If the inside temperature of a space rises to about 25oC then air conditioning will probably be necessary to maintain comfort levels. This internal temperature (around 25oC) may change depending on some variables such as: Type of building Location of building Duration of high internal temperature Expected comfort conditions. Degree of air movement Percentage saturation In some buildings it may be possible to maintain a comfortable environment with mechanical ventilation but the air change rate will
tend to be high (above about 8 air changes per hour) which can in itself cause air distribution problems. Since air conditioning is both expensive to install and maintain, it is best avoided if possible. This may possibly be achieved by careful building design and by utilising methods such as:
window blinds or shading methods heat absorbing glass heat reflecting glass Openable windows higher ceilings Smaller windows on south facing facades Alternative lighting schemes.
If air conditioning is the only answer to adequate comfort in a building then the main choice of system can be considered. Full comfort air conditioning can be used in summer to provide cool air (approx. 13oC to 18oC) in summer and warm air (approx. 28oC to 36oC) in winter. Also the air is cleaned by filters, dehumidified to remove moisture or humidified to add moisture. Air conditioning systems fall into three main categories, and are detailed in the following pages;
1. 2. 3.
Central plant systems. Room air conditioning units. Fan coil units.
Central plant systems have one central source of conditioned air which is distributed in a network of ductwork. Room air conditioning units are self-contained package units which can be positioned in each room to provide cool air in summer or warm air in winter. Fan coil units are room units and incorporate heat exchangers piped with chilled water and a fan to provide cool air.
There are other forms of air conditioning such as; Chilled beams Induction units Variable Air Volume units Dual duct systems Chilled ceiling, But we will consider the more commonly used methods first.
Heater Battery
Supply air
Return air fan Schematic Diagram of Central Plant Air Conditioning System
balanced ventilationsystem with The system shown above resembles a plenumheating but with the addition of a cooling coil. section. For information on balanced ventilation seeVENTILATION In winter the heater batterywill be on and the cooling coilwill probably be switched off for the majority of buildings. In summer the heater batterywill not need to have the same output and the cooling coilwill be switched on. A humidifier may be required to add moisture to the air when it is 'dry'. 20% to 30%. This is when outdoor air has a low humidity of around In the U.K. low humidities are rare and therefore humidification is sometimes not used. In dryer regions humidification is required through most of the year whereas in tropical air conditioning one of the main features of the system is the ability to remove moisture from warm moist air.
Dampersare used in air conditioning central plant systems to control the amount of air in each duct. It is common to have 20%fresh air and 80%recirculated air to buildings. In buildings with high occupancy the fresh air quantity should be calculated based on C.I.B.S.E. data., this may require a higher percentage of fresh air (i.e. more than 20%). SeeVentilation section for examples of fresh air rates.
Pre-filter Pre-heater Fresh air
+
+
Humidifier
Supply air
Room
Return air
Return air fan Schematic Diagram of Central Plant Air Conditioning System with Preheater, Dampers, Humidifer and Filters
Filters are required to remove particles of dust and general outdoor pollution. This filter is sometimes called a coarse filter or pre-filter. dust filter is positioned in the fresh air intake A removable fibreglass duct or in larger installation an oil filled viscous filter may be used. fine dust The secondary filter, after the mix point, is used to remove particles or other contaminant picked up in the rooms and recirculated bag filter is generally used for this back into the plant. A removable where a series of woven fibre bags are secured to a framework which can be slid out of the ductwork or air handling unit (A.H.U.) for replacement.
In some cases it is usual to place fan the in front of (that is upstream of) the heater battery and cooling coil. This is because fans operate best if the system resistance is outlet at the rather than the inlet of the impeller. This is shown on the schematic diagrams above. The photograph below shows a typical air handling unit with handles on the doors for access to equipment.
1. 2.
The photographs below show a ceiling mounted cassette and an outdoor unit.
A smallhermetically sealed compressor is used to provide refrigerant gas at the pressure required to operate the refrigeration cycle. The condenseris used tocondensethe refrigerant to a liquid which is then reduced in pressure and piped to the cooling coil.
Cool Air
Thermostat
Fan coil units may be looked upon as being small air handling units located in rooms and they can be piped with chilled water for cooling and low temperature hot water (LTHW) for heating if necessary. The room temperature can be controlled with low, medium and high fan speeds and chilled water flow is varied with a two-port or three-port motorised valve. Two-pipe, three-pipe and four-pipe systems have been used. The four-pipe system has two heating and two cooling pipes and may have a single heat exchanger or two separate heat exchangers for heating and cooling.
It is useful to have a summer/winter changeover switch in the main control system to avoid both heat exchangers being on at the same time. A three-pipe system used heating flow, cooling flow and common return Pipework.
3.
4. 5.
No long runs of ductwork. Can be used to heat as well as cool if a reversing valve is fitted.
4. 5. 6. 7.
Fan coil units are similar is some respects to Room Air Conditioners.
5. 6.
room air conditioners. Also boilers will be required if heating mode is installed. Freshair facility may not be installed. Cooling output is limited to about 5 kW .
6. Check out the recommended air flow rate from CIBSE Guide B2 (Ventilation and Air Conditioning) Section 3 - Requirements. Use the higher value of air change rate for design purposes. Example 1 Determine the supply, fresh air and recirculation air flow rates for the Sports Centre (Fitness Suite No.1) shown below. See Assignments section Drawings. The room is to be fully air conditioned.
17 m
44 m
DATA
Occupancy = 80 people Room volume = 3740 m 3. Room temperature = 18oC from table 3.19 CIBSE guide. Sensible heat gain = 70 kW from calculations (not shown) See Heat Gains section of these notes for further details. Supply air temp. = 13oC from psychrometric chart (not shown) See Psychrometrics section of these notes for further details. Supply air density = 1.225 kg/m 3. See Science section Properties of air density at 13 oC and 50%
Volume flow rate (m 3/s) Volume flow rate (m 3/h) Supply Air Rate (AC/h)
Table 3.1 Summary of Recommendations (Guide B2) directs to Table 3.19. From Table 3.19 for Fitness Centre the air flow rate is 10 to 12 AC/h.
Use higher value of 12 AC/h supply air rate as found from above Table. This higher value is then used to size all plant and ductwork. Fresh Air Rate Section 3.2.1.3 Body odour (CIBSE guide B2) gives the following information;
Therefore in the absence of further information, it is recommended that 8 litre.s-1 per person should be taken as the minimum ventilation rate to control body odour levels in rooms with sedentary occupants.
Since the level of activity is higher than sedentary in the Fitness Room, we will adopt a fresh air rate of 24 l/s per person.
Fresh air rate = = = = = 24 l/s x 80 people 1920 l/s 1.92 m 3/s 1.92 x 3600 = 6912 m 3/h / 3740 = 1.9 / 12.0 (x 100%) =
Cooling Coil Pre-filter Pre-heater Supply fan Bag filter(s) Supply air 12.0 AC/h Heater Battery
12.47 m3/s
Room
Dampers
12.47 m3/s
Return air fan Schematic Diagram Of Central Plant Air Conditioning System
A slight negative pressure may be provided in the Fitness Room. This is so that contaminated air does not enter the adjoining Reception / Foyer area. The Return air amount may be increased to 110% of the previously calculated value; that is, 13.2 AC/h or 13.72 m3/s.
Introduction
Heat gains from the sun can lead to increases in internal temperatures beyond the limits of comfort. This is usually above 24oC dry bulb temperature in the UK. A software programme such as Hevacompis often used to determine the internal summertime temperatures for a building. It is therefore necessary to determine the amountsolar of radiationthat is transmitted into buildings through; windows, walls, roof, floor and by admitting external air into the building. Several measures can be adopted to reduce solar radiationin buildings. These are external and internal shading and by careful building design. Natural vegetation such as tall trees can also reduce solar heat gains. Window areas can be reduced although natural day lighting is important in northern latitudes in winter so there is a limit to glass reduction. Buildings can be orientated so that there is less window area facing directly south. These are just some of the ways to reduce solar radiation .
