INDEX
Installation
Support
Software
Programming
2. System Installation
3. Access Window
4. KV-D20 Operator
Interface Panel
1. Introduction
1. Programming
2. Editor
2. Instructions
3. Simulator
3. Interrupts
4. Monitor
4. High-speed Counters
5. Appendices
5. Positioning Control
6. Interrupts, High-speed
Counters, Positioning
Control
5. KV-10/80 Hardware
6. Handheld Programmer
7. Serial Communication
8. Programming
Examples
KEYENCE CORPORATION
1-3-14, Higashi-Nakajima,
Higashi-Yodogawa-ku,
Osaka, 533-8555, Japan
PHONE: 81-6-6379-2211
FAX: 81-6-6379-2131
User's Manual
Visual KV Series 3 Programming
1. Configuration and
Specifications
Visual KV Series
Programming
Safety Precautions
This instruction manual describes the operation and function of the KV Series PLC.
Read this manual carefully to ensure safe use and maximum performance from your
KV Series PLC.
Symbols
The following symbols alert you to important messages. Be sure to read these
messages carefully.
Failure to follow instructions may lead to injury. (electric
CAUTION
Note:
Conventions
This manual describes the operation/function of all Keyence KV Series PLC.
Note following conventions when you use.
Visual KV (Series)
KV-10xx, 16xx, 24xx, 40xx
KV-10AR/AT/DR/DT
KV-24AR/AT/DR/DT
KV-16AR/AT/DR/DT
KV-40AR/AT/DR/DT
Conventional KV (Series)
KV-300 (Series)
KV-10/80 (Series)
KV-10R(W)/T(W)
KV-24R(W)/T(W)
KV-80R(W)/T(W)
KV-300
KV-16R(W)/T(W)
KV-40R(W)/T(W)
General Precautions
At startup and during operation, be sure to monitor the functions and performance of the KV Sereis PLC.
We recommend that you take substantial safety measures to avoid any damage
in the event a problem occurs.
Do not open or modify the KV Series PLC or use it in any way other than described in the specifications.
When the KV Series PLC is used in combination with other instruments, functions and performance may be degraded, depending on operating conditions and
the surrounding environment.
Do not use the KV Series PLC for the purpose of protecting the human body.
Note: The built-in display may show the error message "Error 40" blinking the very
first time you turn on the power supply to the Visual KV Series. Press any key
around the display to cancel this message.
The Visual KV Series shows this message when no program is loaded.
(1)
Note to User
When using the Visual KV Series in the following conditions or environments, be
sure to use the Visual KV Series with sufficient margin regarding the rating and
functions, take appropriate safety precautions such as fail-safe, and contact our
sales personnel if any questions arise.
Use for nuclear power control, railway facilities, air service facilities, vehicles,
combustion devices, medical equipment, amusement machines, safety equipment, etc.
Use for applications where large effects are predicted to be given on human lives
and properties and safety is especially requested.
For wiring materials, use lead wires whose sheath is 0.4 mm or more.
(2)
(3)
Interrupt function
The Visual KV Series is equipped with four high-speed interrupt inputs of
10 s maximum.
Input time constant change function
The time constant can be set in 7 steps from 10 s to 10 ms.
Double memory backup functions
In addition to a conventional SRAM battery backup function, the Visual KV Series
is also equipped with an EEPROM backup function.
The time constant for an input relay specified by the HSP instruction is 10 s.
The analog trimmer function is set with the Access Window built into the basic
unit.
The available device setting range of the TMIN instruction is from 0 to 65535.
[Handheld programmer KV-P3E(01) can display 0 to 9999 .]
The specifications for output current of transistor outputs Nos. 500 to 502 is 100
mA.
Conventional KV Series expansion units are not available as expansion units for
the Visual KV Series.
The channel setting switch is not provided for expansion units. Channels are
determined in connection order.
Scans in expansion I/O units are not synchronous with the scan time in Visual KV
Series basic units.
Data memory device Nos. DM1000 to DM1999 are assigned as special data
memories.
(4)
CAUTION
When using the ladder support software "KV IncrediWare (DOS)" or "LADDER
BUILDER for KV Ver. 1.0x", set the model to "KV-300".
DM0 to DM1999 are only available.
When the ladder support software "LADDER BUILDER for KV Ver. 1.0x" is
used, do not use the monitors Change All function. If the Change All function
is used, the basic unit may be damaged. Never use the Change All function.
Peripheral units and other units incompatible with the Visual KV Series
Peripheral units in the conventional KV Series and other units shown below are not
compatible with the Visual KV Series.
(5)
Never leave both the KV-D20 operator interface panel and KV-P3E(01) handheld
programmer on simultaneously for a long period of time.
(6)
1 Installation
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Handheld Programmer
Describes how to use the handheld programmer and memory card.
Chapter 7
Chapter 8
Chapter 9
Chapter 10
Troubleshooting
This chapter describes the error code list, countermeasures against problems, and error
indications for each unit.
Appendices
The appendix includes a list of ladder program applications and the index.
2 Support Software
Chapter 1
Introduction
Describes the items included in the package, the product outline, the method to connect
a personal computer, the installation method, etc.
(7)
Chapter 2
Editor
Describes the operating procedures in Editor mode.
Chapter 3
Simulator
Describes the operating procedures in Simulator mode.
Chapter 4
Monitor
Describes the operating procedures in Monitor mode.
Appendices
Includes instructions list, devices list, sample program list and quick reference for key
operation and shortcuts.
3 Programming
Chapter 1
Programming
Describes basic knowledge including program creation procedures, device configuration,
relay assignments, special functions to set and confirm Visual KV Series operations, as
well as the extended ladder diagrams. Understand the contents described here completely at first before creating programs.
Chapter 2
Instructions
Describes the concrete usage of instructions in the KV Series.
Refer to "Chapter 3 Interrupts" on page 3-183 for details of interrupt instructions.
Refer to "Chapter 4 High-speed counters" on page 3-195 for details of the high-speed
counters used in the application instruction.
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Serial Communication
The KV Series can be connected to an external device with an RS-232C interface to
establish communication.
This chapter describes communications specifications, how to connect the KV Series to
external devices, and how to perform communication.
Chapter 8
Programming Examples
Describes the typical programming examples for KV-10/80 Series. These programs can
be used for Visual KV Series. However, pay attention to the I/O addressing compatibility
before use.
(8)
Contents
3
Programming
Chapter 1
Programming
1.1
Before Creating Programs .............................................................................. 3-2
1.1.1 Flow from Introduction to Operation ................................................................... 3-2
1.1.2 Scan Time ........................................................................................................... 3-3
Scan time ..................................................................................................... 3-3
Input response time delay ............................................................................ 3-3
1.2
User Memory .................................................................................................... 3-4
1.2.1 Program Capacity ............................................................................................... 3-4
Maximum number of lines in a program ....................................................... 3-4
Calculating the byte count used ................................................................... 3-4
1.3
Device Configuration ....................................................................................... 3-5
1.3.1 Device List .......................................................................................................... 3-5
Relay list ...................................................................................................... 3-5
List of I/O relays in basic units ..................................................................... 3-5
List of relays in expansion units ................................................................... 3-6
1.3.2 Relay No. ............................................................................................................ 3-7
Address No. ................................................................................................. 3-7
Contact No. .................................................................................................. 3-8
Channel No. ................................................................................................. 3-8
1.3.3 Assigning Relay Nos. .......................................................................................... 3-8
1.3.4 Input Relays ........................................................................................................ 3-9
Basic unit ..................................................................................................... 3-9
Expansion unit ........................................................................................... 3-10
1.3.5 Output Relays ................................................................................................... 3-10
Output operation time ................................................................................ 3-10
1.3.6 Internal Utility Relays ........................................................................................ 3-11
Retentive function of internal utility relays .................................................. 3-11
1.3.7 Special Utility Relays ........................................................................................ 3-12
Description ................................................................................................. 3-12
1.3.8 Special Utility Relay List ................................................................................... 3-14
Special relays and arithmetic operation flags ............................................ 3-14
Special utility relays for high-speed counter(0) .......................................... 3-14
Special utility relays for high-speed counter(1) .......................................... 3-15
Other special utility relays .......................................................................... 3-15
1.3.9 Timers and Counters ........................................................................................ 3-18
Timer/Counter list ....................................................................................... 3-18
Description ................................................................................................. 3-18
1.3.10 Data Memories ................................................................................................. 3-19
1.3.11 Temporary Data Memory .................................................................................. 3-21
1.3.12 Relay Nos. and Functions ................................................................................. 3-22
1.4
Special Functions .......................................................................................... 3-23
1.4.1 Input Time Constant Change Function ............................................................. 3-23
Setting the input time constant for basic units using special utility relays .. 3-23
1.4.2 Modifying the Input Relay Time Constant ......................................................... 3-24
Modification within the CPU ....................................................................... 3-24
1.4.3 Constant Scan Time Mode ............................................................................... 3-25
1.4.4 Output Disabled Function ................................................................................. 3-26
1.4.5 Input Refresh Disabled Function ...................................................................... 3-26
1.4.6 Contact Comment Save Function ..................................................................... 3-27
1.4.7 Special Functions ............................................................................................. 3-28
Constant Scan Time Mode ........................................................................ 3-28
Output Disabled Function .......................................................................... 3-28
Input Refresh Disabled Function ................................................................ 3-28
1.5
1.5.1
1.5.2
1.5.3
(9)
Chapter 2
Chapter 3
Instructions
2.1
2.1.1
2.1.2
2.1.3
2.1.4
2.1.5
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.3
2.4
2.4.1
2.4.2
2.4.3
2.5
Interrupts
Visual KV
3.1
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.3
Direct Input/Output ...................................................................................... 3-197
3.3.1 Direct Input ..................................................................................................... 3-197
3.3.2 Direct Output ................................................................................................... 3-197
3.4
3.4.1
3.4.2
3.4.3
3.4.4
Chapter 4
High-speed Counters
4.1
Visual KV
4.2
Outline of High-speed Counters ................................................................. 3-206
4.2.1 High-speed Counters and High-speed Counter Comparators ........................ 3-206
Structure of high-speed counters and high-speed counter comparators . 3-206
Specifications of high-speed counters ..................................................... 3-208
High-speed counter comparators ............................................................. 3-209
4.2.2 Internal Clock for High-speed Counters .......................................................... 3-210
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.5
4.3.6
4.5
(10)
4.5.1
4.5.2
4.5.3
4.5.4
4.5.5
Chapter 5
Positioning Control
Visual KV
5.1
Outline of Positioning Control .................................................................... 3-254
5.1.1 Ramp-up/down Control ................................................................................... 3-254
5.2
Parameter Setting and Operating Procedures .......................................... 3-255
5.2.1 Parameter Setting Procedure ......................................................................... 3-255
5.2.2 Operating Procedure ...................................................................................... 3-257
5.3
5.3.1
5.3.2
5.3.3
Chapter 6
KV-300, KV-10/80
6.1
Interrupt Instructions ................................................................................... 3-268
6.1.1 Description of Interrupts .................................................................................. 3-268
Input processing for routine program and interrupt routine ...................... 3-268
Types of interrupt ..................................................................................... 3-268
Interrupt priority ........................................................................................ 3-269
Interrupt routine ........................................................................................ 3-269
Direct output ............................................................................................. 3-270
Direct input ...............................................................................................3-270
6.1.2 Interrupt Instructions ....................................................................................... 3-271
6.2
Direct Clock Pulse ........................................................................................ 3-276
6.2.1 Output of Direct Clock Pulse ........................................................................... 3-276
Outline of High-Speed Counters .............................................................. 3-276
Outline of Pulse Output ............................................................................ 3-279
Examples of Pulse Output ....................................................................... 3-284
6.3
Positioning Control ...................................................................................... 3-296
6.3.1 Positioning Control (Ramp-up/down Control) ................................................. 3-296
Outline of positioning control .................................................................... 3-296
Setting and application of parameters ..................................................... 3-297
Examples of stepping motor control ......................................................... 3-300
Chapter 7
Serial Communication
7.1
7.1.1
7.1.2
7.1.3
7.2
Serial Communication ................................................................................. 3-308
7.2.1 Command Transmission Procedure ............................................................... 3-308
(11)
Chapter 8
7.2.2
7.2.3
7.2.4
7.2.5
7.2.6
7.2.7
7.3
7.3.1
7.3.2
7.3.3
7.4
Programming Examples
8.1
List
......................................................................................................... 3-324
8.2
Details ......................................................................................................... 3-326
8.2.1 Reference Program Examples ........................................................................ 3-326
Basic Instructions ..................................................................................... 3-326
Application Instructions ............................................................................ 3-334
Arithmetic Instructions .............................................................................. 3-343
3-367
Installation
Chapter 1
Visual KV
1.1
System Configuration ...................................................................................... 1-2
1.1.1 System Configuration ......................................................................................... 1-2
1.2
Specifications ................................................................................................... 1-4
1.2.1 General Specifications ........................................................................................ 1-4
1.2.2 AC Power Specifications .................................................................................... 1-5
Visual KV Series operation at power interruption ........................................ 1-5
1.2.3 Performance Specifications ................................................................................ 1-6
Data backup function against instantaneous power interruption ................. 1-7
1.3
Common I/O Specifications of Basic Units ................................................... 1-8
1.3.1 Model of a Basic Unit .......................................................................................... 1-8
1.3.2 Common I/O Specifications ................................................................................ 1-8
1.4
KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit) ............................................. 1-10
1.4.1 Part Names and Functions ............................................................................... 1-10
1.4.2 Terminal Layout Drawings and I/O Circuit Diagrams ........................................ 1-11
KV-10AR/DR (Relay output type) .............................................................. 1-11
KV-10AT(P)/DT(P) (Transistor output type) ............................................... 1-13
1.4.3 AC Power Input (KV-10AR/AT(P)) .................................................................... 1-14
1.4.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature 1-15
1.4.5 Dimensions ....................................................................................................... 1-16
1.5
KV-16AR/AT(P)/DR/DT(P) (16-I/O Basic Unit) ............................................. 1-17
1.5.1 Part Names and Functions ............................................................................... 1-17
1.5.2 Terminal Layout Drawings and I/O Circuit Diagrams ........................................ 1-18
KV-16AR/DR (Relay output type) .............................................................. 1-18
KV-16AT(P)/DT(P) (Transistor output type) ............................................... 1-20
1.5.3 AC Power Input (KV-16AR/AT(P)) .................................................................... 1-21
1.5.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature 1-22
1.5.5 Dimensions ....................................................................................................... 1-23
1.6
KV-24AR/AT(P)/DR/DT(P) (24-I/O Basic Unit) ............................................. 1-24
1.6.1 Part Names and Functions ............................................................................... 1-24
1.6.2 Terminal Layout Drawings and I/O Circuit Diagrams ........................................ 1-25
KV-24AR/DR (Relay output type) .............................................................. 1-25
KV-24AT(P)/DT(P) (Transistor output type) ............................................... 1-27
1.6.3 AC Power Input (KV-24AR/AT(P)) .................................................................... 1-28
1.6.4 Relationship between Continuous Simultaneous ON Ratio and Ambient Temperature 1-29
1.6.5 Dimensions ....................................................................................................... 1-30
1.7
(12)
Chapter 2
System Installation
Visual KV
2.1
2.1.1
2.1.2
2.1.3
(13)
Chapter 3
Access Window
Visual KV
3.1
Overview of the Access Window .................................................................. 1-80
3.1.1 What is the Access Window ............................................................................. 1-80
3.1.2 Access Window Use Examples ........................................................................ 1-80
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.3
Digital Trimmer Mode .................................................................................... 1-84
3.3.1 Function and Operating Procedure ................................................................... 1-84
Key operation and screen display .............................................................. 1-84
