Вы находитесь на странице: 1из 115

Hitachi

Air Conditioning
Product Catalogue
Engineering for tomorrow.
And the tomorrow after that.
www.hitachiaircon.com | www.hitachiheating.com
Models
Split Systems
Set Free VRF Systems
Close Control
Ventilation
Domestic Heating
Samurai Chillers
Control Systems

Page
58 - 65 Set Free VRF Systems
Mini 2-pipe
Side Flow 2-pipe
Modular 2 and 3-pipe
Combinations
CH Boxes
System Free indoor units
System Free Accessories/Pipe Kits
66 - 69 Close Control
Twin DC Inverter
70 - 75 Ventilation
KPI Total Energy Recovery
KPI Heat Recovery
Active Total Energy Recovery
Econofresh Kit
76 - 83 Domestic Heating
Yutaki-M Monobloc air-to-water heat pump
Yutaki-S Split type air-to-water heat pump
Accessories
84 - 87 Samurai Chillers
Air Cooled
Water Cooled
Condenserless Cooling Only
88 - 91 Control Systems and Accessories
Individual controls
Group controls
BMS Interface controls
Accessories
92 - 116 Helping You
Training
Warranty
Alarm Codes
Wiring Diagrams
DIP switches
Conditions of Sale
Contents

Page
08 Product Range
10 - 17 Wall Mounted
RAC S-Series
RAC Shirokuma
RAC Summit
Utopia ES
Utopia IVX
Utopia Centrifugal
18 - 25 Cassettes
RAC Monozone (600x600)
Utopia ES 4-Way
Utopia ES 2-Way
Utopia IVX 4-Way Cassette/2-Way Cassette
Utopia IVX Centrifugal 4-Way Cassette/2-Way Cassette
26 - 31 In the Ceiling (ducted)
RAC Monozone
Utopia ES
Utopia IVX
Utopia IVX Centrifugal
32 - 37 Ceiling Suspended
Utopia ES
Utopia IVX
Utopia IVX Centrifugal
38 - 43 Floor Mounted
RAC Shirokuma
RAC NX2
Utopia ES
44 - 49 Multizone Multi Split Systems
Multizone Outdoor Units
Multizone Indoor Units
Combinations
RAC Accessories
50 - 57 Twin, Triple and Quad Splits
Utopia ES, Centrifugal and
IVX Systems
Utopia ES
Utopia IVX
Utopia IVX Centrifugal
System Free Indoor Units
System Free Accessories/Pipe Kits
Utopia AHU Interface Controllers
Why Hitachi?
With so much to choose from in the market, here are some
key reasons to buy from Hitachis extensive range of products:
RAC
Our market-leading S-Series wall mounted range has a high COP of 6.13 and high EER
of 6.0 for low running costs.
Utopia
No outdoor space, listed building or restrictive covenants?
Install Utopia Centrifugal - now with IVX individual control - the Outdoor thats an Indoor.
Set Free
Comfort protection function across the range so you wont hear complaints about cold draughts!
Ventilation
Capacities of up to 2000m
3
per hour from a unit thats less than 650mm high (the lowest height
on the market); a compact solution where installation space is limited.
Domestic Heating
Market-leading COP combined with great energy savings
(5kW output from 1kW input) fantastic news for the
domestic market when fuel costs are on the increase.
Samurai
Supremely reliable and precise control to within +/- 0.5C.
Control Systems and Accessories
H-LINK II across the entire Hitachi product range means you can use Hitachi system free controls
for any mix of products.
Heating Manufacturer of the Year
The judges felt Hitachi provided an excellent
submission, a great product and the way forward.
Hitachis Yutaki M Heat Pump
Hitachi Product Catalogue | 5
Flexibility built in
Look for the System Free logo on all pages featuring our System Free indoor units which can be
combined with outdoor units from our Utopia splits or Set Free VRF ranges for the ultimate in exibility.
Energy saving technology
http://etl.decc.gov.uk/etl
Many Hitachi systems have an energy rating of A and are listed on the Energy Technology register: making them eligible for 100%
rst year enhanced capital allowances. (System cost and reasonable cost of installation).
Quality control
Hitachis Japanese factories and its overseas afliates have acquired International Standard Quality Management System
ISO9001 and ISO14001 authorisation. The factories perform thorough product quality control using various environmental tests.
Hitachi Room Air Conditioning indoor and outdoor units are manufactured according to this ISO certication system.
Hitachi products all carry the necessary CE declaration markings, and also feature in the extensive Eurovent Listing
programme. Listing in the Eurovent directory helps ensure peace of mind for the installer and the end user, as it certies the
important operating parameters and performance of the units.
World-renowned technology
Hitachi manufactured the rst screw and scroll compressors in the world (230 patents on 6 components).
The performance of Hitachi air conditioning products is greatly improved by the high efciency high pressure scroll compressors.
Hitachi pioneered DC Inverter PAM driven Room Air Conditioners and uses this technology to drive its compressors and fans.
Nominal & UK Conditions
Nominal conditions cooling
Indoor temperature 27C DB, 19C WB
Outdoor temperature 35C DB , 24C WB
Nominal conditions heating
Indoor temperature 20C DB
Outdoor temperature 7C DB, 6C WB
UK Conditions
Indoor temperature 23C DB, 16C WB
Outdoor temperature 30C DB
S Y S T E M
FREE
Why Hitachi?
System Free complete exibility
Hitachi is particularly proud of its System Free concept of indoor units, providing the flexibility to combine indoors with outdoor
units from either the Utopia split systems or Set Free VRF ranges. This gives you enormous scope when planning your climate
solution and facilitates an optimum room climate for all areas.
Utopia outdoor units
Hitachis Utopia Split systems range
is available in capacities from 5.0kW
to 33kW. Models include Utopia ES
and IVX, which have a common
cabinet appearance allowing them
to be installed together. The Utopia
Centrifugal units are designed to be
installed indoors with field supplied
ductwork. System free indoor units
and controls are compatible across
the entire range.
Set Free outdoor units
Hitachis Set Free range of air
conditioning systems with variable
refrigerant flow (VRF) is available
in capacities from 8kW to 165kW.
Models include Mini 2-pipe,
Side Flow 2-pipe and Modular
2 or 3-pipe system allowing heat
pump or heat recovery options to
suit customer requirements. System
free indoor units and controls are
compatible across the entire range.
Indoor units

Wall-mounted

Cassette

Ceiling-suspended

In the ceiling

Floor-mounted

Total heat exchanger
System Free remote controls and accessories
System free controls can also be used for the RAC* range using PSC-6RAD adapter.
PC-ART PC-ARF
* excludes S-Series
S Y S T E M
FREE
Hitachi Product Catalogue | 7
Functions may vary among the remote controls.
BMS:
MODBUS
KNX
CS NET WEB
BACNET
HARC LONWORKS

CENTRALISED:
CS NET WEB
Optional touchscreen
TS002-UK
GROUP:
PSC-A64S / PSC-A1T / PSC-A64GT
LOCAL:
PC-ARF / PC-ART / PC-ARH / PC-LH3A
Hitachi products also benefit from the versatile range of
System Free controls to fulfil different requirements. The
extensive range includes a variety of wired and wireless
remote controllers as well as the option of different group
controllers. It is also possible to connect all Utopia Splits,
Set Free VRF and Samurai Chillers to Hitachis CS Net Web
which provides centralised or remote access control via an
internet connection.
Remote controls
Utopia Split systems Set Free VRF
ES (Simultaneous Operation)
IVX (Individual Operation)
Centrifugal (Simultaneous/individual Operation)
Compatible with System Free indoor units
FS(V)(Y)N2E Mini 2-pipe
FSNM Side Flow 2-pipe
FSXN Modular 2 or 3-pipe
Product Range
Split Systems (kW) 2.0 2.5 3.5 5.0 6.0 7.1 8.0 9.0 10.0 12.5 14.0 20.0 25.0 30.0
Wall Mounted
Cassettes
In the Ceiling (ducted)
Ceiling Suspended
Floor Mounted
Multizone Multi Splits
Utopia ES
Utopia IVX
Utopia Centrifugal
A
COP 6.13
COP 4.55
COP 4.17
COP 3.62
COP 4.30
COP 4.11
A
A
A
A
A
COP 3.10
B
COP 4.55
A
COP 4.47
A
Set Free VRF (kW) 8 11 14 16 22 28 33 40 45 50 56 63 69
Mini 2-pipe
Side Flow heat pump (2-pipe)
Modular heat pump (2-pipe)
Modular heat recovery (3-pipe)
Samurai (kW) 112 130 156 178 206 260 312 356 400 412
Air Cooled (Cooling Only)
Air Cooled (Heat Pump)
Water Cooled
Conderserless
Ventilation (m
3
/hr)* 250 500 800 1000 1500 2000
Total Energy Recovery
Heat Recovery
Active Total Energy Recovery
*Econofresh also available
73 80 85 90 96 101 107 113 118 124 130 135 140 145 150
468 534 618 712 824 890 1030
For full details, refer to Technical Manual
COP 4.17
COP 4.17
A
A
A COP 4.14
A COP 4.55
Domestic
Heating (kW)
5 8 10 12.5 14 20 24
Yutaki - M
Yutaki - S
A COP 4.50
COP 5.01 A
Close Control 56
Twin DC Inverter
A ESEER 3.52
ESEER 3.45 A
A ESEER 4.86
ESEER 4.32 A
A EER 2.80
Wall Mounted
Features and Benets
All RAC Wall mounted units
DO lnverter teohno|ogy
24 hour |nfra red remote oontro||er as standard
|ow no|se |eve|s.
RAC S-Series
Oapao|t|es from 1.8kW to 4.2kW
Market-|ead|ng OOP of 6.13 and EER of 6.0
H|gh effo|enoy soro|| oompressor
|ow runn|ng oost of on|y 18 / 33 per year*
S|eek front pane| w|th a meta|||o fn|sh
Ant|baoter|a| sta|n|ess o|ean propert|es.
* Based upon 500 hours of 100% run time
with a cost of 8 pence / 16 cents per kW/hr on 2.5 kW unit
RAC Shirokuma
Oapao|t|es from 2.5kW to 6.3kW
Oompat|b|e w|th H-|lNK oontro| / OS Net Web
A/A energy-effo|enoy rat|ng
H|gh effo|enoy soro|| oompressor
n|ts are ava||ab|e |n a var|ety of oo|ours to
compliment any interior
P|asma a|r pur|fy|ng system.
RAC Summit
Oapao|t|es from 2.0kW to 9.3kW
Oompat|b|e w|th H-|lNK oontro| / OS Net Web
A/A energy-effo|enoy rat|ng exo|udes RAS-80 YH5A}.
Utopia Wall Mounted
Oapao|t|es from 5.0kW to 11.2kW
H|gh effo|enoy soro|| oompressor
Frost proteot|on
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Hitachi Product Catalogue | 11
Product Summary
S-Series
RAS 18~35SX8
Shirokuma
RAS 25~50WX8(W)(B)
Summit
RAS 18~80FH6/FH7/YH5A
Utopia ES
RPK 2~4.0FSN2M
Utopia IVX
RPK 3~4.0FSN2M
Utopia Centrifugal
RPK 3.0FSN2M
Nominal Cooling
Capacity (kW)
1.8 ~ 3.5 2.5 ~ 5.0 2.0 ~ 8.0 5.0 ~ 10.0 7.1 ~ 10.0 7.1
Nominal Heating
Capacity (kW)
2.1 ~ 4.2 3.4 ~ 6.3 2.5 ~ 9.3 5.6 ~ 11.2 8.0 ~ 11.2 8.0
Refrigerant R410A R410A R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range
(Cooling)
-10C / +43C -10C / +43C -10C / +43C -10C / +43C -10C / +43C -5C / +43C
Operating Range
(Heating)
-20C / +21C -15C / +21C -15C / +21C -10C / +15C (*) -20C / +15C -15C / +15C
Std. Remote
Controller Type
Infra Red Infra Red Infra Red Wired or Infra Red Wired or Infra Red Wired or Infra Red
Remote Control
Timer
-
24hr or 7 Day
Option
24hr or 7 Day
Option
24hr or 7 Day
Option
24hr or 7 Day
Option
24hr or 7 Day
Option
Selected Models (*) -15C 2.0/2.5 models
RAC S-Series
Outdoor Units
Wall Mounted
For full technical details refer to Technical Manual
RAS 18SX8 RAS 25SX8 RAS 35SX8
Nominal Capacity (Min ~ Max) (kW)
Cooling 1.8 (0.5~2.4) 2.5 (0.5~3.4) 3.5 (0.5~4.1)
Heating 2.1 (0.6~4.4) 3.2 (0.6~6.1) 4.2 (0.6~7.6)
UK Cooling Capacity (kW)
Total 1.9 2.7 4.3
Sensible 1.7 2.4 2.8
EER/COP
Cooling 6.00 5.38 4.19
Heating 6.13 5.47 4.80
Energy Label
Cooling A A A
Heating A A A
Indoor Sound Pressure Level dB(A)
Cooling 38/32/26/20 42/34/28/20 43/34/28/20
Heating 39/33/27/23 42/35/30/20 44/35/30/20
Indoor Fan (m
3
/min)
Cooling 8.0/6.2/4.5/3.5 11.5/8.3/7.2/5.2 11.9/8.8/8.1/5.2
Heating 9.5/7.0/5.5/3.3 12.5/9.0/8.0/5.3 13.4/10.2/9.0/5.3
Dimensions (mm)
& Weight (kg)
Height 298
Width 793
Depth 233
Weight 11.5
RAC 18SX8 RAC 25SX8 RAC 35SX8
Outdoor Sound Pressure Level dB(A)
Cooling 45 45 46
Heating 46 45 46
Dimensions (mm)
& Weight (kg)
Height 570
Width 750
Depth 288
Weight 36
Operating Range (C)
Cooling -10 ~ +43
Heating -20 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Piping (m)
Length 20
Lift 10
Pre-charged 20
Power Supply 230V 1ph 50Hz
Power to Indoor & Outdoor
Interconnecting Cables No. 4 4 4
Starting Current (A) 5.8 5.8 6.2
Running Current (230v) (A)
Cooling 2.87 2.87 4.35
Heating 3.72 3.72 4.49
Recommended Fuse Size (A) 16 16 16
RAC-SX8
RAR-3R5 RAS-SX8
For full technical details refer to Technical Manual
Outdoor Units
Wall Mounted
Hitachi Product Catalogue | 13
RAC Shirokuma
RAC-WX8
RAS-WX8 RAS-WX8
RAS 25WX8 (W/B) RAS 35WX8 (W/B) RAS 50WX8 (W/B)
Nominal Capacity (Min ~ Max) (kW)
Cooling 2.5 (0.9~3.1) 3.5 (0.9~4.0) 5.0 (0.9~5.2)
Heating 3.4 (0.9~4.4) 4.2 (0.9~5.0) 6.3 (0.9~7.5)
UK Cooling Capacity (kW)
Total 2.2 2.7 4.3
Sensible 2.0 2.4 2.8
EER/COP
Cooling 4.31 3.57 3.22
Heating 4.30 4.16 3.61
Energy Label
Cooling A A A
Heating A A A
Indoor Sound Pressure Level dB(A)
Cooling 38/32/26/20 41/35/29/22 48/39/31/25
Heating 39/33/27/23 41/35/30/22 48/39/31/25
Indoor Fan (m
3
/min)
Cooling 8.0/6.2/4.5/3.5 9.7/7.0/5.6/4.6 11.5/9.2/6.8/4.8
Heating 9.5/7.0/5.5/3.3 10.3/8.5/6.6/4.4 13.0/9.6/7.3/4.8
Dimensions (mm)
& Weight (kg)
Height 295
Width 795
Depth 198
Weight 10
RAC 25WX8 RAC 35WX8 RAC 50WX8
Outdoor Sound Pressure Level dB(A)
Cooling 45 46 50
Heating 46 47 52
Dimensions (mm)
& Weight (kg)
Height 548 600
Width 750 792
Depth 288 299
Weight 35 42
Operating Range (C)
Cooling -10 ~ +43
Heating -15 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
Piping (m)
Length 20 30
Lift 10 10
Pre-charged 20 30
Power Supply 230V 1ph 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened 2 Core Screened 2 Core Screened
Starting Current (A) 3.9 4.7 8.1
Running Current (230v) (A)
Cooling 2.87 4.35 6.83
Heating 3.72 4.49 7.66
Recommended Fuse Size (A) 16 16 16
RAR-3U4
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Outdoor Units
Wall Mounted
For full technical details refer to Technical Manual
RAC Summit
RAS 18FH6 RAS 25FH6 RAS 35FH6 RAS 50FH7 RAS 60YH7 RAS 70YH7 RAS 80YH5A
Nominal Capacity
(Min~Max) (kW)
Cooling 2.0(0.9~2.5) 2.5(0.9~3.1) 3.5(0.9~4.0) 5.0(0.9~5.2) 6.05(0.9~6.5) 7.0(0.9~8.0) 8.0(1.5~8.5)
Heating 2.5(0.9~3.2) 3.4(0.9~4.4) 4.2(0.9~5.0) 6.5(0.9~8.1) 7.05(0.9~9.0) 8.2(0.9~9.5) 9.3(1.5~9.7)
UK Cooling Capacity (kW)
Total 1.9 2.4 3.3 4.2 5.3 6.47 7.4
Sensible 1.7 2.0 2.5 3.1 4.0 4.8 5.4
EER/COP
Cooling 3.64 3.57 3.21 3.20 3.24 3.23 2.61
Heating 4.31 3.86 3.78 3.82 3.62 3.64 3.00
Energy Label
Cooling A A A A A A D
Heating A A A A A A D
Indoor Sound Pressure
Level (dB(A)
Cooling 35/32/26/20 38/32/26/20 42/35/29/25 47/39/28/24 48/42/33/30 47/42/33/30 46/43/40/36
Heating 36/33/27/23 39/33/27/23 42/35/30/26 47/39/31/27 49/42/34/33 47/42/33/30 47/44/41/39
Indoor Fan
(m
3
/min)
Cooling 7.3/6.7/5.8/5.2 8.5/7.0/6.05.4 10.0/8.0/6.5/5.7 12.0/9.5/6.5/5.5 15.5/11.5/9.0/8.0 17.0/15.5/10.5/8.5 19.0/16.5/13.5/12.1
Heating 8.0/7.0/5.8/5.5 9.5/8.0/7.0/5.8 10.8/8.5/7.5/6.1 12.5/10.0/7.0/6.0 17.5/12.0/8.5/8.0 18.0/14.5/10.5/8.5 19.0/16.5/13.5/12.8
Dimensions (mm) &
Weight (kg)
Height 280 295 330
Width 780 1030 1150
Depth 220 207 245
Weight 9.5 12 15 15
RAC 18YH6 RAC 25YH6 RAC 35YH6 RAC 50YH7 RAC 60YH7 RAC 70YH7 RAC 80YH5
Outdoor Sound
Pressure Level dB(A)
Cooling 44 46 46 50 50 52 55
Heating 46 48 49 52 53 54 57
Dimensions (mm)
& Weight (kg)
Height 550 548 650 800 875
Width 700 750 850 850 925
Depth 258 288 298 298 315
Weight 27 35 45 55 75
Operating Range (C)
Cooling -10~43
Heating -15~21
Refrigerant Piping
(mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 6.35(1/4) 6.35(1/4) 6.35(1/4)
Gas 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 20 30
Lift 10 20
Pre-
charged
20 20
Power Supply 230V 1ph 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened 2 Core Screened 2 Core Screened 2 Core Screened 4 Core Screened 4 Core Screened 4 Core Screened
Starting Current (A) 3.0 4.5 5.3 7.1 10.0 10.0 14.0
Running Current (230v) (A)
Cooling 3.0 3.8 5.2 7.2 8.5 10.0 14.1
Heating 2.9 4.5 5.3 7.6 8.6 10.1 14.3
Recommended Fuse Size (A) 16 16 16 16 16 20 30
RAC-YH6
RAS-YH5A RAS-FH6/7 RAR-3U1/3
RAC-YH7
For full technical details refer to Technical Manual
Hitachi Product Catalogue | 15
Utopia ES
Outdoor Units
Wall Mounted
RPK-FSN2M
RAS-HVRNS2(E)
PC-ART
RPK 2.0FSN2M RPK 2.5FSN2M RPK 3.0FSN2M RPK 4.0FSN2M
Nominal Capacity (Min ~ Max) (kW)
Cooling 5.0 (2.0 ~ 5.6) 6.0 (2.2 ~ 6.3) 7.1 (3.4 ~ 8.0) 10.0 (4.9 ~ 11.2)
Heating 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 8.0 (3.4 ~ 9.0) 11.2 (5.0 ~ 12.5)
UK Cooling Capacity (kW)
Total 5.2 5.8 7.5 10.6
Sensible 3.7 4.2 5.3 7.5
EER/COP
Cooling 3.14 2.96 2.82 2.61
Heating 3.21 3.00 3.08 2.81
Energy Label
Cooling B C C D
Heating C D D D
Indoor Sound Pressure Level dB(A) 41/39/37 43/40/37 43/40/37 49/46/43
Indoor Fan (m
3
/min) 14/12/10 17/16/14 17/16/14 22/20/17
Dimensions (mm)
& Weight (kg)
Height 295 333
Width 1030 1150
Depth 208 245
Weight 12 18
Recommended Fuse Size (A) 5 5 5 5
Outdoor 1 RAS 2.0HVRN2 RAS 2.5HVRN2 RAS 3.0HVRNS2 RAS 4.0HVRNS2E
Outdoor 3 - - - RAS 4.0HRNS2E
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 45 (43) 46 (44) 48 (46) 50 (48)
Heating 47 48 50 52
Dimensions (mm) & Weight (kg)
Height 600 800
Width 792 950
Depth 300 370
Weight 1/3 42 / - 44 / - 79 / 79
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db
Heating (-15 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 9.52 (3/8) 9.52 (3/8)
Gas 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 50 30 50
Lift 30 30 30 30
Pre-charged 30 / 30g/m 30 / 30g/m 20 / 30g/m 20 / 40g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - 3Ph 380-415V 50Hz
Power to Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10
Running Current (1/3) (A)
Cooling 6.9 8.8 11.0 14.2
Heating 7.6 10.2 11.3 13.8
Recommended Fuse Size (1/3) (A) 16 / - 20 / - 25 / - 32 / 16
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Outdoor 1 RAS 3.0HVRNM2E RAS 4.0HVRNM2E
Outdoor 3 - RAS 4.0HRNM2E
Outdoor Sound Pressure Level
(Set Back) d(B)A
Cooling 47 (43) 49 (45)
Heating 49 51
Dimensions (mm)
& Weight (kg)
Height 800 1380
Width 950 950
Depth 370 370
Weight 1/3 67/- 98/98
Operating Range (C)
Cooling (-10 ~ 46)db
Heating (-20 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 70
Lift 30 30
Pre-charged 30 / 40g/m 30 / 60g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - 3Ph 380-415V 50Hz
Power To Outdoor Outdoor
Interconnection wires No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10
Running Current (1/3) (A)
Cooling 10.3 / - 13.5 / 4.8
Heating 11.3 / - 15.6 / 5.5
Recommended Fuse Size (1/3) (A) 20 / - 32 / 16
Outdoor Units
Wall Mounted
Utopia IVX
RPK-FSN2M PC-ART
RAS-HVRNME
RPK 3.0FSN2M RPK 4.0FSN2M
Nominal Capacity (Min-Max) (kW)
Cooling 7.1 (3.2 ~ 8.0) 10.0 (4.9 ~ 11.2)
Heating 8.0 (3.5 ~ 10.6) 11.2 (5.0 ~ 14.0)
UK Cooling Capacity (kW)
Total 7.5 10.6
Sensible 5.3 7.5
EER/COP
Cooling 3.02 3.22
Heating 3.10 3.13
Energy Label
Cooling B A
Heating D D
Indoor Sound Pressure Level dB(A) 43/40/37 49/46/43
Indoor Fan m
3
/min 17/16/14 22/20/17
Dimensions (mm)
& Weight (kg)
Height 333
Width 1150
Depth 245
Weight 18
Recommended Fuse Size (A) 5 5
S Y S T E M
FREE
Hitachi Product Catalogue | 17
Wall Mounted
Outdoor Units
Utopia Centrifugal
RPK 3.0FSN2M
Nominal Capacity (Min-Max) (kW)
Cooling 7.1 (3.2 ~ 8.0)
Heating 8.0 (3.5 ~ 9.0)
UK Cooling Capacity (kW)
Total 7.5
Sensible 5.3
EER/COP
Cooling 2.64
Heating 2.62
Energy Label
Cooling D
Heating E
Indoor Sound Pressure Level dB(A) 43/40/37
Indoor Fan m
3
/min 17/16/14
Dimensions (mm)
& Weight (kg)
Height 333
Width 1150
Depth 245
Weight 18
Recommended Fuse Size (A) 5
RASC 3.0HVRNE
Outdoor Sound Pressure Level dB(A)
Cooling 46
Heating 46
Dimensions (mm)
& Weight (kg)
Height 430
Width 1250
Depth 1300
Weight 168
Outdoor Fan (Min-Nom-Max) (m/min) 34 / 40 / 44
Static Pressure (Min-Nom-Max) (Pa) 100 / 50 / 15
Operating Range (C)
Cooling (-5 ~ 43)db
Heating (-15 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8)
Gas 15.88(5/8)
Piping (m)
Length 30
Lift 30
Pre-charged 20 / 60g/m
Power Supply 1 Phase 1Ph 220-240V 50Hz
Power To Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10
Running Current (A)
Cooling 11.3
Heating 11.9
Recommended Fuse Size (A) 32
RASC-HVRNE
RPK-FSN2M PC-ART
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Product Summary
RAC Monozone
600x600 cassette
RAI 25~50NH5A
Utopia ES
600x600
RCIM 2.0FSN2
Utopia ES
4-Way
RCI 2.0 ~ 6.0FSN3E
2-Way
RCD 2.0 ~ 5.0FSN2
Nominal Cooling Capacity (kW) 2.5 ~ 5.0 5.0 5.0 ~ 14.0 5.0 ~ 12.5
Nominal Heating Capacity (kW) 3.5 ~ 6.5 5.6 5.6 ~ 16.0 5.6 ~ 14.0
Refrigerant R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range (Cooling) (db) -10C / +43C -5C / +43C -10C / +43C -10C / +43C
Operating Range (Heating) (wb) -15C / +15C -15C / +15C -10C / +15C (*) -10C / +15C (*)
Std. Remote Controller Type Infra Red Wired or Infra Red Wired or Infra Red Wired or Infra Red
Remote Control Timer 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option
Condensate Pump Yes Yes Yes Yes
Selected Models (*) -15C 2.0/2.5 models (*) -15C 2.0/2.5 models
Features and Benets
Cassettes
RAC Monozone 600 x 600 Cassette
Oapao|t|es from 2.5kW to 6.5kW
Oompaot des|gn
The 600mm x 600mm ceiling unit neatly ts
inside a standard ceiling module which minimises
installation work
F|ex|b|e a|r fow system
The user can select between 2-Way, 3-Way
or 4-Way operation of auto swing louvres
24 hour |nfra red remote oontro||er as standard.
Utopia 4-Way Cassette
Oapao|t|es from 5.0kW to 16kW
H|gh OOP and EER
COP 4.55 and EER 3.97
Oompaot des|gn
The depth of the units vary from just 248 to 298mm,
so they can be installed in a reduced space inside a
false ceiling
Adaptab|e for h|gh oe|||ngs
Frost proteot|on
lnd|v|dua| un|t oontro|
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Hitachi Product Catalogue | 19
Utopia IVX Utopia IVX Centrifugal**
4-Way
RCI 3.0 ~ 6.0FSN3E
2-Way
RCD 3.0 ~ 5.0FSN2
4-Way
RCI 3.0 ~ 5.0FSN3E
2-Way
RCD 3.0 ~ 5.0FSN2
7.1 ~ 14.0 7.1 ~ 12.5 7.1 ~ 12.5 7.1 ~ 12.5
8.0 ~ 16.0 8.0 ~ 16.0 8.0 ~ 14.0 8.0 ~ 14.0
R410A R410A R410A R410A
DC-Inverter DC-Inverter DC-Inverter DC-Inverter
-10C / +43C -10C / +43C -5C / +46C -5C / +46C
-15C / +15C -15C / +15C -15C / +15C -15C / +15C
Wired or Infra Red Wired or Infra Red Wired or Infra Red Wired or Infra Red
24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option
Yes Yes Yes Yes
** 3HP Std. Inverter Centrifugal ** 3HP Std. Inverter Centrifugal
Utopia 2-Way Cassette
Oapao|t|es from 5.0kW to 14kW
|ow prof|e des|gn
The compact turbo fan simplies the structure
and reduces the height of the unit to 298mm.
The units low prole design allows easy installation
in the most conned spaces inside a ceiling
Adaptab|e for h|gh oe|||ngs
|ow no|se
Frost proteot|on
lnd|v|dua| un|t oontro|
Standard hard w|red remote oontro||er
with built in 7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Outdoor Units
600x600 Cassette
For full technical details, refer to Technical Manual
RAC Monozone
RAI 25NH5A RAI 35NH5A RAI 50NH5A
Nominal Capacity (Min ~ Max) (kW)
Cooling 2.5(0.9~3.0) 3.5(0.9~4.0) 5.0(0.9~5.2)
Heating 3.5(0.9~5.0) 4.8(0.9~6.6) 6.5(0.9~8.1)
UK Cooling Capacity (kW)
Total 2.3 3.2 4.1
Sensible 1.8 2.4 3.0
EER/COP
Cooling 3.60 3.18 2.51
Heating 3.72 3.53 3.01
Energy Label
Cooling A B E
Heating A B D
Indoor Sound Pressure Level (dB(A)
Cooling 35/32/29/25 39/34/29/26 43/35/32/29
Heating 36/33/30/27 40/36/32/29 43/36/32/30
Indoor Fan (m
3
/min)
Cooling 8.5/7.0/5.8/5.5 10.8/8.0/5.8/5.5 12.0/8.0/5.8/5.5
Heating 8.5/7.0/5.8/5.5 10.8/8.0/5.8/5.5 12.0/8.0/5.8/5.5
Dimensions (mm)
& Weight (kg)
(Panel RAI-ECPM)
Height 285
Width 580
Length 580
Panel 32/650/650
Weight 20 (4)
RAI-NH5A RAI-NH5A RAI-NH5A
RAC-NH5 RAR-3U1
RAC 25NH5 RAC 35NH5 RAC 50NH5
Outdoor Sound Pressure Level dB(A)
Cooling 46 47 50
Heating 46 49 52
Dimensions (mm)
& Weight (kg)
Height 570 650
Width 750 850
Depth 280 298
Weight 38 45
Operating Range (C)
Cooling -10 ~ +43
Heating -15 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
Piping (m)
Length 20
Lift 10
Pre-charged 20
Power Supply AC 1Ph 220~230V 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened 2 Core Screened 2 Core Screened
Starting Current (A) 4.2 6.1 10.0
Running Current (230v) (A)
Cooling 3.05 4.85 8.74
Heating 4.15 6.00 9.49
Recommended Fuse Size (A) 16 16 16
Hitachi Cassettes
2-way, 3-way and 4-way air outlet control
that can be used in ceiling heights of up to 4.2m
Contact aircon.enquiries@hitachi-eu.com
to nd out more
Hitachi Product Catalogue | 21
RAS-HVRN2S RAS-HVRNS2(E) RAS-HVRNM2E
RCIM 2.0FSN2 RCI 2.0FSN3E RCI 2.5FSN3E RCI 3.0FSN3E RCI 4.0FSN3E RCI 5.0FSN3E RCI 6.0FSN3E
Mini 600x600 4-Way 4-Way 4-Way 4-Way 4-Way 4-Way
Nominal Capacity
(Min-Max) (kW)
Cooling 5.0 (2.2 ~ 5.6) 5.0 (2.2 ~ 5.6) 6.0 (2.2 ~ 6.3) 7.1 (3.4 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0)
Heating 5.6 (2.2 ~ 7.1) 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 8.0 (3.4 ~ 9.0) 11.2 (5.0 ~ 12.5) 14.0 (6.0 ~ 16.0) 16.0 (6.0 ~ 18.0)
UK Cooling
Capacity (kW)
Total 5.3 5.3 5.9 7.5 10.6 13.1 15.6
Sensible 3.8 4.1 4.3 5.9 8.3 9.7 11.4
EER/COP
Cooling 3.11 3.97 3.28 3.06 3.01 2.91 2.45
Heating 3.31 4.55 3.80 3.29 3.48 3.24 2.88
Energy Label
Cooling B A A B B C E
Heating C A A C B C D
Indoor Sound
Pressure Level dB(A)
42/39/37 32/30/28 32/30/28 34/32/30 38/35/33 39/37/35 42/40/36
Indoor Fan (m/min) 16/14/12 16/14/12 20/17/15 26/23/20 32/28/24 34/29/25 37/32/27
Dimensions (mm)
& Weight (kg)
Height 295 248
Width 570 840
Depth 570 840
Grille 700/700/35 950/950/37
Weight 17 (3.5) 24 (6) 26 (6)
Recommended Fuse
Size (A)
5 5 5 5 5 5 5
Outdoor 1 RAS 2.0HVRN2 RAS 2.0HVRN2 RAS 2.5HVRN2 RAS 3.0HVRN2S RAS 4.0HVRNS2E RAS 5.0HVRNS2E RAS 6.0HVRNS2E
Outdoor 3 - - - - RAS 4.0HRNS2E RAS 5.0HRNS2E RAS 6.0HRNS2E
Outdoor Sound Pressure
Level (Set Back) dB(A)
Cooling 45 (43) 45 (43) 46 (44) 48 (46) 50 (48) 52 (50) 55 (53)
Heating 47 47 48 50 52 54 57
Dimensions (mm)
& Weight (kg)
Length 600 600 800
Width 792 792 950
Depth 300 300 370
Weight 1/3 42 / - 42 / - 42 / - 44 / - 79 / 79 83 / 83 83 / 83
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db (-10 ~ 43)db
Heating (-10 ~ 15)wb (-10 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping
(mm) (in)
Liquid 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 12.7(1/2) 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 50 50 30 50 50 50
Lift 30 30 30 30 30 30 30
Pre-charged 30 / 30g/m 30 / 30g/m 30 / 30g/m 20 / 30g/m 20 / 40g/m 30 / 60g/m 30 / 60g/m
Power Supply
1 phase
1Ph 220-240V
50Hz
1Ph 220-240V 50Hz
3 phase - - - - 3Ph 380-415V 50Hz
Power To Outdoor Outdoor
Interconnection wires No.
LNE + 2 Core
Screened
LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10 < 10 < 10
Running Current
(1/3) (A)
Cooling 6.8 5.4 7.8 9.9 15.4 / 5.0 18.4 / 6.5 24.6 / 8.7
Heating 7.2 5.2 7.9 10.4 14.9 / 4.9 18.5 / 6.6 23.8 / 8.4
Recommended Fuse
Size (1/3) (A)
16 / - 16 / - 20 / - 25 / - 32 / 16 32 / 16 32 / 16
Outdoor Units
Utopia ES
4-Way Cassette
RCI-FSN3E PC-ART RCIM-FSN2
S Y S T E M
FREE
Hitachi Product Catalogue | 23
RCD 2.0FSN2 RCD 2.5FSN2 RCD 3.0FSN2 RCD 4.0FSN2 RCD 5.0FSN2
2-Way 2-Way 2-Way 2-Way 2-Way
Nominal Capacity
(Min-Max) (kW)
Cooling 5.0 (2.2 ~ 5.6) 6.0 (2.2 ~ 6.3) 7.1 (3.4 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0)
Heating 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 8.0 (3.4 ~ 9.0) 11.2 (5.0 ~ 12.5) 14.0 (6.0 ~ 16.0)
UK Cooling
Capacity (kW)
Total 5.3 5.9 7.5 10.6 13.1
Sensible 4.0 4.4 5.6 7.7 9.7
EER/COP
Cooling 3.14 2.87 2.81 3.01 3.03
Heating 3.09 3.13 3.08 3.48 3.31
Energy Label
Cooling B C C B B
Heating D D D B C
Indoor Sound
Pressure Level dB(A)
35/32/30 38/34/31 38/34/31 40/36/33 43/40/36
Indoor Fan (m/min) 15/13/11 19/16/14 19/16/14 29/24/21 34/29/25
Dimensions (mm)
& Weight (kg)
Height 298 298
Width 620 620
Depth 860 1420
Grille 1100/710/30 1660/710/30
Weight 27 (6) 30 (6) 30 (6) 48 (8)
Recommended Fuse
Size (A)
5 5 5 5 5
Outdoor 1 RAS 2.0HVRN2 RAS 2.5HVRN2 RAS 3.0HVRN2S RAS 4.0HVRNS2E RAS 5.0HVRNS2E
Outdoor 3 - - - RAS 4.0HRNS2E RAS 5.0HRNS2E
Outdoor Sound Pressure
Level (Set Back) dB(A)
Cooling 45 (43) 46 (44) 48 (46) 50 (48) 52 (50)
Heating 47 48 50 52 54
Dimensions (mm)
& Weight (kg)
Length 600 800
Width 792 950
Depth 300 370
Weight 1/3 42 / - 42 / - 44 / - 79 / 79 83 / 83
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db
Heating (-10 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping
(mm) (in)
Liquid 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 50 30 50 50
Lift 30 30 30 30 30
Pre-charged 30 / 30g/m 30 / 30g/m 20 / 30g/m 20 / 40g/m 30 / 60g/m
Power Supply
1 phase
1Ph 220-240V
50Hz
3 phase - - - 3Ph 380-415V 50Hz
Power To Outdoor
Interconnection wires No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10
Running Current
(1/3) (A)
Cooling 6.7 / - 8.8 / - 10.8 / - 15.4 / 5.4 17.5 / 6.2
Heating 7.7 / - 9.5 / - 11.1 / - 14.9 / 5.3 17.9 / 6.3
Recommended Fuse
Size (1/3) (A)
16 / - 20 / - 25 / - 32 / 16 32 / 16
Outdoor Units
2-Way Cassette
RCD-FSN2 PC-ART
Utopia ES
RAS-HVRN2S RAS-HVRNS2(E)
For full technical details, refer to Technical Manual
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Outdoor Units
Utopia IVX
4-Way / 2-Way Cassette
RCI-FSN3E RCD-FSN2 PC-ART
* 3HP Std. Inverter Centrifugal.
RAS-HVRNM2E
RCI 3.0FSN3E RCI 4.0FSN3E RCI 5.0FSN3E RCI 6.0FSN3E RCD 3.0FSN2 RCD 4.0FSN2 RCD 5.0FSN2
4-Way 4-Way 4-Way 4-Way 2-Way 2-Way 2-Way
Nominal Capacity
(Min-Max) (kW)
Cooling 7.1 (3.2 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0) 7.1 (3.2 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0)
Heating 8.0 (3.5 ~ 10.6) 11.2 (5.0 ~ 14.0) 14.0 (6.0 ~ 18.0) 16.0 (6.0 ~ 20.0) 8.0 (3.5 ~ 10.6) 11.2 (5.0 ~ 14.0) 14.0 (6.0 ~ 18.0)
UK Cooling
Capacity (kW)
Total 7.5 10.6 13.1 15.6 7.5 10.6 13.1
Sensible 5.9 8.3 9.7 11.4 5.6 7.7 9.7
EER/COP
Cooling 3.66 3.90 3.62 3.29 3.05 3.47 3.31
Heating 4.05 4.10 4.06 3.72 3.30 3.41 3.70
Energy Label
Cooling A A A A B A A
Heating A A A A C B A
Indoor Sound
Pressure Level dB(A)
34/32/30 38/35/33 39/37/35 42/40/36 38/34/31 40/36/33 39/37/35
Indoor Fan (m/min) 26/23/20 32/28/24 34/29/25 37/32/27 19/16/14 29/24/21 34/29/25
Dimensions (mm)
& Weight (kg)
Height 840 860 1420
Width 840 620 620
Depth 298 298 298
Grille 950/950/37 1100/710/30 1660/710/30
Weight 26 (6) 30 (6) 48 (8)
Recommended Fuse
Size (A)
5 5 5 5 5 5 5
Outdoor 1
RAS
3.0HVRNM2E
RAS
4.0HVRNM2E
RAS
5.0HVRNM2E
RAS
6.0HVRNM2E
RAS
3.0HVRNM2E
RAS
4.0HVRNM2E
RAS
5.0HVRNM2E
Outdoor 3 -
RAS
4.0HRNM2E
RAS
5.0HRNM2E
RAS
6.0HRNM2E
-
RAS
4.0HRNM2E
RAS
5.0HRNM2E
Outdoor Sound Pressure
Level (Set Back) dB(A)
Cooling 47 (43) 49 (45) 51 (47) 51 (48) 47 (43) 49 (45) 51 (47)
Heating 49 51 53 53 49 51 53
Dimensions (mm)
& Weight (kg)
Length 800 1380 800 1380
Width 950 950 950 950
Depth 370 370 370 370
Weight 1/3 67 / - 98 / 98 105 / 105 105 / 105 67 / - 98 / 98 105 / 105
Operating Range (C)
Cooling (-10 ~ 46)db (-10 ~ 46)db
Heating (-20 ~ 15)wb (-20 ~ 15)wb
Refrigerant Piping
(mm) (in)
Liquid 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 70 75 75 50 70 75
Lift 30 30 30 30 30 30 30
Pre-charged 30 / 40g/m 30 / 60g/m 30 / 60g/m 30 / 60g/m 30 / 40g/m 30 / 60g/m 30 / 60g/m
Power Supply
1 phase 1Ph 220-240V 50Hz 1Ph 220-240V 50Hz
3 phase - 3Ph 380-415V 50Hz - 3Ph 380-415V 50Hz
Power To Outdoor Outdoor
Interconnection wires No. LNE + 2 Core screened LNE + 2 Core screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10 < 10 < 10
Running Current
(1/3) (A)
Cooling 8.2 / - 10.9 / 3.9 14.7 / 5.2 18.1 / 6.4 9.9 / - 12.2 / 4.3 15.9 / 5.6
Heating 8.4 / - 11.6 / 4.1 14.7 / 5.2 18.3 / 6.5 10.3 / - 14.0 / 4.9 15.9 / 5.6
Recommended Fuse
Size (1/3) (A)
25 32 / 16 32 / 16 32 / 16 25 32 / 16 32 / 16
S Y S T E M
FREE
Hitachi Product Catalogue | 25
RASC-HVRN(M)E
RCI 3.0FSN3E RCD 3.0FSN2 RCI 5.0FSN3E RCD 5.0FSN2
4-Way 2-Way 4-Way 2-Way
Nominal Capacity (Min-Max) (kW)
Cooling 7.1 (3.4 ~ 8.0) 7.1 (3.4 ~ 8.0) 12.5 (4.7 ~ 14.0) 12.5 (4.7 ~ 14.0)
Heating 8.0 (3.4 ~ 9.0) 8.0 (3.4 ~ 9.0) 14.0 (5.0 ~ 16.0) 14.0 (5.0 ~ 16.0)
UK Cooling Capacity (kW)
Total 7.5 7.5 13.1 13.1
Sensible 5.9 5.6 9.7 9.0
EER/COP
Cooling 2.90 2.78 2.71 2.69
Heating 3.10 2.69 3.10 3.01
Energy Label
Cooling C D D D
Heating D E D D
Indoor Sound Pressure Level dB(A) 34/32/30 38/34/31 39/37/35 43/40/36
Indoor Fan (m
3
/min) 26/23/20 19/16/14 34/29/25 34/29/25
Dimensions (mm)
& Weight (kg)
Height 840 860 840 1420
Width 840 620 840 620
Depth 298 298 298 298
Grille 950/950/38 1100/710/30 950/950/38 1660/710/30
Weight 26 (6) 30 (6) 26 (6) 48 (8)
Recommended Fuse Size (A) 5 5 5 5
RASC 3.0HVRNE* RASC 5.0HVRNME
Outdoor Sound Pressure Level dB(A)
Cooling 46 55
Heating 46 56
Dimensions (mm)
& Weight (kg)
Height 430 430
Width 1250 1250
Depth 1300 1300
Weight 168 176
Outdoor Fan (Min-Nom-Max) (m/min) 34 / 40 / 44 60 / 65/ 69
Static Pressure (Min-Nom-Max) (Pa) 100 / 50 / 15 100 / 50 / 12
Operating Range (C)
Cooling (-5 ~ 43)db (-5 ~ 46)db
Heating (-15 ~ 15)wb (-15 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8)
Piping (m)
Length 30 70
Lift 30 30
Pre-charged 20 / 60g/m 15 / 60g/m
Power Supply 1 Phase 1Ph 220-240V 50Hz 1Ph 220-240V 50Hz
Power To Outdoor Outdoor
Interconnecting Cables No. LNE + 2 Core Screened LNE + 2 Core Screened
Starting Current (A) < 10 < 10
Running Current (230v) (A)
Cooling 11.3 22
Heating 11.9 21.6
Recommended Fuse Size (A) 32 40
Utopia IVX Centrifugal
Outdoor Units
4-Way / 2-Way Cassette
RCI-FSN3E RCD-FSN2 PC-ART
* 3HP Std. Inverter Centrifugal.
For full technical details, refer to Technical Manual
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
In the Ceiling (ducted)
RAC Monozone In the Ceiling (ducted)
Oapao|t|es from 2.5kW to 4.8kW
Oompaot des|gn
The units are only 750mm long and 235mm in depth
Oho|oe of a|r |ntake d|reot|on
Air intake direction can be horizontal or vertical by
interchanging the bottom panel with the fan cover
Bu||t-|n dra|n pump
Hard w|red remote oontro||er as standard
Oompat|b|e w|th H-|lNK oontro| /
ready to connect to PCS-6RAD adapter.
Monozone In the Ceiling
Utopia In the Ceiling (ducted)
Oapao|t|es from 5.0kW to 28.0kW
H|gh OOP and EER
COP of 4.17 and EER of 3.72
S||m but sturdy des|gn
The RPI has a reinforced structure to give the unit
more rigidity when it is suspended. It also has one
of the lowest heights in the market when its installed
Adjustab|e stat|o pressure
The unit has 3 static pressure settings providing
greater installation exibility and can be adapted to
suit the installation requirements
Bu||t-|n dra|n pump
Frost proteot|on
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Hitachi Product Catalogue | 27
Product Summary
Monozone
RAD 25 ~ 35NH7A
Utopia ES
RPI 2.0 ~ 10.0FSN3E
Utopia IVX
RPI 3.0 ~ 10.0FSN3E
Utopia IVX Centrifugal*
RPI 3.0 ~ 10.0FSN3E
Nominal Cooling
Capacity (kW)
2.5 ~ 3.5 5.0 ~ 25.0 7.1 ~ 25.0 7.1 ~ 25.0
Nominal Heating
Capacity (kW)
3.5 ~ 4.8 5.6 ~ 28.0 8.0 ~ 28.0 8.0 ~ 28.0
Refrigerant R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range
1

