impact on present-day tall buildings, especially in the mid-height range. To assess the risk posing the two steel moment-frame buildings from an 1857-like earthquake on the San Andreas fault, a nite source model of the magnitude 7.9 November 3, 2002 Denali fault earthquake is mapped on to the San Andreas fault with rupture initiating at Parkeld in Central California and propagating a distance of about 290 km in a south-easterly direction. As the rupture proceeds down south from Parkeld and hits the big bend on the San Andreas fault it sheds off a signicant amount of energy into the San Fernando valley, generating large amplitude ground motion there. A good portion of this energy spills over into the Los Angeles basin with many cities along the coast such as Santa Monica and Seal Beach and more inland areas going east from Seal beach towards Anaheim experiencing long-duration shaking. In addition, the tail-end of the rupture sheds energy from SH/Love waves into the San Gabriel valley (Baldwin Park-La Puente region). These seismic waves get trapped and amplied in the basin. The peak velocity is of the order of 1 m.s1 in the Los Angeles basin, including downtown Los Angeles, and 2 m.s 1 in the San Fernando valley. Signicant displacements occur in the basins but not in the mountains. The peak displacements are in the neighborhood of 1 m in the Los Angeles basin and 2 m in the San Fernando valley. The ground motion simulation is performed using the spectral element method based seismic wave propagation program, SPECFEM3D. To study the effects of the ground motion simulated at 636 sites (spread across southern California, spaced at about 3.5 km each way), computer models of an existing 18-story steel moment-frame building and a redesigned building with the same conguration (redesigned to current standards using the 1997 Uniform Building Code) are analyzed using the nonlinear structural analysis program, FRAME3D. For these analyses, the building Y direction is aligned with the geographical north direction. As expected, the existing building model fares much worse than the redesigned building model. Fracture occurs in at least 25% of the connections in this building when located in the San Fernando valley. About 10% of connections fracture in the building when located in downtown Los Angeles and the mid-Wilshire district (Beverly Hills), while the numbers are about 20% when it is located in Santa Monica, west Los Angeles, Inglewood , Alhambra, Baldwin Park, La Puente, Downey, Norwalk, Brea, Fullerton, Anaheim and Seal Beach. The peak interstory drifts in the middle-third and bottom-third of the existing building are far greater than the top-third pointing to damage being localized to the lower oors. The localization of damage in the lower oors rather than the upper oors could potentially be worse because of the risk of more oors pancaking on top of each other if a single story gives way. Consistent with the extent of fracture observed, the peak drifts in the existing building exceed 0.10 when located in the San Fernando valley, Baldwin Park and neighboring cities, Santa Monica, west Los Angeles and neighboring cities, Norwalk and neighboring cities, and Seal Beach and neighboring cities, which is well into the postulated collapse regime. When located in downtown Los Angeles and the mid-Wilshire district, the building would

v barely satisfy the collapse prevention criteria set by FEMA [4] with peak drifts of about 0.05. The performance of the newly designed 18-story steel building is signicantly better than the existing building for the entire region. However, the new building still has signicant drifts indicative of serious damage when located in the San Fernando valley or the Baldwin Park area. When located in coastal cities (such as Santa Monica, Seal Beach etc.), the Wilshire-corridor (west Los Angeles, Beverly Hills, etc.), Norwalk and neighboring cities, or the booming Orange County cities of Anaheim and Santa Ana, it has peak drifts of about 0.05 once again barely satisfying the FEMA collapse prevention criteria [5]. In downtown Los Angeles it does not undergo much damage in this scenario. Thus, even though this building has been designed according to the latest code it suffers damage that would necessitate closure for some time following the earthquake in most areas, but this should be expected since this is a large earthquake and building codes are written to limit the loss of life and ensure collapse prevention for such large earthquakes and not necessarily limit damage. A second scenario considered in the study involves the same Denali earthquake source mapped to the San Andreas fault but with rupture initiating in the south and propagating to the north (with the largest amount of slip occurring to the north in Central California) instead of the other way around. The results of such a scenario indicate that ground shaking would be far less severe demonstrating the effects of directivity and slip distribution in dictating the level of ground shaking and the associated damage in buildings. The peak drifts in existing and redesigned building models are in the range of 0.020.04 indicating that there is no signicant danger of collapse. However, damage would still be signicant enough to warrant building closures and compromise life safety in some instances. The ground motion simulation and the structural damage modeling procedures are validated using data from the January 17, 1994, Northridge earthquake while the band-limited nature of the ground motion simulation (limited to a shortest period of 2 s by the current state of knowledge of the 3-D Earth structure) is shown to have no signicant effect on the response of the two tall buildings considered here with the use of observed records from the 1999 Chi Chi earthquake in Taiwan and the 2001 Tokachi-Oki earthquake in Japan.

vi

Contents
Acknowledgements Summary 1 Introduction 1.1 Scope of the Simulation . . . . . 1.1.1 Scenarios Considered . . 1.1.2 Buildings Considered . . 1.1.3 End-to-End Simulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii iv 1 2 2 2 3 4 4 4 5 5 9 11 14 14 15 20 20 20 23 25 32 37 38 44 58 70 72

2 Building Details 2.1 Existing Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Redesigned (New) Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Gravity Loading Criteria for the Two Buildings . . . . . . . . . . . . . . . . . . 2.4 Seismic Criteria for the Design of the New Building . . . . . . . . . . . . . . . . 2.5 Wind Criteria for the Design of the New Building . . . . . . . . . . . . . . . . . 2.6 Design of the New Building per UBC97 Using the Commercial Program ETABS 2.7 Nonlinear Analysis of Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . 2.7.1 Analysis Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.7.2 Pushover Analyses of the Two Buildings . . . . . . . . . . . . . . . . .

3 Software Used for the End-to-End Simulations 3.1 SPECFEM3D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 FRAME3D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Limitations of the Study 5 Validation Using the Northridge Earthquake Data 6 Effect of Filtering Records on Building Analyses 7 Past Earthquakes on the San Andreas Fault 8 Source Model Used in the Simulation of the Magnitude 7.9 Earthquakes on the San Andreas Fault 9 Scenario 1: North-to-South Rupture of the San Andreas Fault 10 Scenario 2: South-to-North Rupture of the San Andreas Fault 11 Conclusions 12 Future Research

vii A Section Database B Existing Building Frame Elevations and Beam and Column Sizes C Redesigned Building Frame Elevations and Beam and Column Sizes 73 74 81

D Scenario 1 (North-to-South Rupture): Performance of Existing and Redesigned Building Models Based on Plastic Rotations in Beams and Panel Zones 91 E Scenario 2 (South-to-North Rupture): Performance of Existing and Redesigned Building Models Based on Plastic Rotations in Beams and Panel Zones 95 F Details of the Performance of Existing and Redesigned Building Models in 8 Southern Californian Cities 99 F.1 Site: Thousand Oaks (Latitude 34.18750, Longitude 118.87500) . . . . . . . . . . . . . . . . . . . . 100 F.1.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 F.1.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 F.2 Site: Northridge (Latitude 34.21875, Longitude 118.53125) . . . . . . . . . . . . . . . . . . . . . . . 107 F.2.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 F.2.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 F.3 Site: West Los Angeles (Latitude 34.03125, Longitude 118.40625) . . . . . . . . . . . . . . . . . . . 114 F.3.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 F.3.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 F.4 Site: Downtown Los Angeles (Latitude 34.06250, Longitude 118.25000) . . . . . . . . . . . . . . . . 121 F.4.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122 F.4.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 F.5 Site: Baldwin Park (Latitude 34.09375, Longitude 118.00000) . . . . . . . . . . . . . . . . . . . . . 128 F.5.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129 F.5.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132 F.6 Site: Anaheim (Latitude 33.84375, Longitude 117.90625) . . . . . . . . . . . . . . . . . . . . . . . . 135 F.6.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 F.6.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139 F.7 Site: Long Beach (Latitude 33.78125, Longitude 118.18750) . . . . . . . . . . . . . . . . . . . . . . 142 F.7.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 F.7.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 F.8 Site: Santa Ana (Latitude 33.75000, Longitude 117.87500) . . . . . . . . . . . . . . . . . . . . . . . 149 F.8.1 Existing Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 F.8.2 Redesigned Building Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

viii

List of Figures
1.1 Geographical scope of the simulation (The color scheme reects topography, with green denoting low elevation and yellow denoting mountains): The solid black triangles denote the 636 sites at which seismograms are computed and buildings are analyzed. The white box is the surface projection of the Northridge fault. The red line in the inset is the surface trace of the 290 km rupture of the San Andreas fault that is the primary focus of this study. The area enclosed by the blue polygon denotes the region covered by the 636 sites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Structural models of buildings studied: [A] Perspective view of existing building (designed using codes prior to the 1997 Uniform Building Code). [B] Perspective view of redesigned (new) building (redesigned using the 1997 Uniform Building Code). . . . . . . . . . . . . . . . . . . . . . . . . . . Plans of the existing building showing the location of columns and moment-frame (MF) beams (the frame elevations with beam and column sizes are given in Appendix B). . . . . . . . . . . . . . . . . Plans of the redesigned building showing the location of columns and moment-frame (MF) beams (the frame elevations with beam and column sizes are given in Appendix C). Note the greater number of moment-frame bays in the redesigned building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The 1997 Uniform Building Code response spectrum used in the design of the new building (C a = 0.48 and Cv = 0.64). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pushover analysis of the existing and the redesigned buildings: (A) X direction pushover roof displacement versus base shear. (B) X direction pushover base shear (solid lines) and roof displacements (dashed lines) as functions of time. (C) Y direction pushover roof displacement versus base shear. (D) Y direction pushover base shear (solid lines) and roof displacements (dashed lines) as functions of time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Element arrangement in frame model showing joint nodes, attachment points, local beam nodes and coordinate systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Slip model for the January 17, 1994, magnitude 6.7 Northridge earthquake determined using a wavelet transform approach. The red star denotes the hypocenter and the white arrows denote the slip vector. The dip angle of the fault is 40 degrees (see Figure 1.1 for the surface projection of the fault) . . . . . Northridge simulation Data versus synthetic seismograms: (A) nearby stations north of the rupture; (B) distant stations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Northridge validation analysis of existing building in Woodland Hills subjected to Oxnard Blvd. record (WHOX): Measured 18th oor (A) N-S and (B) E-W displacements versus corresponding computed displacements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analysis of the existing building subjected to the Oxnard Boulevard, Woodland Hills (WHOX) record from Northridge earthquake (station located 0.5 mile from the building): Observed connection fractures (squares) versus simulated fractures (solid triangles) (A) South moment-frame (along grid A, east-west direction) of the building (Frame 1); (B) North moment-frame (along grid D, east-west direction) of the building (Frame 4); (C) West moment-frame (along grid 1, north-south direction) of the building (Frame 6); (D) East moment-frame (along grid 6, north-south direction) of the building (Frame 7). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1

5 6

2.2 2.3

7 10

2.4 2.5

19

3.1 5.1

22

25 26

5.2 5.3

28

5.4

29

ix 5.5 5.6 6.1 6.2 6.3 6.4 8.1 Comparison of the horizontal components of velocity of three records from the 1994 Northridge earthquake, SATI, CNPK, and WHOX (Source: URS Corporation). . . . . . . . . . . . . . . . . . . . . . Permanent offsets on the four faces of the existing building model (penthouse plan shown here) computed using the WHOX record from the Northridge earthquake. . . . . . . . . . . . . . . . . . . . . . Pseudo-acceleration response spectra of records (north component) from the Chi-Chi and Tokachi-Oki earthquakes: Comparison of spectra of unltered (solid) and ltered (dashed) records. . . . . . . . . . Pseudo-acceleration response spectra of records (east component) from the Chi-Chi and Tokachi-Oki earthquakes: Comparison of spectra of unltered (solid) and ltered (dashed) records. . . . . . . . . . Peak drifts observed in the existing building analyses using ltered and unltered records. Pen colors used to plot the points match those used in Figures 6.1 and 6.2. . . . . . . . . . . . . . . . . . . . . . Peak drifts observed in the redesigned building analyses using ltered and unltered records. Pen colors used to plot the points match those used in Figures 6.1 and 6.2. . . . . . . . . . . . . . . . . . Slip distribution of the 2002 Denali earthquake constrained by teleseismic body and strong motion waveforms as well as GPS vectors. The color scheme reects the slip amplitude and contours reect the rupture initiation time. The hypocenter is indicated by the red star. White arrows denote the slip direction and magnitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault north-to-south rupture. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault north-to-south rupture, capped particle velocity case. . . . . . . . . . . . . . . . . . . 1999 ChiChi earthquake: Peak ground velocities. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Denali source inversion: Data (black) versus synthetic seismograms (red) for Pump Station 10 (3 km from the fault trace). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 31 33 34 35 36

38 39 40 42 43 47 48 48 49 49 50 51 52 52 53

8.2 8.3 8.4 8.5 9.1

Mw 7.9 earthquake (north-to-south rupture) on the San Andreas Fault ground shaking: Map of peak velocities (east component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.2 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak velocities (north component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.3 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak velocities (vertical component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.4 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (east component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.5 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (north component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.6 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (vertical component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.7 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the top-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.8 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the middle-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.9 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the bottom-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.10 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios anywhere in the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

x 9.11 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Permanent offset at the penthouse level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.12 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections that fracture (out of a total of 710 connections with the two ends of each moment-frame beam and column dened as connections). . . . . . . . . . . . . . . . . . . . . . . . . 9.13 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the top-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . 9.14 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the middle-third of the building. . . . . . . . . . . . . . . . . . . . . . . . 9.15 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the bottom-third of the building. . . . . . . . . . . . . . . . . . . . . . . . 9.16 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault Redesigned Building Performance: Peak drift ratios anywhere in the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.17 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas Fault redesigned building performance: Permanent offset at the penthouse level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1 Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault south-to-north rupture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.2 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (east component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.3 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (north component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.4 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (vertical component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.5 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (east component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.6 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (north component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.7 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (vertical component). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.8 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the top-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.9 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the middle-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.10Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the bottom-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.11Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios anywhere in the building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.12Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Permanent offset at the penthouse level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.13Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections that fracture (out of a total of 710 connections with the two ends of each moment-frame beam and column dened as connections). . . . . . . . . . . . . . . . . . . . . . . . . 10.14Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the top-third of the building. . . . . . . . . . . . . . . . . . . . . . . . . . 53

54 55 55 56 56 57 59 60 60 61 61 62 62 63 64 64 65 65

66 67

xi 10.15Mw 7.9 earthquake (south-to-north rupture) on the San Andreas mance: Peak drift ratios in the middle-third of the building. . . . 10.16Mw 7.9 earthquake (south-to-north rupture) on the San Andreas mance: Peak drift ratios in the bottom-third of the building. . . . 10.17Mw 7.9 earthquake (south-to-north rupture) on the San Andreas mance: Peak drift ratios anywhere in the building. . . . . . . . . 10.18Mw 7.9 earthquake (south-to-north rupture) on the San Andreas mance: Permanent offset at the penthouse level. . . . . . . . . . B.1 B.2 B.3 B.4 B.5 B.6 C.1 C.2 C.3 C.4 C.5 C.6 C.7 C.8 C.9 Frame 1 elevation: Existing building Frame 2 elevation: Existing building Frame 3 elevation: Existing building Frame 4 elevation: Existing building Frame 5 elevation: Existing building Frame 6 elevation: Existing building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . fault . . . fault . . . fault . . . fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . redesigned building perfor. . . . . . . . . . . . . . . . . redesigned building perfor. . . . . . . . . . . . . . . . . redesigned building perfor. . . . . . . . . . . . . . . . . redesigned building perfor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 68 68 69 75 76 77 78 79 80 82 83 84 85 86 87 88 89 90

Frame 1 elevation: Redesigned building Frame 2 elevation: Redesigned building Frame 3 elevation: Redesigned building Frame 4 elevation: Redesigned building Frame 5 elevation: Redesigned building Frame 6 elevation: Redesigned building Frame 7 elevation: Redesigned building Frame 8 elevation: Redesigned building Frame 9 elevation: Redesigned building

D.1 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D.2 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level. . . . D.3 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level. D.4 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D.5 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D.6 Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E.1 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

91 92 92

93

93

94

95

xii E.2 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level. . . . E.3 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level. E.4 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E.5 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E.6 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.1 Mw 7.9 earthquake (south-to north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Thousand Oaks. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpassltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Thousand Oaks (the drift scale is saturated at 0.10). . . . . . . . . . . . . . . . . . . . . . Plastic rotation in percent of a radian in the moment-frames of the existing building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (eastwest direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . . Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Momentframe along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Thousand Oaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Thousand Oaks (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Northridge. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 96

97

97

98

100 101

F.2 F.3

102

F.4

103 104

F.5 F.6

105

F.7

106

F.8

107

xiii F.9 F.10 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Northridge (the drift scale is saturated at 0.10). . . . . . . . . . . . . . . . . . . . . . . . 108 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . . . 109 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . 110 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Northridge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . . 112 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Northridge (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . 113 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): West Los Angeles. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpassltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: West Los Angeles (the drift scale is saturated at 0.10). . . . . . . . . . . . . . . . . . . . 115 Plastic rotation in percent of a radian in the moment-frames of the existing building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . 116 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Momentframe along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . 117 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: West Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . 119 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: West Los Angeles (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . 120

F.11

F.12 F.13

F.14

F.15

F.16 F.17

F.18

F.19 F.20

F.21

xiv F.22 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Downtown Los Angeles. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . F.23 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Downtown Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.24 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . F.25 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Momentframe along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . F.26 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Downtown Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.27 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . F.28 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Downtown Los Angeles (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Momentframe along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . F.29 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Baldwin Park. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.30 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Baldwin Park (the drift scale is saturated at 0.10). . . . . . . . . . . . . . . . . . . . . . . F.31 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (eastwest direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . . F.32 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . F.33 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Baldwin Park. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

121 122

123

124 125

126

127

128 129

130

131 132

xv F.34 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (eastwest direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . F.35 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Baldwin Park (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (northsouth direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . F.36 Mw 7.9 earthquake south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Anaheim. Also shown are the timehistories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.37 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Anaheim (the drift scale is saturated at 0.10). . . . . . . . . . . . . . . . . . . . . . . . . F.38 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . . . F.39 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . F.40 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Anaheim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.41 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (eastwest direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . F.42 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Anaheim (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (northsouth direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . F.43 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Long Beach. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.44 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Long Beach. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.45 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (eastwest direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . .

133

134

135 136

137

138 139

140

141

142 143

144

xvi F.46 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . F.47 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Long Beach. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.48 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (eastwest direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . F.49 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Long Beach (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . F.50 Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Santa Ana. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.51 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Santa Ana. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.52 Plastic rotation in percent of a radian in the moment-frames of the existing building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . . . . . . . . F.53 Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration. . . . . . . . . . F.54 Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Santa Ana. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.55 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (eastwest direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . . . . . . F.56 Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Santa Ana (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (northsouth direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration. . . . . . . . . . . . .

145 146

147

148

149 150

151

152 153

154

155

xvii

List of Tables
2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 F.1 F.2 F.3 F.4 F.5 F.6 F.7 F.8 F.9 F.10 F.11 F.12 F.13 F.14 Gravity loading criteria (UBC97 [6]). . . . . . . . . . . . . . . . . . . . . . . Seismic design criteria (UBC97 [6]). . . . . . . . . . . . . . . . . . . . . . . . Wind design criteria (UBC97 [6]). . . . . . . . . . . . . . . . . . . . . . . . . Seismic design parameters for the new building. . . . . . . . . . . . . . . . . . Wind design parameters for the new building. . . . . . . . . . . . . . . . . . . Building natural periods and modal directions (rst 3 modes). . . . . . . . . . . Building seismic drift ratios. . . . . . . . . . . . . . . . . . . . . . . . . . . . Building wind drift ratios. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steel material properties used in the analysis of the existing building model. . . Steel material properties used in the analysis of the redesigned building model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 9 9 12 12 13 14 14 16 17

Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Thousand Oaks. . . . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Thousand Oaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Thousand Oaks. . . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Thousand Oaks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Northridge. . . . . . . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Northridge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Northridge. . . . . . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Northridge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: West Los Angeles. . . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: West Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: West Los Angeles. . . . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: West Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Downtown Los Angeles. . . . . Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Downtown Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

101 101 104 104 108 108 111 111 115 115 118 118 122 122

xviii F.15 Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Downtown Los Angeles. . . . F.16 Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Downtown Los Angeles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.17 Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Baldwin Park. . . . . . . . . . F.18 Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Baldwin Park. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.19 Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Baldwin Park. . . . . . . . . F.20 Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Baldwin Park. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.21 Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Anaheim. . . . . . . . . . . . . F.22 Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Anaheim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.23 Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Anaheim. . . . . . . . . . . . F.24 Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Anaheim. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.25 Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Long Beach. . . . . . . . . . . F.26 Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Long Beach. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.27 Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Long Beach. . . . . . . . . . F.28 Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Long Beach. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.29 Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Santa Ana. . . . . . . . . . . . F.30 Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Santa Ana. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F.31 Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Santa Ana. . . . . . . . . . . F.32 Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Santa Ana. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 125 129 129 132 132 136 136 139 139 143 143 146 146 150 150 153 153

Chapter 1

Introduction

The risk of earthquakes in southern California arises from two sources well mapped out faults such as the San Andreas, Newport-Inglewood, and Santa Monica-Hollywood-Raymond faults that have some form of surface expression, and the network of blind-thrust faults hidden deep inside the Earth that includes the Northridge fault and the Puente Hills fault underneath downtown Los Angeles. While the San Andreas strike-slip fault system has the potential for large earthquakes (moment magnitude 8, roughly every 200 years [7, 8]), the blind-thrust faults have the potential for more moderate moment magnitude 7 earthquakes [9]. Fortunately, the urban areas of southern California have thus far been spared from the strongest shaking generated by large strike-slip earthquakes. However, the magnitude 6.7 earthquake of 1994 on the Northridge blind-thrust fault caused 57 deaths and economic losses in excess of $ 40 billion [10, 11]. This earthquake exposed the vulnerability of steel moment-resisting frame buildings to fracture [12, 13, 14]. These buildings resist lateral forces from an earthquake through bending in rigidly-connected (welded) beams and columns. Due to certain construction practices and the use of non-ductile weld material, a signicant number of connections fractured in some of these buildings. Many of the moment-frame buildings in southern California were constructed before 1976 [15] when there was inadequate understanding of the nature and power of earthquake forces, and their effects on buildings. So the question arises as to what would happen to the many tall steel buildings in the mid-height range 1 in the Los Angeles and San Fernando basins if a large earthquake were to occur on the San Andreas fault. Can we estimate damage and consequent losses in these buildings? There have been many improvements in building codes and construction practices since 1994, and buildings designed according to the latest code (1997 Uniform Building Code, UBC97 [6]) are expected to perform far better than existing buildings 2 in large earthquakes. Will they in fact, and if so, is this performance adequate? Before these questions can be answered, more fundamental questions need to be addressed, e.g.: What kind of shaking would be experienced in this region during such an earthquake? What would the frequency content of the shaking be? What about the amplitude and duration of signicant shaking? In this study state-of-the-art computational tools in seismology and structural engineering are combined to perform an end-to-end three-dimensional (3-D) simulation of the rupture of a 290 km section of the San Andreas fault, the generation and propagation of the resulting seismic waves, the subsequent ground shaking in the Los Angeles and San Fernando basins, and the resulting damage to two 18-story steel moment-frame buildings in the region. A decade ago, Heaton et al. [16, 17, 18] simulated the near-source ground motions of a magnitude 7.0 thrust earthquake on a spatial grid of 60 km by 60 km using a vertically stratied crustal model that approximates the rock properties in the Los Angeles basin, and then modeled the response of a 20-story steel-frame building and a 3-story base-isolated building. Olsen et al. [19] and Graves [20] simulated seismic wave propagation generated by a magnitude 7.75 earthquake on a different section of the San Andreas fault. Here many aspects of the earthquake-structure problem are integrated into a comprehensive end-to-end simulation by including the nite-source model of a real earthquake [21, 22], 3-D
1 There are many reasons to look at the performance of this particular class of buildings. The dominant modes of these buildings have natural periods in the range corresponding to that of the large-amplitude seismic waves expected from a large earthquake on the San Andreas fault. There are more steel buildings in this class than reinforced concrete ones (e.g., in 1993, there were 190 steel buildings above 8 stories as compared to 121 concrete buildings [15] in the Los Angeles and Ventura Counties. For buildings in the mid-height range this ratio is likely to be more skewed towards steel). However, this is not to say that concrete buildings will not perform poorly. Similarly, it is generally assumed that highrise buildings 40 stories and larger, with dual structural systems offering greater redundancy, and super-highrise buildings (60 stories and greater), with structural systems that resemble tubes to counter wind forces (which usually govern the design at these heights), will be able to resist shaking from a distant earthquake fairly well. However, no detailed damage analyses studies have been performed to conrm their safety during either large distant earthquakes or even moderate near-source earthquakes that could generate large displacement pulses at great velocities. 2 For the purposes of this report, existing buildings are buildings designed using codes preceding the Uniform Building Code of 1997 [6] and new buildings are those that have been or will be designed using this code.

2 Earth structure [23, 24], 3-D seismic wave propagation [25], and 3-D nonlinear damage analyses of buildings using three-component ground motion [26, 27], validating these procedures using real data from recent earthquakes.

1.1 Scope of the Simulation


The seismological domain of our analysis includes all of southern California and extends north into the central valley beyond Parkeld. However, we restricted the engineering analysis to the main sedimentary basins of San Fernando, Los Angeles, and San Gabriel (Figure 1.1). For the scenarios considered in this study, ground motions south of Irvine going towards San Diego are unlikely to be strong enough to warrant a detailed engineering analysis. While the population of tall buildings in southern California is quite widespread, a major fraction is located in and around downtown Los Angeles, the mid-Wilshire district, west Los Angeles, and Santa Monica. There are quite a few tall buildings spread across the San Fernando valley as well, e.g., in Woodland Hills, Canoga Park, and Camarillo. There are about 30-40 tall buildings in Orange County (comprising the cities of Orange, Irvine, Costa Mesa, Newport Beach, Anaheim, Santa Ana, Garden Grove, etc.). A host of new tall buildings are being planned in Orange County with thirteen proposed high-rises in the cities of Anaheim and Santa Ana. Unfortunately, an inventory of steel buildings of different heights with geographical distribution is not readily available. The best available data in this regard comes from the EQE report [15] that states that in 1993 there were 190 steel buildings taller than 8 stories in Los Angeles and Ventura counties but had little information regarding their location and breakup in terms of height (beyond 8 stories). Given this lack of information on existing buildings, it was decided to divide the entire southern California region into a uniformly spaced grid (with a spacing of 1/32 of a degree or approximately 3.5 km each way) consisting of 636 sites shown by solid triangles in Figure 1.1. The strategy was to place structural models of the buildings considered in this study at each of these sites on the grid and analyze them for ground motion from the scenario earthquake considered. The results are presented in the form of damage/drift performance maps.