Function and operating procedure ............................................................. 1-84
3.4
Device Mode ................................................................................................... 1-87
3.4.1 Function and Operating Procedure ................................................................... 1-87
Devices that can be displayed and changed ............................................. 1-87
Key operation and screen display .............................................................. 1-87
Selecting the device and displaying the current value/set value ................ 1-88
Changing a numeric value ......................................................................... 1-89
Holding the setting ..................................................................................... 1-91
3.4.2 Screen Display for Each Device Type .............................................................. 1-91
Data memory (DM) .................................................................................... 1-91
Temporary data memory (TM) ................................................................... 1-91
Timer/counter (T/C) .................................................................................... 1-92
High-speed counter comparator (CTC) ...................................................... 1-92
Trimmer (TRM) .......................................................................................... 1-93
Relay (RLY) ...............................................................................................1-93
3.5
System Mode .................................................................................................. 1-94
3.5.1 Function and Operating Procedure ................................................................... 1-94
Key operation and screen display .............................................................. 1-94
LOAD mode and SAVE mode .................................................................... 1-96
Display in LOAD/SAVE mode .................................................................... 1-96
3.6
Message Display ............................................................................................ 1-97
3.6.1 Error Messages and Error Status ..................................................................... 1-97
3.6.2 User Messages ................................................................................................. 1-97
How to use the user messages .................................................................. 1-98
Chapter 4
Visual KV
4.1
4.1.1
4.1.2
4.1.3
(14)
Chapter 5
KV-300, KV-10/80
5.1
System Configuration .................................................................................. 1-166
5.1.1 KV-300 ............................................................................................................1-166
5.1.2 KV-10/80 ......................................................................................................... 1-167
5.2
Module/Unit Specifications ......................................................................... 1-168
5.2.1 Wiring: KV-U4 Power Supply Module ............................................................. 1-168
Parts and functions .................................................................................. 1-168
5.2.2 Wiring: KV-U5 DC Power Distribution Module ................................................ 1-169
Parts and functions .................................................................................. 1-169
5.2.3 Wiring: KV-300 CPU ....................................................................................... 1-170
Parts and functions .................................................................................. 1-170
5.2.4 Wiring: KV-C16X/C32X Connector Input Module ........................................... 1-171
Parts and functions .................................................................................. 1-171
5.2.5 Wiring: KV-C32T/B16R/B16S Connector Output Module ............................... 1-172
Parts and functions .................................................................................. 1-172
5.2.6 Wiring: KV-R1A I/O Distribution Module ......................................................... 1-173
Parts and functions .................................................................................. 1-173
5.2.7 Wiring: KV-R8X/R16X/R8R/R16R/R8T/R16T I/O Terminal Modules ............. 1-174
Parts and functions .................................................................................. 1-174
5.2.8 Module Names and Functions ........................................................................ 1-175
5.2.9 Peripheral Equipment Names and Functions ................................................. 1-176
5.3
5.3.1
5.3.2
5.3.3
(15)
5.3.6 Connecting the AC Power Supply Module and DC Power Distribution Module .... 1-182
KV-U4 AC Power Supply Module ............................................................ 1-182
KV-U5 DC Power Distribution Module ..................................................... 1-182
5.3.7 I/O Connectors ................................................................................................ 1-183
KV-300 CPU ............................................................................................ 1-183
KV-C16X/C32X ........................................................................................ 1-184
KV-C32T/B16R/B16S .............................................................................. 1-185
KV-R8X/R16X/R8R/R16R/R8T/R16T ...................................................... 1-186
5.3.8 I/O Terminal Modules: Communication Cables and Power Distribution ......... 1-187
Transmission distance by cable type ....................................................... 1-187
Connection patterns ................................................................................. 1-187
Incorrect wiring patterns ........................................................................... 1-188
Power distribution .................................................................................... 1-188
5.3.9 Connector Assembly Instructions ................................................................... 1-189
5.3.10 KV-300 CPU I/O Indicators ............................................................................. 1-191
5.3.11 KV-10/80 Expansion Units .............................................................................. 1-192
5.3.12 Mounting Environment .................................................................................... 1-194
Chapter 6
Handheld Programmer
6.1
Using the Handheld Programmer ............................................................... 1-196
6.1.1 Outline of the Handheld Programmer ............................................................. 1-196
6.1.2 Precautions ..................................................................................................... 1-198
6.2
Basic Operations ......................................................................................... 1-200
6.2.1 Basic Programming Operation ........................................................................ 1-200
6.3
6.4
Memory Card ................................................................................................ 1-230
6.4.1 Functions [used with KV-P3E(01)] .................................................................. 1-230
6.4.2 Storage Capacity ............................................................................................ 1-230
CLEAR ..................................................................................................... 1-232
NEW ......................................................................................................... 1-233
ACCS ....................................................................................................... 1-234
ACCS: SAVE ........................................................................................... 1-235
ACCS: LOAD ........................................................................................... 1-236
ACCS: VERIFY ........................................................................................ 1-236
ACCS: DELETE ....................................................................................... 1-237
Chapter 7
KV-300
7.1
Outline ......................................................................................................... 1-240
7.1.1 Features .......................................................................................................... 1-240
7.2
7.2.1
7.2.2
7.2.3
7.3
7.3.1
7.3.2
7.3.3
(16)
Chapter 8
KV-300
8.2
Configuration ...............................................................................................1-313
8.2.1 Parts and Functions ........................................................................................ 1-313
8.2.2 System Configuration ..................................................................................... 1-314
8.3
Installation .................................................................................................... 1-315
8.3.1 Terminal Nos. ................................................................................................. 1-315
(17)
8.3.2
8.3.3
8.3.4
8.3.5
8.4
8.4.1
8.4.2
8.4.3
8.4.4
8.4.5
8.4.6
8.4.7
8.4.8
8.4.9
8.5
8.5.1
8.5.2
8.5.3
Chapter 9
KV-10/80
9.2
Configuration ............................................................................................... 1-335
9.2.1 Part Names and Functions ............................................................................. 1-335
KV-AD4 .................................................................................................... 1-335
KV-DA4 .................................................................................................... 1-336
9.2.2 Specifications .................................................................................................. 1-337
KV-AD4 .................................................................................................... 1-337
KV-DA4 .................................................................................................... 1-339
9.2.3 System Configuration ..................................................................................... 1-341
9.3
9.3.1
9.3.2
9.3.3
9.6
(18)
Chapter 10
Troubleshooting
10.1
10.1.1
10.1.2
10.1.3
10.1.4
10.2
Appendices
Appendix A. Specifications and Dimensions [Visual KV Series] .................... 1-382
A.1
System Specifications [Visual KV Series] ....................................................... 1-382
Hardware ................................................................................................. 1-382
Software and Programming ..................................................................... 1-383
AC power supply unit ............................................................................... 1-384
A.2
Common I/O Specifications of Basic Units ..................................................... 1-384
Input specifications .................................................................................. 1-384
Output specifications (relay output): KV-10AR/DR, KV-16AR/DR,
KV-24AR/DR, and KV-40AR/DR .............................................................. 1-385
Output specifications (transistor output): KV-10AT(P)/DT(P),
KV-16AT(P)/DT(P), KV-24AT(P)/DT(P), and KV-40AT(P)/DT(P) ............ 1-385
A.3
Expansion Unit Specifications ........................................................................ 1-385
A.4
Dimensions .....................................................................................................1-389
Appendix B. Specifications and Dimensions [KV-300 Series] ......................... 1-392
B.1
System Specifications [KV-300 Series] .......................................................... 1-392
Hardware ................................................................................................. 1-392
Software and Programming ..................................................................... 1-393
AC Power supply module/DC power distribution module ........................ 1-394
B.2
Module Specifications ..................................................................................... 1-398
KV-300 CPU ............................................................................................ 1-398
KV-C16X/C32X Input Modules ................................................................ 1-399
KV-C32T/B16R/B16S Output Modules ................................................... 1-400
KV-R8X/R16X I/O Terminal Modules ....................................................... 1-401
KV-R8T/R16T/R8R/R16R I/O Terminal Modules ..................................... 1-402
KV-R8T/R16T/R8R/R16R I/O Terminal Modules (RUN Output) .............. 1-403
KV-R1A I/O Distribution Module .............................................................. 1-403
B.3
Dimensions .....................................................................................................1-404
Appendix C.
1-419
Support software
Chapter 1
Introduction
1.1
1.2
Outline of the Ladder Builder for KV .............................................................. 2-3
1.2.1 Operating environment and system configuration .............................................. 2-3
1.2.2 Features and functions of the Ladder Builder for KV .......................................... 2-4
Features of the Ladder Builder for KV ......................................................... 2-4
Functions of the Ladder Builder for KV ........................................................ 2-6
1.3
(19)
Chapter 2
1.5
1.6
1.6.1
1.6.2
1.6.3
1.6.4
1.6.5
Editor
KV-300
2.1
Outline of the Editor Functions .................................................................... 2-26
2.1.1 Cautions for editing ladder programs ................................................................ 2-26
2.2
Edit Screen .....................................................................................................2-27
2.2.1 Name and function of each part of the screen .................................................. 2-27
2.2.2 Ladder program window screen ....................................................................... 2-28
2.3
2.3.1
2.3.2
2.3.3
2.3.4
2.3.5
2.3.6
2.3.7
2.4
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
2.4.6
2.5
2.5.1
2.5.2
2.5.3
2.6
Edit and Arrangement .................................................................................. 2-52
2.6.1 Copy, move, and delete .................................................................................... 2-52
2.6.2 Inserting and deleting lines ............................................................................... 2-57
2.7
2.7.1
2.7.2
2.7.3
2.7.4
2.7.5
2.8
Editing the Mnemonic List ........................................................................... 2-67
2.8.1 Displaying and terminating a mnemonic list ..................................................... 2-67
2.8.2 Copy, move, and delete .................................................................................... 2-69
2.9
Displaying the Use Status ............................................................................. 2-70
2.9.1 Displaying a use status list ............................................................................... 2-70
2.10 Setting the System .........................................................................................2-71
2.10.1 Setting the system ............................................................................................ 2-71
2.11 Entering and Developing Macros ................................................................ 2-72
2.11.1 Creating a macro file .........................................................................................2-72
2.11.2 Entering and developing macros ...................................................................... 2-74
2.12
2.12.1
2.12.2
2.12.3
2.13
(20)
Chapter 3
Simulator
3.1
Outline of the Simulator Functions .............................................................. 2-84
3.1.1 Outline of the functions ..................................................................................... 2-84
3.1.2 Restrictions in the simulator .............................................................................. 2-84
3.2
Starting up and Exiting from the Simulator ................................................. 2-86
3.2.1 Operating procedure for startup and exit .......................................................... 2-86
3.2.2 Name and function of each part of the screen .................................................. 2-88
Chapter 4
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.4
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.5
3.5.1
3.5.2
3.5.3
3.5.4
3.5.5
3.5.6
3.5.7
Monitor
4.1
4.1.1
4.1.2
4.1.3
4.2
Communicating with the PLC ..................................................................... 2-136
4.2.1 Setting the PLC communication parameters .................................................. 2-136
4.2.2 Setting the comment transfer .......................................................................... 2-138
4.3
Starting up and Exiting from the Monitor .................................................. 2-139
4.3.1 Operating procedures for startup and exit ...................................................... 2-139
4.3.2 Name and function of each part of the screen ................................................ 2-143
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.4.5
4.4.6
4.4.7
4.5
Monitor All and Registration Monitor ......................................................... 2-148
4.5.1 Functions of the monitor all window ................................................................ 2-148
4.5.2 Functions of the registration monitor .............................................................. 2-148
4.6
4.6.1
4.6.2
4.6.3
(21)
Appendices
Appendix A Error Message List ......................................................................... 2-156
A-1
System errors ................................................................................................. 2-156
A-2
Memory errors ................................................................................................ 2-156
A-3
File errors ........................................................................................................ 2-157
A-4
Installation errors ............................................................................................ 2-157
A-5
Errors that occur in the editor ......................................................................... 2-158
A-6
Errors that occur in the monitor/simulator ....................................................... 2-159
A-7
Communication errors (displayed in the monitor) ........................................... 2-159
A-8
PLC errors ...................................................................................................... 2-160
A-9
Errors that occur during compilation ............................................................... 2-161
Appendix B Instruction List ............................................................................... 2-163
B-1
Basic instructions ............................................................................................ 2-163
B-2
Application instructions ................................................................................... 2-164
B-3
Arithmetic instructions ..................................................................................... 2-165
B-4
Interrupt instructions ....................................................................................... 2-166
Appendix C Relay No. List .................................................................................. 2-167
C-1
Relays, timers, counters, and memory numbers for each model ................... 2-167
Appendix D Special Utility Relay List ................................................................ 2-168
D-1
Special relays and arithmetic operation flags ................................................. 2-168
D-2
Special utility relays for high-speed counter (0) .............................................. 2-168
D-3
Special utility relays for high-speed counter (1) .............................................. 2-169
D-4
Other special utility relays ............................................................................... 2-169
D-5
Memory switches ............................................................................................ 2-172
D-6
Special memory list ......................................................................................... 2-172
Appendix E Devices for KV-10R(W)/T(W) to 80R(W)/T(W), KV-300 ................ 2-174
E-1
Special utility relays ........................................................................................ 2-174
E-2
Memory switches ............................................................................................ 2-176
E-3
Special memory list ......................................................................................... 2-176
Appendix F Sample Program List ..................................................................... 2-178
F-1
Description of sample ladder programs .......................................................... 2-178
Appendix G Quick Reference ............................................................................. 2-180
G-1 Editor .............................................................................................................. 2-180
G-2 Simulator ......................................................................................................... 2-188
G-3 Monitor ............................................................................................................ 2-195
Appendix H Notes for Programming ................................................................. 2-201
H-1
Circuits that must be modified ........................................................................ 2-201
H-2
Precautions for programming ......................................................................... 2-202
H-3
Programs which cannot be decompiled .......................................................... 2-203
Appendix I
Appendix J
2-215
(22)
Caution
KEYENCE has thoroughly checked and reviewed this manual. Please contact
the sales office listed at the end of this manual if you have any questions or
comments regarding this manual or if you find an error.
