100% Stator Ground Protection (64G Element) Setting Spreadsheet (SEL-300G and SEL-700G Relays)

Introduction:
This spreadsheet is designed to aid in calculating the settings 64RAT, 64G2P, and 64G1P when four-wire potentials are used (DELTA_Y = Y). Refer to approriate Relay Instruction Manual (SEL-300G or SEL-700G) for other settings or when delta potentials are used.

How to Use the Spreadsheet:


1. Select Worksheet Gen. 1. 2. Select cell B1 and change default Station name (e.g. same as TID setting of the Relay). This step will reset the sheet by automatically deleting all default data. 3. Press Tab key to select cell I1 and enter Rated MW of the generator. 4. Press Tab key again to select cell M1 and enter Rated Phase-Phase kV. 5. Continue the process until you have entered appropriate VP3 and VN3 values in all available cells. A. Select 300G or 700G in the cell C3. Enter all VP3 & VN3 values in same unit (secondary or primary volts) as used in Meter Report of the selected relay. B. VP3 and VN3 values are required at no-load and full-load (yellow background cells D7, E7, D17, and E17). C. VP3 & VN3 values at up to nine additional loads can be entered. The additional measurements are highly recommended for added security. D. Values entered for PF and Lag/Lead are for record purpose only, they are not used in the calculations. E. The MW, VP3, and VN3 are used in the calculations, if entered they must be entered in group of three in any of the Rows 8 - 16. 6. Cells E21-E23 and F21-F23 show calculated settings based on the stated criteria and the data entered. It is possible that the entered data may not include the worst case therefore the Item 7 below is extra important. 7. Please review the Element Coverage's, overlap achieved, and notes displayed on the worksheet. You must change/accept the Actual settings (cells F21-F23) only after the review and also evaluation of any potential "what if" scenarios. 8. For additional Generators Copy the worksheet Gen. 1 with desired name (e.g. Gen. 2) and repeat the above steps.

Disclaimer:
This program is provided at no cost to SEL customers.
NO EXPRESS OR IMPLIED WARRANTIES (INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE) APPLY FOR THIS PROGRAM. SEL Customers are entirely responsible for their use of and reliance on this program and any data contained therein, including without limitation any algorithms.

192376730.xls.ms_office

Page 1 of 4

100% Stator Ground Protection (64G Element) Setting Spreadsheet (SEL-300G and SEL-700G Relays)

ting all default data.

elected relay.

gs

OR THIS PROGRAM. n any algorithms.

192376730.xls.ms_office

Page 2 of 4

SEL-300G / SEL-700G Relay 100% Stator Ground Protection Function Setting Worksheet
Station: XYZ Power Station Gen.: No. 1 Relay: SEL- 300G 3rd Harmonic Voltage Measurements Load PF Lag/Ld VP3 VN3 MW V sec. V sec. 0.00 --2.662 7.690 Rated MW: 725.00 Phase PT Ratio to 1 (PTR): 200.00 Machine Rated f-f kV: 24.00 Neut. PT Ratio to 1 (PTRN): 60.00

64G Element Coverage at No Load Dif. Volt. Lo Wndg MinCovRow Coverage when Element-Overlap is minimum V sec. Cov. Index 3.33333 100% 0.030 45.9% 1 Lower Upper Element Dead Element 90% Coverage Band Coverage 0.000 100.0% 0 80% 0.0% 0.000 100.0% 0 64G1 5.0% 95.0% 70% 0.000 100.0% 0 64G2 45.9% 1.2% 52.9% 60% 0.000 100.0% 0 50% 0.000 100.0% 0 40% 0.000 100.0% 0 30% 0.000 100.0% 0 20% 0.000 100.0% 0 10% 0% 0.000 100.0% 0 64G1 64G2 725.00 5.080 14.710 0.022 46.2% 0 Element 0 Element Coverage Calculated Actual 0 Setting Criteria Dead Band Settings Settings 45.9% 64RAT = 2.89 2.9 2.9 64G2P, Greater than 0.14 0.2 0.2 Notes: Minimum Element-Overlap Achieved = 40.9% 64G1P, less than or = (Typical) 11.55 11.5 11.5 100% stator winding coverage achieved. Worst case Element Boundaries (from neutral) Consider higher 64G2P for improved security. 64G2, Minimum Low-Winding Coverage 45.9% <--- Indicates optional fields. 64G1, Low-Winding Dead Band 5.0% <--- Indicates required fields 64G2, Upper-Coverage Boundary 47.1%
Stator Winding from Neutral

2.662 0 0 0 0 0 0 0 0 0 5.08 0

192376730.xls.ms_office

Page 3 of 4

SEL-300G / SEL-700G Relay 100% Stator Ground Protection Function Setting Worksheet

7.69 0 0 0 0 0 0 0 0 0 14.71

192376730.xls.ms_office

Page 4 of 4