(Cooling) (db)
-10C / +43C -5C / +43C -15C / +43C (*) -5C / +46C
Operating Range
(Heating) (wb)
-15C / +15C -10C / +15C (*) -20C / +15C -15C / +15C
Std. Remote
Controller Type
Wired Wired or Infra Red Wired or Infra Red Wired or Infra Red
Remote Control Timer 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option
Condensate Pump Yes Yes
#
Yes
#
Yes
#
Static Pressure (Pa) Adjustable Adjustable Adjustable Adjustable
Return Air Direction Rear or Bottom Rear or Bottom
#
Rear or Bottom
#
Rear or Bottom
#
Selected Models
(*) -15C 2.0/2.5 models
#
Option available on 8HP and 10HP
(*) -10C 3.0~ 6.0 models
#
Option available on 8HP and 10HP
* 3HP Std. Inverter Centrifugal
#
Option available on 8HP and 10HP
Outdoor Units
In the Ceiling (ducted)
For full technical details, refer to Technical Manual
RAC Monozone
RAD 25NH7A RAD 35NH7A
Nominal Capacity (Min ~ Max) (kW)
Cooling 2.5(0.9~3.0) 3.5(0.9~4.0)
Heating 3.5(0.9~5.0) 4.8(0.9~6.6)
UK Cooling Capacity (kW)
Total 2.3 3.2
Sensible 1.8 2.2
EER/COP
Cooling 3.60 2.82
Heating 3.61 2.82
Energy Label
Cooling A C
Heating A D
Indoor Sound Pressure Level dB(A)
Cooling 36/34/31/29 36/34/31/29
Heating 37/33/30/27 37/33/30/27
Indoor Fan (m
3
/min)
Cooling 8.2/7.3/6.2/5.5 8.5/7.6/6.2/5.5
Heating 9.2/7.5/6.2/5.5 9.3/7.6/6.2/5.5
Static Pressure (Pa) Standard 30 (low 25, High 35)
Dimensions (mm)
& Weight (kg)
Height 235
Width 750
Length 400
Weight 19
RAC 25NH5 RAC 35NH5
Outdoor Sound Pressure Level dB(A)
Cooling 46 47
Heating 46 49
Dimensions (mm)
& Weight (kg)
Height 570
Width 750
Depth 280
Weight 38
Operating Range (C)
Cooling -10 ~ +43
Heating -15 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8)
Piping (m)
Length 20
Lift 10
Pre-charged 20
Power Supply 230V 1 ph 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened 2 Core Screened
Starting Current (A) 4.2 6.1
Running Current (230v) (A)
Cooling 3.05 5.45
Heating 4.26 7.47
Recommended Fuse Size (A) 16 16
RAD-NH7A PM RAD 18 NH7
RAC-NH5
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 29
Utopia ES
In the Ceiling (ducted)
PC-ART RPI-FSN3E
Outdoor Units
RPI 2.0FSN3E RPI 2.5FSN3E RPI 3.0FSN3E RPI 4.0FSN3E RPI 5.0FSN3E RPI 6.0FSN3E RPI 8.0FSN3E RPI 10.0FSN3E
Nominal Capacity
(Min-Max) (kW)
Cooling 5.0 (2.2 ~ 5.6) 6.0 (2.2 ~ 6.3) 7.1 (3.4 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0) 20.0 (9.0 ~ 22.4) 25.0 (11.2 ~ 28.0)
Heating 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 8.0 (3.4 ~ 9.0) 11.2 (5.0 ~ 12.5) 14.0 (6.0 ~ 16.0) 16.0 (6.0 ~ 18.0) 22.4 (8.3 ~ 25.0) 28.0 (9.0 ~ 31.5)
UK Cooling
Capacity (kW)
Total 5.3 5.9 7.5 10.6 13.1 15.6 18.0 22.0
Sensible 4.0 4.5 5.6 7.7 9.4 11.2 12.8 16.0
EER/COP
Cooling 3.56 2.89 2.70 2.92 2.93 2.75 2.57 2.41
Heating 3.84 3.62 3.17 3.21 3.33 3.23 3.07 3.03
Energy Label
Cooling A C D C C D E E
Heating A A D C C C D D
Indoor Sound
Pressure Level dB(A)
SP-00 33/31/29 35/33/30 35/35/31 37/36/35 39/38/36 40/39/38 54/54/51 55/55/52
Indoor Fan (m/min) SP-00 16/15/13 19/17/15 22/20/17 30/28/25 35/32/28 36/33/29 66/66/60 75/75/68.5
Static Pressure (Pa) SP-01/00/02 80/50/25 80/50/25 100/60/25 120/80/30 120/80/30 120/80/30 220/220/180 220/220/180
Dimensions (mm)
& Weight (kg)
Height 275 275 423
Width 1084 1474 1592
Depth 600 600 600
Weight 35 37 37 49 49 49 85 87
Recommended
Fuse Size (A)
5 5 5 5 5 5 10 10
Outdoor 1 RAS 2.0HVRN2 RAS 2.5HVRN2 RAS 3.0HVRN2S RAS 4.0HVRNS2E RAS 5.0HVRNS2E RAS 6.0HVRNS2E - -
Outdoor 3 - - - RAS 4.0HRNS2E RAS 5.0HRNS2E RAS 6.0HRNS2E RAS 8.0HRNSE RAS 10.0HRNSE
Outdoor Sound
Pressure Level
(Set Back) dB(A)
Cooling 45 (43) 46 (44) 48 (46) 50 (48) 52 (50) 55 (53) 53 (51) 60 (56)
Heating 47 48 50 52 54 57 55 62
Dimensions (mm)
& Weight (kg)
Length 600 800 1380
Width 792 950 950
Depth 300 370 370
Weight 42 / - 42 / - 44 / - 79 / 79 83 / 83 83 / 83 135 141
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db
Heating (-10 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping
(mm) (in)
Liquid 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)*
Gas 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 28.6(1/8)* 28.6(1/8)*
Piping (m)
Length 50 50 30 50 50 50 50 50
Lift 30 30 30 30 30 30 30 30
Pre-charged 30 / 30g/m 30 / 30g/m 20 / 30g/m 20 / 40g/m 30 / 60g/m 30 / 60g/m 30 / 65g/m 30 / 120g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz - -
3 Phase - - - 3Ph 380-415 50Hz
Power To Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10 < 10 < 10 < 10
Running Current
(1/3) (A)
Cooling 5.7 / - 8.6 / - 10.4 / - 16.1 / 4.9 17.6 / 6.2 21.1 / 7.5 - / 10.7 - / 14.6
Heating 5.9 / - 8.0 / - 10.5 / - 16.9 / 5.0 17.3 / 6.1 20.5 / 7.3 - / 9.9 - / 13.5
Recommended
Fuse Size (A)
(1/3) 16 / - 20 / - 20 / - 32 / 16 32 / 16 32 / 16 - / 25 - / 25
RAS-HVRNS2(E)
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
* 3HP Std. Inverter Centrifugal
Utopia IVX
Outdoor Units
In the Ceiling (ducted)
PC-ART RPI-FSN3E
RPI 3.0FSN3E RPI 4.0FSN3E RPI 5.0FSN3E RPI 6.0FSN3E RPI 8.0FSN3E RPI 10.0FSN3E
Nominal Capacity (kW)
Cooling 7.1 (3.2 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0) 20.0 (9.0 ~ 22.4) 25.0 (11.2 ~ 28.0)
Heating 8.0 (3.5 ~ 10.6) 11.2 (5.0 ~ 14.0) 14.0 (6.0 ~ 18.0) 16.0 (6.0 ~ 20.0) 22.4 (8.3 ~ 25.0) 28.0 (9.0 ~ 31.5)
UK Cooling Capacity (kW)
Total 7.5 10.6 13.1 15.6 20.5 25.4
Sensible 5.6 7.7 9.4 11.2 15.8 20.1
EER/COP
Cooling 3.55 3.72 3.50 3.16 2.84 2.72
Heating 3.86 4.17 3.76 3.62 3.51 3.34
Energy Label
Cooling A A A B C D
Heating A A A A B C
Indoor Sound Pressure Level dB(A) SP-00 35/35/31 37/36/35 39/38/36 40/39/38 54/54/51 55/55/52
Indoor Fan (m
3
/min) SP-00 22/20/17 30/28/25 35/32/28 36/33/29 66/66/60 75/75/68.5
Static Pressure (Pa) SP-01/00/02 100/60/25 120/80/30 120/80/30 120/80/30 220/220/180 220/220/180
Dimensions (mm)
& Weight (kg)
Height 275 275 423
Width 1084 1474 1592
Depth 600 600 600
Weight 37 49 49 49 85 87
Recommended Fuse Size (A) 5 5 5 5 10 10
Outdoor 1
RAS
3.0HVRNM2E
RAS
4.0HVRNM2E
RAS
5.0HVRNM2E
RAS
6.0HVRNM2E
- -
Outdoor 3 -
RAS
4.0HRNM2E
RAS
5.0HRNM2E
RAS
6.0HRNM2E
RAS
8.0HRNME
RAS
10.0HRNME
Outdoor Sound
Pressure Level dB(A)
Cooling 47 (43) 49 (45) 51 (47) 51 (48) 52 (50) 55 (53)
Heating 49 51 53 53 54 57
Dimensions (mm)
& Weight (kg)
Height 800 1380 1650
Width 950 950 1100
Depth 370 370 390
Weight 1/3 67 / - 98 / 98 105 / 105 105 / 105 - / 170 - / 170
Operating Range (C)
Cooling (-10 ~ 46)db (-15 ~46)db
Heating (-20 ~ 15)wb (-20 ~15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)* 12.70(1/2)*
Gas 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 28.6(1/8)* 28.6(1/8)*
Piping (m)
Length 50 70 75 75 100 100
Lift 30 30 30 30 30 30
Pre-charged 30 / 40g/m 30 / 60g/m 30 / 60g/m 30 / 60g/m Calculate Calculate
Power Supply
1 Phase 1Ph 220-240V 50Hz -
3 Phase - 3Ph 380-415V 50Hz
Power to Outdoor
Interconnecting Cables No. LNE + 2 Core screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10 < 10
Running Current (1/3) (A)
Cooling 8.2 10.9 / 3.9 15.0 / 5.3 18.1 / 6.4 9.2 12.0
Heating 8.0 / - 10.7 / 3.8 14.5 / 5.1 18.2 / 6.4 - / 9.2 - / 12.3
Recommended Fuse Size (A) (1/3) 8.3 / - 10.7 / 3.8 15.2 / 5.4 18.1 / 6.4 - / 8.2 - / 11.1
RAS-HRNM(2)E
S Y S T E M
FREE
Hitachi Product Catalogue | 31
RASC-HVRNE
Utopia IVX Centrifugal
Outdoor Units
In the Ceiling (ducted)
RPI 3.0FSN3E RPI 5.0FSN3E RPI 10.0FSN3E
Nominal Capacity (kW)
Cooling 7.1 (3.4 ~ 8.0) 12.5 (4.7 ~ 14.0) 23.0 (10.3 ~ 25.0)
Heating 8.0 (3.4 ~ 9.0) 14.0 (5.0 ~ 16.0) 25.0 (9.4 ~ 26.0)
UK Cooling Capacity (kW)
Total 7.4 12.6 22.0
Sensible 5.2 9.1 17.4
EER/COP
Cooling 2.73 2.61 2.41
Heating 2.68 2.97 2.64
Energy Label
Cooling D D E
Heating E D E
Indoor Sound Pressure Level dB(A) SP-00 35/35/31 39/38/36 55/55/52
Indoor Fan (m
3
/min) SP-00 22/20/17 35/32/28 75/75/68.5
Static Pressure (Pa) SP-01/00/02 100/60/25 120/80/30 220/220/180
Dimensions (mm)
& Weight (kg)
Height 275 275 423
Width 1084 1474 1592
Depth 600 600 600
Weight 37 49 87
Recommended Fuse Size (A) 5 5 10
Outdoor 1 RASC 3.0HVRNE* RASC 5.0HVRNME -
Outdoor 3 - - RASC 10.0HRNME
Outdoor Sound Pressure Level dB(A)
Cooling 46 55 68
Heating 46 56 68
Dimensions (mm)
& Weight (kg)
Height 430 640
Width 1250 1850
Depth 1300 985
Weight 168 176 262
Outdoor Fan (Min-Nom-Max) (m/min) 34 / 40 / 44 60 / 65/ 69 90 / 105 / 109
Static Pressure (Min-Nom-Max) (Pa) 100 / 50 / 15 100 / 50 / 12 130 / 62 / 25
Operating Range (C)
Cooling (-5 ~ 43)db (-5 ~ 46)db
Heating (-15 ~ 15)wb (-15 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8) 12.7 (1/2)
Gas 15.88(5/8) 15.88(5/8) 28.6(1/8)*
Piping (m)
Length 30 70 50
Lift 30 30 30
Pre-charged 20 / 60g/m 15 / 60g/m 7.5 / 120g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz -
3 Phase - 3Ph 380-415V 50Hz
Power to Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10
Running Current (1/3) (A)
Cooling 11.3 / - 22 / - - / 20.1
Heating 11.9 / - 21.6 / - - / 20.2
Recommended Fuse Size (A) (1/3) 32 / - 40 / - - / 40
* 3HP Std. Inverter Centrifugal.
PC-ART RPI-FSN3E
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Ceiling Suspended
Features and Benets
Utopia Ceiling Suspended
Oapao|t|es from 5.0kW to 16.0kW
H|gh OOP and EER
COP of 3.62 and EER of 3.32
E|egant des|gn
An innovative fan and heat exchanger design led
to the creation of todays ultra slim ceiling unit.
Fully adjustable mounting brackets allow the unit
to be tted ush with the ceiling
S|mp|e and fex|b|e |nsta||at|on
To expand the installation and positioning options
the unit has a choice of two drain pipe connections,
also refrigeration pipes can be connected to the left,
right or rear of the unit
Automat|o sw|ng |ouvre
A highly efcient, multi blade centrifugal fan along with
the automatic swing louvre generates a powerful and
evenly distributed airow ensuring comfort throughout
the room
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Hitachi Product Catalogue | 33
Product Summary
Utopia ES
RPC 2.0 ~ 6.0FSN2E
Utopia IVX
RPC 3.0 ~ 6.0FSN2E
Utopia IVX Centrifugal*
RPC 3.0 ~ 5.0FSN2E
Nominal Cooling Capacity (kW) 5.0 ~ 14.0 7.1 ~ 14.0 7.1 ~ 12.5
Nominal Heating Capacity (kW) 5.6 ~ 16.0 8.0 ~ 16.0 8.0 ~ 14.0
Refrigerant R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter
Operating Range
1
(Cooling) (db) -10C / +43C -10C / +43C -5C / +46C
Operating Range (Heating) (wb) -10C / +15C (*) -15C / +15C -15C / +15C
Std. Remote Controller Type Wired or Infra Red Wired or Infra Red Wired or Infra Red
Remote Control Timer 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option
Condensate Pump No No No
Selected Models (*) -15C 2.0/2.5 models * 3HP Std. Inverter Centrifugal
Outdoor Units
RAS-H(V)RNM2E
Utopia ES
Outdoor 1 RAS 2.0HVRN2 RAS 2.5HVRN2 RAS 3.0HVRN2S RAS 4.0HVRNS2E RAS 5.0HVRNS2E RAS 6.0HVRNS2E
Outdoor 3 - - - RAS 4.0HRNS2E RAS 5.0HRNS2E RAS 6.0HRNS2E
Outdoor Sound
Pressure Level dB(A)
Cooling 45 (43) 46 (44) 48 (46) 50 (48) 52 (50) 55 (53)
Heating 47 48 50 52 54 57
Dimensions (mm)
& Weight (kg)
Height 600 800
Width 792 950
Depth 300 370
Weight 1/3 42 / - 42 / - 44 / - 79 / 79 83 / 83 83 / 83
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db
Heating (-10 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 6.35(1/4) 6.35(1/4) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 12.7(1/2) 12.7(1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 50 30 50 50 50
Lift 30 30 30 30 30 30
Pre-charged 30 / 30g/m 30 / 30g/m 20 / 30g/m 20 / 40g/m 30 / 60g/m 30 / 60g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - - - 3Ph 380-415 50Hz
Power to Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10 < 10 < 10
Running Current (1/3) (A)
Cooling 7.5 / - 9.9 / - 10.4 / - 16.1 / 5.7 18.8 / 6.6 24.8 / 8.8
Heating 8.5 / - 10.8 / - 10.5 / - 16.9 / 6.0 19.1 / 6.7 24.1 / 8.5
Recommended Fuse Size (A) (1/3) 16 / - 20 / - 20 / - 32 / 16 32 / 16 32 / 16
RPC
2.0FSN2E
RPC
2.5FSN2E
RPC 3.0FSN2E RPC 4.0FSN2E RPC 5.0FSN2E RPC 6.0FSN2E
Nominal Capacity (Min-Max)
(kW)
Cooling 5.0 (2.2 ~ 5.6) 6.0 (2.2 ~ 6.3) 7.1 (1.5 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0)
Heating 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 8.0 (1.5 ~ 9.0) 11.2 (5.0 ~ 12.5) 14.0 (6.0 ~ 16.0) 16.0 (6.0 ~ 18.0)
UK Cooling Capacity (kW)
Total 5.3 5.9 7.5 10.6 13.1 15.6
Sensible 4.0 4.5 5.6 7.7 9.4 11.2
EER/COP
Cooling 2.73 2.55 2.82 2.62 2.80 2.41
Heating 2.73 2.73 3.16 2.81 3.09 2.83
Energy Label
Cooling D E C D D E
Heating E E D D D D
Indoor Sound Pressure Level dB(A) 44/42/38 46/43/41 48/45/42 49/45/39 49/46/41 50/48/44
Indoor Fan (m
3
/min) 15/13/10 18/16/12 21/17/15 30/24/19 35/28/21 37/32/27
Dimensions (mm)
& Weight (kg)
Length 1094 1314 1314 1574
Width 625 625 625 625
Depth 163 163 225 225
Weight 28 31 31 35 41 41
Recommended Fuse Size (A) 5 5 5 5 5 5
Ceiling Suspended
RPC-FSN2E PC-ART
S Y S T E M
FREE
Hitachi Product Catalogue | 35
Utopia IVX
RPC-FSN2E PC-ART
Ceiling Suspended
Outdoor Units
RAS-HVRNS2(E)
RPC 3.0FSN2E RPC 4.0FSN2E RPC 5.0FSN2E RPC 6.0FSN2E
Nominal Capacity (Min-Max) (kW)
Cooling 7.1 (3.2 ~ 8.0) 10.0 (4.9 ~ 11.2) 12.5 (5.7 ~ 14.0) 14.0 (6.0 ~ 16.0)
Heating 8.0 (3.5 ~ 10.6) 11.2 (5.0 ~ 14.0) 14.0 (6.0 ~ 18.0) 16.0 (6.0 ~ 20.0)
UK Cooling Capacity (kW)
Total 7.8 10.5 13.1 15.7
Sensible 5.4 7.5 9.2 11.0
EER/COP
Cooling 3.07 3.32 3.24 2.79
Heating 3.25 3.28 3.62 3.34
Energy Label
Cooling B A A D
Heating C C A C
Indoor Sound Pressure Level dB(A) 48/45/42 49/45/39 49/46/41 50/48/44
Indoor Fan (m
3
/min) 21/17/15 30/24/19 35/28/21 37/32/27
Dimensions (mm)
& Weight (kg)
Length 1314 1314 1574
Width 625 625 625
Depth 163 225 225
Weight 31 35 41 41
Recommended Fuse Size (A) 5 5 5 5
Outdoor 1 RAS 3.0HVRNM2E RAS 4.0HVRNM2E RAS 5.0HVRNM2E RAS 6.0HVRNM2E
Outdoor 3 - RAS 4.0HRNM2E RAS 5.0HRNM2E RAS 6.0HRNM2E
Outdoor Sound Pressure Level dB(A)
Cooling 47 (43) 49 (45) 51 (47) 51 (48)
Heating 49 51 53 53
Dimensions (mm) & Weight (kg)
Height 800 1380
Width 950 950
Depth 370 370
Weight 1/3 67 / - 98 / 98 105 / 105 105 / 105
Operating Range (C)
Cooling (-10 ~ 46)db
Heating (-20 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Length 50 70 75 75
Lift 30 30 30 30
Pre-charged 30 / 40g/m 30 / 60g/m 30 / 60g/m 30 / 60g/m
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - 3Ph 380-415V 50Hz
Power to Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10 < 10 < 10
Running Current (1/3) (A)
Cooling 9.5 / - 12.6 / 4.4 16.1 / 5.1 21.2 / 7.5
Heating 10.2 / - 14.4 / 5.1 16.1 / 5.4 20.2 / 7.2
Recommended Fuse Size (A) (1/3) 20 / - 32 / 16 32 / 16 32 / 16
S Y S T E M
FREE
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Utopia IVX Centrifugal
Outdoor Units
Ceiling Suspended
RPC-FSN2E PC-ART
RPC 3.0FSN2E RPC 5.0FSN2E
Nominal Capacity (Min-Max) (kW)
Cooling 7.1 (1.5 ~ 8.0) 12.5 (4.7 ~ 14.0)
Heating 8.0 (1.5 ~ 9.0) 14.0 (5.0 ~ 16.0)
UK Cooling Capacity (kW)
Total 7.6 13.1
Sensible 5.5 9.4
EER/COP
Cooling 2.70 2.63
Heating 2.62 2.98
Energy Label
Cooling D D
Heating E D
Indoor Sound Pressure Level dB(A) 48/45/42 49/46/41
Indoor Fan (m
3
/min) 21/17/15 35/28/21
Dimensions (mm)
& Weight (kg)
Length 1314 1574
Width 625 625
Depth 163 225
Weight 31 41
Recommended Fuse Size (A) 5 5
RASC-HVRN(M)E
RASC 3.0HVRNE* RASC 5.0HVRNME
Outdoor Sound Pressure Level
dB(A)
Cooling 46 55
Heating 46 56
Dimensions (mm)
& Weight (kg)
Height 430
Width 1250
Depth 1300
Weight 168 176
Outdoor Fan (Min-Nom-Max) (m/min) 34 / 40 / 44 60 / 65/ 69
Static Pressure (Min-Nom-Max) (Pa) 100 / 50 / 15 100 / 50 / 12
Operating Range (C)
Cooling (-5 ~ 46)db
Heating (-15 ~ 15)wb (-15 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8)
Piping (m)
Length 30 70
Lift 30 30
Pre-charged 20 / 60g/m 15 / 60g/m
Power Supply 1 Phase 1Ph 220-240V 50Hz
Power To Outdoor
Interconnecting Cables No. LNE + 2 Core Screened
Starting Current (A) < 10 < 10
Running Current (230v) (A)
Cooling 11.3 22
Heating 11.9 21.6
Recommended Fuse Size (A) 32 40
* 3HP Std. Inverter Centrifugal
S Y S T E M
FREE
Hitachi Utopia IVX Centrifugal
Can be installed inside where circumstances or planning
regulations restrict the use of traditional-style outdoor units
Contact aircon.enquiries@hitachi-eu.com
to nd out more
Hitachi Price List | 37
Features and Benets
Floor Mounted
All RAC Floor Mounted
|ow no|se on|y 20 dBA} |n s|eep mode}
Heat|ng performanoe down to -15O
ambient temperature
Auto restart w|th |ast mode and auto ohangeover
W|re|ess remote oontro||er as standard
Optional simplied hard wired or infra red remote
controller with 7 day timer
Compatible with H-LINK II Control and CS Net Web
controls that integrate with all leading BMS protocols.
RAC Shirokuma Floor Mounted
Oapao|t|es from 2.5kW to 6.5kW
Sty||sh des|gn
Units are available in a variety of colours
to compliment any interior
H|gh 4.31 OOP and 4.30 EER
Nano t|tan|um f|ter
F|ex|b|e mount|ng pos|t|on
The unit comes with a removable stand which gives
the option of mounting it on the wall.
RAC NX2 Floor Mounted
Oapao|t|es from 2.5kW to 6.0kW
Oompaot and sty||sh des|gn
A/A energy effo|enoy rat|ng
Sta|n|ess stee| pre-f|ter |s standard.
Utopia Floor Mounted
Oapao|t|es from 5.0kW to 7.0kW
Oompaot des|gn
The space saving design (620mm in height, 220mm
in depth), ts perfectly into the space below bay
windows and allows the unit to be freely installed
without spoiling the aesthetics of a room
Opt|ona| |ooat|on for remote oontro| sw|toh
It is also possible to conceal the remote controller as
there is space to install a PC-ART inside the casing
var|ab|e a|r d|soharge d|reot|on
Frost proteot|on
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Hitachi Product Catalogue | 39
Product Summary
Shirokuma NX2 Standard Utopia ES
RAF 25 ~ 50FX8 RAF 25 ~ 50NX2
Floor Mounted uncased
RPFI 2.0 ~ 2.5FSN2E
Floor Mounted cased
RPF 2.0 ~ 2.5FSN2E
Nominal Cooling Capacity (kW) 2.5 ~ 5.0 2.5 ~ 5.0 5.0 ~ 6.3 5.0 ~ 6.3
Nominal Heating Capacity (kW) 3.4 ~ 6.5 3.4 ~ 6.0 5.6 ~ 7.0 5.6 ~ 7.0
Refrigerant R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range
1
(Cooling) (db) -10C / +43C -10C / +43C -10C / +43C -10C / +43C
Operating Range (Heating) (wb) -15C / +15C -15C / +15C -15C / +15C -15C / +15C
Std. Remote Controller Type Infra Red Infra Red Wired or Infra Red Wired or Infra Red
Remote Control Timer 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option 24hr or 7 Day Option
Condensate Pump No No No No
Selected Models
Outdoor Units
Floor Mounted
RAC Shirokuma
RAF 25FX8 (W/B) RAF 35FX8 (W/B) RAF 50FX8 (W/B)
Nominal Capacity (Min ~ Max) (kW)
Cooling 2.5 (0.9~3.1) 3.5 (0.9~4.0) 5.0 (0.9~5.2)
Heating 3.4 (0.9~4.4) 4.2 (0.9~5.0) 6.5 (0.9~8.1)
UK Cooling Capacity (kW)
Total 2.4 3.1 4.2
Sensible 1.9 2.5 3.1
EER/COP
Cooling 4.31 3.43 3.21
Heating 4.30 3.69 3.65
Energy Label
Cooling A A A
Heating A A A
Indoor Sound Pressure Level dB(A)
Cooling 38/31/26/20 39/31/26/20 43/36/29/22
Heating 38/31/27/23 39/31/26/20 44/36/29/22
Indoor Fan (m
3
/min)
Cooling 10.5/8.5/6.5/4.5 10.5/8.5/6.5/4.5 11.5/9.0/7.5/5.0
Heating 11.0/9.0/7.0/5.0 11.0/9.0/7.0/5.0 12.0/9.5/8.0/5.5
Dimensions (mm)
& Weight (kg)
Height 590
Width 750
Depth 215
Weight 15
RAC 25FX8 RAC 35FX8 RAC 50FX8
Outdoor Sound Pressure Level dB(A)
Cooling 45 46 50
Heating 47 48 52
Dimensions (mm)
& Weight (kg)
Height 548 600
Width 750 792
Depth 288 299
Weight 35 42
Operating Range (C)
Cooling -10 ~ +43
Heating -15 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
Piping (m)
Length 20 30
Lift 10 10
Pre-charged 20 30
Power Supply 230V 1ph 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened 2 Core Screened 2 Core Screened
Starting Current (A) 4.0 5.8 8.2
Running Current (230v) (A)
Cooling 2.97 4.67 6.85
Heating 3.82 5.58 7.82
Recommended Fuse Size (A) 16 16 16
RAF-FX8 RAR-3U2
RAC-FX8
Hitachi Product Catalogue | 41
RAC NX2
Outdoor Units
Floor Mounted
For RAC accessories see page 49
RAF 25NX2 RAF 35NX2 RAF 50NX2
Nominal Capacity (Min ~ Max) (kW)
Cooling 2.5 (0.9-3.1) 3.5 (0.9-4.0) 5.0 (0.9-5.2)
Heating 3.4 (0.9-4.4) 4.2 (0.9-5.0) 6.0 (0.9-7.3)
UK Cooling Capacity (kW)
Total 2.1 2.9 4.2
Sensible 1.9 2.5 3.2
EER/COP
Cooling 3.57 3.21 3.21
Heating 3.86 3.78 3.61
Energy Label
Cooling A A A
Heating A A A
Indoor Sound Pressure Level dB(A)
Cooling 38/32/26/20 40/32/27/22 44/37/29/26
Heating 38/32/26/20 39/32/26/23 44/37/29/25
Indoor Fan (m
3
/min)
Cooling 9.0/7.7/6.3/5.0 10.0/8.3/6.8/5.5 10.8/8.8/7.2/6.2
Heating 10.0/8.3/6.8/5.3 10.8/9.0/7.3/5.8 12.0/9.5/7.8/6.7
Dimensions (mm)
& Weight (kg)
Height 600
Width 760
Depth 235
Weight 14
RAC 25NX2 RAC 35NX2 RAC 50NX2
Outdoor Sound Pressure Level dB(A)
Cooling 46 47 52
Heating 48 49 52
Dimensions (mm)
& Weight (kg)
Height 505 548 600
Width 700 750 792
Depth 258 288 299
Weight 27 35 40
Operating Range (C)
Cooling -10 ~ +43
Heating -15 ~ +21
Refrigerant Piping (mm) (in)
Liquid 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Gas 9.52 (3/8) 9.52 (3/8) 12.7 (1/2)
Piping (m)
Length 20
Lift 10
Pre-charged 20
Power Supply 230V 1ph 50Hz
Power to Outdoor
Interconnecting Cables No. 2 Core Screened
Starting Current (A) 4.0 5.8 8.2
Running Current (230v) (A)
Cooling 2.97 4.67 6.85
Heating 3.82 5.58 7.82
Recommended Fuse Size (A) 16 16 16
RAF-NX2
RAC-NX2
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
RPFI-FSN2E RPF-FSN2E PC-ART
RAS-HVRN2
Floor Uncased and Floor Cased
RPFI 2.0FSN2E
Uncased
RPF 2.0FSN2E
Cased
RPFI 2.5FSN2E
Uncased
RPF 2.5FSN2E
Cased
Nominal Capacity (Min ~ Max) (kW)
Cooling 5.0 (2.2 ~ 5.6) 5.0 (2.2 ~ 5.6) 6.0 (2.2 ~ 6.3) 6.0 (2.2 ~ 6.3)
Heating 5.6 (2.2 ~ 7.1) 5.6 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1) 7.0 (2.2 ~ 7.1)
UK Cooling Capacity (kW)
Total 5.3 5.3 5.9 5.9
Sensible 3.9 3.9 4.3 4.3
EER/COP
Cooling 3.11 3.11 2.64 2.64
Heating 3.18 3.18 2.84 2.84
Energy Label
Cooling B B D D
Heating D D D D
Sound Pressure Level dB(A) 39/36/32 32/36/39 42/38/34 34/38/42
Indoor Fan (m
3
/min) 16/14/11 11/14/16 16/14/11 11/14/16
Dimensions (mm)
& Weight (kg)
Length 620 630 620 630
Width 1223 1420 1223 1420
Depth 220 220 220 220
Weight 27 33 28 34
Recommended Fuse Size (A) 5 5 5 5
RAS 2.0HVRN2 RAS 2.5HVRN2
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 45 (43) 46 (44)
Heating 47 48
Dimensions (mm)
& Weight (kg)
Height 600 600
Width 792 792
Depth 300 300
Weight 42 42
Operating Range (C)
Cooling (-10 ~ 43)db (-10 ~ 43)db
Heating (-10 ~ 15)wb (-10 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 6.35(1/4) 6.35(1/4)
Gas 12.7(1/2) 12.7(1/2)
Piping (m)
Length 50 50
Lift 30 30
Pre-charged 30 / 30g/m 30 / 30g/m
Power Supply 1Ph 220-240V 50Hz 1Ph 220-240V 50Hz
Power to Outdoor Outdoor
Interconnecting Cables No. LNE + 2 Core Screened LNE + 2 Core Screened
Starting Current (A) < 10 < 10
Running current (A)
Cooling 6.7 9.7
Heating 7.4 10.5
Recommended Fuse Size (A) 16 20
Utopia ES
Outdoor Units
Floor Mounted
S Y S T E M
FREE
Hitachi NX2
With A/A energy rating and capacities from 2.5kW to 6.0kW,
the NX2 oor mount can be installed with RAC Multizone
product ranges for total comfort
Contact aircon.enquiries@hitachi-eu.com
to nd out more
Hitachi Product Catalogue | 43
Features and Benets
Multizone
Multi Split systems
The Hitachi Multizone range was the worlds
rst all-DC Inverter Multisplit system with zone
by zone cooling or heating for up to six rooms.
Hitachi DC scroll and DC twin-rotary compressor,
together with award-winning DC inverter PAM
technology, aid the achievement of a system
power factor of almost 100%, thus providing
unparalleled performance and efciency.
RAC Multizone
H|gh OOP and EER
COP of 4.34 and EER of 4.47
A|r qua||ty
A washable carbon and anti-bacteria air purifying
lter ensures that the micro dust, pollen particles
and odours that can collect on lters can be
easily removed
Oompat|b|||ty
Compatibility between product ranges of outdoor
and indoor units
Ooo||ng operat|on under |ow temperatures
The wide range of units have been designed
for cooling operation under low temperatures,
down to -10C. This feature enables cooling to
be obtained even in winter on buildings with high
internal heat gains due to lighting, people and
machines, particularly in areas such as shops and
lecture rooms. The heating operation under low
temperature, down to -15C can also be performed
Oontro| opt|ons
Infra red remote controller with 24hr timer, simplied
hard wired controller or hard wired remote controller
with built in 7 day timer
Compatible with H-LINK Control/Ready to Connect
to PCS-6RAD Adapter.
Hitachi Product Catalogue | 45
Product Summary
RAM 35QH5
2 Rooms
RAM 52QH5
2 Rooms
RAM 53QH5
3 Rooms
RAM 71QH5
4 Rooms
RAM 90QH5
5 Rooms
RAM 130QH5
6 Rooms
Nominal Cooling Capacity (kW)
3.5
(1.5-4.0)
5.2
(1.5-6.6)
5.2
(1.5-6.6)
7.1
(2.4-8.8)
9.0
(1.5-9.5)
12.6
(1.5-13.2)
Nominal Heating Capacity (kW)
4.2
(1.5-5.0)
6.8
(1.5-7.2)
6.8
(1.5-7.2)
8.6
(2.6-9.5)
11.0
(1.5-11.5)
14.4
(1.5-14.4)
Refrigerant R410A R410A R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range (Cooling) (db) -10C / +43C
Operating Range (Heating) (wb) -15C / +21C
Remote Controller Type Hard Wired or Infra Red
Remote Control Timer 24hr or 7 Day option
Outdoor Units
For full technical details, refer to Technical Manual
RAM 35QH5 RAM 52QH5 RAM 53QH5 RAM 71QH5 RAM 90QH5 RAM 130QH5
Nominal Capacity (Min-Max) (kW)
Cooling 3.5 (1.5 - 4.0) 5.2 (1.5 - 6.6) 5.2 (1.5 - 6.6) 7.1 (2.4 - 8.8) 9.0 (1.5 - 9.5) 12.6 (1.50 - 13.20)
Heating 4.2 (1.5 - 5.0) 6.8 (1.5 - 7.2) 6.8 (1.5 - 7.2) 8.6 (2.8 - 9.5) 11.0 (1.5 - 11.5) 14.4 (1.50 - 14.40)
EER/COP
Cooling 3.72 3.47 3.41 3.32 3.81 3.01
Heating 4.94 3.79 4.03 4.03 4.47 3.79
Energy Label
Cooling A A A A A B
Heating A A A A A A
Maximum Indoor Units 2 2 3 4 5 1, 2, 3 4, 5, 6
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 49(43) 52(45) 52(45) 53(43) 55(46) 55(48)
Heating 51(44) 53(45) 53(45) 56(43) 58(52) 56(48)
Dimensions (mm)
& Weight (kg)
Height 570 650 650 800 800 1450
Width 750 850 850 850 950 855
Depth 280 298 298 298 370 308
Weight 40 50 50 55 71 113
Operating Range (C)
Cooling -10C / 43C (db)
Heating -15C / 21C (wb)
Power Supply AC 1Ph 220-230V 50Hz
Power To Outdoor
Interconnecting Cables No. / Indoors 2 Core Screened
Starting Current (A) 5.8 11 11 14.5 16 20
Running Current (230v) (A)
Cooling 5.7 6.6 6.7 9.4 10.8 19.2
Heating 6.2 7.9 7.4 9.6 11.3 17.4
Recommended Fuse Size (A) 16 16 16 30 30 30
At least two indoor units should be connected (RAM-90QH5)
At least four indoor units should be connected (RAM-130QH5)