1.1.1 Scenarios Considered


Two scenarios involving the rupture of a 290 km segment of the San Andreas fault are considered in this study. The rst scenario consists of the rupture initiating at Parkeld in central California and propagating in a south-easterly direction with the slip increasing gradually from Parkeld to a maximum value just north-west of the region of interest and dropping off abruptly to zero (Figure 1.1, inset). This slip distribution is derived from a nite-source inversion of the November 3, 2002, Denali earthquake. The second scenario consists of the same source but ipped in direction with the rupture initiating just north of the region of interest and terminating at Parkeld with the peak slip occurring close to Parkeld. These two scenarios were specically chosen to illustrate the effects of directivity and slip distribution on the computed ground motion.

1.1.2 Buildings Considered


Two buildings have been considered in this study. The base building is an existing 18-story steel moment-frame building located on Canoga Avenue in Woodland Hills that had signicant damage (moment-frame connection fractures) during the 1994 Northridge earthquake. This building has been the subject of detailed study by many research groups following the Northridge earthquake [13]. The second building is similar to the base building, but the structural system (lateral force-resisting system) has been redesigned according to the current building code, the 1997 Uniform Building Code (UBC97 [6]). The two fundamental differences between these two buildings is that the new building has been designed for larger earthquake forces (accounting for near-source effects) and for stringent redundancy requirements in the lateral force-resisting system. This leads to signicantly different dynamic properties for the buildings. In gen-

34.25

San Fernando Simi Valley Sunland Chatsworth Northridge La Canada Canoga Park Thousand Oaks Burbank North Hollywood Encino Pasadena Hollywood Alhambra Beverly Hills Los Angeles Santa Monica Inglewood

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

34

-120
Parkfield

Malibu Point Dume -118

Montebello Downey Compton Norwalk

Whittier

36

El Segundo

Torrance Long Beach

33.75

Los Angeles

34 0

Seal Beach

Santa Ana

km 7.5 15

Irvine Huntington Beach

-119

-118.75

-118.5

-118.25

-118

-117.75

Figure 1.1: Geographical scope of the simulation (The color scheme reects topography, with green denoting low elevation and yellow denoting mountains): The solid black triangles denote the 636 sites at which seismograms are computed and buildings are analyzed. The white box is the surface projection of the Northridge fault. The red line in the inset is the surface trace of the 290 km rupture of the San Andreas fault that is the primary focus of this study. The area enclosed by the blue polygon denotes the region covered by the 636 sites. eral the redesigned building can be expected to perform better than the existing building in the event of an earthquake. The description of the two buildings, the design methodology for the new building, and the detailed comparison of the two buildings in terms of dynamic properties, static strength, and ductility, are presented in Chapter 2.

1.1.3 End-to-End Simulations


An end-to-end simulation is one that includes the simulation of fault rupture, seismic wave propagation, ground motion computation, and structural damage analyses. Chapter 3 details the state-of-the-art seismological and structural computational tools used for the end-to-end simulations in this study. The rest of the report is devoted to the validation of the simulation procedure using data from the Northridge eathquake (Chapter 5), the validity of utilizing the band-limited simulated ground motion for the analysis of the two buildings (Chapter 6), the historical activity on the San Andreas fault with emphasis on the 1857 earthquake (Chapter 7), description of the source model used in the simulations (Chapter 8), and the results of the two scenario earthquake simulations (Chapters 9 and 10). The last two chapters (11 and 12) summarize the main ndings of the study and outline the future direction for research in this critical area of seismic research.

Chapter 2

Building Details

2.1 Existing Building


The existing building considered in this study is a modern 18-story welded steel moment-frame building located within ve miles of the epicenter of the 1994 Northridge earthquake. The building was designed in 1984 for the lateral force requirements of the 1982 Uniform Building Code [28] and construction was completed in 1986-87. It has 17 ofce stories above ground and a mechanical penthouse above that. There is a single basement. The height of the building above ground is 248-4 with a typical story height of 13-0 and taller rst, seventeenth, and penthouse stories. The plan conguration of the building is fairly uniform over its height. The lateral force resisting system consists of 2bay welded steel moment-frames, two apiece in either principal direction of the building. There are a few setbacks that do not affect the lateral force-resisting system signicantly. The east, west, and south moment-frames lie on the perimeter of the building, while the north frame is located one bay inside of the perimeter. This gives rise to some torsional eccentricity. Many moment-frame beam-to-column connections in the building fractured during the Northridge earthquake and the building has been extensively investigated since then by various engineering research groups [27, 13]. Their ndings are outlined in Chapter 5. Figure 2.1A shows the isometric view of a structural model of the building. The oor plans are given in Figure 2.2 while the frame elevations with beam and column sizes are given in Appendix B. A36 steel with nominal yield strength of 36 ksi is used for all beams, while A572 Grade 50 steel with nominal yield strength of 50 ksi is used for all columns. The oor is made of lightweight concrete slab on metal deck supported by steel beams and girders framing into gravity and moment-frame columns.

2.2 Redesigned (New) Building


There have been many improvements in building codes and construction practices since 1994, and buildings designed according to the 1997 Uniform Building Code [6] are required to resist larger earthquake forces if located in regions close to major faults. Their lateral force-resisting systems are also required to be more redundant which, in the case of moment-frames, translates to a greater number of bays. They are expected to perform far better than existing buildings in large earthquakes and it is of interest to study the performance of such buildings under the scenario earthquakes considered here. To this end, the existing building has been redesigned for UBC97 requirements. The gravity and wind loading criteria from the existing building were retained for the design of the new building (these are given in the next few sections). The stricter lateral force and redundancy requirements led to a reconguration of the lateral system resulting in a greater number of bays of moment-frame in each direction (4 bays on each face of the building). The oor plans with the location of moment-frames are given in Figure 2.3. The frame elevations with beam and column sizes are presented in Appendix C. Note that the moment-frame that was located in the interior of the existing building on grid D has been moved to the perimeter to grid E. The 2-story space required at the lobby of the building precludes moment-frame beams on grid E at the second oor between grids 1 & 2, 3 & 4, and 4 & 5. This probably prompted the structural engineers of the existing building to move the frame to the interior of the building to grid D. But since the stiffness demand at the lower levels is not as high, it was concluded here that the frame would be stiff enough with a single beam at the second oor on grid E. Box-sections are used for the columns left unsupported laterally for two stories at E-1, E-4, E-5, and E-6, to keep the slenderness ratio governing the design within reasonable limits. ASTM A572 Grade 50 steel with nominal yield strength of 50 ksi is used for both beam and column sections, as well as for

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 20 0 0 10
A

0 20 30 40 20 0 0 10
B

20

30

40

Figure 2.1: Structural models of buildings studied: [A] Perspective view of existing building (designed using codes prior to the 1997 Uniform Building Code). [B] Perspective view of redesigned (new) building (redesigned using the 1997 Uniform Building Code). doubler plates that are provided to strengthen panel zones.

2.3 Gravity Loading Criteria for the Two Buildings


The gravity loading criteria for both buildings are given in Table 2.1. The loads are based on the occupancy particular to each oor. Thus, the loads on the typical oor of the two buildings correspond to the ofce occupancy category in this table while the loads on the mechanical/penthouse oor and the roof correspond to those listed in the mechanical and roof occupancy categories, respectively. Other loads not listed in the table include the self-weight of the lateral force-resisting system (moment-frame beams and columns) and the gravity columns.

2.4 Seismic Criteria for the Design of the New Building


All of southern California (the domain of interest in this study) falls under Seismic Zone 4 [6]. Hence, the new building is designed for Zone 4 requirements. It is assumed that the building is located at a distance of 5 km from a Type A fault 1 . The soil at the site is assumed to be of Type Sb which corresponds to a rock site with shear wave velocity in
1 Seismic source types are classied based on the maximum magnitude, M, and the slip rate, SR, on the fault. Type A sources are faults that have a moment magnitude potential of M 7.0 and a slip rate SR 5mm/yr. These types of faults are considered to be active and capable of

6
1 2 3 4 5 6 1 2 3 4 5 6

9.25 m (304")

9.55 m (314")

9.55 m (314")

9.55 m (314")

9.25 m (304")

North

9.25 m (304") E

9.55 m (314")

9.55 m (314")

9.55 m (314")

9.25 m (304")

North

E 5 MF MF (280") 8.53 m 4 MF MF (304") 9.25 m

5 MF MF

(304")

9.25 m

D (280") 8.53 m

4 MF MF 6 3 MF MF

7 (280") 8.53 m

C MF

6 3 MF

7 (280") 8.53 m

B (304") (304") 9.25 m 9.25 m 2 Y X 2 Y A X

MF 1 SECOND FLOOR PLAN

MF

MF 1

MF

PLAN OF THIRD AND FOURTH FLOORS

A
1 2 3 4 5 6 1 2 3 4

B
5 6

9.25 m (304")

9.55 m (314")

9.55 m (314")

9.55 m (314")

9.25 m (304")

North

9.25 m (304") E

9.55 m (314")

9.55 m (314")

9.55 m (314")

9.25 m (304")

North

E 9.25 m 5 MF MF (280") 8.53 m 4 MF MF (304")

5 MF MF

(304")

9.25 m

D (280") 8.53 m

4 MF MF 6 3 MF MF

7 (280") 8.53 m

C MF

6 3 MF

7 (280") 8.53 m

B (304") (304") 9.25 m 9.25 m 2 Y X 2 Y A X

MF 1

MF

MF 1 PENTHOUSE PLAN

MF

TYPICAL PLAN FLOORS 5 THROUGH 17

C
2 3 4 5

9.55 m (314")

9.55 m (314")

9.55 m (314")

North

E 5 MF MF (280") 8.53 m 4 (304") 9.25 m

C (280") 8.53 m 3

B (304") 9.25 m 2 Y X

MF 1 ROOF PLAN

Figure 2.2: Plans of the existing building showing the location of columns and moment-frame (MF) beams (the frame elevations with beam and column sizes are given in Appendix B).

7
1 2 3 4 5 6 1 2 3 4 5 6

9.25 m (304")

9.55 m (314") MF

9.55 m (314")

9.55 m (314")

9.25 m (304")

North

9.25 m (304") E

9.55 m (314") MF MF

9.55 m (314") MF 5

9.55 m (314") MF

9.25 m (304")

North

E (304") 9.25 m

MF (280") 8.53 m 4 MF MF

MF

D MF

MF (280") 8.53 m 4 MF

MF

(304")

9.25 m

7 3

9 (280") 8.53 m

C MF

7 3

9 (280") 8.53 m

MF

MF

MF (304") 9.25 m 2 MF Y X MF

B 2 MF Y A X MF

MF (304") 9.25 m

MF

MF

MF 1 SECOND FLOOR PLAN

MF

MF

MF 1

MF

PLAN OF THIRD AND FOURTH FLOORS

A
1 2 3 4 5 6 1 2 3 4

B
5 6

9.25 m (304")

9.55 m (314") MF MF

9.55 m (314") MF 5

9.55 m (314") MF

9.25 m (304")

North

9.25 m (304") E

9.55 m (314") MF MF

9.55 m (314") MF 5

9.55 m (314") MF

9.25 m (304")

North

E (304") 9.25 m

(304")

9.25 m

MF (280") 8.53 m 4 MF MF

MF

D MF

MF (280") 8.53 m 4 MF MF

MF

7 3

9 (280") 8.53 m

C MF

7 3 MF

9 (280") 8.53 m

MF

MF

MF (304") 9.25 m 2 MF Y X MF

B 2 MF Y A X MF

MF (304") 9.25 m

MF

MF

MF 1

MF

MF

MF 1 PENTHOUSE PLAN

MF

TYPICAL PLAN FLOORS 5 THROUGH 17

C
2 3 4 5

9.55 m (314")

9.55 m (314") MF

9.55 m (314")

North

E (304") 9.25 m

D (280") 8.53 m 8 (280") 8.53 m MF 3 4 MF 7

B (304") 9.25 m 2 Y X

MF 1 ROOF PLAN

Figure 2.3: Plans of the redesigned building showing the location of columns and moment-frame (MF) beams (the frame elevations with beam and column sizes are given in Appendix C). Note the greater number of moment-frame bays in the redesigned building.

Occupancy Ofce

Item Concrete Slab on Metal Deck Floor Fill (Carpet) Partitions (Metal Stud & Dry Wall) Mechanical Floor Framing Live Load Concrete Slab on Metal Deck Floor Fill Mechanical Floor Framing Live Load Concrete Slab on Metal Deck Waterproong Mechanical Floor Framing Live Load Glass Cladding

kg Load ( m 2)

255.00 10.00 100.00 50.00 15.00 250.00 255.00 120.00 35.00 40.00 1200.00 255.00 10.00 35.00 15.00 250.00 40.00

Mechanical

Roof

Cladding

Table 2.1: Gravity loading criteria (UBC97 [6]).

9 Seismic Zone Factor (Z ) Seismic Source Type Closest Distance to Source Soil Type Importance Factor (I ) Structural System Factor (R) Structural Over-strength Factor (0 ) Near-Source Factor (Na ) Near-Source Factor (Nv ) Seismic Coefcient (Ca ) Seismic Coefcient (Cv ) Lateral System Type Factor (Ct ) 0.400 A 5.000 km Sb 1.000 8.500 2.800 1.200 1.600 0.480 0.640 0.085

Table 2.2: Seismic design criteria (UBC97 [6]). Exposure Basic Wind Speed (v ) Importance Factor (Iw ) Windward Coefcient (Cq ) Leeward Coefcient (Cq ) B 70.00 mph 1.00 0.80 0.50

Table 2.3: Wind design criteria (UBC97 [6]). the range of 7601500 m.s1 . It should be recognized that these criteria may vary from one analysis site to the next in southern California but would be applicable to a large proportion of the considered analysis sites. The seismic design criteria for the new building are given in Table 2.2. Based on these criteria, the UBC97 design spectrum is computed and is shown in Figure 2.4.

2.5 Wind Criteria for the Design of the New Building


The new building is assumed to be located in an area that is categorized as Exposure B 2 . The wind design criteria for the new building are given in Table 2.3. Like the seismic criteria, the wind criteria assumed here would not be applicable to all the analysis sites but is fairly representative of southern Californian conditions.
producing large magnitude events. Most segments of the San Andreas fault fall under this category. See reference [26] for a summary of the design of buildings using UBC97. 2 The code classies terrains into three exposure categories, B, C, and D. Exposure B has terrain with buildings, forest, or surface irregularities, covering at least 20% of the ground level area extending 1 mile or more from the site. Exposures C and D correspond to progressively atter terrain. Using the basic wind speed, dened as the fastest-mile wind speed associated with an annual probability of 0.02 measured at a point 10 m above the ground for an area having exposure category C, the wind stagnation pressure on the building is computed which is then corrected for height, exposure, gust conditions, and structure type to arrive at the incident wind forces on the windward and leeward faces of the building.

10

1.4

1.2

1 Spectral Acceleration (g)

0.8

0.6

0.4

0.2

3 Time Period (sec)

Figure 2.4: The 1997 Uniform Building Code response spectrum used in the design of the new building (C a = 0.48 and Cv = 0.64).

11

2.6 Design of the New Building per UBC97 Using the Commercial Program ETABS
A three-dimensional linear elastic model of the building is built using the commercial program ETABS. In addition to the design of beams and columns, the program is capable of checking for the strong column-weak beam criterion in the code. P effects 3 are included in the analysis. The program accounts for P effects from the seismic weight (Dead Load) alone. However, there is a provision to specify a scaling factor for these effects. This factor can be used to include the P effects from Live Load. Assuming that during an earthquake, the building is loaded with 30% of the design Live Load (which on the average works out to about 15% of the design Dead Load), a value of 1.15 is used for this scale factor. The design procedure is outlined below. A rigid foundation is assumed. 1. After the structural model (with preliminary member sizes) including masses and loads is built, a linear dynamic response spectrum analysis is performed. For this purpose, the UBC97 [6] response spectrum (Figure 2.4) corresponding to the seismic parameters of the site given in Table 2.2 is used. 2. The program computes the frame-element weights and these are added on to the dead weight of the structure to arrive at the total seismic weight. The code static base shear is then computed based on this total seismic weight. 3. The program computes the dynamic spectral base shear. As per the code, this base shear can be scaled down to 100% of the static base shear for the design of irregular buildings and 90% of the static base shear for the design of regular buildings. 4. The program also computes the center of mass for each oor. As per the code accidental eccentricity criterion, the center of mass is shifted by 5% of the building dimension in each of the two principal directions. An eccentricity in the location of the center of mass would generate a torsional component in the response and the intent of the code is to ensure some torsional resistance in the design to account for modeling errors that may result in an incorrect center of mass location, e.g., not including oor slab openings for elevators and stairs in the model. 5. The analysis is repeated with the new center of mass and the spectral scaling factor. The member forces from this analysis are scaled up by the frame redundancy factors, x and y , in the two horizontal directions. The code requires that there be a minimum number of bays of moment-frames in each of the two principal directions and it penalizes those buildings that have insufcient redundancy by scaling up the member forces by x and y ([6], Section 1630.1.1). 6. The scaled member forces are used to check the stresses in the beams and columns. If the members are inadequate, the sizes are increased and the process is repeated. This iterative process is carried out until the design is satisfactory. Similarly, interstory drifts are checked against allowable limits and the stiffness of the structure is adjusted to satisfy the drift limits. 7. ETABS also computes the required doubler plates at joints as per UBC97 ([6], Section 2213.7.2). The thicknesses of these doubler plates are rounded to the nearest eighth of an inch. 8. The building design is then checked for wind forces. The wind pressure is computed per UBC97 [6] in conjunction with the wind design criteria specied in Table 2.3. The interstory drifts due to wind forces are restricted to the limit specied therein.
3 When the forces from an earthquake displace a building laterally, the gravity loads acting vertically downward cause an overturning moment on the structure about its base, in addition to the overturning moment caused by the lateral forces themselves. This second-order effect that can lead to global instability of the building is termed the P effect.

12

Height of Building (Hn in meters) Code Fundamental Period (sec) Base Shear (V ) Static Base Shear (metric Tonnes) Base Shear for X-Drift Computation Base Shear for Y-Drift Computation System Redundancy Factor (x ) System Redundancy Factor (y ) Irregular Building? Seismic Inelastic Drift Ratio Limit, max M
* % of Seismic Weight + Only 90% of this is used for design

75.690 2.181 6.024%+ 773.20+ 2.074% 2.074% 1.244 1.249 No 0.02

Table 2.4: Seismic design parameters for the new building.

X-Direction Base Shear (metric Tonnes) Y-Direction Base Shear (metric Tonnes) Drift Ratio Limit

282.17 374.06 0.0025

Table 2.5: Wind design parameters for the new building. The seismic design parameters and the wind design parameters for the new building are given in Tables 2.4 and 2.5, respectively. The redesign of the existing building resulted in an average steel weight of 65.7 kg/m 2 compared to an average steel weight of 60.1 kg/m2 for the existing building (these are based on a combined oor area of the second and upper oors including the roof amounting to 26338 m2 ). These numbers include the allowance for oor framing given in Table 2.1. The computed natural periods and modal directions for both buildings are given in Table 2.6. These are based on the assumption that Live Load does not contribute to the seismic mass (UBC97 guideline). The modal direction factors identify the predominant direction of excitation associated with each of the modes. The factors are percentages associated with the X- and Y-translational and Z-rotational directions. The sum of the three values add up to 100. The

13 Building ID Mode Number Period (sec) Modal Direction Factors X-Trans EB1 1 2 3 1 2 3 4.43 4.22 2.47 3.72 3.51 2.24 97.86 0.10 2.06 47.24 52.71 0.08 Y-Trans 0.10 99.89 0.03 52.72 47.27 0.01 Z-Rotn 2.04 0.01 97.91 0.04 0.02 99.91

EB1R

Table 2.6: Building natural periods and modal directions (rst 3 modes). factors of a particular mode are given by: %X = 100
i

M i 2 X,i M i 2 Y,i
i

(2.1) (2.2) (2.3)

%Y = 100 %Z = 100
i

M,i 2 Z,i

where the summations are over all the stories, Mi and M,i represent the translational mass and the mass moment of inertia of the ith story, respectively, X,i and Y,i represent the X and Y -translational mode shape components at the ith story, respectively, and Z,i represents the corresponding Z -rotational mode shape component. The computed interstory drift ratios from the response spectral analyses of the redesigned building are given in Table 2.7. The X and Y drifts corresponding to two cases spectral direction corresponding to building X and Y directions are listed. The elastic drift, s , is computed for each case by taking the square root of the sum of the squares (SRSS) of these drifts. As per the Uniform Building Code [6], the Maximum Inelastic Response Drift, M , of the structure is extrapolated from the elastic drift ratio, s , as follows: M = 0.7Rs (2.4)

where R is the Structural System Factor given in Table 2.2. = 0.025 for structures having a The code requires that the calculated interstory story drift, M , not exceed max M max fundamental period of less than 0.7 seconds and M = 0.02 for structures with greater periods. The computed drift ratios from the wind analysis of the redesigned building are given in Table 2.8. The limit of 0.0025, although not set by the code, is enforced in the design of tall buildings so that non-structural components such as facades and partitions can be designed to accommodate this movement during design wind-storms. In the case of the new building this requirement governs the design of the beams. When compared to columns, beams usually play a greater role in controlling the stiffness of moment-frames.

14 Building ID EB1R Spectral Direction X Y X-Drift 0.0015 0.0007 Y-Drift 0.0007 0.0015 SRSS s 0.0017 0.0017 SRSS M 0.0098 0.0098 max M 0.0200 0.0200

Table 2.7: Building seismic drift ratios. Building ID EB1R Wind Direction X Y X-Drift 0.00180 0.00015 Y-Drift 0.00011 0.00240 SRSS w 0.00180 0.00240 max w 0.00250 0.00250

Table 2.8: Building wind drift ratios.

2.7 Nonlinear Analysis of Buildings


3-D structural models of both the existing and the redesigned buildings are built using elastober elements for momentframe beams and columns, panel-zone elements (with linear-quadratic shear stress-strain behavior) for joints, and elastic plane-stress elements for oor diaphragms. Gravity columns are modeled using plastic-hinge elements. Loads on these columns contribute to the P effect (see footnote 2 in Section 2.6) that plays a signicant role in tall building response. Gravity beams that are used for supporting the oor slab and are pin-connected (simply supported at their ends with no moment transfer) are not included in the model as they do not contribute stiffness or strength to the lateral force-resisting system. The SAC report [13], from which the structural details of the existing building are extracted, does not clearly indicate whether the joints in the existing building were reinforced with doubler plates or not. For this study, it is assumed that doubler plates are not provided in the existing building. The new building designed for UBC97 regulations does have doubler plates reinforcing the panel zones in some of the beam-column connections. These are included in the computer model of the new building. In order to compute reactions at the base of the buildings, translational springs with large stiffness are placed in the two principal directions of the building at the base of all the columns. Pushover analyses are performed on the two building models in either direction to assess and compare their static lateral strengths and ductility. All the nonlinear analyses are carried out using the program, FRAME3D, details of which are given in the next chapter.

2.7.1 Analysis Assumptions


The following are the assumptions made in the analyses: 1. A rigid foundation is assumed with the base of all columns assumed xed. Soil-structure interaction (SSI) is not included. 2. Strength degradation in the various elements due to weld fracture is included for the existing building but not for the new building (since weld defects have been corrected following the lessons learnt from the Northridge earthquake of 1994 and this mode of failure is not expected to occur in buildings built today). Thus, for the new building model collapse can occur only through P effects, whereas, for the existing building model element failures due to weld fractures in combination with P effects could result in global instability, especially if

15 the element happens to be a column in a lower story. While many probabilistic distributions of ber fracture strains for elastober beam and column elements are investigated for the pushover analyses (described in the next section) and the validation of the numerical procedure using data from the Northridge earthquake (Chapter 5), the more realistic FRAC-S distribution described in the next section is used for the San Andreas simulations (Chapters 9 and 10). 3. Composite action arising out of the shear connection between the concrete slab on metal deck and the momentframe beams is not included. 4. At each level, the story mass is lumped at column locations based on plan tributary area. 5. 30% of the Live Load is included along with the Dead Load in the lumped masses. 6. An average of 30% of the Live Load is included in the gravity loads for ground motion analyses. 7. Gravity columns are modeled using plastic hinge elements and their contribution to the P effects is automatically included. They are assumed continuous over the height of the building. 8. Trusses and horizontal braces are modeled using plastic hinge elements with pinned-end conditions. 9. Detailed material properties used in the analysis of the existing and redesigned building models are given in Tables 2.9 and 2.10, respectively. 10. An effective thickness of 10.16 cm (4 inches) is assumed for the plane-stress elements representing the concrete slab on metal deck. 11. The concrete elastic modulus is taken to be 2.53x109 kg/m2 (3605 ksi) corresponding to a compressive strength fc of 2.81x106 kg/m2 (4 ksi). 12. Poissons ratio for the plane-stress elements is taken to be 0.3.