The heat gain through the glass windows is divided two into parts since there is a heat gain due to temperature differencebetween outside and inside and another gain due to solar radiationshining through windows. The method adopted uses the CIBSE guide A (2006) and CIBSE Guide J (2002). The Tables that are referred to are CIBSE guide A (2006) Solar cooling loads inTables 5.19 to 5.24 . CIBSE Guide J (2002) Air and Sol-air temperatures in Table 5.36 (London), Table 5.37 (Manchester) and Table 5.38 (Edinburgh) This set of Tables is in Appendix A6 at the end of the guide. Table 5.36 (London)starts at page A6-121. If internal gains are to estimated then CIBSE Guide A (2006) Table 6.4 to 6.17 are also required. It would be helpful to have these Tables close by, to complete the calculations. An example of a heat gain claculation is given CIBSE in Guide A (2006) section 5.8.2 example 5.3. Heat gains through solid ground floors are minimal and can be neglected.
This gain only applies to materials of negligible thermal capacity i.e. glass.
Qg =
eqn. 1
Where; Qg Ag = =
Ag . Ug (t o- tr)
2 oC) Ug = 'U' value for glass (W/m (see CIBSE guide A (2006) Table 3.23 to 3.32). to = outside air temperature o ( C). Can be obtained from CIBSE Guide J (2002) - Tables 5.36 to 5.38 for various months and times in the day. oC) tr = room air temperature (
Qsg =
eqn. 2
where Qsg = qsg = Table 5.19 to 5.24 Fc = Fs = Ag =
Fc . F s. q sg . A g
Actual cooling load (W) Tabulated cooling load from CIBSE Guide A (2006) 2 (W/m ) Air node correction factor from Table below. Shading factor from Table below. 2) Area of glass (m
The Air point control factors c (F ) and Shading factors s) (F are given in the Table below for various types of glass, building weights and for open and closed blinds.
Air node correction factors (F c) Building Weight Light Heavy Single Glazing Horizontal blind 0.91 0.83 Double glazing Horizontal blind 0.91 0.90
Shading factors (F s) Type of glass Clear 6mm Bronze tinted 6mm Bronze tinted 10mm Reflecting Building Weight Light Heavy Light Heavy Light Heavy Light Heavy Single Glazing Open Closed horizontal horizontal blind blind 1.00 0.77 0.97 0.77 0.86 0.77 0.85 0.78 0.77 0.64 0.62 0.77 0.73 0.73 0.57 0.57 Double glazing Open Closed horizontal horizontal blind blind 0.95 0.74 0.94 0.76 0.66 0.55 0.66 0.54 0.53 0.48 0.47 0.57 0.47 0.48 0.41 0.41
The CIBSE guide method of calculating solar gains through glazing in Guide A (2006), section 5.8.1.1 uses a slightly different formula as follows;
Qsg =
where
S.q sg . A g
Qsg = Actual cooling load (W) qsg = Tabulated cooling load from CIBSE Guide A (2006) 2 Table 5.19 to 5.24 (W/m ) S = Mean solar gain factor at the environmental node or air node from CIBSE Guide A (2006) Table 5.7. 2) Ag = Area of glass (m
Conditions
Typical building
Seated very light work Offices, hotels, apartments Moderate office work Offices, hotels, apartments Standing, light work; Department store, retail store walking Walking standing Sedentary work Light bench work Athletics Bank Restaurant Factory Gymnasium
LIGHTING Average power density from CIBSE Guide A (2006) - Tables 6.4. ELECTRICAL EQUIPMENT - PCs and Monitors CIBSE - Guide A (2006) Tables 6.7 and 6.8. Laser Printers and Photocopiers CIBSE Guide A (2006) - Tables 6.9 and 6.10 Electric Motors CIBSE Guide A (2006) - Table 6.13 and 6.14. Lift Motors CIBSE Guide A (2006) - Table 6.15. Cooking equipment C IBSE Guide A (2006) - Table 6.17. Heat load is found from; Q int. = Heat from Occupants + Heat from Lighting from Electrical Equipment + Heat from Cooking + Heat
t eo
eqn. 4.1
where
ta = outside air temperature o ( C) = absorption coefficient of surface I = intensity of direct solar radiation on a surface at right 2 angles to the rays of the sun. (W/m ) a = solar altitude (degrees) n = wall-solar azimuth angle (degrees) Is = intensity of scattered radiation normal to a surface 2 (W/m ) 2 oC) hso = external surface heat transfer coefficient (W/m
t eo
sol-air temperature o ( C)
The U.K. values of sol-air temperature are found from CIBSE Guide J (2002) Table 5.36 (London), Table 5.37 (Manchester) and Table 5.38 (Edinburgh) . Table 5.36 (London)starts at page A6-121.
Q
eqn. 4.2
A.U(e t m - tr)
Q = heat gain through wall at time 2 A = area of wall (m ) 2 U = overall thermal transmittance (W/m oC) (See Thermal Transmission in Science section of the notes) or (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. t em = 24 hour mean sol-air temperatureo( C) CIBSE Guide J (2002) - Table 5.36 to 5.38. tr = constant dry resultant temperature o (C). In practice room dry bulb is used. where,
2. The variation from the mean solar gain is subject to both a decrement factor and time lag.
Q
eqn. 4.3
f ( teo - tem)
Q = Heat gain through wall at time ( ) = time lag in hours (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. t eo = sol-air temperature at time ( (oC) CIBSE Guide J (2002) - Table 5.36 to 5.38. t em = 24 hour mean sol-air temperatureo( C) CIBSE Guide J (2002) - Table 5.36 to 5.38. f = decrement factor (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. where
Q =
eqn. 4.4
Q = heat gain through wall at time (Watts) = time lag in hours (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. 2 A = area of wall (m ) 2 U = overall thermal transmittance (W/m oC) (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. t em = 24 hour mean sol-air temperatureo( C) CIBSE Guide J (2002) - Table 5.36 to 5.38. tr = constant dry resultant temperature o (C) In practice room dry bulb is used. f = decrement factor (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. t eo = Sol-air temperature at time ( ) (oC) CIBSE Guide J (2002) - Table 5.36 to 5.38 where,
Qsi =
eqn. 6
where
n . V (t o- tr) / 3
Qsi = Sensible heat gain (W) n = number of air changes per hour -1 (h) (see note below) 3) V = volume of room (m to = outside air temperature o ( C) Can be obtained from CIBSE Guide J (2002) - Tables 5.36 to 5.38 for various months and times in the day. oC) tr = room air temperature (
Infiltration gains should be added to the room heat gains. Recommended infiltration rates are 1/2 air change per hour for most air-conditioning cases or 1/4 air change per hour for double glazing or if special measures have been taken to prevent infiltration. or Ventilation or fresh air supply loads can be added to either the room central plant loads but should only be accounted for once.
Q total Glass
Ag . Ug (to - tr)
1.
Sensible
+ + + + +
Fc . F s . qsg . Ag Qint. A.U [( tem - tr) + f ( e t o - tem)] A.U [( tem - tr) + f ( e t o - tem)] n . V (t o - tr) / 3
eqn. 7 In the majority of cases, by far the greatest external fluctuating component is the solar heat gain through the windows. Therefore, it will be this gain which determines when the total heat gain maximum. to the room is a Heat gains may be calculated and displayed in table form as shown below. Heat Gain from 1. Sensible transmission through glass 2. Solar gain through glass 3. Internal 4. External walls 5. Roof 6. Ventilation Total
2 Heat gain per m floor area = 3 Heat gain per m space =
Watts
100%
Latent Gains
Latent heat gainsare calculated so that the Total heat gaincan be determined to complete a psychrometric chart. Total heat gain = Sensible heat gain Latent + heat gains AlsoLatent heat gains are required to size Chillers. Latent heat gains are comprised of latent gain from occupantsand from natural infiltration fresh air . Latent heat gains from occupantscan be obtained from CIBSE Guide A (2006) - Table 6.3 shown above. The following formula gives the infiltration latent heat gain.
Qli
Where; Qli N V mso msr
0.8 . n . V ( m so msr )
= Infiltration latent heat gain (W) -1 = Number of air changes per hour ) (h 3 = Room volume (m ) = Moisture content of outside air (g/kg d.a.) from psychrometric chart. = Moisture content of room air (g/kg d.a.) from psychrometric chart.