KEYENCE assumes no liability for damages resulting from the use of the information in this manual, item 3 above notwithstanding.
All company names and product names in this manual are registered trademarks or
trademarks of their respective owners.
(23)
Chapter 1
Programming
This chapter describes basic knowledge including program creation procedures,
device configuration, relay assignments, special functions to set and confirm Visual
KV Series operations, as well as the extended ladder diagrams. Understand the
contents described here completely at first before creating programs.
1.1
1.1.1
1.1.2
1.2
1.2.1
1.3
1.3.1
1.3.2
1.3.3
1.3.4
1.3.5
1.3.6
1.3.7
1.3.8
1.3.9
1.3.10
1.3.11
1.3.12
1.4
1.4.1
1.4.2
1.4.3
1.4.4
1.4.5
1.4.6
1.4.7
1.5
1.5.1
1.5.2
1.5.3
3-23
3-24
3-25
3-26
3-26
3-27
3-28
Fig. 1
PB1 = N.O. contact switch
PB2 = N.C. contact switch
PB1
PB2
RL
(Relay)
Time chart
PB1 contact
PB2 contact
PL
ON
OFF
ON
OFF
ON
PL
OFF
Next, a program is created that will use the same operation as this circuit to control a PLC.
Program examination
Circuit 1 shows relay symbols for the latch circuit.
Examine which contact in the Visual KV Series is used for each pushbutton switch and pilot lamp
(Table 1). When many I/O devices are required for control, expansion units should also be considered.
Table 1
Circuit 1
RL
PB1 PB2
RL
Relay (coil)
Relay (contact)
RL
Relay (contact)
PL
Pilot lamp
I/O device
Pushbutton switch PB1 (N.O. contact)
Pushbutton switch PB2 (N.C. contact)
Relay RL
Pilot lamp PL
Contact No.
Input relay (0000)
Input relay (0001)
Internal relay (1000)
Output coil (0500)
Program creation
Edit a program using the "LADDER BUILDER for KV" programming support software creation tool.
Ladder diagram
0000
0001*
1000
1000
1000
0500
Coding list
LD
0000
OR
1000
AND 0001
OUT 1000
LD
1000
OUT 0500
END
Operation
3-2
Chapter 1 Programming
Input processing
Program execution
Output processing
The duration of time required to perform one cycle is called the scan time (or cycle
time). The scan time varies based on program size and the instructions used in the
program.
Input signal
ON
OFF
Scan time
Input processing
Program
execution
Output processing
Input processing
Program
execution
Output processing
Program
execution
Input processing
Read
Output processing
Input processing
Program
execution
Output processing
Input processing
Output processing
Read
Scan time
Reference: The maximum and minimum values of the input response time are as
follows.
Maximum value: Input time constant + Scan time x 2 + Output response delay time
Minimum value: Input time constant + Scan time + Output response delay time
Note 1: When the input time constant is made small by setting the HSP instruction,
special utility relay 2813, and data memory DM1940, a signal may not be received if
its ON time is shorter than the scan time.
Note 2: The INT instruction is independent of the scan time.
Note 3: The minimum scan time is 140 s (with the basic unit).
Chapter 1 Programming
3-3
11
For more about byte counts for each instruction, refer to "2.1 Instruction List" (p.3-34).
Total byte count of the memory used by instructions 6,000 bytes / 12,000
bytes
For example, the allowable number of steps to be written can be calculated from the
memory occupied by the instructions as follows.
12,000 bytes / 3 bytes (average byte count of an instruction) = 4,000 steps
Note: If either the memory occupied by the instructions or the memory occupied by
objects of a program exceeds the specified memory capacity, the program cannot
be written or executed.
0000
0500
T000
0500
Line No.
Instruction
Operand
Byte count
00000
LD
0000
00001
OR
0500
00002
TMR
000#00020
00003
ANB
T000
OUT
0500
00004
Total
3-4
Chapter 1 Programming
Number of objects
14 bytes
32 bytes
Normal use
High-speed
use (1)
0000
0001
0002
Input relays
(Direct input
allowed area)
Interrupt inputs
INT0 to INT3
Remarks
(Polarity inversion
allowed)
Input captures
0003
High-speed
counter 0 input
High-speed
counter 1 input
0004
0005
0006
Input relays
0007
0008
0009
0010 to 0415
0502
A phase
input
B phase
input
Output relays
(Direct output
allowed area)
11
Preset
input
Input relays
0500
0501
High-speed
counter 0
High-speed
counter 1
High-speed
counter 0
High-speed
counter 1
High-speed
counter 0
High-speed
counter 1
0503
70 points
0504 to 0915
Output relays
76 points
1000 to 1915
160 points
2000 to 2815
144 points
2900 to 2915
2,144 points
Note 1: The ON/OFF status of the set functions is always cleared when the operation mode is changed from PROGRAM to RUN. However, special utility relays 2700
to 2715 are held even when the operation mode is changed from PROGRAM to
RUN or when the power is turned off.
Note 2: Internal utility relays can be held by setting the MEMSW instruction
KV-10xx
KV-16xx
KV-24xx
KV-40xx
0000 to 0005
0000 to 0009
0000 to 0015
0000 to 0107
0500 to 0503
0500 to 0505
0500 to 0507
0500 to 0515
Chapter 1 Programming
3-5
KV-E4X
KV-E8X
KV-40
KV-10/16/24
KV-10/16/24
KV-E16X
KV-40
KV-40
KV-10/16/24
100 to 103 200 to 203 100 to 107 200 to 207 100 to 115 200 to 215
200 to 203 300 to 303 200 to 207 300 to 307 200 to 215 300 to 315
300 to 303 400 to 403 300 to 307 400 to 407 300 to 315 400 to 415
400 to 403
400 to 407
400 to 415
Output units
Connection
order
1st output
module
2nd output
module
3rd output
module
4th output
module
KV-E4T(P)/R
KV-E8T(P)/R
KV-E16T(P)/R
600 to 603
600 to 607
600 to 615
700 to 703
700 to 707
700 to 715
800 to 803
800 to 807
800 to 815
900 to 903
900 to 907
900 to 915
I/O units
KV-E4XR/T(P)
Connection
order
1st input
module
2nd input
module
3rd input
module
4th input
module
1st output
module
2nd output
module
3rd output
module
4th output
module
*
*
3-6
Input relays
Output relays
KV-10/16/24
KV-40
100 to 103
200 to 203
200 to 203
300 to 303
300 to 303
400 to 403
KV-10/16/24
KV-40
603 to 606
603 to 606
703 to 703
703 to 703
803 to 803
803 to 803
903 to 903
903 to 903
400 to 403
Relay Nos. of expansion units are automatically assigned in the order of connection.
The connection order is counted only for input and output units. When I/O units are
connected, they are counted as input units and output units separately.
Chapter 1 Programming
12515
Contact No.
(00 to 15)
Address No.
(Input: 0 to 4, output: 5 to 9)
Address No.
Address Nos. are assigned to basic units, input expansion units, output expansion
units, and I/O expansion units. Zero to 4 are assigned to input units, while 5 to 9 are
assigned to output units. Address Nos. assigned in a unit vary based on the number
of I/O terminals and the connection position of the unit.
Model
Basic units
Address Nos.
KV-10xx
0, 5
KV-16xx
0, 5
KV-24xx
0, 5
KV-40xx
0, 1, 5
kV-E4X
1 to 4*
KV-E8X
1 to 4*
KV-E16X
1 to 4*
KV-E4R/E4T(P)
6 to 9
KV-E8R/E8T(P)
6 to 9
KV-E16R/E16T(P)
6 to 9
KV-E4XR/E4XT(P)
1 to 4*, 6 to 9
11
* 2 to 4 in KV-40xx
Chapter 1 Programming
3-7
Contact No.
Contact Nos. are input/output terminal Nos. of basic units, input expansion units,
output expansion units, and I/O expansion units.
Example
In the KV-E4X, with 4 input terminals, the contact Nos. are 0 to 3. In the KVE16T(P), with 16 input terminals, the contact Nos. are 0 to 15.
In a unit with 16 or more terminals, the contact No. of the 17th terminal returns to
0 and its address No. is increased by 1.
Example
In the KV-40AR, with 40 terminals (24 input and 16 output terminals), address
No. 0 is assigned to input terminal Nos. 1 to 16 and address No. 1 is assigned to
input terminal Nos. 17 to 24
Channel No.
The channel No. is the higher order digit in the contact No.
b) KV-E4X Input
expansion
unit
Input: 4 points
c) KV-E8R Output
expansion unit
Output: 8 points
With the connections above, the relay Nos. for each unit are assigned as shown in
the table below.
3-8
Unit
a) KV-16AR
b) KV-E4X
c) KV-E8R
Chapter 1 Programming
Basic unit
Input relay time constant
Though the time constant is usually 10 ms 20%, it can be changed using the
following settings.
While special utility relay 2813 remains ON, the time constant can be changed in
7 steps by setting data memory DM1940 as follows.
When DM1940 is set to 0: 10s 20%
1: 20 s 20%
2: 500 s 20%
3: 1 ms 20%
4: 2.5 ms 20%
5: 5 ms 20%
6: 10 ms 20%
Never set a numeric value of 7 or larger.
11
For more about changing the input time constant, refer to "1.4.1 Input Time Constant Change
Function" (p.3-23).
"HSP instruction" (p.3-86), "INT instruction" (p.3-192), "4.1 High-speed Counter Instructions"
(p.3-204)
Note 1: While special utility relay 2813 remains ON, the input time constant can be
specified for all input relays in a basic unit.
Note 2: Never enter a number of 7 or larger to data memory DM1940.
Note 3: The input time constant specified by data memory DM1940 becomes
effective at the rising edge of special utility relay 2813. To change the input time
constant, first change data memory DM1940, then set special utility relay 2813 to
OFF and ON again. Or change the operation mode of a KV basic unit from PROGRAM to RUN.
Note 4: If the HSP instruction and special utility relay 2813 are used at the same
time, priority is given to the HSP instruction.
Note 5: Only when a high-speed counter input or INT instruction is given, available
input signals do not depend on the scan time.
Chapter 1 Programming
3-9
Expansion unit
Input relay time constant
By setting special utility relays 2609 to 2612 to ON, the time constant in input expansion units can be set to 10 s.
Special utility
relay No.
2609*
2610
2611
2612
*
Function
Input time constant of input expansion unit
with relay Nos. 0100 to 0115
Input time constant of input expansion unit
with relay Nos. 0200 to 0215
Input time constant of input expansion unit
with relay Nos. 0300 to 0315
Input time constant of input expansion unit
with relay Nos. 0400 to 0415
Transistor output
OFF ON: 50 s or less (10 s or less in 500 to 502)
ON OFF: 250 s or less (10 s or less in 500 to 502, 100 s or less for other
outputs in the basic unit)
Relay output
OFF ON: 10 ms or less
ON OFF: 10 ms or less
Transistor output type
KV-10AT(P)/DT(P)
KV-16AT(P)/DT(P)
KV-16AR/DR
KV-24AT(P)/DT(P)
KV-40AT(P)/DT(P)
KV-24AR/DR
KV-40AR/DR
KV-E4T
KV-E8T(P)
KV-E4R
KV-E8R
KV-E16T(P)
KV-E4XT(P)
KV-E16R
KV-E4XR
Note 1: When programming direct clock pulses, output relays 0500 and 0501 are
used to output pulses in a transistor-type output unit.
Note 2: When the ramp-up/down control function is used, output relay 0502 outputs
positioning pulses in a transistor-type output unit.
"Chapter 5. Positioning Control" (p.3-253)
Note 3: When the specified frequency pulse output function is used, output relay
0501 outputs pulses in a transistor-type output unit.
"4.5.1 Specified Frequency Pulse Output Function" (p.3-228)
3-10
Chapter 1 Programming
For more about setting the memory switch, refer to "MEMSW instruction" (p.3-92).
Upper limit
switch
(0000)
0001
1000
0001
#00010
T000
0000
1001
Lower limit
switch
(0001)
Move-down
(0500)
1000
1001
#00010
T001
T000
0501
0500
T001
0500
0501
END
Move-up
(0501)
ENDH
Note: The retentive function is effective only when internal utility relays retained by
the self-retentive circuit or the SET/SFT/KEEP instruction are also retained by the
memory switch.
Internal utility relays are not retained in the program shown below.
0000
1001
Chapter 1 Programming
3-11
11
Description
Relay 2002: Always ON
By setting an output relay to ON using relay 2002, the output relay can be used as a
"running indicator output".
2002
HSP
0100
2002
00000
LDA
DM0000
STA
#03600
C000
2006
1000
C000
Relay 2007: Remains OFF during only one scan when operation is started.
This relay can be used when a signal needs to be sent after a specific period
(equivalent to one scan) after operation is started. This relay can also be used for
an initial reset at the start of operation.
After one scan, this relay remains ON.
1000
2007
#00100
C005
0000
3-12
Chapter 1 Programming
SFT
D
1100
CLK
1100
2008
RES
2008
#00000
LDA
DM0000
STA
Chapter 1 Programming
3-13
11
Relay No.
Always ON.
2003*
Always OFF.
2004*
2005*
2006*
2007*
2008*
2010*
2011*
2012*
2009*
Function
2002*
Read-only relay.
Relay No.
Function
2100*
2101*
Multiplication
mode
2113
2114
ON: Cleared
OFF: Not cleared
ON: Prohibited
OFF: Permitted
ON: Set to OFF
OFF: Not set to OFF
ON: Set to ON
OFF: Not set to ON
ON: Reversed
OFF: Not reversed
ON: Prohibited
OFF: Permitted
ON: Set to OFF
OFF: Not set to OFF
ON: Set to ON
FF: Not set to ON
ON: Reversed
OFF: Not reversed
ON: Cleared
OFF: Not cleared
1 pulse
x2
x4
2 pulses
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Note: Never use special utility relays that are not shown above.
