Вы находитесь на странице: 1из 64

VITOSOL

System Design Guidelines

Vitosol 200-F Vitosol 300-T


Model SP3

Viessmann solar collectors – Vitosol 200-F


the right solution for every application Flat plate solar collector for installation on pitched
and flat roofs, and for freestanding installation

Using solar energy to heat domestic hot water and to


provide a backup for space heating Vitosol 300-T
Vacuum tube solar collector, based on the heat pipe
principle, for installation on sloped and flat roofs and for
freestanding installation

5167 156 v3.1 05/2008


Safety, Installation and Warranty Requirements

Safety, Installation and Warranty Requirements

Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the
instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or
loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual
subsections).

H Licensed professional heating H Grounding/lightning protection of the


contractor solar system CAUTION
The installation, adjustment, service, In the lower part of the building, Avoid scratching or sudden shocks to
and maintenance of this equipment install an electrical conductor on the glass cover of the solar panel.
must be performed by a licensed solar circuit’s piping system in
professional heating contractor. compliance with local regulations.
Connection of the solar system to a
" Please see section new or existing lightning protection or CAUTION
entitled “Important the provision of local grounding should Never step on collectors or solder in
Regulatory and only be carried out by a licensed close proximity to the glass surface
Installation professional, who must take into of the solar panel.
Requirements”. account the prevailing conditions on
site.
H Applicability
H Product documentation Vitosol solar collectors are designed
Read all applicable documentation for use in closed loop heating systems
before commencing installation. Store CAUTION for domestic hot water heating, space
documentation near boiler in a readily Observe maximum load and distance heating and pool heating via a heat
accessible location for reference in from edge before installing the exchanger. The use of Viessmann
the future by service personnel. substructure to the roof. If necessary, heat transfer medium “Tyfocor-HTL”
consult with a structural engineer to is strongly recommended.
" For a listing of determine if the structure is suitable
applicable literature, for installing solar collectors. The
please see section collectors must be securely mounted IMPORTANT
entitled “Important so that the mountings can withstand
Regulatory and Safety intense wind conditions and local Pool water or potable water cannot be
Requirements”. snow loads. pumped directly through the Vitosol
collectors. Damage to collectors caused
by corrosion, freezing or scaling will
void warranty.
H Advice to owner CAUTION
Once the installation work is
Gloves and eye protection must be
complete, the heating contractor must
worn when handling solar panels.
familiarize the system
operator/ultimate owner with all
equipment, as well as safety
precautions/requirements, shut-down CAUTION
procedure, and the need for
Solar panel connection pipes and
professional service annually.
solar heating fluid can become hot
enough to cause severe burns.
Extreme caution must be taken if
H Warranty panels have been in a stagnant
Information contained in condition (no flow of fluid).
this and related product
documentation must be
read and followed. Failure
to do so renders warranty
null and void.
5167 156 v3.1

2
Contents

Contents Page

Safety Safety Instructions


Important Regulatory and Installation Requirements
General Information About these Instructions
Product Information
Important Regulatory and Installation Requirements
Basic Principles of Solar Technology Subsidies, Permits and Insurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Solar Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
HExploiting solar energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H Solar radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
H Global radiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
H Exploiting solar energy with collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
H Influence of alignment, inclination and shade on energy yield . . . . . . . . . 10
H Inclination and orientation of collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
H Angle of inclination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Overall System Optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Specification Construction and Function of Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13


H Vitosol 200-F – flat panel collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
H Vitosol 300-T – vacuum tube collector based on the heat pipe principle 14
Collector Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Solar coverage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Collector Installation and Mounting Details . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
H Installation options for different collector types . . . . . . . . . . . . . . . . . . . . . 18
H Vitosol 200-F flat panel collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
H Support weight requirements - Vitosol 300-T . . . . . . . . . . . . . . . . . . . . . . . . 24
General Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Notes on Planning and Operation Calculating the Required Absorber Surface Area . . . . . . . . . . . . . . . . . . . . . . 27
H Calculating the absorber surface area and DHW cylinder capacity . . . . . 27
H Calculating the absorber surface area for space heating . . . . . . . . . . . . . . 28

Sizing Pipe Diameters and Circulation Pump . . . . . . . . . . . . . . . . . . . . . . . . . . 31


H Sizing pipe diameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
H Installation examples for Vitosol 200-F, models SV2 and SH2 . . . . . . . . 35
H Collector pressure drop information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
H Sizing pipe circulation pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
H Technical information on the Solar-Divicon . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Safety Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
H Liquid capacity of solar heating system components . . . . . . . . . . . . . . . . . 37
H Diaphragm expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
H Technical data for the expansion tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
H Pressure relief valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
H High limit safety cut-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
H Thermostatic mixing valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5167 156 v3.1

3
Contents

Contents (continued) Page

System Designs General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44


H How to implement the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
System Design 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
H Dual-mode DHW heating with Vitocell-B 100 or Vitocell-B 300
DHW tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Design 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
H Dual-mode DHW heating and space heating backup
with heating water storage tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
System Design 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
H Dual-mode DHW heating with two DHW tanks . . . . . . . . . . . . . . . . . . . . . . 50
System Design 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
H Dual-mode DHW and swimming pool water heating . . . . . . . . . . . . . . . . . 53
System Design Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
H System with bypass circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
H Bypass circuit with solar cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
H System with energy-saving mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Appendix Calculation Example Based on the Viessmann ”ESOP” Program . . . . . . . . 58


H Solar heating systm with dual-coil DHW tank . . . . . . . . . . . . . . . . . . . . . . . 58
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

5167 156 v3.1

4
Safety

Important Regulatory and Installation Requirements

Codes Please carefully read this manual prior


The installation of solar heating to attempting installation. Any
systems might be governed by warranty is null and void if these
individual local rules and regulations for instructions are not followed.
this type of product, which must be
observed. The installation of this unit This product must be installed
shall be in accordance with local codes. observing not only the necessary
Always use latest editions of codes. product literature (see list), but also
all local, provincial/state plumbing and
Mechanical room building codes, as they apply to this
Ensure the mechanical room complies product and all periphery equipment.
with the requirements of the system
design guideline and/or technical data For information regarding other
manual. Viessmann System Technology
The solar storage tank must be installed componentry, please reference
in a mechanical room which is never documentation of the respective
subject to freezing temperatures. product.
If not in use and danger of freezing
exists in the mechanical room, ensure We offer frequent installation and
water in tank is drained. service seminars to familiarize our
partners with our products. Please
inquire.

