Академический Документы
Профессиональный Документы
Культура Документы
TM
Table of Contents
Section 1.0 General
1.1 1.2 1.3 1.4 1.5 1.6 1.7 Scope Codes and Standards Inspections Shipment Drawings Utilities Interconnecting Installation
Page
2 2 2 2 3 3 4 4 5 5 5 6 7 22 22 22 24 25 29 30 30 30 30 34 35 36
2.0
Instrumentation
2.1 2.2 2.3 2.4 Scope Identification Instrumentation Design Requirements Field Mounted Instruments
3.0
Control Panels
3.1 3.2 3.3 3.4 3.5 Scope Enclosures Programmable Logic Controllers Control Panel Assembly Operator Interface Terminal (OIT)
4.0
Installation
4.1 4.2 4.3 4.4 4.5 4.6 Scope Enclosures Electrical Equipment Grounding Air Tubing Instrument Installation Guidelines
1 of 36
TM
Table of Contents
2 of 36
TM
Table of Contents
3 of 36
TM
1.7
Interconnecting Installation Wiring from the Control Panel to each equipment skid and the Operators Console will be provided at the site by the purchaser following schematics supplied by the vendor. If required, a Motor Control Center (MCC) and local disconnect switches shall be provided by the purchaser. All wiring between vendor supplied motors or heaters and the MCC or disconnects is the responsibility of the purchaser. Where required, one instrument air connection point per equipment skid shall be provided for the purchaser to connect to the plant instrument air supply.
Table of Contents
4 of 36
TM
Table of Contents
5 of 36
TM
Table of Contents
6 of 36
TM
Figure 2-1: Differential Pressure Transmitter Electronic differential pressure transmitters shall be diaphragm actuated, low hysteresis, two wire type. Maximum measurement error shall not exceed 0.25% of span, including combined effect of linearity, hysteresis and deadband. Zero shift shall not exceed 0.25% of upper range limit for 100F temperature shift. Output signal shall be 4-20 mA DC. 4 mA shall correspond to 0% span, 20 mA to 100% span. Transmitters shall be factory calibrated for the specific application. Zero and span shall be field-adjustable within selected transmitter range. Process connections shall be 1/2" NPT and shall be suitable for manifold mounting. Three-valve, 316SS manifolds directly mounted to the transmitters shall be provided. Universal mounting brackets shall be included. Wetted parts shall be 316SS unless application requires other material. LCD indicators shall be provided with scale in engineering units and accuracy 0.1% of span. Integral square root extraction shall be provided for flow measurement.
Table of Contents
7 of 36
TM
Figure 2-2: Pressure-Type Level Transmitter Pressure type liquid level transmitters shall be flange mounted, diaphragm actuated, low hysteresis, two-wire type. Maximum measurement error shall not exceed 0.25% of span, including combined effect of linearity, hysteresis and deadband. Zero shift shall not exceed 0.25% of upper range limit for 100F temperature shift. Output signal shall be 4-20 mA DC. 4 mA shall correspond to 0% span, 20 mA to 100% span. Transmitters shall be factory calibrated for the specific application. Zero and span shall be field-adjustable within selected transmitter range. Process connection shall be via a 3", 150 lb., 316SS flange, unless application requires other material or flange rating. All wetted parts shall be 316SS unless application requires other material. The transmitter fill material shall be silicone, unless otherwise noted. LCD indicators shall be provided with 0-100% scale and accuracy of 0.1% of span.
Table of Contents
8 of 36
TM
Table of Contents
9 of 36
TM
Table of Contents
10 of 36
TM
Conductivity analyzer/ transmitters shall be electronic two or four wire type, with temperature compensation, flow-through temperature compensated sensor, sample well and automatic isolation valve where required. Sensors for dilute acid and dilute caustic concentration measurements shall be inserted directly into the process lines for safety reasons. Maximum measurement error shall not exceed the following values: accuracy of 1% of full scale. repeatability of 0.5% of full scale.
Output signals shall be 4-20 mA DC. 4 mA shall correspond to 0% span, 20 mA to 100% span. Analyzers shall contain an integral indicator with engineering units scale. Regenerant analyzers shall indicate concentration percentages. Conductivity sensors shall be supplied with cable for connection to the analyzer.