RAM-QH5
RAC Multi Split Systems
Indoor Units
Hitachi Product Catalogue | 47
RAC Multi Split Systems
For full technical details, refer to Technical Manual
RAK-QH8(S)
Indoor Unit RAK 18QH8S (W/B)* RAK 25QH8 (W/B) RAK 35QH8 (W/B) RAK 50QH8 (W/B)
Nominal Cooling (kW) 2.0 2.5 3.5 5.0
Nominal Heating (kW) 2.5 3.6 4.5 6.7

Indoor Unit RAI - 25NH5A RAI - 35NH5A RAI - 50NH5A
Nominal Cooling (kW) 2.5 3.5 5.0
Nominal Heating (kW) 3.6 4.5 6.7

RAF-QH8
Indoor Unit RAF 25QH8 (W/B) RAF 35QH8 (W/B) RAF 50QH8 (W/B)
Nominal Cooling (kW) 2.5 3.5 5.0
Nominal Heating (kW) 3.6 4.5 6.7

Indoor Unit RAF - 25NX2 RAF - 35NX2 RAF - 50NX2
Nominal Cooling (kW) 2.5 3.5 5.0
Nominal Heating (kW) 3.6 4.5 6.7

* RAK 18QHS8 can be DIP switched to size 12
RAI-NH5A RAI
RAD-NH7A
Indoor Unit RAD - 18NH7A RAD - 25NH7A RAD - 35NH7A RAD - 50NH7A
Nominal Cooling (kW) 2.0 2.5 3.5 5.0
Nominal Heating (kW) 2.5 3.6 4.5 6.7

RAF-NX2
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Combinations
For full technical details, refer to Technical Manual
Further Control options available see page 86
RAM 35QH5
2 Indoor Units
No.1 No.2
12 12 ~ 35
18 18 ~ 35
25 25 ~ 35

RAM 52QH5
2 Indoor Units
No.1 No.2
12 12 ~ 50
18 18 ~ 50
25 25 ~ 50
35 35 ~ 50

RAM 53QH5
2 Indoor Units 3 Indoor Units
No.1 No.2 No.1 No.2 No.3
12 12 ~ 50 12 12 12 ~ 50
18 18 ~ 50 12 18 18 ~ 50
25 25 ~ 50 12 25 25 ~ 35
35 35 ~ 50 12 35 35
18 18 18 ~ 50
18 25 25 ~ 35
18 35 35
25 25 25 ~ 35

RAM 71QH5
2 Indoor Units 3 Indoor Units 4 Indoor Units
No.1 No.2 No.1 No.2 No.3 No.1 No.2 No.3 No.4
12 12 ~ 50 12 12 12 ~ 50 12 12 12 12 ~ 50
18 18 ~ 50 12 18 18 ~ 50 12 12 18 18 ~ 50
25 25 ~ 50 12 25 25 ~ 50 12 12 25 25 ~ 50
35 35 ~ 50 12 35 35 ~ 50 12 12 35 35 ~ 50
50 50 12 50 50 12 18 18 18 ~ 50
18 18 18 ~ 50 12 18 25 25 ~ 50
18 25 25 ~ 50 12 18 35 35
18 35 35 ~ 50 12 25 25 25 ~ 35
25 25 25 ~ 50 12 25 35 35
25 35 35 ~ 50 18 18 18 18 ~ 50
35 35 35 18 18 25 25 ~ 35
18 18 35 35
18 25 25 25 ~ 35
25 25 25 25 ~ 35

Minimum of 2 indoor units must be connected.
Single unit operation possible.
RAM 90QH5
2 Indoor Units 3 Indoor Units 4 Indoor Units 5 Indoor Units
No.1 No.2 No.1 No.2 No.3 No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.5
18 18~50 18 18 18~50 18 18 18 18~50 18 18 18 18 18~50
25 25~50 18 25 25~50 18 18 25 25~50 18 18 18 25 25~50
35 35~50 18 35 35~50 18 18 35 35~50 18 18 18 35 35~50
50 50 18 50 50 18 18 50 50 18 18 18 50 50
25 25 25~50 18 25 25 25~50 18 18 25 25 25~50
25 35 35~50 18 25 35 35~50 18 18 25 35 35~50
25 50 50 18 25 50 50 18 18 35 35 35
35 35 35~50 18 35 35 35~50 18 25 25 25 25~50
35 50 50 18 35 50 50 18 25 25 35 35~50
50 50 50 25 25 25 25~50 18 25 35 35 35
25 25 35 35~50 25 25 25 25 25~50
25 25 50 50 25 25 25 35 35
25 35 35 35~50 25 25 35 35 35
35 35 35 35~50 - - - - -

RAC Multi Split Systems
Hitachi Product Catalogue | 49
Combinations
Model Code
SPX-RCK3 Wired Remote Controller - WX8, FH6, FH7, YH7, YH5A, NH5A, NH7A, FX8, NX2, QH8
SPX-RCK2 Wireless Remote Controller & Receiver Kit - RAD-NH7A
SPX-WKT1 Wired Remote Controller + 7 Day Timer - WX8, FH6, FH7, YH7, YH5A, NH5A, NH7A, FX8, NX2, QH8
SPX-DST1 Optional Distributor Kit for SPK-WKT1
SPX-WDST8M Optional wiring kit for SPX-WKT1 & SPX-DST1
PSC-6RAD H-LINK Adapter - WX8, FH6, FH7, YH7, YH5A, NH5A, NH7A, FX8, NX2, QH8

RAC Accessories
Model
L TOTAL L MIN L MAX H MAX H INDOOR Piping Pre-charged
(m) (m) (m) (m) (m) Liq. (mm) (in) Gas (mm) (in) (m) / (g/m)
RAM 35QH5 35 5 25 20 5 6.35(1/4) x 2 9.52(3/8) x 2 35 / -
RAM 52QH5 35 5 25 20 5 6.35(1/4) x 2 9.52(3/8) x 2 35 / -
RAM 53QH5 45 5 25 20 5 6.35(1/4) x 3 9.52(3/8) x 3 35 / 20g/m
RAM 71QH5 60 5 25 20 5 6.35(1/4) x 4 9.52(3/8) x 4 30 / 20g/m
RAM 90QH5 75 5 25 20 5 6.35(1/4) x 5 9.52(3/8) x 5 30 / 15g/m
RAM 130QH5
L1
45 5
25
20 5 6.35(1/4) x 3 9.52(3/8) x 3 35 / 20g/m L2
L2 + L3 <35
L3
L4
45 5
25
20 5 6.35(1/4) x 3 9.52(3/8) x 3 35 / 20g/m L5
L5 + L6 <35
L6

|1 + |2 + |3 + |n = | 7O7/|
/|n|m0m o|o|n |en|| oe| |nooo| = | MIN
/ax|m0m o|o|n |en|| oe| |nooo| = | MAX
/ax|m0m |e||| o|//e|ence = | MAX
/ax|m0m |e||| o|//e|ence oe|ween |nooo| = | INDOOR

RAM 130QH5
4 Indoor Units 5 Indoor Units 6 Indoor Units
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
No.1 No.2 No.3 No.4 No.1 No.2 No.3 No.4 No.5 No.1 No.2 No.3 No.4 No.5 No.6
18 18~50 18 18~50 18 18~50 18 18 18~50 18 18 18~50 18 18 18~50
18 25~50 18 25~50 18 18~50 18 25 25~35 18 18 18~50 18 25 25~35
18 35~50 35 35~50 18 18~50 18 35 35 18 18 18~50 18 35 35
25 25~50 25 25~50 18 18~50 25 25 25~35 18 18 18~50 25 25 25~35
35 35~50 35 35~50 25 25~50 18 18 18~50 18 25 25~35 18 18 18~50
25 25~50 18 25 25~35 18 25 25~35 18 25 25~35
25 25~50 18 35 35 18 25 25~35 18 35 35
25 25~50 25 25 25~35 18 25 25~35 25 25 25~35
35 35~50 18 18 18~50 18 35 35 18 18 18~50
35 35~50 18 25 25~35 18 35 35 18 25 25~35
35 35~50 18 35 35 18 35 35 18 35 35
35 35~50 25 25 25~35 18 35 35 25 25 25~35
25 25 25~35 18 18 18~50
25 25 25~35 18 25 25~35
25 25 25~35 18 35 35
25 25 25~35 25 25 25~35

