PAGE NO.

2 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION


TABLE OF CONTENTS


1.0 SCOPE

2.0 CROSS REFERENCES

3.0 APPLICABLE CODES AND STANDARDS

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General
4.2 Ratings
4.3 Materials
4.4 Cable Marking and Identification

5.0 TESTS

5.1 Type (Design) Tests
5.2 Routine (Production) Tests
5.3 Special Tests

6.0 PACKING AND SHIPPING

7.0 DATA SCHEDULE



PAGE NO. 3 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION
1.0 SCOPE

This SEC Transmission Material Standard Specification (TMSS) specifies the
minimum technical requirements for design, engineering, manufacture, inspection
testing and performance of Power and/or Control Cables, rated 600/1000V, intended to
be used in the system of Saudi Electricity Company (SEC), Saudi Arabia.


2.0 CROSS REFERENCES

This Transmission Material Standard Specification shall be read in conjunction with
the latest revision of SEC Transmission General Specification No. 01-TMSS-01 titled
General Requirements for all Equipments/Materials which shall be considered as an
integral part of this TMSS.

This TMSS shall also be read in conjunction with SEC Transmission Purchase Order
or Contract Schedules for project, as applicable.


3.0 APPLICABLE CODES AND STANDARDS

The latest revision/amendments of the Codes and Standards listed hereunder shall be
applicable for the equipment/material covered in this specification. In case of conflict,
the vendor/manufacturer may propose equipment/materials conforming to one group
of Industry Codes and Standards quoted hereunder without jeopardizing the
requirements of this TMSS.

3.1 IEC 60227-1 Polyvinyl Chloride Insulated Cables of Rated Voltages
up to and Including 450/750V, Part 1: General
Requirements

3.2 IEC 60229 Tests on Cable Oversheaths which have a Special
Protective Function and are applied by Extrusion.

3.2 IEC 60502-1 Power Cables with Extruded Insulation and their
Accessories for Rated Voltages from 1 kV up to 30 kV,
Part 1: Cables for Rated Voltages of 1 kV and 3 kV

3.3 ASTM B-3 Soft or Annealed Copper Wire

3.4 ASTM B-8 Concentric-Lay-Stranded Copper Conductors, Hard,
Medium-Hard, or Soft

3.5 ASTM B-33 Tinned Soft or Annealed Copper Wire for Electrical
Purposes

3.6 ANSI/NFPA 70 National Electrical Code

3.7 ICEA S-73-532 / Standard for Control Cables
NEMA WC 57



PAGE NO. 4 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

3.8 ICEA S-95-658 / Standard for Non-Shielded Power Cables Rated 2000
NEMA WC 70 Volts or Less for the Distribution of Electrical
Energy

3.9 ICEA T-27-581/ Standard Test Methods for Extruded Dielectric Power,
NEMA WC 53 Control, Instrumentation and Portable Cables

3.10 IEEE C37.122 Guide for Gas-Insulated Substations

3.11 UL 44 Standard for Safety Thermoset-Insulated Wires and
Cables

3.12 UL 83 Standard for Safety Thermoplastic-Insulated Wires and
Cables

3.13 UL 854 Standard for Safety Service-Entrance Cables

3.14 UL 1569 Standard for Safety Metal-Clad Cables


4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

4.1.1 The cable shall be manufactured in accordance with above mentioned
IEC standards or equivalent ICEA standards and shall meet or exceed
the requirements of this specification in all respects.

4.1.2 The cable shall be designed for use in all low voltage power and/or
control circuits and for installation in conduits, underground ducts or
cable trays/raceways or for directly buried installations as specified in
the Data Schedule.

4.1.3 For GIS applications, the control cable shall be properly shielded over
the assembled cores per IEEE C37.122.1 in the 1-30 MHz frequency
range.

4.2 Ratings

The cable ratings shall be as specified in Data Schedule.

4.3 Materials

4.3.1 Conductor

a. Conductor material shall be either annealed copper or aluminum
for power cables and annealed copper for control cables.



PAGE NO. 5 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION
b. Conductors 4 mm

and larger shall be stranded. Conductors


below 4 mm

may be stranded or solid as specified in the Data
Schedule.

c. When conductor tinning is specified in the Data Schedule, the
requirements shall be as per ASTM B-33 or equivalent.

4.3.2 Insulation

a. The insulation material shall be PVC or XLPE as indicated in
Data Schedule.

b. The insulation shall be heat and moisture resistant, and flame
retardant.

c. The minimum average thickness of the insulation shall be as
specified in Table 1.

d. For multiconductor cables, fillers shall be of nonhygroscopic
material compatible with the insulation and suitable for the
operating temperature of the cables.