2.7.2 Pushover Analyses of the Two Buildings


To quantify the actual strength and ductility (deformation potential) of the two buildings in the two principal directions, pushover analyses are performed in either direction. In these analyses the building is subjected to a slow, ramped, horizontal ground acceleration that increases at the constant rate of 0.3 g/minute, and its response is computed dynamically. The structural model is identical to that used in the earthquake analyses except that masses for the horizontal degrees of freedom are recalculated to total the seismic design mass, W/g, with a distribution that is proportional to the UBC97 [6] seismic static design loads. Thus, in this analysis technique the lateral loads are essentially the horizontal seismic design forces proportionally increasing with time at a slow rate. The results of this analysis can also be used to quantify the ductility of the building in terms of its post-yield displacement capacity. The results of the pushover analyses of both buildings are presented in Figure 2.5. The base shear in the direction of pushing is shown plotted as a percentage of the seismic weight of the building against the displacement at the 18 th oor (penthouse level) for the two models of the existing building that include fracture, denoted by EB1-FRAC-S & EB1-FRAC-W, and fracture-excluded models of the existing and redesigned buildings, denoted by EB1-UNFRAC and EB1R-UNFRAC, respectively. The seismic weights computed according to UBC97 for the existing and new buildings are 12689 metric tonnes (27974 K) and 12835 metric tonnes (28297 K), respectively. The ultimate strength of the existing building model in the X direction varies between 7.5% and 7.85% of its seismic weight for the three cases FRAC-S, FRAC-W, & UNFRAC, while the ultimate strength of the redesigned building model in the X direction is 9.5% of its seismic weight. Plotted on Figure 2.5B are the base shear as a percentage of the seismic weight (solid

16

Usage Beams & Columns

Property Elastic modulus, E Shear modulus, G Strain-hardening slope, s ph , for plastic hinge elements used to model gravity columns Yield stress, y , for beam sections W36x300W36x230 W36x194W36x135 Yield stress, y , for column sections W14x730 W14x500W14x311 Yield strain,
y

kgf m Units
kg 20388731162.41 m 2 kg 8155492464.96 m2

Kip in Units 29000.00 ksi 11600.00 ksi 0.02

0.02

32059522.10 33254723.59 38457365.33 40285320.54 0.0017

kg m2 kg m2

45.60 ksi 47.30 ksi 54.70 ksi 57.30 ksi 0.0017

kg m2 kg m2

Slope at initiation of strain hardening, Es , for Elastober Elements Ultimate stress, u , for elastober elements used to model beams Ultimate stress, u , for elastober elements used to model columns Strain at initiation of strain hardening, y , for elastober elements Ultimate strain, u , for elastober elements Panel Zones Shear modulus, G Shear yield stress, y

407774623.25 39652566.81 48089283.16 0.0120 0.1600

kg m2

580.00 ksi 56.40 ksi 68.40 ksi 0.0120 0.1600

kg m2

kg m2

kg 8155492464.96 m 2 kg 19077524.83 m2

11600.00 ksi 27.14 ksi

Table 2.9: Steel material properties used in the analysis of the existing building model.

17

Usage Beams & Columns

Property Elastic modulus, E Shear modulus, G Strain-hardening slope, s ph , for plastic hinge elements used to model gravity columns Yield stress, y , for beams Yield stress, y , for columns Yield strain, y Slope at initiation of strain hardening, Es , for Elastober Elements Ultimate stress, u , for elastober elements used to model beams Ultimate stress, u , for elastober elements used to model columns Strain at initiation of strain hardening, y , for elastober elements Ultimate strain, u , for elastober elements

kgf m Units
kg 20388731162.41 m 2 kg 8155492464.96 m 2

Kip in Units 29000.00 ksi 11600.00 ksi 0.02

0.02

35152984.76 35152984.76 0.0017

kg m2 kg m2

50.00 ksi 50.00 ksi 0.0017 580.00 ksi 65.00 ksi 65.00 ksi 0.0120 0.1600

407774623.25 45698880.19 45698880.19 0.0120 0.1600

kg m2

kg m2

kg m2

Panel Zones

Shear modulus, G Shear yield stress, y

kg 8155492464.96 m 2 kg 20295585.22 m2

11600.00 ksi 28.87 ksi

Table 2.10: Steel material properties used in the analysis of the redesigned building model.

18 lines) and the penthouse displacement (dashed lines) as a function of time for the X-pushover of each model. The penthouse lateral displacement in the X direction at which ultimate strength is reached is about 68 inches (1.73 m) for both building models which corresponds to an average inclination of 2.3% over the height. Both building models are stronger in the Y direction with ultimate strengths of about 8%W for the existing building and close to 10%W for thr redesigned building. Plotted on Figure 2.5D are the base shear as a percentage of the seismic weight (solid lines) and the penthouse displacement (dashed lines) as a function of time for the Y-pushover for each case. The penthouse lateral displacement in the Y direction at which ultimate strength is reached is about 60 inches (1.52 m or 2.0% average inclination) for the three existing building models and 75 inches (1.91 m or 2.5% average inclination) for the new building model. The FRAC-W model assumes a constant fracture strain of 0.9 y (where y is the yield strain) for all the bottom bers of the moment-frame beams. For fracture strain of the beam top-ange and web bers, the following probability distribution is assumed: 30% probability that the fracture strain is 10 y ; 30% probability that it is 20 y ; 20% probability that it is 40 y ; and 20% probability that it is 80 y . For each ber a random number is generated and using this number a fracture strain consistent with the assumed probability distribution is assigned to that ber. For column ange and web bers it is assumed that the fracture strains are far greater than the rupture strain, thus, precluding the occurrence of fractures. The FRAC-S model makes the same assumptions with regard to the fracture strain as the FRAC-W model except that the fracture strains for the bottom-ange bers of the moment-frame beams are determined based on the following probability distribution: 20% probability that the fracture strain is 0.9 y ; 20% probability that it is 2 y ; 20% probability that it is 5 y ; 20% probability that it is 15 y ; and 20% probability that it is 40 y .

19

0.1 Solid Line X Base Shear (Fraction of Seismic Weight) EB1RUNFRAC X Base Shear (Fraction of Seismic Weight) 0.08 EB1UNFRAC EB1FRACS 0.06 EB1FRACW

0.1 EB1RUNFRAC

3.81

EB1FRACS 0.06 EB1FRACW

2.29

0.04

0.04

1.52

0.02

0.02

0.76

0.76

1.52 2.29 3.05 Roof X Displacement (m)

3.81

20

40 60 Time (sec)

80

0 100

A
0.1 Solid Line Y Base Shear (Fraction of Seismic Weight) EB1RUNFRAC Y Base Shear (Fraction of Seismic Weight) 0.08 EB1UNFRAC EB1FRACS 0.06 EB1FRACW 0.1 EB1RUNFRAC

B
3.81

EB1FRACS 0.06 EB1FRACW

2.29

0.04

0.04

1.52

0.02

0.02

0.76

0.76

1.52 2.29 3.05 Roof Y Displacement (m)

3.81

20

40 60 Time (sec)

80

0 100

Figure 2.5: Pushover analysis of the existing and the redesigned buildings: (A) X direction pushover roof displacement versus base shear. (B) X direction pushover base shear (solid lines) and roof displacements (dashed lines) as functions of time. (C) Y direction pushover roof displacement versus base shear. (D) Y direction pushover base shear (solid lines) and roof displacements (dashed lines) as functions of time.

Dashed Line Roof Y Displacement (m)

0.08

EB1UNFRAC

3.05

Dashed Line Roof X Displacement (m)

0.08

EB1UNFRAC

3.05

20

Chapter 3

Software Used for the End-to-End Simulations

3.1 SPECFEM3D
SPECFEM3D (http://www.geodynamics.org) is a 3-D seismic wave propagation software that uses the spectral element method [25] which is based upon a weak formulation of the equations of motion and combines the exibility of a nite-element method with the accuracy of a global pseudospectral method. The nite-element mesh honors all rst- and second-order discontinuities in the Earth model. To maintain a relatively constant resolution throughout the model in terms of the number of grid points per wavelength, the size of the elements is increased with depth in a conforming fashion, thus retaining a diagonal mass matrix. In the Earths mantle and inner core we solve the wave equation in terms of displacement, whereas in the liquid outer core we use a formulation based upon a scalar potential. The three domains are matched at the inner core-outer core and core-mantle boundaries, honoring the continuity of traction and the normal component of velocity. The mesher accommodates lateral variations in compressional wave speed, shear-wave speed, and density, a 3-D crustal model, ellipticity, as well as topography and bathymetry. The solver can handle fully anisotropic 3-D Earth models as well as attenuation, and incorporates the effects of the oceans, rotation, and self-gravitation in the context of the Cowling approximation. To simulate ground motion in the Los Angeles basin from regional earthquakes, a special version of SPECFEM3D, SPECFEM3D BASIN, tailored to simulate seismic wave propagation in sedimentary basins is used. The mesh generator is specically written for the simulation of wave propagation in southern California, but can be modied for use in other geographical areas. The solver is completely general and can be used to simulate seismic wave propagation on regional and local scales. The sedimentary basin model (Harvard-LA velocity model [29]) is constrained by hundreds of petroleum industry well logs and more than 20000 km of seismic reection proles. The numerical simulations account for three-dimensional variations of seismic wave speeds and density, topography and bathymetry, and attenuation. This method has been shown to reliably model ground motion down to a period of approximately 2 s [23, 24]. Thus the simulated ground motions can only be used to study the behavior of building structures whose dominant modes of vibration have natural periods greater than 2 s, which implies tall buildings of 15 stories or more. The top soil layer is not included in the Earth model due to lack of sufcient data and the numerical complexity associated with low shear wave velocities in the layer (the minimum S-wave speed in the basin for the Harvard-LA velocity model is 687 m.s1 ) which would require a very dense numerical grid to be correctly sampled. This typically softer layer may have the effect of amplifying the ground motion.

3.2 FRAME3D
Nonlinear damage analyses of the building models subjected to the simulated ground motion in this study are carried out using the program FRAME3D (http://www.frame3d.caltech.edu) that is based on the nite-element method and is capable of performing time-history analysis. A three-dimensional structural model of a framed building using this program consists of grids of beams and columns. The setup of the model is comprised of three element classes: panel zone elements for joints, beam elements for beams and columns, and diaphragm elements for oor and roof slabs. The arrangement of these elements in a typical structural model is illustrated in Figure 3.1. The two beam element types can be used for either beams or columns. The plastic hinge beam element consists of two nodes at which biaxial exural yielding is permitted, leading to the formation of plastic hinges. Elastic rotational springs are connected across

21 the plastic hinge locations to model strain-hardening. Axial yielding is also permitted. The elastober beam element is divided into three segments two end nonlinear segments and an interior elastic segment. The cross-sections of the end segments are subdivided into bers. Associated with each ber is a nonlinear hysteretic stress-strain law for axial stress and strain. This accounts for coupling of nonlinear material behavior between bending about the major and minor axes of the cross-section and axial deformation. The panel zone element models nonlinear shear deformation in the region of the joint where the beams and columns intersect. The joint region consists of a length of column within the depth of the connecting beams. Shear deformation is due, primarily, to opposing moments from the beams and columns at the joint caused by the frame being subjected to lateral loads. The joint is modeled by two planar orthogonal panels forming a cruciform section. Edges of these panels contain attachment points a, b, c, and d where beams attach, and e and f on the top and bottom,respectively, where columns attach (Figure 3.1). Each panel may yield and strain harden in shear. The diaphragm element is used to model the in-plane stiffness of oor slabs. It is essentially a 4-noded plane-stress element that remains elastic at all times. Refer to [26] for the detailed theory of each of these element types. A key feature of FRAME3D is that full geometric updating is included in both static and dynamic analyses to accommodate large nodal translations and rotations. This automatically accounts for the P effects and allows the analysis to follow a buildings response well into collapse. It involves updating the locations of the joint nodes, attachment points, and the local beam nodes, as well as the orientations of the local element coordinate systems [30, 31, 32]. The program utilizes an iteration strategy applied to an implicit time-integration scheme to solve the nonlinear equations of motion at each time-step.

22

f c b d e 2 Plastic hinge beam element M L a

Joint Nodes: J, K, L, M Attachment Points: a, b, c, d, e, f Local Beam Nodes: 1, 2, 3, 4

Diaphragm element (reduced size) 1 f J K

1 2 b J d

_ Y

c
Z Y X

Segments

f c b 4 2 d e a

_ X

_ Z

a 1 3

Elastofiber beam element

e
Z Y X

Panel zone element

Figure 3.1: Element arrangement in frame model showing joint nodes, attachment points, local beam nodes and coordinate systems.

23

Chapter 4

Limitations of the Study

For a study such as this, that is of interest to various stake-holders that do not necessarily have a seismological or structural or technical background, it is crucial to list the limitations clearly to put the results in the right perspective. It is in this spirit that the following key limitations should be recognized while considering the results: 1. Validation of the numerical procedures adopted here is based on the magnitude 6.7 Northridge earthquake of January 17, 1994, while the scenario earthquakes simulated here are of magnitude 7.9 (with about two orders of magnitude greater energy release). Similarly, the source mechanism of the Northridge earthquake was a thrust mechanism that did not break the surface while the San Andreas simulation is one of strike-slip source mechanism with surface break. Furthermore, the amount of data collected during the Northridge earthquake, especially from building response, is fairly limited, and this restricts the extent to which the numerical procedures can be convincingly validated. 2. For the San Andreas simulation, only a single source model (from the nite-source inversion of the Nov. 3, 2002, Denali, Alaska earthquake) has been considered. Other sources could give noticeably different results. Having said this, the potential for large earthquakes with comparable amounts of slip does exist as evidenced by the San Andreas earthquake in 1857 (see Chapter 7), and it is critical to estimate accurately the implications through detailed modeling of at least one scenario at the expense of loss of generality. 3. The top soil layer (of about 30 m) close to the free surface is not included in the Earth model due to lack of sufcient data and the numerical complexity associated with low shear wave velocities in the layer. This typically softer layer may have the effect of amplifying the ground motion [33, 34]. Theoretically, the peak amplication occurs at periods Tm = 4d1 /m1 , m = 1, 3, 5, etc. where d1 is the depth and 1 is the shearwave velocity in the overburden soft layer, and is given by 2 2 /1 1 where 2 and 1 are the densities of the basement and the overburden, respectively, and 2 is the shear-wave velocity in the basement. This amplication could be quite different from place to place based on the depth of the top-soil layer, the density contrast, and the shear-wave speed contrast between the underlying basement and the overburden layer, and there is insufcient data to determine the amplication in the entire region. Having said this, the buildings that we analyze are long-period structures most affected by long-period waves with wavelengths far greater than the depth of the unmodeled soil layer; these waves simply do not see the layer and as a result the effect of the top soil layer on the simulated ground motion (with periods longer than 2 s) is likely to be insignicant. Furthermore, maps of the geotechnical layer do not currently exist for southern California. A nal limitation is that 3-D seismic wave propagation codes that can handle a geotechnical layer are currently not available. Including the geotechnical layer, when a model becomes available, will require the consideration of very high frequencies and much higher resolution, and therefore the numerical cost would be high. 4. Ground motion, simulated using SPECFEM3D BASIN, in the Los Angeles basin has been shown to be accurate down to a period of only 2 s [24]. Hence computed ground motions have been lowpass-ltered to this period using a Butterworth lter (actually bandpass-ltered between 2 and 1000 s). The effect of ltering ground motions on the response of tall buildings (especially of the type considered here) has been shown not to be signicant in Chapter 6. Nevertheless, this could vary from case to case and the results should be viewed upon as being in the ballpark of (and not exactly) what to expect from such an earthquake.

24 5. The structure foundations have not been included in the structural models. Soil-structure interaction (SSI, e.g., [35, 36]) is not included in the analyses. Dynamic nonlinear SSI is not a well understood phenomenon because of the lack of recorded data and the difculty to design accurate numerical tools to study it. One of the few real-world examples of extensive SSI research is a 14-story reinforced concrete storage building in Hollywood constructed in 1925 [37, 38, 39]. These studies indicate that the change in various structural response parameters in this building during the October 1, 1987, magnitude 5.9 Whittier Narrows earthquake due to SSI could have been up to 20%. SSI is an active area of research and should be incorporated into future studies of this kind. 6. Stiffness of partitions, and stair & elevator enclosures is not included. 7. Some critical failure modes such as local ange buckling of I-sections are not included in the structural modeling. Not including these failure modes could result in under-predicting the damage in these models. 8. Column splices have not been modeled. Column splices are typically located three feet above the oor slab with the intention of locating them away from the high-moment (high exural stress) regions near beam-column joints. In the absence of axial load, the theoretical point of contraexure (zero moment) is at mid-height of the column. In the case of columns, axial load does exist and buckling failure could occur at mid-height (rst mode buckling). So the splice location of three feet above the oor slab is chosen to avoid the most vulnerable locations of the column. These splices are weak points and could fail especially if the column goes into tension during the earthquake. Once again, not including column splices could result in under-predicting the structural damage. 9. Composite action of moment-frame beams has not been included. Moment-frame beams are connected to the concrete slab on metal deck through shear connectors (studs). This leads to some part of the slab in the vicinity of the beam to act as being part of the beam, leading to increased stiffness and strength. The effect of this is two-fold. Firstly, it could make the moment-frames stiffer attracting greater seismic forces, but this could be partly offset by the increased strength from composite action. In addition since this would make the beams stronger in relation to the columns, it could have the effect of pushing the location of plastic yielding into the columns, which could result in greater overall building damage. Having said this, more analysis needs to be done to investigate the effect of composite action of moment-frame beams on overall building response. 10. It is not clear from the SAC report [13] whether doubler plates were provided to strengthen the panel zones in the columns of the existing building in Woodland Hills. If these were provided, then this data is missing in the SAC report. Hence no doubler plates are included in the existing building model in this study. With doubler plates, the performance of the model would be enhanced. The redesigned building has been provided with doubler plates per the UBC97 [6] provisions.

25

Chapter 5

Validation Using the Northridge Earthquake Data

The rst step in a study such as this is the validation of the numerical procedure using data from a regional earthquake. The only major regional earthquake for which extensive data has been recorded in southern California is the magnitude 6.7, January 17, 1994, Northridge earthquake. Two independent data sets are required for validation. Using the rst data set, a nite source model of the earthquake is created which is then used to simulate ground motion in the region. The computed seismograms are then compared against the second data set for validation. While many research groups have determined kinematic fault models by tting seismic waveform data [40, 41], a wavelet transform approach [21] that can extract more information about slip heterogeneity by simultaneously considering both the time and frequency characteristics of the waveforms is used. The resulting nite-source model is shown in Figure 5.1. Using the spectral-element method [25], ground motion generated by this nite-source model of the Northridge earthquake is then simulated. In addition to the 636 sites under consideration, seismograms are computed at southern Californian seismic stations that recorded the shaking during the earthquake. The synthetic seismograms (red) are compared against the recorded data (black) at nearby stations north of the fault and at distant stations in Figure 5.2. All the waveforms are lowpass-ltered with a corner period of 2 s (in practice, they are bandpass-ltered between 21000s). The synthetic seismograms are able to capture the large pulses in the nearby stations while there is a very good match in most waveforms corresponding to distant stations.

Strike= 122 degrees


km

-10

-5

Depth km

10

15

20 cm 0 25 50 75 100 125 150 175 200


Figure 5.1: Slip model for the January 17, 1994, magnitude 6.7 Northridge earthquake determined using a wavelet transform approach. The red star denotes the hypocenter and the white arrows denote the slip vector. The dip angle of the fault is 40 degrees (see Figure 1.1 for the surface projection of the fault)

26

U57 U56 SCS RRS PIRU JFP CAS

26 deg. 25 km 341 deg. 22 km 30 deg. 12 km 40 deg. 10 km 325 deg. 33 km 24 deg. 12 km 347 deg. 38 km

N-S N-S N-S N-S N-S N-S N-S

15.0 cm/s 51.1 cm/s 43.9 cm/s 47.3 cm/s 17.9 cm/s 50.1 cm/s 22.3 cm/s

-5
(A)

0
E-W

10 sec

15
N-S

20

25
U-D

30

1.2 cm

1.1 cm

0.6 cm

SVD 135km PAS 36km GSC 200km DGR 156km 0.5 cm 0.2 cm 0.5 cm 0.6 cm 1.4 cm 1.0 cm 2.2 cm 1.4 cm 1.6 cm

0
(B)

50

100 0

50

100 0

50

100

sec

sec

sec

Figure 5.2: Northridge simulation Data versus synthetic seismograms: (A) nearby stations north of the rupture; (B) distant stations.

27 While there is a sufcient amount of ground motion data to validate the seismological component of the numerical procedure, the same is not true of tall building performance. Not many tall buildings in the region were instrumented at the time, especially of the type considered here (18-story steel moment-frame buildings). One building that was instrumented was the 18-story steel moment-frame building described in Chapter 2. This building, located in Woodland Hills, was designed in 1984 using the 1982 Uniform Building Code and constructed in 1986-87. A computer model of this building is illustrated in Figure 2.1A. Following the Northridge earthquake, problems associated with the alignment of elevators prompted a survey which evaluated the plumbness of the building. The survey indicated that the building was leaning 6 inches to the north at roof level. A damage investigation of the building revealed fracture in 29 out of the 154 beam bottom ange-to-column welds in the east and west moment-resisting frames [13]. The investigation included visual inspection of all moment-frame beam bottom ange-to-column welds, and the ultrasonic testing of 39 top ange-to-column welds and some bottom ange-to-column welds. The west moment-frame had 23 weld fractures while the east moment-frame had 6 fractures. No weld fractures were observed in the north and south moment-frames. No top ange weld-fractures were observed in any of the moment-frames. All fractures that were observed were visible from the top of the bottom ange. The fractures included cracks through the weld, cracks at the back of the weld adjacent to the column ange, and cracks that went into the column ange and exited the column ange above the weld. All weld fractures seemed to have initiated from the root of the full penetration welds. There was a three-component SMA-1 accelerograph on the 18 th oor of the building that recorded the oor acceleration [42]. Unfortunately, the closest free-eld seismometer was at the Oxnard Boulevard seismic station (WHOX) located in Woodland Hills, about half a mile away from the building. Nevertheless, the building model was analyzed for shaking from the recorded WHOX data. This nonlinear damage analysis of the structure was performed using the nite-element-method-based program, FRAME3D, described in Chapter 3. The computed displacements at the 18th oor in the north-south and east-west directions are compared against the corresponding measured displacements in Figure 5.3. The computed peak displacement in the north-south direction is within 5% of the measured displacement. However, the peak displacement in the east-west direction is off by a factor of 2. There is a minor lengthening of the period in the measured displacement that is not captured by the computed displacements. Also, the measured displacement attenuates faster than the computed displacement. These differences could be due to any or all of the following reasons: the ground motion used in the analysis was not recorded at the base of the building but half-a-mile away; the instrument at the roof was maintained by the owner of the building and its reliability is uncertain; rocking of the building about its base (due to the nite stiffness of the soil), which is not included in the xed-base structural model, could contaminate the displacement record measured at the roof and the observed period may actually be a combination of purely translational and rocking modes; as damage accumulates in a building during an earthquake, (non-hysteretic) damping increases signicantly. However, in the structural model while hysteretic damping is modeled accurately in a non-linear fashion, non-hysteretic supplemental damping is considered to be viscous and linear, and as damage accumulates it does not increase correspondingly. The location of the fractures in the four moment-frames in the building from the analyses is compared against the location of observed fractures in the building in Figure 5.4. Since all the fractures were observed in the bottom ange weld [13], for the purposes of this analysis, the fracture strain in all the welds in the building model, except the beam bottom-ange welds, was taken to be far greater than the steel ber rupture strain. The fracture strain for the beam bottom-ange welds was varied and the structural analysis was carried out repeatedly until the total number of weld fractures in the model matched the observed number of fractures in the building following the Northridge earthquake. A beam bottom-ange weld fracture strain of 1.05 times the yield strain, y , results in a total of 29 weld fractures in the analysis which is the same as what was observed in the eld. The fracture distribution in the various momentframes of the model is now compared against that observed in the building in Figure 5.4. In both cases the fractures are conned to the north-south moment-frames. Majority of the fractures occur in the top-third of the moment-frames in both cases. However, while most fractures (23) in the building occurred in the west moment-frame with fewer

28
50 Penthouse (18th Floor) northsouth displacement response

Displacement (cm)

50

Measured Computed (west face) Computed (east face) 0 10 20 30 sec 40 50 60

(A)
50

Penthouse (18th Floor) eastwest displacement response

Displacement (cm)

50

Measured Computed (north face) Computed (south face) 0 10 20 30 sec 40 50 60

(B)

Figure 5.3: Northridge validation analysis of existing building in Woodland Hills subjected to Oxnard Blvd. record (WHOX): Measured 18th oor (A) N-S and (B) E-W displacements versus corresponding computed displacements. fractures (6) in the east moment-frame, the reverse is true for the model with 6 fractures in the west moment-frame and 20 fractures in the east moment-frame. If the sign of the east component of the ground motion is reversed, then the damage pattern in the model is similar to the observed pattern. However, based on personal communications with the California Geological Survey (CGS), it was determined that the recording instrument was a three-component SMA-1 strong motion accelerograph for which the orientation reversal of one of the two horizontal components is possible only in conjunction with the orientation reversal of the other horizontal component. The direction of the rst arrival of the Oxnard Boulevard, Woodland Hills (WHOX, latitude 34.18, longitude -118.59) record (velocity) north component, agrees well with the north components of two nearby records, Canoga Park (CNPK, latitude 34.212, longitude -118.607) and Saticoy Street (SATI, latitude 34.209, longitude -118.517) as shown in Figure 5.5. This indicates that the orientation of the north component of the WHOX instrument is correct implying that the orientation of the east component must be correct as well since the instrument is of the SMA-1 type. But the orientation of the rst arrival of the east component of the WHOX instrument seems to be out-of-phase with that of the CNPK instrument (also of the SMA-1 type) which cannot be explained. Adding to the mystery is the fact that a twin building with the same conguration, design, and orientation had a very different damage pattern compared to the building considered here (based on personal communication with Mr. Terrence Paret, Wiss, Janney, Elstner Associates, Inc.). The details of this building were not included in the SAC report [13]. To summarize, the seismological component of the numerical procedure was validated adequately using the mea-

29

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure 5.4: Analysis of the existing building subjected to the Oxnard Boulevard, Woodland Hills (WHOX) record from Northridge earthquake (station located 0.5 mile from the building): Observed connection fractures (squares) versus simulated fractures (solid triangles) (A) South moment-frame (along grid A, east-west direction) of the building (Frame 1); (B) North moment-frame (along grid D, east-west direction) of the building (Frame 4); (C) West momentframe (along grid 1, north-south direction) of the building (Frame 6); (D) East moment-frame (along grid 6, north-south direction) of the building (Frame 7).