3-14
Chapter 1 Programming
Relay No.
2200*
2201*
2202*
2203
2204
2205
2206
2207
2208
2209
2210
2211
2212
2213
2214
*
Function
ON: Cleared
OFF: Not cleared
ON: Prohibited
OFF: Permitted
ON: Set to OFF
OFF: Not set to OFF
ON: Set to ON
OFF: Not set to ON
ON: Reversed
OFF: Not reversed
ON: Prohibited
OFF: Permitted
ON: Set to OFF
OFF: Not set to OFF
ON: Set to ON
OFF: Not set to ON
ON: Reversed
OFF: Not reversed
ON: Cleared
OFF: Not cleared
Read-only relay.
Multiplication
mode
2213
2214
1 pulse
x2
x4
2 pulses
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Note: Never use special utility relays that are not shown above.
2305
Function
External outputs disabled
(outputs 0500 to 0915)
External refresh inputs disabled
(inputs 0000 to 0415)
Constant scan time mode
(write preset value in TM29)
Remains ON for one scan when scan time exceeds
preset constant scan time.
Start flag for frequency counter operation.
2306
2307
2308
2300
2301
2303
2304
2309
2310
2314
2315
ON: Disabled
OFF: Not disabled
ON: Disabled
OFF: Not disabled
ON: Enabled
OFF: Disabled
ON: Enabled
OFF: Disabled
* Read-only relay.
Chapter 1 Programming
3-15
11
2415
2500
2501
2502
2503
2504
2505
2506
2507
2508
2509
2510
2511
2512
2513
2515
3-16
Function
Timing of CTH0 external signal
OFF
External preset
OFF
OFF
not used
ON
At falling edge
ON
OFF
At rising edge
ON
ON
Level
At rising edge
OFF
ON
At falling edge
ON
OFF
At rising edge
ON
ON
At both edges
At rising edge
OFF
ON
At falling edge
ON
OFF
At rising edge
ON
ON
At both edges
External preset
OFF
OFF
not used
ON
At falling edge
ON
OFF
At rising edge
ON
ON
Level
At rising edge
OFF
ON
At falling edge
ON
OFF
At rising edge
ON
ON
At both edges
At rising edge
OFF
ON
At falling edge
ON
OFF
At rising edge
ON
ON
At both edges
Chapter 1 Programming
Function
Input time constant of input expansion unit with relay
Nos. 0100 to 0115
Input time constant of input expansion unit with relay
Nos. 0200 to 0215
Input time constant of input expansion unit with relay
Nos. 0300 to 0315
Input time constant of input expansion unit with relay
Nos. 0400 to 0415
Clearing of input at expansion disconnect
2712
2714
OFF: 10 ms
ON: 10 s
OFF: 10 ms
ON: 10 s
OFF: 10 ms
ON: 10 s
OFF: 10 ms
ON: 10 s
OFF: Cleared
ON: Not cleared
This area is stored
even when the
operation mode is
changed from
PROGRAM to RUN,
or when the power is
turned off (without
being affected by the
MEMSW instruction).
This area is not
cleared even if the
utility relay All Clear
function is activated.
However, this area is
cleared when an All
Clear is executed
without registering a
program.
2715
2800
2801
2802
2803
2804
2805
2806
2807
2808
2809
2812
2813
Sets input time constant to all inputs in basic module (except inputs used by
HSP instruction).
OFF: Sets input time constant to 10 ms.
ON: Refers to value stored in DM1940, then determines input time constant.
2814
HKEY instruction: Multiple keys are prohibited.
2815
HKEY instruction: Scan is finished.
2900 to 2915 HKEY information storage area.
Note: Never use special utility relays that are not shown above.
Chapter 1 Programming
3-17
11
Timer/Counter list
Name
Timer
Counter
Contact
T000 to T249
Coil
(instruction)
TMR000 to 249
TMH000 to 249
TMS000 to 249
C000 to C249
Number
250 in total
C000 to 249
UDC000 to 249
Description
Timers
When 0.1-s timers (TMR) and high-speed 0.001-s timers (TMS) are used as
contacts, the "Tnnn" No. is used for both types. However, the form for setting is
different. "TMRnnn#ddddd" is used for 0.1-s timers, "TMHnnn#ddddd" is used for
high-speed 0.01-s timers, and "TMSnnn#ddddd" is used for high-speed 1-ms
timers (nnn = timer No, ddddd = timer set value).
When the PLC is stopped, all timers are reset and their current values become
equivalent to set values.
Counters
When counters (C) and up/down counters (UDC) are used as contacts, the
"Cnnn" No. is used for both types. However, the form for setting is different.
"Cnnn#ddddd" is used for counters, while "UDCnnn#ddddd" is used for up/down
counters.
In one program, different numbers must be assigned to each of the counters and
up/down counters.
Even when operation is stopped, each counter stores whatever value it has at
that time.
"TMR instruction" (p.3-67), "TMH instruction" (p.3-68), "TMS instruction" (p.3-69), "C instruction" (p.372), "UDC instruction" (p.3-76).
3-18
For details about high-speed counters and high-speed counter comparators, refer to "Chapter 4 Highspeed Counters" (p.3-203).
Chapter 1 Programming
Description
Not specified (can be used by user)
DM1000 to DM1099
DM1100 to DM1199
DM1200 to DM1299
DM1300 to DM1399
DM1400
DM1403
DM1404
DM1405
DM1401
DM1402
DM1406/DM1407
DM1408/DM1409
:
DM1468/DM1469
DM1470
DM1471 to DM1479
DM1480
DM1481
DM1482
DM1483
DM1484
DM1485
DM1486
DM1487 to DM1499
DM1565 to DM1569
DM1664 to DM1699
DM1670 to DM1675
DM1676
Chapter 1 Programming
3-19
11
DM1680 to DM1699
Description
Area for direct access mode for the KV-D20 operator interface
panel
KV-D20 Operator interface panel: Display device attributes
DM1764 to DM1799
DM1806 to DM1809
DM1826 to DM1899
DM1677 to DM1679
DM1900/DM1901*
DM1902/DM1903*
DM1904/DM1905*
DM1906/DM1907*
DM1908/DM1909*
DM1910/DM1911*
DM1912/DM1913
DM1914/DM1915
DM1916/DM1917
DM1918/DM1919
DM1920/DM1921
DM1922/DM1923
DM1924/DM1925
DM1926/DM1927
DM1928/DM1929*
DM1930/DM1931*
DM1932/DM1933*
DM1934/DM1935*
DM1936
DM1937
DM1938
DM1939
DM1940
DM1941 to DM1943
DM1944
DM1945 to DM1949
DM1950
DM1951 to DM1999
Read-only relay.
Note 1: 16-bit binary data is stored in each of the data memories as for internal
registers.
Note 2: The data stored in data memories is held even when the power is turned off
or when the All Clear function is executed. The backup time is 20 days or more in
the KV-10xx, and 2 months or more in other models.
Note 3: DM1000 to DM1999 are assigned as special data memories.
3-20
Chapter 1 Programming
Usage
Attribute
TM00
R/W
TM01
R/W
Attribute
*
R: Read
R/W
R*
R/W
R*
R
W: Write
Both R and W are enabled when special functions are not used.
Note 1: Temporary data memories are initialized when the power is turned on.
Note 2: TM20, TM30, and TM31 are read-only, so cannot be used for writing.
However, TM28 can be used for both reading and writing if special functions are not
used.
Note 3: TM00 and TM01 are used by the MUL and DIV instructions. Never use them
for any other purpose.
Chapter 1 Programming
3-21
11
0 7 5 1 5
Channel No.
Unit Nos.
Unit nos. are assigned to units within the KV-300 system, with the unit connected to
the right of the KV-300 CPU (see the figure below) assigned as no. 7. The CPU is
assigned as unit no. 0.
CPU
0
16
17
Address Nos.
Address nos. are assigned to the input units, output units, and I/O terminal units.
The following table shows the assignment of address nos. to units.
Unit
KV-300 CPU
CPU
0, 5
KV-C16X
16-input unit
KV-C32X
32-input unit
0. 1
KV-B16R
16-output unit
KV-B16S
16-output unit
KV-C32T
32-output unit
5, 6
KV-R8X
0 to 4 *
KV-R16X
KV-R8R
KV-R16R
KV-R8T
KV-R16T
3-22
Address No.
5 to 9 *
The KV-R1A I/O Distribution Unit accommodates 5 input units and 5 output units.
Addresses are set with address switches.
Chapter 1 Programming
Setting the input time constant for basic units using special utility relays
The input time constant for a basic unit can be changed using data memory DM1940
and special utility relay 2813.
Though the input time constant is usually 10 ms, it can be changed to a value that
corresponds to the number stored in DM1940 by setting special utility relay 2813 to
ON.
If the HSP instruction and special utility relay 2813 are used at the same time,
priority is given to the HSP instruction and the number stored in DM1940 is ignored.
Special utility relay 2813
OFF: Sets the input time constant to 10 ms.
ON: Refers to the number stored in DM1940, then determines the input time
constant.
Number stored in DM1940
0
1
2
3
4
5
6
7 or more
Note 1: Be sure to set the input time constant to 10 s when using the 30-kHz high-speed
counter input.
Note 2: Never enter a number that is 7 or larger to data memory DM1940.
Note 3: The input time constant specified by data memory DM1940 becomes effective at the
rising edge of special utility relay 2813.
To change the input time constant, first change data memory DM1940, then set special utility
relay to OFF and ON again. Or change the operation mode of the KV basic unit from
PROGRAM to RUN.
Note 4: The input time constant for input relays set by the HSP instruction is 10 s.
For more about the HSP instruction, refer to "HSP instruction" (p.3-86).
For more about setting the input time constant for expansion units, refer to "Input time
constant for expansion units" (p.1-76).
Note 5: Set the special utility relay using the SET/RES instructions.
Note 6: When the input time constant is set to 1 ms or less, connect the output equipment
without contacts. If connecting output equipment with contacts, contact bounds may enter.
Note 7: Except for interrupts and high-speed counters, signals whose ON time is shorter than
the scan time may not be received even if the input time constant is set to a small value.
Chapter 1 Programming
3-23
11
24V
1 ms
0 ms 10 ms
5V 0 ms 10 ms
1 ms
As shown in above figures, an external switch can be used to select the input time
constant only on the KV-C32X/C16X Connector Input Units and KV-R16X/R8X I/O
Terminal Units.
KV-C32X/C16X
KV-R16X/R8X
0ms 1ms 10ms
25 s 20%
1 ms 20%
10 ms 20%
Note: Connect a solid-state contact output device when the input time constant is
set to 1 ms for 25 s. Connection of a contact output device may result in contact
bounce.
Setting
10 s 20%
25 s 20%
10 ms 20%
Default
Note 1: When using the 30 kHz high-speed counter input, turn ON special utility
relay 2813.
Note 2: When special utility relay 2813 is ON, the input time constant of input relays
0000 to 0009 is set to 10 s 20%.
Note 3: The input time constant remains 10 ms 20% if the HSP instruction is used
when special utility relay 2813 is ON.
Note 4: When the input time constant is set to 10 s or 25 s, a solid-state output
device must be connected. Connection of a contact output device may result in
contact bounce.
3-24
Chapter 1 Programming
2008
#00020
LDA
TM29
STA
11
2303
SET
Note 1: Be sure to set the constant scan time value so it is larger than the actual
scan time.
Note 2: If the actual scan time exceeds the set scan time, special utility relay 2304
turns ON (during the next 1 scan) while the actual scan time is written to TM28 (unit:
1 ms).
Note 3: The scan time can be set up to 200 ms in temporary data memory TM29. If
a value larger than 200 ms is input, it will be treated as 200 ms.
Chapter 1 Programming
3-25
2300
For more about operating procedures, refer to the "Chapter 6. Handheld Programmer" (p.1-195).
2301
For more about operating procedures, refer to the "Chapter 6. Handheld Programmer" (p.1-195).
Note: Once external input refresh is prohibited, it can be permitted only by setting
special utility relay 2301 to OFF from the Access Window, the "KV IncrediWare
(DOS)" or "LADDER BUILDER for KV" programming support software, or the KVP3E(01) handheld programmer.
3-26
Chapter 1 Programming
This function transfers contact comments to the Visual KV Series using the "KV
IncrediWare (DOS)" or "LADDER BUILDER for KV" programming support
software.
The Visual KV Series can store not only programs but also comments registered
to each contact using the "KV IncrediWare (DOS)" or "LADDER BUILDER for
KV" programming support software.
A program may not be easy to understand if only device Nos. are used. By
registering comments to the contacts, the program can be easily debugged and
more efficiently maintained.
The number of contact comments that can be transferred is up to 1,000 for both
normal transfer and compression transfer.
The KV-D20 operator interface panel includes the contact comment display
function.
For more about operating procedures, refer to "2.5 Entering Comments/Labels" (p.1-46) and "4.2.2
Setting the comment transfer" (p.2-138).
Chapter 1 Programming
3-27
11
Example
Set the constant scan time to 20 ms.
02008
#00200
LDA
TM29
STA
2303
SET
Note 1: The set value for the constant scan time must be greater than the actual
scan time. Otherwise, special utility relay 2304 turns on during every scan to disable
constant scan time mode.
Note 2: If the scan time exceeds the set value, special utility relay no. 2304 turns on
during the next scan.
Example
Use the output disabled function by executing FORCED RESET/RESET to special
utility relay No. 2300 from the monitor display.
Example
Set input relay No. 0000 to ON to disable input refresh; set to OFF to enable input
refresh.
0000
2301
Note: If input refresh is disabled, it is not enabled until input relay No. 0000 is turned
on from the handheld programmer.
3-28
Chapter 1 Programming
Only output
circuits can
be written.
Only input
circuits can
be
assembled.
Both input
circuits and
output circuits
can be
assembled.
Only output
circuits can
be
assembled.
Chapter 1 Programming
3-29
11
Example
When DM0000 stores 1000, 0500 turns ON.
2000, 0501 turns ON.
3000, 0502 turns ON.
Conventional ladder diagram
2010
0500
#01000
CMP
#02000
CMP
2010
0501
2010
0500
#03000
CMP
2010
0502
2002
#02000
CMP
2010
0501
2002
#03000
CMP
2010
0502
DM0000
LDA
2002
2002
Example
When the start switch is set to ON, a lamp is lit for three seconds, a buzzer is
sounded for two seconds, and then the motor starts to rotate.