Working on the equipment The completeness and functionality of


The installation, adjustment, service, field supplied electrical controls and
and maintenance of this equipment components must be verified by the
must be done by a licensed professional heating contractor. These include
heating contractor who is qualified and pumps, valves, air vents, thermostats,
experienced in the installation, service, temperature and pressure relief
and maintenance of solar heating controls, etc.
systems. There are no user serviceable
parts on this equipment.

Ensure main power supply to


equipment, the heating system, and all
external controls has been deactivated.
Take precautions in both instances to
avoid accidental activation of power
during service work.

Technical literature Leave all literature at the installation


Literature applicable to all aspects of site and advise the system
the Vitosol: operator/ultimate owner where the
- Technical Data Manual literature can be found. Contact
- Installation Instructions Viessmann for additional copies.
- Start-up/Service Instructions
- Operating Instructions
and User’s Information Manual
- System Design Guidelines
5167 156 v3.1

5
General Information

About these Instructions

Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include ”WARNING”, ”CAUTION”, and ”IMPORTANT”. See below.

Warnings draw your attention to the


WARNING presence of potential hazards or
Indicates an imminently hazardous important product information.
situation which, if not avoided, could
result in substantial product/property
damage, serious injury or loss of life.

Cautions draw your attention to the


CAUTION presence of potential hazards or
Indicates an imminently hazardous important product information.
situation which, if not avoided, may
result in minor injury or
product/property damage.

Helpful hints for installation, operation


IMPORTANT or maintenance which pertain to the
product.

This symbol indicates that additional,


pertinent information is to be found in
the adjacent column.

This symbol indicates that other


instructions must be referenced.

Product Information

Vitosol 200-F, Models SV2, SH2


Flat panel solar collector with 25 ft.2 /
2.3 m2 collector area.

Max. stagnation temperature 430°F /


221°C
Max. operating pressure 87 psig /
6 bar

Vitosol 300-T, SP3 Series


Vacuum tube solar collector with 22
and 32 ft.2 / 2 and 3 m2 collector area.

Max. stagnation temperature 302°F /


150°C
Max. operating pressure 87 psig /
6 bar
5167 156 v3.1

6
Basic Principles of Solar Technology

Subsidies, Permits and Insurance

Solar heating systems for DHW or Your local planning office will be able to
swimming pool heating are subsidised advise you about whether solar heating
by many regional and local authorities. systems need planning permission.
Request information about subsidies
from your local authority. Viessmann solar collectors are tested
Further information is available from our for impact resistance, incl. hail impact,
sales offices. in accordance with DIN EN 12975-2.
Nevertheless, we would recommend
you include the collectors in your
building insurance, to protect you from
losses arising from any extraordinary
natural phenomenon. Our warranty
excludes such losses.

Solar Energy

Exploiting solar energy

The sun has provided the earth with Thanks to the use of highly
light and heat for billions of years. sophisticated collectors and a perfectly
Without it, our existence on earth matched overall system, the economic
would be impossible. use of solar energy is no longer a
We have been using the sun’s heat futuristic vision, but a proven everyday
since time immemorial. In summer, it reality.
heats our buildings directly, while in Considering that fuel prices will
winter we make use of solar energy continue to rise in the years ahead,
stored in the form of wood, coal, oil and investing in a solar heating system can
gas, to provide heat for our buildings be viewed as a ”genuine” investment in
and domestic hot water. the future.
To protect fuel reserves, the heating
industry has committed itself to finding
more responsible ways of handling
these precious resources, which have
accumulated naturally over millions of
years.
One rational way of achieving this aim is
to make direct use of solar energy by
means of collectors.
5167 156 v3.1

7
Basic Principles of Solar Technology

Solar Energy (continued)

Solar radiation

Solar radiation represents a flow of


energy irradiated uniformly in all
directions by the sun. Of that energy,
an output of 429 Btu/h/ft.2 or
1.36 kW/m2, the so-called solar
S constant, hits the outer earth’s
atmosphere.

RT

Diffused celestial radiation Heat radiation of the absorber


Direct solar radiation Heat radiation of the glass cover
Wind, rain, snow, convection Useful collector output
Convection losses Reflection
Conduction losses RT Return
S Supply

Global radiation

6000
direct
After penetrating the earth’s
radiation atmosphere, the solar radiation is
5000 reduced by reflection, dispersion and
Solar irradiation in Wh/(m2 x d)

diffused
radiation absorption by dust particles and
4000 gaseous molecules. That portion of this
radiation which passes unimpeded
3000
through the atmosphere to strike the
earth’s surface is known as direct
2000
radiation.
1000
The portion of the solar radiation which
0 is reflected and/or absorbed by dust
Jan. Feb. March April May June July Aug. Sept. Oct. Nov. Dec. particles and gas molecules and
irradiated back strikes the earth’s
surface indirectly is known as diffused
radiation.

The total radiation striking the earth’s


surface is the global radiation Eg, i.e.,
global radiation = direct radiation +
diffused radiation.
In the latitudes of North America, the
typical global radiation under optimum
conditions (clear, cloudless sky at mid-
day) amounts to a max. of 317
5167 156 v3.1

Btu/h/ft.2 or 1 000 W/m2.


With solar collectors, as much as 75 %
of this global radiation can be utilised,
depending on the type of collector.

8
Basic Principles of Solar Technology

Solar Energy (continued)

Exploiting solar energy using solar collectors

The useful energy which a collector can The amount of global energy varies The type of collector, as well as its
absorb depends on several factors. from location to location (see maps inclination and orientation, are also very
The main factor is the total solar energy below). important (see page 10). If the solar
available. installation is to be operated
economically, careful dimensioning of
the system components is also
essential.
Annual global radiation in Canada

Btu/ft2/day
2.5 - 3 kwh/m2/day 787-945
3 - 3.3 kwh/m2/day 945-1040
3.3 - 3.6 kwh/m2/day 1040-1134
3.6 - 3.9 kwh/m2/day 1134-1228
3.9 - 4.2 kwh/m2/day 1228-1323
4.2 - 4.4 kwh/m2/day 1323-1386
4.4 - 4.7 kwh/m2/day 1386-1481
> 4.7 kwh/m2/day >1481

Annual global radiation in the United States

Btu/ft2/day
3 - 4 kwh/m2/day 945-1260

4 - 5 kwh/m2/day 1260-1575

5 - 6 kwh/m2/day 1575-1890

6 - 7 kwh/m2/day 1890-2205
5167 156 v3.1

Note: Average mean daily global radiation on a south-facing surface tilted at an angle equal to the latitude of the location.