30

Velocity
70.00 0.0 70.00 0.0 60.00 0.0 amplitude 40.00 0.0 40.00 0.0 50.00 0.0 sati 0 61.165

cnpk 0 61.063

whox 0 57.709

sati 90 31.114

cnpk 90 32.172

whox 90 41.887

0.0

10.0

20.0

30.0 time (sec)

40.0

50.0

60.0

Figure 5.5: Comparison of the horizontal components of velocity of three records from the 1994 Northridge earthquake, SATI, CNPK, and WHOX (Source: URS Corporation). nfsmith0: Wed Jun 15 09:45:47 PDT 2005
/net/snell/u1/nancy/MiscProjects/Swami_NRwhox.Apr05

sured records from the 1994 Northridge earthquake. However, the structural component of the procedure could be validated only to a limited extent due to unavailability of suitable data and variability in the quality of construction resulting in uncertainty in the modeling environment. While the various elements used for modeling buildings in the program FRAME3D have been tested individually [31, 32], validation of an assembled building has been a challenge. The pre-Northridge weld defects in steel moment-frames were due to many reasons, some of them human. Here is an extract from the Federal Emergency Management Agency document, FEMA-353 [43]: The joint between the bottom beam ange and column ange is typically made as a downhand eld weld, often by a welder sitting on top of the beam ange, in a so-called wildcat position. To make the weld from this position each pass must be interrupted at the beam web, with either a start or stop of the weld at this location. This welding technique often results in poor quality welding at this critical location, with slag inclusions, lack of fusion and other defects. These defects can serve as crack initiators, when the connection is subjected to severe stress and strain demands. From this description, it is clear that the presence or absence of defects in welds can and is often dictated by the skill and ability of the welder. Finally, a note on the permanent tilt of the building at the penthouse level. Surveys conducted after the Northridge earthquake to check how far the building was tilted out-of-plumb indicated that the building was leaning six inches to the north [13]. The permanent tilt 1 on the four faces of the computational model are shown in Figure 5.6. Twisting of
1 Permanent

tilt at a given location in the building model is computed by taking the displacement time-history at that location and lowpass-

31
1 9.25 m (304") 2 9.55 m (314") 3 9.55 m (314") 4 9.55 m (314") 5 9.25 m (304") North 6

5.69 cm (2.24") 7.49 cm (2.95") (304") 9.25 m

North MomentFrame

D (280") 8.53 m

West MomentFrame

East MomentFrame

C (280") 8.53 m

3.05 cm (1.20")

B (304") 9.25 m Y X South MomentFrame

2.39 cm (0.94")

Figure 5.6: Permanent offsets on the four faces of the existing building model (penthouse plan shown here) computed using the WHOX record from the Northridge earthquake. the model has resulted in a non-uniform pattern of permanent tilting on the four faces. The north-east corner has a net permanent tilt of 3.7 inches in a north-westerly direction.

ltering it using a Butterworth lter with the lter corner period at 10 s and taking the average over a time-window that has the minimum variance. The length of the time window was taken to be 5 s. Note that this is the tilt in the building that is relative to the ground and building tilt resulting from ground tilt or structure foundation differential settlement following the earthquake would not be captured by the structural model.

32

Chapter 6

Effect of Filtering Records on Building Analyses

As described in Chapter 4, ground motion simulated using SPECFEM3D BASIN in the Los Angeles basin has been shown to be accurate down to a period of only 2 s. Due to this limitation, all the broadband time-histories computed using SPECFEM3D BASIN are lowpass-ltered using a Butterworth lter with the corner period at 2 s (in practice bandpass-ltered between 2 s and 1000 s). The ltered ground motion records are used as input to building analyses. However, building response is a function of the entire frequency band of the ground motion with the building higher modes corresponding to shorter periods getting excited by high-frequency ground motion. So the question arises as to what the effect of excluding the high-frequency ground motion is on the response of the buildings considered in this study. Since dominant modes of the two 18-story buildings considered here have periods greater than 2 s, it is theorized that the effect of the higher-frequencies in the ground motion may not have a signicant impact on their response. To conrm this hypothesis, the following study has been performed: 1. A total of 13 three-component records from the magnitude 7.5, September 21, 1999, Chi-Chi earthquake in Taiwan, and the magnitude 8.3, September 26, 2001, Tokachi-Oki earthquake in Japan, are considered. Response spectra of the north and east components of these records are shown in Figures 6.1 and 6.2, respectively. Also shown on these plots are the fundamental periods of the existing and redesigned buildings, and the corner period of the lowpass-lter for comparison. From the spectra, it is clear that the chosen records span a wide range of intensities of ground motion. 2. These records are bandpass-ltered between 2 s and 1000 s. 3. Nonlinear analyses of the existing and redesigned building models subjected to the ltered and unltered records are carried out using FRAME3D. Shown in Figures 6.3 and 6.4 are the peak interstory drift ratios computed in either building model using the ltered records plotted against those computed using the corresponding unltered records. If the high-frequency ground motion had no effect whatsoever on the response of the buildings, then all the points would fall on the diagonal. The fact that most of the points are aligned quite closely with the diagonal indicates that the effect of high-frequency ground motion (the range of frequencies not included in this study) on the building response (for the two buildings considered in this study) is not signicant and can be safely ignored. In essence the initial S wave damages the building leading to its softening, thus shifting its natural frequency spectrum farther into the long-period regime and further reducing the effect of the high-frequency content in the ground motion. Note that the pen colors used to plot the points on these gures correspond to those used in plotting the response spectra in Figures 6.1 and 6.2. Thus, each point can be identied with the corresponding ground motion record.

33

1000

Response Spectra of Unfiltered (Solid) and LowPass Filtered (Dashed) Acceleration Records from the ChiChi and TokachiOki Earthquakes NS Component HKD113 LowPass Cutoff Period TF=2.00s

900

HKD112 Redesigned Bldg Fundamental Period TN48W=3.51s Redesigned Bldg Fundamental Period TN42E=3.71s Existing Bldg Fundamental Period TNS=4.22s HKD109 Existing Bldg Fundamental Period TEW=4.43s HKD100 HKD096 HKD091 HKD077 CWBT120 CWBT116 CWBT109 CWBT063 CWBT049 CWBC101

800

700

Spectral Acceleration (cm/s2)

600

500

400

300

200

100

4 Period (s)

Figure 6.1: Pseudo-acceleration response spectra of records (north component) from the Chi-Chi and Tokachi-Oki earthquakes: Comparison of spectra of unltered (solid) and ltered (dashed) records.

34

1000

Response Spectra of Unfiltered (Solid) and LowPass Filtered (Dashed) Acceleration Records from the ChiChi and TokachiOki Earthquakes EW Component HKD113 LowPass Cutoff Period TF=2.00s

900

HKD112 Redesigned Bldg Fundamental Period TN48W=3.51s Redesigned Bldg Fundamental Period TN42E=3.71s Existing Bldg Fundamental Period TNS=4.22s HKD109 Existing Bldg Fundamental Period TEW=4.43s HKD100 HKD096 HKD091 HKD077 CWBT120 CWBT116 CWBT109 CWBT063 CWBT049 CWBC101

800

700

Spectral Acceleration (cm/s2)

600

500

400

300

200

100

4 Period (s)

Figure 6.2: Pseudo-acceleration response spectra of records (east component) from the Chi-Chi and Tokachi-Oki earthquakes: Comparison of spectra of unltered (solid) and ltered (dashed) records.

35

0.1 0.09 0.08 Peak Drift (Using Filtered Records) 0.07 0.06

Existing Building

ChiChi TokachiOki

CWBC101

CWBT063 0.05 0.04 0.03 0.02 0.01 0 CWBT049 CWBT116 CWBT120 HKD091 HKD109 HKD100 HKD077 HKD096 HKD113 HKD112 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 Peak Drift (Using Unfiltered Records) 0.09 0.1 CWBT109

Figure 6.3: Peak drifts observed in the existing building analyses using ltered and unltered records. Pen colors used to plot the points match those used in Figures 6.1 and 6.2.

36

0.1 0.09 0.08 Peak Drift (Using Filtered Records) 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0

Redesigned Building

ChiChi TokachiOki

CWBC101

CWBT063 CWBT109 CWBT049 CWBT120 CWBT116 HKD109 HKD091 HKD100 HKD077 HKD096 HKD113 HKD112 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 Peak Drift (Using Unfiltered Records) 0.09 0.1

Figure 6.4: Peak drifts observed in the redesigned building analyses using ltered and unltered records. Pen colors used to plot the points match those used in Figures 6.1 and 6.2.

37

Chapter 7

Past Earthquakes on the San Andreas Fault

Paleoseismology, the recognition and characterization of past earthquakes from evidence in the geological record, has contributed fundamentally to understanding earthquakes by extending the known record of earthquakes into past centuries and millennia. This extension of the historic and instrumental record has revealed the size, location, and timing of past earthquakes, as well as some clues about the length and regularity of earthquake cycles, and the variability of rupture magnitude and extent from event to event on a particular fault [44]. Extensive radiocarbon dating of earthquakes has been carried out at Pallett Creek, a paleoseismic site astride the San Andreas fault 55 km northeast of Los Angeles. This site contains a record of twelve large earthquakes preserved in interbedded marsh and stream deposits [7]. The dating of the ten most recent of these episodes leads to an estimate of the average interval between these episodes of about 132 years [44]. Five of the nine intervals are shorter than a century; three of the remaining four intervals are about two to three centuries long. These ten episodes occurred in four clusters, each of which consists of two or three events. Earthquakes within the clusters are separated by periods of several decades, but the clusters are separated by dormant periods of two to three centuries. The last major earthquake on the southern half of the San Andreas fault was the Fort Tejon earthquake (magnitude originally estimated to be 7.9 by Sieh [1], but subsequently upgraded to approximately 8.25 by the US Geological Survey) that occurred on January 9, 1857, which was preceded by two estimated-magnitude 7.0 earthquakes on December 8 and 21, 1812. The 1857 event was produced by several meters of sudden lateral slip along the south-central reach of the fault and was felt over at least 350,000 km2 [1]. Most reports indicate that the duration of the earthquake was between 1 and 3 min. Based on paleoseismological evidence, Kerry Sieh [1] reconstructed the slip distribution along the fault for this event. The rupture initiated at Cholame about 25 km south of Parkeld in Central California, grew to a peak slip of about 9.5 m at Wallace Creek (about 67 km from Cholame), and propagated south past Wrightwood in southern California for a total distance of about 330 km. The next day, the following account appeared in the Los Angeles Star newspaper [2]: Doors were slammed to and fro, water was turned out of bowls and pitchers, and in the river the water rushed violently to one bank and then back again, the motion being repeated several times. William Wallace of Los Angeles wrote in his journal [3]: This morning at 8.5 oclock, I was walking to Wolfskills and was near his brick house. Suddenly I felt a sort of vertigo. My legs refused to support me. I swayed to and fro like a drunken man. The ground rose up before me, and I reached out my hand to sustain myself against the wall. The wall cracked and rocked. The water which usually runs downhill had doubled upon itself and was rushing with fury towards me. When I saw this, the idea of an earthquake occurred to me. The ground swayed vertically back and forth, without violence, but with considerable force continuing about 1.5 minutes. Both of these accounts are indicative of long-period, large-amplitude, long-duration ground motion. Since tall buildings have long natural periods, this could impose a severe demand on the tall building stock in southern California. According to Weldon et al. [45], even though the current 148-year hiatus in activity on the San Andreas fault is not exceptional, since no lull in the past 1600 years appears to have lasted more than about 200 years when the current hiatus ends, a substantial portion of the fault is likely to rupture either as a single long rupture or a series of overlapping ruptures in a short time interval. To conclude, the potential for a big earthquake with a large amount of slip on the San Andreas fault exists. In order to prepare for this, it is critical to quantify the effects of such a scenario and this study is an effort in that direction.

38

Chapter 8

Source Model Used in the Simulation of the

Magnitude 7.9 Earthquakes on the San Andreas Fault


Large earthquakes occur as a result of a nite length of fault rupturing. When simulating ground motion from such earthquakes, it is critical to have a realistic source model (slip distribution in time along the fault). Assuming a pointsource could lead to erroneous results. The prime objective of this study is to simulate an 1857-like earthquake on the San Andreas fault. Instead of empirically constructing an earthquake source which could add another dimension to the uncertainty inherent in a study of this nature, a nite-source model of the November 3, 2002, magnitude 7.9 earthquake on the Denali fault system in Alaska that is geometrically similar to the San Andreas fault is used in this study. The Denali earthquake initiated as a magnitude 7.1 thrust event on the Susitna Glacier fault, quickly changed to a strike-slip mode of rupture and propagated southeastward along the Denali fault for 218 km, before jumping to the Totschunda fault and continuing further for about 76 km [46]. The slip distribution of this earthquake has been estimated (Figure 8.1) using teleseismic body waves and strong motion waveforms as well as GPS vectors [22]. Here, the slip on the Denali and Totschunda faults (290 km long), amounting to a moment magnitude of 7.9, has been mapped on to the San Andreas fault with rupture initiating at Parkeld and progressing southeastward a distance of about 290 km (Figure 1.1 inset). The maximum depth of rupture is about 20 km. The surface slip (Figure 8.2) grows slowly to 7.4 m and then drops off drastically towards the end of the rupture 1 . The peak slip at depth is about 12 m. The peak particle velocity is 4.3 m.s1 2 .
0 0 Depth (km)
20
10

50
30
30

100

Denali-Totschunda 150
60
60
50

200

250

70

10 20 -10 0

40

10 10

80

40

30

50

10 20
10

Depth (km)

0 5 10
5
5

cm 0 200 400 600 800 1000 1200

Figure 8.1: Slip distribution of the 2002 Denali earthquake constrained by teleseismic body and strong motion waveforms as well as GPS vectors. The color scheme reects the slip amplitude and contours reect the rupture initiation time. The hypocenter is indicated by the red star. White arrows denote the slip direction and magnitude It should be noted that the prediction capability of the nite source used in this study is band limited. It is dependent on the shortest period of seismic signals used to construct the model, which in most cases is about 2 sec, but could be as short as 1 sec when the stations are close to the fault where the source signature is the strongest with little contamination from 3-D propagation effects, e.g., the 1994 Northridge earthquake.
1 This is contrary to what happened in the 1857 San Andreas earthquake, where the slip along the fault is deduced to have grown quickly to a peak value of about 9.5 m and then dropped off gradually [1]. 2 Since particle velocity is not constrained as well as the slip in the inversion, a scenario in which the particle velocity is articially capped at 1 m.s1 is considered (Figure 8.3). The resulting ground motions in the region of interest (far away) are not signicantly different from the uncapped particle velocity scenario in the context of the present study.

90

70

80

60

90

20

70

39

10 8 6 4 2 0 37 36 35 34 Latitude 33 122 120 Longitude 116 118 114

San Andreas Fault Rupture Rupture Initiation Slip (peak=7.4m) Particle Velocity (peak=4.3m/s) Rupture time (peak=94.3s)

Slip (m)

Figure 8.2: Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault north-to-south rupture.

40

10 8 6 4 2 0 37 36 35 34 Latitude 33 122 120 Longitude 116 118 114

San Andreas Fault Rupture Rupture Initiation Slip (peak=7.4m) Particle Velocity (peak=1.0m/s) Rupture time (peak=94.3s)

Slip (m)

Figure 8.3: Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault north-to-south rupture, capped particle velocity case.

41 Strong motion data in tandem with teleseismic and GPS data is used to constrain the Denali earthquake nitesource model. To demonstrate that nite-source models can be signicantly improved by combining different types of data, a numerical experiment is conducted using the extensive strong motion dataset of the 1999 ChiChi earthquake. In addition to the data from many strong motion and GPS stations, twenty-one teleseismic P-waveforms downloaded from the Incorporated Research Institutions for Seismology (IRIS) data center have been included. Three nite-source models (Figure 8.4) are constructed: 1. In the rst case, teleseismic data alone is used to construct a single-plane fault model. The fault plane has a strike of 18 and a dip angle of 30 to the east. The location of the fault is dened using the hypocenter location obtained by the local network managed by Central Weather Bureau (CWB), Taiwan. The rupture plane is allowed to extend generously from surface to Moho and is divided into subfaults with dimensions of 5 km by 5 km. The inverted results are referred to as Teleseismic. 2. In the second case, teleseismic data is combined with GPS data for the inversion of the rupture history, this time on a more realistic 3-plane fault geometry constructed using static data only [47]. In this case, the vertical extension of fault plane is limited to 18 km based on the previous GPS inversion. The inverted results in this case are referred to as Tele+GPS. 3. In the third case, selected strong motion data is combined with GPS data and a more complex rise time function representation [22] is used to constrain the slip model. Given the abundant data involved and the care taken in its analysis, this model can be considered to be the most accurate representation of the actual rupture. It is labeled as Strong+GPS. Of the three models, the Teleseismic model explains the teleseismic data set the best. Adding the static data and using a realistic fault geometry only slightly decreases the waveform ts. This is consistent with the fact that the co-seismic eld dominates the GPS measurements [48]. In addition, it suggests that fault bending could not be resolved using teleseismic P waves alone. Adding other teleseismic phases, such as SH, may be able to resolve this. The slip distributions of Tele+GPS and Strong+GPS models are quite similar to each other but there are substantial discrepancies between these and the slip distribution of the Teleseismic model, particularly at the northern end. This is primarily due to the difference in the assumed fault geometry. However, the big asperities of the Teleseismic are still very similar to the preferred model, Strong+GPS, and not all events of this size have such radial geometrical complexity. For the Denali earthquake source inversion, all the above mentioned datasets have been used and fault geometry has been constructed based on the surface break. Taking into consideration the limited number of strong motion and GPS stations, the accuracy of the Denali earthquake source model can be considered to be similar to the Tele+GPS case discussed above. While it is possible that the ground shaking could be underestimated to some extent, the simulations resulting from the use of this source model would be sufciently reliable for the purposes of this study. Finally, for the case of the Denali earthquake source inversion, synthetic seismograms have been computed at Pump Station 10 which is the only near-fault station and they match very well with the data in both velocity and displacement (Figure 8.5). Note that the shortest period used in the inversion is 2 sec.

42

120 40'

121 00'

121 20' Observation

120 40'

121 00'

121 20' Teleseismic

24 20'

24 20'

24 00'

24 00'

23 40' 30 km

23 40' 30 km

120 40'

121 00'

121 20' Tele+GPS

120 40'

121 00'

121 20' Strong+GPS

24 20'

24 20'

24 00'

24 00'

23 40' 30 km

23 40' 30 km

30

60

90

120

150 cm/sec

180

210

240

270

300

Figure 8.4: 1999 ChiChi earthquake: Peak ground velocities.

43

Figure 8.5: Denali source inversion: Data (black) versus synthetic seismograms (red) for Pump Station 10 (3 km from the fault trace).

44

Chapter 9

Scenario 1: North-to-South Rupture of the San

Andreas Fault
The two techniques adopted by seismologists to simulate ground motion consist of either a deterministic or an empirical approach. In the deterministic approach, the elastic wave equation is solved numerically in a realistic 3-D Earth model and the ground motion is directly computed without any additional assumptions. In the case of the Los Angeles basin, the accuracy and frequency limitations depend on the quality of the 3-D Los Angeles basin model, which has improved steadily over the last decade, and on the numerical resolution of the 3-D seismic wave propagation simulation. For this study, one of the two well-accepted 3-D southern California Earth models, the Harvard-LA model [29], has been used (the other being the SCEC Community Velocity Model [49, 50, 51]). Both velocity models allow for the simulation of the basin response down to a shortest period of approximately 2 s [23]. The deterministic approach is considered the more reliable approach in the seismological society given the current state of knowledge. The second commonly used seismological approach consists of generating broadband ground motion through empirical methods that combine a stochastic approach at high frequencies with a deterministic approach at low frequencies [52, 53]. These methods are still nascent in their development. They are tailored for a given earthquake and have to be re-tuned on a case-by-case basis. Being empirical, they cannot be proved or validated consistently for various types of earthquakes, and hence they are not reliable enough at this stage. Given that the results of the study will not be affected signicantly by excluding high-frequency content (Chapter 6), the robust, deterministic (read reproducible) approach to simulating the ground-motions has been adopted for this prototype study. Using the spectral-element method, seismograms are computed at each of the 636 hypothetical tall-building sites (Figure 1.1). The minimum S wave velocity in the Harvard-LA basin model is 687 m.s 1 . The horizontal size of the mesh cells at the surface is approximately 270 m in each direction. The resulting number of grid points per S wavelength is about 5. The time step used for the computations is 9 ms, with a total number of 30000 steps, i.e., a total duration of 270 s. Shown in Figures 9.19.3 and 9.49.6 are maps of the three components of peak velocity and displacement, respectively, lowpass-ltered using a Butterworth lter with a corner period at 2 s. Gaussian smoothing over a nearest neighborhood interpolation scheme is used for all the maps. The solid circles in these maps correspond to the cities shown in Figure 1.1. The San Fernando valley experiences severe shaking. As the rupture proceeds down south from Parkeld and hits the bend in the San Andreas fault, it sheds off a signicant amount of energy into the region that is directly in front of it, which happens to be the San Fernando valley (see http://www.ce.caltech.edu/krishnan for a movie of the rupture and seismic wave propagation). A good portion of this energy spills over into the Los Angeles basin, with many cities along the coast such as Santa Monica and Seal Beach and more inland areas going East from Seal beach towards Anaheim experiencing long-duration shaking. In addition, the tail-end of the rupture sheds energy from SH/Love waves into the San Gabriel valley (Baldwin Park-La Puente region), which is bounded by a line of mountains that creates a mini-basin, further amplifying the ground motion. The peak velocity is of the order of 1 m.s1 in the Los Angeles basin, including downtown Los Angeles, and 2 m.s 1 in the San Fernando valley. The map of peak displacements has characteristics quite similar to that of the peak velocities, with signicant displacements in the basins but not in the mountains. The peak displacements are in the neighborhood of 1 m in the Los Angeles basin and 2 m in the San Fernando valley. To study the effects of the simulated ground motion on the two 18-story steel moment-frame buildings (Chapter 2) located at each of the 636 sites shown in Figure 1.1, computer models of the Woodland Hills existing and redesigned

45 buildings described in Chapter 2 are analyzed. As before, the analyses are performed using the FRAME3D program [30]. The peak interstory drift is the most reliable performance measure to evaluate structural performance. The Federal Emergency Management Agency (FEMA) proposes limits on the peak drift ratio for classifying building performance 1 . Another damage measure that can be used to rate structure performance is plastic rotation in beams, columns and panel zones. Plastic rotation at the ends of beams and columns is dened as the permanent rotation after unloading the element that has yielded in exure and is measured in radians or % of a radian. Panel-zone plastic rotation is dened as the unrecoverable permanent shear strain in the joint and is also measured in radians or % of a radians. Excessive plastic rotations in the panel zones, beams and columns indicate damage and structural degradation, important factors in collapse potential. These plastic rotations can be compared against the structural performance levels set by the FEMA [4]. Even though this FEMA document is meant for the seismic rehabilitation of existing buildings, in this study the same performance standards are utilized for the redesigned building model as well for comparison with the existing building model. The three structural performance levels specied in FEMA-356 are Collapse Prevention, Life Safety, and Immediate Occupancy in decreasing order of structural damage. The plastic rotations at the ends of beams and columns, and in the panel zones can be compared to the acceptable limits prescribed in FEMA-356 [4] for each of the performance levels, and based on this, the performance of each of these components can be classied into one of IO, LS, CP performance levels or, alternately, a collapsed state. In the modeling of the existing building beam-to-column connections, the fracture mode of failure that was widely observed during the Northridge earthquake is included. In the presence of weld-fracture, it is not clear how the performance levels can be assigned to beam-column components based on plastic rotations. For example, upon fracture of all bers at the end of a beam, its stiffness drops to zero under tension and the beam would not be able to carry additional moment and hence the beam-end rotation does not grow any further. For small fracture strains the connection may fracture, but since the rotation is small, the connection could receive a good performance rating. Thus, while technically a fractured connection should receive a CO rating, it may end up with an LS rating. Hence, for the existing building model it may be better to classify connection performance using the fracture index which represents the percentage of connections in the building that fractured. Since the Northridge earthquake, this defect has been corrected and this mode of failure is not expected in buildings built today. So for the redesigned building, the performance indices based on the plastic rotations may be reasonable. Despite the complications arising out of fracture, the performance indices based on plastic rotation are provided for the existing building as well for comparison with the redesigned building. The results corresponding to the performance of the building models based on the plastic rotations are presented in Appendices D and E. Nevertheless, it is better to judge the performance of the existing and redesigned building models based on the interstory drift measure as it is devoid of the subjectivity associated with the empirical limits proposed for plastic rotations. To put the results on existing buildings in perspective, note that while the population of tall buildings in southern California is quite widespread, a major fraction is located in downtown Los Angeles, the mid-Wilshire district (Beverly Hills), west Los Angeles, and Santa Monica. There are quite a few tall buildings spread across the San Fernando valley as well, e.g., in Woodland Hills and Canoga Park, and 30-40 tall buildings in Orange County (comprising the cities of Orange, Irvine, Costa Mesa, Newport Beach, Anaheim, Santa Ana, Garden Grove, etc.). A host of new tall buildings are being planned in Orange County with thirteen proposed high-rises in the cities of Anaheim and Santa Ana.
1 Since there is very little usable data to assess the performance of tall buildings based on calculated interstory drifts, in this study an empirical approach proposed by the Federal Emergency Management Agency (FEMA) is taken. For rehabilitation of existing buildings, FEMA 356 [4] denes three performance levels: Immediate Occupancy (IO) refers to a post-earthquake damage state in which very limited structural damage has occurred. The risk of life-threatening injury as a result of structural damage is very low, and although some minor structural repairs may be appropriate, these would generally not be required prior to reoccupancy. Life Safety (LS) is a post-earthquake damage state that includes damage to structural components but retains a margin against onset of partial or total collapse. Collapse Prevention (CP) refers to a post-earthquake damage state that includes damage to structural components such that the structure continues to support gravity loads but retains no margin against collapse. For existing buildings, the interstory drift limits for the IO, LS, and CP performance levels specied by FEMA are 0.007, 0.025, and 0.05, respectively. For the design of new steel moment-frame buildings, FEMA 350 [5] denes only two performance levels, the IO and CP levels. For buildings taller than 12 stories, the specied interstory drift limits for these levels are 0.01 and 0.06, respectively.