0000
1100
DIFU
1100
1000
STG
0500
#00030
T000
T000
1001
JMP
1001
STG
0501
#00020
T001
T001
1002
JMP
1002
STG
0502
0000
1000
SET
ENDS
T000
1001
T001
T001
T002
1001
#00020
T001
#00030
T002
1001
0500
1003
3-30
Chapter 1 Programming
1001
STG
1003
1003
When the start switch (0000) is set to OFF, the motor is stopped
and all operations are reset.
#00010
T000
1003
1002
0000
1002
1002
When timer 0 turns ON three seconds later, the lamp goes out, a
buzzer (0501) is sounded, and timer 1 is activated.
1000
DIFU
T002
T000
When the start switch (0000) is set to ON, a lamp (0500) is lit and
timer 0 is activated.
0501
1000
DIFU
1000
1001
SET
0500
#00010
T000
T000
1002
JMP
1002
STG
0501
#00020
T001
T001
1003
JMP
1003
STG
0500
#00030
T002
T002
1001
JMP
0501
0500
0000
0500
0501
0501
LD 0000
OUT 0500
OUT 0501
LD 0000
OUT 0500
CON
OUT 0501
The CON instruction for connection is added.
(The scan time is not affected.)
0001
0002
1002
1003
DIFU
0000
1000
1000
1001
1000
1003
0001
1000
1000
0002
1001
0500
1001
1001
1001
0500
Because the program can be written in only one line when an extended adder
diagram is used, it is easier to look at and understand compared with a program
written using a conventional ladder diagram.
Chapter 1 Programming
3-31
11
3-32
Chapter 1 Programming
Chapter 2
Instructions
Describes the concrete usage of instructions in the KV Series.
Refer to "Chapter 3 Interrupts" on page 3-191 for details of interrupt instructions.
Refer to "Chapter 4 High-speed counters" on page 3-203 for details of the highspeed counters used in the application instruction.
2.1
2.1.1
2.1.2
2.1.3
2.1.4
2.1.5
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.3
2.4
2.4.1
2.4.2
2.4.3
2.5
Visual KV Series
Visual KV Series
Symbol
nnnn
LOAD
LOAD BAR
nnnn
AND
nnnn
Function
Exec.time
(s)
Bytes
Page
LD
0.7 to 1.6
3 (12)
3-57
LDB
0.7 to 1.6
3 (12)
3-57
0.7 to 0.9
3 (8)
3-58
0.7 to 0.9
3 (8)
3-58
AND
R No.
T/C No.
AND BAR
nnnn
OR
nnnn
OR
0.7 to 0.9
3 (8)
3-60
OR BAR
nnnn
ORB
0.7 to 0.9
3 (8)
3-60
0.8
1 (4)
3-61
0.8
1 (4)
3-63
1.5
3 (12)
3-65
1.5
3 (12)
3-65
1.9 to 12.8
3 (14)
3-66
0500 to 1915
2009
2100 to 17915
Forces R/T/C OFF when input 1.9 to 20.5
T000 to T249
is ON.
C000 to C249
CTH0 to CTH1
CTC0 to CTC3
3 (14)
3-66
ANB
AND LOAD
ANL
OR LOAD
ORL
OUT
nnnn
OUT
R No.
OUT BAR
SET
nnnn
nnnn
SET
OUB
0500 to 1915
2009
2300 to 17915 Forces relay ON and holds
T000 to T249 this status when input is ON.
C000 to C249
SET
R No.
T/C No.
nnnn
RES
RES
0.1-s
TIMER
#ddddd
Txxx
TMR
0.01-s
TIMER
#ddddd
T
Txxx
H
TMH
(FUN49)
RESET
3-34
T No.,
# preset
value
Chapter 2 Instructions
000 to 249
#00000 to
#65535
12.0 to 17.8
2 (6)
3-67
12.0 to 17.8
2 (6)
3-68
Exec.time
(s)
Bytes
Page
12.0 to 17.8
2 (7)
3-69
#00000 to
# preset value,
#65535
Sets 16-bit up-counter.
C No., counter 000 to 249
input R
0000 to 17915
12.0 to 17.8
4 (7)
3-72
13.0 to 24.0
2 (10)
3-76
3 (10)
3-78
3 (10)
3-78
3 (11)
3-80
(*)
5 (15)
3-82
3.8 to 9.4
3 (8)
3-86
MC
(FUN24)
0.2
1 (4)
3-89
MCR
MCR
(FUN25)
0.2
1 (0)
3-89
MEMSW
$xxxx
MEMSW
(FUN26)
3 (0)
3-92
Performs no operation.
1 (0)
3-94
END
1 (1)
3-94
ENDH
1 (0)
3-94
Instruction
Symbol
Mnemonic
1-ms
TIMER
#ddddd
T
S Txxx
TMS
(FUN51)
COUNTER
#ddddd
Cxxx
nnnn
UP-DOWN
COUNTER
UP
DW #ddddd
RES
DIFFERENTIATE UP
nnnn
DIFU
DIFFERENTIATE
DOWN
nnnn
DIFD
KEEP
UDC xxx
UDC
(FUN52)
DIFD
(FUN09)
KEEP
KEEP
(FUN22)
SET nnnn
RES
SFT
(FUN39)
D
nnnn
CLK
RES mmmm
HSP
nnnn
MASTER
CONTROL
MC
MEMORY
SWITCH
HSP
(FUN18)
END HI
R No.
nnnn: 1st R
No. mmmm:
Last R No.
R No.
$ constant
NOP
(FUN30)
NOP
END
C No.,
# preset value
R No.
HIGH
SPEED
MASTER
CONTROL
RESET
Operand
DIFU
(FUN10)
SFT
SHIFT
Visual KV Series
END
ENDH
Operand value
000 to 249
#00000 to
#65535
1000 to 1915
3000 to 9915
0500 to 1915
2009
2100 to 17915
Function
1000 to 1915
Sets shift register.
3000 to 9915
(KV-10)
0000 to 0005
(KV-16)
0000 to 0009
(KV-24)
0000 to 0015
(KV-40)
0000 to 0107
$ 0000 to
$ FFFF
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
*1 34 + 0.25 + n x 0.25 (n: No. of shift steps)
All operand values are shown in normal notation. The corresponding relay numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F
Chapter 2 Instructions
3-35
12
Visual KV Series
Symbol
Mnemonic
WAIT ON
nnnn
ON
mmmm
W-ON
WAIT OFF
nnnn
OFF
mmmm
W-OFF
17915
T000 to T249
nnnn:
R, T, C C000 to C249
CTC0 to CTC3
Nos.
mmmm:
mmmm: 1000 to 1915
3000 to 9915
R No.
1000 to 1915
R No.
WAIT UP
EDGE
WAIT
DOWN
EDGE
W-UE
nnnn
mmmm
CON
(FUN 06)
PUSH
MPS
READ
MRD
POP
MPP
nnnn
STG
nnnn
JMP
JMP
(FUN 21)
END
STAGE
ENDS
ENDS
(FUN 14)
STEP
STEP END
STP
nnnn
STP
(FUN 45)
STE
STE
(FUN 43)
Page
5 (12)
3-96
5 (12)
3-96
5 (12)
3-98
1 (0)
3-98
1 (4)
3-102
3.2
1 (4)
3-103
6.8
1 (4)
3-103
10.5 to 13.0
3 (10)
3-103
3 (8)
3-106
1 (4)
3-106
2.5
3 (10)
3-106
5 (12)
1 (0)
3-114
Turns ON
3-114
R, T, C
Nos.
3000 to 9915
0000 to 0009 When input is ON, turns R of
current stage OFF and moves 4.3 to 7.5
to stage specified by operand.
Turns current stage OFF and
next stage ON when input is
ON.
R No.
nnnn:
0000 to
0500 to 9915
Executes program between
T000 to T249 STP & STE when R (operC000 to C249 and) is ON.
CTC0 to CTC3
11.2 to 13.4
Is used with STEP to make
program step.
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
All operand values are shown in normal notation. The corresponding relay
numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
3-36
Bytes
STG
(FUN 44)
JUMP
Exec.time
(s)
W-DE
CONNECT
STAGE
nnnn
mmmm
Function
Chapter 2 Instructions
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F
Instruction
INTERVAL
TIMER
16-BIT
COUNTER
16-BIT
COUNTER
COMPARATOR
16-BIT
COUNTER
Symbol
ITVL
PLS
DMnnnn
PAUSE
mmmm
RES
CTH0
nnnn
#ddddd
CTCn
CTH1
nnnn
16-BIT
COUNTER
COMPARATOR
#ddddd
CTCn
SUBROUTINE
CALL
nn
CALL
Mnemonic
CTH
Count input
R
CTC
n:
Comparator
n: 0,1
No.
ddddd: #00001
ddddd:
to #65535
# preset
value
5 (10)
3-117
0004
2100
2101
2102
14.4
4 (6)
3-204
Hardware-based comparator
between preset & current
values of high-speed counter
2.3 to 3.5
(CTH0). This comparator is
turned ON when these
values are equal.
2 (6)
3-204
0005
0500
2200
2201
2202
14.4
4 (6)
3-204
CTC
Hardware-based comparator
between preset & current
values of high-speed counter
(CTH1). This comparator is
turned ON when these
values are equal.
2.3 to 3.5
2 (6)
3-204
CALL
(FUN 03)
Subroutine
No.
00 to 99
Executes subroutine
specified by operand.
5.4 to 6.5
2 (8)
3-122
Subroutine
No.
00 to 99
Represents beginning of
subroutine specified by
operand.
2 (4)
3-122
4.3
1 (4)
3-122
12.0 to
18.0
3 (20)
3-125
0.5
1 (4)
3-125
22.1 to
180.0
5 (10)
3-131
RET
(FUN 33)
REPEAT
START
FOR
nnnn
FOR
(FUN 16)
Represents end of
subroutine.
# constant,
DM No.
TMxx
#00000 to
#65535
DM0000 to
DM1999
TM00 to TM29
HKEY
(FUN 17)
Executes program
between FOR & NEXT
for number of times
specified by operand.
Represents end of
repetition.
NEXT
(FUN 29)
20.0 to 80.0
n:
Comparator
n: 2,3
No.
ddddd: #00001
ddddd:
to #65535
# preset
value
RET
Page
Count input
R
SUBROUTINE
RETURN
HKEY
nnnn
mmmm
Bytes
CTH
SBN
(FUN 38)
16-KEY INPUT
Exec.time
(s)
Function
DMnnnn:
DM0000 to Measures pulse-to-pulse
DM1985
interval & pulse width in
mmmm:
specified mode.
1000 to 1912
3000 to 9912
ITVL
SBN
nn
NEXT
Operand value
DMnnnn:
DM No.
mmmm: R
No.
SUBROUTINE
ENTRY
REPEAT END
Operand
Visual KV Series
nnnn:
Input R
mmmm:
Output R
nnnn:
0000 to 415
mmmm:
0500 to 915
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
All operand values are shown in normal notation. The corresponding relay
numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F
Chapter 2 Instructions
3-37
12
Visual KV Series
DATA
MEMORY
WRITE
TRIMMER
SETTING
Symbol
Mnemonic
nnnn
DW
DMmmmm
DW
n
TMIN
TMIN
(FUN 50)
Operand value
nnnn:
#/$ constant
DMmmmm:
DM No.
nnnn:
#0000 to
#65535
$0000 to
$FFFF
DMmmmm:
DM0000 to
DM1999
0 to 1
Trimmer No.
n
TMIN
nnnn
LDA
LOAD A
nnnn
LDA
@TMIN
@(FUN 50)
0000 to 17915
T000 to T249
C000 to C249
LDA
CTH0 to CTH1
(FUN 23)
R No.,
DM0000 to
C/T No.,
DM1999
DM No,
TM00 to TM31
TM xx,
#00000 to
#/$ constant,
#65535
@LDA
#TMxx
$0000 to $FFFF
@(FUN 23)
#TM00 to
#TM29
2
STA
(FUN 42)
nnnn
STA
STORE A
nnnn
STA
@STA
@(FUN 42)
nnnn
CMP
CMP
(FUN 04)
nnnn
CMP
@CMP
@(FUN 04)
nnnn
ADD
ADD
(FUN00)
R No.,
C/T No.,
DM No.,
TM xx,
#TMxx
0500 to 1915
2100 to 17915
T000 to T249
C000 to C249
CTH0 to
CTC3
DM0000 to
DM1999
TM00 to TM29
#TM00 to
#TM29
COMPARE
ADD
nnnn
ADD
nnnn
SUB
SUBTRACT
nnnn
SUB
DM0000 to
DM1999
TM00 to TM31
@ADD
#00000 to
@(FUN 00) DM/TM No.
#65535
TMxx,
$0000 to
#/$ constant,
$FFFF
SUB
#TMxx
#TM00 to
(FUN 46)
#TM29
@SUB
@(FUN 46)
nnnn
MUL
MUL
(FUN 28)
nnnn
MUL
@MUL
@(FUN28)
MULTIPLY
3-38
Function
Operand
Transfers content of
internal register to
location specified by
operand, or changes
preset value when T/C is
specified as operand.
Compares content of
internal register and
value specified by
operand.
Exec.time
(s)
Bytes
Page
8.0
5 (8)
3-136
8.9
1 (6)
3-138
20.9
1 (16)
6.4 to 14.0
3 (8)
3-140
18.4 to 26.0
3 (18)
6.6 to 28.5
3 (8)
3-140
18.0 to 40.5
3 (18)
10.8 to 35.6
3 (6)
3-146
22.8 to 47.6
3 (16)
3 (6)
3-150
3 (16)
3 (6)
3-150
3 (16)
3 (6)
3-150
3 (16)
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
Chapter 2 Instructions
Instruction
Symbol
nnnn
DIV
DIVIDE
nnnn
DIV
nnnn
ANDA
AND A
nnnn
ANDA
nnnn
ORA
OR A
nnnn
ORA
nnnn
EORA
EXCLUSIVE
OR A
nnnn
EORA
SHIFT
RIGHT A
SHIFT LEFT
A
Mnemonic
Operand
DM0000 to
DM1999
TM00 to TM31
R No.,
#00000 to
DM No.,
#65535
TM xx,
$0000 to
#/$ constant,
@DIV
$FFFF
#TMxx
@(FUN 11)
#TM00 to
#TM29
DIV
(FUN 11)
ANDA
(FUN 01)
0000 to 17915
DM0000 to
DM1999
@ANDA
R No.,
TM00 to TM31
@(FUN 01) DM No.,
#00000 to
TM xx,
#65535
#/$
constant,
ORA
$0000 to
#TMxx
(FNC 31)
$FFFF
#TM00 to
@ORA
#TM29
@(FUN 31)
0000 to 17915
DM0000 to
DM1999
R No.,
TM00 to TM31
DM No.,
#00000 to
TM xx,
#65535
#/$ constant,
$0000 to
#TMxx
@EORA
$FFFF
@(FUN 15)
#TM00 to
#TM29
EORA
(FUN 15)
#dd
SRA
SRA
(FNC 41)
#dd
SRA
@SRA
@(FUN 41)
#dd
SLA
SLA
(FNC 40)
#dd
SLA
@SLA
@(FUN 40)
#dd
RRA
RRA
(FUN 37)
#dd
RRA
@RRA
@(FUN 37)
#dd
RLA
RLA
(FUN 35)
ROTATE
LEFT A
#dd
RLA
@RLA
@(FUN 35)
Exec.time
(s)
Function
17.4 to 43.3
Divides content of internal
register by value specified
by operand and inputs
result back to same
29.4 to 55.3
register.