For full technical details, refer to Technical Manual
RAC Multi Split Systems
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
Twin, Triple
and Quad Splits
Utopia ES, Centrifugal and IVX Systems
Utopia ES
Oapao|t|es from 7.1kW to 28.0kW
Oompaot des|gn
The ES range is small and compact;
the units have only one fan (7.0 kW 16kW models)
Oommon appearanoe
Common cabinet size and exterior of the Utopia ES
and Utopia IVX allows for the units to be installed
together creating a uniform appearance
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
Utopia IVX Centrifugal
Oapao|t|es from 7.1kW to 28.0kW
Hitachis range of Utopia Centrifugal units can be
installed indoors with eld supplied ductwork and
are therefore ideal for situations where installations
have to be hidden or where circumstances do not
allow for the use of traditional styled outdoor units
Low temperature operations
Wide working range including outdoor unit fan
control in cooling mode for operating at low ambient
temperature as standard (-5C to 43C cooling)
F|ex|b|e |n|et a|r and out|et a|r opt|on oompat|b|||ty
Compatible with all Hitachi System Free indoor units
lnd|v|dua| oontro| and |mproved oonneot|v|ty
Individual indoor unit control with an increased
number of twins, triple and quad combinations
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols
top|a ser|es oontro|, H-|lNK oonneot|on
H-LINK wiring system requires only two transmission
wires connecting each indoor unit and outdoor unit
for up to 16 refrigerant cycles, and connecting wires
for all indoor units and all outdoor units in series.
Hitachi Product Catalogue | 51
Product Summary
Utopia ES Utopia IVX System Utopia Centrifugal
Twin, Triple & Quad Splits Twin, Triple & Quad Splits Twin, Triple & Quad Splits
Nominal Cooling Capacity (kW) 7.1 ~ 25.0 7.1 ~ 30.0 7.1 ~ 25.0
Nominal Heating Capacity (kW) 8.0 ~ 28.0 8.0 ~ 33.5 8.0 ~ 28.0
Refrigerant R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter
Operating Range (Cooling) (db) -10C / +43C (-15C ~ +46C) db (*) -5C / +43C
Operating Range (Heating) (wb) -15C / +15C (-20C / +15C) wb -15C / +15C
Indoor Unit Type All System Free Indoor units (inc mixed Indoor units on a system)
Remote Controller Type Wired or Infra Red
Remote Control Timer 24hr or 7 Day option
Condenser Air Direction - - Adjustable
(*) -5 3.0~6.0 models
Utopia IVX
Oapao|t|es from 7.1kW to 33.0kW
The Utopia IVX is a very efcient product and is
a further development on its predecessor which
was presented the Shoeene Taishou (Energy
Efciency Award) by the Japanese Government
H|gh OOP and EER
COP of 4.10 and EER of 3.90
Seasona| performanoe
The optimised refrigerant circuit increases seasonal
COP for heating and seasonal EER for cooling by 4%
Oompaot des|gn
The unit uses a horizontal discharge twin fan design
allowing for a more efcient use of oor space
lnd|v|dua| oontro| and |mproved oonneot|v|ty
Individual indoor unit control with an increased
number of twins, triple and quad combinations
(90-115% diversity - 4, 5 and 6HP models)
Oommon appearanoe
Common cabinet size and exterior of the IVX
and Utopia ES allows for the units to be installed
together creating a uniform appearance
Oo|d draft prevent|on
Frost proteot|on
Greater |nsta||at|on fex|b|||ty
The Utopia IVX changes the way we think about twin,
triple and quad split congurations and is the perfect
choice for installations requiring individual unit control
but have no need for the piping length capabilities
available with more expensive VRF systems
More effo|ent oontro|
By the use of individual control we can create a
more comfortable environment for rooms that
have unbalanced loads. This also leads to more
economical operation as units not requiring operation
will stop, reducing wasted energy
Standard hard w|red remote oontro||er w|th bu||t |n
7 day timer
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
Optional integration with all leading BMS protocols.
High-load Area Low-load Area
Indoor Temperature
24C
Set Temp.
24C
Continued Operation
Stopped
Comfortable Comfortable
IVX SYSTEM
Comfortable
Indoor Temperature
25C
RAS-H(V)RNM2E RAS-H(V)RNM2E RAS-HRNM
Utopia IVX
Outdoor 1 RAS 3.0HVRNM2E RAS 4.0HVRNM2E RAS 5.0HVRNM2E RAS 6.0HVRNM2E
Outdoor 3 - RAS 4.0HRNM2E RAS 5.0HRNM2E RAS 6.0HRNM2E
Possible
Combinations
Single 3.0 - 4.0 - 5.0 - 6.0 -
Twin 1.5 1.5
Connected Capacity
90% ~ 115% (3.6 ~ 4.6HP)
Connected Capacity
90% ~ 115% (4.5 ~ 5.8HP)
Connected Capacity
90% ~ 115% (5.4 ~ 6.9HP)
Triple -
Quad - Min Indoor Capacity 0.8HP Min Indoor Capacity 0.8HP Min Indoor Capacity 0.8HP

Utopia IVX RAS 8.0HRNM RAS 10.0HRNM RAS 12.0HRNM
Possible
Combinations
Single 8.0 - - - 10.0 - - - - - - -
Twin
4.0 4.0 - - 6.0 4.0 - - 6.0 6.0 - -
5.0 3.0 - - 5.0 5.0 - - - - - -
Triple
3.0 3.0 3.0 - 3.0 3.0 3.0 - 4.0 4.0 4.0 -
3.0 3.0 2.5 - 4.0 3.0 3.0 - -
3.0 2.5 2.5 - - -
3.0 3.0 2.3 - - -
Quad
2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0
2.5 2.5 2.0 2.0 3.0 3.0 2.5 2.0 4.0 3.0 3.0 2.5
2.5 2.0 2.0 2.0 3.0 2.5 2.5 2.5 4.0 3.0 2.5 2.5
2.5 2.5 1.8 1.8 3.0 3.0 2.0 2.0 3.0 3.0 3.0 2.5
2.5 2.3 1.8 1.8 3.0 2.5 2.5 2.0 3.0 3.0 2.5 2.5
2.5 2.0 2.0 1.8 3.0 3.0 2.3 2.3 4.0 4.0 2.3 2.3
2.3 2.3 1.8 1.8 3.0 3.0 2.3 2.0 4.0 3.0 3.0 2.3
2.3 2.0 2.0 1.8 3.0 2.5 2.5 2.3 4.0 3.0 2.5 2.3

Twin, Triple and Quad Splits | ES
Utopia Split Systems
Utopia ES
Outdoor 1 RAS 3.0HVRNS2 RAS 4.0HVRNS2E RAS 5.0HVRNS2E RAS 6.0HVRNS2E - -
Outdoor 3 - RAS 4.0HRNS2E RAS 5.0HRNS2E RAS 6.0HRNS2E RAS 8.0HRNSE RAS 10.0HRNSE
Possible
Combinations
Single 3.0 - 4.0 - 5.0 - 6.0 - - 8.0 - 10.0 -
Twin
1.5 1.5 2.0 2.0 2.5 2.5 3.0 3.0 - 4.0 4.0 5.0 5.0
- 2.0 2.0 2.5 2.5 3.0 2.5 - -
- 2.3 2.0 3.0 2.3 - -
- 2.5 1.8 3.0 1.8 - -
Triple
- 2.5 2.0 1.8 1.8 1.8 3.0 3.0 3.0 - -
- - - 2.0 2.0 2.0 - -
- - - 2.0 2.0 1.8 - -
- - - 2.0 1.8 1.8 - -
- - - 2.5 1.5 1.5 - -
Quad - - - 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5

RAS-HVRNS2 RAS-HVRNS2E RAS-HRNSE
Twin, Triple and Quad Splits | IVX
For full technical details, refer to Technical Manual.
Please refer to individual product pages for dimensional data.
Hitachi Product Catalogue | 53
Utopia Split Systems
Twin, Triple and Quad Splits | IVX Centrifugal
RASC-H(V)RN(M)E
Utopia
Centrifugal
Outdoor 1 RASC 3.0HVRNE RASC 5.0HVRNME -
Outdoor 3 - - RASC 10.0HRNME
Possible
Combinations
Single 3.0 - 5.0 - - - 10.0 -
Twin
1.5 1.5 2.5 2.5 - - 6.0 4.0
- 3.0 2.3 - - 5.0 5.0
- - - - - 8.0 2.0
Triple
- 1.8 1.8 1.5 - 3.0 3.0 3.0 -
- - 4.0 3.0 3.0 -
Quad
- - 2.5 2.5 2.5 2.5
- - 3.0 3.0 2.5 2.0
- - 3.0 2.5 2.5 2.5
- - 3.0 3.0 2.0 2.0
- - 3.0 2.5 2.5 2.0
- - 3.0 3.0 2.3 2.3
- - 3.0 3.0 2.3 2.0
- - 3.0 2.5 2.5 2.3
* 3HP Std. Inverter Centrifugal

For full technical details, refer to Technical Manual.
Please refer to individual product pages for dimensional data.
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
System Free Indoor Units
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0
Size 20 25 - 35 42 50 60 - 71 100
Wall Mounted RPK-FSN2M
Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0 5.7 6.3 7.1 10.0
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6 6.4 7.0 8.0 11.2
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3 5.5 5.9 7.5 10.6
UK Sensible Cooling (kW) 1.5 1.9 2.3 2.7 3.1 3.8 4.1 4.4 5.6 7.5

RPK-FSN2M
Twin, Triple and Quad Splits
RCD-FSN2
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0 5.0
Size 20 25 - 35 42 50 60 - 71 100 125
2-Way Cassette RCD-FSN2
(including grille) Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0 5.7 6.3 7.1 10.0 12.5
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6 6.4 7.0 8.0 11.2 14.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3 5.5 5.9 7.5 10.6 13.1
UK Sensible Cooling (kW) 1.7 2.1 2.3 2.7 3.2 4.0 4.1 4.4 5.6 7.7 9.0

HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0
Size 20 25 - 35 42 50 60 - 71 100 125 140
4-Way Cassette RCI-FSN3E
(including grille) Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0 5.7 6.3 7.1 10.0 12.5 14.0
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6 6.4 7.0 8.0 11.2 14.0 16.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3 5.5 5.9 7.5 10.6 13.1 15.6
UK Sensible Cooling (kW) 1.7 2.1 2.5 2.8 3.4 4.1 4.0 4.3 5.9 8.3 9.7 11.4

HP 0.8 1.0 1.3 1.5 1.8 2.0
Size 20 25 - 35 42 50
Mini 4-Way
Cassette
RCIM-FSN2
Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0
(including grille)
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3
UK Sensible Cooling (kW) 1.6 1.9 2.4 2.7 3.1 3.8

RCIM-FSN2
RCI-FSN3E
S Y S T E M
FREE
Capacity achieved via dip switch setting capacity range (HP) Model allows dipswitch adjustment
+
For full technical details, refer to Technical Manual. Please refer to individual product pages for dimensional data.
Hitachi Product Catalogue | 55
RPIM-FSN2E RPI-FSN2E
HP 0.8 1.0 1.3 1.5
Size 20 25 - 35
Mini
In the Ceiling
RPIM-FSN2E
(Slim Width) Nominal Cooling (kW) 1.9 2.5 3.0 3.6
Nominal Heating (kW) 2.2 2.8 3.4 4.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7
UK Sensible Cooling (kW) 1.7 2.1 2.3 2.6

HP 0.8 1.0 1.3 1.5
Size 20 25 - 35
In the Ceiling RPI-FSN2E
(Low Height) Nominal Cooling (kW) 1.9 2.5 3.0 3.6
Nominal Heating (kW) 2.2 2.8 3.4 4.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7
UK Sensible Cooling (kW) 1.7 2.1 2.3 2.7

HP 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0
Size 42 50 60 - 71 100 125 140
Ceiling RPC-FSN2E
Suspended Nominal Cooling (kW) 4.4 5.0 5.7 6.3 7.1 10.0 12.5 14.0
Nominal Heating (kW) 5.0 5.6 6.4 7.0 8.0 11.2 14.0 16.0
UK Total Cooling (kW) 4.3 5.3 5.5 5.9 7.5 10.6 13.1 15.6
UK Sensible Cooling (kW) 3.1 3.8 4.0 4.2 5.4 7.6 9.4 11.2

RPC-FSN2E
HP 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0 8.0 10.0
Size 42 50 60 - 71 100 125 140 200 250
In the Ceiling RPI-FSN3E
(Standard) Nominal Cooling (kW) 4.4 5.0 5.7 6.3 7.1 10.0 12.5 14.0 20.0 25.0
Nominal Heating (kW) 5.0 5.6 6.4 7.0 8.0 11.2 14.0 16.0 22.4 28.0
UK Total Cooling (kW) 4.3 5.3 5.5 5.9 7.5 10.6 13.1 15.6 18.0 22.0
UK Sensible Cooling (kW) 3.3 4.0 4.2 4.5 5.6 7.7 9.4 11.2 13.9 17.4

RPI-FSN3E
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5
Size 20 25 - 35 42 50 60 -
Floor Mounted RPFI-FSN2E
Uncased Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0 5.7 6.3
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6 6.4 7.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3 5.5 5.9
UK Sensible Cooling (kW) 1.5 1.9 2.3 2.7 3.1 3.9 4.0 4.3

RPFI-FSN2E
System Free Indoor Units
Twin, Triple and Quad Splits
S Y S T E M
FREE
Capacity achieved via dip switch setting capacity range (HP) Model allows dipswitch adjustment
+
For full technical details, refer to Technical Manual. Please refer to individual product pages for dimensional data.
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Model Description
PC-ART Standard Wired Remote Controller (inc. 7 Day Time Clock)
PC-ARF Wired LED Controller with advanced graphical interface (inc 7 Day Time Clock)
PC-ARH Simple Wired Remote Controller
PC-LH3A Wireless Remote Controller (Receiver kit required inc. with RPK-FSN2M)
PC-ALHN Receiver Kit panel mounted (RCI-FSN3E)
PC-ALHD Receiver Kit panel mounted (RCD-FSN2)
PC-ALHC Receiver Kit panel mounted (RCIM-FSN2)
PC-ALHZ Receiver Kit wall mounted (All System Free Indoor Units)
TE-03N Twin Pipe Kit (3HP System)
TE-04N Twin Pipe Kit (4HP System)
TE-56N Twin Pipe Kit (5 & 6HP System)
TE-08N Twin Pipe Kit (8HP System)
TE-10N Twin Pipe Kit (10 & 12HP System)
TRE-06N Triple Pipe Kit (4 ~ 6HP System)
TRE-810N Triple Pipe Kit (8 ~ 12HP System)
QE-810N Quad Pipe Kit (8 ~ 12HP System)
E-102SN2 Piping Kit (Only use with 8 ~ 12HP Utopia IVX)
E-162SN2 Piping Kit (Only use with 8 ~ 12HP Utopia IVX)

RPF-FSN2E
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5
Size 20 25 - 35 42 50 60 -
Floor Standard RPF-FSN2E
Cased Nominal Cooling (kW) 1.9 2.5 3.0 3.6 4.4 5.0 5.7 6.3
Nominal Heating (kW) 2.2 2.8 3.4 4.0 5.0 5.6 6.4 7.0
UK Total Cooling (kW) 2.1 2.6 3.2 3.7 4.3 5.3 5.5 5.9
UK Sensible Cooling (kW) 1.5 1.9 2.3 2.7 3.1 3.9 4.0 4.3

System Free Indoor Units
Twin, Triple and Quad Splits
System Free Accessories
For full technical details, refer to Technical Manual.
For centralised controllers and BMS interfaces see page 88
S Y S T E M
FREE
Capacity achieved via dip switch setting capacity range (HP) Model allows dipswitch adjustment
+
For full technical details, refer to Technical Manual. Please refer to individual product pages for dimensional data.
Hitachi Product Catalogue | 57
Utopia AHU Interface
Control Box EXV-2.0E1* EXV-2.5E1* EXV-3.0E1* EXV-4.0E1* EXV-5.0E1* EXV-6.0E1* EXV-8.0E1* EXV-10.0E1*
Dimensions (mm)
& Weight (kg)
Height 291
Width 241
Depth 87
Weight 3.2 3.5
Power Supply 1 Phase 1Ph 220-240V 50Hz
Allowed Fan Current (A) 2.5 15
Expansion Valve Box EXV-2.0E1* EXV-2.5E1* EXV-3.0E1* EXV-4.0E1* EXV-5.0E1* EXV-6.0E1* EXV-8.0E1* EXV-10.0E1*
Dimensions (mm)
& Weight (kg)
Height 431
Width 199
Depth 103
Weight 2.7 4.5
Note:- lnclude PC-ART Remote Controller if feld supplied thermostats are not to be used.
* New model - only available when existing stock is sold.
For full technical details, refer to Technical Manual
Outdoor Unit
DX-Kit
Allowed Heat Exchanger Capacity (kW) Heat Exchanger Volume (dm3)
Utopia IVX Utopia ES Code Mode Nominal Min Max Min Max
- RAS 2HVRN2 EXV-2.0E
Cooling 5.0 4.0 5.6
0.57 1.16
Heating 5.6 4.5 7.1
- RAS 2.5HVRN2 EXV-2.5E
Cooling 6.0 4.8 6.3
0.89 1.35
Heating 7.0 5.6 7.1
RAS 3HVRNM2E RAS 3HVRNS2 EXV-3.0E
Cooling 7.1 5.7 8.0
1.03 1.57
Heating 8.0 6.4 9.0
RAS 4H(V)RNM2E RAS 4H(V)RNS2E EXV-4.0E
Cooling 10.0 8.0 11.2
1.51 2.37
Heating 11.2 9.0 12.5
RAS 5H(V)RNM2E RAS 5H(V)RNS2E EXV-5.0E
Cooling 12.5 10.0 14.0
1.92 2.37
Heating 14.0 11.2 16.0
RAS 6H(V)RNM2E RAS 6H(V)RNS2E EXV-6.0E
Cooling 14.0 11.2 16.0
1.92 2.92
Heating 16.0 12.8 18.0
RAS 8HRNM RAS 8HRNS EXV-8.0E
Cooling 20.0 16.0 22.4
2.92 3.89
Heating 22.4 17.9 25.0
RAS 10HRNM RAS 10HRNS EXV-10.0E
Cooling 25.0 20.0 28.0
3.89 4.76
Heating 28.0 22.4 31.5
Twin, Triple and Quad Splits
Features and Benets
Set Free VRF Systems
Control Systems
Mini
2-pipe
FS(V)N(Y)(2)(E.)
Sideow
2-pipe
FSNM
Modular
2-pipe
FSXN
Modular
3-pipe
FSXN
Nominal Cooling Capacity (kW) 8.0 ~ 16.0 22.4 ~ 33.5 22.4 ~ 150.0 22.4 ~ 150.0
Nominal Heating Capacity (kW) 9.0 ~ 18.0 25.0 ~ 37.5 25.0 ~ 165.0 25.0 ~ 165.0
Power Supply 1 / 3 3 3 3
Refrigerant R410A R410A R410A R410A
Capacity Control DC-Inverter DC-Inverter DC-Inverter DC-Inverter
Operating Range (Cooling) (db) -5C / +43C -15C / +43C -5C / +43C -5C / +43C
Operating Range (Heating) (wb) -20C / +15C -20C / +15C -15C / +15C -20C / +15C
Connection Ratio 50 ~ 130% 50 ~ 130% 50 ~ 130% 50 ~ 130%
Indoor Unit Quantity 1 ~ 9 1 ~ 10 1 ~ 64 1 ~ 64
Indoor Unit Type All System Free Indoor Units
Control Systems Individual, groups, centralised and BMS
All Set Free VRF Systems
Oomfort proteot|on funot|on - a||ows degree po|nt off
coil temperature setting on all indoor units
DO lnverter teohno|ogy
|ow no|se
|ong p|pe runs
System Free |ndoor un|ts and oontro|s aoross the
whole range
Power sav|ng demand oontro| for reduoed peak
loads and energy savings
Frost proteot|on
N|ght set baok mode
Oontro| opt|ons
Individual control options are Infra red remote
controller with 24hr timer, simplied hard wired
controller or hard wired remote controller with built
in 7-day timer.
FS(V)(Y)N2E Mini 2-pipe
Oapao|t|es from 8.0kW to 18.0kW
Oompaot des|gn
H|gh OOP and EER
COP of 4.14 and EER of 4.07.
Hitachi Product Catalogue | 59
FSNM Sidefow 2-pipe
Oapao|t|es from 22.4kW to 37.5kW
lnd|v|dua| oontro|
Any combination of 10 System Free indoor
units with a total diversity of 50-130% can be
individually controlled
Oompaot des|gn
The unit uses a horizontal discharge twin fan design
allowing for more efcient use of oor space.

FSXN Modular 2 or 3-pipe
Oapao|t|es from 22.4kW to 165.0kW
||ghtwe|ght and modu|ar 2-p|pe heat pump or
3-pipe heat recovery to suit customer requirements
Two highly-effective heat pump systems in one unit:
A two-pipe system for open plan environments and
a three-pipe system for individual spaces, allowing
your customers to tailor their air conditioning needs
to meet a diverse range of building requirements
|ow no|se
Select from 3 settings with up to 8dB noise reduction.
Hitachi FSXN VRF
Offer 2-pipe and 3-pipe options from a single unit for
air conditioning that can be tailored to meet changing
building requirements
Visit hitachiaircon.com/tomorrow
to nd out more
RAS-FSVNE
Mini 2-pipe
Outdoor 1 RAS-3FSVNE RAS-4FSVN2E RAS-5FSVN2E RAS-6FSVN2E
Outdoor 3 - RAS-4FSNY2E RAS-5FSNY2E RAS-6FSNY2E
Nominal Capacity (kW)
Cooling 8.0 11.2 14.0 15.5
Heating 9.0 12.5 16.0 18.0
UK Cooling Capacity (kW) Total 7.4 10.4 13.0 14.4
EER/COP
Cooling 3.54 4.07 3.61 3.32
Heating 3.59 4.14 3.81 3.67
Maximum number of Indoor Units No. 4 6 8 9
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 45 (41) 49 (45) 51 (47) 51 (48)
Heating 47 51 53 53
Dimensions (mm)
& Weight (kg)
Height 800 1380
Width 850 950
Depth 315 370
Weight 66 97 97 97
Operating Range (C)
Cooling -5C / +43C (db) -5C / +46C (db)
Heating -20C / +15C (wb)
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8)
Piping (m)
Total Length 65 125 125 125
Lift 25 30 30 30
Pre-charged Calculate Calculate Calculate Calculate
Power Supply
1 220-240V 50Hz
- 3Ph 380-415V 50Hz
Starting Current (1/3) (A) 7.0 / - 10.5 / 5.0 15.0 / 5.0 15.0 / 5.0
Running Current (1/3) (A)
Cooling 9.6 / - 12.2 / 4.1 17.2 / 5.8 20.7 / 7.0
Heating 10.7 / - 13.4 / 4.6 18.6 / 6.3 21.7 / 7.4
Recommended Fuse Size (1/3) (A) 25 / - 25 / 16 32 / 16 32 / 16
RAS 8FSNM RAS 10FSNM RAS 12FSNM
Nominal Capacity (kW)
Cooling 22.4 28.0 33.5
Heating 25.0 31.5 37.5
UK Cooling Capacity (kW) Total 20.8 26.0 31.2
EER/COP (Outdoor Only)
Cooling 3.56 3.37 3.13
Heating 4.24 4.04 3.79
Maximum number of Indoor Units No. 10 10 10
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 53 (50) 56 (53) 59 (55)
Heating 55 58 55
Dimensions (mm)
& Weight (kg)
Height 1650
Width 1100
Depth 390
Weight 170 170 173
Operating Range (C)
Cooling (-5 ~ 43)db
Heating (-20 ~ 15)wb
Refrigerant Piping (mm) (in)
Liquid 9.52(3/8) 12.7(1/2) 12.7(1/2)
Gas 19.05 (3/4) 22.20 (7/8) 22.20 (7/8)
Piping (m)
Total Length 250 250 250
Lift 40 40 40
Pre-charged Calculate Calculate Calculate
Power Supply 3 380-415V 50Hz
Starting Current (A) 8 8 8
Running Current (A)
Cooling 9.4 12.4 15.8
Heating 8.8 11.7 14.7
Recommended Fuse Size (A) 16 20 25
RAS FSNM
RAS-FS(V)(Y)N2E
Sideow 2-pipe
Set Free VRF Systems
Hitachi Product Catalogue | 61
For full technical details, refer to Technical Manual hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Modular
Set Free VRF Systems
RAS 8FSXN RAS 10FSXN RAS 12FSXN RAS 14FSXN RAS 16FSXN RAS 18FSXN
Nominal Capacity (kW)
Cooling 22.4 28.0 33.5 40.0 45.0 50.0
Heating 25.0 31.5 37.5 45.0 50.0 56.0
UK Cooling Capacity (kW) Total 19.3 24.1 28.8 34.4 38.7 43.0
EER/COP (Outdoor)
Cooling 3.85 3.79 3.41 3.25 3.23 3.37
Heating 4.17 4.11 3.60 3.89 3.90 3.81
Maximum number of Indoor Units No. 13 16 19 23 26 26
Outdoor Sound Pressure Level
(Set Back) dB(A)
Cooling 58 (53) 58 (53) 60 (55) 62 (57) 62 (57) 63 (58)
Dimensions (mm)
& Weight (kg)
Height 1720 1720 1720 1720 1720 1720
Width 950 950 950 1210 1210 1210
Depth 765 765 765 765 765 765
Weight 225 225 225 315 315 335
Operating Range (C)
Cooling -5C / +43C
Heating -20C / +15C
Refrigerant Piping (mm) (in)
Liquid 9.53 (3/8) 9.53 (3/8) 12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 15.88 (5/8)
Gas 19.05 (3/4) 22.22 (7/8) 28.57 (1 1/8) 28.57 (1 1/8) 28.57 (1 1/8) 28.57 (1 1/8)
Piping (m)
Max. Length 1000 1000 1000 1000 1000 1000
Lift 50 50 50 50 50 50
Pre-charged Calculate Calculate Calculate Calculate Calculate Calculate
Power Supply 3 380-415V 50Hz
Starting Current (A) 8 8 8 95 95 113
Running Current (A)
Cooling 9.3 11.9 15.7 20.2 22.6 24.1
Heating 9.6 12.3 16.7 18.8 20.8 23.8
Recommended Fuse Size (A) 16 20 25 32 32 32
Model RAS 20FSXN RAS 22FSXN RAS 24FSXN RAS 26FSXN RAS 28FSXN RAS 30FSXN
Combinations
RAS 8FSXN RAS 8FSXN RAS 10FSXN RAS 12FSXN RAS 14FSXN RAS 14FSXN
RAS 12FSXN RAS 14FSXN RAS 14FSXN RAS 14FSXN RAS 14FSXN RAS 16FSXN
Model RAS 32FSXN RAS 34FSXN RAS 36FSXN RAS 38FSXN RAS 40FSXN RAS 42FSXN
Combinations
RAS 16FSXN RAS 16FSXN RAS 18FSXN RAS 12FSXN RAS 12FSXN RAS 12FSXN
RAS 16FSXN RAS 18FSXN RAS 18FSXN RAS 12FSXN RAS 12FSXN RAS 12FSXN
- - - RAS 14FSXN RAS 16FSXN RAS 18FSXN
Model RAS 44FSXN RAS 46FSXN RAS 48FSXN RAS 50FSXN RAS 52FSXN RAS 54FSXN
Combinations
RAS 12FSXN RAS 12FSXN RAS 12FSXN RAS 14FSXN RAS 16FSXN RAS 18FSXN
RAS 14FSXN RAS 16FSXN RAS 18FSXN RAS 18FSXN RAS 18FSXN RAS 18FSXN
RAS 18FSXN RAS 18FSXN RAS 18FSXN RAS 18FSXN RAS 18FSXN RAS 18FSXN
Combinations
For full technical details, refer to Technical Manual
RAS FSXN
Hitachi Product Catalogue | 63
System free Indoor Units
Set Free VRF Systems
RCD-FSN2
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0 5.0
Size 20 25 32 40 - 50 - 63 71 100 125
2-Way Cassette RCD-FSN2
(including grille) Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6 6.5 7.1 8.0 11.2 14.0
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3 7.8 8.5 9.0 12.5 16.0
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2 6.0 6.4 7.5 10.5 12.7
UK Sensible Cooling (kW) 1.7 2.1 2.5 2.8 3.2 3.9 4.4 4.7 5.6 7.7 8.8

RCI-FSN3E
HP 0.8 1.0 1.3 1.5 1.8 2.0
Size 20 25 32 40 - 50
Mini 4-Way Cassette RCIM-FSN2
(including grille) Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2
UK Sensible Cooling (kW) 1.6 1.9 2.5 2.9 3.1 3.7

HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0
Size 20 25 32 40 - 50 - 63 71 100 125 140
4-Way Cassette RCI-FSN3E
(including grille) Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6 6.5 7.1 8.0 11.2 14.0 16.0
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3 7.8 8.5 9.0 12.5 16.0 18.0
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2 6.0 6.4 7.5 10.5 12.7 14.8
UK Sensible Cooling (kW) 1.7 2.1 2.6 3.0 3.4 4.1 4.4 4.7 5.9 8.2 9.4 10.8

CH-6.0N1 CH-10.0N1
Nominal Capacity HP HP 6 6 < HP 10
Maximum number of Indoor Units - 7 8
Input power Watts 20 20
Dimensions (mm)
& Weight (kg)
Height 191 191
Width 301 301
Depth 214 214
Weight 7 7
Refrigerant - R410A (charged with nitrogen to avoid corrosion)
Refrigerant pipe connections Flared connections with nuts and/or ange (factory-supplied)
Refrigerant lines
from the outdoor unit(
1
)
Low pressure 15.88mm (5/8") ~ 19.05mm (3/4") 19.05mm (3/4") ~ 22.2mm (7/8")
High pressure 12.7mm (1/2") ~ 15.88mm (5/8") 15.88mm (5/8") ~ 19.05mm (3/4")
Refrigerant lines
from the indoor unit(
1
)
Liquid line As appropriate for indoor unit capacity (bypasses CH Box)
Gas line 12.7mm (1/2") ~ 15.88mm (5/8") 19.05mm (3/4") ~ 22.2mm (7/8")
CH Boxes
For full technical details, refer to Technical Manual
RCIM-FSN2
S Y S T E M
FREE
Capacity available with dip switch setting capacity range (HP) Adjustable by dipswitch setting
+
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full technical details, refer to Technical Manual For our full range of controls and accessories see pages 88 and 89.
System free Indoor Units
Set Free VRF Systems
RPI-FSN2E
HP 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0 8.0 10.0
Size - 50 - 63 71 100 125 140 200 250
In the Ceiling RPI-FSN3E
(Standard) Nominal Cooling (kW) 5.0 5.6 6.5 7.1 8.0 11.2 14.0 16.0 22.4 28.0
Nominal Heating (kW) 5.7 6.3 7.8 8.5 9.0 12.5 16.0 18.0 25.0 31.0
UK Total Cooling (kW) 4.3 5.2 6.0 6.4 7.5 10.5 12.7 14.8 18.4 22.9
UK Sensible Cooling (kW) 3.3 4.0 4.6 4.9 5.6 7.7 9.1 10.7 14.2 18.1

RPI-FSN3E
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 4.0
Size 20 25 32 40 - 50 - 63 71 100
Wall Mounted RPK-FSN2M
Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6 6.5 7.1 8.0 11.2
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3 7.8 8.5 9.0 12.5
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2 6.0 6.4 7.5 10.5
UK Sensible Cooling (kW) 1.5 1.9 2.5 2.8 3.1 3.7 4.5 4.8 5.6 7.5

RPK-FSN2M
HP 0.8 1.0 1.3 1.5
Size 20 25 32 40
Mini In The Ceiling RPIM-FSN2E
(Slim Width) Nominal Cooling (kW) 2.2 2.8 3.8 4.0
Nominal Heating (kW) 2.5 3.2 4.3 4.8
UK Total Cooling (kW) 2.1 2.6 3.4 3.9
UK Sensible Cooling (kW) 1.7 2.1 2.4 2.8

RPIM-FSN2E RPIM FSN E
HP 0.8 1.0 1.3 1.5
Size 20 25 32 40
In the Ceiling RPI-FSN2E
(Low Height) Nominal Cooling (kW) 2.2 2.8 3.8 4.0
Nominal Heating (kW) 2.5 3.2 4.3 4.8
UK Total Cooling (kW) 2.1 2.6 3.4 3.9
UK Sensible Cooling (kW) 1.7 2.1 2.4 2.8

HP 1.8 2.0 2.3 2.5 3.0 4.0 5.0 6.0
Size - 50 - 63 71 100 125 140
Ceiling Suspended RPC-FSN2E
Nominal Cooling (kW) 5.0 5.6 6.5 7.1 8.0 11.2 14.0 16.0
Nominal Heating (kW) 5.7 6.3 7.8 8.5 9.0 12.5 16.0 18.0
UK Total Cooling (kW) 4.3 5.2 6.0 6.4 7.5 10.5 12.7 14.8
UK Sensible Cooling (kW) 3.1 3.7 4.3 4.6 5.4 7.6 9.1 10.7