9
Basic Principles of Solar Technology

Solar Energy (continued)

Influence of alignment, inclination and shade on energy yield

Optimum alignment and inclination


North Annual The solar generator provides the highest
irradiation
in % annual solar yield for a DHW system
when facing south with an inclination of
approx. 30 to 35 degrees
to the horizontal plane. However, the
installation of a solar heating system is
still viable even when the installation
deviates quite significantly from the
above (south-westerly to south-easterly
alignment, 25 to 55 degrees
West East
inclination).

The graph illustrates the loss of yield


resulting from an installation of the
collector array which is less than
perfect. The graph also indicates that a
shallower inclination is more favourable,
if the collector surface cannot be
pointed south. A solar heating system
Angle of with a 30º inclination and an alignment
South inclination of 45º south-westerly still achieves
95% of its optimum yield. Even with an
Example: east-westerly alignment, you can still
30°; 45° south-west expect 85% with a roof inclination
between 25º and 40º.

A more steeply sloped installation


would be more favourable in winter, but
the system achieves two thirds of its
yield during the summer months. On the
other hand, an angle of inclination less
than 20 degrees should be avoided,
otherwise the solar generator will
become too contaminated, or
snowcovered.

Installing the collector array on different


roofs requires complex hydraulic
interconnections between the individual
collectors.
Every array is equipped with a separate
collector temperature sensor and a
separate pump line.
The increase in energy yield is therefore
offset by the higher installation costs,
resulting in a significantly reduced
cost:benefit ratio.

Shade reduces energy yield

Position and size the collector array so


that the influence of neighbouring
structures, trees, power lines, etc.,
which throw shadows over the array, is
5167 156 v3.1

minimised. Also consider how


neighbouring properties will be likely to
develop over a period of 20 years, as
regards additional buildings, plants and
saplings.

10
Basic Principles of Solar Technology

Solar Energy (continued)

Inclination and orientation of collectors

To achieve optimum energy absorption,


the collectors must be oriented towards
the sun.
The angle of inclination and the azimuth
angle are the dimensions used to
determine the orientation of the
collectors.

Angle of inclination

Angle of inclination α

The angle of inclination a is the angle


between the horizontal and the collector
plane.
For pitched roof installations, the angle of
inclination is determined by the slope of the
roof.
The largest amount of energy can be
captured by the collector’s absorber when
the collector plane is aligned at right
angles to the irradiation of the sun.
Because the angle of irradiation depends
on the time of day and the time of year,
the collector plane should be aligned
according to the position of the sun during
IMPORTANT the phase of maximum energy supply.

The angle of inclination for Vitosol In practice, angles of inclination of


300-T collectors must be at least 25º in between 30 and 45º have proven to be
order to guarantee circulation of the ideal.
evaporator liquid in the heat pipe For most installations in North America,
for example, an angle of inclination of
between 25 and 70º is advantageous,
depending on the period of use.

Lower angles of inclination are better for


applications where more energy is
required in the summer months (i.e. pool
heating). Higher angles of inclination are
better for applications where more energy
is required in the winter months.
Capturing the maximum amount of energy
throughout the year can be achieved using
an angle of inclination equal to the latitude
of the building site. This is ideal for
domestic hot water heating applications.

Azimuth angle

The azimuth angle describes the deviation


Example:
Collector plane of the collector plane from south; the
Deviation from south: 15º east Azimuth angle collector plane aligned to the south is the
azimuth angle = 0º.
Because solar irradiation is at its most
5167 156 v3.1

intensive at midday, the collector plane


should be oriented as closely as possible
to the south. However, deviations from
south up to 45º south-east or south-west
have minimal impact on annual energy
production.

11
Basic Principles of Solar Technology

Overall System Optimization

A high-quality solar collector cannot by H a control unit that is tailored to the Correctly designed solar heating
itself guarantee the optimum operation individual solar heating system, systems with well matched system
of a solar installation. This depends H a DHW tank incorporating a solar heat components can cover 50 to 80 % of
more on the complete system solution exchanger low inside the tank, the annual energy demand for DHW
as a whole. H a preassembled pump station with all heating in detached and semi-detached
Viessmann supplies all the components necessary hydraulic components, houses.
required for a solar heating system: H design details aimed at achieving We will be pleased to assist you with
fast-responding control and therefore the design of solar heating systems.
maximum yields from the solar The elements of a solar heating system
heating system. are shown in the diagram.

T T
DHW

S R

DCW

Solar collector Brass elbow c/w sensor well Collector temperature sensor
Solar-Divicon (pumping station) Dual-mode DHW tank Fast air-vent, c/w shutoff valve *1
Overflow container I Tank temperature sensor
Expansion vessel Air separator R Return to collector
Solar manual filling pump Solar control unit S Supply from collector
System fill manifold valve Flexible connection pipe

*1 Install at least one air-vent valve (quick-acting air-vent valve or a manual vent valve, see page 43) at the highest point of
the system.
5167 156 v3.1

12
Specification

Construction and Function of Collectors

Vitosol 200-F flat panel collector

Vitosol 200-F flat plate solar collector is


available as:
H Vertical version Model SV2 and
horizontal version Model SH2, each
offering 2.3 m2 / 25 ft2 absorber
surface.

The main component of Vitosol 100 is


the Sol-Titanium coated copper
absorber.
It ensures high absorption of solar
radiation and low emission of thermal
radiation. A copper pipe through which
the heat transfer medium flows is fitted
to the absorber. The heat transfer
medium channels the absorber heat
through the copper pipe.
The meander-shaped direct flow
absorber of models SV2 and SH2
provides an extremely even flow
through each individual collector in the
collector arrays.
The absorber is surrounded by a highly
insulated collector housing which
minimises collector heat losses. The
high quality thermal insulation provides
temperature stability and is free from
gas emissions.
The cover comprises a solar glass panel.
The glass has a very low iron content,
thereby reducing reflection losses.

Continuous profiled seal (vulcanised) Mineral fiber


Aluminum frame sections The collector housing comprises a
Solar glass cover, 3.2 mm thick
Aluminum-zinc bottom panel powder-coated aluminium frame
Meander-shaped copper pipe
Connection pipe (recycled aluminium), within which the
Copper absorber
solar glass panel is permanently sealed.
Melamine resin foam
Model SV2 and SH2
Up to twelve collectors can be joined to
form a single collector array. For this
purpose, the standard delivery includes
flexible connection pipes, sealed with
O-rings.

