Errata

NFPA 22
Standard for Water Tanks for Private Fire Protection
2008 Edition Reference: 14.4.5.3 and 14.4.6.1 Errata No.: 22-08-1 The Committee on Water Tanks notes the following errors in the 2008 edition of NFPA 22, Standard for Water Tanks for Private Fire Protection. 1. Revise the reference in 14.4.5.3 to read as follows: 14.4.5.3 The bypass shall be sized to fill the tank in accordance with 13.4.2 14.4.2 but shall not be smaller than 2 in. (50 mm). 2. Revise the reference in 14.4.6.1 to read as follows: 14.4.6.1 When the tank is to be filled by a filling pump, the pump and connections shall be of such size that the tank can be filled in accordance with 13.4.2 14.4.2.

Issue Date: August 20, 2010


(Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/codelist)