Example 1
The room shown below is to be maintained at a constant environmental temperature of 21oC for a plant operation of 12 hours per day. The room is on the intermediate floor of an Library located in London latitute 51.7oN. The internal construction is lightweight demountable partitions, lightweight slab floors and suspended acoustically treated ceilings, shading is intermittent. Calculate the maximum sensible cooling load in the room in July The outside air temperature (to) may be found from CIBSE Guide J (2002) Tables 5.36 page A6-127 (July 4th). The maximum value ocurrs at 16.00 hrs. and is 25.4oC.
DATA:
100 0.5 air changes per hour lightweight, fast. 0.45 W/m2oC, internal insulation, neglect time lag through wall. External wall colour = light. External wall decrement factor f = 0.65 Glass type & 'U' value = clear 6mm, double glazing, U = 2.80 W/m2oC Window blinds = internal blind.. Lighting = 30 Watts / m2 floor area Heat gain from machinery and equipment = 4000 Watts
Occupants Infiltration Building classification Building response External wall 'U' value
= = = = =
NOTE: It should be noted that this total heat gain is used to size central plant items such as Chillers, Condensers and Cooling Towers. Cooling coils are sized usually with a pschrometric chart. Answer Areas:
Area of window Total area of glass Area of glass facing South Area of wall facing South Floor area Room volume = = = = = = = 1.2 x 1.7 = 2.04 m2. 2.04 x 12No. windows = 24.48 m2. 12.24 m2. 22.0 m x 4.0 m high = 88 m2 less glass 88 - 12.24 = 75.76 m2. 22 x 14 = 308m2. 308 x 4 = 1232 m3.
Gains:
1. Sensible transmission through glass Qg Qg Qg 2. where: Qsg Fc Fs qsg = = = = Actual cooling load (W) Air node correction factor from Table in page 2 internal blind, fast response - 0.91. Shading factor from Table in page 2 - for blind/clear/clear, fast response 0.95. Tabulated cooling load from CIBSE Guide A (2006) Table 5.20 Intermittent shading for July 4th , orientation South, 12.30 hours gives maximum of 238 W/m2 2 Area of glass facing South (m ) Qsg Qsg 3. Internal Qint. Qint. Qint. External wall Qint. = = = = = 0.91 x 0.95 x 238 x 12.24 2,518.4 Watts Solar Gain through glass Qsg = Ag Ug (to - tr) = 24.48 x 2.8 (25.4 21) = 301.6 Watts = Fc Fs qsg Ag
Ag
= Qint. Lights (30 W/m2 x 308) + 4000 W + People (100 x 100) 9,240 + 4,000 + 10,000 23,240.0 Watts Q Wall = A U [( tem - tr) + f ( teo - tem)]
4. where,
Q A U tem
= = = =
heat gain through wall at time q+f (Watts) area of wall facing South (m ) overall thermal transmittance given in question as 0.45 2o W/m C. 24 hour mean sol-air temperature (oC) CIBSE Guide J (2002) - Table 5.36 at 12.30 hrs, light wall facing South 22.6oC constant dry resultant temperature (oC). Room dry bulb of 21oC is given. decrement factor for wall is given as 0.65.
2
tr f
= =
sol-air temperature when Tabulated cooling load (qsg) is at 13.00 hrs. CIBSE Guide J (2002) - Table 5.36, light wall, South facing gives 38.8oC. Q+Wall = 75.76 x 0.45 [( 22.6 21) + 0.65 ( 38.8 22.6)] Q+Wall = 34.092 [ 1.6 + 10.53 ] Q+Wall = 413.5 Watts Q+Roof = Qsi Qsi Qsi 7. Q total Q total Q total = = = Qg + Qsg = = = + Nil for intermediate floor. n V (to - tr) / 3 0.5 x 1232 (25.4 21) / 3 903.5 Watts Qint. + Q+Wall + Q +Roof + Qsi 0 + 903.5
teo
5. 6.
Roof Ventilation
Example 2
The room shown below is to be maintained at a constant environmental temperature of 21oC for a plant operation of 12 hours per day. The room is on the intermediate floor of an Office Block located in London. The internal construction is lightweight partitions, concrete hollow slab floors and suspended ceilings. Calculate the maximum sensible cooling load in the room in July. The outside air temperature (to) may be found from CIBSE Guide J (2002) Tables 5.36 page A6-127 (July 4th). The maximum value ocurrs at 16.00 hrs. and is 25.4oC. DATA:
Occupants = 80 Lighting = 35 Watts / m2 floor area Infiltration = 0.4 air changes per hour Building classification = lightweight with fast response. External wall surface texture= dark. External wall thickness = 300mm, internal insulation, decrement factor is 0.27, neglect time lag through wall. Blinds = Internal Heat gain from machinery and equipment = 3000 Watts
Windows - Double Glazing, Each 1.2 m wide x 1.7 m high, Uvalue = 2.6 W/m2oC.
Answer Areas:
Area of window = 1.2 x 1.7 = 2.04 m2. Total area of glass = 2.04 x 10No. windows = Area of glass facing South West = 10.2 m2. Area of wall facing South West Floor area = Room volume = 18 x 16 = 288 x 3 = 20.4 m2.
Gains:
1. Sensible transmission through glass Qg = Ag Ug (to - tr) Qg Qg = 20.4 x 2.6 (25.4 21) = 233.4 Watts
Qsg
Fc Fs qsg Ag
= = = =
Ag
Actual cooling load (W) Air node correction factor from Table in page 2; internal blind, fast response - 0.91. Shading factor from Table in page 2; for blind/clear/clear, fast response 0.95. Tabulated cooling load from CIBSE Guide A (2006) Table 5.20 Intermittent shading for July 4th , orientation South West, 12.30 hours gives maximum of 328 W/m2 2 Area of glass facing South (m ) Qsg Qsg = = 0.91 x 0.95 x 328 x 10.2 2892.3 Watts
3.
Qint. = = =
= Qint. Lights (35 W/m2 x 288) + 3000 W + People (80 x 100) 10,080 + 3,000 + 8,000 21,080.0 Watts Q Wall = A U [( tem - tr) + f ( teo - tem)]
4. where,
heat gain through wall at time (Watts) area of wall facing South West (m ) 2o overall thermal transmittance given in question as 0.35 W/m C. 24 hour mean sol-air temperature (oC) CIBSE Guide J (2002) Table 5.36 at 13.00 hrs, dark wall facing South West 26.7oC constant dry resultant temperature (oC). Room dry bulb of 21oC
2
decrement factor for wall is given as 0.27. sol-air temperature when Tabulated cooling load (qsg) is at 13.00 hrs. CIBSE Guide J (2002) - Table 5.36, dark wall, South Westfacing gives 47.1oC. (dark faade) Q Wall = 43.8 x 0.35 [( 26.7 21) + 0.27 ( 47.1 26.7)] Q Wall = 15.33 [ 5.7 + 5.51 ] Q Wall = 171.9 Watts 5. Roof Q Roof = Nil for intermediate floor.
6.
Ventilation
= = =
7.
= = =
Qg +
Qsg + Qint. + Q Wall + Q Roof + Qsi 233.4 + 2,892.3 + 21,080.0 + 171.9 + 0 + 506.9 24,884.5 Watts
The heat gain in the previous example was 88.8 W/m2 floor area and the total was 27,377 Watts . The heat gain in this example is 86.4 W/m2 floor area and the total is 24,884.5 Watts. The value of sensible heat gain can be used in a psychrometic chart to determine the cooling coil size in an Air Handling Unit (AHU).