A general connection kit with clamping


ring connections enables the collector
array to be readily attached to the pipes
of the solar circuit.
The collector temperature sensor is
installed in the solar circuit flow via a
Technical Data Vitosol 200-F, SV2/SH2 sensor well set.

Model Gross Area Absorber Aperture Dimensions Weight


Area Area
m2 ft2 m2 ft2 m2 ft2 mm in kg lb
5167 156 v3.1

SV2 2.51 27.0 2.32 25 2.33 25.1 1056x 41¾x 52 115


2380x90 93¾x3½
SH2 2.51 27.0 2.32 25 2.33 25.1 2380x90x 93¾x41¾x 52 115
1056 x3½

13
Specification

Construction and Function of Collectors (continued)

Vitosol 300-T vacuum tube collector

Vitosol 300-T vacuum tube collectors


are available in two types:
20 tube version,
30 tube version

The tube shape gives the collector great


stability and high impact resistence.
Re-evacuation of the tubes is not
necessary as the tubes have a
permanent airtight seal.

The vacuum in the glass tubes ensures


optimum heat insulation. Convection
losses between the glass tube and the
absorber are almost completely
eliminated. This enables the utilisation
of even low radiation levels (diffused
radiation). The performance of the
collector does not drop off as
significantly in cold weather as a flat
plate collector. On average,
approximately 30% to 50% higher
annual solar energy gain than flat plate
collectors can be expected.
Built into each vacuum tube is a
Sol-Titanium coated copper absorber. It
is a highly selective surface that
ensures high absorption of solar
radiation and low emission of thermal
radiation.

A heat pipe filled with an evaporator


liquid is arranged on the absorber. The
heat pipe is connected to the condenser
Evacuated glass tube Condenser via a flexible coupling. The condenser is
Heat pipe Double pipe heat exchanger mounted in a double pipe heat
Absorber exchanger.
This involves a so-called ”dry
connection”, i.e. pipes can be rotated or
replaced even when the installation is
filled and under pressure.
Heat is transferred from the absorber to
Technical Data Vitosol 300-T, 2m2/3m2 the heat pipe. This lets the liquid
evaporate. The vapour then rises to the
Model Gross Area Absorber Aperture Dimensions Weight condenser.
Area Area The heat is transferred to the passing
m2 ft2 m2 ft2 m2 ft2 mm in kg lb heat transfer medium by the
double-pipe heat exchanger containing
2m2 2.83 30.5 2.05 22 2.11 22.7 1419x 55¾x 45 99 the condenser which causes the vapour
1996x 78½x to condense. The condensate flows
122 4¾ back into the heat pipe and the process
is repeated.
3m2 4.24 45.6 3.07 33 3.17 34.1 2126x 83¾x 68 150
1996x 78½x Please note:
122 4¾ The angle of inclination must be at least
5167 156 v3.1

25º to guarantee circulation of the


evaporator liquid inside the heat
exchanger.

14
Specification

Construction and Function of Collectors (continued)

Vitosol 300-T (continued)

Absorber surface areas of up to 6 m2


can be joined to form a single collector
array. For this purpose, the standard
delivery includes flexible connection
pipes, sealed with O-rings.
A connection kit with clamping ring
connections enables the collector array
to be readily connected to the pipes of
the solar circuit.
The collector temperature sensor is
installed in a sensor mounting on the
flow pipe in the connection housing of
the collectors.

102mm /
4”

Legend

Groove for retaining clip


5167 156 v3.1

15
Specification

Collector Efficiency

Some of the solar radiation striking the The heat loss factors and optical If the difference between the collector
glass of the collectors is ”lost” due to efficiency combine to form the collector and ambient temperature is zero, the
reflection and absorption. The optical efficiency curve which can be collector loses no heat to the
efficiency ηo takes these losses into calculated on the basis of the following environment, and the efficiency η is at
account. formula: its maximum level; this is known as the
optical efficiency ηo.
When the collectors heat up, they
η = η o − k 1 ⋅ ∆T − k2 ⋅ ∆T
2
transfer heat to the environment as the Eg Eg The thermal capacity is a measure of
result of conduction, radiation and the thermal inertia of the collector, and
convection. These thermal losses are Eg= radiation intensity (W/m2) shows the response behaviour of the
allowed for by the heat loss factors k1 ∆ T = Temperature difference between collector when heating and cooling. A
and k2 . ambient air and collector fluid ºC low thermal capacity is of advantage
with wide ranging temparature and
weather conditions typical in northerly
climates.

The table below lists comparative


values for the optical efficiency and the
heat loss factors as tested in European
certification labs.
Vitosol 200-F and 300-T are both
tested and certified in North America to
SRCC OG-100.

Collector type Opt. efficiency Heat loss factors Spec. thermal


level capacity
p y
*1 in
i % kJ/( 2 · K)
kJ/(m
ηo k1 in k2 in
W/(m2 · K) W/(m2 · K2)
Vitosol 200-F 79.3 3.95 0.0122 6.4
Vitosol 300-T 82.5 1.19 0.009 5.4
*1 ηo based on absorber area
H
0.9

0.8

0.7

0.6

0.5

0.4

0.3

0.2
Efficiency

0.1

0
0 10 20 30 40 50 60 70 80 90 100
Temperature difference in degrees C between ambient air and collector fluid
5167 156 v3.1

Vitosol 300-T
Vitosol 200-F

16
Specification

Solar Coverage

Vitosol 200-F The solar coverage value indicates


what percentage of the energy required
annually for domestic hot water
applications can be covered by the solar
Absorber surface in m2

heating system.
The absorber surface area should be
sized so that the ”production” of
surplus heat is just about avoided
during the summer months.
The higher the solar cover rate, the
lower the efficiency, since a high cover
rate has the effect of raising the
temperature level of the solar circuit.
This results in increased heat losses
ltrs/day and lower seasonal efficiency.
0 13 26 40 53 66 79 92 106 USG/day

DHW consumption The diagrams show the coverage values


that can be achieved with the various
collector types, based on
Vitosol 300-T USG/day
H the meteorological records for a
typical location at 49° latitude,
H south-facing roofs,
Absorber surface in m2

H a roof pitch of 45º and


H a DHW temperature of 113°F / 45ºC
in the standby tank.
This data represents approximate guide
values.