RPC-FSN2E
S Y S T E M
FREE
Capacity available with dip switch setting capacity range (HP) Adjustable by dipswitch setting
+
Hitachi Product Catalogue | 65
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5
Size 20 25 32 40 - 50 - 63
Floor Mounted RPFI-FSN2E
Uncased Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6 6.5 7.1
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3 7.8 8.5
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2 6.0 6.4
UK Sensible Cooling (kW) 1.5 1.9 2.5 2.8 3.1 3.8 4.4 4.7

RPFI-FSN2E
RPF-FSN2E
HP 0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5
Size 20 25 32 40 - 50 - 63
Floor Mounted RPF-FSN2E
Cased Nominal Cooling (kW) 2.2 2.8 3.8 4.0 5.0 5.6 6.5 7.1
Nominal Heating (kW) 2.5 3.2 4.3 4.8 5.7 6.3 7.8 8.5
UK Total Cooling (kW) 2.1 2.6 3.4 3.9 4.3 5.2 6.0 6.4
UK Sensible Cooling (kW) 1.5 1.9 2.5 2.8 3.1 3.8 4.4 4.7

System free Indoor Units
Set Free VRF Systems
For full technical details, refer to Technical Manual
Model
PC-ART
Standard Wired
Remote Controller
(inc. 7 Day Time Clock)
PC-ARF
Wired LED Controller with
advanced graphical interface
(inc 7 Day Time Clock)
PC-ARH
Simple Wired
Remote Controller
PC-LH3A
Wireless Remote Controller
(Receiver kit required inc. with
RPK-FSN2M)
PC-ALHN
Receiver Kit panel
mounted (RCI-FSN3E)
PC-ALHD
Receiver Kit panel
mounted (RCD-FSN3E)
PC-ALHC
Receiver Kit panel
mounted (RCIM-FSN3E)
PC-ALHZ
Receiver Kit wall mounted
(All System Free Indoor Units)

System Free Accessories / Pipe Kits
Pipe Kits
(Set Free - Mini, Side Flow, Modular)
E-102SN2 Pipe Kit (2-pipe)
E-162SN2 Pipe Kit (2-pipe)
E 242SN2 Pipe Kit (2-pipe)
E 302SN2 Pipe Kit (2-pipe)
E 52XN2 Pipe Kit (3-pipe)
E 102XN2 Pipe Kit (3-pipe)
E 162XN2 Pipe Kit (3-pipe)
E 202XN2 Pipe Kit (3-pipe)
E 242XN2 Pipe Kit (3-pipe)
E 322XN2 Pipe Kit (3-pipe)
MH 84AN Pipe Kit (2-pipe header)
MH 108AN Pipe Kit (2-pipe header)
MH 108XN Pipe Kit (3-pipe header)

S Y S T E M
FREE
Capacity available with dip switch setting capacity range (HP) Adjustable by dipswitch setting
+
HP 1.5 2.0 2.5
Size 40 50 63
m/hr 500 800 1000
Active KPI KPI-X3E
Nominal Cooling (kW) 5.3 8.0 10.8
Nominal Heating (kW) 6.9 9.8 12.9
Coil Cooling Cap. (kW) 1.8 2.9 3.7
Coil Heating Cap. (kW) 2.1 3.5 4.4

Pipe Kits
(Set Free - Mini, Side Flow, Modular)
MC 20AN
Modular Set Free
2-pipe Branch Kit
(RAS 20~24FSXN)
MC 21AN
Modular Set Free
2-pipe Branch Kit
(RAS 26~36FSXN)
MC 30AN
Modular Set Free
2-pipe Branch Kit
(RAS 28~54FSXN)
MC 20XN
Modular Set Free
3-pipe Branch Kit
(RAS 20~24FSXN)
MC 21XN
Modular Set Free
3-pipe Branch Kit
(RAS 26~36FSXN)
MC 30XN
Modular Set Free
3-pipe Branch Kit
(RAS 28~54FSXN)

NEW
Available from June 2012
Provisional Data
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Close Control
Features and Benets
Twin DC Inverter
Specically designed and developed to provide
a suitable environment for server and computer
rooms, telecommunications facilities and data
centres, where a need for high sensible cooling
and close control of temperature is required.
Spaoe sav|ng outdoor un|t w|th fex|b|e oonfgurat|on
Fu|| |nverter oontro| prov|d|ng unr|va||ed energy sav|ngs
H|gh sens|b|e heat des|gn -
saving energy by reducing humidication
Head pressure oontro|
lnsta||at|on fex|b|||ty w|th extended p|p|ng |engths -
up to 160m with 70m* height difference
* special order
Hitachi Product Catalogue | 67
Indoor Unit Outdoor Unit
RP 20ACRN RCR 20ACN
Nominal Capacity (kW) 56.6
Sensible Cooling Capacity (kW) 56
Sound Pressure Level (Set Back) dB(A) 60 57 (54)
Dimensions (mm)
& Weight (kg)
Height 1900 1980
Width 2145 1800
Depth 900 900
Weight 925 410
Fan
Model & Quantity Multi Blade Centrifugal x 2 Propeller x 2
Nominal Air Flow Rate (m/min) 350 300
Static Pressure (Pa) 120 (Max. 300) 0 (60)
(*1)
Air Inlet Upper Side Lower Side (Front Side: Optional
(*2)
)
Air Outlet Lower Side Upper Side
Operating Range (C) -15C ~ +43C
Refrigerant Piping (mm) (in)
Liquid 12.7 (1/2) x 2 (Equivalent piping > than 120m: 15.88 (5/8) x 2)
Gas 19.05 (3/4) x 2 (Equivalent piping > than 120m: 22.22 (7/8) x 2)
Direction Bottom (Top - Optional)
(*3)
Bottom or Front or Rear
Piping (m)
Max. Equivalent 185
Max. Length 160
Lift 40 (70 special order)
(*4)
Pre-charged 50
Power Supply 3 380~415V 50Hz
Starting Current (A) Less than Running Current (Maximum Running Current: 49.5A)
Running Current (A) 31.7
Recommended Fuse Size (A) TBC TBC
NOTES:
1. The performance is indicated when the unit is operated under the following conditions:
Indoor Inlet Air Temperature: 27C DB, 19C WB Outdoor Inlet Air Temperature: 35C DB;
Refrigerant Piping Length: 5m (one-way, installed horizontally) at rated compressor frequency
2. The sound pressure level is indicated the value (A scale) measured under the following conditions:
Measurement Points Indoor Unit: 1m from unit front surface, 1m from oor level
Measurement Points Outdoor Unit: 1m from unit front surface, 1.5m from oor level
The above data was measured in an anechoic room, so that reected sound should be taken into consideration in the eld.
In the case that air inlet port is provided at front surface
(*2)
, more affected by reected sound.
3. The external static pressure and airow rate of the fan may not reach the standard value due to air outlet dimension and shape, or obstacles.
4.
(*1)
: Required custom-ordered modication at factory.
(*2)
: Required air inlet grille (optional) mounting.
(*3) (*4)
: Required indoor unit custom-ordered modication at factory.
Indoor Unit ACRN
Close Controller HD2 PCP
Outdoor Unit ACN
Close Control
Twin DC Inverter
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 69
Close Control
Optional Accessories
Model
Condition
Applications
Optional
Accessories
Modied
at Factory
Indoor
Unit
Modication for piping/wiring
through top of unit
- - Applicable
Refrigerant piping and wiring is modied to connect
through the top of the unit
Modication for height difference
up to 70m
- - Applicable
Applicable when the outdoor unit is installed higher
than the indoor unit
Connection piping set CPS-NP560L Applicable -
When piping length is over 120m, piping diameter
shall be sized up
Air inlet chamber BS-NP560D Applicable -
When the duct is connected at air inlet side
(upper part of the unit)
Temperature sensor THM-R2DM Applicable - When the multipoint temperature control is applied
Temperature-humidity sensor THU-R1D Applicable -
When no-dehumidifying control or dehumidifying
control by humidity sensor is applied
Outdoor
Unit
Modication for high external
static pressure switchover
- - Applicable
Modication for high external static pressure to be
switched over at control panel
Front side air inlet grille PN-NP560D Applicable -
Modication to change air inlet from unit bottom side
into unit front side
Bottom side protective grille PN-NP560SD Applicable - To prevent object from entering into unit

For full technical details, refer to Technical Manual hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
Ventilation
KPI-Energy, Heat Recovery
and Active models
A|rfows from 250 to 2,000m
3
/h
The Hitachi heat recovery ventilation system (KPI)
adjusts the temperature and humidity of incoming
fresh air to match the indoor environment
|ow no|se |eve|
The fan motor is the only moving part resulting in low
noise levels of 26dB(A) (NR28)
H|gh|y-effo|ent exohanger w|th the fo||ow|ng features

Fresh air supply for indoor environments

Energy recovery ventilation between supply and


extract air supplies (forced energy exchange
mode) efciencies up to 78%

Automatic ventilation (KPI controls which mode to


operate within to achieve maximum energy efciency)

Ventilation mode (forced bypass mode)

As a consequence of the energy exchange


during the summer period, the cooling load can
be reduced by up to 20%, minimising both capital
and running costs
Ma|ntenanoe
Easy access hatches for the heat exchanger, motor,
fans and electrical box allow in situ maintenance
Hard w|red remote oontro||er w|th bu||t |n 7 day t|mer
as standard control option
Individual control or interfaced with Hitachi
System Free fan coil
Compatible with H-LINK II Control and CS Net Web.
Econofresh
The Econofresh kit is an intelligent accessory device
that is easy to install. The Econofresh kit can provide
up to 100% fresh air and has the ability to provide
free cooling when the outdoor temperature is
below the indoor setting temperature. This kit in
conjunction with the RPI In the Ceiling system will
not only maintain the correct room temperature and
provide fresh air, but also natural cooling therefore
increasing energy savings.
Operat|on mode
Fresh air cooling during intermediate seasons saves
energy. This unit uses an economiser for cooling,
which takes in fresh air if the outdoor temperature
is cooler than the indoor air. No compressor is used
and thus a remarkable amount of energy is saved
Fresh o|ean a|r
A fresh air intake system keeps the air in a room
clean at all times. The optional CO2 sensor can
sense the degree of pollution of the air in the room
and automatically control the fresh air ow
Reduoed power |nput
Utilising the free cooling potential of the UK
climate, the combination of the Econofresh and the
RPI 5.0FSN3E can reduce the power input required
by more than 20% when compared to a standard
RPI 5.0FSN3E system
Standard oontro||er
Hard wired remote controller with built in 7 day timer
(as per RPI-FSN3E In the Ceiling unit)
Oontro| opt|ons
Optional simplied hard wired or infra red remote
controller with 24hr timer
Compatible with H-LINK II Control and CS Net Web
controls that integrate with all leading BMS protocols.
Hitachi Product Catalogue | 71
Product Summary KPI Energy Recovery KPI Heat Recovery Active KPI Econofresh
Model KPI-E3E
(1)
KPI-H3E
(1)
KPI-X3E
(2)
EF
Air Volume (m
3
/min) 250 ~ 2,000 500 ~ 2,000 500 ~ 1,000 21 ~ 210
Total Enthalpy Heat Exchange - -
Sensible Heat Exchange -
Bypass Ventilation -
Free Cooling 10 ~ 100%
DX Coil - - -
EC Fans - EuP Lot 11
2nd Tier Compliant
-
Automatic Ventilation
via CO2 Sensor input

High Efciency Filter
(F7 based on EN779)
Option Option Option -
Power Supply 1 220-240V 50Hz Power supplied from RPI 5.0FSN3E
Fan Coil Type Individual Requires RPI 5.0FSN3E
Remote Controller Type Wired or Infra Red
Remote Control Timer 24hr or 7 Day Option
(1)
KPI-E3E and KPI-H3E
Series models available
from June 2012 (check
with Hitachi Sales Ofce)
Series 2 KPI-E2E and
KPI-H2E models will remain
available until June 2012
(2)
KPI-X3E models will be
available from June 2012
(check with Hitachi Sales
Ofce)
KPI Energy Recovery
Ventilation
Total Energy Recovery KPI 252E3E KPI 502E3E KPI 802E3E KPI 1002E3E KPI 1502E3E KPI 2002E3E
Air Flow Rate (m
3
/h) H/M/L 250-208-180 500-420-360 800-700-597 1000-800-620 1500-1250-970 2000-1560-1240
External Static Pressure
(1)
(Pa) H/M/L 60-40-30 77-50-47 100-75-55 120-80-50 132-90-60 135-84-60
Boost External Static Pressure (Pa) 200 (250m/h) 227 (500m/h) 200 (800m/h) 195 (1000m/h) 246 (1500m/h) 180 (2000m/h)
Sound Pressure Level
(2)
(dB(A) H/M/L 27-26-24 30-28-27 32-31-30 35-32-30 37-35-33 39-38-35
Heat Exchanger Element Air to Air cross ow Celluloid material (Total Energy Exchange)
Temp Exchange Efciency (%) 75 75 75 78 78 78
Enthalpy Exchange Efciency (Heat) 66 65 65 68 68 66.5
Enthalpy Exchange Efciency (Cool) 60 61 62 62 62.5 61.5
Dimensions (mm)
& Weight (kg)
Height 270 330 385 385 525 525
Width 900 1130 1210 1600 1800 1800
Depth 750 920 1015 1295 1130 1430
Weight TBC TBC TBC TBC TBC TBC
Duct Sizes (dia) (mm) 150 200 250 300 355 355
Supplied Air Filter Class (EN779)
(4)
G3 G3 G3 G3 G3 G3
Operation Range
(3)
-20 ~ 46C
Power Supply 1 ~ 230V 50Hz
Running Current (230V) (A) 0.2 0.4 1.0 1.2 1.9 2.7
Recommended Fuse Size (A) 5 5 5 5 5 5
Series 3 KPI-E3E data is provisional (check with Hitachi Sales Ofce)
KPI-E3E and KPI-H3E Series models available from June 2012 (check with Hitachi Sales Ofce)
Series 2 KPI-E2E and KPI-H2E models will remain available until June 2012
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 73
PC-ART KPI-E(H)(2)E
KPI Heat Recovery
Ventilation
Heat Recovery KPI 502H3E KPI 802H3E KPI 1002H3E KPI 1502H3E KPI 2002H3E
Air Flow Rate (m
3
/h) H/M/L 500-420-360 800-700-597 1000-800-620 1500-1250-970 2000-1560-1240
External Static Pressure
(1)
(Pa) H/M/L 77-50-47 100-75-55 120-80-50 132-90-60 135-84-60
Boost External Static Pressure (Pa) 227 (500m/h) 200 (800m/h) 195 (1000m/h) 246 (1500m/h) 180 (2000m/h)
Sound Pressure Level
(2)
(dB(A) H/M/L 30-28-27 32-31-30 35-32-30 37-35-33 39-38-35
Heat Exchanger Element Air to Air cross ow Aluminium material (Heat Exchange)
Temp Exchange Efciency (%) 53 50 50 49 48
Enthalpy Exchange Efciency (Heat) 35 34 33 31 31
Enthalpy Exchange Efciency (Cool) 30 28 28 27 28
Dimensions (mm)
& Weight (kg)
Height 330 385 385 525 525
Width 1130 1210 1600 1800 1800
Depth 920 1015 1295 1130 1430
Weight TBC TBC TBC TBC TBC
Duct Sizes (dia) (mm) 200 250 300 355 355
Supplied Air Filter Class (EN779)
(4)
G3 G3 G3 G3 G3
Operation Range
(3)
-20 ~ 46C
Power Supply 1 ~ 230V 50Hz
Running Current (230V) (A) 0.4 1.0 1.2 1.9 2.7
Recommended Fuse Size (A) 5 5 5 5 5
Series 3 KPI-H3E data is provisional, (check with Hitachi Sales Ofce) KPI-E3E and KPI-H3E
Series models available from June 2012 (check with Hitachi Sales Ofce)
Series 2 KPI-E2E and KPI-H2E models will remain available until June 2012
If a KPI is operated individually add the PC-ART / PC-ARF remote controller to the price.
For details of interlocks with Utopia & Set Free systems contact your local sales ofce.
(1)
Default fan pressure setting
(2)
Sound pressure level has been measured in an anechoic chamber, with the measuring point 1.5m below the centre of the unit,
with no ceiling under the unit and using a sound insulated duct. Reected sound must be considered when installing the unit in the eld.
(3)
The installation of an electric heater is necessary when temperature becomes lower than -5C(DB).
(4)
High efciency lter class F7 (EN779) is available as accessory.
For full technical details, refer to Technical Manual
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Active KPI
Ventilation
Active - Total Energy Recovery
KPI 502X3E KPI 802X3E KPI 1002X3E
Hp 1.5 2.0 2.5
Size 40 50 63
Nominal Set Free Capacity
(1)

Brackets = Coil Cap. (kW)
Cooling 5.3 (1.8) 8.0 (2.9) 10.8 (3.7)
Heating 6.9 (2.1) 9.8 (3.5) 12.9 (4.4)
Nominal Utopia Capacity
(1)

Brackets = Coil Cap. (kW)
Cooling - 7.4 (2.9) 9.7 (3.7)
Heating - 9.1 (3.5) 11.4 (4.4)
Air Flow Rate (m/h) H/M/L 500-430-380 800-700-590 1000-820-740
External Static Pressure
(2)
(Pa) H/M/L 150-120-100 125-95-70 120-85-70
Boost External Static Pressure (Pa) 235 (500m/h) 125 (800m/h) 125 (1000m/h)
Sound Pressure Level
(3)
(dB(A) H/M/L 29-27-26 31-30-29 35-32-30
Heat Exchanger Element Air to Air cross ow Celluloid material (Total Energy Exchange)
Temp Exchange Efciency (%) 75 75 78
Enthalpy Exchange Efciency (Heat) 65 65 68
Enthalpy Exchange Efciency (Cool) 61 62 62
Dimensions (mm)
& Weight (kg)
Height 330 385 385
Width 1630 1710 2100
Depth 920 1015 1295
Weight TBC TBC TBC
Refrigerant Piping (mm (in))
Liquid 6.35 (1/4) 6.35 (1/4) 9.53 (3/8)
Gas 12.7 (1/2) 15.88 (5/8) 15.88 (5/8)
Duct Sizes (dia) (mm) 200 250 300
Supplied Air Filter Class (EN779)
(5)
G3 G3 G3
Operation Range
(4)
-20 ~ 46C
Power Supply 1 ~ 230V 50Hz
Running Current (230V) (A) 0.7 1.2 1.5
Recommended Fuse Size (A) 5 5 5
Series 3 KPI-X3E data is provisional, (check with Hitachi Sales Ofce)
KPI-X3E models will be available from June 2012 (check with Hitachi Sales Ofce)
If a KPI is operated individually add the PC-ART / PC-ARF remote controller to the price.
For details of interlocks with Utopia & Set Free systems contact your local sales ofce.
(1)
The nominal cooling and heating capacity is the combined capacity of the outdoor and indoor units of the system and is based on Standard EN14511.
(2)
Default fan pressure setting.
(3)
Sound pressure level has been measured in an anechoic chamber, with the measuring point 1.5m below the centre of the unit, with no ceiling under the unit and
using a sound insulated duct. Reected sound must be considered when installing the unit in the eld.
(4)
The installation of an electric heater is necessary when temperature becomes lower than -5C(DB).
(5)
High efciency lter class F7 (EN779) is available as accessory.
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 75
EF-NE
New Model
Model description
EF 5NE

Econofresh Kit RPI-5HP
Econofresh Kit EF 5NE
Dimensions (mm)
& Weight (kg)
Height 254
Width 1350+59
Length 270
Weight 12.5
Typical Free Cooling Range (C) 3C ~ 19C
Power Supply Supplied from RPI 5FSN3E
Interconnecting Cables Supplied
Remote Controller Type via Indoor Unit Controller
Econofresh Kit
Ventilation
Econofresh Indoor Unit System
EF 5NE RPI 5FSN3E Utopia ES (5, 10HP)
EF 5NE RPI 5FSN3E Utopia IVX (5 ~ 12HP)
EF 5NE RPI 5FSN3E Utopia Centrifugal (5, 10HP)
EF 5NE RPI 5FSN3E Set Free - Mini, Side Flow, Modular
System Possibilities
For full technical details, refer to Technical Manual
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
Domestic Heating
Yutaki-M Monobloc air to water heat pump
A compact solution where a single unit is
installed on the outside of the property, taking up
no space inside and can be used alongside an
existing heating solution.
Monob|oo a|r-to-water heat pump system
p to 60O |eav|ng water temperature
(55C for 4~6HP)
Oapao|t|es from 7.1kW to 17.5kW
Domest|o hot water as we|| as heat|ng -
ideal boiler replacement technology
MOS approved
H|gh OOPs - market-|ead|ng OOP 4.43 3HP mode|}
S|mp|e and fast |nsta||at|on w|th no refr|gerat|on
handling required
Aooess to government |noent|ves suoh as the
renewable heat incentive
Soreed dry|ng funot|on |dea| for new bu||ds
Easy-to-use w|re|ess oontro||er w|th one-touoh
holiday button and frost protection as standard
Weather oompensat|on oontro|
Yutaki-S Split type air to water heat pump
A split system with auxiliary heating as standard.
Sp||t a|r-to-water heat pump oompr|s|ng |ndoor and
separate outdoor unit
p to 60O |eav|ng water temperature
Oapao|t|es from 5.1kW to 24.0 kW
Domest|o hot water and mu|t|p|e heat|ng/ooo||ng
settings ideal boiler replacement technology
H|gh OOPs - market-|ead|ng OOP of 5.0
(2HP model)
Su|tab|e for heat|ng sw|mm|ng poo|s
Soreed dry|ng funot|on |dea| for new bu||ds
Easy-to-use w|re|ess oontro||er w|th one-touoh
holiday button and frost protection as standard
Weather oompensat|on oontro|
Heating Manufacturer of the Year
The judges felt Hitachi provided an excellent
submission, a great product and the way forward.
Hitachis Yutaki M Heat Pump
Hitachi Product Catalogue | 77
Product Summaryyy Yut Yut Yu Y aki ki aki M -M -M -M Yut YYut Yutaki aki ak -S -SS
Model RHU RHU RH E-A E-A E-A(V) (V) (V HN( HN( HN(1)- 1)- 1 (HM (HM (HM HM)) RWM RWM RW -FS -FS -FSN3E N3EE RWM RWM WM-HF -HFSN3 SN3EE
Nominal Heattt atiing ing i Ca Capacity (kW) 7.1 7.1 7 1 ~ ~ 17. 17 17.55 2.3 2.3 3 ~ ~ 32. 32 32.2222 2.3 2.3 ~~ 32. 332. 2 22
Nominal CCCCool oo ing ng Capacity (kW) - 1.8 1.8 8 ~ ~ ~ 20. 20. 0 888 -
Refrigggeera era erant nt nt R4 R41 R44 0A 0A 0A R41 R41 R 0A 0A 0A R41 R41 R41 10A 0A 00A 0A
Cap ap ap apaci city ty Control DC-In Invert ert e er er DC- DC- DC DC Inv IInv Invert erter er er DCCC DC-Inv nvert erter er
Operating Range (Heating) (wb) -20C / + +37.5C 5C -2 -220C 0 0C / / +35 +35 +35 3 C C CC -2 -20C 0C / / +35 + C
Operatin ng Range (Cooling) (db) - -10 -10C C C / + / + / + / ++46 46 46 46 6 CCCC -
Energy R Rating A AAA A
Remote Controller Type Wireless Wireless
Remote CCo C ntrol Timer 24hr or 7 Day option 24hr or 7 Day option
Domestic Heating
Yutaki-M
Outdoor 1 RHUE 3.0AVHN1 RHUE 4.0AVHN-HM RHUE 5.0AVHN-HM RHUE 6.0AVHN-HM
Outdoor 3 - - RHUE 5.0AHN-HM RHUE 6.0AHN-HM
Capacity
1
Nominal (min~max) (kW) Water (in/out) 30/35C 7.5 (6.2 ~ 11.0) 9.5 (5.0 ~ 10.9) 12.0 (6.9 ~ 15.0) 14.0 (7.8 ~ 17.5)
COP Ambient (db/wb) 7/6C 4.43 4.06 4.01 4.31
Capacity
2
Nominal (min~max) (kW) Water (in/out) 40/45C 7.1 (5.9 ~ 10.2) 9.2 (5.0 ~ 10.2) 11.3 (6.8 ~ 14.0) 13.3 (7.6 ~ 16.5)
COP Ambient (db/wb) 7/6C 3.34 3.05 3.01 3.35
Capacity
3
Nominal (min~max) (kW) Water (in/out) 47/55C 6.4 (5.3 ~ 9.3) - - -
COP Ambient (db/wb) 7/6C 2.71 - - -
Capacity
4
Nominal (min~max) (kW) Water (in/out) 30/35C 6.5 (3.5 ~ 7.1) 6.9 (3.8 ~ 7.9) 8.4 (5.2 ~ 10.9) 9.3 (6.1 ~ 12.3)
COP Ambient (db/wb) -7/-8C 2.4 2.55 2.61 2.6
Capacity
5
Nominal (min~max) (kW) Water (in/out) 40/45C 6.4 (3.4 ~ 6.9) 6.5 (3.7 ~ 7.7) 8.1 (5.0 ~ 10.5) 9.0 (5.8 ~ 12.0)
COP Ambient (db/wb) -7/-8C 2.01 2.22 2.28 2.21
Capacity
6
Nominal (min~max) (kW) Water (in/out) 47/55C 6.2 (3.3 ~ 6.6) - - -
COP Ambient (db/wb) -7/-8C 1.82 - - -
Water Flow Nominal (min~max) (m/hr) 1.29 (0.9 ~ 2.6) 1.92 (0.6 ~ 3.3) 2.4 (0.8 ~ 4.0) 2.4 (0.8 ~ 4.7)
Water Volume (minimum installation) (l) 28 38 46 56
Sound Pressure level dB(A) 49 49 51 52
Dimensions (mm)
& Weight (kg)
Height 800 1480
Width 1250 1250
Depth 440 444
(1/3) Weight 110 / - 150 / - 155 / 160 159 / 164
Operating Range (C) Heating (-20 ~ +40)db
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - - 3Ph 380-415V 50Hz
Running Current (1/3) (A) (excludes pump) 7.5 / - 13.4 / - 16.6 / 7.7 17.6 / 8.2
Starting Current (A) < 10 < 10 < 10 < 10
Recommended Fuse Size (A) (1/3) 25 / - 25 / - 32 / 16 40 / 20
H
e
a
t
i
n
g

C
a
p
a
c
i
t
y
For full technical details, refer to Technical Manual
Heating Manufacturer of the Year
The judges felt Hitachi provided an excellent
submission, a great product and the way forward.
Hitachis Yutaki M Heat Pump
RHUE-A(V)HN(1) AF-RTU-01
Hitachi Yutaki heat pumps
The perfect heating and cooling solution for modern homes
Visit hitachiheating.com
to nd out more about our range of air source heat pumps
Hitachi Product Catalogue | 79
* Performed at the ow rate obtained during testing of the Yutaki-S at standard ambient rating conditions 7C/6C dB/wB
Price does not include room thermostat (see page 82)
For full technical details, refer to Technical Manual
Outdoor 1 RAS 2HVRN2 RAS 3HVRNME-AF
Outdoor 3 - -
Outdoor Sound Pressure Level
(Set Back) d(B)A
Cooling 45 (43) 42 ( 38)
Heating 47 50
Dimensions (mm)
& Weight (kg)
Height 600 800
Width 792 950
Depth 300 370
Weight 42 67
Operating Range (C)
Cooling (10 ~ 46)C db
Heating (-20 ~ 35)C wb
Refrigerant Piping (mm) (in)
Liquid 6.35(1/4) 9.52(3/8)
Gas 12.7(1/2) 15.88(5/8)
Piping (m)
Length 30 30
Lift (OU lower than IU) 30 / (20) 30 / (20)
Pre-charged 30 30
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - -
Starting Current (A) < 10 < 10
Running Current (1/3) (A)
Cooling 5.2 8.2
Heating 4.1 6.8
Recommended Fuse Size (A) 16 / - 25 / -
RAS-H(V)RNM(E)
AF-RTU-02
Yutaki-S
Outdoor Units
RAS-4/5H(V)RNME
RWM-FSN3E
Heating & Cooling RWM 2.0FSN3E RWM 3.0FSN3E
Heating only RWM 2.0HFSN3E RWM 3.0HFSN3E
Capacity Nominal (min~max) (kW) Water (in/out) 30/35C 5.1 (2.3 ~ 8.0) 7.5 (3.1 ~ 11.0)
COP Ambient (db/wb) 7/6C 5.02 4.55
Capacity Nominal (min~max) (kW) Water (in/out) 40/45C 4.7 (2.2 ~ 7.5) 7.1 (2.8 ~ 9.7)
COP Ambient (db/wb) 7/6C 3.51 3.47
Capacity Nominal (min~max) (kW) Water (in/out) 47/55C 4.2 (2.0 ~ 5.5) 6.2 (2.4 ~ 7.6)
COP Ambient (db/wb) 7/6C 2.63 2.65
Capacity Nominal (min~max) (kW) Water (in/out) */35C 4.0 (1.9 ~ 4.7) 6.4 (3.5 ~ 7.5)
COP Ambient (db/wb) -7/-8C 2.65 2.51
Capacity Nominal (min~max) (kW) Water (in/out) */45C 3.8 (1.8 ~ 4.4) 6.0 (3.3 ~ 6.9)
COP Ambient (db/wb) -7/-8C 2.10 2.33
Capacity Nominal (min~max) (kW) Water (in/out) */55C 3.0 (1.6 ~ 3.9) 5.3 (2.9 ~ 5.5)
COP Ambient (db/wb) -7/-8C 1.62 1.80
Capacity Nominal (min~max) (kW) Water (in/out) 12/7C 3.8 (1.8 ~ 5.4) 6.0 (2.5 ~ 6.9)
COP Ambient (db/wb) 35/-C 3.05 3.07
Capacity Nominal (min~max) (kW) Water (in/out) 23/18C 5.4 (2.6 ~ 7.5) 7.1 (3.0 ~ 8.0)
COP Ambient (db/wb) 35/-C 3.83 4.03
Water Flow Nominal (min~max) (m/hr) 0.9 (0.5 ~ 2.2) 1.3 (0.9 ~ 2.6)
Water Volume (minimum installation) (l) 28 28
Sound Pressure level dB(A) 26 27
Dimensions (mm)
& Weight (kg)
Height 890
Width 520
Depth 360
Weight 55 56
Water Pipe Connection Inlet & Outlet G 1-1/4" (male) G 1-1/4" (male)
Pump Input Power (watts) 75 100
Electric Heater Power (kW) Steps 1.0/2.0/3.0 1.0/2.0/3.0
Colour White (RAL 9016)
Power Supply
1 Phase 1Ph 220-240V 50Hz
3 Phase - -
Running Current (1/3) (A) Elec. Heater + Pump 13.3 13.5
Recommended Fuse Size (1/3) (A) 20 20
H
e
a
t
i
n
g