Example 3
The Restaurant shown below is to be maintained at a constant environmental temperature of 22oC for a plant operation of 12 hours per day. The Restaurant area is on the ground floor of an Single storey building located at 51.7oN. The internal construction is lightweight partitions, concrete hollow slab floors and suspended ceilings. Calculate the maximum sensible cooling load in the Restaurant area in July. DATA: Occupants = 70 Lighting = 22 Watts / m2 floor area Infiltration = 1.0 air changes per hour 28oC. Outside air temperature (to) = Building classification = lightweight, fast response building. External wall surface texture = dark. External wall use information from CIBSE guide A (2006) section 8(e) in Table 3.49, 105mm Brick, internal 50mm EPS insulation, 100mm lightweight aggregate concrete block, 13mm dense plaster, cavity wall. Windows Double glazed internal shade, clear 6mm glass, light slatted blinds, intermittent shading. Roof use information from CIBSE guide A (2006) section 2(d) in Table 3.50. Heat gain from equipment = 2000 Watts
7.7 m 14.0 m Roof pitch = 300 Male Toilet 9.5 m Female Toilet 2.7m 3.5 m
Cold Store
Kitchen Lobby Restaurant Reception Prep. Room Entrance PLAN Scale: 1:100 All Restaurant Windows 1.4 m wide x 2.0 m high, double glazed. South
South
Answer Areas:
Area of window Total area of glass Area of glass facing South Area of wall facing South Floor area Ceiling area = = = = = 1.4 x 2.0 = 2.8 m2. 2.8 x 10No. windows = 14.0 m2. 28.0 m2.
14 x 10 = 140 m2. Length x 2(Rafter length inside) Rafter length inside = = = = 14 x 2 (5.774) = 140m2 x 3 + ( 14 x 5 x 2.9 ) = 623 m3.
0.5 x room width / cos roof pitch Rafter length inside = 0.5 x 5 / cos 300. Rafter length inside = 0.5 x 5 / 0.866 = 5.774 metres 161.7 m2.
Gains:
1. Sensible transmission through glass Qg = Ag Ug (to - tr) Qg Qg 2. Solar Gain through glass Qsg = = 28.0 x 2.8 (28 22) = 470 Watts Fc Fs qsg Ag
where: Qsg Fc Fs qsg Ag = = = = = Actual cooling load (W) Air node correction factor from Table in page 2 internal blind, fast response - 0.91. Shading factor from Table in page 2 - for blind/clear/clear, fast response 0.95. Tabulated cooling load from CIBSE Guide A (2006) Table 5.20 Intermittent shading for July 4th , orientation South, 12.30 hours gives maximum of 238 W/m2 2 Area of glass facing South (m ) Qsg = Qsg 3. Internal Qint. Qint. Qint. Qint. = = = = 0.91 x 0.95 x 238 x 14.0 = 2,880 Watts
Qint. Lights (22 W/m2 x 140) + 2000 W + People (70 x 100) 3080 + 2,000 + 7,000 12,080 Watts
4.
External wall Find information from CIBSE Guide A (2006) Table A3.49. Wall is type 8(e) and the decrement factor is 0.42, time lag is 8.8 hours, U value 0.52 W/m2oC. If the maximum solar heat gain is at 12.30 pm and the time lag is 8.8 hours then the time of the relevant sol air temperature is; 12.50 - 8.8 = 3.7 say is at 4.00 am. teo = sol-air temperature when Tabulated cooling load (qsg) is at 04.00 hrs. CIBSE Guide J (2002) - Table 5.36, dark wall, South facing gives 10.4 oC. A correction can be applied to this since we are using outside air temperature (to) of 28oC. The tabulated maximum outside air temperature (to) from CIBSE Guide J (2002) - Table 5.36 page A6-127 (July 4th) ocurrs at 16.00 hrs. and is 25.40C.
The difference in outside temperatures is; 28 25.4 = 2.6 oC. The actual sol air temperature (teo) to use in this example is; 2.6 oC + 10.4 oC = 12.8 oC External wall Q+Wall = A U [( tem - tr) + f ( teo - tem)] Therefore the Solar Gain through a wall at time () is; Q A U tem tr f teo = = = = = = = = heat gain through wall at time (Watts) time lag in hours (see CIBSE guide A (2006) Table 3.49 to 3.55) for typical wall constructions. 2 area of wall facing South (m ) 2o overall thermal transmittance given in CIBSE guide A (2006) section 8(e) in Table 3.49 = 0.52 W/m C. 24 hour mean sol-air temperature (oC) CIBSE Guide J (2002) - Table 5.36 at 13.00 hrs, dark wall facing South 25.8oC constant dry resultant temperature (oC). Room dry bulb of 21oC is given. decrement factor for wall is given in CIBSE guide A (2006) section 8(e) in Table 3.49 = 0.42. sol-air temperature at time () (oC) from above is 12.8oC. Q Wall Q Wall Q Wall Q Wall Q Wall = = = = = A U [( tem - tr) + f ( teo - tem)] 28 x 0.52 [( 25.8 22) + 0.42 ( 12.8 25.8)] 14.56 [ 3.8 + - 5.5 ] - this - 5.5 is a heat loss since it happens so early in the morning and will be neglected. 14.56 [ 3.8 ] 55 Watts
(dark faade)
5.
Find decrement factor (f) from CIBSE Guide A (2006) Table 3.50, use information from section 2(d). The decrement factor is 0.88, time lag is 3.0 hours, U value 0.23 W/m2oC. If the maximum solar heat gain is at 12.30 pm and the time lag is 3.0 hours then the time of the relevant sol air temperature is;
Roof
is at 12.30 hrs - 3.0 = 9.30 hrs teo = sol-air temperature when Tabulated cooling load (qsg) is at 10.00 hrs. CIBSE Guide J (2002) - Table 5.36, dark wall, South facing gives 40.4 oC. A correction can be applied to this since we are using outside air temperature (to) of 28oC. The tabulated maximum outside air temperature (to) from CIBSE Guide J (2002) - Table 5.36 page A6-127 (July 4th) ocurrs at 16.00 hrs. and is 25.40C. The difference in outside temperatures is; 28 25.4 = 2.6 oC. The actual sol air temperature (teo) to use in this example is; 2.6 oC + 40.4 oC = 43 oC Q Roof Q Roof Q Roof Q Roof 6. Ventilation Qsi = = = = = = = A U [( tem - tr) + f ( teo - tem)] 161.7 x 0.23 [(25.8 22) + 0.88 (43 25.8 )] 37.19 [ ( 3.8 + 15.1 ) ] 703 Watts n V (to - tr) / 3 1.0 x 623 (28 22) / 3 1,246 Watts Qsg + Qint. + Q Wall + Q Roof + Qsi 703 + 1,246
Heat Gain from 1. Sensible transmission through glass 2. Solar gain through glass 3. Internal 4. External walls 5. Roof 6. Ventilation Total
Heat gain per m2 floor area = 125 W/m2 Heat gain per m3 space = 28 W/m3
In water coils, hot or chilled water or brine circulates through the tubes of the coil either emitting or absorbing sensible heat as the air flows over the fins attached to the outside surfaces. Usually the flow of water and air are in opposite directions to each other, this being known as counter-flow heat exchanger. This configuration gives maximum heat transfer.
Expansion valve.
Condenser
Air On
Latent heat is absorbed by the air stream from the refrigerant as the refrigerant evaporates. With this type of coil, as with steam, there is no distinction made between parallel and counter-flow since the surface temperature is more uniform owing to the refrigerant in the tubes boiling at a constant temperature. When direct expansion coils are used they become the evaporator of the refrigeration cycle, and may be termed either dry or flooded. In the dry DX coil only a sufficient quantity of refrigerant is introduced to operate in the predominantly vapour state. In the flooded DX coil most of the coil is filled with liquid refrigerant and although this is more efficient, it is not used so much in air-conditioning since the additional refrigerant is expensive.
Evaporator coils come in a variety of shapes and sizes, depending on the type of installation, the amount of cooling capacity needed, and the manufacturer. They are constructed of aluminium finned copper tubing. The copper tubing runs perpendicular to the aluminium fins, making U-turns back and forth until the desired coil size is achieved. Added cooling capacity without an increase in length and width is accomplished by adding more rows of copper tubing. All evaporator coils must have a drain pan to collect the water that condenses as the air flowing across the coil cools. The water can drain away by gravity or be pumped away. The cooling effect that takes place inside the coil requires a pressure drop in the refrigerant. This drop can be accomplished in a number of ways: capillary tube, piston or orifice, or thermostatic expansion valve. A capillary tube is a thin copper tube of predetermined length into which the compressed liquid refrigerant is pumped. The length of the tubing causes the pressure drop and subsequent cooling effect of the refrigerant. A piston or orifice blocks the flow of refrigerant and forces it through a tiny hole, creating the needed pressure drop. A thermostatic expansion valve meters the flow of refrigerant to meet the cooling demand of the coil. It determines this demand by way of a sensing bulb attached to the outlet tube on the coil. Because it can meter the flow to meet demand, the expansion valve can keep the coil at optimum cooling potential.