Note:
Solar fractions will be higher for
locations in southern parts of the USA
due to higher levels of radiation.
ltrs/day
0 13 26 40 53 66 79 92 106 USG/day

DHW consumption

Influence of various parameters on solar coverage

Reference system:
Reference system 62
100 litres/day 76 H 4-person household with hot water
consumption of 53 USG/day / 200
300 litres/day 52
litres/day
400 litres/day 45 H 2 Vitosol 200-F collectors, model
Collector inclination 30° 61 SV2 and SH2
H 45º roof inclination
Collector inclination 60° 61 H South-facing roof orientation
Westerly orientation 45 H Dual-mode DHW cylinder, 300 litres
South-west orientation 56 H Meteorological records for a typical
*1
location at 49° latitude
Vacuum tubes 77
Hannover 55 The bars indicate the expected
coverage values for deviations from the
Freiburg 69 reference system.
0 20 40 60 80
Solar cover rate in %
5167 156 v3.1

*1 For comparable absorber surface area.

17
Specification

Collector Installation and Mounting

Installation options for different collector types

Viessmann offers universal mounting


systems to simplify installation. The
mounting systems are suitable for
virtually all forms of roofs, as well as
installation on flat roofs or ground
mounted free-standing installations.

Fitting Collector type


Pitched roofs A Vitosol 200-F, model SV2
Vitosol 300-T
B Vitosol 200-F, model SH2
Flat roofs C Vitosol 200-F, model SV2, SH2
Vitosol 300-T
Freestanding installation D Vitosol 200-F, model SV2, SH2
Vitosol 300-T

Sloped roofs - rooftop installation


Required roof area

Collector Type A mm A in B mm B in
Vitosol 200-F,
type SV2 2380 93 3/4 1056 + 16*1 41 5/8 + 5/8*1
Vitosol 200-F,
type SH2 1056 41 5/8 2380 + 16*1 93 3/4 + 5/8*1
5167 156 v3.1

Vitosol 300-T,
type SP3, 2m2 2031 80 1418 + 102*1 55 3/4 + 4*1
Vitosol 300-T,
type SP3, 3m2 2031 80 2127 + 102*1 83 3/4 + 4*1
*1 Add this value for every additional collector.
18
Specification

Collector Installation and Mounting (continued)

Vitosol 200-F flat panel collector

Flat collectors are ideally suited for Model SH2 has been specially designed Installation kits are available for
domestic hot water and swimming pool for installation on flat roofs and for installing collectors on flat roofs.
heating applications. freestanding installation. An engineering evaluation is required to
establish additional superimposed loads
Both vertical and horizontal types are Viessmann offers a universal fastening from wind or snow, as described in the
suitable for installation on pitched roofs. system to simplify installation. The local building code. Retain the services
The selection of method of installation fastening system is suitable for virtually of a professional structural engineer to
is influenced by the structural all forms of roof and roofing. calculate additional live loads due to the
characteristics of the building. installation of solar collectors on the
roof.

Sloped Roofs Installation Details

b
40
10

Collector
Lag bolt
Mounting rail
Roof bracket

Collector Dimension a b c
Model SV2 inches 93¾ 74¾ - 82½ 3½
mm 2 380 1 900 - 2 100 89
Model SH2 inches 41¾ 19½ - 35½ 3½
500 - 900 89
5167 156 v3.1

mm 1 138

19
Specification

Collector Installation and Mounting (continued)

Flat roof installation

The collectors should be installed with A collector system must be secured by H Collectors secured against lifting
an angle of inclination of 35º to 45º if additional weights against slippage and require less ballast weight, but
the load capacity of the roof allows lifting (see table on the following page). additional attachment to the roof or
this. Maintain a minimum distance of Slippage is the movement of the building structure with wires, cables
2m/6ft from the roof edge in all collectors on the roof surface due to or other sufficient means.
installations. wind, because of insufficient friction
Outside of this area you may between the roof surface and the

Min. 6 ft/
experience significant increases in wind collector system.
turbulance. The system will also be

2m
hard to access if modifications are H Collectors secured against slippage Roof edge
required. If the roof size dictates a require more ballast weight, but no Min. 6 ft/
modification of the array distribution, additional attachment to the roof or 2m
ensure that arrays of the same size are substructure.
created. Collector
array

Determining the collector row distance


“z”

When installing several collector rows in This should be chosen so that the Example
sequence, exact dimensions (dimension midday sun on Dec. 12 can fall onto the Boston is located approx. 42.5º latitude.
“z”) must be maintained to prevent collector without creating shade. Angle of the sun β= 90º-23.5º-latitude
unwanted shade. In North America, this angle is
(23.5º should be accepted as the
Determine angle of the sun β. dependent upon latitude and is between
constant)
13º (Edmonton) and 41º (Miami).
90º-23.5º-42.5º = 24º

l · sin (180 º - ( α+ β ))
z =
sin β

Vitosol 200-F, type SV2


l l
l = 2380mm
α α α= 45º β = 24º (Boston)
β
2385mm
0 sin (180 º - 69 º)
z z =
sin 24º
z = Collector row distance α = Collector angle of inclination
l = Collector height β = Angle of the sun z = 5474mm
(see page 13 and 14)

Collector row distance ”z” (all


dimensions in mm)
Collector type Vitosol 200-F Vitosol 300-T
Type SV2 Type SH2
Angle of inclination α Angle of inclination α Angle of inclination α

Angle of sun β 35º 45º 35º 45º 35º 45º 55º


15.0º 7059 7880 3140 3550 5991 6772 7349
17.5º 6292 7035 2799 3130 5340 5970 6419
20.0º 5712 6320 2541 2812 4848 5363 5716
5167 156 v3.1

22.5º 5256 5758 2338 2561 4461 4886 5164


25.0º 4887 5303 2174 2359 4148 4500 4716
27.5º 4582 4926 2038 2191 3888 4180 4346

20
Specification

Collector Installation and Mounting (continued)

Vitosol 200-F flat panel collector (continued)

Please refer to Vitosol 200-F Installation


instructions for additional information on IMPORTANT
collector mounting on 5285 710.
An evaluation by a professional
structural engineer is required to
calculate additional live loads due to the
installation of solar collectors on a roof.

Vitosol 200-F, type SV2 and SH2


Collector angle of inclination - 25º or 45º
Ballast to be applied and maximum load on the substructures of flat roofs to DIN 1055

Collector angle of inclination 25º 45º


Ballast against slippage*1 Ballast against lifting*1 Ballast against slippage Ballast against lifting
Installation height above ground m up 8 20 up 8 20 up 8 20 up 8 20
to to to to to to to to to to to to
8 20 100 8 20 100 8 20 100 8 20 100
Ballast to be applied
Type SV2 kg 315 554 793 144 304 465 508 842 1213 128 224 346
Type SH2 kg 323 561 800 155 315 476 492 845 1198 132 254 375

*1 See description on page 20.