Table 1: Minimum Average Thickness of Insulation

Nominal Cross
Sectional
Area of Conductor
Minimum Average
Thickness of Insulation
(mm)
(mm) PVC XLPE
1.5 - 2.5 0.8 0.7
4 - 6 1.0 0.7
10 - 16 1.0 0.7
25 - 35 1.2 0.9
50 1.4 1.0
70 1.4 1.1
95 1.6 1.1
120 1.6 1.2
150 1.8 1.4
185 2.0 1.6
240 2.2 1.7
300 2.4 1.8
400 2.6 2.0
500 2.8 2.2
630 - 2.2

4.3.3 Binder

When required, the binder (or separator) shall be a mylar tape, PVC
binder tape or extruded PVC layer applied over the assembled cores.
The average thickness of the binder shall not be less than 1 mm.


PAGE NO. 6 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

4.3.4 Metallic Shield

When specified in the Data Schedule, the metallic shield shall be a
helically applied flat bare copper tape.

4.3.5 Armor

a. For above ground installations, armor shall be a PVC jacketed,
close-fitting, flexible, corrugated aluminum sheath, seamless or
welded.

b. For direct burial, the cable armor shall consist of close-fitting
flexible corrugated impervious galvanized steel interlocked
sheath.

c. For power cable without grounding conductor, the total cross-
sectional area of the sheath (armor) shall be equal to the
minimum acceptable area of ground conductor required for the
circuit conductor size as listed in Table 2.

Table 2: Size of Armor

Size of Circuit Conductor
Size of Armor
(Minimum Size of
Ground Conductor)
mm AWG/kcmil mm AWG
2.5
4
6 - 10
16 - 25
30 - 70
85 - 130
150 - 200
230 - 330
350 - 450
500
630
14
12
10 - 8
6 - 4
3 - 2/0
3/0 250
300 400
450 650
700 - 900
1000
1250
2.5
4
6
10
16
25
35
35
50
70
-
14
12
10
8
6
4
3
2
1
1/0
-

d. Any bituminous or similar compound used as protective coating
between the sheath and the jacket shall have softening
temperature of 65C.

4.3.6 Jacket

The jacket shall be black, ST
2
type, extruded PVC per IEC 60502-1
with heat, moisture, oil, sunlight, acid, alkali and flame resistant
properties. For flame retardancy, a minimum oxygen index level of
30 % is required.


PAGE NO. 7 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

4.4 Cable Marking and Identification

4.4.1 The outer surface of the cable shall be durably and legibly marked in
English language and Arabic numerals at intervals of 1 (one) meter
with the following minimum information:

a. Rated voltage

b. Insulation Material

c. Conductor material, number of cores and size in mm

d. Manufacturer's name or trademark and country of origin

e. Year of manufacture

The marking shall start at a distance of 50 cm from the inner end of
the cable.

4.4.2 The jacket of all cables, excluding building wires, shall be marked
with the cumulative length at every one meter, with the highest length
mark on the outer end of the cable.

The length marking shall start at one meter distance from the inner
end of the cable, and shall not coincide with the markings described
in subclause 4.4.1.

4.4.3 Cables that cannot be conveniently marked because of physical
limitations of the outer surface, shall be provided with a printed tag or
tape attached to the cable.

4.4.4 On multiconductor power cable, each phase shall be permanently
identified with different solid colors. Identification for 3-phase
system without ground application shall be red, yellow, blue.

4.4.5 For systems with ground or neutral application, the black color shall
indicate the neutral conductor.

4.4.6 Green with yellow stripe insulated conductor shall be used in
equipment grounding.

4.4.7 Cores of multiconductor control cables shall be identified in
accordance with section 4 of IEC 60227-1 or part 5 of ICEA S-73-
532 (NEMA WC 57), section E.3.1, Method I.

4.4.8 Color of single core cable or wire shall be as specified in Data
Schedule.



PAGE NO. 8 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

5.0 TESTS

All test results shall be provided for review and acceptance by SEC.

5.1 Type (Design) Tests

All type (design) tests prescribed in the IEC 60502-1 or ICEA T-27-581
(NEMA WC 53) shall be performed on a representative unit or on the first unit
of every new design or rating to be supplied to SEC.

In lieu of the actual type (design) tests, certified test reports of type (design)
tests performed on an identical unit may be submitted to SEC for review and
approval during bidding stage.

5.2 Routine (Production) Tests

All routine (production) tests prescribed in IEC 60502-1 or ICEA T-27-581
(NEMA WC 53) standard shall be performed on all cables.