Because the cooling coil is an integral part of the air distribution system, its geometry size, number of rows, fin spacing, and fin profile contributes to the airside pressure drop and affects the sound power level of the fans. (Fan power needed to circulate air through the duct system may warrant extra sound attenuation at the air handler.)
Water Removal
Moisture in air can condense in the air stream or when the air impinges upon a solid cool surface. This can happen at sharp bends where water collects in a puddle at the lower surface on the ductwork. A drain can be fitted on vertical sections of ductwork to remove water that has collected. Ducts can also be insulated in areas where condensing moisture is likely to occur. In hospitals and other situations water in ducts is to be avoided since bacteria can multiply in warm moist conditions. Droplet separators have been developed to remove water droplet carry-over from cooling coils. They consist of a media that can absorb the water droplets and transport them down through the material to the drainage section. The system shown below uses a glass-fibre-based material and the droplet separator works best with air velocities between 0 and 4 m/s. The media is so efficient that it can arrest 100 litres of water per cubic metre of media. Some droplet separators are produced as cassettes to ensure easy handling. several cassettes can be linked together to achieve the desired surface area.
Increasing any one of these variables (heat-transfer coefficient, surface area, or log-mean temperature difference) results in more heat transfer. Arguably the most effective way to improve heat-transfer performance is to increase the log-mean temperature difference (LMTD). In the context of a chilled-water cooling coil, LMTD describes the difference between the temperatures of the air passing across the coil fins and the water flowing through the coil tubes: LMTD = (TD2 TD1) / ln (TD2 / TD1)
Where; TD1 = leaving-air and entering-water temperature difference at the coil (C) TD2 = entering-air and leaving-water temperature difference at the coil (C)
One way to increase LMTD is to supply the coil with colder water. Heat-transfer coefficient, Q = U A LMTD Also called U-value or thermal transmittance value, the heat-transfer coefficient describes the overall rate of heat flow through the coil. Three factors determine this rate:
Airside film coefficient describes the barrier (resistance to heat transfer) between the passing air stream and the fin surfaces Waterside film coefficient describes a similar barrier between the inside surfaces of the copper tubes and the circulating fluid
Thermal conductance describes the rate at which heat flows through the aluminium fins and copper tubes of the coil
System designers can do little to affect thermal conductance, but they can alter the film coefficients. Increasing the rate of airflow reduces heat-transfer resistance on the air side of the cooling coil. Likewise, increasing the water velocity reduces the waterside resistance to heat transfer. Fin geometry can improve the overall heat-transfer coefficient, too, by lessening the airside film coefficient. Like velocity, fin geometry can be specified as part of the design of the HVAC system. For comfort-cooling applications, coil fins are usually stamped into waveforms resembling corrugated cardboard. These waveforms create turbulence in the passing air stream, which lessens the resistance to heat transfer. More exaggerated waveforms produce more turbulence. Turbulent water flow, like turbulent airflow, also reduces resistance to heat transfer. And, like fin geometry, it can become an important criterion for coil selection. Waterside turbulence can be created by metal ribbons or helical wires inside the tubes. Called turbulators, these devices create eddies as the water flows across them. Both methods of improving the heat-transfer coefficient (increased velocity and turbulence) create higher pressure drops, which can mean additional fan or pump power. Coil surface area, Q = U A LMTD The third determinant of heat transfer is the coils surface area. Typically, fin spacing for comfort heating or cooling ranges from 24 to 50 fins per metre. Spacing the fins closer together multiplies the surface area by permitting more fins per linear unit. Although the airside pressure drop may increase, adding fins extends the available surface area without affecting the overall size of the coil. Adding rows of tubes also increases the heat-transfer surface area. Most coils are constructed with same-end connections, so rows are usually added in pairs. The weight and cost of the coil increase accordingly, but the airside pressure drop may not. (Wider fin spacing often accompanies the decision to add rows.) The best way to extend the surface area for heat transfer is to decrease the face velocity of the coil, that is, face area relative to airflow: Face velocity = airflow / face area Face velocity can be reduced in one of two ways: by increasing the size of the coil or (paradoxically) by reducing the required airflow. Selecting a physically larger coil increases the initial investment in the coil and the air handler, and may
also enlarge the air-handler footprint ... seldom desirable outcomes. So, how can we reduce the required airflow without sacrificing coil capacity?
The aim of this section of the notes is to allow students to size air conditioning plant such as; Cooling coil, heater battery and humidifier. The notes are divided into several sections as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. PSYCHROMETRY FOR AIR CONDITIONING THE PSYCHROMETRIC CHART EXAMPLES OF PSYCHROMETRIC PROPERTIES AIR CONDITIONING PLANT FOR SUMMER & WINTER BASIC PROCESSES TYPICAL AIR CONDITIONING PROCESSES ANNOTATION AND ROOM RATIO SUMMER AND WINTER CYCLES EXAMPLES
The first section deals with Psychrometry for air conditioning and discusses some properties of moist air. A simplified psychrometric chart is shown for familiarisation, and some examples of how to find air properties are provided. A diagram of an air conditioning system is shown in schematic form in the section entitled AIR CONDITIONING PLANT FOR SUMMER & WINTER. Before sizing takes place the student should also understand the processes that take place in air conditioning systems.
There are four basic processes for summer and winter air conditioning systems. The following basic processes are explained: 1. Mixing 2. Sensible Cooling and Heating 3. Cooling with Dehumidification 4. Humidification The section on Typical Air Conditioning Processes shows winter and summer schematic diagrams and psychrometric charts. There are some more details that may be useful to the designer of air conditioning systems. Further information is as follows: Annotation, Room ratio When the processes have been superimposed onto a psychrometric chart then calculations may commence. These are as detailed in the following sections of the notes. Summer and Winter Cycles 1. Summer cycle psychrometrics 2. Summer cycle calculations 3. Winter cycle psychrometrics 4. Winter cycle calculations 5. Duct and Fan gains. The final section is seven examples of plant sizing using psychrometric charts.
Air at any state point can be plotted on the psychrometric chart. The information that can be obtained from a Psychrometric Chart is as follows: 1. 2. 3. 4. Dry bulb temperature Wet bulb temperature Moisture content Percentage saturation
5. Specific enthalpy 6. Specific volume. The following is a brief description of each of the properties of air. 1. Dry bulb temperature This is the air temperature measured by a mercury-in-glass thermometer. 2. Wet bulb temperature This is the air temperature measured by a mercury-in-glass thermometer which has the mercury bulb wetted by gauze that is kept moist by a reservoir of water. When exposed to the environment the moisture evaporates from the wetted gauze, which gives a lower reading on the thermometer. This gives an indication of how dry or how moist the air is, since in dry air the water will evaporate quickly from the gauze, which depresses the thermometer reading. 3. Moisture content This is the amount of moisture in air given in kg of moisture per kg of dry air e.g. for room air at 21oC dry bulb and 15oC wet bulb, the moisture content is about 0.008 kg/kg d.a. This is a small mass of moisture (0.008 kg = 8 grams) per kg of dry air or 9.5 grams per cubic metre of air. 4. Percentage saturation The Percentage saturation is another indication of the amount of moisture in air. This is the ratio of the moisture content of moist air to the moisture content of saturated air at the same temperature. When air is saturated it is at 100% saturation and cannot hold any more moisture. 5. Specific enthalpy This is the amount of heat energy (kJ) in air per kg.
If heat is added to the air at a heater battery for example, then the amount to be added can be determined from Specific enthalpy change. 6. Specific volume This is the volume of moist air (dry air + water vapour) per unit mass. The units of measurement are m3 per kg. Also specific volume = 1 / density.
This chart is only for demonstration purposes. If accurate assessments are to be carried out use a C.I.B.S.E. chart. Using the Psychrometric Chart If any two properties of air are known then the other four can be found from the psychrometric chart.