Collector supports
The collector supports are pre-assembled. They consist of foot support A, bearing supports and adjustment pieces. The
upper adjustment pieces contain holes for adjusting the angle of inclination.
Connection cross ties are required for 1 to 6 collectors connected in a series.

Type SV2 Type SH2


Foot support hole dimensions Foot support hole dimensions
80 80

11 11
75

75

50 50
722
897
1620
1795

A
A Foot support
100

100
5167 156 v3.1

21
Specification

Collector Installation and Mounting (continued)

Vitosol 200-F

Installation on substructures A

A Connection cross ties

Y
Z *1
X

*1 For calculating dimension “z”, see page 20

Installation with ballast A

A Connection cross ties

Y
Z *1
X

*1 For calculating dimension “z”, see page 20


5167 156 v3.1

Collector type x mm x in y mm y in
SV2 590 23 1/4 481 19
SH2 1920 75 5/8 481 19

22
Specification

Collector Installation and Mounting (continued)

Vitosol 300-T sloped roof installation details

230mm /
9”
340mm /
13.4”

1650mm / Deviations from south


65” can be compensated by
1600mm / axial rotation of the
63” vacuum tubes.

Collector
Roof bracket
Roof joist
Collector installation rail with tube mountings
Roof sheathing complete with shingles
Lag bolt

2m2 version 1419mm/55 3/4” 102mm / 4” 3m2 version 2126mm/83 3/4”


5167 156 v3.1

23
Specification

Collector Installation and Mounting (continued)

Flat roof support weight requirements - Vitosol 300-T

Collector angle of inclination of 25º


Weight of supports

Secured against slippage*1 Secured against lifting*1


Installation height above ground ft. up to 26 26 to 66 up to 26 26 to 66
m up to 8 8 to 20 up to 8 8 to 20
Weight of supports 2m2 3m2 2m2 3m2 2m2 3m2 2m2 3m2
Version Version Version Version Version Version Version Version
lbs per support A 168 256 284 430 57 90 112 176
kg per support A 76 116 129 195 26 41 51 80

lbs per support B 225 342 392 593 141 220 276 421
kg per support B 102 155 178 269 64 100 125 191

*1 See description on page 20.

Support A
Support B

Model 2m2 Version 3m2 Version


Dimension X inches 76¼ 76¼
mm 1940 1940
Dimension Y inches 56¾ 84½
mm 1440 2149
Surface area (X x Y) ft.2 30 44½
m2 2.80 4.15
Weight of lbs 99 150
collector kg 45 68
5167 156 v3.1

24
Specification

Collector Installation and Mounting (continued)

Flat roof support weight requirements - Vitosol 300-T (continued)

Collector angle of inclination of 45º


Weight of supports

Secured against slippage Secured against lifting


Installation height above ground ft. up to 26 26 to 66 up to 26 26 to 66
m up to 8 8 to 20 up to 8 8 to 20
Weight of supports 2m2 3m2 2m2 3m2 2m2 3m2 2m2 3m2
Version Version Version Version Version Version Version Version
lbs per support A H 20 344 390 586 -- -- -- --
kg per support A 225 156 177 266 -- -- -- --
102
lbs per support B 564 633 948 161 245 302 454
kg per support B 377 256 287 430 73 111 137 206
171

Support A
Support B

Model 2m2 Version 3m2 Version


Dimension X inches 60¼ 60¼
mm 1530 1530
Dimension Y inches 56¾ 84½
mm 1440 2149
Surface area (X x Y) ft.2 24 35
m2 2.20 3.27
Weight of lbs 99 150
collectors kg 45 68
5167 156 v3.1

25
Specification

General Installation Instructions

H Vitosol solar collectors are hailproof. H An access door or skylight should be


Nevertheless we recommend to provided in the roof in the vicinity of
include bad weather and hail damage the collectors to facilitate inspection
coverage into your home owners and maintenance work.
insurance package. Our warranty does
not cover such damages. H When there is a relatively large
distance between the collector panel
H Please observe local building code and the roof ridge, a snow board must
guidelines for maximum load be installed above the collector panel
restrictions on the substructure and in regions where heavy snowfalls can
for necessary distance to roof edge. be expected.

H Make sure to remove snow off H Filling the solar heating systems with
collectors if more than 20” / 50 cm Viessmann “Tyfocor-HTL” heat
have accumulated. transfer medium is highly
recommended. Other heat transfer
H Mount collectors carefully, so that fluids may be suitable if they have the
even during storm and bad weather same temperature range (-35ºC /
mounting clamps can absorb any -31ºF to 170ºC / 338ºF) and are
tension. non-toxic.

H Use high temperature insulation


materials. In pump idle mode and with
strong solar irradiation, collectors
could reach an idle temperature of
over 200ºC / 392ºF. Protect pipe
insulation and sensor cables against
attack by birds and animals.

H Grounding and lightning protection of


the solar heating system
An electrically conductive connection
of the pipework system of the solar
circuit should be implemented in the
lower part of the building in
accordance with local regulations.
Connection of the collector system to
a new or existing lightning protection
system or the provision of local
grounding should only be carried out
by a licensed professional, taking local
conditions into account.

5167 156 v3.1

26
Notes on Planning and Operation

Calculating the Required Absorber Surface Area

Calculating the absorber surface area and DHW tank capacity

Absorber surface area The basis for designing a solar DHW DHW tank capacity (solar storage)
Estimates based on meteorological heating system is the DHW daily The following values can be used as a
conditions such as annual global demand. It can be estimated based on basis for calculating the cylinder
radiation, cloud cover etc. are the following table: storage capacity:
sufficiently accurate for practical The total available solar DHW tank
purposes. In order to obtain a DHW Demand capacity (dual-coil tank or preheating
comprehensive summary of the solar Vp tank) should be sized on the basis of
coverage for domestic hot water litres/(d · person) 1.5 to 2 times the daily requirements.
heating, it is recommended that this For DHW temps For fluctuating DHW demand use larger
estimate should form the basis of a temps. storage (daily demand x2). For relatively
calculation carried out using a solar 45ºC 60ºC constant demand use value 1.5.
computer simulation. Viessmann can The minimum solar storage tank volume
provide design support and computer Residential should be based on 50 liter/m2/
simulations upon request. Contact your properties*1 1.25gal/ft2 collector absorber area.
local Viessmann sales representative. High demands 50 - 80 35-56
The cover rate determined by this Average demands 30- 50 21-35
program should be 50 to 60 % for Low demands 15 - 30 11-21
relatively small systems (detached
house), and at least 40 % for larger
systems (apartment block).
Guide values for estimating the required
absorber surface area can be drawn
from the table on page 30.
The absorber surface area calculated on
the basis of this table has proved to be
accurate in practice.