Table of Contents
11 of 36
TM
pH analyzers shall be electronic two or four-wire type with temperature compensation, flow-through temperature compensated sensor, sample well and automatic sample valve where required. Maximum measurement error shall not exceed the following values: accuracy of 0.03 pH. repeatability of 0.01 pH.
Output signal shall be 4-20 mA DC. 4 mA shall correspond to 0% span, 20 mA to 100% span. Analyzers shall contain an integral indicator with engineering units scale. pH electrodes shall be supplied with a cable for connection to the analyzer.
Table of Contents
12 of 36
TM
Figure 2-6: Silica Analyzers Silica analyzers shall be rangable with output programmable over the range 0-5000 ppb of SiO2. Output signals shall be 4-20 mA DC. Analyzers shall be microprocessor based and shall incorporate the heteropoly blue method using ascorbic-acid reduction for analysis. Analyzers shall contain an integral indicator with engineering units scale. Maximum measurement error shall not exceed 1 ppb at a range of 0-100 ppb. Automatic reagent shut-off shall be provided.
Table of Contents
13 of 36
TM
Figure 2-7: Sodium Monitor Sodium monitors shall be electronic four wire type, with temperature compensation, flow-through temperature compensated sensor, sample well and automatic isolation valve when required. Maximum measurement error shall not exceed the following values: accuracy of +/- 0.4% of span repeatability of +/- 0.5% of span
Output signals shall be 4-20 mA DC. 4 mA shall correspond to 0% span, 20 mA to 100% span. Monitors shall contain an integral indicator with engineering units scale. Sensors shall be supplied with cable for connection to the monitor.
Table of Contents
14 of 36
TM
Output signals shall be 4-20 mA DC. Local indicators shall be provided. Maximum linearity measurement error shall not exceed 1% of full range.
Table of Contents
15 of 36
TM
Magnetic flowmeters shall include a flow tube and remote flow indicator. Maximum measurement error shall not exceed 1% of range. Output signals shall be 4-20 mA DC. Flow tubes installed in lined or other non-conductive pipe shall have grounding rings.
Table of Contents
16 of 36
TM
Figure 2-10: Differential Pressure Switch All wetted parts shall be 316SS, or as application requires. Maximum error shall not exceed the following values: 5% of full scale. 1% of full scale - repeatability of set point.
One single-pole double-throw contact shall be provided. Rating shall be 5 A at 120 VAC minimum. Where indication is required, scales shall be direct-reading type.
Table of Contents
17 of 36
TM
Figure 2-11: Pressure Indicator Pressure indicators shall be bourdon tube or bellows, back blow-out type. Materials of construction shall be suitable for the application. All wetted parts shall be 316SS. Maximum indication error shall not exceed 1% of span. Indicator dials shall be minimum 2-1/2" in diameter. Normal operating range shall be between 33 and 67% of span. Pigtail syphons for direct-mounting shall be provided for steam service. Isolating diaphragms with silicone fill, unless otherwise noted, shall be provided where required by process, complete with 1/2" NPT inlet and outlet connections.
Table of Contents
18 of 36
TM
Figure 2-12: Differential Pressure Flow Indicator Differential pressure flow indicators shall be bellows, diaphragm or piston type. Materials of construction shall be suitable for the application. Maximum indication error shall not exceed 5% of span. Indicator dials shall be minimum 4-1/2" In diameter. Normal operating range shall be between 33 and 67% of span. Process connections shall be 1/4" NPT. 2.4.15 Current-to-PneumatIc Transducers I/P Transducers shall accept 4-20 mA DC input signal. The output signal shall be 3-15 PSI. 4 mA inputs shall correspond to 3 PSI output (0% span); 20mA inputs shall correspond to 15 PSI output (100% span). Zero and span shall be field-adjustable. The instrument air inlet to the transducer shall be through a filter regulator provided by the vendor.