EXAMPLE 2 Find the specific volume and wet-bulb temperature of air at 20oC drybulb temperature and 50% saturation.
Referring to the chart below, a vertical line is drawn upwards from 20oC dry-bulb temperature until it intersects with the 50% saturation curve. The intersection point is sometimes referred to as the state point. The specific volume is found to be 0.84 m3/kg and the wet-bulb temperature is 14oC
EXAMPLE 3 Find the specific volume, percentage saturation and moisture content of air at 15oC dry-bulb temperature and 10oC wet-bulb temperature. Referring to the chart below, a vertical line is drawn upwards from 15oC dry-bulb temperature until it intersects with the 10oC wet-bulb temperature line. This intersection is the state point. The specific volume is found to be 0.823 m3/kg, the percentage saturation 52% and the moisture content 0.0054 kg/kg d.a.
EXAMPLE 4 Find the specific volume, wet-bulb temperature, moisture content and specific enthalpy of air at 35oC dry-bulb temperature and 30% saturation. Referring to the chart below, a vertical line is drawn upwards from 35oC dry-bulb temperature until it intersects with the 30% saturation curve. This intersection is the state point. The specific volume is found to be 0.883 m3/kg, the wet-bulb temperature is 22oC, the moisture content 0.011kg/kg d.a. and the specific enthalpy 65 kJ/kg.
m1 + m 2 = m 3 m1 h1 + m2 h2 = m3 h3
Where: m = mass flow rate of air (kg/s) h = specific enthalpy of air (kJ/kg) found from psychrometric chart.
For sensible heating: The amount of heating input to the air approximates to; H1-2 = m x Cp x (t2 - t1) Or more accurately from psychrometric chart: H1-2 = m x (h2 - h1) For sensible cooling: The amount of cooling input to the air approximates to; H2-1 = m x Cp x (t2 - t1) Or more accurately from psychrometric chart: H2-1 = m x (h2 - h1)
Where: H = Heat or cooling energy (kW) m = mass flow rate of air (kg/s) Cp = Specific heat capacity of air, may be taken as 1.01 kJ/kg degC. t = Dry bulb temperature of air (oC) h = specific enthalpy of air (kJ/kg) found from psychrometric chart.
In the absence of a suitable psychrometric chart the following formula may be used; The sensible heat removed is: The latent heat removed is: H1-2 = m x Cp x (t1 - t2) H2-3 = m x hfg x (g2 - g3)
Where: H = Cooling energy (kW) m = mass flow rate of air (kg/s) Cp = Specific heat capacity of air, may be taken as 1.01 kJ/kg degC. t = Dry bulb temperature of air (oC) hfg = latent heat of evaporisation, may be taken as 2454 kJ/kg @20oC. g = moisture content of air from psychrometric chart (kg/kg dry air)
One air stream is cooled down to the ADP and the other air stream by-passes the coil surfaces to give an off-coil air temperature (mixed air stream) a little higher than the ADP. This may be looked upon as an inefficiency of the coil and is usually given as the cooling coil contact factor. The process is shown on the psychrometric chart below.
The steam package unit is situated close to the air duct and is sized to meet the maximum requirements; this is usually in winter in the U.K. A steam pipe (sometimes hoses are used) passes from the packaged unit to the air duct and steam at 100oC is injected into the air stream via. a sparge pipe. The un-used steam is drained from the system via a condensate tundish and drain. It is important to layout the steam pipework so that any condensate will drain back to the unit. The psychrometric process is shown below.
See summer and Winter Cycles section for calculation of amount of moisture added at humidifier.
The schematic diagram below shows a typical plant system for winter air conditioning.
Annotation
The state points on a psychrometric chart may be given numbers or symbols to identify them. If symbols are used the following system may be adopted:
Room Ratio
This is the ratio of sensible to total heat in the room for summer or winter. The total heat gain (summer) or loss (winter) will be determined by adding the Latent and Sensible heat in a room or rooms, i.e. (SUMMER) Total heat gain (WINTER) Total heat = Sensible heat loss + Latent heat gain = Sensible heat gain + Latent heat gain
The room ratio is used on a psychrometric chart to determine the supply air state point. A room ratio line is superimposed from the protractor on the psychrometric chart onto the main body of the chart by a line passing through the room state point R.
An example calculation is as follows: Sensible heat gain Latent heat gain Total heat gain Room ratio Room ratio = = = = = 9.0 kW 2.25 kW 9.0 kW + 2.25 kW= Sensible / Total heat 9 / 11.25 = 0.8 11.25 kW.
The supply air state point must also be somewhere on this room ratio line to meet the room heat gain requirements i.e. the room ratio line always passes through points R and S.
Note: The cooling coil output of 38.2 kW is a much higher value than the sensible heat gain of 10.8 kW. It should be remembered that the difference is these two values is mostly from the fresh air cooling load. It takes quite a lot of energy in summer to cool fresh air coming into air handling units. This can be minimised by bringing in minimum fresh air but not too little otherwise the building will suffer from lack of oxygen and feel stuffy. Sometimes mistakes are made when sizing cooling apparatus. If a cooling coil or indoor cooling unit is sized on the sensible heat gain only without allowing for fresh air load then it will be grossly undersized. That is why psychrometric charts are required to calculate cooling coil output including fresh air loads. So, dont size cooling coil and indoor cooling units on sensible heat gain only if there is fresh air coming into the plant? Size these items of plant using a psychrometric chart.
6. Find the mix point M by measuring the length of the line O-R and multiply this by the mixing ratio. On a full size CIBSE psychrometric chart these measures 110mm. The ratio of recirculated air is 0. 110mm x 0.8 = 88mm Therefore;
Measure up the O-R line from point O by 88mm. This determines point M. If there is more recirculated air than outside air at the mix point, then point M will be closer to point R than point O. 7. Find the room ratio.
This is the sensible to total heat ratio. Neglect signs i.e. the total heat for the room will be Sensible loss plus Latent gain. Total heat = 18 kW sensible + 4.5 kW latent = 22.5 kW total. Heat ratio = 18 / 22.5 = 0.8
Plot this ratio on the protractor, top segment, on the psychrometric chart and transfer this line onto the chart so that it passes through point R.
8. Find the supply air dry bulb temperature by calculation. 9. Plot the supply air condition S on the room ratio line. This is on a horizontal line from point M to the right hand side of the chart, and intersects with the RRL.
C.
..............therefore:
Hheater battery = ma (hS - hM) Hheater battery = 1.55 (50 - 34) Hheater battery = 24.8 kW Therefore the heater battery load is 24.8 kW.
5.
Find the mix point M by measuring the length of the line O-R and multiply this by the mixing ratio. On a full size CIBSE psychrometric chart these measures 85mm. The ratio of recirculated air is 0.8. .. Therefore; 85mm x 0.8 = 68mm Measure down the O-R line from point O by 68mm. This determines point M.
Find the room ratio. This is the sensible to total heat gain ratio. Total heat = 8 kW sensible + 2 kW latent = 10 kW total. Heat ratio = 8 / 10 = 0.8 Plot this ratio on the protractor, bottom segment, on the psychrometric chart and transfer this line onto the chart so that it passes through point R. 7. Plot the Apparatus Dew Point ADP of the cooling coil. This is on the 100% saturation curve. The ADP is 80C.
6.
8. 9.
Join points M and ADP. Find the off-coil condition W by measuring the length of the line M-ADP and multiply this by the cooling coil contact factor.. On a full size CIBSE psychrometric chart these measures 75mm. The cooling coil contact factor is 0.8. .. Therefore; 75mm x 0.8 = 60mm. Measure down along the line M-ADP by 60mm. This determines point W.
Plot the supply air condition S. The reheater process will be a horizontal line from point W to point S. Point S is on the room ratio line. The supply air temperature is 17oC.
10.