C
a
p
a
c
i
t
y
C
o
o
l
i
n
g

C
a
p
a
c
i
t
y
Domestic Heating
Domestic Heating
Hitachi Product Catalogue | 81
RAS 4HVRNME-AF RAS 5HVRNME-AF RAS 6HVRNME-AF - -
RAS 4HRNME-AF RAS 5HRNME-AF RAS 6HRNME-AF RAS 8HRNME-AF RAS 10HRNME-AF
44 (40) 46 (42) 48 (45) 52 (50) 55 (53)
52 55 55 54 56
1380 1650
950 1100
370 390
107 108 108 170 170
(10 ~ 46)C db
(-20 ~ 35)C wb
9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)* 12.70(1/2)*
15.88(5/8) 15.88(5/8) 15.88(5/8) 28.6(1/8)* 28.6(1/8)*
30 30 30
30 / (20) 30 / (20) 30 / (20) 30 / (20) 30 / (20)
30 30 30 30 30
1Ph 220-240V 50Hz - -
3Ph 380-415V 50Hz
< 10 < 10 < 10 < 10 < 10
9.8 / 3.3 12.8 / 4.3 17.2 / 5.7 5.7 8.4
9.2 / 3.0 11.6 / 3.9 14.5 / 4.8 6.3 8.0
20 / 16 32 / 16 32 / 16 - / 16 - / 20
RWM 4.0FSN3E RWM 5.0FSN3E RWM 6.0FSN3E RWM 8.0FSN3E RWM 10.0FSN3E
RWM 4.0HFSN3E RWM 5.0HFSN3E RWM 6.0HFSN3E RWM 8.0HFSN3E RWM 10.0HFSN3E
9.8 (4.8 ~ 13.5) 12.0 (6.3 ~ 16.3) 14.0 (5.9 ~ 17.8) 19.6 (11.3 ~ 25.5) 24.0 (11.6 ~ 32.0)
4.47 4.36 4.11 4.45 4.41
9.2 (4.5 ~ 12.5) 11.3 (5.6 ~ 15.5) 13.3 (5.6 ~ 16.5) 18.4 (10.6 ~ 24.5) 22.6 (10.9 ~ 31.0)
3.42 3.16 3.01 3.43 3.40
8.1 (4.0 ~ 10.0) 10.1 (5.1 ~ 13.7) 12.6 (5.4 ~ 13.9) 16.2 (9.3 ~ 20.5) 20.2 (9.8 ~ 27.4)
2.59 2.60 2.47 2.70 2.67
7.6 (2.9 ~ 9.8) 9.0 (3.3 ~ 11.5) 9.4 (3.5 ~ 12.0) 14.8 (8.8 ~ 17.8) 18.0 (8.9 ~ 21.6)
2.42 2.40 2.34 2.63 2.61
7.1 (2.8 ~ 8.5) 8.3 (3.1 ~ 10.2) 8.7 (3.2 ~ 10.4) 14.2 (8.4 ~ 16.6) 16.6 (8.2 ~ 20.4)
2.14 1.92 1.81 2.17 2.16
5.9 (2.4 ~ 6.3) 7.7 (2.9 ~ 8.7) 7.9 (3.0 ~ 8.9) 11.8 (7.0 ~ 12.6) 15.4 (7.6 ~ 17.7)
1.55 1.55 1.46 1.73 1.72
7.2 (2.6 ~ 8.2) 9.2 (3.3 ~ 10.3) 10.5 (3.1 ~ 11.5) 14.4 (6.7 ~ 16.4) 18.4 (6.4 ~ 20.6)
3.06 3.03 2.61 3.53 3.12
10.0 (3.6 ~ 11.2) 12.9 (4.7 ~ 15.0) 15.0 (4.4 ~ 17.8) 20.0 (9.3 ~ 23.5) 24.5 (8.6 ~ 29.0)
3.88 4.02 3.50 4.43 3.57
1.7 (1.0 ~ 3.3) 2.1 (1.1 ~ 3.6) 2.4 (1.2 ~ 3.6) 3.4 (2.0 ~ 4.7) 4.1 (2.2 ~ 4.8)
38 46 55 76 92
28 28 28 29 29
890 890
520 670
360 360
59 61 61 81 85
G 1-1/4" (male) G 1-1/4" (male) G 1-1/4" (male) G 1-1/4" (male) G 1-1/4" (male)
130 140 140 250 260
2.0/4.0/6.0 2.0/4.0/6.0 2.0/4.0/6.0 3.0/6.0/9.0 3.0/6.0/9.0
White (RAL 9016)
1Ph 220-240V 50Hz or 3Ph 380-415V 50Hz
- -
3Ph 380-415V 50Hz
26.7 / 9.3 26.7 / 9.3 26.7 / 9.3 - / 14.1 - / 14.2
40 / 16 40 / 16 40 / 16 - / 20 - / 20
For full technical details, refer to Technical Manual hitachiheating.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Domestic Heating
Yutaki Accessories
Model Code Range
Controller Pack Yutaki-M - (A(V)HN / A(V)HN-HM) Controller Pack - Controller + Room Thermostat (55C machine)
ATW-CPA-01 Controller CP60 Yutaki-M - (A(V)HN1) Controller Pack CP60 Controller + Room Thermostat (60C machine)
ATW-CPA-02 Yutaki-M - (A(V)HN1) Advanced Controller + Room Thermostat (60C machine) (check availability)
ATW-RTU-01 Yutaki-S (RWM - FSN3E) On/Off Thermostat (Receiver + Room Thermostat)
ATW-RTU-02 Yutaki-S (RWM - FSN3E) Intelligent Thermostat (Receiver + Room Thermostat)
ATW-RTU-03 Yutaki-S (RWM - FSN3E) 2nd Temp Thermostat, only RTU-02 (Only Room Thermostat)
RHM-EH01E Yutaki-M - (All Models) Hydraulic Module - Electric Heater inc Control Pack
RHM-BC01E Yutaki-M - (All Models) Hydraulic Module - Boiler Combination inc Control Pack
ATW-PK-01 Yutaki-M - (A(V)HN1) Pump Kit (Top-S 25/7)
ATW-PK2-01 Yutaki-M - (A(V)HN1) Pump Kit (Top-S 25/10)
ATW-PK3-01 Yutaki-M - (A(V)HN1) Pump Kit (Top-S 25-70/180)
Pump Kit A (small) Yutaki-M - (A(V)HN / A(V)HN-HM) Pump Kit A
Pump Kit B (big) Yutaki-M - (A(V)HN / A(V)HN-HM) Pump Kit B
ATW-WCV-01 Yutaki-M - (All Models) Water Check Valve
WEH-6E Yutaki-M - (All Models) Both 1 & 3 Electric Heater 6kW - (2/4/6kW stages)
ATW-HSK-01 Yutaki-M/S Hydraulic Separator
ATW-3WV-01 Yutaki-M/S 3-Way Valve
ATW-2KT-01 Yutaki-M/S 2nd Zone Temperature Kit
ATW-AQT-01 Yutaki-M/S Aquastat
ATW-WTS-02Y Yutaki-M/S Water Temperature Sensor for Hot Water Tank (included with HAPE Tank)
DBS-26 Yutaki-M/S Drain Boss Kit
ATW-MVM-01 Yutaki-S (RWM - FSN3E) Mixing valve motor
ATW-DPK-01 Yutaki-S (RWM - 2.0~6.0FSN3E) Drain Pan Kit for RWM
ATW-DPK-02 Yutaki-S (RWM - 8 ~ 10FSN3E) Drain Pan Kit for RWM
ATW-AOS-01 Yutaki-S (RWM - FSN3E) Auxiliary output signal box
ATW-20S-01 Yutaki-S (RWM - FSN3E) 2nd Outdoor Temperature Sensor
ATW-WTS-02 Yutaki-S (RWM - FSN3E) Water Temperature Sensor (2nd Temp control, boiler combination)
ATW-SPS-01 Yutaki-S (RWM - FSN3E) Swimming Pool Sensor
DHWT200E - 2.5H1E Yutaki-M/S 200L Enamelled Tank inc. 2.5kW electric heater
DHWT300E - 2.5H1E Yutaki-M/S 300L Enamelled Tank inc. 2.5kW electric heater
DHWT200S - 2.5H1E Yutaki-M/S 200L Stainless Steel Tank inc. 2.5kW electric heater
DHWT300S - 2.5H1E Yutaki-M/S 300L Stainless Steel Tank inc. 2.5kW electric heater
DHWT-CP-01 Yutaki-M/S Permanent cathode protection for enamelled tank 200L
DHWT-CP-02 Yutaki-M/S Permanent cathode protection for stainless steel tank 200L
DHWT-CP-03 Yutaki-M/S Permanent cathode protection for enamelled tank 300L
DHWT-CP-04 Yutaki-M/S Permanent cathode protection for stainless steel tank 300L
DHWT-SWG-01 Yutaki-M/S Safety valves

For full technical details, refer to Technical Manual
1
2
3
4
5
6
7
8
9
10
11
12
13
15
11
16
17
18
14
Hitachi Product Catalogue | 83
Yutaki Accessories
Domestic Heating
1 3 2 4 5
6 7 8 9 10
15
16 17 18
11 12 13 14
For full technical details, refer to Technical Manual hitachiheating.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
Samurai Chillers
Hitachi Samurai Chillers offer world-renowned reliability thanks to Hitachis twin screw compressors.
Unlike some competitors, Hitachi manufactures the compressors and was, in fact, the worlds rst
supplier of screw chiller units.

All Samurai Chillers
The outt|ng-edge range offers ooo||ng on|y un|ts from
110~1030kW - available with heat recovery option
and Heat Pump models from 120~600kW
Oont|nuous oapao|ty oontro| prov|des a 15 to 20%
energy saving over step control
|ow sound
Hitachi uses high technology to achieve the lowest
sound. The adoption of DC Inverter twin blade fans,
rather than four, achieves a reduction of noise level.
Low noise and super low noise models are available
Preo|se oontro| of out|et water to w|th|n +/-0.5O,
independent of cooling load
Exoe||ent part|a| |oad performanoe
STAR DE|TA start|ng system, wh|oh reduoes the
maximum starting current
Wor|d-renowned tw|n sorew oompressors - h|gh|y
reliable with very low noise and vibration
Sma|| |nsta||at|on spaoe
Due to the meticulous design of each and every
component, it is possible to achieve exceptionally
high cooling capacity values per square metre.
Hydraulic Module Option -
Single and Dual Pump Models
Hitachi Hydraulic modules are a compact design
integrated inside the Chiller unit. They are assembled
with all interconnecting piping and wiring during
manufacture ready for installation.
Available for Air-Cooled Cooling Only RCU2E(40~80)
AG2 and Air Cooled Heat Pump RHU2E(40~80)AG2
models. Available with single or dual pumps and with
or without a buffer tank.
Other options available, please contact your local
sales ofce.
Hitachi Product Catalogue | 85
Samurai
Air Cooled Cooling Only
RCU2E 40~400AG2
Air Cooled Heat Pump
RHU2E 40~240AG2
Water Cooled
RCUE 40~240WG2
Condenserless Cooling Only
RCUE 40~120CLG2
Nominal Cooling Capacity (kW) 112 ~ 1030 106 ~ 585 134 ~ 696 120 ~ 360
Nominal Heating Capacity (kW) - 110 ~ 556 161 ~ 824 -
Refrigerant R407C R407C R407C R407C
Compressor Type Screw Screw Screw Screw
Operating Range (Cooling) (-15C ~ 46C)db (-15C ~ 46C)db - -
Operating Range (Heating) - (-15C ~ 15.5C)db - -
No. Circuits 1 ~ 5 1 ~ 3 1 ~ 3 1 ~ 2
Samurai Chillers
Air Cooled Cooling Only
RHU2E
40AG2
RHU2E
50AG2
RHU2E
60AG2
RHU2E
70AG2
RHU2E
80AG2
RHU2E
100AG2
RHU2E
120AG2
RHU2E
140AG2
RHU2E
160AG2
RHU2E
180AG2
RHU2E
210AG2
RHU2E
240AG2
Cooling Capacity
1
kW 106 123 148 169 195 246 296 338 390 444 507 585
Heating Capacity
2
kW 110 127 152 185 185 254 304 370 370 456 555 555
Power Input (Cooling) kW 37.9 42.7 52 60 70 85.4 104 120 140 156 180 210
Power Input (Heating) kW 40.7 44.5 54 68 68 89 108 136 136 162 204 204
EER 2.8 2.88 2.85 2.82 2.79 2.88 2.85 2.82 2.79 2.85 2.82 2.79
COP 2.7 2.85 2.81 2.72 2.72 2.85 2.81 2.72 2.72 2.81 2.72 2.72
ESEER 3.36 3.45 3.42 3.38 3.34 3.45 3.42 3.38 3.34 3.42 3.38 3.34
Sound Power Level
(Std/LN/SLN)
dB(A)
82/80/78 83/81/79 84/82/80 85/83/81 85/83/81 86/84/82 87/85/83 88/86/84 88/86/84 89/87/85 91/89/87 91/89/87
Sound Pressure Level
(Std/LN/SLN)
3
dB(A)
52/50/48 53/51/49 54/52/50 55/53/51 55/53/51 55/53/51 56/54/52 57/55/53 57/55/53 57/55/53 58/56/54 58/56/54
Height mm 2430
Width mm 1900
Depth mm 2190 2790 4090 5290 5990 7790
Net Weight kg 1550 1600 1670 1880 1950 3050 3250 3670 3780 4780 5440 5650
Capacity Control
- Continuous Capacity Control
% 15 ~ 100
Number of Circuits - 1 1 1 1 1 2 2 2 2 3 3 3
Water Pipe Connection
in 3 Victaulic (1 x Inlet / 1 x Outlet) per Circuit
in - Common Water Pipe Connection Option available
Leaving Water Outlet
Temperature (Cool)
C 5 ~ 15 (-10 option)
Leaving Water Outlet
Temperature (Heat)
C 35 ~ 55
Ambient Temperature C -15 ~ 46 Cooling / -10 ~ 15.5wb Heating
Air Cooled Heat Pump
NOTES: Please refer to notes 1 and 3
RCU2E
40AG2
RCU2E
50AG2
RCU2E
60AG2
RCU2E
70AG2
RCU2E
80AG2
RCU2E
100AG2
RCU2E
120AG2
RCU2E
140AG2
RCU2E
160AG2
RCU2E
180AG2
RCU2E
210AG2
RCU2E
240AG2
RCU2E
280AG2
RCU2E
320AG2
RCU2E
350AG2
RCU2E
400AG2
Cooling Capacity
1
kW 112 130 156 178 206 260 312 356 412 468 534 618 712 824 890 1030
Power Input kW 38.6 44.7 53 61 70 89.4 106 122 140 159 183 210 244 280 305 350
EER 2.9 2.91 2.94 2.92 2.94 2.91 2.94 2.92 2.94 2.94 2.92 2.94 2.92 2.94 2.92 2.94
ESEER 3.48 3.49 3.52 3.5 3.52 3.49 3.52 3.5 3.52 3.52 3.5 3.52 3.5 3.52 3.5 3.52
Sound Power Level
(Std/LN/SLN)
dB(A)
82/80/78 83/81/79 84/82/80 85/83/81 85/83/81 86/84/82 87/85/83 88/86/84 88/86/84 89/87/85 91/89/87 91/89/87 92/90/88 92/90/88 94/92/90 94/92/90
Sound Pressure Level
(Std/LN/SLN)
3
dB(A)
52/50/48 53/51/49 54/52/50 55/53/51 55/53/51 55/53/51 56/54/52 57/55/53 57/55/53 57/55/53 58/56/54 58/56/54 59/57/55 59/57/55 60/58/56 60/58/56
Height
mm
2430
Width
mm
1900
Depth mm 2190 2790 4090 5290 5990 7790 10290 12790
Net Weight kg 1430 1470 1560 1760 1820 2830 3000 3420 3550 4450 5070 5250 6750 7000 8450 8750
Capacity Control % 15 ~ 100
Number of Circuits - 1 1 1 1 1 2 2 2 2 3 3 3 4 4 5 5
Water Pipe
Connection
in 3 Victaulic (1 x Inlet / 1 x Outlet) per Circuit
in - Common Water Pipe Connection Option available
Leaving Water
Outlet Temperature
C 5 ~ 15 (-10 option)
Ambient Temperature C -15 ~ 46
NOTES: Please refer to notes 1, 2 and 3
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 87
Samurai Chillers
Water Cooled
RCUE
40WG2
RCUE
50WG2
RCUE
60WG2
RCUE
80WG2
RCUE
100WG2
RCUE
120WG2
RCUE
150WG2
RCUE
180WG2
RCUE
200WG2
RCUE
240WG2
Cooling Capacity
4
kW 134 160 194 232 320 388 445 525 600 696
Heating Capacity
5
kW 161.1 192.3 233.9 274.7 384.7 467.9 526.9 621.9 719.5 824.2
Power Input (Cooling)
4
kW
33.5 40 49.1 54.5 80 98.2 104.5 123.5 148.5 163.5
Power Input (Heating)
5
kW
39.8 47.5 58.3 64.7 95 116.6 124.1 146.7 176.4 194.2
EER 4.0 4.0 4.0 4.3 4.0 4.0 4.3 4.3 4.0 4.3
COP 4.0 4.0 4.0 4.2 4.0 4.0 4.2 4.2 4.1 4.2
ESEER 4.52 4.52 4.46 4.81 4.52 4.46 4.83 4.82 4.55 4.82
Sound Power Level dB(A) 83 84 86 86 88 90 90 91 92 93
Sound Pressure Level dB(A) 68 69 71 71 72 74 74 75 76 77
Height mm 1520 1700 1580
Width mm 1105
Depth mm 850 1465 2350
Net Weight kg 750 765 830 950 1570 1670 1770 2500 2580 2670
Capacity Control
- Continuous Capacity Control
% 15 ~ 100
Number of Circuits - 1 1 1 1 2 2 2 3 3 3
Water Pipe Connection
(Evaporator)
in 3 Victaulic (1 x Inlet / 1 x Outlet) 3 Victaulic (3 x Inlet / 3 x Outlet)
in - 5 Victaulic (1 x Inlet / 1 x Outlet)
Water Pipe Connection
(Condenser)
in 3 Victaulic (1 x Inlet / 1 x Outlet) 3 Victaulic (3 x Inlet / 3 x Outlet)
in - 5 Victaulic (1 x Inlet / 1 x Outlet)
Leaving Water Outlet
Temperature (Cool)
C 5 ~ 15 (-10 option)
Leaving Water Outlet
Temperature (Heat)
C 25 ~ 55
Condenser Water
Outlet Temprature
7
C 22 ~ 45 (55* option)
RCUE
40CLG2
RCUE
50CLG2
RCUE
60CLG2
RCUE
80CLG2
RCUE
100CLG2
RCUE
120CLG2
Cooling Capacity
6
kW 120 145 180 240 290 360
Power Input kW 34.4 42.4 52.1 68.8 84.8 104.2
EER 3.5 3.4 3.5 3.5 3.4 3.5
ESEER 4.32 4.32 4.28 4.32 4.23 4.28
Sound Power Level dB(A) 83 84 86 86 88 90
Sound Pressure Level dB(A) 68 69 71 71 72 74
Height mm 1520 1720
Width mm 1045 1104
Depth mm 885 1471
Net Weight kg 630 680 730 1200 1310 1380
Capacity Control
- Continuous Capacity Control
% 15 ~ 100
Number of Circuits - 1 1 1 2 2 2
Water Pipe Connection
(Evaporator)
in 3 Victaulic (1 x Inlet / 1 x Outlet)
Leaving Water
Outlet Temperature
C 5 ~ 15 (-10 option)
Condensing Temperature C 30 ~ 65
Condenserless Cooling Only
NOTES: Please refer to notes 4 and 5.
7
( ) is in case of high condensing option and heat pump operation option.
NOTES: Please refer to note 6
NOTES:
1. The nominal cooling capacities are based on the
European Standard EN14511.
Chilled Water Inlet / Outlet Temperature: 12 / 7C
Condenser Inlet Air Temperature: 35C
2. The nominal heating capacities are based on the
European Standard EN14511.
Heated Water Inlet / Outlet Temperature: 40 / 45C
Evaporator Air Inlet Temperature: 6C wb
3. Sound Pressure level measured at 10m
4. The nominal cooling capacities are based on the
European Standard EN12055.
Chilled Water Inlet / Outlet Temperature: 12 / 7C
Cooling Water Inlet / Outlet Temperature: 30 / 35C
5. The nominal heating capacities are only for Heat Pump
Operation Option and based on following conditions.
Chilled Water Inlet / Outlet Temperature: 12 / 7C
Hot Water (Condenser) Inlet / Outlet Temperature: 40 / 45C
6. The nominal cooling capacities are based on the
following conditions.
Chilled Water Inlet / Outlet Temperature: 12 / 7C
Condensing Temperature: 45C
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Features and Benets
Control Systems
and Accessories
H-LINK II
H-LINK II across the entire Hitachi product range
means you can use Hitachi System Free controls
for any mix of products.
CS Net Web
Hitachis CS Net Web is a standalone control system
that allows users to fully monitor and control their
air conditioning from anywhere with web access.
Single and multiple sites can be monitored from one
central point and the user can ascertain the system
performance at all times.
CS Net Web can control up to 512 indoor units and
up to 64 outdoor units connected to the H-LINK
communication system.
Optional touchscreen
Hitachis touchscreen allows intuitive control of up
to four CS Net Web central controllers. It can be
xed to either a wall or table using the supplied
mounting bracket.
BMS Interfaces
BMS interfacing options are compatible with the
Utopia, Set Free and Samurai Chiller ranges allowing
the connection of Hitachi H-LINK air conditioning
units to building management systems using
Modbus, BacNet, KNX and LonWorks

protocols.
ModBus
Interface to allow a ModBus compatible building
management system to control and monitor up to
32 H-LINK compatible indoor units, or up to eight
Samurai Chillers via a RS485 connection. Up to
eight controllers can be connected to one H-LINK
communications circuit.
KNX
Interface to allow a KNX compatible building
management system to control and monitor up
to 16 H-LINK compatible indoor units. This unit is
an accessory for the CS Net Web central controller
and connects to the BMS system via a KNX-TP1
type connection.
HARC BX (A/B) LonWorks

Interface to allow a LonWorks

compatible building
management system to control and monitor up to
64 (option A) or 32 (option B) H-LINK compatible
indoor units.
BMS interface HARC70-CE1/OP LonWorks

Interface to allow integration of Hitachi H-LINK and


LonWorks

BMS systems. Two options are available


dependent on the level of control required.
BACNet
Interface to allow a BACNet compatible building
management system to control and monitor
up to 64 H-LINK compatible indoor units via
the BACNet/IP protocol.
Hitachi Product Catalogue | 89
Control Systems and Accessories
Individual Controls
Group Controls
RAC Controls
SPX-RCK3 Wired Remote Controller - WX8, FH6, YH7, YH5A, NH5A, NH7A, FX8, NX2, QH8
SPX-RCK2 Wireless Remote Controller & Receiver Kit - RAD-NH7A
SPX-WKT1
Wired Remote Controller + 7 Day Timer - WX8, FH6, YH7, YH5A, NH5A, NH7A,
FX8, NX2, QH8
SPX-DST1 Optional Distributor Kit for SPK-WKT1 (centralised control of up to 13 indoor units)
SPX-WDST8M Optional wiring kit for SPX-WKT1 & SPX-DST1
PSC-6RAD
H-LINK Adapter connects RAC models: WX8, FH6, YH7, YH5A, NH5A, NH7A, FX8,
NX2 and QH8 to H-LINK
System Free Controls
PC-ART Std. Wired Remote Controller (inc 7 Day Time Clock) (System Free Indoor Units)
PC-ARF
Wired LED Controller with advanced graphical interface (inc 7 Day Time Clock)
(System Free Indoor Units)
PC-ARH Simple Wired Remote Controller - (System Free Indoor Units)
PC-LH3A Wireless Remote Controller - Receiver kit required (inc. with RPK-FSN2M)
PC-ALHN Receiver Kit panel mounted (RCI-FSN3E)
PC-ALHD Receiver Kit panel mounted (RCD-FSN3E)
PC-ALHC Receiver Kit panel mounted (RCIM-FSN3E)
PC-ALHZ Receiver Kit wall mounted (All System Free Indoor Units)

Group Controls
PSC-A64GT Touchscreen Central Controller (64 Groups, 160 Units - System Free)
PSC-A64S Central Controller (64 Groups, 160 Units - System Free)
CSC 5S Central Controller - (up to eight Samurai Chillers)
PSC-A1T 7 Day Timer
CS Net Web (v3.0)
Web based Control, Stand alone or with Touchscreen below
(64 outdoor units, 512 indoor units)
TS002 Touchscreen for CS Net Web
PC-A1IO Control/Monitor 3rd party equipment via CS Net Web
PSC-5HR H-LINK Relay - extend H-LINK wiring up to maximum 1,000m

BMS Interface Controls
HC-A32MB ModBus Interface, control/monitor 32 System Free indoor units or 8 Samurai Chillers
HARC-BX (A/B) LonWorks

Interface, control/monitor 64(A) or 32(B) System Free indoor units


HARC-70CE1 (OP) LonWorks

Interface, control/monitor up to 4 Samurai Chillers


HC-A16KNX KNX Interface, control/monitor 16 System Free indoor units
HC-A64BNP BACNet Interface, control/monitor 64 System Free indoor units

SPX-RCK3
SPX-WKT1
SPX-RCK2
PC-ART
PCS-A64GT
PC-ARH
PC-ARF
PSC-A64S CS Net Web
PSC-A1T
Touchscreen
BMS Interface Controls
For full technical details, refer to Technical Manual
Control Systems and Accessories
Hitachi Product Catalogue | 91
For full technical details, refer to Technical Manual
S Y S T E M
FREE
Accessories
PCC1A Optional Function Connector Cables (pack of 5) - Utopia and Set Free
THM-R2AE Remote Sensor
PDF-23C3 Side Duct Connection Flange (RCI 1.0~3.0FSN3E)
PDF-46C3 Side Duct Connection Flange (RCI 4.0~6.0FSN3E)
PD-75 Fresh Air Intake Kit, 75mm dia (RCI 1.0~6.0FSN3E)
PI 23LS5 Cassette 3-Way outlet kit
DBS 26 Drain Boss Kit (All Outdoor Units except below)
DBS 12L Drain Boss Kit (RAS 2.0 ~ 2.5HVRN2 + RAS 3.0HVRNS2)
DBS-TP10A Drain Boss Kit (RAS-FSXN)
DU M1E Drain Pump Kit (RPIM-FSN2E)

PCC1A
DBS 26
PD-75
DBS 12L
THM-R2AE
DU M1E
Accessories
Pipe Kits (Utopia ES, IVX, Centrifugal)
TE-03N Twin Pipe Kit (3HP System)
TE-04N Twin Pipe Kit (4HP System)
TE-56N Twin Pipe Kit (5 & 6HP System)
TE-08N Twin Pipe Kit (8HP System)
TE-10N Twin Pipe Kit (10 & 12HP System)
TRE-06N Triple Pipe Kit (4 ~ 6HP System)
TRE-810N Triple Pipe Kit (8 ~ 12HP System)
QE-810N Quad Pipe Kit (8 ~ 12HP System)
E-102SN2 Piping Kit (Only use with 8 ~ 12HP IVX)
E-162SN2 Piping Kit (Only use with 8 ~ 12HP IVX)

Pipe Kits (Set Free - Mini, Side Flow, Modular)
E-102SN2 Piping Kit (Only use with 8 ~ 12HP IVX)
E-162SN2 Piping Kit (Only use with 8 ~ 12HP IVX)
E 242SN2 Pipe Kit (2-pipe)
E 302SN2 Pipe Kit (2-pipe)
E 52XN2 Pipe Kit (3-pipe)
E 102XN2 Pipe Kit (3-pipe)
E 162XN2 Pipe Kit (3-pipe)
E 202XN2 Pipe Kit (3-pipe)
E 242XN2 Pipe Kit (3-pipe)
E 322XN2 Pipe Kit (3-pipe)
MH 84AN Pipe Kit (2-pipe header)
MH 108AN Pipe Kit (2-pipe header)
MH 108XN Pipe Kit (3-pipe header)
MC 20AN
Modular Set Free 2-pipe Branch Kit
(RAS 20~24FSXN)
MC 21AN
Modular Set Free 2-pipe Branch Kit
(RAS 26~36FSXN)
MC 30AN
Modular Set Free 2-pipe Branch Kit
(RAS 28~54FSXN)
MC 20XN
Modular Set Free 3-pipe Branch Kit
(RAS 20~24FSXN)
MC 21XN
Modular Set Free 3-pipe Branch Kit
(RAS 26~36FSXN)
MC 30XN
Modular Set Free 3-pipe Branch Kit
(RAS 28~54FSXN)

Pipe Kits
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full details, refer to Technical Manual
Helping You
D
ir
e
c
t

S
a
le
s

(
U
K
)
E
: a
irco
n
.en
q
u
iries@
h
ita
ch
i-eu
.co
m
T: 0
1
6
2
8
5
8
5
3
9
4
S
p
a
r
e
s
E
:

a
ir
c
o
n
.s
p
a
r
e
s
@
h
it
a
c
h
i-
e
u
.c
o
m
T
:

0
1
6
2
8

5
8
5

3
9
4
h
i
t
a
c
h
i
a
i
r
c
o
n
.
c
o
m
/
s
p
a
r
e
p
a
r
t
s
Technical (UK)
T: 01628 585 393
Technical and Service
Manuals available at
hitachiaircon.com
Proactively meeting the expectations
of our customers through continuous innovation
D
o
w
n
lo
a
d
o
u
r la
te
st
se
le
c
tio
n
(H
iT
o
o
lk
it)
so
ftw
a
re
a
t
h
itach
iairco
n
.co
m
Hitachi Product Catalogue | 93
D
ire
c
t
S
a
le
s
(Ire
la
n
d
)
E: aircon.ireland@
hitachi-eu.com
T: 00 353 1216 4406
A
p
p
l
i
c
a
t
i
o
n
s
E
: a
ir
c
o
n
.a
p
p
lic
a
t
io
n
s
@
h
it
a
c
h
i-
e
u
.c
o
m
T
: 0
1
6
2
8
5
8
5
3
9
4
Training
E: aircon.training@hitachi-eu.com
T: 01628 585 394
Warranty
E: aircon.warranty@hitachi-eu.com
T: 01628 585 393
hitachiaircon.com/warranty
2
4
-
h
o
u
r


a
la
r
m

c
o
d
e
s
T: 0
1
6
2
8
5
8
5
3
9
3
(o
p
tio
n
2
) o
r
v
is
it h
ita
c
h
ia
irc
o
n
.c
o
m

to
d
o
w
n
lo
a
d
o
u
r n
ew
a
la
rm
co
d
es A
p
p

T
e
c
h
n
i
c
a
l

(
I
r
e
l
a
n
d
)

T
: 0
0
3
5
3
1
2
9
6
8
0
6
5
T
e
c
h
n
i
c
a
l

a
n
d

S
e
r
v
i
c
e

M
a
n
u
a
l
s

a
v
a
i
l
a
b
l
e

a
t
h
i
t
a
c
h
i
a
i
r
c
o
n
.c
o
m
Hitachis Training Centre
Helping you increase your
technical and product knowledge
Hitachi offer high-quality training courses in its aircademy training
centre based at Hitachi Europe Headquarters in Maidenhead,
Berkshire. This newly-refurbished centre is dedicated to excellence
and a wide range of Hitachi air conditioning and refrigeration
products are displayed.
The equipment is fully operational and used extensively throughout
all training courses allowing Hitachi to offer practical, hands-on
experience to attendees.
All training is given by highly-skilled engineers with vast industry
experience and an in-depth knowledge of Hitachi products.
If you have any specic training requests please contact us and
our engineers will be happy to tailor a course to suit your needs. Contact aircon.training@hitachi-eu.com
Product training courses
Hitachis one-day product-specic training courses are provided
FREE OF CHARGE.
Lunch included.
Morning 09.45-12.45 Afternoon 13.30-17.00
Mechanical and electrical courses
Mechanical and electrical training courses, such as basic
refrigeration and air conditioning, safe handling of refrigerants,
IEE wiring regulations, electrical inspection and essential
electrics are available with an external partner upon request.
All courses provide CITB or City and Guilds qualications
upon completion.
System explanation
Software and hardware
set up
lP address set
up demonstration
System commissioning
Direct connection and
connecting to LAN
BMS integration
CS Net Web for the Field Engineer
System operation
Water pipe work
design and application
Controls
Electrical installation
and control wiring
Refrigerant cycle operation
Controller installation
and operation
lnverter control and operation
Optional function
Commissioning
Hands on" system testing
Refrigerant piping limitations
(Yutaki S)
Yutaki Air to Water Heat Pump for the Field Engineer
Selection software/Hi-ToolKit
demonstration
Product application
Pipe work selection
Unit application
System limitations
Controls and BMS application

