Вы находитесь на странице: 1из 8

1ZSC000562-AAV en

Tap-changers for power transformers Product guide

Vacuum on-load tap-changers

Our new generation of tap-changers utilize the most recent vacuum interrupter technology. This design philosophy allows the arcs during load commutations to occur in vacuum interrupters and not in the tap-changer oil. This greatly reduces the need for maintenance and creates the potential for using environmental-friendly insulating fluids. Final product dependability is ensured through extensive testing beyond international standards combined with decades of experience

from developing technical solutions. ABB offers a full range of products for both high voltage and low voltage regulation. Our tap-changers are paired with robust, dependable motor drives that are configurable to meet a wide range of environmental conditions and customer specifications. From the compact BUL and versatile BUE for in-tank tap changers to the digitally controlled SMD with integrated Tap Logic Monitoring System (TLMS) for the type VRLTC tap-changer.

On-load tap-changer, type VRLTC

On-load tap-changer, type VUBB

2 Tap-changers for power transformers | 1ZSC000562-AAV en

Type VRLTC Application Maximum rated through-current Three-phase star point Three-phase fully insulated Highest rated lightning impulse/ power frequency withstand to earth Highest system voltage Maximum rated phase step voltage Maximum number of operating positions Linear With change-over selector Technology: 17 33 Vacuum reactance 34.5 kV 1000 V 2000 A 2000 A 200 kV / 70 kV fully insulated

Type VUBB

Type VUCG

Type VUCL

Single unit: three-phase star point, and three-phase

Single unit: single-phase and three-phase star point Multiple units: three-phase fully insulated

600 A 600 A 380 kV / 140 kV 76 kV 1600 V

800 A 800 A 1050 kV / 460 kV 300 kV 3500 V

1000 A 1000 A 1050 kV / 460 kV 300 kV 4500 V

10 19 Vacuum resistive

22 35 Vacuum resistive

22 35 Vacuum resistive

On-load tap-changer, type VUCG

On-load tap-changer, type VUCL

1ZSC000562-AAV en | Tap-changers for power transformers 3

Conventional on-load tap-changers

Unsurpassed simplicity, convenient accessibility and no requirements for special tools is the hallmark of our conventional tap-changers. ABBs customer-focused design philosophy has stood the test of time for over 100 years and resulted in designs with fewer parts and lower maintenance costs. In addition to increased reliability, tap-changers with fewer parts allow for considerable reduction in size and cost.

Our tap-changers are matched with trustworthy, rugged motor drives that are configurable to meet a wide range of environmental conditions and customer specifications. From the compact BUL and versatile BUE for in-tank tap changer models to the fully integrated BUF for the type UZ on-tank tap-changer.

On-load tap-changer, type UZ

On-load tap-changer, type UBB

4 Tap-changers for power transformers | 1ZSC000562-AAV en

Type UZ Application Maximum rated through-current Three-phase star point Three-phase fully insulated Highest rated lightning impulse/ power frequency withstand to earth Highest system voltage Maximum rated phase step voltage Maximum number of operating positions Linear With change-over selector 17 33 145 kV 2000 V 600 A 600 A 650 kV / 275 kV

Type UBB

Type UCG

Type UCL

Type UCC/UCD

Single unit: three-phase star point, and three-phase fully insulated 500 A 500 A 350 kV / 140 kV 76 kV 1500 V

Single unit: single-phase and three-phase star point Multiple units: three-phase fully insulated 600 A 1500 A 1050 kV / 460 kV 300 kV 3500 V 900 A 2400 A 1050 kV / 460 kV 300 kV 4500 V 1600 A 1600 A 1050 kV / 460 kV 300 kV 5000 V

14 27

22 35

22 35

18 35

On-load tap-changer, type UCG

On-load tap-changer, type UCL

On-load tap-changer, type UCC

1ZSC000562-AAV en | Tap-changers for power transformers 5

De-energized tap-changers

Our designs are proven solutions with decades of successful field experience. Their simplicity and ease of installation make ABBs de-energized tap-changers the preferred solution by transformer manufacturers worldwide. Multiple deck arrangements make our designs the most space saving de-

energized tap changers available in the market. Both bridging and linear options are available with ratings up to 4000 A and 1050 kV BIL. And, with little to no required maintenance, our designs have proven to be an ideal solution to both utility and industrial customers.

Type DTU Maximum rated through-current Highest rated lightning impulse / power frequency withstand to earth Lightning impulse / power frequency withstand between adjacent contacts Maximum number of operating positions 7 140 kV / 50 kV 1500 A (500 A per deck) 650 kV / 275 kV

Type DTL 2000 A 650 kV / 275 kV 140 kV / 50 kV 7

Type DTW 4060 A (1015 A per deck) 1050 kV / 460 kV 180 kV / 75 kV 5

De-energized tap-changer, type DTU

De-energized tap-changer, type DTL

De-energized tap-changer, type DTW

6 Tap-changers for power transformers | 1ZSC000562-AAV en

Life cycle support

We are committed to stand behind our products for as long as they are in operation. Product support, documentation and training is therefore essential. This includes immediate availability of parts for all models, 24-hour access to support personnel and the existence of a global reporting network. Some of our UC tap-changer types are possible to upgrade without the need to rebuild; they can be upgraded with vacuum technology as quickly and as easily as performing a normal overhaul. In many cases this makes it possible to increase the tapchangers nominal load and at the same time benefit from all the advantages associated with vacuum technology.

1ZSC000562-AAV en | Tap-changers for power transformers 7

Contact us

We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its content in whole or in parts is forbidden without ABBs prior written consent.

ABB Inc. 1133 South Cavalier Drive Alamo, Tennesseee 38001, USA Phone: +1 800 955 8399 +1 731 696 5561 Fax: +1 731 696 5377 www.abb.com/electricalcomponents

Copyright 2013 ABB, All rights reserved. 1ZSC000562-AAV en, 2013-05-15

ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com