EXCLUSIVE-ORs each of
16 bits of internal register
and that of value specified
by operand, and inputs
result back to same
register.
ROTATE
RIGHT A
Operand value
Visual KV Series
8.2 to 33.1
Bytes
Page
3 (6)
3-150
3 (16)
3 (8)
3-159
3 (18)
3 (8)
3-161
3 (18)
3 (8)
3-164
20.2 to 45.1
3 (18)
9.3 to 27.6
2 (6)
12
3-166
21.3 to 39.6
2 (16)
9.2 to 27.6
2 (6)
3-166
21.2 to 39.6
2 (16)
#01 to #16
10.3 to 28.6
Rotates contents of
internal register and carry
bit (2009) clockwise by
operand value.
22.3 to 40.6
10.3 to 28.6
Rotates contents of
internal register and carry
bit (2009) counterclock22.3 to 40.6
wise by operand value.
2 (6)
3-169
2 (16)
2 (6)
3-169
2 (16)
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
All operand values are shown in normal notation. The corresponding relay numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F
Chapter 2 Instructions
3-39
Instruction
Visual KV Series
Symbol
Mnemonic
COM
COM
(FUN 05)
COMPLEMENT
INCREMENT
MEMORY
DECREMENT
MEMORY
MULTIPLEXER
COM
@COM
@(FUN 05)
nnnn
INC
INC
(FNC 19)
nnnn
INC
@INC
@(FUN 19)
nnnn
DEC
DEC
(FNC 07)
nnnn
DEC
@DEC
@(FUN 07)
#n
MPX
MPX
(FUN 27)
#n
MPX
@MPX
@(FUN 27)
DMX
DMX
(FUN 12)
DMX
@DMX
@(FUN 12)
TBCD
TBCD
(FUN 47)
TBCD
@TBCD
@(FUN 47)
TBIN
TBIN
(FUN 48)
TBIN
@TBIN
@(FUN 48)
Operand
DM/TM No.
# constant
2
TRANSFER
BCD
TRANSFER
BIN
ASC
ASC
(FUN 02)
ASC
@ASC
@(FUN 02)
RASC
RASC
(FUN 32)
RASC
@RASC
@(FUN 32)
ROOT
ROOT
(FUN 36)
ROOT
@ROOT
@(FUN 36)
ASCII
CONVERT
REVERSE
ASCII
CONVERT
SQUARE
ROOT
Exec.time
(s)
Bytes
5.6
1 (4)
3-171
17.6
1 (14)
9.8
3 (6)
21.8
3 (16)
10.4
3 (6)
22.4
3 (16)
DM0000 to
DM1999
TM00 to
TM29
DM0000 to
DM1999
TM00 to
TM29
10.1
1 (6)
#0 to #3
22.1
1 (16)
Converts position of
highest order bit with 1 in
internal register into 4-bit
data.
22.6
1 (4)
34.6
1 (14)
Converts content of
internal register (16-bit
binary) into 4-digit BCD
data.
5.6
1 (4)
17.6
1 (14)
9.6
1 (4)
21.6
1 (14)
9.7
1 (4)
21.7
1 (14)
9.3
1 (4)
21.3
1 (14)
95.7
1 (4)
107.7
1 (14)
Converts content of
internal register (4-digit
BCD) into 16-bit binary
data.
Page
3-172
3-172
3-176
3-176
3-180
3-180
3-183
3-183
3-185
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
All operand values are shown in normal notation. The corresponding relay
numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
3-40
Function
DM/TM No.
DEMULTIPLEXER
Operand
value
Chapter 2 Instructions
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F (OUTPUT)
Visual KV Series
Symbol
Mnemonic
INTERRUPT
DISABLED
DI
DI
(FUN 08)
INTERRUPT
ENABLED
EI
EI
(FUN 13)
INT
nnnn
INT
CTCn
RETI
R No.
000 to 003
Comparator
No.
CTC0 to
CTC3
RETI
(FUN 34)
Exec.time
(s)
Bytes
Page
Disables execution of
interrupt.
2.2
1 (12)
3-193
Enables execution of
interrupt.
4.0
1 (10)
3-193
Executes interrupt
instructions between INT
and RETI at rising/falling
edge of input relays 0000
through 0003.
60.0 to
90.0
1 (8)
3-192
60.0 to
90.0
1 (8)
3-192
Represents end of
interrupt.
18.0 to
22.0
1 (4)
3-192
Function
Operand value
INT
(FUN 20)
INTERRUPT
RETURN
INTERRUPT
Operand
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
All operand values are shown in normal notation. The corresponding relay
numbers in X-Y-M notation are shown below:
Normal notation
0000 to 0415
0500 to 0915
1000 to 6915
7000 to 17915
X-Y-M notation
X000 to X04F
Y050 to Y09F
M1000 to M6915
X700 to X174F or Y750 to Y179F
00
ADD
13
EI
26
MEMSW
39
SFT
01
ANDA
14
ENDS
27
MPX
40
SLA
02
ASC
15
EORA
28
MUL
41
SRA
03
CALL
16
FOR
29
NEXT
42
STA
04
CMP
17
HKEY
30
NOP
43
STE
05
COM
18
HSP
31
ORA
44
STG
06
CON
19
INC
32
RASC
45
STP
07
DEC
20
INT
33
RET
46
SUB
08
DI
21
JMP
34
RET1
47
TBCD
09
DIFD
22
KEEP
35
RLA
48
TBIN
10
DIFU
23
LDA
36
ROOT
49
TMH
11
DIV
24
MC
37
RRA
50
TMIN
12
DMX
25
MCR
38
SBN
51
TMS
52
UDC
Chapter 2 Instructions
3-41
12
KV-300
KV-300 Series,
Series, KV-10/80
Number of bytes represents the memory capacity required for each instruction.
Number in ( ) represents the memory capacity required for object code of each
instruction.
Abbreviations: R: Relay, T: Timer, C: Counter, #: Decimal, $: Hex.
KV-10/16/24/40/80
Mnemonic Operand Operand value Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
nnnn
LOAD
LOAD BAR
nnnn
AND BAR
1.5 to 2.5
3 (4)
3-57
LDB
2.1 to 3.5
3 (6)
3-57
AND
1.5 to 2.5
R No.
T/C No.
ANB
0000 to 2915
T000 to T063
C000 to C063
CTC0 to CTC3
0000 to 6915
T000 to T119
C000 to C119
2.7 to 4.5
CTC0 to CTC3
OR
nnnn
OR
1.5 to 2.5
OR BAR
nnnn
ORB
2.7 to 4.5
AND LOAD
ANL
1.0 to 1.4
OR LOAD
ORL
1.0 to 1.4
nnnn
OUT
OUT
0500 to 1915
2009
2300 to 2915
nnnn
OUT BAR
OUB
nnnn
SET
(SET)
nnnn
RESET
(RES)
0.1-s TIMER
#ddddd
T xxx
SET
R No.
0500 to 1915
2009
2100 to 2915
T000 to T063
C000 to C063
CTH0 to CTH1
CTC0 to CTC3
RES
5.2 to 8.4
0500 to 1915
2009
2300 to 6915 6.4 to 10.4 3 (17) ON/OFF status to R
coil.
0500 to 1915
2009
2100 to 6915
T000 to T119 3.1 to 24.0 3 (8)
C000 to C119
CTH0 to CTH1
CTC0 to CTC3
TMR
000 to 063
#00000 to
#65535
#ddddd
H xxx
TMH
(FNC49)
1-ms TIMER
#ddddd
S xxx
TMS
(FNC51)
COUNTER
#ddddd
C xxx
nnnn
# preset
value, C
No., clock
source R
#00000 to
65535
000 to 063
0000 to 6915
UP-DOWN
COUNTER
UP #ddddd
DW
RES
UDC
(FNC52)
C No.,
# preset
value
000 to 063
#00000 to
#65535
3-42
000 to 119
#00000 to
#65535
Chapter 2 Instructions
3-58
3-58
3-60
3-60
3-61
3-63
3-65
3-65
0.01-s
TIMER
UDC xxx
Page
LD
nnnn
nnnn
AND
Function
#00000 to
#65535
19.0 to 21.0 4 (7)
000 to 119
0000 to 6915
000 to 119
#00000 to
#65535
3-66
3-67
3-68
3-69
3-72
3-76
Instruction
Symbol
DIFFERENTIATE UP
nnnn
DIFU
DIFFERENTIATE
DOWN
KEEP
KEEP
(FNC22)
R No.
0500 to 1915
2009
2100 to 2915
SFT
(FNC39)
R No.1st
& last R
Nos.
1000 to 1915
HSP
(FNC18)
R No.
(KV-10)
0000 to 0005
(KV-16)
0000 to 0009
D
nnnn
CLK
RES mmmm
HIGH
SPEED
HSP
MASTER
CONTROL
MC
nnnn
SFT
nnnn
MCR
MEMSW
$xxxx
$xxxx
NOP
END
END HI
1000 to 1915
DIFD
(FNC09)
SHIFT
MEMORY
SWITCH
DIFU
(FNC10)
nnnn
DIFD
SET
RES
MASTER
CONTROL
RESET
KV-10/16/24/40/80
Operand
value
Mnemonic Operand
Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
R No.
KEEP
END
ENDH
1000 to 1915
3000 to 6915
0500 to 1915
2009
2100 to 6915
1000 to
19153000 to
6915
(KV-24)
0000 to 0015
(KV-40)
0000 to 0107
Page
Turns ON R for 1
11.0 to 13.0 3 (5) scan time at rising
edge of input.
Turns ON R for 1
11.0 to 13.0 3 (5) scan time at falling
edge of input.
Turns ON R and
9.0 to 26.0 3 (5) holds this status when
SET input is ON.
5 (7) Turns OFF R when
RESET input is ON.
(*)
8.0 to 9.0
MC
(FNC24)
1.8 to 3.2
MCR
(FNC25)
0.6 to 1.0
MEMSW $ constant
(FNC26)
Function
3 (4)
3-78
3-78
3-80
3-82
3-86
3-89
3-89
3 (0)
NOP
(FNC30)
3-94
END
3-94
ENDH
3-94
$ 0000 to $ FFFF
3-92
KV-300
KV-300
Instruction
Symbol
Exec.time
Bytes
(s)
Function
Page
LD
3-57
LDB
3-57
Mnemonic Operand
Operand value
nnnn
LOAD
nnnn
LOAD BAR
nnnn
AND
AND BAR
AND
R No.
T/C No.
nnnn
ANB
0000 to 0009
0500 to 17915
T000 to T249
C000 to C249
CTC0 to CTC3
OR
nnnn
OR
OR BAR
nnnn
ORB
AND LOAD
ANL
0.55
1 (3)
OR LOAD
ORL
0.55
1 (3)
Chapter 2 Instructions
3-58
3-58
3-60
3-60
3-61
3-63
3-43
12
KV-300
KV-300 Series,
Series, KV-10/80
KV-300
Instruction
Symbol
Mnemonic Operand
Operand value
Exec.time
Bytes
(s)
0500 to 1915
2009
2300 to 17915
0.20 to 0.56
nnnn
OUT
OUT
nnnn
OUB
OUT BAR
nnnn
(SET)
SET
nnnn
RESET
(RES)
0.1-s TIMER
#ddddd
T xxx
SET
RES
#ddddd
H xxx
TMH
(FNC49)
1-ms TIMER
#ddddd
S xxx
TMS
(FNC51)
COUNTER
#ddddd
C xxx
nnnn
UP-DOWN
COUNTER
UP #ddddd
DW
RES
UDC xxx
# preset
value, C
No., clock
source R
C No.,
UDC
(FNC52) # preset
value
000 to 249
#00000 to 65535
#00000 to #65535
000 to 249
0000 to 0009
0500 to 17915
7.60 to 9.45
000 to 249
#00000 to #65535
DIFU
FNC10)
DIFFERENTIATE DOWN
nnnn
DIFD
DIFD
(FNC09)
KEEP
KEEP
(FNC22)
R No.
SFT
(FNC39)
1st &
last R
Nos.
0500 to 1915
2009
2100 to 17915
1000 to 1915
3000 to 6915
(*) 7000 to 9915
HSP
(FNC18)
R No.
0000 to 0009
R No.
SHIFT
D
nnnn
CLK
RES mmmm
nnnn
SFT
HSP
HIGH
SPEED
nnnn
T No.,
# preset
value
3-65
0500 to 1915
2009
2100 to 17915
T000 to T249
C000 to C249
CTH0 to CTH1
CTC0 to CTC3
nnnn
DIFU
SET
RES
3-65
DIFFERENTIATE UP
KEEP
Page
0500 to 1915
2009
2100 to 17915
T000 to T249
C000 to C249
TMR
0.01-s TIMER
R No.
3 (8)
Function
1000 to 1915
3000 to 6915
(*) 7000 to 9915
4 (7)
3-66
3-67
3-68
3-69
3-72
3-76
3-78
3-82
6.70
4.66 to 4.92
3-78
3-80
3-86
3-89
MASTER
CONTROL
MC
MC
(FNC24)
0.20
MASTER
CONTROL
RESET
MCR
MCR
(FNC25)
1 (0)
3-89
MEMORY
SWITCH
MEMSW
$xxxx
$xxxx
3 (0)
3-92
NOP
(FNC30)
1 (0)
Performs no operation.
3-94
END
0.95
1 (1)
3-94
ENDH
1 (0)
3-94
NOP
END
END HI
END
ENDH
MEMSW $ constant
(FNC26)
$0000 to $FFFF
Note: 14.0 + 3.0 x (n) to 17.0 + 3.0 x (n) (n represents number of times the original
data is generated.)