46 The results of the building analyses (see http://www.ce.caltech.edu/krishnan for movies of buildings swaying under the earthquake resulting in permanent tilt or collapse) corresponding to a north-to-south rupture of the San Andreas fault are summarized in Figures 9.7 through 9.12 for the existing 18-story steel building and Figures 9.13 through 9.17 for the new 18-story steel building. Gaussian smoothing over a nearest neighborhood interpolation scheme is used for all the maps. Figure 9.12 shows the percentage of connections where fracture occurs in the existing building. Fracture occurs in at least 25% of the connections in this building when located in the San Fernando valley. Note that the scale saturates at 25% and that this number is exceeded at many locations. About 10% of the connections fracture in the building when it is located in downtown Los Angeles and the mid-Wilshire district (Beverly Hills), while the numbers are about 20% when it is located in Santa Monica, west Los Angeles, Inglewood, Alhambra, Baldwin Park, La Puente, Downey, Norwalk, Brea, Fullerton, Anaheim, and Seal beach. Figures 9.7 through 9.9 show the peak interstory drift that occurs in the top-third, middle-third, and bottom-third of the existing building, respectively. Figure 9.10 collates these into a single map showing the peak drift occurring in the building. The fact that the peak interstory drifts in the middle-third and bottom-third of the existing building model are far greater than the top-third indicates that the damage is localized in the lower oors. The localization of damage in the lower oors rather than the upper oors could potentially be worse because of the risk of more oors pancaking on top of each other if a single story gives way. Peak interstory drifts beyond 0.10 are indicative of probable collapse, drifts beyond 0.06 are indicative of severe damage, while drifts below 0.01 are indicative of minimal damage not requiring any repairs. Consistent with the extent of fracture observed, the peak drifts in the existing building model exceed 0.10 when it is located in the San Fernando valley, Baldwin Park and neighboring cities, Santa Monica, west Los Angeles and neighboring cities, Norwalk and neighboring cities, and Seal Beach and neighboring cities, which is well into the postulated collapse regime (see footnote 1). Note that the scale saturates at 0.10, and in fact the drifts exceed this number in many locations in these regions. When located in downtown Los Angeles and the mid-Wilshire district, the building would barely satisfy the collapse prevention criteria set by FEMA [4] with peak drifts of about 0.05. Plotted on Figure 9.11 are the magnitude and direction of the permanent offset of the building at the penthouse level following the earthquake 2 . The length of the arrow is proportional to the magnitude. The scale is saturated at 1.5 m which corresponds roughly to an average inclination of 2% over the height of the building. The performance of the newly designed 18-story steel building is signicantly better than the existing building for the entire region. However, note that the new building has signicant drifts indicative of serious damage when located in the San Fernando valley or the Baldwin Park area. Figures 9.13 through 9.15 show the peak interstory drift that occurs in the top-third, middle-third, and bottom-third of the redesigned building, respectively. Figure 9.16 collates these into a single map showing the peak drift occurring in the building. When located in coastal cities (such as Santa Monica, Seal Beach etc.), the Wilshire corridor (west Los Angeles, Beverly Hills, etc.), the mid-city region (Downey, Norwalk, etc.) or the booming Orange County cities of Anaheim and Santa Ana, it has peak drifts of about 0.05, once again barely satisfying the FEMA collapse prevention criteria [5]. In downtown Los Angeles it does not undergo much damage in this scenario. Thus, even though this building has been designed according to the latest code, it suffers damage that would necessitate closure for some time following the earthquake in most areas, but this should be expected since this is a large earthquake and building codes are written to limit the loss of life and ensure collapse prevention for such large earthquakes, but not necessarily limit damage. Plotted on Figure 9.17 are the magnitude and direction of the permanent offset of the building at the penthouse level following the earthquake. The redesigned building too has large permanent offsets at many locations. For eight representative sites out of the 636 analysis sites, detailed results of building performance are given in Appendix F. These sites are located in Thousand Oaks, Northridge, West Los Angeles, Baldwin Park, Anaheim, Long
2 This permanent offset is a result of the irrecoverable plastic deformation in the structural components beams, columns, and joints. The building leaning in such a fashion would lead to scores of problems starting with misalignment of elevators. As an example, the 6 inch tilt in the Woodland Hills building following the Northridge earthquake led to misalignment in the elevators. Bringing the building back to plumb would inevitably result in building closure and signicant direct and indirect costs.

47 Beach, and Santa Ana. Of these, the existing building model is seen collapsing in Thousand Oaks and Northridge. Included in this appendix are snapshots of building deformation immediately following the earthquake, time histories of the three components of ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), time histories of the east and north components of the penthouse displacements of the existing and redesigned building models, tables detailing the performance of the structural components (plastic rotation in beams, columns, and panel zones), bar diagrams illustrating the peak interstory drifts over the height of the two building models, maps of plastic rotation in beams, columns, and panel zones, and, nally, maps of fracture locations in the moment-frames of the existing building. It should be mentioned that for the north-to-south rupture of the San Andreas fault considered here, if the slip distribution along the fault were like the 1857 earthquake, i.e., rising quickly to the peak value and then gradually dropping off [1], instead of the other way around, results could be quite different. Also, directivity can have a significant impact on ground shaking and the resulting building damage. For example, for a south-to-north rupture of the same earthquake described in the next chapter, building damage is far less severe.
1.8

0.2

Thousand Oaks
1.6
1.4

1.

34.25

1.8

Simi Valley
2

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 0.6
0.8

6
1.6
1. 4

Malibu
0.

34
1.2
0.6

Point Dume

Santa Monica
0.6

Montebello Inglewood Whittier


0.8

La Puente
1

0.8

Beverly Hills 0.6

0.8

1.2
1

1. 12

0.4

Hollywood

0.4

Monrovia Azusa Baldwin Park


0.6
0.4

Alhambra

Los Angeles

Diamond Bar Brea Fullerton

0.6

El Segundo

Downey Compton Norwalk

0.8

E-W Vel (m/s)

0.4

Torrance

0.6

Anaheim

Long Beach

33.75

Seal Beach
0.6

Santa Ana
0.6

Irvine Huntington Beach

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

-118.25 1.2 1.4 1.6

-118 1.8 2.0

-117.75

Figure 9.1: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas Fault ground shaking: Map of peak velocities (east component).

48
Simi Valley
1

34.25
1

Thousand Oaks

0.8

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
6 0. 0.8

Monrovia Azusa Baldwin Park La Puente


0.6
0.4
0.4

0.6
1.2

Beverly Hills Malibu Point Dume


0.6 Monica Santa

Hollywood 4
0.

Alhambra
0.6

0. 8

0. 4

Los Angeles

34
1

Montebello Inglewood Whittier Downey Compton


0.8

0.4

2 1.

0.4

1.4

0.

Torrance Long Beach


0.6

Anaheim

0.6

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach


0.4

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

-118.25 1.2 1.4 1.6

-118 1.8 2.0

0.6

Figure 9.2: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak velocities (north component).
0.6

0.8

Diamond Bar Brea

El Segundo

0.6

Norwalk

N-S Vel (m/s)

Fullerton

6 0.

-117.75

0.6

0.2

Simi Valley

34.25
Thousand Oaks
0.6

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Santa Monica Inglewood El Segundo
0.2
0. 2

Malibu Point Dume


0. 2

Los Angeles Montebello Whittier Downey Compton Norwalk


0.2

0.6

0.6

La Puente Diamond Bar


0.2

0.4

34

0.4

0.4

Monrovia Azusa Baldwin Park

0.

Alhambra

0. 2

Brea

Z Vel (m/s)
0.2

Fullerton Anaheim

0.4

Torrance Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

-118.25 1.2 1.4 1.6

-118 1.8 2.0

-117.75

Figure 9.3: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak velocities (vertical component).

49
1 .6

1.8

1.

34.25

1.4

1.4

Simi Valley .8
1

Thousand Oaks
1
1.

2
1

0.8

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.6 Pasadena
0. 4

0.2

1.6

1.4

1.8

1.6

Monrovia Azusa Baldwin Park


0.6
0.4

Hollywood Beverly Hills Santa Monica Inglewood


0.6

0.

0.6 Alhambra

Malibu

Los Angeles Montebello Whittier Downey Compton


0.6

34
1

Point Dume

La Puente Diamond Bar Brea Fullerton Anaheim

1.2

0.6

El Segundo

Norwalk

0.6

0.8

0.4

E-W Dis (m)

0.4

Torrance Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

-118.25 1.2 1.4 1.6

-118 1.8 2.0

-117.75

Figure 9.4: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (east component).
0.8

Simi Valley

34.25

Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank 0.8 North Hollywood Encino 0.6 Pasadena Hollywood Beverly Hills Alhambra
0. 6

0.4

Monrovia Azusa Baldwin Park La Puente


0.4

0.6

1.

Malibu

Los Angeles Montebello Whittier Downey Compton


0. 6

0.

0.6

0.

34

0.8

Point Dume

Santa Monica Inglewood El Segundo

Diamond Bar Brea Fullerton Anaheim

Norwalk

N-S Dis (m)


33.75

0.4

Torrance

Long Beach Seal Beach Santa Ana

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

0.4

Irvine Huntington Beach

-118.25 1.2 1.4 1.6

-118 1.8 2.0

-117.75

Figure 9.5: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (north component).

50

Simi Valley

34.25
Thousand Oaks

Chatsworth Northridge Canoga Park


0. 4

San Fernando Sunland La Canada Pasadena Alhambra Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim Long Beach
0.2

0.2

Encino

Burbank North Hollywood Hollywood

0.2

0.2

Beverly Hills Santa Monica Inglewood El Segundo


0.2

Malibu

Los Angeles Montebello Whittier Downey Compton


0.2

34

0.4

Point Dume

Norwalk
0.2

Z Dis (m)
33.75

0.2

Torrance

Seal Beach

Santa Ana

Irvine Huntington Beach

0.2

-119

-118.75 0.0 0.2 0.4

-118.5 0.6 0.8 1.0

-118.25 1.2 1.4 1.6

-118 1.8 2.0

-117.75

Figure 9.6: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault ground shaking: Map of peak displacements (vertical component).

51
Simi 0. Valley
04
0.03

0.04

0.04

34.25

0.05
0.04

0.03

Thousand Oaks
0.0 5

Chatsworth Northridge 7 05 0.0 0. Canoga Park


0. 05
0.

Encino

03

Burbank North Hollywood Hollywood Beverly Hills

La Canada Pasadena 0.02 Alhambra


3 0.0

0.04

0 0.
0. 01

Monrovia Azusa Baldwin Park


0.03

0.0

0.0 3

San Fernando Sunland


4 0.0

0.0

0.03

6 0.0

0.0 6

0.03

Malibu Point Dume


1 0.0

0.02

34

0.02 Santa

Monica Inglewood

Montebello Whittier
0.0 3

La Puente Diamond Bar Brea Fullerton


0.0

0.02

El Segundo

Downey

Compton
02 0.

Norwalk

Peak Drift in the Top Third of the Existing Building


33.75

Torrance
0.01

Long Beach Seal Beach Santa Ana

0.01

0.02

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

0.04

Los Angeles

Anaheim

Figure 9.7: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the top-third of the building.

0.02

0.05

0 .0

0.0 3

0.02

0.02

-117.75

52
Simi Valley San Fernando Sunland La Canada Burbank North Hollywood 0.02 Pasadena 0.05 Beverly Hills
.05 08 0 Santa 0. Monica
0.03

0.02

34.25
Thousand Oaks

Chatsworth Northridge Canoga Park


0.1 9 0 8 0.0 .0 0.07 0 0.06 0.05 .04 0.0

Encino
3

Hollywood 0 .03
08 0.

Alhambra
0.07

0.0

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea


0.0 3

0.0

1 0.

06 78 0. 0.0 0.0 .09 0

Malibu

0.

0.0 4

0.0

02

Los Angeles

34
0 0 0 .0 .0 .1 0 9 8 .0 7 0 6 .0 5 0 .0 0.0 43

Point Dume

0.1

Inglewood
0.0 8
0.1

6 0.0

Montebello Downey Compton


0.0 7

Whittier
4 0.0

7 08 0.0 0. 9 0.0

0.1
0.09

0.05

0.06 0.0 7

El Segundo
0. 05

Peak Drift in the Middle Third of the Existing Building


33.75
0.0 2

0 0.

Norwalk

0.

06

0.04 0.03

0.06 0 Torrance

0.0 7

.0

Fullerton Anaheim
0. 05

0.02

Long Beach
0 .1 Seal Beach 0. 08 0.09 0.07

0.06

0. Santa Ana 04

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 9.8: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the middle-third of the building.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.02 Pasadena 6 0.0 0.05
00 .0 .1 0 .0 980.
0.04

34.25
Thousand Oaks

0.02

.02

Malibu

2 0.0

Beverly Hills
0. 04
0 Monica Santa .08

Hollywood 0 .03

0.0
0. 07

8Alhambra

Baldwin Park 0
4

Los Angeles

.0

0.0

0.0

34
00 .0 .1 .0 98 00 .0 7 .0 0 6 .0 0 5 .0 04 .03

Point Dume
7

0.1

5 0.0 6 0.0 0.07

Montebello Whittier
0.

0.09

La Puente Diamond Bar Brea Fullerton

Inglewood
08

0.06

Compton
0.1
0.05

Peak Drift in the Bottom Third of the Existing Building

0.0 0.04 0.03

0.02

0.

04

Long Beach
0.1 9 Seal Beach 8 0.0 0.0 0.07

0.0

Torrance

0.0

0.04

El Segundo

Downey
0. 09

Norwalk
7

Anaheim

0.06

0.0

33.75
0.0 2

0.

03

Monrovia Azusa
0.0

07

0.0

0. 1

6 .0 8 .0.7 00 00

8 0.09 0.0

0.09 0.05

0.07

Santa 0. Ana 0
4

0.05

Irvine Huntington Beach

0.03

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 9.9: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios in the bottom-third of the building.

53
Simi Valley San Fernando Sunland La Canada
0.0 2

0.0

0.02

34.25
Thousand Oaks

Chatsworth Northridge Canoga Park


0.1 0.09 08 0.07 0. 0.06 0.04 0.05 0. 0
2

Encino
3

Burbank North Hollywood Hollywood 0 .03


4 0.0

Pasadena
0.06

Monrovia Azusa Baldwin Park


5 0.0

0.0

Malibu

0.0

Beverly Hills
8 Santa 0.0 Monica
0.05 6 0. 0.0 07

0.0 8

Alhambra
0.0 7

0.0

0.1

67 .0 .00 .08 9 00 0.0

Los Angeles

0 0 0 ..0 .1 0 0 9 8 .0 .0 0 7 6 .0 5 0 .0 0. 4 03

0.06

El Segundo

0.0

0.0 7

8
0.1

Downey Compton
0.05

0.04

0.1

0.1

34

Point Dume

Montebello

La Puente Diamond Bar Brea Fullerton Anaheim


0. 03

Inglewood

Whittier
0.05

0.07

Existing Building Drift Index


33.75
0.0 2

0.0 0.04 0.03

0.06 Torrance

0.02

Long Beach
0.06
0.0 5
0. 1 Seal Beach 08 0.0.09 0.07
0. Ana Santa 0 4

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

0.0 7 0. 06

Figure 9.10: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Peak drift ratios anywhere in the building.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra

08 0.0.09

Norwalk

0.09

09 0.

-117.75

34.25
Thousand Oaks

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Permanent Tilt (m) at the Penthouse of the Existing Building (Arrow denotes tilt direction)
33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2

-118.5 0.4 0.6 0.8

-118.25 1.0 1.2

-118 1.4

-117.75

Figure 9.11: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Permanent offset at the penthouse level.

54

22 .5 25

20

Simi Valley

34.25

Thousand Oaks

25

.5 20 22

15

.5

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood 17 5 Encino .5 Pasadena 10 7.5
2. 5
2.5

25

12

22.5

Hollywood Beverly Hills


7.5
12.5

12.5

Monrovia 1Azusa 0 Baldwin Park


7.5
12.5 15

Alhambra
17.5 15

Malibu Point Dume

Los Angeles

25

20 22.5

34

Santa Monica
17.5

10
12.5 Inglewood

Montebello Downey Compton


15
10

La 17.5

Puente Diamond Bar Brea

Whittier Norwalk
12.5
12.5

17.5

7.5

El Segundo
12.5

15

10

Existing Building Connection Fracture 2. 5 Percentage

15 12.5

Fullerton Anaheim

12

.5

2.5

10 7.5

Torrance

Long Beach

33.75
2.5
10

Seal Beach
12. 5

Santa Ana

10

15

Irvine Huntington Beach


7.5

10

-119

-118.75 0.0 4.5

-118.5 9.0

-118.25 13.5 18.0

-118 22.5

-117.75

Figure 9.12: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections that fracture (out of a total of 710 connections with the two ends of each moment-frame beam and column dened as connections).

55
0.03
0.02

Simi Valley
0. 04

34.25

0.03

Thousand Oaks
0.03

0.0

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 2 .0
0

0. 02

34

Point Dume
0.01
0.0 1

Santa Monica Inglewood

0.03

Montebello Downey Compton Norwalk


0.02

Whittier Brea

0.03

0 .0 4

Monrovia 0.02 Azusa


02 0.
0.03

2 0.0

.03
0.0

Hollywood
1

Beverly Hills

Alhambra
2 0.0

Baldwin Park La Puente Diamond Bar

Malibu

Los Angeles

0.02

El Segundo

0.0 2

Peak Drift in the Top Third of the New Building


33.75

Fullerton
0.0 2

Torrance
0.0 1

Anaheim Long Beach


0.02

0.02

Seal Beach

Santa Ana

Irvine Huntington Beach


0.01

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 9.13: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the top-third of the building.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 2 0.0 0.0 Pasadena 3
0.0 4
0.04
0.02

0.02

0.0 9

34.25

0.1

Thousand Oaks

0.02

Malibu
0.0 3

0.05

Inglewood El Segundo
0.0 4
0.

0. 03

0.

34

Point Dume
02

0.1

0.04

04

Whittier 0

0.0

Santa Monica

Montebello Downey Compton Norwalk


0.0

La Puente Diamond Bar Brea

.06

0.03

Peak Drift in the Middle Third of the New Building

0.0

0.01

Long Beach Seal Beach


0.0 4

0.

-119

0.01

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

0.0

Irvine Huntington Beach


3

-117.75

Figure 9.14: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the middle-third of the building.

0.03

33.75

03

0.02

Santa Ana

0.02

Torrance

0.05

Fullerton Anaheim

0.05

Los Angeles

0.

0.0 0.1 9 0.08 76 0.0 0.05 0.0

Hollywood

0.03

Monrovia Azusa 0 Baldwin Park


.03 0.04

Beverly Hills

0.

06

09

Alhambra
0.05

.08 0 0.07

0.06

0.04

03 0.

4 0.0

56
0.08

0.01

0.01

Simi Valley

34.25
.1 00 .08
0.
0.06

Thousand Oaks

San Fernando Sunland 4 Chatsworth 0.0 Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.03 Pasadena
0.04
0.02
2 0.0 Hollywood

0.0 9 0.1
0.07

Monrovia 0.02 Azusa


6
0 Baldwin 0.0 4 Park

09

09 .1 .0 08 6 .0 0.05 .0 0 7 0 .0

Malibu Point Dume

0.0
0.04

Beverly Hills

0.0

Los Angeles

0.06

Alhambra
0.0

0.03 0.

0.05

Inglewood
0.03 0.0 2

Peak Drift in the Bottom Third of the New Building

0 0.

0.03

0.

05

El Segundo
0. 04

Downey Compton Norwalk


0. 04

0.0

34

Santa Monica

Montebello Whittier
0.05

La Puente Diamond Bar Brea Fullerton Anaheim


3 0.0
6

0.0 4

0.02

0.04

Torrance
0.01

Long Beach
.03 Seal 0

Irvine Huntington Beach


0.
0.01
0.03

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 9.15: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the bottom-third of the building.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.02 0.0 Pasadena 3 4
0.0 5

0.02

34.25

Thousand Oaks

0.0

0.1 0.0 9

0.0

0.08

09 .1 0.0 86 .0 0 .0.05 0 7 0.0 0

0.02

Beverly Hills Malibu


0.0

Hollywood

0.03

Monrovia 0.0 Azusa


3 0.0 4 0.Baldwin 05

Alhambra
0.06
0.0 6

Park

Los Angeles

0.05

0.

34

0.0 4

Point Dume
02

Santa Monica
0.04

Montebello Inglewood
0.04

La Puente Diamond Bar Brea Fullerton


0.02
6 5 0.04 0.0 0.0

Whittier Downey Norwalk


0.05
0.0 4

0.03

El Segundo
0.04

Compton

0.01

Long Beach
4
0.03

33.75

Seal Beach
0.0 4

0.0

Irvine Huntington Beach


0.03

-119

0.01

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

0.0

New Building Drift Index

0.02

Torrance

Anaheim
3

Santa Ana

-117.75

Figure 9.16: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault Redesigned Building Performance: Peak drift ratios anywhere in the building.

0.03

0.02

0.02

33.75

Beach

Santa Ana

0. 04

02

0.0 9 0.1
0.07
0.06

0.0 3

57

Simi Valley

34.25
Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Alhambra

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Malibu

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Permanent Tilt (m) at the Penthouse of the New Building (Arrow denotes tilt direction)
33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2

-118.5 0.4 0.6 0.8

-118.25 1.0 1.2

-118 1.4

-117.75

Figure 9.17: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas Fault redesigned building performance: Permanent offset at the penthouse level.

58

Chapter 10

Scenario 2: South-to-North Rupture of the San

Andreas Fault
A natural question to ask is what would happen if the rupture were to proceed from south to north instead of the other way around with the peak slip occurring close to Parkeld. The results of such a scenario (surface slip for which is shown in Figure 10.1), presented in this chapter, indicate that ground shaking would be far less severe. This demonstrates the effect of directivity and slip distribution in dictating the level of ground shaking and the associated damage in buildings. Shown in Figures 10.210.4 and 10.510.7 are the peak velocities and displacements, respectively, of the ground motion time-histories lowpass-ltered using a Butterworth lter with a corner period at 2 s. While the San Fernando valley still experiences the most shaking, Santa Monica and, to some extent, Baldwin Park are not too far behind. The peak velocities are of the order of 0.6 m.s1 in the San Fernando valley, 0.5 m.s1 in Santa Monica and El Segundo, and 0.3 m.s1 in the remaining parts of Los Angeles and Orange Counties. The corresponding peak displacements are in the range of 0.5-0.6 m in the San Fernando valley, 0.4-0.5 m in Santa Monica and El Segundo, and 0.3-0.4 m in the remaining parts of Los Angeles and Orange Counties. The reduced level of shaking is reected in the results of the building analyses (Figures 10.810.13 for the existing building model and Figures 10.1410.18 for the redesigned building model). Figure 10.13 shows the percentage of connections where fracture occurs in the existing building model. Fracture occurs in 37% of the connections in this building when located in the San Fernando valley. About 45% of the connections fracture in the building model when it is located in Santa Monica or El Segundo. In most other areas, there is little or no risk associated with moment-frame connection fractures. Figures 10.8 through 10.10 show the peak interstory drift that occurs in the top-third, middlethird, and bottom-third of the existing building, respectively. Figure 10.11 collates these into a single map showing the peak drift occurring in the building. As for rupture scenario 1, the peak interstory drifts in the middle-third and bottom-third of the existing building are greater than the top-third which indicates that the damage is localized in the lower oors. Peak interstory drifts beyond 0.06 are indicative of severe damage, while drifts below 0.01 are indicative of minimal damage not requiring any repairs. Peak drifts are in the neighborhood of 0.03 in the San Fernando valley, Santa Monica, El Segundo and Baldwin Park. Peak drifts in most other areas are less than 0.02. Plotted on Figure 10.12 are the magnitude and direction of the permanent offset of the existing building model at the penthouse level following the earthquake. Once again, the length of the arrow is proportional to the magnitude. There is negligible permanent tilting of the existing building model in the entire domain of the analysis. This is dramatically different from scenario 1 results once again revealing the role of directivity and slip distribution in dictating the level of damage. The performance of the newly designed 18-story steel building is slightly better than the existing building for the entire region. Figures 10.14 through 10.16 show the peak interstory drift that occurs in the top-third, middle-third, and bottom-third of the redesigned building, respectively. Figure 10.17 collates these into a single map showing the peak drift occurring in the building. Peak drifts are in the neighborhood of 0.020.03 when the building model is located in the San Fernando valley, Santa Monica, El Segundo and Baldwin Park. Building peak drifts in most other areas are in the neighborhood of 0.01. Plotted on Figure 10.18 are the magnitude and direction of the permanent offset of the redesigned building model at the penthouse level following the earthquake. To summarize, the results for both the existing and redesigned building models indicate that there is no signicant danger of collapse. However, damage would still be signicant enough to warrant building closures and compromise life safety in some instances.

59

10 8 6 4 2 0 37 36 35 34 Latitude 33 122 120 Longitude 116 118 114

San Andreas Fault Rupture Rupture Initiation Slip (peak=7.4m) Particle Velocity (peak=4.3m/s) Rupture time (peak=94.3s)

Slip (m)

Figure 10.1: Surface slip, particle velocity, and rupture time, for the simulated magnitude 7.9 earthquake on the San Andreas fault south-to-north rupture

60
0.
0.5

0.5

Simi Valley
0.4

34.25

Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.6 Pasadena
0.4

0.5

0.3

0.6

Monrovia Azusa Baldwin Park


0.1
0.2

0.2

0.1

Beverly Hills
0.2

Hollywood 0.
1

0.3

Alhambra

0.

