BM POWER SUPPLY & ELECTRICAL SERVICES

Customer Location

: JMY ENGINEERING : IM DIGITAL INC. (FPIP Sto. Tomas, Batangas)

Date: Nov. 30,2013

Transformer Specifications
Capacity Phase Frequency Cooling Class High Voltage Low Voltage Vector Diagram HV Tap Position Impedance Temperature Rise Insulating Liquid Brand Serial Number Year Manufactured 1500KVA Three (3) 60 Hz ONAN 460V 380V Dyn Not applicable 5.91% 60C Mineral oil Shinsoeng Industrial Co., Ltd. 11844 2011.10

Certified Test Results 1. Insulation Resistance and Dielectric Adsorption/Polarization Index of Windings (Megger Test):
Test Voltage DC (in KV) 1 1 1 Five-Minutes (in GIgaohms) 24.5 29.8 22.1

Primary to Ground Secondary to Ground Primary to Secondary


Note:

1. The minimum Insulation Resistance two (2) Megaohms/KV or 100 Megaohms for 0 to 600V; 1000 Megaohms for 601-5000V; and 5000 Megaohms for greater than 5000V.

Remarks: PASSED Test Instrument: MEGGER, MIT520/2 2. Transformer Insulating Oil Dielectric Breakdown Voltage (DBV) test: Trials 1 2 3 4 5 Average
Note:

41.9 39.0 30.1 30.0 32.2 34.6

As Found DBV KV KV KV KV KV KV

The average Dielectric Breakdown Voltage of transformer insulating oil should be 26KV or higher to be considered Satisfactorily Good.

Remarks: PASSED Test Instrument: HIPOTRONICS, DIGITAL OIL TESTER

BM POWER SUPPLY & ELECTRICAL SERVICES


Tel# 563-2946 / 563-2957 / 561-0544 Fax# 563-2969 / 562-4421 Email Address: bmpowermain@yahoo.com

Secondary Voltage

3.

Transformer Turns Ratio (TTR) Test:

(per phase) 220

Tap 1
Note:

Primary Voltage (per phase) 460

Computed ratio 2.091

U,V/O,U 2.075

As found Ratio V,W/O,V W,U/O,W 2.075 2.075

As found ratio must not exceed 0.5% of computed ratio

Remarks: PASSED Test Instrument: MEGGER, TTR

4.

Winding Resistance Test:


Tap As Found Resistance Test Test Current 1A U,W U,V W,V 0.002m 0.002m 0.003m Secondary Side O,U O,V O,W 0.002m 0.002m 0.003m

Note:

Data obtained to be compare for each phases must at least approximately balanced.

Remarks: PASSED Test Instrument: BIDDLE, DLRO

5.

Excitation Current Test (No Load Test):


As Found Excitation Current @ HIGH SIDE Test Voltage U,V U,W V,W 491 4.22 5.08 3.97

Note:

1. Excitation current, test data pattern for three phase transformer is two (2) similar readings and one (1) lower reading; 2. Excitation current at rated voltage of transformer should not exceed 3% of full load current

Remarks: PASSED Test Instrument: NANOVIP (ammeter,voltmeter,wattmeter)

6. Evaluation and Recommendation: All tests conducted on transformer with the above specifics satisfactorily passed and/or meet the standards for maintained liquid filled transformers (ANSI/NETA-MTS2011) thus transformer is ready for energization.

Tested By:

Checked by:

ERWIN GARCIA

CHRISTIAN AARON AZCUETA

BM POWER SUPPLY & ELECTRICAL SERVICES


Tel# 563-2946 / 563-2957 / 561-0544 Fax# 563-2969 / 562-4421 Email Address: bmpowermain@yahoo.com