Set Free and Utopia Selection and Design
Selection software
Product application
Pipe work selection
Unit application
System limitations
Controls and BMS application
Samurai Selection and Design
Pipework design
and installation
Electrical installation
and control wiring
Refrigerant cycle operation
Controller installation
and operation
lnverter control
and operation
Optional functions
Commissioning
and system set up
Troubleshooting
and system interrogation
Hands on" system testing
CS Net Web and BMS
interfacing overview
Dip switch settings
Samurai Chillers for the Field Engineer
Set Free VRF and Utopia Inverter Splits for the Field Engineer
System operation
Refrigeration pipe work
design and installation
Electrical installation and
control wiring
Refrigerant cycle operation
Controller installation
and operation
lnverter control and operation
Optional functions
Commissioning
Hands on" system testing
CS Net Web and BMS
interfacing overview
Room Air Conditioners for the Field Engineer
System operation
Refrigeration and waterside
pipe work design and
installation
Electrical installation
and control wiring
Dip switch settings
Refrigerant cycle operation
lnverter control and operation
Optional functions
Commissioning and
system interrogation
Hands on" system testing
CS Net Web and BMS
interfacing overview
Controller installation
and operation
Hitachi Price List | 95
Contact
T: 01628 585394
E: aircon.training@hitachi-eu.com
F: 01628 585500
Every precaution has been taken during
the design and manufacture of Hitachi Air
Conditioning equipment to ensure the
products conform to the highest standards.
In the event of a warranty fault the owner should advise
the original installer. The following sets out the current
Hitachi Air Conditioning Europe SAS warranty policy.
For all RAC products the warranty period shall be for 36 months
(3 years) from date of invoice.
S-Series
Shirokuma
Summit
Mono/MuItizone*
NX2
For all Utopia and Set Free the warranty period shall be 60 months
(5 years) from date of invoice**.
System Free indoor units
Set Free outdoor units*
Changeover boxes
Branch kits
Utopia ES outdoor units*
Utopia IVX outdoor units*
Utopia CentrifugaI outdoor units*
TotaI Heat Exchanger
Econofresh
Yutaki-M
Yutaki-S
For all Samurai Chillers the warranty period shall be 36 months
(3 Years) from the date of invoice.
Air CooIed CooIing OnIy
Air CooIed Heat Pump
Water CooIed CooIing OnIy
CondenserIess CooIing OnIy
For all Central Control Systems the warranty period shall be
36 months (3 years) from the date of invoice.
CS Net Web
Modbus
I-O
BACNet
KNX
HARC LonWorks