Malibu

Los Angeles Montebello Whittier


0.2

34

Point Dume

Santa Monica
3 0.
0.4

La Puente

Inglewood

Diamond Bar Brea Fullerton Anaheim

0.3

0.2

0.4

El Segundo

Downey Norwalk
0.2

Compton

E-W Vel (m/s)


0.1

0.2

Torrance Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4 0.5

-118.25 0.6 0.7 0.8

-118 0.9 1.0

0.2

-117.75

Figure 10.2: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (east component).
0.1

Simi Valley
0.4

34.25

0.4
3

Thousand 0 Oaks .2
0.3 0.2
0. 3

0.

San Fernando Sunland Chatsworth Northridge 0.2 La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills
0.1

Monrovia Azusa Baldwin Park La Puente


0.1

Alhambra

34

0.

Malibu

Los Angeles Montebello Whittier Downey Compton Norwalk Brea Fullerton


0.2

Point Dume

Santa Monica

Inglewood El Segundo
0.2

Diamond Bar

N-S Vel (m/s)


0.2

0.1

Torrance Long Beach Seal Beach

Anaheim

33.75

Santa Ana

Irvine .2 Huntington0Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4 0.5

-118.25 0.6 0.7 0.8

-118 0.9 1.0

-117.75

Figure 10.3: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (north component).

0.1

0.3

0.2

61
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra
0. 1

34.25

0.1

Thousand Oaks
0.1

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier


0.1

34

Point Dume

Santa Monica Inglewood El Segundo


0.1

Downey

Compton

Norwalk

0.1

0.1

Z Vel (m/s)

Torrance Long Beach

33.75

Seal Beach
0.1

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4 0.5

-118.25 0.6 0.7 0.8

-118 0.9 1.0

-117.75

Figure 10.4: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak velocities (vertical component).
0.56
0.64
0.16

Simi Valley

0.56
0.24

Encino

0.3

Thousand Oaks

Burbank North Hollywood Hollywood Beverly Hills

0.4

La Canada Pasadena

Alhambra

0.4

0.08

34.25
0.56 0.48 0.4

Chatsworth Northridge 0.4 8 Canoga Park

San Fernando Sunland

Monrovia Azusa Baldwin Park La Puente


0.16
0.2 4

34

0.0 4 3. 2

0.4

Point Dume

0.

16

Malibu

Los Angeles 0.1 6 Montebello Whittier Downey Compton


0.
0.1

0.32

0.24

0.32

Santa Monica
0.

El Segundo

24 0.32

Inglewood

Diamond Bar Brea Fullerton Anaheim


0. 24

0.4

Norwalk

0.1

E-W Dis (m)

0.24

Torrance

16

0.16

Long Beach Seal Beach Santa Ana

33.75

Irvine Huntington Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4

-118.25 0.5 0.6

-118 0.7 0.8

-117.75

Figure 10.5: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (east component).

62
0.16

0.08

34.25
0.4

0.2

0.48

Thousand Oaks

0.24

0.3

Monrovia Azusa Baldwin Park


0.16

0.48

0.3

.16

Hollywood Beverly Hills

Alhambra

0.24

Malibu
0.2 4

Los Angeles Montebello

34

Point Dume

Santa Monica

La Puente Diamond Bar Brea Fullerton Anaheim

Inglewood El Segundo
0.24

Whittier Downey
0 Norwalk .16

Compton
0. 24

N-S Dis (m)

0.16

0.16

Torrance

Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4

-118.25 0.5 0.6

-118 0.7 0.8

-117.75

Figure 10.6: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (north component).
0.08
0.16

Simi Valley
0.16

34.25

Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
0.08
0. 08

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood Beverly Hills


0.1

Alhambra

34

Point Dume

Malibu

Los Angeles Montebello Whittier 0 Downey Compton


.08

Santa Monica Inglewood El Segundo

Norwalk

Z Dis (m)

0.08

0.08

Torrance Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.1 0.2

-118.5 0.3 0.4

-118.25 0.5 0.6

-118 0.7 0.8

-117.75

Figure 10.7: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault ground shaking: Map of peak displacements (vertical component).

0.08

Simi Valley
0.4

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
4 0.2
0.16

0.24

63
0.01

Simi Valley

34.25
Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
0 .0 1

Monrovia Azusa
1

0.0

Malibu
0.0 1

34

Point Dume

Santa Monica
0.0

Montebello Inglewood
1

Whittier Downey Compton Norwalk Brea

0.0

0.01

Hollywood Beverly Hills

Alhambra

Baldwin Park La Puente Diamond Bar

Los Angeles

El Segundo

Peak Drift in the Top Third of the Existing Building


33.75

Fullerton Anaheim

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.8: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the top-third of the building.

64
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.02 Pasadena
0.01

34.25

0.0

0.02

0.02

0.0

0.0

0.02

0.01

34

Point Dume
3
1

Montebello Whittier Downey Compton Norwalk

0.0 1

Malibu

Santa Monica

0.01

0.

Los Angeles
01

0.01

0.04

Thousand Oaks

0.02

0.02

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood Beverly Hills

Alhambra

Inglewood El Segundo
0.02

Peak Drift in the Middle Third of the Existing Building


33.75

0.0

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.9: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the middle-third of the building.
0.0 3

0.

03

Simi Valley
0. 02

34.25

Thousand Oaks

0.02

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank Encino .02 North Hollywood 0 Pasadena
0.01

0.0

0.0

0.0

0.01

34
0.02

0.0

Point Dume
3

0.02

Inglewood

Whittier Downey Compton Norwalk Brea

0.0

Malibu

Santa Monica

0.01

0.0

Los Angeles
1

0.01

0.04
0.02

Monrovia Azusa Baldwin Park La Puente Diamond Bar

Hollywood Beverly Hills

Alhambra

Montebello

.03

El Segundo
0.01

Peak Drift in the Bottom Third of the Existing Building


33.75

Fullerton Anaheim

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.10: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios in the bottom-third of the building.

65
0.0 3
0.03

Simi Valley

34.25

Thousand Oaks

0.02

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 0.02 Pasadena
0.01

0.02

0 .0

34

Point Dume
3
0 .0 1

0.

02

Montebello Whittier Downey Norwalk

0.0

Malibu

Santa Monica
0.02

0.01

0.

Los Angeles
01

0.01

0.04

0.02

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood Beverly Hills

Alhambra

Inglewood 0.01

0.0

El Segundo
0.01

Compton

Existing Building Drift Index


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.11: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Peak drift ratios anywhere in the building.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra

34.25
Thousand Oaks

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Permanent Tilt (m) at the Penthouse of the Existing Building (Arrow denotes tilt direction)
33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2

-118.5 0.4 0.6 0.8

-118.25 1.0 1.2

-118 1.4

-117.75

Figure 10.12: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Permanent offset at the penthouse level.

66

Simi Valley
7.5

34.25

Thousand Oaks
2.5

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park 2.5 Burbank Encino 2.5 North Hollywood Pasadena Hollywood Beverly Hills Alhambra

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Malibu

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica
2.5

Inglewood

El Segundo

2.5

Existing Building Connection Fracture Percentage

2.5

Torrance Long Beach Seal Beach

33.75

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 4.5

-118.5 9.0

-118.25 13.5 18.0

-118 22.5

-117.75

Figure 10.13: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections that fracture (out of a total of 710 connections with the two ends of each moment-frame beam and column dened as connections).

67
0.01
0.01

Simi Valley

34.25
Thousand Oaks
0.01

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
0. 01

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood Beverly Hills

Alhambra

Malibu
0.0

Los Angeles Montebello Whittier Downey Compton Norwalk

34
0.01

Point Dume

Santa Monica

0.01

Inglewood El Segundo

Peak Drift in the Top Third of the New Building


33.75

0.

01

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.14: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the top-third of the building.
0.0 2

Simi Valley

34.25
0.02

Thousand Oaks

0.02

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 0.01 Hollywood Beverly Hills Alhambra

01

0.

34
1 0.0

Inglewood El Segundo
0.0 1

Whittier Downey Compton Norwalk

0.01

0.0

0.03

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

0.02

Malibu Point Dume

Los Angeles Montebello

Santa Monica

Peak Drift in the Middle Third of the New Building


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.15: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the middle-third of the building.

68
Simi Valley
3 0.0

34.25

Thousand Oaks

0.0

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 0.01 Hollywood Beverly Hills Alhambra

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

0.02

0.02

Malibu

Los Angeles Whittier Downey Compton Norwalk


0.01

34
0.0 1

0.02

Inglewood El Segundo
0.0 1

Peak Drift in the Bottom Third of the New Building


33.75

Torrance Long Beach Seal Beach

0.0

Point Dume

Santa Monica

Montebello

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.16: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Peak drift ratios in the bottom-third of the building.
0.0 2

Simi Valley
0.0

34.25

Thousand Oaks
0.02

0.02

0.0

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 0.01 Hollywood Beverly Hills Alhambra

34
1 0.0

0.0

0.02

Inglewood El Segundo
0.0 1

Whittier Downey Compton Norwalk

0.01

New Building Drift Index


33.75

3
0.0 2

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Malibu Point Dume

Santa Monica

0.

01

Los Angeles Montebello

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.00 0.02

-118.5 0.04

-118.25 0.06 0.08

-118 0.10

-117.75

Figure 10.17: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Peak drift ratios anywhere in the building.

69

Simi Valley

34.25
Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Alhambra

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Malibu

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Permanent Tilt (m) at the Penthouse of the New Building (Arrow denotes tilt direction)
33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0.0 0.2

-118.5 0.4 0.6 0.8

-118.25 1.0 1.2

-118 1.4

-117.75

Figure 10.18: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Permanent offset at the penthouse level.

70

Chapter 11

Conclusions

Comprehensive end-to-end simulations of two magnitude 7.9 earthquakes on the San Andreas fault and the resulting damage on models of an existing and a redesigned 18-story steel moment-frame building have been performed. The 2002 Denali earthquake nite-source model has been mapped to the San Andreas fault and ground motions in the southern California region are computed at 636 chosen sites for two rupture scenarios (a) north to south with rupture initiating at Parkeld; and (b) south to north with rupture terminating at Parkeld. 3-D computer models of an existing building in Woodland Hills that got damaged during the 1994 Northridge earthquake and the same building redesigned according to the 1997 Uniform Building Code are analyzed for the three-component ground motion (lowpass-ltered using a Butterworth lter with a corner period of 2 s) at each of the 636 considered sites. Performance of the building models has been classied primarily based on the peak interstory drift ratio. The following are the conclusions of this study: 1. For the north-to-south rupture scenario, the peak ground velocity is of the order of 2 m.s 1 in the San Fernando Valley and 1 m.s1 in the Los Angeles basin, while the corresponding numbers for the south-to-north rupture scenario are 0.6 m.s1 and 0.4 m.s1 , respectively. 2. For the north-to-south rupture scenario, the peak ground displacement is of the order of 2 m in the San Fernando Valley and 1 m in the Los Angeles basin, while the corresponding numbers for the south-to-north rupture scenario are 0.6 m and 0.4 m respectively. The stark contrast between the ground motions in the two cases is an illustration of the effects of directivity and slip distribution in dictating the intensity of ground motion. 3. Under the ground motion from the north-to-south rupture, peak drifts in the existing building model far exceed 0.10 in the San Fernando Valley, Santa Monica and West Los Angeles, Baldwin Park and neighboring cities, Compton and neighboring cities, and Seal Beach and neighboring cities. Peak drifts are in the 0.060.08 range in Huntington Beach, Santa Ana, Anaheim and neighboring cities, while the numbers are in the 0.040.06 range for the remaining areas including downtown Los Angeles. Peak drifts exceeding 0.10 are indicative of probable collapse, while drifts exceeding 0.06 are indicative of severe damage. Peak drifts in excess of 0.025 could compromise life-safety. 4. The results for the redesigned building are better than the existing building. However, the peak drifts in many areas in the San Fernando valley still exceed 0.10, and they are in the range of 0.040.06 for most cities in the Los Angeles basin. While this may not conclusively be indicative of collapse, it certainly points to signicant damage and may result in building closures. 5. Under the ground motion from the south-to-north rupture, the peak drifts in existing and redesigned building models are in the range of 0.020.04, indicating that there is no signicant danger of collapse. However, this is indicative of damage signicant enough to warrant building closures and compromise life safety in some instances. Finally, these conclusions are particular to the two 18-story steel moment-frame buildings considered in the study. Other buildings with varied conguration, constructed with other materials, and having distinct frequency content could have damage patterns quite different from the results presented here. Having said this, the fact remains that the potential for a big earthquake with a large amount of slip on the San Andreas fault exists, and with the current state

71 of knowledge of the southern Californian Earth structure, this study indicates that serious damage occurs in these two 18-story steel moment-frame buildings in at least one of the plausible scenarios.

72

Chapter 12

Future Research

The eld of end-to-end simulations is still nascent in its development and is the wave of the future. The advent of parallel computing as a seismological tool in the last decade has revolutionized the eld. As more data becomes available, simulations can be validated and improved tremendously. In the coming decade, it is inevitable that this eld will take center-stage in the assessment of infrastructure in the United States and elsewhere. Future work in this area could involve one or many of the following aspects: 1. Improving the source models: This requires data gathering for earthquakes of various magnitudes on the faults of interest in a given region. It is crucial to not only have a greater number of data sets, but also have a variety of data types. Combinations of GPS, strong motion and teleseismic data sets yield the best results in terms of characterizing the source. 2. This work needs to be extended to other faults in southern California so that a broad picture of risk associated with regional earthquakes emerges. Some important faults in the region which require immediate attention are the Newport-Inglewood and Santa Monica-Hollywood-Raymond fault systems in addition to blind-thrust faults such as the Puente Hills fault under downtown Los Angeles. 3. The Earth velocity model needs to be improved to enable reliable simulation of broad-band ground motion. This is especially critical for the assessment of short structures (including wood-frame structures). This requires the procurement of large amounts of data from future earthquakes. 4. Validation of the numerical procedures, both seismological and structural, require ground-motion and buildingmotion and building-damage data from future earthquakes. Items 1 through 4 call for increased seismic instrumentation in the region including extensive instrumentation of building and other civil structures. 5. This work needs to be extended to other types of buildings. These should be classied based on type of lateral system, material (reinforced concrete, steel, wood etc.), geometry (height, plan), and function (residential, commercial, etc.). 6. Improving structural component and assembly modeling . This involves eliminating some of the limitations of this study described in Chapter 4 including, but not limited to, soil-structure interaction, column splices, column local ange buckling, composite action of beams, stiffness from partitions and elevator/stair enclosures, etc. 7. Including the top-soil layer in the ground motion simulation. 8. Performing similar analyses in other regions in the world. To start with, this involves instrumenting the region, recording data from regional and distant earthquakes, and creating and validating regional Earth models. Once the computational infrastructure is ready, the procedures described in this study can be adopted to perform end-to-end simulations.

73

Appendix A

Section Database

The sizes of box-sections used for beams and columns in the redesigned building (see Appendix C for beam and column sizes) are provided in this appendix. The sizes of wide-ange sections shown in Appendices B and C are taken from the AISC LRFD manual of steel construction [54]. Section Designation B14x14x171 B16x16x227 B18x18x282 B20x20x352 B22x22x430 B30x24x668 H (m) 0.350 0.400 0.450 0.500 0.550 0.750 B (m) 0.350 0.400 0.450 0.500 0.550 0.600 Tf (m) 0.025 0.029 0.032 0.036 0.040 0.045 Tw (m) 0.025 0.029 0.032 0.036 0.040 0.055

74

Appendix B

Existing Building Frame Elevations and Beam

and Column Sizes

75
EW FRAME (1) ALONG GRID A: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")
W30x99

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x311 W36x135 W14x43 W14x311 W36x150 W14x311 W36x150 W14x43 W14x311 W36x170 W14x61 W14x342 W36x170 W14x61 W14x342 W36x194 W14x74 W14x370 W36x194 W14x74 W14x370 W36x230 W14x90 W14x398 W36x230 W14x90 W14x398 W36x230 W14x99 W14x426 W36x230 W14x99 W14x426 W36x230 W14x455 W36x230 W14x120 W14x455 W36x230 W14x132 W14x500 W36x230 W10x33 W14x132 W14x500 W36x300 W12x65 W14x159 W14x730 W36x300

W14x311 W36x135 W14x311 W36x150 W14x311 W36x150 W14x311 W36x170 W14x342 W36x170 W14x342 W36x194 W14x370 W36x194 W14x370 W36x230 W14x398 W36x230 W14x398 W36x230 W14x426 W36x230 W14x426 W36x230 W14x455 W36x230 W14x455 W36x230 W14x500 W36x230 W14x500 W36x300 W14x730 W36x300 W14x730 W14x500 W14x500 W14x455 W14x455 W14x426 W14x426 W14x398 W14x398 W14x370 W14x370 W14x342 W14x342 W14x311 W14x311

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464")
W8x24

W14x43

W14x311

W14x120

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x730

W12x65

W14x159

W14x730

W14x730

W14x730

W14x730

Figure B.1: Frame 1 elevation: Existing building

76
EW FRAME (2) ALONG GRID B: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x61

W14x68

W14x68

W14x61

W14x311

W14x61

W14x68

W14x68

W14x61

W14x311

4.78 m (158") Level 17F El. 65.63 m (2154")

W14x311

W14x68

W14x90

W14x90

W14x68

W14x311

3.96 m (130") Level 16F El. 61.67 m (2024")

W14x311

W14x68

W14x90

W14x90

W14x68

W14x311

3.96 m (130") Level 15F El. 57.71 m (1894")

W14x342

W14x90

W14x109

W14x109

W14x90

W14x342

3.96 m (130") Level 14F El. 53.75 m (1764")

W14x342

W14x90

W14x109

W14x109

W14x90

W14x342

3.96 m (130") Level 13F El. 49.78 m (1634")

W14x370

W14x120

W14x132

W14x132

W14x120

W14x370

3.96 m (130") Level 12F El. 45.82 m (1504")

W14x370

W14x120

W14x132

W14x132

W14x120

W14x370

3.96 m (130") Level 11F El. 41.86 m (1374")

W14x398

W14x143

W14x159

W14x159

W14x143

W14x398

3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114")

W14x398

W14x143

W14x159

W14x159

W14x143

W14x398

W14x426

W14x176

W14x193

W14x193

W14x176

W14x426

3.96 m (130") Level 8F El. 29.97 m (984")

W14x426

W14x176

W14x193

W14x193

W14x176

W14x426

3.96 m (130") Level 7F El. 26.01 m (854")

W14x455

W14x193

W14x211

W14x211

W14x193

W14x455

3.96 m (130") Level 6F El. 22.05 m (724")

W14x455

W14x193

W14x211

W14x211

W14x193

W14x455

3.96 m (130") Level 5F El. 18.09 m (594")

W14x500

W14x283

W14x233

W14x233

W14x283

W14x500

3.96 m (130") Level 4F El. 14.12 m (464")

W14x500

W14x283

W14x233

W14x233

W14x283

W14x500

3.96 m (130") Level 3F El. 10.16 m (334")

W14x730

W14x283

W14x283

W14x283

W14x283

W14x730

3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x730

W14x283

W14x283

W14x283

W14x283

W14x730

Figure B.2: Frame 2 elevation: Existing building

77
EW FRAME (3) ALONG GRID C: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x61

W14x68

W14x68

W14x68

W14x311

W14x61

W14x68

W14x68

W14x68

W14x311

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464") 3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x311

W14x82

W14x90

W14x90

W14x90

W14x311

W14x311

W14x82

W14x90

W14x90

W14x90

W14x311

W14x342

W14x99

W14x109

W14x120

W14x109

W14x342

W14x342

W14x99

W14x109

W14x120

W14x109

W14x342

W14x370

W14x132

W14x132

W14x145

W14x132

W14x370

W14x370

W14x132

W14x132

W14x145

W14x132

W14x370

W14x398

W14x159

W14x159

W14x176

W14x159

W14x398

W14x398

W14x159

W14x159

W14x176

W14x159

W14x398

W14x426

W14x176

W14x193

W14x211

W14x193

W14x426

W14x426

W14x176

W14x193

W14x211

W14x193

W14x426

W14x455

W14x211

W14x211

W14x233

W14x211

W14x455

W14x455

W14x211

W14x211

W14x233

W14x211

W14x455

W14x500

W14x233

W14x233

W14x257

W14x233

W14x500

W14x500

W14x233

W14x233

W14x257

W14x233

W14x500

W14x730

W14x283

W14x283

W14x311

W14x283

W14x730

W14x730

W14x283

W14x283

W14x311

W14x283

W14x730

Figure B.3: Frame 3 elevation: Existing building

78
EW FRAME (4) ALONG GRID D: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")
W30x99

9.55 m (314")
W30x99

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x311 W33x141 W14x311 W14x311 W33x152 W14x311 W14x311 W33x152 W14x311 W14x311 W33x201 W14x342 W14x342 W33x201 W14x342 W14x342 W33x221 W14x370 W14x370 W33x221 W14x370 W14x370 W33x241 W14x398 W14x398 W33x241 W14x398 W14x398 W33x241 W14x426 W14x426 W33x241 W14x426 W14x426 W33x241 W14x455 W14x455 W33x241 W14x455 W14x455 W33x241 W14x500 W33x241 W14x500 W14x500 W33x241 W14x500 W14x730 W36x300

W14x311 W33x141 W14x311 W33x152 W14x311 W33x152 W14x311 W33x201 W14x342 W33x201 W14x342 W33x221 W14x370 W33x221 W14x370 W33x241 W14x398 W33x241 W14x398 W33x241 W14x426 W33x241 W14x426 W33x241 W14x455 W33x241 W14x455 W33x241 W14x500 W33x241 W14x500 W33x241 W14x730 W36x300

W14x311

W14x61

W14x311

W14x61

W14x311

4.78 m (158") Level 17F El. 65.63 m (2154")

W14x311

W14x82

W14x311

3.96 m (130") Level 16F El. 61.67 m (2024")

W14x311

W14x82

W14x311

3.96 m (130") Level 15F El. 57.71 m (1894")

W14x342

W14x99

W14x342

3.96 m (130") Level 14F El. 53.75 m (1764")

W14x342

W14x99

W14x342

3.96 m (130") Level 13F El. 49.78 m (1634")

W14x370

W14x132

W14x370

3.96 m (130") Level 12F El. 45.82 m (1504")

W14x370

W14x132

W14x370

3.96 m (130") Level 11F El. 41.86 m (1374")

W14x398

W14x159

W14x398

3.96 m (130") Level 10F El. 37.90 m (1244")

W14x398

W14x159

W14x398

3.96 m (130") Level 9F El. 33.93 m (1114")

W14x426

W14x176

W14x426

3.96 m (130") Level 8F El. 29.97 m (984")

W14x426

W14x176

W14x426

3.96 m (130") Level 7F El. 26.01 m (854")

W14x455

W14x211

W14x455

3.96 m (130") Level 6F El. 22.05 m (724")

W14x455

W14x211

W14x455

3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464")

W14x500

W14x500

W14x233

W14x500

W14x500

W14x233

W14x500

3.96 m (130") Level 3F El. 10.16 m (334")

W14x730

W14x283

W14x730

3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x500

W14x730

W14x730

W14x730

W14x283

W14x730

Figure B.4: Frame 4 elevation: Existing building

79
EW FRAME (5) ALONG GRID E: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x48

W14x48

W14x43

W14x48

W14x48

W14x43

4.78 m (158") Level 17F El. 65.63 m (2154")

W14x43

W14x53

W14x53

W14x43

3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464")
W10x33

W14x43

W14x53

W14x53

W14x43

W14x61

W14x68

W14x68

W14x61

W14x61

W14x68

W14x68

W14x61

W14x74

W14x82

W14x82

W14x74

W14x74

W14x82

W14x82

W14x74

W14x90

W14x90

W14x90

W14x90

W14x90

W14x90

W14x90

W14x90

W14x99

W14x109

W14x109

W14x99

W14x99

W14x109

W14x109

W14x99

W14x120

W14x132

W14x132

W14x120

W14x120

W14x132

W14x132

W14x120

W14x132

W14x145

W14x145

W14x132

W8x24

W14x132

W14x145

W14x145

W14x132

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x730

W14x211

W14x233

W14x233

W14x211

W12x65

W14x730

W14x211

W14x233

W14x233

W14x211

W12x65

Figure B.5: Frame 5 elevation: Existing building

80
NS FRAME (6) ALONG GRID 1: ELEVATION A
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

B
8.53 m (280")

D
8.53 m (280") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174")

W36x135 W14x311 W36x150 W14x311 W36x150 W14x311 W36x170 W14x342 W36x170 W14x342 W36x194 W14x370 W36x194 W14x370 W36x230 W14x398 W36x230 W14x398 W36x230 W14x426 W36x230 W14x426 W36x230 W14x455 W36x230 W14x455 W36x230 W14x500 W36x230 W10x33 W14x500 W36x300 W12x65 W14x730 W36x300

W36x135 W14x311 W36x150 W14x311 W36x150 W14x311 W36x170 W14x342 W36x170 W14x342 W36x194 W14x370 W36x194 W14x370 W36x230 W14x398 W36x230 W14x398 W36x230 W14x426 W36x230 W14x426 W36x230 W14x455 W36x230 W14x455 W36x230 W14x500 W36x230 W14x500 W36x300 W14x730 W36x300 W14x730 W14x500 W36x300 W14x730 W8x24 W14x500 W14x455 W14x455 W14x426 W14x426 W14x398 W14x398 W14x370 W14x370 W14x342 W14x342 W14x311 W14x311 W14x311

Level Penthouse El. 70.41 m (2310") 4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464") 3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204")
W14x730

W12x65

W14x730

W14x730

6.20 m (204") Level 1F El. 0.00 m (00")

Figure B.6: Frame 6 elevation: Existing building

81

Appendix C

Redesigned Building Frame Elevations and

Beam and Column Sizes

82
EW FRAME (1) ALONG GRID A: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")
W30x148

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W24x207 W30x148 B14x14x171 W30x148 B14x14x171 W30x148 B14x14x171 Doubler Plate Thickness W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B16x16x227 W30x173 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 W14x68 B20x20x352 W30x191 W14x109 B22x22x430 W30x191 W30x148 W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 9.5 mm W30x191 W27x281 13.0 mm W30x191 W27x281 W30x191 B30x22x644 W30x191