Table of Contents
19 of 36
TM
Figure 2-13: Filter/Regulator Filter/regulators shall be suitable for reducing pressure from 80-100 psig to 20-50 psig, as required. Filter/regulators shall have a 1.5" dial pressure gauge for outlet pressure measurement. Range shall be as noted on the drawings. Filters shall be a 5-micron grade or better. 2.4.17 Automatic Isolation Valves Automatic isolation solenoid valves shall be 2-way, 316SS body, 1/4" NPT connection, complete with screw type terminals and junction box. The valve housing including junction box shall be rated NEMA 4 as a minimum.
Table of Contents
20 of 36
TM
Table of Contents
21 of 36
TM
Table of Contents
22 of 36
TM
Table of Contents
23 of 36
TM
Figure 2-15: PLC Rack The PLC shall be selected from the Allen-Bradley PLC 5 Series of logic controllers, unless otherwise noted. Discrete I/O modules shall be 16 point - 1771-IAD and 1771-OAD (120 VAC) or 1771-IBD and 1771-OBD (24 VDC), or equal. Power supplies shall be - 1771 -P7 or 1771 -PS4, or equal.
29 Royal Road, Guelph, Ontario, Canada N1H 1G2 Telephone:(519) 836-0500, Fax:(519) 837-3067, Website www.glegg.com
Table of Contents
24 of 36
TM
Table of Contents
25 of 36
TM
Table of Contents
26 of 36
TM
Terminal Blocks Terminal blocks shall be compression type, capable of accepting a minimum of two 12 AWG wires and rated no less than 20 A. Terminal blocks shall be grouped according to function and voltage level. As a minimum, twenty percent spare terminals shall be provided. Terminal blocks shall be grouped as shown on the drawings. Jumpering of live voltages using non-insulated comb type jumpers will not be accepted isolated comb jumpers, wire jumpers or jumper bars shall be used. Terminal blocks shall be installed flush with the wiring duct. Terminal blocks shall be installed a minimum of six inches above the panel floor, and flush with the wiring duct front face. Not less than two inches shall be provided between terminal blocks and wiring duct or equipment for ease in wiring and wire number legibility. Terminal block groups shall be permanently identified with an engraved lamacoid nameplate as specified on the Control Panel drawings. Field side of terminal block shall be free of wiring. An empty run of wiring duct shall be provided for field wiring.
Table of Contents
27 of 36
TM
Table of Contents
28 of 36
TM
The OIT shall be a PC compatible workstation running Windows NT as a minimum. The PC shall meet or exceed the following requirements: 166 MHz processor, 512 Kilobyte Cache memory, 500 Megabyte hard drive, 32 Megabyte RAM memory, 16X CD-ROM, 104 key keyboard and 3 button mouse. The color monitor shall be 15-inch diagonal, SVGA capable with 0.28-mm dot pitch maximum. The OIT shall be located in a freestanding, NEMA 4 enclosure, separate from the control panel.
Table of Contents
29 of 36
TM
Table of Contents
30 of 36
TM
Low voltage wiring shall be color coded as follows: 120 VAC control signals red. 120 VAC power neutral AC ground foreign voltage 24 VDC 0 VDC DC ground 4 to 20mA (+) 4 to 20 mA (-) drain black. white. green. yellow. blue. blue with white stripe. green with white stripe. black. white. bare.
Table of Contents
31 of 36
TM
Table of Contents
32 of 36
TM
Table of Contents
33 of 36
TM
Table of Contents
34 of 36
TM
Air tubing shall be minimum diameter of 1/4". Air tubing shall be installed parallel to piping and close to support structures where practical. Each run of tube shall be continuously supported and held in place with the appropriate tubing clips and fasteners. Tubing supports shall be installed in a manner to preclude failure due to vibration. Each solenoid box shall be completely tubed and wired to all skid devices that are connected through the box. Solenoid cabinet shall be mounted on a rack at the equipment where the solenoids are tubed. Branch air supply piping from the air header shall be 1/2" schedule 40, carbon steel pipe conforming to class C, or 1/4" OD tubing. All branch takeoffs shall be from the top of the air header. Line size blowdown valves shall be provided for each air header run of different elevation.
Table of Contents
35 of 36
TM
Table of Contents
36 of 36