AII other controIIers wiII be covered under the warranty


period for the applicable indoor unit.
For all spare parts, the warranty period shall be 12 months
parts only.
Warranty
All components requested to be returned should be sent
to Hitachi Air Conditioning Europe SAS (Warranty
Department) Whitebrook Park, Lower Cookham Road,
Maidenhead, SL6 8YA clearly marked with the Warranty
number. Components returned without a valid Warranty
number will not be accepted.
Within the above specied time periods, all products are
guaranteed against manufacturing faults in workmanship and
material. The faulty component will be replaced free of charge
provided the correct procedures are complied with and a labour
contribution can be claimed during the rst 3 years***, the
amounts of which are laid out on next page.
The warranty policies are subject to the following conditions.
The Hitachi Air Conditioning Europe SAS equipment is installed using
the correct working practices, and installed within the parameters set
out in the technical manuals for each unit, and maintained regularly
(minimum of every 6 months, site dependant, by a qualied installer)
in accordance with the manufacturers recommendations.
Placing a claim
Place your claim online
Contact the warranty department on 01628 585 393, and ask
for your secure login to be set up and place your warranty claim
online at hitachiaircon.com/warranty
You can then track the progress of your claim live online, and
gain access to tracking and despatch details and receive email
notication of your warranty progression.
If any of the information is not available at the time of claim, then
the part can be ordered via an ofcial purchase order and a credit
arranged retrospectively, when all the information is available.
(This must be within 60 days of the original date of failure).
All warranty claims must be made within 60 days of failure.
Any claim submitted after the 60 day period WILL NOT be
considered for approval.
Parts should be held by the customer for a period of 30 days
during which time if required, Hitachi Air Conditioning Europe SAS
can request the return of the parts at our cost for inspection and
a RMA number will be issued. If it is deemed to have failed out
of warranty the part will be invoiced to the customer at our
standard spare parts rate.
Repeat warranty requests will be subject to Hitachi Air Conditioning
Europe SAS investigation and possible site visit. An ofcial
purchase order will be required to purchase the part, pending
a decision on the validity of the claim. All parts will be inspected
within 14 days, and a credit issued if the warranty is accepted.
For warranty claims rejected following inspection, the part will
be returned and invoiced to the customer at our standard spare
parts rate and |f app||oab|e a s|te v|s|t oharge of 550.00 per day.
Normal wear and tear is excluded.
Any claim not submitted in accordance with Hitachi Air Conditioning
Europe SAS procedures WILL NOT be considered for credit.
* Approved combinations only.
** Subject to Hitachi Air Conditioning Europe SAS assisting with the
commissioning, and commissioning reports being logged with ourselves.
Failure to comply will result in the warranty reverting to 36 months (3 years)
parts and labour contribution.
``` Exceo| soa|es w||c| a|e oa||s on|,.

For a wallet-sized list of alarm codes for
RAC, Set Free VRF and Utopia Split Systems
Contact aircon.technical@hitachi-eu.com
to request a copy
Or visit hitachiaircon.com
to download our new alarm codes App
Android
Scan this QR Code
using your Android
phone to download our
new alarm codes App
iPhone - iOS
Scan this QR Code
using your iPhone - iOS
phone to download our
new alarm codes App
Hitachi Product Catalogue | 97
Alarm Codes
Alarm Codes for
RAC S-Series, Shirokuma, Summit, Monozone and MuItizone
Indoor unit faults
Flashing
TIMER
lamp
Main cause
1 time
The indoor heat exchanger temperature is too low in
the heating mode or it is too high in the cooling mode
2 times Outdoor unit is under forced operation
3 times Communication error between indoor and outdoor units
4 times Outdoor unit alarm check outdoor alarm indication
5 times
Fan motor rotation error (Mono/Multizonej Power relay
error (Summit/Premium SX unitj
6 times Drain high level water alarm
7 times Drain pump forced operation
8 times Louver defective
9 times lnlet air or heat exchanger thermistor fault
10 times Fan motor overload
11 times High voltage generator fault
12 times Communication error between indoor and outdoor units
13 times Eeprom error on PCB
17 times Switching PCB fault
18 times Cleaning unit defect
19 times Failure of peltier device
Flashing
CLEAN
lamp
Main cause
1 time Front cover is open
4 times Failure of the cleaning unit motor or detection switch
Flashing
MONITOR
lamp
Main cause
1 time Front cover is open
4 times Outdoor unit fault, check outdoor LED indication
Outdoor unit faults
Flashing
LD 301
Main cause
1 time Normal operation
2 times Compressor overload
3 times Low compressor rotation
4 times Compressor switching failure
5 times Overload activation
6 times Compressor over temperature alarm
7 times Faulty thermistor (check LD 303 to identify which one)
8 times Compressor rotation below minimum speed
9 times
Communication alarm
(On Multizone LD 304 indicates which indoor unit
1 time = unit no.1, 2 times unit no.2 and so onj
10 times Abnormal power source detected
12 times Fan alarm
13 times Eeprom error
14 times Over voltage on power module
Flashing
LD 304
Main cause
1 time Communication error
Flashing
LD 303
Main cause
1 time Over heat thermistor
2 times Defrost thermistor
3 times Ambient thermistor
4 times Expansion line thermistor (unit 1j
5 times Suction line thermistor (Unit 1)
6 times Expansion line thermistor (unit 2j
7 times Suction line thermistor (Unit 2)
8 times Expansion line thermistor (unit 3j
9 times Suction line thermistor (Unit 3)
10 times Expansion line thermistor (unit 4j
11 times Suction line thermistor (Unit 4)
12 times Expansion line thermistor (unit 5j
13 times Suction line thermistor (Unit 5)
Alarm Codes
Hitachi Product Catalogue | 99
For full technical details, refer to Technical Manual
Alarm Codes for
Set Free Side FIow 2-pipe, ModuIar 2-pipe heat pump / 3 pipe heat recovery
lf RUN lamp fashes for 2 seconds, there is a failure
in transmission between the indoor unit and the
remote control switch.
Possible causes are:
The remote cable is broken
Contact failure in the remote control cable
lC or microcomputer defective
ln all cases, contact your service provider.
lf RUN lamp fashes 5 times (5 secondsj with unit
number and alarm code displayed, note the alarm
code (see table Alarm codesj and contact your
service provider.
Alarm Code
Alarm Code
Alternate indication
every second
Indoor unit number
Model code
Number of indoor units connected
Model Code
Indication Model
H
Heat Pump
P
Inverter
F
Multi
C
Cooling
Unit
E
Others
L
KPI
Code No. Category Type of Abnormality Main cause
01 Indoor unit Protection device activation (float switch)
Float switch activation (high water level in drain pan.
Blockage in drain pipe, float switch activated or drain pump faulty)
02 Outdoor unit Protection device activation
HP switch activation (pipe blocked, excess refrigerant, non condensable
present). Phase loss or incorrect rotation (Utopia only), float switch activation
or MT open circuit (Centrifugal unit only)
03 Transmission
Abnormality between indoor
and outdoor communication
Incorrect wiring, loose terminals, disconnect cable, blown fuse, outdoor unit
switched off. Incorrect address setting
04 Transmission
Abnormality between inverter PCB
and outdoor PCB
Inverter PCB - Outdoor PCB transmission fault
(loose connector, broken cable, blown fuse)
Transmission
Abnormality between fan controller
and outdoor PCB
Fan controller - Outdoor PCB transmission fault
(loose connector, broken cable, blown fuse)
05 Power phase Abnormality in the power phases Incorrect power supply, inverted phase connection, open phase
06 Voltage
Abnormal inverter voltage Abnormal inverter
controller voltage
Outdoor voltage drop, insufficient power. Capacitor or electronic problem
on inverter compressor
Voltage
Abnormal inverter voltage Abnormal fan
controller voltage
Outdoor voltage drop, insufficient power. Capacitor or electronic problem
on fan motor
07
Refrigerant
Cycle
Drop in discharge gas superheat
Excessive refrigerant charge, thermistor fault, incorrect wiring,
incorrect pipe connection, expansion valve locked in open position
(connector disconnected).
08
Refrigerant
Cycle
Increase in discharge gas temperature
Insufficient refrigerant charge, blocked pipe, thermistor fault, incorrect
wiring, incorrect pipe connection, expansion valve locked in closed position
(connector disconnected)
09 Outdoor unit Tripping of protection device Fan motor failure
0A Transmission Abnormality between outdoor and indoor units Incorrect wiring, broken cable, loose terminals
Outdoor unit
Incorrect outdoor unit address setting.
Main unit of the outdoor unit incorrectly set
Duplicate address setting of outdoor units (secondary units) in the same
refrigerant cycle system
0C Outdoor unit Main unit of the outdoor unit incorrectly set
Two (or more) outdoor units defined as the main unit in the same
refrigerant cycle system
11 Indoor unit Air inlet thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
12 Indoor unit Air outlet thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
13 Indoor unit Frost protection thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
14 Indoor unit Gas pipe thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
Alarm Codes for
Utopia ES, IVX and CentrifugaI
Alarm Codes
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Alarm Codes
For full technical details, refer to Technical Manual
Alarm Codes for RAS FSNM
Set Free Side FIow 2-pipe, ModuIar 2-pipe heat pump / 3 pipe heat recovery
Alarm Codes for
Utopia ES, IVX and CentrifugaI
Continued...
Code No. Category Type of Abnormality Main cause
15 Indoor unit Outdoor air thermistor (KPI) Incorrect wiring, disconnected wiring, broken cable, short circuit
16 Indoor unit Remote thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
17 Indoor unit Remote controller thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
19 Fan motor Indoor fan protection device activation Fan motor overheating, locking
20 Outdoor unit
Discharge gas thermistor at top of compressor
(Utopia)
Incorrect wiring, disconnected wiring, broken cable, short circuit
21 Outdoor unit High pressure sensor Incorrect wiring, disconnected wiring, broken cable, short circuit
22 Outdoor unit Outdoor air thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
23 Outdoor unit
Discharge gas thermistor at top of compressor
(VRF)
Incorrect wiring, disconnected wiring, broken cable, short circuit
24 Outdoor unit Heat exchanger liquid pipe thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
25 Outdoor unit Heat exchanger gas pipe thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
26 Outdoor unit Suction gas thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
29 Outdoor unit Low pressure sensor Incorrect wiring, disconnected wiring, broken cable, short circuit
31 Outdoor unit
Incorrect capacity setting on outdoor and
indoor units
Combination capacity incorrectly set.
Excessive or insufficient total indoor unit capacity.
32 System
Loss of communication with 1 indoor unit
(Multi system)
Loss of power, Incorrect wiring, loose terminals, disconnect cable,
blown fuse, outdoor unit switched off. Incorrect address setting
35 Indoor unit Indoor unit no. incorrectly set Indoor unit no. duplicated in same refrigeration cycle
38 Outdoor unit
Abnormality in the control circuit for outdoor
unit protection
Protection detection device fault (incorrect wiring of outdoor PCB)
39 Compressor
Abnormal operation current in constant
speed compressor
Over current, blown fuse, current sensor fault, instant power failure,
voltage drop, abnormal power supply or faulty compressor
3A Outdoor unit Abnormal outdoor unit capacity Outdoor unit capacity >54 HP
Outdoor unit
Voltage or combination of outdoor unit models
incorrectly set
Voltage or combination of secondary and main units incorrectly set
Outdoor unit
Abnormal transmission between the main unit
and the secondary units
Incorrect wiring, disconnected wiring, broken cable, PCB fault
41
Refrigerant
Cycle
Cooling overload
(possible activation of high pressure device)
O.U. pipe thermistor temp. is higher than 55 C and the compressor
top temp. is higher than 95 C, O.U. protection device is activated
42
Refrigerant
Cycle
Heating overload
(high-pressure device may be activated)
If I.U. freeze protection thermistor temp. is higher than 55
and compressor top temp. is higher than 95
44
Refrigerant
Cycle
Low-pressure increase protection device
activation
Overload during cooling, high temperature with heating,
locked expansion valve (loose connector)
45
Refrigerant
Cycle
High pressure increase protection
device activation
Blocked condenser, pipe blocked, excess refrigerant,
non condensable present
47
Refrigerant
Cycle
Low-pressure decrease protection device
activation (vacuum protection)
"Insufficient refrigerant, refrigerant pipes blocked, expansion valve locked in
closed position (VRF). Stoppage due to excessive decrease of evaporating
temperature (Temp < -35 C) is activated 3 times in one hour, motor locked
in heating mode.
Hitachi Product Catalogue | 101
Alarm Codes
For full technical details, refer to Technical Manual
Alarm Codes for RAS FSNM
Set Free Side FIow 2-pipe, ModuIar 2-pipe heat pump / 3 pipe heat recovery
Alarm Codes for
Utopia ES, IVX and CentrifugaI
Continued...
Code No. Category Type of Abnormality Main cause
48
Inverter
compressor
Inverter over current protection
device activation
Overload, compressor fault
51
Inverter
compressor
Abnormal inverter current sensor Current sensor fault
53
Inverter
compressor
Inverter error signal detection
Controller IC error signal detection
(over current, low-voltage and short-circuit protection)
54
Inverter
compressor
Abnormal inverter fin temperature Abnormal inverter fin thermistor, heat exchanger clogging, fan motor fault
55
Inverter
compressor
Inverter fault Inverter PCB fault
56 Fan controller
57 Fan controller Fan controller protection activation
Controller IC error signal detection (over current, low-voltage
and short-circuit protection), instant over current. Abnormal rotation speed
58 Fan controller Fan controller protection activation
Controller IC error signal detection (over current, low-voltage
and short-circuit protection), instant over current
59
Inverter
compressor
Abnormality inverter fin thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
5A Fan controller Abnormal fan controller fin temperature Fin thermistor fault, heat exchanger clogging, fan motor fault
Fan controller Over current protection activation Fan motor fault
5C Fan controller Abnormal fan controller sensor
Current sensor fault (instant over current, increased fin temperature,
low voltage, earthing fault, step-out)
96
KPI Unit
Sensor
Room Temperature thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
97
KPI Unit
Sensor
Fresh air thermistor Incorrect wiring, disconnected wiring, broken cable, short circuit
EE System
Compressor protection alarm (cannot be reset
from the remote controller)
This alarm code is displayed when the following alarms are triggered three
times within six hours: 02, 07, 08, 39, 43 to 45, 47
Outdoor
unit number
setting
Unit number or address number
of the outdoor unit incorrectly set
A number greater than 64 has been set for the refrigerant cycle or address
Indoor unit
number
setting
Connection number of the indoor unit
incorrectly set
There are more than 17 units not corresponding to H-LINK II connected
to one system
C1 CH unit Incorrect indoor unit connection
There are 2 or more CH units connected between the outdoor
and indoor units
C2 CH unit
Connection number of the indoor unit
incorrectly set
There are 9 or more indoor units connected to the CH unit
C3 CH unit Incorrect indoor unit connection
Indoor units from different refrigerant cycles have been connected to the
CH unit
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Alarm Codes
Alarm Codes for
Domestic Heating Yutaki-M
Checking the 7-Segment display.
SEG.1 SEG.2
8 8
8 8 8
Upper side
SEG.3 SEG.4 SEG.5
Lower side
Code number Type of Abnormality
8 8
Proceeding Initialisation
8 8
Power ON (During unit stoppagej
p u
Pump Operation (During unit stoppagej
p u
Waiting of pump feedback (During unit operationj
8 f
Stoppage by Thermo-OFF
h e
Heating operation (Normal operation)
h e p o
Heating operation (Activation of forced compressor frequency control due to low pressure difference: forced up)
h e p 1
Heating operation (Activation of forced compressor frequency control due to high pressure difference: forced down)
h e p 2
Heating operation (Activation of forced compressor frequency control due to excessively high discharge pressure: forced downj
h e p 3
Heating operation (Activation of forced compressor frequency control due to excessively high current: forced downj
h e p 4
Heating operation (Activation of forced compressor frequency control due to excessively high inverter fn temperature: forced downj
p- 0 6
Retry operation (by alarm 02-91, t1j
p- 1 1
Retry operation (by alarm 02-e1j
p- 1 2
Retry operation (by alarm 02-h1j
p- 1 7
Retry operation (by alarm 51, 52, 53, 54j
p- 1 8
Retry operation (by alarm 04, 06j
e 0 (Flickering)
lnitialising electronic expansion valve
f 8
Fan manual operation
0 2 H 1
Activation of high pressure switch
0 2 h 1
Activation of protection control for excessively high pressure
0 2 L 1
Activation of low pressure control
0 2 e 1
Excessively low pressure difference
0 2 6 1
Excessively high discharge gas temperature
0 2 9 1
Excessively low temperature of heating exchanger refrigerant inlet
0 2 E 1
Excessively low suction gas temperature
0 4
Abnormal transmission between lnverter PCB and Main PCB
0 5
Abnormality of Power Supply Phase
0 6
Excessively low voltage or excessively high voltage for the inverter
1 1
Failure of water inlet temperature thermistor
1 2
Failure of water outlet temperature thermistor
1 3
Activation of freeze protection control (water inlet)
0 2 1 3
Activation of freeze protection control (water outlet)
1 4
Excessively high water temperature (compressor runningj
2 1
Failure of refrigerant evaporating temperature thermistor (Open/Shortj
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 103
Alarm Codes
Code number Type of Abnormality
2 2
Failure of ambient temperature thermistor (Open/Shortj
2 3
Failure of discharge gas temperature thermistor (Open/Shortj
2 4
Failure of refrigerant liquid temperature thermistor (Open/Shortj
2 6
Failure of suction gas temperature thermistor (Open/Shortj
2 7
Failure of discharge gas pressure sensor (Open/Shortj
2 8
Failure of suction gas pressure sensor (Open/Shortj
3 0
lncorrect PCB Setting
3 2
Transmission error between Main PCBs (this alarm code is not available in this modelj
4 0
lncorrect PCB operation
5 1
Abnormal operation of the current sensor
5 2
Activation of protection for inverter instantaneous over current
5 3
Transistor module protection activation
5 4
lncrease in the inverter fn temperature
5 7
Abnormality of fan motor protection
5 p
No feed back signal from water pump
6 e
Cooler water failure (this alarm is not available in this unitj
6 C
Condenser water failure (this alarm is not available in this unitj
p u (Flickering)
Excessively high water temperature (compressor stopj
f a
Failure of fan motor (MF1)
f 6
Failure of fan motor (MF2)
Alarm Codes for
Domestic Heating Yutaki-M
Continued...
For full technical details, refer to Technical Manual hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Alarm Codes
Alarm Code Indication on Remote Control Switch: Alarm indication Alarm code
HITACHI
Code
No.
Origin Type of Abnormality Main cause
02 Outdoor
Activation of Outdoor Unit Protection Device
(Except for Alarm Codes 41, 42)
High-pressure interrupting device activated
03 Outdoor Transmission Error
Outdoor fuse meltdown, Indoor/outdoor connection wiring
(breaking, wiring error, etc.)
04 Outdoor Inverter Transmission Abnormality
Control PCB Inverter PCB connection wiring
(breaking, wiring error, etc.)
05 Outdoor Power Phase Detection Abnormality Power source wiring open phase in Indoor units
06 Outdoor Undervoltage, Overvoltage
Outdoor PCB abnormality, inverter PCB abnormality,
DM, CB abnormality
07 Outdoor Abnormal Decrease of Discharge Gas Superheat Degree
Excessive refrigerant, expansion valve open-locked,
Fan motor locked
08 Outdoor Compressor-Top Temperature Over-Increase
Shortage or leakage of refrigerant, piping clogging,
Fan motor locked
11 Indoor Water Inlet Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
12 Indoor Water Outlet Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
13 Indoor Indoor Liquid Pipe Temperature Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
14 Indoor Indoor Gas Pipe Temperature Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
15 Indoor Water Outlet C2 thermistor Abnormality Loose, disconnected, broken or short-circuited connector
16 Indoor Water DHW Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
17 Indoor Auxiliary Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
18 Indoor Water Outlet Boiler Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
19 Indoor Water Outlet HP Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
20 Outdoor Compressor-Top Temperature Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
22 Outdoor Outdoor Temperature Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
24 Outdoor Outdoor Heat Exchanger Liquid Pipe Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
31 Outdoor Indoor/Outdoor Combination Setting Error
Outdoor/Indoor Unit capacity setting error,
Indoor total capacity excessively large/small
35 Outdoor Indoor Unit Number Setting Error
Indoor units with the same number
in a refrigerant piping system
Alarm Codes for
Domestic Heating Yutaki-S
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 105
Alarm Codes
Code
No.
Origin Type of Abnormality Main cause
38 Outdoor Outdoor Protection Detection Circuit Abnormality Outdoor PCB abnormality, Error in wiring to outdoor PCB
41 Outdoor Cooling Overload
Outdoor heat exchanger clogging/short circuit,
Broken outdoor fan motor
42 Outdoor Heating Overload
Outdoor heat exchanger clogging/short circuit,
Expansion valve closed-locked
47 Outdoor Suction Pressure Decrease Prevention Activated
Shortage or leakage of refrigerant, pipe clogging,
Expansion valve closed-locked, Fan motor locked
48 Outdoor Overload Operation Protection Activation
Cycle abnormality, Inverter PCB abnormality,
DM abnormality, Heat exchanger clogging, etc.
51 Outdoor Inverter Current Sensor Abnormality
Error in CT wiring, Outdoor PCB abnormality,
Inverter PCB abnormality
53 Outdoor Inverter Module Error Compressor, ISPM abnormality, Heat exchanger clogging, etc.
54 Outdoor Inverter Fin Temperature Abnormality
Fin thermistor abnormality, Heat exchanger clogging,
Fan motor abnormality
55 Outdoor Inverter Non-Operation Inverter not operating or broken
56
Outdoor
Fan
Fan motor abnormality
Disconnected wire of Incorrect wiring between control PCB
and inverter PCB. Incorrect wiring or fan motor abnormality
59 Outdoor Inverter Fin Temperature Thermistor Abnormality Loose, disconnected, broken or short-circuited connector
1 Outdoor Error in Address/Refrigerant System Setting Address/refrigerant system setting over 64
EE Outdoor Compressor Factor Alarm
Alarm to notify damage to compressor occurs
3 times within 6 hours
70 Indoor Hydraulic alarm
Water pressure or water fow is not detected
in the hydraulic cycle
71 Indoor Water Pump Feedback
72 Indoor Thermostat Heater Alarm High temperature is detected in Electric Heater T>75C
73 Indoor Mixing overheating limit protection for Mixed circuit Circuit 2 supply temperature > Target temperature + offset
74 Indoor Unit overheating limit protection Two > Tmax +5K
75 Indoor
Freeze Protection by Cold water inlet,
outlet temperature detection
76 Indoor
Freeze Protection Stop by Indoor
Liquid Temperature Thermistor
Tl or Tg < -20C for 30 seconds (Only heating mode)
77 Indoor Opentherm Communication Failure
No Opentherm communication for a continuous period
of 1 minute.
78 Indoor RF Communication Failure
No communication for 1 hour with one or two RF receivers
which are bound to the RF-Bridge.
79
Indoor-
Outdoor
Unit Capacity Setting Error No concordance between indoor and outdoor unit capacities
80
Indoor
LCD
LCD H-link Transmission Error
No H-link communication for a continuous period of 1 minute
between Indoor and LCD User control by connection wiring
(breaking, wiring error, etc.)
Alarm Codes for
Domestic Heating Yutaki-S
Continued...
For full technical details, refer to Technical Manual hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full technical details, refer to Technical Manual
Alarm Codes
Alarm codes for
Samurai Chiller
lf the unit is operated under abnormal conditions,
an alarm code (refer to the table belowj is
indicated and the Alarm"LED lamp is lighted.
Function of 7-Segment Light Emitted Diode on
Control Panel is as shown in the table below.
SEG.1 SEG.2
88 88
7 Segments on Control Panel
Code
Content
No. 1
Cycle
No. 2
Cycle
No. 3
Cycle
No. 4
Cycle
No. 5
Cycle
C 1 H 1 C 2 H 3 C 3 H 3 C 4 H 4 C 5 H 5
Activation of High Pressure Switch
C 1 L 1 C 2 L 2 C 3 L 3 C 4 L 4 C 5 L 5
Activation of Low Pressure Protection Control
C 1 L 1 C 2 L 2 C 3 L 3 C 4 L 4 C 5 L 5
Excessively Low Pressure
C 1 5 1 C 2 5 2 C 3 5 3 C 5 5 4 C 5 5 5
Activation of Thermal Relay for Compressor or Malfunction of Auxiliary Relay ARn
C 1 6 1 C 2 6 2 C 3 6 3 C 4 6 4 C 5 6 5
Activation of Discharge Gas Thermistor
C 1 7 1 C 2 7 2 C 3 7 3 C 4 7 4 C 5 7 5
Activation of Compressor Internal Thermostat
C 1 9 1 C 2 9 2 C 3 9 3 C 4 9 4 C 5 9 5
Excess Low Temperature of Cooler lnlet Refrigerant
C 1 8 1 C 2 8 2 C 3 8 3 C 4 8 4 C 5 8 5
Activation of Suction Gas Thermistor
C 1 0 5 C 2 0 5 C 3 0 5 C 4 0 5 C 5 0 5
Phase Abnormally
C 1 1 2 C 2 1 2 C 3 1 2 C 4 1 2 C 5 1 2
Failure of Water Outlet Thermistor (Only for 2 - 5 cycle unitj
C 1 1 3 C 2 1 3 C 4 1 3 C 4 1 3 C 5 1 3
Activation of Freeze Protection Control (More Than 2 Cycle Unit)
C 1 2 1 C 2 2 1 C 3 2 1 C 4 2 1 C 5 2 1
Failure of Cooler inlet Refrigerant Thermistor (Open / Shortj
C 1 2 3 C 2 2 3 C 3 2 3 C 4 2 3 C 4 2 3
Failure of Discharge Gas Thermistor (Open / Shortj
C 1 2 4 C 2 2 4 C 3 2 4 C 4 2 4 C 5 2 4
Failure of Thermistor set before Expansion valve
C 1 2 5 C 2 2 5 C 3 2 5 C 4 2 5 C 5 2 5
Failure of Water Outlet Thermistor (Rear side of Water Coolerj
C 1 2 6 C 2 2 6 C 3 2 6 C 4 2 6 C 5 2 6
Failure of Suction Gas Thermistor (Open / Shortj
C 1 2 7 C 2 2 7 C 3 2 7 C 4 2 7 C 5 2 7
Failure of Discharge Gas Pressure Sensor (Open / Shortj
C 1 2 8 C 2 2 8 C 3 2 8 C 4 2 8 C 5 2 8
Failure of Suction Gas Pressure Sensor (Open / Shortj
C 1 F 0 C 2 F 0 C 3 F 0 C 4 F 0 C 5 F 0
lncorrect Setting of Fan Number
F 1 1 1 F 2 1 1 F 3 1 1 F 4 1 1 F 5 1 1
Fan lnverter Rotation Abnormally *1
F 1 2 1 F 2 2 1 F 3 2 2 F 4 2 2 F 5 2 2
Activation of Fan lnverter Over Current Protection Control *1
F 1 3 1 F 2 3 1 F 3 3 1 F 4 3 1 F 5 3 1
Fan lnverter Phase Abnormally *1
F 1 4 1 F 2 4 1 F 3 4 1 F 4 4 1 F 5 4 1
Error Communication between lnverter PCB and Control or Fan Control PCB *1
F1 51 F2 51 F3 51 F4 51 F5 51
lnverter Power Supply Abnormally *1
Code
Content
No. 1
Cycle
No. 2
Cycle
No. 3
Cycle
No. 4
Cycle
No. 5
Cycle
0 5 0 5
Phase Abnormally
1 1 1 1
Failure of Water Inlet Temperature Thermistor
1 2 1 2
Failure of Water Outlet Thermistor (Only for Single Cycle Unitj
1 3 1 3
Activation of Thermal Relay for Compressor or Malfunction of Auxiliary Relay ARn
2 2 2 2
Failure of Ambient Temperature Thermistor (Open / Shortj
S P S P
No Feedback Signal from Water Pump
4 0 4 0
lncorrect Operation
E U E U
Error Communication between Expansion valve PCB and Control PCB
F 6 F 6
Error Communication between Fan Control PCB and Control PCB
C P C P
Error Communication between Control PCB (PCBC1, PCBC2)
PUPU Alarm of Excessively High Water Temperature
6 E 6 E
Alarm of Water Failure (Differential Pressure Switch or Flow Switch Optionj
A P A P
Activation of Additional Protection Device
0 3 0 3
Error Communication between Chiller and Remote Controller (lf CSC-5S is connected.j
F 1 P 7 F 2 P 7 F 3 P 7 F 4 P 7 F 5 P 7
Retry Operation (More Than 3 Fans Retry at The Same Timej
F 1 P 8 F 2 P 8 F 3 P 8 F 4 P 8 F 5 P 8
Retry Operation (by Alarm Fx-41 or Fx-51, x: Cycle No.j
C 1 P 5 C 2 P 5 C 3 P 5 C 4 P 5 C 5 P 5
Retry Operation (by Alarm Cx-6x or Cx-7x, x: Cycle No.j
C 1 2 8 C 2 2 8 C 3 2 8 C 4 2 8 C 5 2 8
Failure of Suction Gas Pressure Sensor (Open / Shortj
C 1 P 6 C 2 P 6 C 3 P 6 C 4 P 6 C 5 P 6
Retry Operation (by Alarm Cx-9x or Cx-Lx, x: Cycle No.j
"-"" : Flickering , *1 : Right side segment shows Fan No. 2 1
Self Inspection Functions for
Samurai Chiller
Continued...

Normal Indication
lf the unit is operated under a normal operation condition, the operation code
(refer to the table belowj is indicated on 7-Segment LED's of the control panel.
Code
Content
No. 1
Cycle
No. 2
Cycle
No. 3
Cycle
No. 4
Cycle
No. 5
Cycle
C 1 8 8 C 2 8 8 C 3 8 8 C 4 8 8 C 5 8 8
Power Supply, After Stoppage
C 1 C 8 C 2 C 8 C 3 C 8 C 4 C 8 C 5 C 8
Cooling Operation
C 1 8 F C 2 8 F C 3 8 F C 4 8 F C 5 8 F
Stoppage by Thermo-OFF
P U P U
Pump Operation, Warning of Pump Feedback
C 1 C 8 C 2 C 8 C 3 C 8 C 4 C 8 C 5 C 8
Activation of Current Limiter
C 1 E 0 C 2 E 0 C 3 E 0 C 4 E 0 C 5 E 0
lnitializing Electronic Expansion valve
For full technical details, refer to Technical Manual
Alarm Codes
Hitachi Product Catalogue | 107
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full technical details, refer to Technical Manual
RAC S-Series
Hitachi Product Catalogue | 109
1~/N
220-240V / 50Hz
ELB
A B C A B C L1 N
Indoor Outdoor
Key
Mains
Field supplied
isolator
Field supplied
fuse
ELB
Earth leakage
circuit breaker
Earth
3 core 1.5mm
shielded
4 core 1.5mm
shielded
Optional wiring
1~/N
220-240V / 50Hz
ELB
C
Optional
wired
controller
CN18
D L1 N C D
Indoor Outdoor
RAC Summit
<
5.0kW
Optional
wired
controller
C
N
1
8
Optional
wired
controller
C
N
1
8
C1
D1
C1
D1
C2
D2
C3
D3
C2
D2
C3
D3
Optional
wired
controller
C
N
1
8
1~/N
220-240V / 50Hz
ELB
L1
N
Indoor
Indoor
Indoor
Outdoor
Up to 6 |ndoor un|ts
RAC Multizone
1~/N
220-240V / 50Hz
ELB
Optional
wired
controller
CN18
L1 N A B C D A B C D
Indoor Outdoor
RAC WX8, Summit > 5.0kW, DH7
Wiring Diagrams
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full technical details, refer to Technical Manual
Wiring Diagrams
Indoor
Outdoor
Indoor
Outdoor
L1 N 1 2
2 A B 1 N L1
1~/N
220-240V / 50Hz
ELB
2 A B 1 N L1 2 A B 1 N L1
L3 N L1 L2 1 2
2 A B 1 N L1
3~/N
380-415V / 50Hz
ELB
2 A B 1 N L1 2 A B 1 N L1
To next un|t
To next un|t
Key
Field supplied
isolator
Field supplied
fuse
ELB
Earth leakage
circuit breaker
Earth
m 2 core 0.75m
shielded
Mains
Set Free Mini VRF
Utopia ES, IVX & Centrifugal
For full technical details, refer to Technical Manual
Hitachi Product Catalogue | 111
N L3 L2
A B C
L1
1 2 3 4
ELB
ELB
ELB
L1 N
B A 2 1
3~/N
380-415V/50Hz
ELB
1~/N
220-240V/50Hz
N L3 L2 L1
1 2 3 4
N L3 L2 L1
1 2 3 4
L1 N
B A 2 1
ELB
ELB
ELB
L1 N
B A 2 1
L1 N
To next unit
B A 2 1
Indoor
Outdoor
Key
Field supplied
isolator
Field supplied
fuse
ELB
Earth leakage
circuit breaker
Earth
m 2 core 0.75m
shielded
Mains
Wiring Diagrams
Set Free 2-pipe heat pump
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
For full technical details, refer to Technical Manual
Wiring Diagrams
N L3 L2
A B
L1
1 2 3 4
ELB
ELB
L1 N
B A 2 1
3~/N
380-415V/50Hz
ELB
1~/N
220-240V/50Hz
N L3 L2 L1
1 2 3 4
L1 N
B A 2 1
ELB
ELB
ELB
ELB
ELB
ELB
L1 N
B A 2 1
L1 N
B A 2 1
N L1 2 1
3 4
N L1 2 1
3 4
N L1 2 1
3 4
CH Box
Outdoor
Indoor
CH Box
To next un|t
To next un|t
To next un|t
Key
Field supplied
isolator
Field supplied
fuse
ELB
Earth leakage
circuit breaker
Earth
m 2 core 0.75m
shielded
Mains
Set Free 3-pipe heat recovery
Hitachi Product Catalogue | 113
DIP Switches
No. of refrigerant
cycle (setting for
the first digit)
Address of the
indoor unit (setting
for the first digit)
Address of the
indoor unit (setting
for the first digit)
No. of refrigerant
cycle (setting for
the first digit)
DSW5 / DSW10
DSW4 / DSW1
Setting of DIP switches and RSW switches
Notes:
1.Turn off the power supply before setting the DIP switches. Otherwise, the switch settings are invalid.
2.To set the position of the RSW rotary switches, insert a screwdriver into the groove of the RSW.
For full technical details, refer to Technical Manual hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Conditions of Sale
(7) In the case of the Buyer residing in the United Kingdom, unless otherwise
stated, HITACHI will at its own expense deliver to the Buyers premises. In
the case of exports, unless otherwise stated, delivery will be FOB
(Incoterms 2000) at a U.K. port designated by HITACHI.
(8) The delivery by HITACHI of a greater or lesser quantity of the Goods than
the quantity provided for in the Contract, the delivery of other goods not
provided for in the Contract, or the delivery of the Goods only some of
which are defective, shall not entitle the Buyer to reject all of the Goods
delivered. In order that HITACHI can comply with its carriers conditions
any claim in respect of error in quantity or type of Goods or in respect of
damage to the Goods in transit must be made in writing to HITACHI and
the carrier notified in both cases within 3 days of receipt of the Goods.
Failure to make such claim shall constitute unqualified acceptance of the
Goods and waiver by the Buyer of all claims relating to error in quantity or
type of goods delivered or relating to the condition of Goods delivered.
Similarly, if any Goods invoiced by HITACHI are not delivered, in order that
HITACHI can claim against its carriers where appropriate the Buyer must
notify HITACHI within 10 days of the date of invoice, failing which the
Buyer will be liable to pay for the Goods in full. Where liability for error in
quantity, or type of Goods or in respect of damage to the Goods in transit
is accepted by HITACHI, HITACHIs only obligation shall be, at its option,
to make good any shortage or non-delivery and/or as appropriate to
replace or repair any Goods found to be damaged or defective and/or to
refund the cost of such Goods to the Buyer.
(9) If the Buyer refuses or fails to take delivery of Goods tendered in
accordance with this Contract HITACHI shall be entitled to terminate this
Contract with immediate effect, to dispose of the Goods as HITACHI may
determine, and to recover from the Buyer any loss and expenses incurred
as a result of such refusal or failure.
(10) Section 32 (2) of the Sale of Goods Act 1979 shall not apply. HITACHI
shall not be required to give the Buyer the notice specified in Section 32
(3) of the Act.
(11) Unless expressly agreed in writing by HITACHI, all Goods shall be packed
in accordance with HITACHIs standard practice. The Buyer shall meet the
costs of any special packaging requested by the Buyer or any packaging
rendered necessary by delivery by any means other than HITACHIs normal
means of delivery.
5. RISK AND TITLE
(1) Notwithstanding delivery, property in the Goods supplied shall remain with
HITACHI until those Goods and any other goods the subject of any other
contract with HITACHI have been paid for in full (together with any accrued
interest) and until property passes in accordance with this term:-
(a) Risk in the Goods shall pass on delivery and the Buyer shall store the
Goods separately or in such a way as will show clearly that they are
HITACHIs property and the Buyer will ensure that they are kept in good
condition and insured against loss or damage for HITACHIs benefit. Until
property in the Goods passes to the Buyer, the Buyer shall hold the
proceeds of any claim on the insurance policy on trust for HITACHI and
shall immediately account to HITACHI with the proceeds.
(b) The Buyer shall hold the Goods in a fiduciary capacity and as bailee for
HITACHI who may without prejudice to any other of its rights repossess
the Goods to which it has retained title as aforesaid and thereafter re-sell
the same and for this purpose the Buyer hereby grants an irrevocable right
and licence to HITACHIs servants and agents to enter upon all or any of
its premises with or without vehicles during normal business hours for the
purpose of inspecting and/or repossessing Goods to which it has retained
title. This right shall continue to subsist notwithstanding the termination of
this Contract for any reason and is without prejudice to any accrued rights
of HITACHI hereunder or otherwise.
(c) The Buyer may dispose of the Goods in the ordinary course of its business
as principal and may pass title to a third party but the proceeds of sale
arising therefrom shall be kept in a separate account on trust for HITACHI
until such time as full payment for the Goods supplied has been made.
(d) HITACHI may at any time detach or separate any of its Goods which may
have been incorporated in or attached to goods belonging to the Buyer or
any third party.
(2) HITACHI reserve the right, exercisable at its option by notice in writing to
the Buyer, to waive the provisions of subclause 5(1) above at any time
before payment has been made for the Goods supplied by the Buyer and
to declare that property in the Goods shall have passed to the Buyer.
(3) Notwithstanding that property in the Goods shall not have passed to the
Buyer, HITACHI, without prejudice to any other of its rights, may sue for
the price of the Goods supplied in the event that payment is not made on
the due date.
(4) Any return of Goods wholly or partly by the Buyer to HITACHI, except in
the case of defective Goods pursuant to Clause 8, shall be subject to
HITACHIs prior written consent and Buyers payment to HITACHI of
interest charges for the period from the date of HITACHIs shipment of
1. DEFINITIONS
In these conditions;
(1) HITACHI means: Hitachi Air Conditioning Europe SAS, UK Branch
(registration no. BR015653), Whitebrook Park, Lower Cookham Road,
Maidenhead, Berkshire, SL6 8YA, United Kingdom.
(2) Buyer means: the person, firm or company specified overleaf, to whom
HITACHIs Quotation, Sales Confirmation or Invoice is addressed.
(3) Goods means: the goods to be sold by HITACHI to the Buyer under the
Contract.
(4) Contract means: the contract of sale hereby formed between HITACHI
and Buyer.
2. CONSTRUCTION OF CONTRACT
(1) The terms of the Contract shall consist of the particulars overleaf and
these conditions. Any term overleaf which is at variance with these
conditions shall prevail over these conditions, which shall be construed
accordingly, except with regard to price in respect of which provisions of
subclause 6 (2) shall prevail.
(2) No other terms (whether contained in any document issued by the Buyer
or in any written or oral communication between the parties) shall apply to
the Contract nor shall these conditions or the particulars overleaf be
modified without HITACHIs written agreement.
(3) These conditions and the particulars overleaf shall be a complete record of
the agreement between the parties with regard to the sale of the Goods.
These conditions apply to all sales of Goods by HITACHI to the Buyer and
shall apply in place of and prevail over any terms or conditions contained
or referred to in the Buyers order or in correspondence or elsewhere or
implied by trade, custom, practice or course of dealing unless agreed to in
writing pursuant to subclause 2 (2) above and any purported provisions to
the contrary are hereby excluded or extinguished.
(4) The Buyer must ensure that any pre-contractual representation on which it
wishes to rely has been specified in the particulars overleaf. In entering the
Contract, the Buyer does not rely upon any such representation made by
or on behalf of HITACHI which has not been so specified.
(5) The acceptance by HITACHI of any Buyers order, wholly or partly, does
not imply any commitment by HITACHI to accept any other order (or any
other part of an order) whenever placed.
3. QUOTATIONS AND ORDERS
(1) Unless accepted before lapse or withdrawal, or renewed in writing by
HITACHI, quotations shall lapse automatically after 30 days, but may be
withdrawn earlier by HITACHI.
(2) Quotations are for information only and are not firm offers. There shall be
no binding contract until HITACHI has accepted the buyers order by
despatching HITACHIs official Sales Confirmation.
4. DELIVERY
(1) The scope of supply by HITACHI under the Contract shall be strictly limited
to those specified overleaf, and no other goods or services are included.
(2) HITACHI will use all reasonable endeavours to deliver the Goods on or
before the delivery date specified overleaf, however, HITACHI does not
undertake, guarantee or warrant that delivery will be made on the delivery
date specified.
(3) Any such delivery date specified shall be extended by any period or
periods during which the manufacture or delivery of the Goods or other
work by HITACHI in connection with this Contract is prevented, hindered,
delayed or rendered uneconomic by reason of a Force Majeure Event (as
defined in clause 19 below).
(4) The Buyer acknowledges that, in the case of semiconductor products,
optoelectronic products and other electronic components, due to the
advanced technology in the Goods and the specialist nature of the
manufacturing process, manufacture of the Goods by HITACHIs normal
means may result in a loss of yield. In the event of such a loss of yield
HITACHI shall notify the Buyer and shall use its best endeavours to supply
the Goods in accordance with this Contract. If due to a Force Majeure
Event or due to loss of yield HITACHI has insufficient stocks to meet all its
commitments HITACHI may apportion stock between its customers at its
sole discretion.
(5) If any delivery time specified overleaf is so extended by more that 90 days
then the Buyer shall be entitled to give written notice to HITACHI requiring
the Goods to be delivered within 30 days of the date of such notice, failing
which the Buyer shall have the right to give further written notice
determining the Contract forthwith.
(6) HITACHI shall be entitled to deliver the Goods in one or more instalments.
Where delivery is effected by instalment each instalment shall be treated
as a separate contract. Delay in delivery or other default of any instalment
shall not relieve the Buyer of its obligations to accept and pay for the
remaining deliveries.
Hitachi Product Catalogue | 115
Conditions of Sale
from defective materials, faulty workmanship or otherwise howsoever
arising and whether or not caused by the negligence of HITACHI, its
employees or agents SAVE THAT HITACHI shall accept liability for death
or personal injury caused by the negligence of HITACHI.
9. INSOLVENCY AND DEFAULT
If the Buyer fails to pay HITACHI in accordance with these conditions or
breaches any other of these conditions or any other contract with HITACHI
or enters into a deed of arrangement or commits an act of bankruptcy or
compounds with his creditors or if a receiving order is made against him or
if (being a company) an order is made or a resolution is passed for the
winding-up of the Buyer (otherwise than for the purposes of amalgamation
or reconstruction previously approved in writing by HITACHI) or if a receiver
is appointed over any of the Buyers assets or undertakings or if
circumstances arise which entitle the Court or a creditor to appoint a
receiver or manager or which entitle the Court to make a winding-up order
or if the Buyer takes or suffers any similar or analogous action in
consequence of debt HITACHI may, without prejudice to its other rights,
postpone delivery or manufacture (both in respect of the Contract in
question and any other contracts HITACHI might have with the Buyer) until
such payment has been made or other breach rectified and/or (at its
option) to terminate the Contract (and/or any other such contracts) and to
recover payment for all deliveries already made and for the cost of materials
and labour already expended for the purpose of future deliveries (less any
allowance of the value thereof as utilised by HITACHI for other purposes)
and also to recover from the Buyer a sum equivalent to HITACHIs loss of
profit arising out of such termination. The exercise of HITACHIs option to
postpone delivery or manufacture shall not prevent the subsequent
exercise of HITACHIs option to terminate the Contract and/or any other
such contracts.
10. THIRD PARTY RIGHTS
(1) In this clause 10 Third Party Rights shall mean any rights under letters
patent, registered or unregistered designs, trademarks, copyright or any
other intellectual property rights and rights in know-how whether or not
capable of being protected by statute, which are owned or controlled by
any third party.
(2) Where any of the Goods are produced to the Buyers specification or where
the Buyers use of the Goods infringes any Third Party Rights
notwithstanding that the Goods themselves do not constitute such an
infringement, the Buyer shall indemnify HITACHI against all actions, claims,
costs, damages or losses arising from any infringement of such rights in
respect of the Goods so produced or the use to which the Buyer has put
the Goods as the case may be.
(3) Any reference by HITACHI to patents, copyright, registered designs, trade
marks and analogous forms of protection shall not constitute a warranty of
the validity thereof.
(4) HITACHI does not warrant that the Goods do not infringe any Third Party
Rights, and all warranties to that effect whether express or implied,
statutory or otherwise are hereby excluded. If at any time it is alleged that
the Goods infringe any Third Party Rights, or if in HITACHIs reasonable
opinion such an allegation is likely to be made, HITACHI may at its option
and at its own expense:
(a) modify or replace the Goods without detracting from the overall
performance of the Goods, so as to avoid the infringement; or
(b) procure for the Buyer the right to continue to use the Goods; or
(c) repurchase the Goods at the price paid by the Buyer.
(5) HITACHI shall have no liability to the Buyer in the event of Goods infringing
or being alleged to infringe any Third Party Rights. In the event that the
Goods are or may be the subject of Third Party Rights, HITACHI shall be
obliged to transfer to the Buyer only such right, title or interest as HITACHI
may have.
(6) The Buyer shall notify HITACHI forthwith of any claim made or action
brought or threatened alleging infringement of any Third Party Rights.
HITACHI shall have control over and conduct any such proceedings in such
manner as it shall determine. The Buyer shall provide all such reasonable
assistance in connection therewith as HITACHI may request.
11. SPECIFICATIONS AND INFORMATION
(1) Unless expressly agreed in writing by HITACHI, all drawings, designs,
specifications and particulars of dimensions and weights and other such
information submitted by HITACHI are approximate only and HITACHI shall
have no liability in respect of any deviation therefrom. HITACHI shall be
entitled to amend the technical specifications of the Goods without notice.
(2) HITACHI accepts no responsibility for any errors, omissions or other
defects in any drawings, designs or specifications prepared by, or on behalf
of, the Buyer or the Buyers agents, sub-contractors or employees, and
HITACHI shall be indemnified by the Buyer against any and all liabilities and
expenses incurred by HITACHI arising therefrom.
such Goods to the Buyer to the date of HITACHIs receipt of such Goods.
Freight, insurance and any other expenses incurred in connection with
such return shall be borne by the Buyer.
6. PRICES
(1) Unless otherwise stated overleaf, prices of the Goods shall be exclusive of
VAT, export duty and foreign import duty and any other import or other
taxes, which shall where applicable be the subject of additional charges.
(2) Prices stated in any quotation or in HITACHIs Sales Confirmation are
provisional only and subject to adjustment to take account of increases in
HITACHIs costs and overheads, including, without limitation, costs of
carriage and labour costs. The Contract price shall be HITACHIs price
ruling at the date of despatch. All quotations/sales confirmations and
invoices are issued subject to the unconditional reservation of HITACHIs
right to adjust prices in respect of the following:-
(a) Changes in the prevailing exchange rate between the currency in which
the price is to be paid and the Japanese Yen.
(b) Changes in the current EU import duty.
7. PAYMENT
(1) (1) If HITACHI has granted the Buyer credit facilities, the payment of the
price must be made in full within 30 days of the date of invoice, unless
otherwise specified overleaf or agreed to by HITACHI. Any extension of
credit allowed for the Buyer may be changed or withdrawn at any time.
Where no credit has been granted, payment must be made in full in cash
prior to delivery. Payment shall be made in full direct to HITACHI in the
currency invoiced. The Buyer shall not be entitled to exercise any right of
set-off, counterclaim, abatement or analogous deduction against payment
due to HITACHI. Time of payment is of the essence of a Contract.
HITACHI reserves the right to suspend the provision of Goods to the
Buyer where any amounts are overdue under any Contract with the Buyer
until all such amounts have been paid.
(2) HITACHI shall be entitled to charge daily interest on any overdue sum at
the rate of 3 per cent per annum above the current base lending rate of
Barclays Bank PLC from due date until the date of actual payment in full
(including any accrued interest) (after, as well as before, judgement).
(3) If, in the opinion of HITACHI, the creditworthiness of the Buyer shall have
deteriorated prior to the delivery, HITACHI may require full or partial
payment of the price prior to delivery or the provision of security for
payment in full (including any accrued interest) by the Buyer in a form
acceptable to HITACHI notwithstanding any credit terms that may have
been agreed between HITACHI and the Buyer.
(4) Notwithstanding any purported contrary appropriation by the Buyer, all
payments made by the Buyer to HITACHI shall be appropriated first to
Goods which have been resold by the Buyer and then to Goods which
remain in the possession or under the control of the Buyer.
(5) HITACHI is entitled to offset any amount owing to it from the Buyer against
any amount owed to the Buyer by HITACHI.
8. DEFECTIVE GOODS
(1) If the Goods are defective on delivery, and the defects arise from faulty
materials or workmanship and are not caused by fair wear and tear,
abnormal or unsuitable conditions of storage, transportation or use, or the
combination of the Goods with any goods not supplied by HITACHI or any
act, neglect or default of the Buyer or any third party and HITACHI is given
written notice of the defects promptly upon discovery by the Buyer and at
any rate within six months (or such other period of time as may specifically
be agreed to by HITACHI for certain types of Goods) after delivery then,
unless otherwise specified overleaf, HITACHIs sole obligation shall be (at
its option) to repair or replace the defective item or allow the Buyer the
price thereof and to pay or reimburse the reasonable carriage charges for
the return of defective Goods to HITACHI and for delivery of the replaced
or repaired item.
(2) Unless otherwise agreed between HITACHI and the Buyer, if any of the
Goods are not HITACHI made, the provisions of subclause 8(1) above
shall apply only to the extent covered by any warranty made by the
supplier of such Goods to HITACHI.
(3) The Buyer shall retain the Goods at its premises until instructed by
HITACHI to return them. Goods alleged to be defective shall be subject to
inspection and testing by HITACHI at its own or (if HITACHI so chooses) at
the Buyers premises and the Buyer shall allow HITACHI adequate facilities
at the Buyers premises to investigate the complaint.
(4) Subject to subclause 8(1) above, HITACHI gives no representation or
warranty and there is not incorporated in the Contract any condition
whether express or implied, statutory or otherwise, as to the Goods other
than the statutory warranty of title, and any such representations,
conditions or warranties are hereby expressly excluded and HITACHI shall
be under no liability to the Buyer for any loss, damage or injury (including
special, direct, indirect or consequential loss and loss of profit) resulting
hitachiaircon.com
Email: aircon.enquiries@hitachi-eu.com
Call: 01628 585 394
Conditions of Sale
16. WAIVER
Failure by HITACHI to exercise or enforce any rights hereunder shall not
be deemed to be a waiver of any such right nor operate so as to bar the
exercise or enforcement thereof at any time or times thereafter.
17. NOTICES
Any notice hereunder shall be deemed to have been duly given if sent by
pre-paid first class post, telex, or telefax to the party concerned as its last
known address. Notices sent by first class post shall be deemed to have
been given seven days after despatch and notices sent by telex or telefax
shall be deemed to have been given on the date of despatch.
18. CANCELLATION
The contract may be cancelled or rescheduled by the Buyer only with
HITACHIs written consent. In the event of such cancellation the Buyer
shall pay to HITACHI a cancellation charge, equal to HITACHIs cost
incurred up to the date of cancellation plus HITACHIs loss of profit.
The amount of such charge shall be notified to the Buyer upon HITACHIs
written acknowledgement of cancellation and shall be paid within 30 days
of such notification.
19. FORCE MAJEURE
(1) If HITACHI is prevented, hindered or delayed from or in supplying the
Goods in accordance with these conditions by a Force Majeure Event
HITACHI may, at its option:
(a) suspend deliveries while the Force Majeure Event continues;
(b) if HITACHI has insufficient stocks to meet its commitments, apportion
available stocks between its customers as it decides; or
(c) terminate any contract so affected with immediate effect by written notice
to the Buyer; and HITACHI shall not be liable for any loss or damage
suffered by the Buyer as a result.
(2) In this clause Force Majeure Event means an event beyond the
reasonable control of HITACHI including, without limitation, strike, lock-out,
labour dispute or shortage of labour, act of God, war, riot, civil commotion,
malicious damage, compliance with a law or governmental order, rule,
regulation or direction, accident, breakdown of plant or machinery, fire,
flood, storm, earthquake, shortage of utilities, materials or other
circumstances affecting the supply of materials from HITACHIs normal
source of supply for materials for the Goods.
20. LAW AND JURISDICTION
The Buyer shall be responsible for all obligations, financial or otherwise,
imposed in respect of the Goods, on either of the parties, under any
environmental legislation applicable to the parties, including but not limited
to Directive 2002/96/EC on waste electrical and electronic equipment and
any legislation enacted pursuant to it.
21. LAW AND JURISDICTION
The law of the Contract shall be English law and the parties hereby submit
to the jurisdiction of the English Courts save that HITACHI shall be entitled
to bring proceedings against the Buyer in the courts of any jurisdiction
where the Buyer resides or carries on business.
22. INTELLECTUAL PROPERTY RIGHTS
The Buyer agrees that it shall not obtain any right, title or interest in or to
any intellectual property (including, without limitation, patents, trademarks,
registered or unregistered designs, copyrights and rights in designs or
inventions) in the Goods and that it shall not do or permit anything to be
done in its use of such intellectual property in the Goods which would or
could jeopardise their validity.
23. GENERAL
(1) Headings herein are for easy reference purpose only, and shall not be
construed as defining the scope or meaning of any provisions.
(2) The invalidity, illegality or unenforceability of the whole or part of a
condition does not affect or impair the continuation in force of the
remainder of these conditions.
(3) A person who is not a party to this contract has no right under the
Contracts (Rights of Third Parties) Act 1999 to enforce any of its terms but
this does not affect any right or remedy of a third party which exists or is
available apart from that Act.
(4) A reference to a statutory provision includes a reference to the statutory
provision as modified or re-enacted or both from time to time and any
subordinate legislation made under the statutory provision.
April 2012
(3) All drawings, designs, specifications and information submitted by HITACHI
are confidential and shall not be disclosed to any third party without
HITACHIs written consent.
12. LIMITATION OF LIABILITY
(1) HITACHI shall not be liable for any indirect or consequential loss, loss of
revenue, loss of goodwill, and/or loss of anticipated savings in each case
howsoever caused.
(2) Without prejudice to subclause 12(1) HITACHI shall not be liable to the
Buyer for any loss or damage whether for negligence, breach of contract,
misrepresentation or otherwise, for a sum greater, in aggregate, than the
amount actually paid by the Buyer to HITACHI under the Contract.
(3) The limitation of liability in subclauses 12(1) and 12(2) above shall not
operate to exclude or restrict HITACHIs liability for fraud or deceit or for
death or personal injury caused by its negligence.
(4) For the avoidance of doubt HITACHI will have no liability to the Buyer for
any delays in deliveries due to circumstances described in subclauses 4(3)
and 4(4) of these conditions.
13. ASSIGNMENT
Neither party shall without the prior written consent of the other party
(which shall not be unreasonably withheld) assign or sub-contract any
of its rights or duties under the Contract and upon such consent being
given shall furnish copies of any such assignments to the other party.
14. LICENSES AND CONSENTS
(1) If any license or consent of any government or other authority shall be
required for the acquisition, carriage or use of the Goods by the Buyer,
the Buyer shall obtain the same at its own expense and if necessary
produce evidence of the same to HITACHI on demand. Failure to do so
shall not entitle the Buyer to withhold or delay payment of the price. Any
additional expenses or charges incurred by HITACHI resulting from such
failure shall be for the Buyers account.
(2) If HITACHI needs to obtain an export license from the competent
authorities of the U.K. or, in the case of a drop shipment, of another
country, the Buyer shall furnish HITACHI with all information required by
HITACHI for such purpose, including, but not limited to, the country of
ultimate destination and the name and address of the consignee, and
shall warrant that such information is true, accurate and sufficiently
detailed. The Buyer further agrees to take all necessary procedures in
connection therewith, including, but not limited to, application for and
acquisition of international import certificate, import license and delivery
verification, as applicable. The Buyer shall not directly or indirectly
re-export the Goods, wholly or partly, or any relevant technology, services
or technical data to those countries, the export of such Goods,
technology, services or data to which is restricted under the laws of the
government issuing the said relevant export license (except where such
export license specifically approves). In the event that any of the Goods,
or any materials, parts or components incorporated in them, or relevant
technical data supplied by HITACHI are of United States origin, the Buyer
agrees to comply with the U.S. Export Administration regulations.
(3) The Buyer shall not export, re-export or make available the Goods, wholly
or partly or any relevant technical data to any destinations subject to
United Nations, EC and/or national sanctions, or to any person or
organisation subject to United Nations, EC and/or national sanctions, or
for any purpose prohibited by such sanctions. The Buyer shall not resell
the Goods, whether directly or indirectly, for export to a country in breach
of any export controls, laws, rules or regulations of the country of origin of
the Goods.
(4) The Buyer confirms that the Goods or any relevant technical data will not
be used for purposes related to the proliferation of any weapons of mass
destruction (chemical, biological or nuclear weapons and related missiles).
(5) The Buyer shall keep documentation for at least four (4) years from the
date of HITACHIs shipments as evidence that all Goods supplied to the
Buyer have been received in the destination permitted under the laws of
the government issuing the export licence, and the Buyer will produce
such evidence upon HITACHIs request.
(6) HITACHIs obligations under any Contract shall be conditional upon all
necessary licenses or consents being obtained from the relevant
authorities.
(7) The Buyer shall separately confirm to HITACHI the strict observation
hereof (Notice of Confirmation).
15. TRADE TERMS
In any case where Goods are sold CIF or FOB or on the basis of
other international trade terms, the meaning of such terms contained
in Incoterms 2000 as revised from time to time shall apply except where
inconsistent with any of the provisions contained in these conditions.
Specications in this catalogue are subject to change
without notice in order that HITACHI may bring the latest
innovations to their customers, omitting typing errors.
Hitachi Air Conditioning Europe SAS.
Whitebrook Park, Lower Cookham Road, Maidenhead,
Berkshire SL6 8YA United Kingdom
tel: 01628 585 394
email: aircon.enquiries@hitachi-eu.com
www.hitachiaircon.com
HELGB PC 001_12