W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 9.5 mm W30x191 W27x281 13.0 mm W30x191 W27x281 W30x191 B30x22x644 W30x191 B22x22x430 B16x16x227 B14x14x171 B14x14x171 B14x14x171

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464")
W14x68

B16x16x227

B16x16x227

B16x16x227

B18x18x282

B18x18x282

B18x18x282

B18x18x282

B20x20x352

B20x20x352

B20x20x352

B20x20x352

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x109

W14x109

B22x22x430

B30x22x644

B30x22x644

B22x22x430

W14x109

Figure C.1: Frame 1 elevation: Redesigned building

83
EW FRAME (2) ALONG GRID B: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174")

W24x207

W14x68

W14x68

B14x14x171

W30x124 B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B22x22x430 W30x191

Level Penthouse El. 70.41 m (2310") 4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464") 3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W24x207

W24x207

W14x68

W14x68

B14x14x171

W24x207

W24x207

W14x68

W14x68

B14x14x171

W24x207

W24x207

W14x68

W14x68

B14x14x171

W24x229

W24x229

W14x109

W14x109

B16x16x227

W24x229

W24x229

W14x109

W14x109

B16x16x227

W24x229

W24x229

W14x120

W14x120

B16x16x227

W24x229

W24x229

W14x120

W14x120

B16x16x227

W27x258

W27x258

W14x145

W14x145

B18x18x282

W27x258

W27x258

W14x145

W14x145

B18x18x282

W27x258

W27x258

W14x176

W14x176

B18x18x282

W27x258

W27x258

W14x176

W14x176

B18x18x282

W27x281

W27x281

W14x233

W14x233

B20x20x352

W27x281

W27x281

W14x233

W14x233

B20x20x352

W27x307

W27x307

W14x283

W14x283

B20x20x352

W27x307

W27x307

W14x283

W14x283

B20x20x352

B30x24x668

B30x24x668

W14x455

W14x455

B22x22x430

B30x24x668

B30x24x668

W14x455

W14x455

B22x22x430

B22x22x430

Figure C.2: Frame 2 elevation: Redesigned building

84
EW FRAME (3) ALONG GRID C: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W14x176

W14x68

W14x68

W14x176

W24x207

W14x176

W14x68

W14x68

W14x176

W24x207

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764") 3.96 m (130") Level 13F El. 49.78 m (1634") 3.96 m (130") Level 12F El. 45.82 m (1504") 3.96 m (130") Level 11F El. 41.86 m (1374") 3.96 m (130") Level 10F El. 37.90 m (1244") 3.96 m (130") Level 9F El. 33.93 m (1114") 3.96 m (130") Level 8F El. 29.97 m (984") 3.96 m (130") Level 7F El. 26.01 m (854") 3.96 m (130") Level 6F El. 22.05 m (724") 3.96 m (130") Level 5F El. 18.09 m (594") 3.96 m (130") Level 4F El. 14.12 m (464") 3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W24x207

W14x176

W14x68

W14x68

W14x176 W24x207

W24x207

W14x176

W14x68

W14x68

W14x176 W24x207

W24x229

W14x176

W14x109

W14x109

W14x176 W24x229

W24x229

W14x176

W14x109

W14x109

W14x176 W24x229

W27x258

W14x176

W14x120

W14x120

W14x176 W27x258

W27x258

W14x176

W14x120

W14x120

W14x176 W27x258

W27x258

W14x193

W14x145

W14x145

W14x193 W27x258

W27x258

W14x193

W14x145

W14x145

W14x193 W27x258

W27x258

W14x193

W14x176

W14x176

W14x193 W27x258

W27x258

W14x193

W14x176

W14x176

W14x193 W27x258

W27x281

W14x233

W14x233

W14x233

W14x233 W27x281

W27x281

W14x233

W14x233

W14x233

W14x233 W27x281

W27x307

W14x233

W14x283

W14x283

W14x233 W27x307

W27x307

W14x233

W14x283

W14x283

W14x233 W27x307

B30x24x668

W14x455

W14x455

W14x455

W14x455

B30x24x668

B30x24x668

W14x455

W14x455

W14x455

W14x455

B30x24x668

Figure C.3: Frame 3 elevation: Redesigned building

85
EW FRAME (4) ALONG GRID D: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B22x22x430 W30x191 B22x22x430 B20x20x352 B20x20x352 B20x20x352 B20x20x352 B18x18x282 B18x18x282 B18x18x282 B18x18x282 B16x16x227 B16x16x227 B16x16x227 B16x16x227 B14x14x171 B14x14x171 B14x14x171

W14x68

W14x68

W24x207

W14x68

W14x68

W24x207

W24x207

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130")

W14x68

W14x68

W24x207 W24x207

Level 16F El. 61.67 m (2024") 3.96 m (130")

W14x68

W14x68

W24x207 W24x207

Level 15F El. 57.71 m (1894") 3.96 m (130")

W14x109

W14x109

W24x229 W24x229

Level 14F El. 53.75 m (1764") 3.96 m (130")

W14x109

W14x109

W24x229 W24x229

Level 13F El. 49.78 m (1634") 3.96 m (130")

W14x120

W14x120

W24x229 W24x229

Level 12F El. 45.82 m (1504") 3.96 m (130")

W14x120

W14x120

W24x229 W24x229

Level 11F El. 41.86 m (1374") 3.96 m (130")

W14x145

W14x145

W27x258 W27x258

Level 10F El. 37.90 m (1244") 3.96 m (130")

W14x145

W14x145

W27x258 W27x258

Level 9F El. 33.93 m (1114") 3.96 m (130")

W14x176

W14x176

W27x258 W27x258

Level 8F El. 29.97 m (984") 3.96 m (130")

W14x176

W14x176

W27x258 W27x258

Level 7F El. 26.01 m (854") 3.96 m (130")

W14x233

W14x233

W27x281 W27x281

Level 6F El. 22.05 m (724") 3.96 m (130")

W14x233

W14x233

W27x281 W27x281

Level 5F El. 18.09 m (594") 3.96 m (130")

W14x283

W14x283

W27x307 W27x307

Level 4F El. 14.12 m (464") 3.96 m (130")

W14x283

W14x283

W27x307 W27x307

Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x455

W14x455

B30x24x668 B30x24x668

B22x22x430

B22x22x430

W14x455

W14x455

B30x24x668 B30x24x668

Figure C.4: Frame 4 elevation: Redesigned building

86
EW FRAME (5) ALONG GRID E: ELEVATION 1
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

2
9.55 m (314")

9.55 m (314")
W30x148

5
9.55 m (314") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")

W24x207 W30x148 B14x14x171 W30x148 B14x14x171 W30x148 B14x14x171 Doubler Plate Thickness W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B16x16x227 W30x173 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 W14x68 B20x20x352 W30x191 W14x109 B22x22x430 W30x191 W30x148 W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 9.5 mm W30x191 W27x281 13.0 mm W30x191 W27x281 W30x191 B30x22x644

W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 9.5 mm W30x191 W27x281 13.0 mm W30x191 W27x281 W30x191 B16x16x227 B14x14x171 B14x14x171 B14x14x171

4.78 m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764")

B16x16x227

3.96 m (130") Level 13F El. 49.78 m (1634")

B16x16x227

3.96 m (130") Level 12F El. 45.82 m (1504")

B16x16x227

3.96 m (130") Level 11F El. 41.86 m (1374")

B18x18x282

3.96 m (130") Level 10F El. 37.90 m (1244")

B18x18x282

3.96 m (130") Level 9F El. 33.93 m (1114")

B18x18x282

3.96 m (130") Level 8F El. 29.97 m (984")

B18x18x282

3.96 m (130") Level 7F El. 26.01 m (854")

B20x20x352

3.96 m (130") Level 6F El. 22.05 m (724")

B20x20x352

3.96 m (130") Level 5F El. 18.09 m (594")

B20x20x352

3.96 m (130") Level 4F El. 14.12 m (464")

B20x20x352

W14x68

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x109 B30x22x644 B22x22x430

W14x109

B22x22x430

B30x22x644

W14x109

Figure C.5: Frame 5 elevation: Redesigned building

87
NS FRAME (6) ALONG GRID 1: ELEVATION A
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

B
8.53 m (280")

D
8.53 m (280") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174")

W30x124 W24x207 W30x132 W24x207 W30x132 W24x207 Doubler Plate Thickness W30x148 W24x229 W30x148 W24x229 W30x173 W27x229 W30x173 W27x229 W30x173 W27x258 W30x173 W27x258 W30x173 W27x258 W30x173 W27x258 W30x191 W27x281 W30x191 W27x281 W30x191 W27x307 W30x191 W14x68 W27x307 W30x191 W14x109 B30x24x668 W30x191

W30x124 W24x207 W30x132 W24x207 W30x132 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x307 13.0 mm W30x191 W27x307 W30x191 B30x24x668 W30x191 B22x22x430 B16x16x227 B14x14x171 B14x14x171 B14x14x171

Level Penthouse El. 70.41 m (2310") 4.78m (158") Level 17F El. 65.63 m (2154") 3.96 m (130") Level 16F El. 61.67 m (2024") 3.96 m (130") Level 15F El. 57.71 m (1894") 3.96 m (130") Level 14F El. 53.75 m (1764")
B16x16x227

3.96 m (130") Level 13F El. 49.78 m (1634")

B16x16x227

3.96 m (130") Level 12F El. 45.82 m (1504")

B16x16x227

3.96 m (130") Level 11F El. 41.86 m (1374")

B18x18x282

3.96 m (130") Level 10F El. 37.90 m (1244")

B18x18x282

3.96 m (130") Level 9F El. 33.93 m (1114")

B18x18x282

3.96 m (130") Level 8F El. 29.97 m (984")

B18x18x282

3.96 m (130") Level 7F El. 26.01 m (854")

B20x20x352

3.96 m (130") Level 6F El. 22.05 m (724")

B20x20x352

3.96 m (130") Level 5F El. 18.09 m (594")

B20x20x352

3.96 m (130") Level 4F El. 14.12 m (464")

B20x20x352

W14x68

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

W14x109

W14x109

B30x24x668

B30x24x668

B22x22x430

W14x109

Figure C.6: Frame 6 elevation: Redesigned building

88
NS FRAME (7) ALONG GRID 2: ELEVATION A
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

B
8.53 m (280")

D
8.53 m (280")
W30x124

E
9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")
B14x14x171

W24x207 W30x124 B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B22x22x430 W30x191 B30x24x668 W27x307 W27x307 W27x281 W27x281 W27x258 W27x258 W27x258 W27x258 W27x229 W27x229 W24x229 W24x229 W24x207 W24x207 W24x207

W14x176 W30x124 W14x176

B14x14x171 W30x124 B14x14x171 W30x124

4.78 m (158") Level 17F El. 65.63 m (2154")

W14x176

B14x14x171 W30x124

B14x14x171

3.96 m (130") Level 16F El. 61.67 m (2024")

W14x176

B14x14x171 W30x148

B14x14x171

3.96 m (130") Level 15F El. 57.71 m (1894")

W14x176

B16x16x227 W30x148

B16x16x227

3.96 m (130") Level 14F El. 53.75 m (1764")

W14x176

B16x16x227 W30x148

B16x16x227

3.96 m (130") Level 13F El. 49.78 m (1634")

W14x176

B16x16x227 W30x148

B16x16x227

3.96 m (130") Level 12F El. 45.82 m (1504")

W14x176

B16x16x227 W30x173

B16x16x227

3.96 m (130") Level 11F El. 41.86 m (1374")

W14x193

B18x18x282 W30x173

B18x18x282

3.96 m (130") Level 10F El. 37.90 m (1244")

W14x193

B18x18x282 W30x173

B18x18x282

3.96 m (130") Level 9F El. 33.93 m (1114")

W14x193

B18x18x282 W30x173

B18x18x282

3.96 m (130") Level 8F El. 29.97 m (984")

W14x193

B18x18x282 W30x191

B18x18x282

3.96 m (130") Level 7F El. 26.01 m (854")

W14x233

B20x20x352 W30x191

B20x20x352

3.96 m (130") Level 6F El. 22.05 m (724")

W14x233

B20x20x352 W30x191

B20x20x352

3.96 m (130") Level 5F El. 18.09 m (594")

W14x233

B20x20x352 W30x191

B20x20x352

3.96 m (130") Level 4F El. 14.12 m (464")

W14x233

B20x20x352 W30x191

B20x20x352

3.96 m (130") Level 3F El. 10.16 m (334")

W14x455

B22x22x430 W30x191

B22x22x430

3.96 m (130") Level 2F El. 6.20 m (204") 6.20 m (204") Level 1F El. 0.00 m (00")

B22x22x430

B30x24x668

W14x455

B22x22x430

B22x22x430

Figure C.7: Frame 7 elevation: Redesigned building

89
NS FRAME (8) ALONG GRID 5: ELEVATION A
9.25 m (304") LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

B
8.53 m (280")
W30x124

D
8.53 m (280") 9.25 m (304")

Level ROOF El. 75.69 m (2484") 5.28 m (174") Level Penthouse El. 70.41 m (2310")
B14x14x171

B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x124 B14x14x171 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B22x22x430 W30x191 B22x22x430 B20x20x352 B20x20x352 B20x20x352 B20x20x352 B18x18x282 B18x18x282 B18x18x282 B18x18x282 B16x16x227 B16x16x227 B16x16x227 B16x16x227 B14x14x171 B14x14x171 W30x124 B14x14x171

W14x176

W24x207 W30x124

W14x176

W24x207 W30x124

4.78 m (158") Level 17F El. 65.63 m (2154")

W14x176

W24x207 W30x124

B14x14x171

3.96 m (130") Level 16F El. 61.67 m (2024")

W14x176

W24x207 W30x148

B14x14x171

3.96 m (130") Level 15F El. 57.71 m (1894")

W14x176

W24x229 W30x148

B16x16x227

3.96 m (130") Level 14F El. 53.75 m (1764")

W14x176

W24x229 W30x148

B16x16x227

3.96 m (130") Level 13F El. 49.78 m (1634")

W14x176

W27x229 W30x148

B16x16x227

3.96 m (130") Level 12F El. 45.82 m (1504")

W14x176

W27x229 W30x173

B16x16x227

3.96 m (130") Level 11F El. 41.86 m (1374")

W14x193

W27x258 W30x173

B18x18x282

3.96 m (130") Level 10F El. 37.90 m (1244")

W14x193

W27x258 W30x173

B18x18x282

3.96 m (130") Level 9F El. 33.93 m (1114")

W14x193

W27x258 W30x173

B18x18x282

3.96 m (130") Level 8F El. 29.97 m (984")

W14x193

W27x258 W30x191

B18x18x282

3.96 m (130") Level 7F El. 26.01 m (854")

W14x233

W27x281 W30x191

B20x20x352

3.96 m (130") Level 6F El. 22.05 m (724")

W14x233

W27x281 W30x191

B20x20x352

3.96 m (130") Level 5F El. 18.09 m (594")

W14x233

W27x307 W30x191

B20x20x352

3.96 m (130") Level 4F El. 14.12 m (464")

W14x233

W27x307 W30x191

B20x20x352

3.96 m (130") Level 3F El. 10.16 m (334") 3.96 m (130") Level 2F El. 6.20 m (204")

W14x455 B30x24x668 B22x22x430

B22x22x430

B22x22x430

W14x455

6.20 m (204") Level 1F El. 0.00 m (00")

Figure C.8: Frame 8 elevation: Redesigned building

90
NS FRAME (9) ALONG GRID 6: ELEVATION A
304" LEGEND: W Wideflange section B Box section Section Designation: Depth (in) x Width (in) x Weight (lb/ft) Depth (in) x Weight (lb/ft)

B
280"

D
280" 304"

Level ROOF El. 2484" 158"


W30x124 B14x14x171 W30x132 B14x14x171 W30x132 B14x14x171 Doubler Plate Thickness W30x148 B16x16x227 W30x148 B16x16x227 W30x173 B16x16x227 W30x173 B16x16x227 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x173 B18x18x282 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 B20x20x352 W30x191 W14x68 B20x20x352 W30x191 W14x109 B22x22x430 W30x191 W30x124 W24x207 W30x132 W24x207 W30x132 W24x207 W30x148 W24x229 3.1 mm W30x148 W24x229 6.3 mm W30x173 W27x258 6.3 mm W30x173 W27x258 9.5 mm W30x173 W27x258 9.5 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x173 W27x258 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x281 13.0 mm W30x191 W27x307 13.0 mm W30x191 W27x307 W30x191 B30x24x668 W30x191 B30x24x668 W24x229 W24x207 W24x207 W24x207

Level Penthouse El. 2310" 130" Level 17F El. 2154"

130" Level 16F El. 2024" 130" Level 15F El. 1894" 130" Level 14F El. 1764"

W24x229

130" Level 13F El. 1634"

W27x229

130" Level 12F El. 1504"

W27x229

130" Level 11F El. 1374"

W27x258

130" Level 10F El. 1244"

W27x258

130" Level 9F El. 1114"

W27x258

130" Level 8F El. 984"

W27x258

130" Level 7F El. 854"

W27x281

130" Level 6F El. 724"

W27x281

130" Level 5F El. 594"

W27x307

130" Level 4F El. 464"

W27x307

W14x68

130" Level 3F El. 334" 130" Level 2F El. 204" 204" Level 1F El. 00"

W14x109

W14x109

B22x22x430

B30x24x668

B30x24x668

W14x109

Figure C.9: Frame 9 elevation: Redesigned building

91

Appendix D

Scenario 1 (North-to-South Rupture):

Performance of Existing and Redesigned Building Models Based on Plastic Rotations in Beams and Panel Zones
Plotted in Figures D.1 through D.3 are the percentage of connections 1 in the existing building where plastic rotations exceed the IO, LS, and CP performance levels, respectively, when subjected to ground motion from scenario 1 (northto-south rupture) earthquake on the San Andreas fault. Corresponding results for the redesigned building are shown in Figures D.4 through D.6.
36
40

40

Simi Valley

34.25
Thousand Oaks

Chatsworth Northridge Canoga Park


40 Encino 28 24 20 12 8

36

Burbank North Hollywood


16

La Canada
20 24 28
16 Pasadena

12

32

16

San Fernando Sunland

16

12

36

32

Hollywood

Beverly Hills Santa Monica


32

32 36 Alhambra

Monrovia Azusa
24 28 32

0 Baldwin Park

3 4 6

Malibu
16

Los Angeles Montebello 4 Whittier


32
0

34
36

28

Point Dume
4
20 24

La Puente Diamond Bar Brea Fullerton Anaheim


32
16
24

36

Inglewood
36

28 40 22 40 12

El Segundo
32

Downey Compton Norwalk


36

Existing Building Damage Index (>IO) 8

16

Torrance
28
32
4

Long Beach Seal Beach Santa Ana


28
20

32

33.75

32

Irvine Huntington Beach


28

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

20

36

Figure D.1: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level.

1 Connections as dened here include the two ends each beam, and the one or two panel zones in each joint. Column ends are excluded as the FEMA356 criteria for assessing column performance make a distinction between force-controlled and deformation-controlled columns and are not amicable to presentation in a simple manner as can be done for beams and panel zones. The criteria for deformation-controlled columns (which are dened as those carrying limited axial load) are based on the plastic rotations similar to beams and panel zones. However, in the case of force-controlled columns yielding is not permissible, hence, there cannot be any performance levels associated with these columns.

32

12

2420

-117.75

92
28

Simi Valley
28

24

20

16

34.25
28

Thousand Oaks
24

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park 28 Burbank North Hollywood Encino 16 Pasadena 4
24
12
8

Beverly Hills
4

20
24

16

20

Monrovia Azusa
8 Baldwin Park

Hollywood Malibu

Alhambra
12

Los Angeles

12

24

16 20

34

Point Dume

Santa Monica
12
8

Montebello Whittier Downey Compton


12

La Puente Diamond Bar Brea Fullerton


8

Inglewood

Existing Building Damage Index (>LS)

12 8

El Segundo

Norwalk

Torrance

Anaheim

Long Beach

33.75
8

Seal Beach

Santa Ana
4

12

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure D.2: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level.
16

Simi Valley
20

34.25
24

20 Thousand Oaks

24

24

24 16

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank 20 North Hollywood Encino 2 1 8 Pasadena
4

20

16

34

20

4 8 12

Existing Building Damage Index (>CP)

16

20

Monrovia Azusa Baldwin Park La Puente


4
8

Hollywood Beverly Hills Malibu

Alhambra
8

Los Angeles

Point Dume

Santa Monica
8

Montebello Whittier Downey


4

Inglewood
8

Diamond Bar Brea Fullerton

El Segundo
4

Compton
4

Norwalk
8
4

Torrance

Anaheim

Long Beach

33.75

Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure D.3: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level.

93
32

28 40

36

40

28 33 62

Simi Valley
40

34.25
Thousand Oaks
24

36 2 28 3
4

8 4

Beverly Hills Santa


32 Monica
28

32

16 Hollywood 12

Alhambra

Baldwin Park
36

20

34
36

40

Point Dume
8

24

Malibu

Los Angeles Montebello


24

La Puente Diamond Bar Brea Fullerton

24

Inglewood
28

Whittier Downey Compton


2 32 8

26 1 10 2

New Building 16 Damage Index (>IO) 8 12


4

Torrance Long Beach


28

28

28

32

20

24

24

24

36

El Segundo

Norwalk

Anaheim
20
24

33.75
16

Seal Beach

24

Santa Ana
12

12
16

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 20 Pasadena 16 24
4
12
8

Monrovia 16 20Azusa 2
28 4 32

36

-119

Figure D.4: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level.
12

32

20

28

24

Irvine Huntington Beach

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Simi Valley

34.25
8

Thousand Oaks
12

12

8
4

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino 12 Pasadena Beverly Hills
4

16

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood Malibu

Alhambra

16

34
4

12

Los Angeles Montebello Whittier Downey Compton Norwalk

Point Dume

Santa Monica Inglewood El Segundo

New Building Damage Index (>LS)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure D.5: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level.

94

Simi Valley

34.25

Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena 8 Hollywood Beverly Hills Alhambra

12

12

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

4
8

Malibu Point Dume

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Santa Monica Inglewood El Segundo

New Building Damage Index (>CP)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure D.6: Mw 7.9 earthquake (north-to-south rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level.

95

Appendix E

Scenario 2 (South-to-North Rupture):

Performance of Existing and Redesigned Building Models Based on Plastic Rotations in Beams and Panel Zones
Plotted in Figures E.1 through E.3 are the percentage of connections 1 in the existing building where plastic rotations exceed the IO, LS, and CP performance levels, respectively, when subjected to ground motion from scenario 2 (southto-north rupture) earthquake on the San Andreas fault. Corresponding results for the redesigned building are shown in Figures E.4 through E.6.
12

34.25
20

16
12

Simi Valley

Thousand Oaks
8

San Fernando Sunland Chatsworth Northridge La Canada 8 Canoga Park Burbank 12 Encino 8 North Hollywood Pasadena
4

12

Monrovia Azusa Baldwin Park


4

Hollywood Beverly Hills Malibu Santa Monica


12

Alhambra

12

Los Angeles Montebello

34
12

Point Dume
8

4 8

La Puente Diamond Bar Brea Fullerton Anaheim

Inglewood

Whittier Downey Compton Norwalk

16

Existing Building Damage Index (>IO)4

12

20

El Segundo

Torrance Long Beach Seal Beach

33.75

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.1: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level.

1 Connections as dened here include the two ends each beam, and the one or two panel zones in each joint. Column ends are excluded as the FEMA356 criteria for assessing column performance make a distinction between force-controlled and deformation-controlled columns and are not amicable to presentation in a simple manner as can be done for beams and panel zones. The criteria for deformation-controlled columns (which are dened as those carrying limited axial load) are based on the plastic rotations similar to beams and panel zones. However, in the case of force-controlled columns yielding is not permissible, hence, there cannot be any performance levels associated with these columns.

96
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra

34.25
Thousand Oaks

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Existing Building Damage Index (>LS)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.2: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra

34.25
Thousand Oaks

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

Existing Building Damage Index (>CP)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.3: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault existing building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level.

97
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena
4

34.25

16

Thousand Oaks
4

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Hollywood
8

Beverly Hills Malibu Point Dume


4

Alhambra

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Santa Monica
4

12

Inglewood

El Segundo

New Building Damage Index (>IO)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.4: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Immediate Occupancy (IO) level.
Simi Valley San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Malibu Alhambra

34.25
Thousand Oaks

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

New Building Damage Index (>LS)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.5: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Life Safety (LS) level.

98

Simi Valley

34.25
Thousand Oaks

San Fernando Sunland Chatsworth Northridge La Canada Canoga Park Burbank North Hollywood Encino Pasadena Hollywood Beverly Hills Alhambra

Monrovia Azusa Baldwin Park La Puente Diamond Bar Brea Fullerton Anaheim

Malibu

Los Angeles Montebello Whittier Downey Compton Norwalk

34

Point Dume

Santa Monica Inglewood El Segundo

New Building Damage Index (>CP)


33.75

Torrance Long Beach Seal Beach

Santa Ana

Irvine Huntington Beach

-119

-118.75 0 4 8

-118.5 12 16 20

-118.25 24 28 32

-118 36 40

-117.75

Figure E.6: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault redesigned building performance: Percentage of connections with plastic rotation exceeding the FEMA356 Collapse Prevention (CP) level.

99

Appendix F

Details of the Performance of Existing and

Redesigned Building Models in 8 Southern Californian Cities

100

F.1 Site: Thousand Oaks (Latitude 34.18750, Longitude 118.87500)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Thousand Oaks

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.1: Mw 7.9 earthquake (south-to north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Thousand Oaks. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

101

F.1.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.2: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Thousand Oaks (the drift scale is saturated at 0.10).

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 130 52 8 22 140 60 12 72 183 73 13 15 764 71 9 80 712 75 12 125

Perf. Level CO CO CO CO CO

Force-controlled components Not Yielded Yielded 11 5 11 5

Table F.1: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Thousand Oaks.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 101 115 119 769 698

(0.1-1.0]% 70 40 48 73 83

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 12 11 5 4 27 15 12 5 19 16 7 14 25 10 15 11 31 28 9 2

(5.0-6.0]% 5 9 4 6 4

> 6.0% 4 61 57 31 85

Table F.2: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Thousand Oaks.