Hs / ( Cp ( tr - ts ) )
Sensible heat gain to room (kW) mass flow rate of air (kg/s) Specific heat capacity of humid air (approx.1.01 kJ/kg degC) room temperature (oC) supply air temperature (oC)
ma ( hM - hADP)
Cooling coil output (kW) mass flow rate of air (kg/s) specific enthalpy at condition M (kJ/kg) determined from psychrometric chart. specific enthalpy at condition ADP (kJ/kg) determined from psychrometric chart
The specific enthalpies at points M and ADP are shown on the psychrometric Chart below. H cooling coil H cooling coil = = 1.584 ( 50.5 - 25) 40.4 kW
ma ( hS - hW)
Heater battery output (kW) mass flow rate of air (kg/s) specific enthalpy at condition S (kJ/kg) determined from psychrometric chart. specific enthalpy at condition W (kJ/kg) determined from psychrometric chart.
The specific enthalpies at points S and W are shown on the psychrometric Chart below.
Example 4.
A conference room is to be maintained at 21oC dry-bulb temperature, 50% saturation in winter. The sensible heat loss for the room is 17.0 kW. The latent heat gain is 40 Watts per person (see Air Conditioning section). Determine the Preheater and reheater outputs required and the amount of moisture to be added at the humidifier in litre/hour, by using a psychrometric chart if the plant schematic is as shown below.
DATA:
Outdoor condition is -2oC, 80% saturation. The outdoor air and recirculated air ratio is 50%/50%. Maximum occupancy is 250 people. The Preheater off coil temperature is 5oC. Supply air quantity is 8 air changes per hour. 3 Room volume is 20 x 12 x 4m high = 960 m .
Supply air mass flow rate (kg/s) = Supply air quantity (m3/s) / Specific Volume (m3/kg) Supply air mass flow rate (kg/s) = 2.13 (m3/s) / 0.87 (m3/kg) Supply air mass flow rate (kg/s) = 2.45 kg/s The fresh air flow rate (kg/s) = 2.45 kg/s x 50% = 1.23 kg/s
4.
Find the mix point M by measuring the length of the line P-R and multiply this by the mixing ratio. The line measures 82mm long. 82 x 0.5 = 41 mm 6. Find the room ratio. Plot this ratio on the protractor, so that it passes through point R. Total heat is 17 kW sensible + 10 kW latent = 27kW. Ratio is 17/27 = 0.63.
5.
7.
This is found by calculation because we have already calculated the mass flow rate of supply air from information given in the question.
Hs
Where: Hs = ma = Cp = tr = ts =
ma x Cp ( ts - tr )
Sensible heat loss from room (kW) mass flow rate of air (kg/s) Specific heat capacity of humid air (approx.1.01 kJ/kg degC) room temperature (oC) supply air temperature (oC)
( ts - tr ) ( ts - tr ) ( ts - tr ) ( ts - 21) ts ts 8. 9.
= = = = = =
Hs / ma x Cp 17 / 2.45 x 1.01 6.87 deg.C 6.87 deg.C 21 + 6.87 deg.C 27.87 oC say 28 oC.
Plot the supply air condition S on the room ratio line. Plot condition H on the psychrometric chart.
This is vertically down from point S, and horizontally across from point M. This is because M-H is the reheater process and thus a horizontal line and H-S is the humidification process and is close to a vertical line if steam is used.
Humidifier Output
The amount of moisture added to the air may be calculated from the following formula:
m moisture added = 2.45 (0.0064 - 0.0054) m moisture added = 2.45 (0.001) m moisture added = 0.00245 kg/s 1 litre of water weights 1 kg, therefore; m moisture added = 0.00245 litre/s m moisture added = 0.00245 litre/s x 3600 = 8.82 litres/hour
Example 5
A Lecture Theatre measures 15 m x 10 m x 6 m high. It is to be air conditioned in summer so that the room is maintained at 22oC dry-bulb temperature, 50% saturation. Determine the cooling coil and reheater outputs required by using a psychrometric chart if the plant schematic is as shown below. DATA:
Outdoor condition The Apparatus Dew Point ADP The latent heat gain The sensible heat gain Maximum occupancy is 28oC, 80% saturation. is 7.5oC. is 10.0 kW. is 12.0 kW. is 200 people.
The cooling coil contact factor is unknown at present and should be calculated. Use CIBSE guide B2 (2001) to determine air flow rates and calculate the mass flow rate of fresh air and supply air to the room. The lecture room may be taken as an Assembly hall. The room is a non-smoking area.
= =
The specific volume at the outside condition may be determined from a psychrometric chart. It is 0.88 m3/kg. Mass flow rate = Volume flow rate / specific volume Mass flow rate (Fresh Air) = 1.6 / 0.88 =
Supply Air Flow Rate
1.82 kg/s .
If the maximum ventilation supply air rate is taken from Table 3.6 to be 10.0 air changes per hour, then the mass flow rate can be calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate (ac/h) Volume of room (m3) = 15 x 10 x 6 = 900 m3 3 3 Volume flow rate (m /h) = 900 (m ) x 10 (ac/h) Volume flow rate (m3/h) = 9000 m3/h 3 Volume flow rate (m /s) = 9000 / 3600 = 2.5 m3/s.
Mass flow rate = Volume flow rate / specific volume The specific volume at the supply condition may be approximated at this stage from a psychrometric chart. It is 0.834 m3/kg. Mass flow rate (Supply Air) = 2.5 / 0.834 = 3.0 kg/s.
The ratio by mass is therefore; Fresh air rate Supply air rate Recirculation air rate = = = 1.82 kg/s 3.00 kg/s 3.00 - 1.82 = 1.18 kg/s
The ratio of fresh air to total supply air is; 1.82 / 3.00 = 0.6, i.e. 60% fresh air and therefore 40% recirculated air. It is not unusual to have a high percentage of fresh air in a high occupancy room such as a Lecture theatre. The air flows are shown on the schematic diagram below.
Hs
ma x Cp ( tr - ts )
Where: Hs = = ma Cp = tr = ts =
Sensible heat gain to room (kW) mass flow rate of air (kg/s) Specific heat capacity of humid air (approx.1.01 kJ/kg degC) room temperature (oC) supply air temperature (oC)
1. Points O, M and R can be shown on the chart. 2. Point ADP can be indicated and lines drawn between these points as shown.
3. The room ratio line can be drawn. 4. Point S is then shown on the chart, on the room ratio line at 18oC. 5. A horizontal line is then drawn from point S towards the line O ADP. 6. Point W can then be found where the horizontal line W - S intersects the line O - ADP. From the psychrometric chart point W is at approximately 9 dry bulb. The heat ratio is 12 kW sensible / 22 kW total = 0.545.
o
H cooling coil =
ma (hM - hADP)
Where: H cooling coil ma hM hADP = = = = Cooling coil output (kW) mass flow rate of air (kg/s) specific enthalpy at condition M (kJ/kg) determined From psychrometric chart. specific enthalpy at condition ADP (kJ/kg) Determined from psychrometric chart
The specific enthalpies at points psychrometric Chart above. H cooling coil = H cooling coil =
H heater battery
Where: H heater battery = = ma hS = hW =
ma ( hS - hW)
Heater battery output (kW) mass flow rate of air (kg/s) specific enthalpy at condition S (kJ/kg) determined from psychrometric chart. specific enthalpy at condition W (kJ/kg) determined from psychrometric chart.
The specific enthalpies at points psychrometric Chart above. H heater battery = H heater battery =
DATA:
1. Indoor condition all year 2. Outdoor condition summer 3. Outdoor condition winter 4. Maximum occupancy 5. ADP of the cooling coil 6. Fresh air requirement 7. Supply air rate 8. Frost off coil temperature 22oC dB temperature, 50% saturation. 28oC dB temperature, 80% saturation. 3oC dB temperature, 80% saturation. 1000 people. 8 oC 12 l/s/person 8 air changes per hour. 7oC.