Typical Solar Storage and Collector Selection

# People Daily DHW Demand Solar Tank Vitosol 200-F Flat Plate Vitosol 300-T
in household @ 50ºC/120ºF Capacity Collectors SH2/SV2 Tube Collectors
120L 200L
2 1 1x2m2
32 gal. 53 gal.
180-240L 300L
3-4 2 1x3m2
48-63 gal. 79 gal.
300-360L 450L
5-6 3 1x2m2 + 1x3m2
79-95 gal. 120 gal.
5167 156 v3.1

27
Notes on Planning and Operation

Calculating the Required Absorber Surface Area

System for space heating backup - DHW cylinder and collector

100
The period when the greatest amount of
solar energy is available does not
coincide with the time when the most
heat is required.
While the heat consumption for DHW
75 A heating is relatively constant
throughout the year, only very little
solar energy is available at the times
when the heat demand for central
heating is at its highest (see diagram).
A relatively large absorber area is
50 required to provide central heating
Energy requirement or gain (%)

backup. In summer, this can result in


stagnation in the solar circuit. Systems
E
for heating backup require additional
storage tanks and controls.
The basis for sizing a solar heating
25 B system for central heating backup is the
space heating demand of the building
D during spring, autumn and in winter, as
well as the heating demand in summer
C (i.e. the demand for DHW heating).
0
Heat demand in summer, e.g to avoid
condensation in cellars, to use
Aug.

underfloor heating in bathrooms,


Nov.
Dec.
Mar.

Sep.
Apr.

Jun.
Jan.
Feb.

May

Oct.
Jul.

increases the demand. For efficient


operation of a solar central heating
backup, the collector area should be 2
A Space heating requirement for one house (typical construction) to 2.5 times larger than the DHW heat
B Space heating requirement for one low energy house demand in summer requires.
C Hot water requirement To avoid excessive summer time
D Solar energy yield at 5 m2 absorber surface (2 flat collectors) temperature stagnation avoid using
E Solar energy yield at 15 m2 absorber surface (6 flat collectors) collector areas greater than 3 times
what would be used for DHW
requirements only.

Concentrating exclusively on the central For buildings with a higher energy


heating demand can lead to problematic demand the coverage drops lower.
oversizing of the system. Use the Viessmann ESOP calculation
For low energy houses (heat demand program when making sizing
less than 50 kWh/(m2p.a.), solar calculations.
coverage of 20 to 25% refers to the Max. connectable collector area when
total energy demand, incl. provision for using Vitocell tanks must follow the
DHW heating. chart on page 31.
5167 156 v3.1

28
Notes on Planning and Operation

Calculating the Required Absorber Surface Area (continued)

Swimming pool water heating system - heat exchanger and collector

Open-air swimming pools Note


Revising and maintaining the pool
Open-air swimming pools are mainly temperature at a higher base level using
used between May and September [in a conventional heating system does not
northern USA]. The energy demand alter this ratio. However, the pool will
required depends mainly on the leakage be heated up much more quickly.
rate, evaporation, loss (water must be
replenished cold) and the transmission 25

Average pool temperature in 0C


heat loss. Through using a cover, the
evaporation and consequently the
energy demand of the pool is reduced 20
to a minimum. The largest energy input
comes direct from the sun, which 15
shines onto the pool surface. Therefore
the pool has a ”natural” base
temperature which can be shown in the 10
adjacent diagram as an average pool
temperature over the operating time. 5 Location Boston
40m2 Upper surface
A solar heating system in no way alters 1.5m deep
this typical temperature pattern. The 0
Jan Feb MarApr May Jun Jul Aug Sep Oct Nov Dec protected position
solar application leads to a definite covered at night
increase in the base temperature.
Subject to the ratio between the pool 8
surface and the collector area, a
Average temperature increases

different temperature can be reached. 7


6
The adjacent diagram shows with
which ratio of aperture or absorber area 5
to the pool surface what average 4
in degrees C/day

temperature increase can be reached.


This ratio is independent of the collector 3
type used due to the comparably low 2
collector temperatures and the
operating period (summer). For this 1
reason, unglazed collectors are most
0
often used for outdoor pools. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2
Ratio-absorber area to the pool surface
(open-air swimmimg pool)
Indoor swimming pools

Indoor swimming pools generally have a On a summer day (clear skies), a 62.6 kWh
higher target temperature than open-air collector system used to heat a Collector area: =13.9m2
pools and are used throughout the year. swimming pool in northern USA 4.5 kWh/m2
If, over the course of the year, a produces energy of approx. 4.5kWh/m2
constant pool temperature is required, absorber area. This corresponds to 6 collectors.
indoor swimming pools must be heated
in dual-mode. To avoid sizing errors, the Calculation example for Vitosol 200-F For a first approximation (cost
energy demand of the pool must be Pool surface: 36 m2 estimate), an average temperature loss
measured. For this, suspend heating the Average pool depth: 1.5m of 1C/day can be used. With an average
water for 48 hours and determine the Pool capacity: 54m3 pool depth of 1.5m an energy demand
temperature at the beginning and end of Temperature loss of 1.74kWh/day is required to maintain
the test period. The daily energy on 2 days: 2ºC the base temperature. It is therefore
5167 156 v3.1

demand can therefore be calculated Daily energy demand: sensible to use approx. 0.4m2 absorber
from the temperature difference and the area per m2 of pool surface.
capacity of the pool. For new builds, kWh
the heat demand of the swimming pool 54m3⋅1K⋅1.16 = 62.6kWh
K m3
must be calculated.