5.3 Special Tests

If required in Data Schedule, special tests shall be performed on all cables in
accordance with IEC 60502-1 or equivalent.


6.0 PACKING AND SHIPPING

In addition to the applicable requirements of 01-TMSS-01, the following packing and
shipping instructions are applicable.

6.1 The cable shall be delivered without splices on nonreturnable standard size
reels properly packed and lagged externally to provide physical protection for
the cable shipment and to facilitate field handling and long term storage.
Wood lagging shall have a minimum thickness of 25 mm.

6.2 The cable ends shall be sealed with a waterproof, heat shrinkable plastic or
elastomeric end cap with adhesive type sealing compound. Cable ends shall be
properly secured to the reel.

6.3 Reel Markings

6.3.1 Cable reels/drums shall be marked in legible and indelible letters
giving the following particulars:

a. Manufacturers name or trademark and country of origin
b. Year of manufacture
c. Type of cable
d. Number of cores and conductor size in mm
2
e. Cable rating


PAGE NO. 9 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION
f. Shipping length and overall diameter of cable
g. Minimum bending radius
h. Maximum pulling tension
i. Gross weight
j. Dimensions of reel
k. Direction of rolling of reel
l. Serial number of reel
m. J.O. number/contract number (if applicable)
n. SEC purchase order number
o. 11-TMSS-10, Rev. 0

6.3.2 All markings shall appear on both sides of the reel.



PAGE NO. 10 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION
7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,
600/1000V RATING

SEC Enquiry No. Date:

SEC Purchase Order
No.
Date:
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE CODES AND STANDARDS

Standards to which material shall conform *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

Cable application (Power or Control)

Cable installation
(conduit, duct, trays, direct burial, GIS etc.)

Voltage rating (kV) *

Fault current duration (sec.)

Available ground fault current (kA)
(when shielded cable is required)

Conductor DC resistance per km at 20C
()
*


'A'- SEC SPECIFIED DATA/PARAMETER.
'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.



PAGE NO. 11 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,
600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)

Conductor AC resistance per km at 20C
()
*

Minimum Insulation resistance per km at
20C (M)
*

Maximum permissible continuous
conductor temperature (C)
*

Maximum rated temperature of
insulation material (C)
*

Maximum permissible continuous
jacket temperature (C)
*

4.3.1 Conductor Material Cu / Al

Conductor cross sectional area (mm) *

For conductors 4mm and larger:
Number of strands per conductor *

Diameter of compacted strand (mm) *

Number of conductors *

For conductors below 4mm:
Stranding required ? Yes / No

Number of strands per conductor *

Diameter of compacted strand (mm) *

Number of conductors *




PAGE NO. 12 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,
600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS (Continued)

Outer diameter of conductor (mm) *

Is conductor tinning required? Yes / No

4.3.2 Insulation Material PVC / XLPE

Minimum average thickness of insulation
(mm)
*

Outer diameter over insulation (mm) *

Insulation shield material, if any

Thickness of insulation shield (mm) *

4.3.3 Binder required ? Yes / No

4.3.4 Metallic shield required ? Yes / No

Thickness of metallic shield (mm) *

4.3.5 Armor material, if any

4.3.6 Jacket Material PVC

Average jacket thickness (mm) *

Overall diameter of cable (mm) *

4.4.7 Reference standard for core
identification (IEC, ICEA)
*

4.4.8 Color of single core cable/wire (if
applicable)
*


PAGE NO. 13 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION

7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,
600/1000V RATING

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

5.0 TESTS

5.3 List of special tests, if required



6.0 PACKING AND SHIPPING

6.3 Cable weight (kg/km) *

Reel and cable weight (kg) *

Cable length per Reel (m) *

Total quantity required (m)

Cable reel diameter (mm) *

Cable reel width (mm) *

Maximum pulling tension (kN) *

Minimum bending radius (mm) *



PAGE NO. 14 OF 14 11TMSS10R0/YM


Date of Approval: March 18, 2006
11-TMSS-10, Rev. 0 TRANSMISSION MATERIALS STANDARD SPECIFICATION
7.0 DATA SCHEDULE

POWER AND/OR CONTROL CABLE, COPPER OR ALUMINUM CONDUCTOR,
600/1000V RATING

ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY
SEC:
A.







ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY
BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
B.







OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/
CONTRACTOR:
B.





Actual Manufacturer
of Equipment/Material
Vendor/Supplier/
Contractor

Name of the Company
Location and address



Name and Signature of
authorized
epresentative

and date


Official Seal/Stamp
of the Company &
Date