3-44
Chapter 2 Instructions
KV-10/16/24/40/80
Mnemonic Operand Operand value Operand value Exec.time
Bytes
(s)
KV-10/16
KV-24/40/80
nnnn
ON
mmmm
W-ON
WAIT OFF
nnnn
OFF
mmmm
W-OFF
WAIT UP
EDGE
nnnn
mmmm
W-UE
WAIT DOWN
EDGE
nnnn
mmmm
W-D
WAIT ON
nnnn:
0000 to 2915
T000 to T063
nnnn: C000 to C063
R,T, or C CTC0 to CTC3
No.
mmmm:
1000 to 1915
nnnn:
0000 to 6915
T000 to T119
C000 to C119
CTC0 to CTC3
mmmm:
1000 to 1915
3000 to 6915
11.0 to
13.0
11.0 to
13.0
14.0 to
18.0
14.0 to
18.0
CONNECT
CON
[FNC 06]
0.4 to
0.6
PUSH
MPS
11.0 to
14.0
READ
MRD
8.0 to
10.0
POP
MPP
10.0 to
12.0
nnnn
STG
STG
[FNC 44]
11.0 to
14.0
JUMP
nnnn
JMP
JMP
[FNC 21]
END
STAGE
ENDS
ENDS
[FNC 14]
STEP
STP
nnnn
STP
[FNC 45]
STAGE
R No.
STEP END
STE
ITVL
SUBROUTINE ENTRY
SUBROUTINE
RETURN
DM0000 to
DM1985
1000 to 1912
3000 to 6912
3-96
3-98
3-98
3-102
3-103
3.7 to
5.3
0.00
DM0000 to
DM0985
1000 to 1912
3-96
7.0 to
9.0
29.0 to
79.0
Clock
source Rs
0004
2100 to 2102
9.0 to
39.0
#ddddd
CTCn
CTC
n:
Comparator
No.
ddddd: #
preset value
n: 0,1
ddddd: #00000 to #00255
3.0 to 4.0
CTH1
nnnn
CTH
Clock
source Rs
0005
2200 to 2202
8.0 to
48.0
#ddddd
CTCn
CTC
n: Comparator No.
ddddd: #
preset value
n: 2,3
ddddd: #00000 to #65535
3.0 to 4.0
nn
CALL
CALL
[FNC 03]
Subroutine No.
00 to 99
8.0 to
10.0
SBN
nn
SBN
[FNC 38]
Subroutine No.
00 to 99
0.00
RET
RET
[FNC 33]
CTH0
nnnn
SUBROUTINE CALL
STE
[FNC 43]
CTH
8-BIT
COUNTER
16-BIT
COUNTER
COMPARATOR
0000 to 6915
T000 to T119
C000 to C119
CTC0 to CTC3
Page
10.0 to
13.0
DM & R
No.
PLS
nnnn
DM
PAUSE mmmm
RES
16-BIT
COUNTER
0000 to 2915
T000 to T063
C000 to C063
CTC0 to CTC3
1000 to 1915
3000 to 6915
ITVL
INTERVAL
TIMER
8-BIT
COUNTER
COMPARATOR
R, T, C
Nos.
1000 to 1915
Function
3-106
3-114
Measures pulse-to-pulse
5 (7) interval & pulse width in
specified mode.
3-117
3-277
3-277
3-204
3-204
3-122
Represents beginning of
2 (0) subroutine specified by
operand.
3-122
Chapter 2 Instructions
3-45
12
Instruction
Symbol
KV-300
KV-300 Series,
Series, KV-10/80
Mnemonic Operand
REPEAT
START
FOR
nnnn
FOR
[FNC 16]
REPEAT
END
NEXT
NEXT
[FNC 29]
HKEY
nnnn
mmmm
16-KEY
INPUT
HKEY
[FNC 17]
# constant,
DM No.
KV-10/16/24/40/80
Operand value Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
Function
Page
#00000 to
#00000 to
#65535
#65535
DM0000 to 5.0 to 20.0 3 (15)
DM0000 to
DM1999
DM0999
TM00 to TM29 TM00 to TM29
Executes program
between FOR & NEXT
for number of times
specified by operand.
3-125
1 (3)
Represents end of
repetition.
3-125
5 (7)
1.7 to 2.3
I/O R
nnnn:0000 to 0009
10000 to 10415
:
17000 to 17415
mmmm:10500 to 10915
:
17500 to 17915
71 to 370
KV-300
KV-300
Instruction
Symbol
Mnemonic Operand
WAIT ON
nnnn
ON
mmmm
W-ON
WAIT OFF
nnnn
OFF
mmmm
W-OFF
WAIT UP
EDGE
nnnn
mmmm
W-UE
WAIT DOWN
EDGE
nnnn
mmmm
W-DE
nnnn:
R,T, or
C No.
Operand value
nnnn:
0000 to 0009
0500 to 17915
T000 to T249
C000 to C249
CTC0 to CTC3
mmmm:
1000 to 1915
3000 to 6915
(*)7000 to 9915
Exec.time
Bytes
(s)
Function
CONNECT
CON
[FNC 06]
PUSH
MPS
1.30
1 (9)
READ
MRD
2.70
POP
MPP
nnnn
STG
STAGE
STG
[FNC 44]
R No.
JUMP
nnnn
JMP
JMP
[FNC 21]
END
STAGE
ENDS
ENDS
[FNC 14]
STEP
STEP END
INTERVAL
TIMER
16-BIT
COUNTER
3-46
STP
nnnn
STP
[FNC 45]
STE
STE
[FNC 43]
ITVL
PLS
nnnn
DM
PAUSE mmmm
RES
CTH0
nnnn
R, T,
C Nos.
1000 to 1915
3000 to 6915
(*)7000 to 9915
0000 to 0009
0500 to 6915
(*)7000 to 9915
T000 to T249
C000 to C249
CTC0 to CTC3
ITVL
DM & R No.
DMnnnn:
DM0000 to DM9985
mmmm:
1000 to 1912
3000 to 6912
(*)7000 to 9912
CTH
Clock
source Rs
0004
2100
2101
2102
Chapter 2 Instructions
Page
3-96
3-96
3-98
3-98
3-102
3-103
3-103
1 (9)
1 (0)
3-106
1.30
3 (9)
3-114
1 (0)
3-114
13.80 to
17.30
3.85
Measures pulse-to-pulse
5 (11) interval & pulse width in
specified mode.
4 (7)
3-117
KV-300
Instruction Symbol
Mnemonic Operand
Operand value
Exec.time
Bytes
(s)
CTC
n:
Comparator
No.
ddddd: #
preset value
n: 0, 1
ddddd:
#00000 to #65535
CTH
Clock
source Rs
0005
2200
2201
2202
CTC
n:
Comparator
No.
ddddd: #
preset value
n: 2, 3
ddddd:
#00000 to #65535
CALL
Subroutine
[FNC 03]
No.
00 to 99
3.16
SBN
nn
SBN
[FNC 38]
00 to 99
RET
RET
[FNC 33]
REPEAT
START
FOR
nnnn
FOR
[FNC 16]
REPEAT
END
NEXT
NEXT
[FNC 29]
16-BIT
COUNTER
COMPARATOR
#ddddd
CTCn
16-BIT
COUNTER
CTH1
nnnn
16-BIT
COUNTER
COMPARATOR
#ddddd
CTCn
SUBROUTINE CALL
nn
CALL
SUBROUTINE ENTRY
SUBROUTINE
RETURN
16-KEY
INPUT
HKEY
nnnn
mmmm
HKEY
[FNC 17]
Subroutine
No.
#00000 to #65535
DM0000 to DM9999
TM00 to TM29
3.85
1.55
I/O R
nnnn:0000 to 0009
10000 to 10415
:
17000 to 17415
mmmm:0500 to 0503
10500 to 10915
:
17500 to 17915
16.50
Page
Hardware-based comparator
between preset & current
2 (0) values of high speed counter. 3-204
This comparator is turned ON
when these values are equal.
3-204
Hardware-based comparator
between preset & current
2 (0) values of high speed counter. 3-204
This comparator is turned ON
when these values are equal.
1.15 to 1.45
# constant,
DM No.
Function
3-122
Represents beginning of
2 (0) subroutine specified by
operand.
3-122
Represents end of
subroutine.
3-122
3-125
1 (6)
Chapter 2 Instructions
3-131
3-47
12
KV-300
KV-300 Series,
Series, KV-10/80
DATA
MEMORY
WRITE
Symbol
nnnn
< DW >
DMmmmm
TRIMMER
SETTING
KV-10/16/24/40/80
Mnemonic Operand Operand value Operand value Exec.time
Function
Bytes
KV-10/16
(s)
KV-24/40/80
#00000 to
#0000 to
#65535
#65535
#/$
$0000 to
$0000 to
3.6 to 6.0 5 (6) Writes constant into
constant,
DW
data memory.
$FFFF
$FFFF
DM No.
DM0000 to
DM0000 to
DM0999
DM1999
TMIN
[FNC 50]
@TMIN
TMIN > @[FNC 50]
Trimmer
No.
0 to 1
nnnn
LOAD A
nnnn
LDA >
nnnn
STORE A
nnnn
STA >
nnnn
COMPARE
nnnn
CMP >
nnnn
ADD
nnnn
ADD >
nnnn
0000 to 2915
T000 to T063
C000 to C063
LDA
R No., CTH0 to CTH1
[FNC 23]
C/T No.,
DM0000 to
DM/TM
DM0999
No.,
TM00 to TM31
#/$
#00000 to
constant,
#65535
@LDA
$0000 to
#TMxx
@[FNC 23]
$FFFF
#TM00 to
#TM29
R No.,
C/T No.,
DM/TM
No.,
#/$
@STA
constant,
@[FNC 42] #TMxx
STA
[FNC 42]
CMP
[FNC 04]
nnnn
SUB >
nnnn
MULTIPLY
nnnn
MUL >
nnnn
SUB
[FNC 46]
@SUB
@[FNC 46]
DIV >
@DIV
@[FNC 11]
Chapter 2 Instructions
3-136
3-138
3-140
Transfers content of
internal register to
location specified by
operand, or changes
preset value when T/
C is specified as
operand.
3-140
3-146
Adds content of
13.0 to 65.0 3 (5) internal register and
value specified by
operand and inputs
25.0 to 79.0 3 (12) result back to same
register.
Subtracts value
15.0 to 68.0 3 (5) specified by operand
from content of
register and inputs
27.0 to 82.0 3 (12) result back to same
register.
DM0000 to
DM0000 to
DM0999
DM1999
TM00 to TM31 TM00 to TM31
MUL
#00000 to
#00000 to 17.0 to 71.0 3 (5)
[FNC 28] DM/TM
#65535
#65535
No.,
$0000 to
$0000 to
#/$
No.,
@MUL
$FFFF
$FFFF
29.0 to 85.0 3 (12)
@[FNC 28] #TMxx
#TM00 to
#TM00 to
#TM29
#TM29
DIV
22.0 to 79.0 3 (5)
[FNC 11]
DIVIDE
nnnn
0500 to 1915
2100 to 2915
T000 to T063
C000 to C063
DM0000 to
DM0999
TM00 to TM29
#TM00 to
#TM29
0000 to 6915
T000 to T119
C000 to C119 10.0 to 46.0 3 (5)
CTH0 to CTH1
DM0000 to
DM1999
TM00 to TM31
#00000 to
#65535
22.0 to 60.0 3 (12)
$0000 to
$FFFF
#TM00 to
#TM29
0500 to 1915
2100 to 6915
T000 to T119 9.0 to 99.0 3 (5)
C000 to C119
DM0000 to
DM1999
TM00 to TM29 21.0 to 113.0 3 (12)
#TM00 to
#TM29
DM0000 to
DM0000 to
DM1999
DM0999
DM/TM TM00 to TM31 TM00 to TM31
@CMP
#00000 to
#00000 to
No.,
@[FNC 04]
#65535
#65535
#/$
$0000 to
$0000 to
constant,
ADD
$FFFF
$FFFF
#TMxx
[FNC 00]
#TM00 to
#TM00 to
#TM29
#TM29
@ADD
@[FNC 00]
SUBTRACT
3-48
Page
Multiplies content of
internal register by
value specified by
operand and inputs
result back to same
register.
Divides content of
internal register by
value specified by
operand and inputs
34.0 to 93.0 3 (12) result back to same
register.
3-150
3-150
3-150
3-150
Instruction
Symbol
nnnn
<ANDA>
AND A
nnnn
ANDA>
nnnn
OR A
nnnn
ORA >
EXCLUSIVE
OR A
SHIFT
RIGHT A
#dd
SRA
[FNC 41]
#dd
@SRA
@[FNC 41]
#dd
SLA
[FNC 40]
#dd
RLA
[FNC 35]
Moves content of
internal register serially
right, allowing each bit
3-169
that leaves right end to
24.0 to 44.0 2 (11) enter carry bit and then
leftmost bit.
Moves content of
12.0 to 29.0 2 (4) internal register serially
left, allowing each bit 3-169
that leaves left end to
24.0 to 43.0 2 (11) enter carry bit and then
rightmost bit.
12.0 to 30.0 2 (4)
COM
[FNC 05]
COM >
@COM
@[FNC 05]
INC
[FNC 19]
nnnn
INC >
nnnn
DEC >
#n
MULTIPLEXER
#01 to #16
@RLA
@[FNC 35]
COMPLEMENT
5.0 to 6.0
DM/TM No.
MPX >
3-171
DM0000 to
DM0000 to
DM0999
DM1999TM00
TM00 to TM29
to TM29
14.0 to 17.0 3 (5)
@DEC
@[FNC 07]
MPX
[FNC 27]
@MPX
@[FNC 27]
Inverts content of
each bit in internal
register.
Subtracts 1 from
content of data
memory specified by
26.0 to 31.0 3 (12) operand.
3-172
#n
1 (3)
Adds 1 to content of
data memory
3-172
24.0 to 29.0 3 (12) specified by operand.
@INC
@[FNC 19]
DEC
[FNC 07]
12
Moves content of
internal register
3-166
serially left by value
22.0 to 42.0 2 (11) specified by operand.
RLA >
#dd
3-166
RRA
[FNC 37]
@RRA
@[FNC 37]
DECREMENT
MEMORY
Moves content of
internal register
serially right by
value specified by
23.0 to 42.0 2 (11) operand.