102

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.3: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

103

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.4: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

104

F.1.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.5: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Thousand Oaks.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 199 80 31 3 275 205 26 44 530 20 0 0 543 121 12 12 584 101 1 2

Perf. Level CO CO LS CO CO

Force-controlled components Not Yielded Yielded 112 140 112 140

Table F.3: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Thousand Oaks.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 189 249 255 710 772

(0.1-1.0]% 61 41 194 207 168

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 29 34 0 0 77 70 32 25 82 19 0 0 23 0 0 0 0 0 0 0

(5.0-6.0]% 0 12 0 0 0

> 6.0% 0 44 0 0 0

Table F.4: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Thousand Oaks.

105

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.6: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Thousand Oaks (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

106

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.7: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Thousand Oaks (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

107

F.2 Site: Northridge (Latitude 34.21875, Longitude 118.53125)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Northridge

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.8: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Northridge. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

108

F.2.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.9: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Northridge (the drift scale is saturated at 0.10).

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 114 60 11 27 112 94 16 62 183 63 13 25 811 77 4 28 694 107 19 100

Perf. Level CO CO CO CO CO

Force-controlled components Not Yielded Yielded 16 4 13 7

Table F.5: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Northridge.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 85 71 85 810 665

(0.1-1.0]% 78 61 73 80 120

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 15 13 7 7 29 31 21 12 25 20 12 12 24 9 1 1 45 25 5 4

(5.0-6.0]% 2 2 5 3 3

> 6.0% 5 57 52 12 73

Table F.6: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Northridge.

109

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.10: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

110

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.11: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

111

F.2.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.12: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Northridge.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 200 105 8 0 270 275 5 0 550 0 0 0 640 66 0 0 686 20 0 0

Perf. Level CP CP IO LS LS

Force-controlled components Not Yielded Yielded 110 124 110 124

Table F.7: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Northridge.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 186 232 282 828 890

(0.1-1.0]% 60 90 251 112 50

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 59 8 0 0 138 60 26 4 17 0 0 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.8: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Northridge.

112

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.13: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Northridge (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

113

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.14: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Northridge (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

114

F.3 Site: West Los Angeles (Latitude 34.03125, Longitude 118.40625)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: West Los Angeles

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.15: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): West Los Angeles. Also shown are the timehistories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

115

F.3.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.16: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: West Los Angeles (the drift scale is saturated at 0.10).

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 135 53 5 19 160 57 10 57 222 61 1 0 888 40 4 6 893 38 3 4

Perf. Level CO CO CP CO CO

Force-controlled components Not Yielded Yielded 2 0 2 0

Table F.9: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: West Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 107 140 147 875 878

(0.1-1.0]% 70 29 61 51 51

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 13 9 4 6 10 29 14 9 18 17 10 7 10 2 2 0 8 2 1 0

(5.0-6.0]% 3 14 5 0 0

> 6.0% 0 39 19 0 0

Table F.10: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: West Los Angeles.

116

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.17: Plastic rotation in percent of a radian in the moment-frames of the existing building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

117

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.18: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

118

F.3.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.19: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: West Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 227 74 12 0 344 206 0 0 550 0 0 0 660 64 1 1 714 12 0 0

Perf. Level CP LS IO CO LS

Force-controlled components Not Yielded Yielded 96 118 96 118

Table F.11: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: West Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 204 298 337 839 904

(0.1-1.0]% 69 77 190 101 36

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 28 12 0 0 93 59 16 7 23 0 0 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.12: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: West Los Angeles.

119

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.20: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: West Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

120

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.21: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: West Los Angeles (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

121

F.4 Site: Downtown Los Angeles (Latitude 34.06250, Longitude 118.25000)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Downtown Los Angeles

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.22: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Downtown Los Angeles. Also shown are the timehistories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

122

F.4.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.23: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Downtown Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 130 65 11 6 196 84 4 0 277 7 0 0 932 2 0 0 934 0 0 0

Perf. Level CO CP LS LS IO

Force-controlled components Not Yielded Yielded 2 4 2 4

Table F.13: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Downtown Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 107 167 190 937 938

(0.1-1.0]% 70 51 84 3 2

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 21 13 1 0 39 22 5 0 4 5 1 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.14: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Downtown Los Angeles.

123

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.24: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

124

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.25: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

125

F.4.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.26: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Downtown Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 232 81 0 0 394 156 0 0 550 0 0 0 702 20 0 0 719 3 0 0

Perf. Level LS LS IO LS LS

Force-controlled components Not Yielded Yielded 100 118 100 118

Table F.15: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Downtown Los Angeles.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 208 309 383 912 936

(0.1-1.0]% 82 143 167 28 4

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 23 0 0 0 92 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.16: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Downtown Los Angeles.

126

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.27: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Downtown Los Angeles (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

127

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.28: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Downtown Los Angeles (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

128

F.5 Site: Baldwin Park (Latitude 34.09375, Longitude 118.00000)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Baldwin Park

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:63.54s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.29: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Baldwin Park. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

129

F.5.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.30: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Baldwin Park (the drift scale is saturated at 0.10).

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 120 60 6 26 130 79 23 52 218 61 5 0 877 35 3 5 890 27 0 3

Perf. Level CO CO CP CO CO

Force-controlled components Not Yielded Yielded 10 10 14 6

Table F.17: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Baldwin Park.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 96 104 113 873 885

(0.1-1.0]% 68 44 74 54 49

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 17 9 7 6 24 26 20 17 37 23 11 9 8 5 0 0 6 0 0 0

(5.0-6.0]% 5 7 5 0 0

> 6.0% 4 42 12 0 0

Table F.18: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Baldwin Park.

130

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.31: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

131

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.32: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

132

F.5.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.33: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Baldwin Park.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 219 62 29 3 295 251 4 0 550 0 0 0 613 81 5 1 670 30 0 0

Perf. Level CO CP IO CO LS

Force-controlled components Not Yielded Yielded 108 132 108 132

Table F.19: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Baldwin Park.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 193 249 261 798 879

(0.1-1.0]% 52 66 286 137 60

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 36 32 0 0 111 92 19 13 3 0 0 0 5 0 0 0 1 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.20: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Baldwin Park.

133

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.34: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Baldwin Park (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

134

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.35: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Baldwin Park (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

135

F.6 Site: Anaheim (Latitude 33.84375, Longitude 117.90625)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Anaheim

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.36: Mw 7.9 earthquake south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Anaheim. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

136

F.6.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.37: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Anaheim (the drift scale is saturated at 0.10).

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 124 64 4 20 161 69 11 43 232 48 4 0 898 30 0 2 909 19 1 1

Perf. Level CO CO CP CO CO

Force-controlled components Not Yielded Yielded 2 8 2 8

Table F.21: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Anaheim.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 120 134 132 900 907

(0.1-1.0]% 72 45 79 33 29

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 15 5 5 4 25 23 8 8 19 16 11 9 6 1 0 0 4 0 0 0

(5.0-6.0]% 6 15 3 0 0

> 6.0% 3 26 15 0 0

Table F.22: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Anaheim.

137

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.38: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

138

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.39: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

139

F.6.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.40: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Anaheim.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 226 56 27 4 350 162 26 12 547 3 0 0 650 55 3 8 689 25 0 2

Perf. Level CO CO LS CO CO

Force-controlled components Not Yielded Yielded 102 122 102 122

Table F.23: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Anaheim.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 199 266 288 822 871

(0.1-1.0]% 52 117 202 107 66

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 33 27 2 0 71 26 20 32 58 2 0 0 9 2 0 0 3 0 0 0

(5.0-6.0]% 0 6 0 0 0

> 6.0% 0 12 0 0 0

Table F.24: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Anaheim.

140

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.41: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Anaheim (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

141

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.42: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Anaheim (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

142

F.7 Site: Long Beach (Latitude 33.78125, Longitude 118.18750)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Long Beach

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.43: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Long Beach. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

143

F.7.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.44: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Long Beach.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 156 45 9 2 201 67 8 8 272 12 0 0 934 2 0 0 934 2 0 0

Perf. Level CO CO LS LS LS

Force-controlled components Not Yielded Yielded 2 2 2 2

Table F.25: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Long Beach.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 128 177 188 933 931

(0.1-1.0]% 58 42 74 7 9

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 15 10 1 0 27 19 9 8 14 4 3 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 2 0 0 0

> 6.0% 0 0 1 0 0

Table F.26: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Long Beach.

144

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.45: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

145

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.46: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

146

F.7.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.47: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Long Beach.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 233 80 0 0 377 173 0 0 550 0 0 0 716 14 0 0 729 1 0 0

Perf. Level LS LS IO LS LS

Force-controlled components Not Yielded Yielded 90 120 90 120

Table F.27: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Long Beach.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 205 323 388 904 937

(0.1-1.0]% 98 120 161 36 3

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 10 0 0 0 104 3 0 0 1 0 0 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.28: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Long Beach.

147

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.48: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Long Beach (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

148

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.49: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Long Beach (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

149

F.8 Site: Santa Ana (Latitude 33.75000, Longitude 117.87500)


Title: San Andreas M 7.9
w
70 70 Z (m) 60 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 Z Disp (m) E Disp (m) Z (m) N Disp (m) 70 Z (m) 60 50 40 30 20 10 0 40 20 Y (m) 0 20 (s) 40 60 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 20 Y (m) 40 Z Vel (m/s) E Vel (m/s) N Vel (m/s) Z (m) 50 40 30 20 10 0 40 20 Y (m) 0 0 20 X (m) Z (m) 40 70 60 50 40 30 20 10 0 0 70 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 20 Y (m) 40 60 50 40 30 20 10 0 0 20 40 X (m) Y (m) 40 30 20 10 0 10 X (m) 0 20 40 N E 2 E Dis (m) 0 2 0 20 40 60

Site: Santa Ana

Existing Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 2 E Dis (m) 0 2 0 20 40 60 20 40 60

Ground Velocity & Displacement System Clock:70.02s

Redesigned Building: Isometric View, Elevations, Plan, and Penthouse Displacement Time Histories

2 N Dis (m) 0 2 0 20 40 60

Figure F.50: Mw 7.9 earthquake (south-to-north rupture) on the San Andreas fault snapshot of building deformation immediately following the earthquake (scaled up by a factor of 5): Santa Ana. Also shown are the time-histories of the three components of the ground velocity and displacement (bandpass-ltered between 2 s and 1000 s), and the east and north components of the penthouse displacement of the existing and redesigned building models.

150

F.8.1 Existing Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.51: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the existing building model: Santa Ana.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 151 51 5 5 200 78 6 0 264 20 0 0 933 3 0 0 936 0 0 0

Perf. Level CO CP LS LS IO

Force-controlled components Not Yielded Yielded 2 2 2 2

Table F.29: Classication of existing building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Santa Ana.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 117 172 187 935 939

(0.1-1.0]% 67 51 65 5 1

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 19 7 2 0 30 18 11 2 12 11 4 3 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 2 0 0

> 6.0% 0 0 0 0 0

Table F.30: Plastic rotation in panel zones, and at the ends of beams and columns of the existing building model: Santa Ana.

151

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.52: Plastic rotation in percent of a radian in the moment-frames of the existing building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

152

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

70

70

60

60

50

50

40

40

30

30

20

20

10

10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.53: Beam bottom-ange weld fracture locations in the moment-frames of the existing building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid D (east-west direction); (C) Moment-frame along grid 1 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.2 for moment-frame conguration.

153

F.8.2 Redesigned Building Performance


18 16 14 12 10 8 6 4 2 0 0 0.02 0.04 0.06 Peak Drift Ratio 0.08 0.1

Figure F.54: Peak east-west/X (white bars) and north-south/Y (black bars) drifts in each story of the redesigned building model: Santa Ana.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

Story

Components within each perf. category IO LS CP CO (> CP) 235 78 0 0 439 111 0 0 550 0 0 0 715 25 0 0 740 0 0 0

Perf. Level LS LS IO LS IO

Force-controlled components Not Yielded Yielded 96 104 96 104

Table F.31: Classication of redesigned building model performance based on plastic rotation in panel zones, and at the ends of beams and columns, using FEMA356 acceptance criteria: Santa Ana.

Component Panel Zone Beam Major Axis Beam Minor Axis Column Major Axis Column Minor Axis

0.1% 217 347 412 905 938

(0.1-1.0]% 72 115 138 35 2

Components in the following plastic rotation ranges (1.0-2.0]% (2.0-3.0]% (3.0-4.0]% (4.0-5.0]% 24 0 0 0 60 20 8 0 0 0 0 0 0 0 0 0 0 0 0 0

(5.0-6.0]% 0 0 0 0 0

> 6.0% 0 0 0 0 0

Table F.32: Plastic rotation in panel zones, and at the ends of beams and columns of the redesigned building model: Santa Ana.

154

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

50

0 10

10

20

30

40

50

Figure F.55: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Santa Ana (A) Moment-frame along grid A (east-west direction); (B) Moment-frame along grid B (east-west direction); (C) Moment-frame along grid D (east-west direction); (D) Moment-frame along grid E (east-west direction). See Figure 2.3 for moment-frame conguration.

155

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

1.0% 70 70

1.0%

60

2.0%

60

2.0%

50 3.0% 40

50 3.0% 40

30

4.0%

30

4.0%

20 5.0% 10

20 5.0% 10

0 10

10

20

30

40

0 10

10

20

30

40

Figure F.56: Plastic rotation in percent of a radian in the moment-frames of the redesigned building model: Santa Ana (A) Moment-frame along grid 1 (north-south direction); (B) Moment-frame along grid 2 (north-south direction); (C) Moment-frame along grid 5 (north-south direction); (D) Moment-frame along grid 6 (north-south direction). See Figure 2.3 for moment-frame conguration.

156

References
[1] Kerry E. Sieh. Slip along the San Andreas fault associated with the great 1857 earthquake. Bulletin of the Seismological Society of America, 68(5):14211448, 1978. [2] Duncan Carr Agnew and Kerry Sieh. A documentary study of the felt effects of the great California earthquake of 1857. Bulletin of the Seismological Society of America, 68(6):17171729, 1978. [3] Aron J. Meltzner and David J. Wald. Foreshocks and aftershocks of the great 1857 California earthquake. Technical Report USGS Open-File Report 98-465, United States Department of the Interior, USGS, Pasadena, California, USA, 1998. [4] FEMA. Prestandard and Commentary for the Seismic Rehabilitation of Buildings. FEMA-356. Federal Emergency Management Agency, USA, 2000. [5] FEMA. Recommended Seismic Design Criteria for New Steel Moment-Frame Buildings. FEMA-350. Federal Emergency Management Agency, USA, 2000. [6] ICBO. 1997 Uniform Building Code. Volume 2. International Conference of Building Ofcials, Whittier, California, USA, 1997. [7] Kerry E. Sieh. Pre-historic large earthquakes produced by slip on the San Andreas fault at Pallett creek, California. Journal of Geophysical Research, 83:39073939, 1978. [8] Kerry E. Sieh. A study of late Holocene displacement history along the South-Central reach of the San Andreas fault. Technical Report Ph.D. Dissertation, Stanford University, California, USA, 1977. [9] J. H. Shaw and J. Suppe. Earthquake hazards of active blind-thrust faults under the central Los Angeles basin. Journal of Geophysical Research, 101(B4):86238642, 1996. [10] Ronald T. Eguchi, James D. Goltz, Craig E. Taylor, Stephanie E. Chang, Paul J. Flores, Laurie A. Johnson, Hope A. Seligson, and Neil C. Blais. Direct economic losses in the Northridge earthquake: A three-year postevent perspective. Earthquake Spectra, 14(2):245264, 1998. [11] William J. Petak and Shirin Elahi. The Northridge earthquake, USA, and its economic and social impact. In EuroConference on Global Change and Catastrophe Risk Management, Earthquake Risks in Europe, IIASA, Laxenburg, Austria, 2000. [12] SAC. Analytical and eld investigations of buildings affected by the Northridge earthquake of January 17, 1994 Part 1. Technical Report SAC 95-04, Part 1, Structural Engineers Association of California, Applied Technology Council, and California Universities for Research in Earthquake Engineering, USA, 1995. [13] SAC. Analytical and eld investigations of buildings affected by the Northridge earthquake of January 17, 1994 Part 2. Technical Report SAC 95-04, Part 2, Structural Engineers Association of California, Applied Technology Council, and California Universities for Research in Earthquake Engineering, USA, 1995. [14] SAC. Surveys and assessments of damage to buildings affected by the Northridge earthquake of January 17, 1994. Technical Report SAC 95-06, Structural Engineers Association of California, Applied Technology Council, and California Universities for Research in Earthquake Engineering, USA, 1995.

157 [15] EQE. The Northridge earthquake of January 17, 1994: Report of data collection and analysis, Part A: Damage and inventory data. Technical Report EQE Project No. 36386.02, EQE International Inc. and The Geographic Information Systems Group of the Governors Ofce of Emergency Services, California, USA, 1995. [16] T. Heaton, J. Hall, D. Wald, and M. Halling. Response of high-rise and base-isolated buildings to a hypothetical Mw 7.0 blind thrust earthquake. Science, 267:206211, 1995. [17] J. Hall, T. Heaton, M. Halling, and D. Wald. Near-source ground motion and its effects on exible buildings. Earthquake Spectra, 11(4):569605, 1995. [18] John F. Hall. Seismic response of steel frame buildings to near-source ground motions. Earthquake Engineering and Structural Dynamics, 27:14451464, 1998. [19] K. B. Olsen, R. J. Archuleta, and J. R. Matarese. Three dimensional simulation of a magnitude 7.75 earthquake on the San Andreas fault. Science, 270:16281632, 1995. [20] Robert W. Graves. Three-dimensional nite-difference modeling of the San Andreas fault: Source parameterization and ground-motion levels. Bulletin of the Seismological Society of America, 88(4):881897, 1998. [21] Chen Ji, David J. Wald, and Don V. Helmberger. Source description of the 1999 Hector Mine, California, earthquake Part I: Wavelet domain inversion theory and resolution analysis. Bulletin of the Seismological Society of America, 92(4):11921207, 2002. [22] Chen Ji, Y. Tan, Don Helmberger, and Jeroen Tromp. Modeling teleseismic P and SH static offsets for great strike-slip earthquakes. In Proceedings of the American Geophysical Union Fall Meeting, USA, 2003. [23] Dimitri Komatitsch, Qinya Liu, Jeroen Tromp, Peter Suss, Christiane Stidham, and John H. Shaw. Simulations of ground motion in the Los Angeles basin based upon the spectral element method. Bulletin of the Seismological Society of America, 94:187206, 2004. [24] Qinya Liu, Jascha Polet, Dimitri Komatitsch, and Jeroen Tromp. Spectral-element moment tensor inversions for earthquakes in Southern California. Bulletin of the Seismological Society of America, 94(5):17481761, 2004. [25] Dimitri Komatitsch and Jeroen Tromp. Introduction to the spectral element method for three-dimensional seismic wave propagation. Geophys. J. Int., 139:806822, 1999. [26] Swaminathan Krishnan. Three-dimensional nonlinear analysis of tall irregular steel buildings subject to strong ground motion. Technical Report EERL 2003-01, Earthquake Engineering Research Laboratory, California Institute of Technology, Pasadena, California, USA, 2003. [27] Anders Carlson. Three-dimensional nonlinear inelastic analysis of steel moment-frame buildings damaged by earthquake excitations. Technical Report EERL 99-02, Earthquake Engineering Research Laboratory, California Institute of Technology, Pasadena, California, USA, 1999. [28] ICBO. 1982 Uniform Building Code. Volume 2. International Conference of Building Ofcials, Whittier, California, USA, 1982. [29] M. P. Suss and J. H. Shaw. P-wave seismic velocity structure derived from sonic logs and industry reection data in the Los Angeles basin. Journal of Geophysical Research, 108(B3):Article no. 2170, 2003. [30] Swaminathan Krishnan. FRAME3D A program for three-dimensional nonlinear time-history analysis of steel buildings: User guide. Technical Report EERL 2003-03, Earthquake Engineering Research Laboratory, California Institute of Technology, Pasadena, California, USA, 2003.

158 [31] Swaminathan Krishnan and John F. Hall. Modeling steel frame buildings in three dimensions Part I: Panel zone and plastic hinge beam elements. Journal of Engineering Mechanics, ASCE (Scheduled for publication in April 2006), 2006. [32] Swaminathan Krishnan and John F. Hall. Modeling steel frame buildings in three dimensions Part II: Elastober beam element and examples. Journal of Engineering Mechanics, ASCE (Scheduled for publication in April 2006), 2006. [33] Norman A. Haskell. Crustal reection of plane SH waves. Journal of Geophysical Research, pages 41474150, 1996. [34] J. G. Anderson, Y. Lee, Y. Zeng, and S. M. Day. Control of strong motion by the upper 30 meters. Bulletin of the Seismological Society of America, 86:17491759, 1996. [35] M.D. Trifunac, M.I. Todorovska, and T.Y. Hao. Full-scale experimental studies of soil-structure interaction a review. In Proceedings of the Second USJapan Workshop on Soil-Structure Interaction, Tsukuba City, Japan, 52 pages (published on CD-ROM), 2001. [36] Jonathan P. Stewart, Raymond B. Seed, and Gregory L. Fenves. Empirical evaluation of inertial soil-structure interaction effects. Technical Report PEER-98/07, Pacic Earthquake Engineering Center, University of California, Berkeley, California, USA, 1998. [37] Giorgio Serino. Dynamic soil-structure interaction in building response from earthquake records. Technical Report UCB/SEMM-1989/01, Department of Civil Engineering, University of California, Berkeley, California, USA, 1989. [38] Gregory L. Fenves and Giorgio Serino. Soil-structure interaction in buildings from earthquake records. Earthquake Spectra, 6(4):641655, 1990. [39] M.D. Trifunac, T.Y. Hao, and M.I. Todorovska. Response of a 14-story reinforced concrete structure to nine earthquakes: 61 years of observation in the Hollywood storage building. Technical Report CE 01-02, Department of Civil Engineering, University of Southern California, Los Angeles, California, USA, 2001. [40] S. H. Hartzell, P. Liu, and C. Mendoza. The 1994 Northridge, California, earthquake: Investigation of rupture velocity, rise time, and high-frequency radiation. Journal of Geophysical Research, 101(B9):2009120108, 1996. [41] David J. Wald, Thomas H. Heaton, and Ken W. Hudnut. A dislocation model of the 1994 Northridge, California, earthquake determined from strong-motion, GPS, and leveling-line data. Bulletin of the Seismological Society of America, 86:S49S70, 1996. [42] R. Darragh, T. Cao, V. Graizer, A. Shakal, and M. Huang. Los Angeles code-instrumented building records from the Northridge, California earthquake of January 17 1994: Processed release No. 1. Technical Report OSMS 94-17, California Strong Motion Instrumentation Program, California Department of Conservation, Division of Mines and Geology (now California Geological Survey), California, USA, 1994. [43] FEMA. Recommended Specications and Quality Assurance Guidelines for Steel Moment-Frame Construction for Seismic Applications. FEMA-353. Federal Emergency Management Agency, USA, 2000. [44] Kerry E. Sieh, Minze Stuiver, and David Brillinger. A more precise chronology of earthquakes produced by the San Andreas fault in southern California. Journal of Geophysical Research, 94:603623, 1989.

159 [45] Ray J. Weldon, Thomas E. Fumal, Glenn P. Biasi, and Katharine M. Scharer. Past and future earthquakes on the San Andreas fault. Science, 308:966967, 2005. [46] Donna Eberhart-Phillips, Peter J. Haeussler, Jeffrey T. Freymueller, Arthur D. Frankel, Charles M. Rubin, Patricia Craw, Natalia A. Ratchkovski, Greg Anderson, Gary A. Carver, Anthony J. Crone, Timothy E. Dawson, Hilary Fletcher, Roger Hansen, Edwin L. Harp, Ruth A. Harris, David P. Hill, Sigrun Hreinsdottir, Randall W. Jibson, Lucile M. Jones, Robert Kayen, David K. Keefer, Christopher F. Larsen, Seth C. Moran, Stephen F. Personius, George Plafker, Brian Sherrod, Kerry Sieh, Nicholas Sitar, and Wesley K. Wallace. The 2002 Denali fault earthquake, Alaska: A large magnitude, slip-partitioned event. Science, 300:11131118, 2003. [47] Chen Ji, Don V. Helmberger, T. Song, K. F. Ma, and David J. Wald. Co-seismic slip distribution and tectonic implication of the 1999 Chi-Chi, Taiwan, earthquake. Geophysical Research Letters, 28(23):43794382, 2001. [48] Shui-Beih Yu, Long-Chen Kuo, Ya-Ju Hsu, Hsuan-Han Su, Chi-Ching Lui, Chin-Shyong Hou, Jiin-Fa Lee, Teng-Chang Lai, Chih-Chung Liu, Cheng-Lun Liu, Teh-Fu Tseng, Chun-Shyong Tsai, and Tzay-Chyn Shin. Preseismic deformation and coseismic displacements associated with the 1999 Chi-Chi, Taiwan, earthquake. Bulletin of the Seismological Society of America, 91(5):9951012, 2001. [49] H. Magistrale, K. McLaughlin, and S. Day. A geology based 3-D velocity model of the Los Angeles basin sediments. Bulletin of the Seismological Society of America, 86:11611166, 1996. [50] H. Magistrale, S. Day, R. Clayton, and R. Graves. The SCEC southern California reference three-dimensional seismic velocity model version 2. Bulletin of the Seismological Society of America, 90(6B):S65S76, 2000. [51] M. Kohler, H. Magistrale, and R. Clayton. Mantle heterogeneities and the SCEC three-dimensional seismic velocity model version 3. Bulletin of the Seismological Society of America, 93:757774, 2003. [52] Robert W. Graves and Arben Pitarka. Simulation of broadband time-histories combining deterministic and stochastic methodologies. In Proceedings of the American Geophysical Union Fall Meeting, USA, 2003. [53] Robert W. Graves. Broadband simulation for a mw 6.7 earthquake on the puente hills fault. Seismological Research Letters, 76:242, 2005. [54] AISC. Manual of Steel Construction, Load and Resistance Factor Design (Second Edition). American Institute of Steel Construction, Inc., USA, 1994.

Вам также может понравиться