9. Latent heat gain 10. Sensible heat gain in summer 11. Sensible heat loss in winter
40 W/person 100 W/person + 20.5 kW fabrics, lights, solar & ventilation gains. 20 W/m3 air volume (estimated)
Fresh air rate = 12 l/s/p x 1000 people = 12,000 l/s = 12.0 m3/s The specific volume at the outside condition may be determined from a psychrometric chart. It is approximately 0.88 m3/kg Mass flow rate = Volume flow rate / specific volume = 13.64 kg/s. Mass flow rate (Fresh Air) = 12.0 / 0.88 Supply Air Flow Rate
The ventilation supply air rate is taken from table B2.3 and is given as 8 air changes per hour; the mass flow rate can be calculated. Volume flow rate (m3/h) Volume of room (m3) Volume flow rate (m3/h) Volume flow rate (m3/h) Volume flow rate (m3/s) Mass flow rate = = = = = Volume of room (m3) x air change rate (ac/h) = 40 x 20 x 8 = 6400 m3 6400 (m3) x 8 (ac/h) 51,200 m3/h 51,200 / 3600 = 14.22 m3/s. Volume flow rate / specific volume
The specific volume at the supply condition may be approximated at this stage from a psychrometric chart. It can be taken as 0.834 m3/kg. 14.22 / 0.834 = 17.05 kg/s. Mass flow rate (Supply Air) =
Recirculation Air Flow Rate Recirculation air rate Recirculation air rate = = Supply air rate - fresh air rate 17.05 - 13.64 = 3.41 kg/s
Fresh Air and Recirc. Ratio. The ratio by mass is therefore; Fresh air rate = 13.64 kg/s Supply air rate = 17.05 kg/s The ratio of fresh air to total supply air is; 13.64 / 17.05 = 0.8, i.e. 80% fresh air and therefore 20% recirculated air.
It is not unusual to have a high percentage of fresh air in a high occupancy room such as a Concert Hall. The air flows are shown on the schematic diagram below.
120.5 / 160.5
0.75
ma x Cp ( tr - ts )
Sensible heat gain to room (kW) mass flow rate of air (kg/s) Specific heat capacity of humid air (approx.1.01 kJ/kg degC) room temperature (oC) supply air temperature (oC)
Rearranging the above formula gives: ( tr - ts ) = Hs / ( ma x Cp ) ( tr - ts ) = 120.5 / (17.05 x 1.01) ( tr - ts ) = 7.0 deg.C, since tr = 22oC ts = 22 - 7.0 = 15.0 oC 15 oC ts = The processes can now be plotted on a psychrometric chart as shown below. 1. Points O, M and R can be shown on the chart. 2. Point ADP can be indicated and lines drawn between these points as shown. 3. The room ratio line can be drawn. 4. Point S is then shown on the chart, on the room ratio line at 18oC. 5. A horizontal line is then drawn from point S towards the line O ADP. 6. Point W can then be found where the horizontal line W - S intersects the line O - ADP.
Cooling Coil Contact Factor On a full size psychrometric chart the length of the line from point M to point ADP is 116mm. The distance from point M to point W is 107mm. The cooling coil contact factor is therefore:
Cooling Coil Output in Summer The cooling coil output is as follows: H cooling coil =
Where: H cooling coil ma hM hADP = = = =
ma ( hM - hADP)
Cooling coil output (kW) mass flow rate of air (kg/s) specific enthalpy at condition M (kJ/kg) determined from psychrometric chart. specific enthalpy at condition ADP (kJ/kg) determined from psychrometric chart
The specific enthalpies at points psychrometric Chart above. H cooling coil = H cooling coil =
NOTE: The cooling coil output is very high and a lot of energy would be required to provide this amount of cooling. The cooling coil load would probably be spread over several air handling units but it could be examined with a view to some reduction. The coil output is high because the mass flow rate of supply air is high (17.05 kg/s ) and the proportion of fresh air is also high ( 80%). The mix point M is at approximately 27 oC dry-bulb so there is little advantage in recirculation in this instance. It would be advantageous to consider the supply airflow rate to see if a lower rate would be acceptable for this building. If 6 air changes per hour are used as the ventilation rate then this would reduce the mass flow rate of supply air. Also the engineer may consider other methods of air-conditioning a hall with a large volume such as using partial radiant cooling where surfaces are cooled rather than air.
Reheater Battery Output in Summer The heater battery or reheater output is as follows: H heater battery = ma ( hS - hW)
Where: H heater battery = Heater battery output (kW) ma = mass flow rate of air (kg/s) hS = specific enthalpy at condition S (kJ/kg) determined from psychrometric chart. = specific enthalpy at condition W (kJ/kg) determined from psychrometric hW chart.
The specific enthalpies at points psychrometric Chart above. H heater battery = H heater battery =
4. 5.
Supply Air Temperature by Calculation The temperature of supply air is calculated from the following formula: Hs
Where: Hs = ma = Cp =
ma x Cp ( ts - tr )
Sensible heat loss from room (kW) mass flow rate of air (kg/s) same as summer rate for constant volume Systems. Specific heat capacity of humid air (approx.1.01 kJ/kg degC) tr = room temperature (oC) ts = supply air temperature(oC)
( ts - tr ) ( ts - tr ) ( ts - tr ) ts ts
= = = = =
Hs / ma x Cp 128 / 17.05 x 1.01 7.43 deg.C 22 + 7.43 deg.C 29.43 oC say 29.5 oC.
6. Plot the condition H at 29.5oC dB. on a horizontal line from M. 7. Plot condition S on a vertical line from H on the RRL. Assume the humidity process is vertical.
Preheater Battery Output (or frost coil) The Preheater battery output is as follows: H preheater battery = maf ( hP - hO)
Where: H preheater battery = Preheater battery output (kW) maf = mass flow rate of fresh air (kg/s) hP = specific enthalpy at condition P (kJ/kg) hO = specific enthalpy at condition O (kJ/kg)
= =
13.64 ( 13 - 3) 136.4 kW
Reheater Battery Output in Winter The reheater battery output is as follows: H reheater battery
Where: H reheater battery ma hH hM = = = = Reheater battery output (kW) mass flow rate of supply air (kg/s) specific enthalpy at condition H (kJ/kg) specific enthalpy at condition M (kJ/kg)
ma ( hH - hM)
= =
The heater battery load may be reduced by using other forms of heating for some of the load, e.g. perimeter convectors or radiators. Humidifier Output in Winter The amount of moisture added to the air may be calculated from the following formula: m moisture added
Where: m moisture added ma msS msH = = = = The amount of moisture or added or steam flow rate (kg/s) mass flow rate of air (kg/s) moisture content at condition S (kg/kg d.a.) moisture content at condition H (kg/kg d.a.)
ma (msS - msH)
m moisture added m moisture added m moisture added m moisture added m moisture added
= = = = =
17.05 (0.0074 - 0.0035) 17.05 (0.0039) 0.0665 kg/s 0.0665 litre/s 0.0665 litre/s x 3600 =
239.4 litres/hour
Example 7 gains
A Computer Suite Theatre measures 24 m x 10 m x 3.5 m high. It is to be air conditioned in summer so that the room is maintained at 22oC dry-bulb temperature, 50% saturation. Determine the cooling coil and reheater outputs required. The air conditioning system is shown schematically below.
DATA:
Outdoor condition The Apparatus Dew Point ADP The internal latent heat gain The internal sensible heat gain is 27oC, 80% saturation. is 8oC is 40 W per person, plus additional Gain of 5 kW. is 200 Watts per computer, 100W Per person and 15 W/m2 floor area For lights. is 6.0 kW is 80 people. is 80. is 0.8. are 2oC. is 20%/80%.
The solar gain through windows Maximum occupancy Number of computers The cooling coil contact factor Duct and fans gains Fresh air, recirculated air ratio
HEAT GAINS
Sensible (200 x 80) + (100 x 80) + (15 x 24 x 10) = 27,600 Watts = 27.6 kW + solar gain 5.0 kW = 32.6 kW
= 3200 Watts = =
Hs / ( Cp ( tr - ts ) )
C.
The processes can now be plotted on a psychrometric chart as shown below. o From the psychrometric chart point W is at approximately 11 C dry bulb. Point D is 11 oC + 2oC (duct and fan gains given in Data) = 13 oC
H cooling coil =
Where: Hcooling coil ma hM hADP = = = =
ma ( hM - hADP)
Cooling coil output (kW) mass flow rate of air (kg/s) specific enthalpy at condition M (kJ/kg) determined from psychrometric chart. specific enthalpy at condition ADP (kJ/kg) determined from psychrometric chart
The specific enthalpies at points psychrometric Chart above. H cooling coil = H cooling coil =
The specific enthalpies at points psychrometric Chart above. H heater battery = H heater battery =