The voltage on remaining units in one series section with "F" units removed. %Vr =
(3)
http://www.gilbertelectricalsystems.com/library/technical_papers/technical_discussions/TD-003/TD-003.php[09.01.2013 14:18:32]
Gilbert Electrical Systems - Technical Discussions - Capacitor Bank Grounded Wye Unbalance Detection Discussion
Neutral current when one complete series section is shorted %In (of rated phase current) =
(4)
LEGEND
I N = I U = V T = V = V R= S = N = F = Neutral Current Rated current of one units Applied lineto-neutral volts Rated voltage of capacitor units Voltage on remaining units in a group with "F" units removed. Number of series sections per phase Number of parallel units per series section Number of units removed from one section
METAL ENCLOSED CAPACITOR GROUNDED WYE APPLICATIONS It is rare that more than one series group is used in metal enclosed applications. If we make that assumption we can simplify the above formulas. Looking a balance load (See Figure 2) with two capacitors per phase, we have the following:
http://www.gilbertelectricalsystems.com/library/technical_papers/technical_discussions/TD-003/TD-003.php[09.01.2013 14:18:32]
Gilbert Electrical Systems - Technical Discussions - Capacitor Bank Grounded Wye Unbalance Detection Discussion
For 2 units in parallel will equal C 1 +C2 =0.00530519 farads =2vars Or Z T = This gives us = 2 amps or, = = = 2amps =
Each leg in a balanced grounded wye capacitor bank as configured above will be 2 amps, and will be zero amps at the ground node point Looking at an unbalance load (See Figure 3)using the same parameters as the balance load given above we have the following:
= 1amp This means the current neutral to ground will be 1 amp and this will flow as unbalance current in the neutral. Looking back at the formula for neutral current formula (1) we had
I U = 1 amp Let V T = V
http://www.gilbertelectricalsystems.com/library/technical_papers/technical_discussions/TD-003/TD-003.php[09.01.2013 14:18:32]
Gilbert Electrical Systems - Technical Discussions - Capacitor Bank Grounded Wye Unbalance Detection Discussion
N=2 S =1 F=1 This gives us 1 amp in the neutral, which confirms our numbers. However, we can really reduce this formula when S = 1. This reduces to and even further
(5)
or
(6)
and if V T = V, this is really simplified to Also the voltage on the remaining units given by %Vr = with S = 1, and V T = V, %Vr will always be 100% For the percentages and per unit values see Table 1 below. Table 1 - Unbalance Verification Grounded Wye Ph-N Volts Cap Volts KVAR Unit Current Total Bank Current N F %Vn %In Multiplier In-Multiplier 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2 3 1 2 3 4 1 2 3 4 5 1 2 3 4 5 6 1 1 100 2 1 100 2 2 100 1 1 100 2 2 100 3 3 100 1 1 100 2 2 100 3 3 100 4 4 100 1 1 100 2 2 100 3 3 100 4 4 100 5 5 100 1 1 100 2 2 100 3 3 100 4 4 100 5 5 100 6 6 100 100 50 100 33.33 66.67 100 25 50 75 100 20 40 60 80 100 16.67 33.33 50 66.67 83.33 100 1 1 2 1 2 3 1 2 3 4 1 2 3 4 5 1 2 3 4 5 6
http://www.gilbertelectricalsystems.com/library/technical_papers/technical_discussions/TD-003/TD-003.php[09.01.2013 14:18:32]
Gilbert Electrical Systems - Technical Discussions - Capacitor Bank Grounded Wye Unbalance Detection Discussion
Web Site Design by TADA! Media Services - Mauldin, SC 2013 - Gilbert Electrical Systems A Division of Mining Controls, Inc. / Subsidiary of Elgin National Industries Page Hits Since January 1, 2012: 249
http://www.gilbertelectricalsystems.com/library/technical_papers/technical_discussions/TD-003/TD-003.php[09.01.2013 14:18:32]