@SLA
@[FNC 40]
#dd
RRA >
INCREMENT
MEMORY
Page
# constant
#dd
ROTATE
LEFT A
Function
SLA >
ROTATE
RIGHT A
KV-10/16/24/40/80
Operand value Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
ANDA
[FNC 01]
nnnn
SRA >
SHIFT
LEFT A
Mnemonic Operand
#0 to #3
Chapter 2 Instructions
3-176
3-49
Instruction
Symbol
DMX
[FNC 12]
DMX >
@DMX
@[FNC 12]
<TBCD>
TBCD
[FNC 47]
TBCD>
@TBCD
@[FNC 47]
TBIN
[FNC 48]
TBIN>
@TBIN
@[FNC 48]
ASC
[FNC 02]
ASC >
@ASC
@[FNC 02]
<RASC>
RASC
[FNC 32]
TRANSFER
BIN
ASCII
CONVERT
REVERSE
ASCII
CONVERT
Function
Page
Converts position of
highest order bit with
1 in internal register
40.0 to 44.0 1 (10) into 4-bit data.
3-176
Converts content of
internal register (16bit binary) into 4-digit
31.0 to 35.0 1 (10) BCD data.
3-180
Converts content of
internal register (4digit BCD) into 16-bit
30.0 to 34.0 1 (10) binary data.
8.0
12.0 to 14.0
ROOT
[FNC 36]
3-183
1 (3)
3-183
3-185
102.0 to
103.0
@ROOT
ROOT>
@[FNC 36]
3-180
1 (3)
Converts content of
lower order byte of
internal register into
20.0 to 22.0 1 (10) 2-digit ASCII code.
@RASC
RASC>
@[FNC 32]
<ROOT>
SQUARE
ROOT
KV-10/16/24/40/80
Operand
value
Mnemonic Operand
Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
DEMULTIPLEXER
TRANSFER
BCD
KV-300
KV-300 Series,
Series, KV-10/80
114.0 to
117.0
1 (3)
KV-300
KV-300
Instruction
Symbol
DATA
MEMORY
WRITE
nnnn
< DW >
DMmmmm
TRIMMER
SETTING
DW
@TMIN
TMIN > @[FNC 50]
LOAD A
nnnn
LDA >
nnnn
STORE A
nnnn
STA >
#/$
constant,
DM No.
Operand value
nnnn:
#0000 to #65535
$0000 to $FFFF
DMmmmm:
DM0000 to DM9999
TMIN
[FNC 50]
nnnn
3-50
Mnemonic Operand
Trimmer
No.
LDA
[FNC 23]
R No.,
C/T No.,
DM/TM
No.,
#/$
@LDA
@[FNC 23] constant,
#TMxx
STA
[FNC 42]
R No.,
C/T No.,
DM/TM
No.,
#/$
@STA
constant,
@[FNC 42]
#TMxx
Chapter 2 Instructions
0, 1
Exec.time
Bytes
(s)
0500 to 1915
2100 to 17915
T000 to T249
C000 to C249
CTC0 to CTC3
DM0000 to DM9999
TM00 to TM29
#TM00 to #TM29
Page
0.60 to
1.40
3-136
5.10 to
5.60
3-138
2.00 to
5.70
0000 to 0009
0500 to 17915
T000 to T249
C000 to C249
CTH0 to CTH1
DM0000 to DM9999
TM00 to TM31
#00000 to #65535
$0000 to $FFFF
#TM00 to #TM29
Function
0.30 to
28.00
3 (12)
2.30 to
30.00
3 (26)
0.20 to
30.00
2.20 to
32.00
KV-300
Instruction
Symbol
nnnn
Mnemonic Operand
Operand value
Exec.time
Bytes
(s)
9.20 to
36.00
CMP
[FNC 04]
COMPARE
nnnn
CMP >
nnnn
@CMP
@[FNC 04]
ADD
[FNC 00]
ADD
DM/TM
No.,
#/$
constant,
#TMxx
DM0000 to DM9999
TM00 to TM31
#00000 to #65535
$0000 to $FFFF
#TM00 to #TM29
11.20 to
38.00
7.70 to
35.00
9.70 to
37.00
nnnn
SUB
[FNC 46]
8.40 to
35.00
nnnn
@SUB
@[FNC 46]
10.40 to
37.00
nnnn
MUL
[FNC 28]
SUBTRACT
SUB >
MULTIPLY
DM/TM
No.,
#/$ No.,
#TMxx
DM0000 to DM9999
TM00 to TM31
#00000 to #65535
$0000 to $FFFF
#TM00 to #TM29
9.80 to
37.00
nnnn
@MUL
@[FNC 28]
nnnn
DIV
[FNC 11]
13.70 to
41.00
nnnn
@DIV
@[FNC 11]
15.70 to
42.00
nnnn
ANDA
[FNC 01]
6.90 to
33.00
MUL >
11.80 to
39.00
DIVIDE
DIV >
<ANDA>
AND A
nnnn
@ANDA
@[FNC 01]
nnnn
ORA
[FNC 31]
nnnn
@ORA
@[FNC 31]
ANDA>
OR A
ORA >
R No.,
DM/TM
No.,
#/$ No.,
nnnn
@EORA
EORA> @[FNC 15] #TMxx
nnnn
EXCLUSIVE
OR A
EORA
[FNC 15]
R No.,
DM/TM
No.,
#/$ No.,
#TMxx
<EORA>
0000 to 0009
0500 to 17915
DM0000 to DM9999
TM00 to TM31
#00000 to #65535
$0000 to $FFFF
#TM00 to #TM29
8.90 to
35.00
6.90 to
33.00
8.90 to
35.00
0000 to 0009
0500 to 17915
DM0000 to DM9999TM00 to
TM31
#00000 to #65535
$0000 to $FFFF
#TM00 to #TM29
6.90 to
33.00
8.9 to
35.00
3-146
@ADD
@[FNC 00]
Page
3 (12)
nnnn
ADD >
Function
Subtracts value
3 (12) specified by operand
from content of register
and inputs result back
3 (26) to same register.
3-150
Multiplies content of
3 (12) internal register by
value specified by
operand and inputs
3 (26) result back to same
register.
3-150
Divides content of
3 (12) internal register by
value specified by
3-150
operand and inputs
3 (26) result back to same
register.
ANDs each of 16 bits of
3 (12) internal register and that
of value specified by
3-159
operand, and inputs
3 (26) result back to same
register.
ORs each of 16 bits of
3 (12) internal register and
that of value specified
by operand, and inputs 3-161
3 (26) result back to same
register.
EXCLUSIVE-ORs each
3 (12) of 16 bits of internal
register and that of value 3-164
specified by operand,
3 (26) and inputs result back to
same register.
Chapter 2 Instructions
3-51
12
KV-300
KV-300 Series,
Series, KV-10/80
KV-300
Instruction Symbol
#dd
@SRA
@[FNC 41]
12.80
#dd
SLA
[FNC 40]
10.80
SLA >
10.80
@SLA
@[FNC 40]
12.80
# constant
12.00
@RRA
@[FNC 37]
14.00
RLA
[FNC 35]
12.00
RLA >
@RLA
@[FNC 35]
14.00
COM
[FNC 05]
6.10
#dd
RRA >
#dd
ROTATE
LEFT A
#dd
COMPLEMENT
COM >
nnnn
INCREMENT
MEMORY
nnnn
INC >
nnnn
DECREMENT
MEMORY
3-52
Moves content of
2 (11) internal register serially
left, allowing each bit
that leaves left end to
2 (25) enter carry bit and then
rightmost bit.
3-169
1 (9)
7.70
3 (12)
@INC
@[FNC 19]
9.70
3 (26)
7.70
3 (12)
@DEC
@[FNC 07]
9.70
#n
MPX
[FNC 27]
7.30
3-171
Adds 1 to content of
data memory specified
by operand.
3-172
MPX >
@MPX
@[FNC 27]
9.30
DMX
[FNC 12]
6.70
1 (9)
DMX >
@DMX
@[FNC 12]
DEMULTIPLEXER
3-169
INC
[FNC 19]
DM0000 to DM9999
TM00 to TM29
# constant
#n
Chapter 2 Instructions
#0 to #3
8.70
3-166
Moves content of
2 (11) internal register serially
right, allowing each bit
that leaves right end to
2 (25) enter carry bit and then
leftmost bit.
1 (23)
DM/TM
No.
Page
8.10
DEC
[FNC 07]
Function
@COM
@[FNC 05]
nnnn
DEC >
MULTIPLEXER
#01 to #16
RRA
[FNC 37]
#dd
ROTATE
RIGHT A
Exec.time
Bytes
(s)
SRA
[FNC 41]
SRA >
SHIFT
LEFT A
Operand value
#dd
SHIFT
RIGHT A
Mnemonic Operand
Converts position of
highest order bit with 1
in internal register into
1 (23) 4-bit data.
3-176
3-176
KV-300
Instruction
TRANSFER
BCD
Symbol
Mnemonic
<TBCD>
TBCD
[FNC 47]
@TBCD
TBCD> @[FNC 47]
Exec.time
Bytes
(s)
13.20
15.20
TBIN
[FNC 48]
14.00
TBIN>
@TBIN
@[FNC 48]
16.00
ASC
[FNC 02]
8.50
ASC >
@ASC
@[FNC 02]
10.50
<RASC>
RASC
[FNC 32]
6.80
ASCII
CONVERT
@RASC
<ROOT>
SQUARE
ROOT
Operand value
TRANSFER
BIN
REVERSE
ASCII
CONVERT
Operand
Page
Converts content of
internal register (16-bit
binary) into 4-digit BCD
1 (23) data.
3-180
Converts content of
internal register (4-digit
BCD) into 16-bit binary
1 (23) data.
3-180
1 (9)
1 (9)
1 (9)
Converts content of
lower order byte of
internal register into 21 (23) digit ASCII code.
3-183
1 (9)
Converts 2-digit ASCII
code into one byte data. 3-183
8.80
ROOT
[FNC 36]
77.70
@ROOT
79.70
Function
1 (23)
Takes square root of 32bit data (TM00: higher
order byte, internal
3-185
register: lower order
1 (23) byte) and inputs result
back to same register.
1 (9)
Chapter 2 Instructions
3-53
12
KV-300
KV-300 Series,
Series, KV-10/80
Function
Page
Symbol
INTERRUPT
DISABLED
< DI >
DI
[FNC 08]
3.0 to 4.6
1 (4)
Disables execution
of interrupt.
3-193
INTERRUPT
ENABLED
< EI >
EI
[FNC 13]
3.0 to 4.6
1 (4)
Enables execution
of interrupt.
3-193
INT
nnn
R No.
RETI
1 (8)
Comparator
No.
INT
CTCn
RETURN
INTERRUPT
35.0 to 48.0
000 to 003
INT
[FNC 20]
INTERRUPT
KV-10/16/24/40/80
Operand value Operand value Exec.time
Bytes
KV-10/16
(s)
KV-24/40/80
Instruction
35.0 to
48.8
CTC0 to CTC3
RETI
[FNC 34]
20.0 to
23.0
1 (3)
Represents end of
interrupt.
3-192
KV-300
KV-300
Mnemonic Operand
Exec.time
Bytes
(s)
Instruction
Symbol
INTERRUPT
DISABLED
< DI >
DI
[FNC 08]
3.20
INTERRUPT
ENABLED
< EI >
EI
[FNC 13]
5.80
INT
nnn
R No.
INT
CTCn
3-54
000 to 003
Function
Page
1 (9)
Disables execution
of interrupt.
3-193
1 (0)
Enables execution
of interrupt.
3-193
40.00 to
80.00
1 (0)
Executes instructions
between INT and
RETI at rising edge
3-192
of any of input 000 to
003 or at falling edge
of 003.
40.00 to
80.00
1 (0)
60 to 100
1 (0)
INT
[FNC 20]
INTERRUPT
RETURN
INTERRUPT
Operand value
RETI
Comparator
No.
RETI
[FNC 34]
Chapter 2 Instructions
CTC0 to CTC3
3-192
Ladder symbol
Represents the form
of the instruction on a
ladder diagram.
Instruction key
Represents the key or
function No. for entry.
Instruction
Describes the name
and brief function of
the instruction.
SET / RES
SET: Set
Mnemonic
Represents the instruction in ladder language.
RES: Reset
SET
RES
Example
Example
Timing diagram
Description
Perform programming
using the given example
to gain experience.
nnnn
SET
nnnn
RES
0000
0500
SET
0001
0500
RES
Coding
Line No.
Instruction
LD
0000
0001
SET
0500
0002
LD
0001
0003
OUB
0500
Description
Output relay 0500 remains ON after input relay 0000 turns OFF. Output relay
0500 turns OFF when input relay 0001 turns ON.
SET instruction sets a latch whereas RES instruction resets it.
RES instruction not only turns OFF relay coils but serves as a reset signal when
a timer or counter is used as an operand.
0001
#00100
C000
00000
C000
RES
0002
Note
Describes the notes
for the instruction.
0001
0002
Coding
Shows the
coding for
the given
example.
#00100
C000
0000
Note: The SET and RES instructions can be entered in any order. Note, however,
that priority is given to the instruction that is entered last.
In the above example, when both 0000 and 0001 are ON, RES has priority over
SET, causing 0500 to remain OFF.
Tips
Differences between SET/RES and KEEP
Basically , SET/RES and KEEP ( p. 3-57 and p. 3-71) serve the same purpose.
SET and RES can be used separately. Therefore, RES can be placed before
SET.
Another instruction may be placed between SET and RES.
KEEP needs only three lines of program, therefore saving memory space when
used a number of times.
Tips
Describes hands-on
techniques for efficient
programming.
Operand
Shows operands (element
Nos.) that can be used for
the instruction.
Operand
0000
0000
0500
RES
0001
0500
SET
LD
RES
LD
SET
0000
0000
0500
0001
0500
KEEP
SET
0500
0001
LD
0000
LD
0001
KEEP 0500
RES
Operands
NEW KV
KV-300
KV-10/16
KV-24/40/80
0500 to 1915
2009
2100 to 17915
T000 to T249
C000 to C249
0500 to 1915
2009
2100 to 17915
T000 to T249
C000 to C249
0500 to 1915
2009
2100 to 2915
T000 to T063
C000 to C063
0500 to 1915
2009
2100 to 6915
T000 to T119
C000 to C119
Key operation
Describes the basic key
operations on the handheld
programmer. Set the mode
switch to PROGRAM.
Key operation
SET
3-66
Operand
ENT
R-SRCH
RES
Operand
ENT
R-SRCH
Chapter 2 Instructions
Chapter 2 Instructions
3-55
12