Академический Документы
Профессиональный Документы
Культура Документы
Start-Up Date:
Contact Phone
11/23/13
Emilo
City
8603313505
State Zip Code Country
Hartford
Supplier Type:
State Contact Name
CT
Contact Phone
USA
Flow Tech
Model Number (Type Code)
South Windsor
CT
Serial Number
Jim Lewis
860-291-8886
Software Revision code
2133600622
314E HEX
Supply Fan
Speed Control
Scalar
Installation Checks - Mechanical Mechanical Installation Cable Connections Proper Grounding Input Fuses Wire run to/from motor Motor cable length Installation Checks - Electrical Drive disconnected - Megger Cable/Motor: Megger test voltage = Input Voltage @ Base Spd L1-L2= L2-L3= L3-L1= T1-T2= T2-T3= T3-T1= 217 216 217 196 196 196
Control (I/O, Feedback) Ambient Temperature Drive Unit cooling / Air flow Motor disengaged Safe to operate machine AutoTune completed
Reading
60-70F
Reading
T1-PE = T2-PE =
T3-PE =
L1 = L2 = L3 = T1 = T2 = T3 =
26 25 26 32 32 32
Additional Comments:
S2 readings recorded at 60hz ,set parameter 2609 noise smoothing to "enable" and para 2606 to 8hz
Performed by:
Derek Labbie
By submittal of this form you commit that all information provided is accurate to the best of your ability, provided to the customer, and the requirements as listed here and in the product user Manual have been completed.