Introduction:
This spreadsheet is designed to aid in calculating the settings 64RAT, 64G2P, and 64G1P when four-wire potentials are used (DELTA_Y = Y). Refer to approriate Relay Instruction Manual (SEL-300G or SEL-700G) for other settings or when delta potentials are used.
Disclaimer:
This program is provided at no cost to SEL customers.
NO EXPRESS OR IMPLIED WARRANTIES (INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE) APPLY FOR THIS PROGRAM. SEL Customers are entirely responsible for their use of and reliance on this program and any data contained therein, including without limitation any algorithms.
192376730.xls.ms_office
Page 1 of 4
100% Stator Ground Protection (64G Element) Setting Spreadsheet (SEL-300G and SEL-700G Relays)
elected relay.
gs
192376730.xls.ms_office
Page 2 of 4
SEL-300G / SEL-700G Relay 100% Stator Ground Protection Function Setting Worksheet
Station: XYZ Power Station Gen.: No. 1 Relay: SEL- 300G 3rd Harmonic Voltage Measurements Load PF Lag/Ld VP3 VN3 MW V sec. V sec. 0.00 --2.662 7.690 Rated MW: 725.00 Phase PT Ratio to 1 (PTR): 200.00 Machine Rated f-f kV: 24.00 Neut. PT Ratio to 1 (PTRN): 60.00
64G Element Coverage at No Load Dif. Volt. Lo Wndg MinCovRow Coverage when Element-Overlap is minimum V sec. Cov. Index 3.33333 100% 0.030 45.9% 1 Lower Upper Element Dead Element 90% Coverage Band Coverage 0.000 100.0% 0 80% 0.0% 0.000 100.0% 0 64G1 5.0% 95.0% 70% 0.000 100.0% 0 64G2 45.9% 1.2% 52.9% 60% 0.000 100.0% 0 50% 0.000 100.0% 0 40% 0.000 100.0% 0 30% 0.000 100.0% 0 20% 0.000 100.0% 0 10% 0% 0.000 100.0% 0 64G1 64G2 725.00 5.080 14.710 0.022 46.2% 0 Element 0 Element Coverage Calculated Actual 0 Setting Criteria Dead Band Settings Settings 45.9% 64RAT = 2.89 2.9 2.9 64G2P, Greater than 0.14 0.2 0.2 Notes: Minimum Element-Overlap Achieved = 40.9% 64G1P, less than or = (Typical) 11.55 11.5 11.5 100% stator winding coverage achieved. Worst case Element Boundaries (from neutral) Consider higher 64G2P for improved security. 64G2, Minimum Low-Winding Coverage 45.9% <--- Indicates optional fields. 64G1, Low-Winding Dead Band 5.0% <--- Indicates required fields 64G2, Upper-Coverage Boundary 47.1%
Stator Winding from Neutral
2.662 0 0 0 0 0 0 0 0 0 5.08 0
192376730.xls.ms_office
Page 3 of 4
SEL-300G / SEL-700G Relay 100% Stator Ground Protection Function Setting Worksheet
7.69 0 0 0 0 0 0 0 0 0 14.71
192376730.xls.ms_office
Page 4 of 4