11/2012
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Table of contents
1 2 Validity..........................................................................................................................................................5 Solved problems...........................................................................................................................................7 2.1 2.2 2.3 2.4 3 General information.......................................................................................................................7 Solved problems in Update 3........................................................................................................8 Solved problems in Update 2......................................................................................................12 Solved problems in Update 1......................................................................................................15
Installation...................................................................................................................................................17
Validity
Validity
This update is valid for the following WinCC flexible 2008 SP3 editions: WinCC flexible 2008 SP3 Compact / Standard / Advanced WinCC flexible 2008 SP3 ASIA Standard / Advanced WinCC flexible 2008 SP3 China WinCC flexible 2008 SP3 Runtime
Installation
To install the update, please follow the instructions in the chapter "Installation".
Solved problems
2.1 General information
General information
General information that could not be included in the manual or Online Help for WinCC flexible 2008 SP3. Character set for Chinese font Chinese font is now supported in data type "String" for connections to SIMATIC S7 300/400. Activate the "Chinese (VR)" option in the Engineering System. The CP936 code page is now used instead of the ASCII code page. The option is available for the following devices: MP 377 WinCC flexible Runtime
2.2
This update rectifies the following problems in the Engineering System and optimizes configuration scenarios:
Pack&Go on Windows operating systems A Pack&Go file that you create on a 64-bit system may not be fully functional on a 32-bit system. A Pack&Go file that you create on a 32-bit system may not be fully functional on a 64-bit system. Transfer in SIMATIC Manager If you are using SIMATIC Manager to transfer a project to an HMI device you cannot edit certain transfer settings. PLC connection of symbolic tags cannot be clearly defined If several connections to the PLC are active, you cannot determine which of the configured connections is used by the tag during runtime. Selecting the hardware component in the tag dialog The tag dialog displays hardware components that do not contain tags that can be used for HMI devices. Compiling projects with formatted text Compilation of a project with formatted text and tags with invalid reference fails with a nonspecific error message. OP 77A: Error message with system function "SetBit" If you assign the "SetBit" system function to the <ESC> key on the OP 77A HMI device, the following error message may be output during compilation of the project: "object xxxx is marked to be activated but does not exist. Tab order of the object groups The tab order differs, depending on whether or not the graphic objects are grouped.. Tab order in screens and faceplates Incorrect processing of the tab order in screens with faceplates. Converting projects Conversion of a project that contains invalid tag interconnections will fail. System function "ActivateClearingScreen" on MP 377 15'' Touch daylight readable System function "ActivateClearingScreen" is not available on the MP 377 15 Touch daylight readable HMI device. Windows 7: Graphic objects in the template After you configure graphic objects in the template and then change the user interface language, the configured objects are no longer visible. This behavior occurs only in Windows 7.
This update fixes the following problems in Runtime and optimizes configuration scenarios:
Printing reports Certain printers may output an incorrect layout when printing the report. Devices affected: PC Runtime <Enter> key on the on-screen keyboard Pressing the <Enter> key on the on-screen keyboard may trigger an unwanted input. Devices affected: PC Runtime Windows CE HMI devices Step View in ProAgent A click in the space next to a sequencer object in ProAgent followed by an activation of system function "SequencerScreenActivateStep" may cause problems in the connected S7 PLC. Devices affected: PC Runtime Windows CE HMI devices Motion View in ProAgent Exceeding the number of rows that can be displayed in the Motion View may lead to problems when you select a row. Devices affected: PC Runtime Windows CE HMI devices Archives in Runtime Due to different time characteristics on certain systems, random problems may occur during archiving at the start of Runtime or at the call of system function "OpenAllArchives". Devices affected: PC Runtime Windows CE HMI devices Serial communication using the Modbus protocol Setup of a canceled connection may fail on specific devices that are connected by means of MODBUS RTU. Moreover, incorrect values are possibly transmitted to the PLC from the panel if data types "Double" or "Float" are used.
10
11
2.3
12
13
14
2.4
Security update
We have been recently informed about vulnerabilities in WinCC flexible. These claims have been thoroughly investigated by our specialists and the security loopholes in WinCC flexible have been closed. Our internal investigation also uncovered additional security loopholes in Sm@rtService (web pages). Update 1 for WinCC flexible 2008 SP3 closes these security loopholes as well.
15
Installation
Requirements
This update requires one of the following WinCC flexible installations: WinCC flexible 2008 SP3 Compact / Standard / Advanced WinCC flexible 2008 SP3 ASIA Standard / Advanced WinCC flexible 2008 SP3 China WinCC flexible 2008 SP3 Runtime Install the update on your configuration PC and Runtime PC.
Procedure
To install the update, proceed as follows: 1. Double-click on the "WinCCflexible2008_SP3_upd3.exe" file. 2. Select the "C:\WinCCflexible2008_SP3_UPD3" as the installation folder in the "WinZip SelfExtractor" dialog. 3. Enable "When done unzipping open .\setup.exe" and exit the dialog by clicking "Unzip". 4. Open your project on the configuration PC. 5. Execute a full compilation with the menu command "Project > Compiler > Rebuild All...". 6. Transfer the project to the HMI device once again.
17