29
Notes on Planning and Operation

Calculating the Required Absorber Surface Area (continued)

Guide values for sizing solar heating systems (continued)

H Absorber surface area (data based on meteorological records for a site at 49° latitude)

Application Required absorber


surface area A 60 % 40 up to 50 %
for coverage of Vitosol 200-F Vitosol 300-T Vitosol 200-F Vitosol 300-T
DHW heating
Detached & semi-detached ft.2/person 13 - 16 8.6 - 10.8 10.8 - 13 6.5 - 8.6
houses m2/person 1.2 - 1.5 0.8 - 1.0 1.0 - 1.2 0.6 - 0.8
Multi-occupancy dwellings ft.2/person 8.6 - 11.8 6.5 - 8.6 6.5 - 8.6 4.3 - 6.5
m2/person 0.8 - 1.1 0.6 - 0.8 0.6 - 0.8 0.4 - 0.6

Information regarding the DHW cylinder

When sizing the solar heating system, heat exchanger, lower indirect coil) and If a higher system temperature range is
observe the max. aperture area which solar circuit return (lower than 10ºC), acceptable, then the number of
may be connected to the different DHW the max. number of collectors collectors can be no more than doubled.
cylinders. mentioned in the table (values apply to
At a design output of 600W/m2 and a all Viessmann collectors) should not be
temperature difference between DHW exceeded.
temperature (at the height of the solar

DHW Tank Capacity Max. connectable number of collectors


Vitosol 200-F Vitosol 300-T 2m2 Vitosol 300-T 3m2
Vitocell-B 300 L/79 gal. 4 5 3
100/300
Vitocell-B 450 L/120 gal. 7 7 5
100/300
Vitocell-V 200 L/53 gal. 3 4 3
100/300 300 L/79 gal. 4 5 3
450 L/120 gal. 7 7 5

5167 156 v3.1

30
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump

Solar heating system operating modes

Volume flow in the collector array H A smaller pump capacity is required


resulting in lower electrical IMPORTANT
Generally, very low flow rates are consumption.
required for Vitosol collectors. This Do not use galvanized pipes, galvanized
results in small pipe and pump In the low-flow operating mode, the fittings or graphitised gaskets. Hemp
requirements. There are different pipes can be sized on the basis of a should be used only in conjunction with
operating modes, which depend on the flowrate of pressure and temperature-resistant
total area of collectors installed, and H Vitosol 200-F: approx. 15 liters/h per sealant.
piping requirements. m2 absorber surface area (approx.
At the same irradiation level, and 0.07 gpm/m2 absorber surface area).
consequently the same collector output, IMPORTANT
a higher flow rate means a lower H Vitosol 300-T: approx. 25 litrers/h per
temperature spread in the collector m2 absorbed surface area (approx. The components used must be resistant
circuit; a lower flow rate means a 0.11gpm/m2 absorber surface area). to the heat transfer medium (for
higher temperature spread. With a high composition, see the datasheet for the
temperature spread, the average With both collector models, a uniform specific collector).
collector temperature increases, i.e the flow rate through all collectors is
operating efficiency of the collector guaranteed if the Viessmann piping
drops accordingly. Therefore, with layout drawings are followed. To reduce IMPORTANT
lower flow rates the use of electrical the amount of installation work required
energy (pump size) reduces and a for the piping, it is advisable to connect The thermal insulation of external piping
smaller size connection pipe is possible. two rows of collectors with all piping must be resistant to temperature, UV
To safeguard a safe flow rate and a connections on one side of the array. radiation and to attack by birds or
turbulent flow, Vitosol flat-plate animals.
collectors require a flow rate of at least Pipe installation information
15 liters/(h.m2). Vitosol tube collectors Insulate internal ”hot” pipework
require at least 25 liters/(h.m2). To minimise the pressure drop through according to current practice (fire
Generally, when setting the collector the piping of the solar heating systems, protection, touch protection), e.g. using
volume flow, the necessary volume the flow velocity in the copper pipe high-temperature resistant insulation,
flow of the connected heat exchanger should not exceed 3.5ft/s. We as offered by Armacell.
should also be taken into account. recommend flow velocities between 1.3
and 2.3ft/s. At these flow velocities,
1. High-flow mode pressure drops of between 1 and 2.5
For solar heating systems up to mbar/m pipe length occur.
270º ft.2 / 25 m2 absorber surface
area, we recommend the high flow For the installation of the collectors, we
operation. This reduces the temperature recommend the use of commercial
spread between supply and return. copper pipe and red bronze fittings or
The higher flow rate requires a slightly stainless steel pipe. The cross-sections
should be sized as for a conventional
larger pipework size, and larger pump
heating system on the basis of flow
sizes. rate and velocity (see the tables below).
In the high-flow operating mode, the
pipes can be sized on the basis of a
flowrate of
H Vitosol 200-F: approx. 40 liters/h per
m2 absorber surface area (approx.
0.18 gpm/m2 absorber surface area).
H Vitosol 300-T: 60 liters/h per m2
absorber surface area
(0.27 gpm/m2 absorber surface area).

2. Low-flow mode
For large solar installations (larger than
270 ft.2 / 25 m2 absorber surface area),
low flow mode operation can be used..
5167 156 v3.1

Advantages of the low-flow mode:


H A high temperature level is reached
quickly in the collector circuit.
H The low flow rate in the collector
circuit means that much smaller pipe
sizes are required.

31
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump (continued)

Sizing pipe diameters (continued)

Vitosol 200-F (high-flow operating mode), 40 liters/(h.m2) or 0.18gpm/m2

Number of 2 3 4 5 6 8 10 12
collectors
Model SV2 and SH2
Volume flow gpm 0.8 1.2 1.6 2.1 2.5 3.3 4.1 4.9
liters/min 3.1 4.6 6.2 7.8 9.3 12.4 15.5 18.6
Flow velocity ft./s 1.3 to 2.3
m/s 0.4 to 0.7
Pressure drop in the ft. of
pipework head/ft. 0.11 to 0.27
mbar/m 1.0 to 2.5

Vitosol 300-T (high-flow operating mode), 60 liters/(h.m2) or 0.3gpm/m2

Absorber m2 2 3 4 5 6 8 10 12 15
surface area
Volume flow gpm 0.53 0.8 1.1 1.3 1.6 2.1 2.6 3.2 4.0
liters/min 2 3 4 5 6 8 10 12 15
Flow velocity ft./s 1.3 to 2.3
m/s 0.4 to 0.7
Pressure drop ft. of
in the head/ft. 0.11 to 0.27
pipework mbar/m 1.0 to 2.5

Vitosol 200-F (low-flow operating mode), 15 liters/(h.m2) or 0.07gpm/m2

Number of 2 3 4 5 6 8 10 12
collectors
Model SV2 and SH2 gpm 0.3 0.5 0.6 0.8 0.92 1.25 1.53 1.85
Volume flow liters/min 1.2 1.8 2.3 2.9 3.5 4.7 5.8 7.0
Flow velocity ft./s 0.7 to 1.3
m/s 0.2 to 0.4
Pressure drop in the ft. of
pipework head/ft. 0.11 to 0.27
mbar/m 1.0 to 2.5

Vitosol 300-T (low-flow operating mode), 25 liters/(h.m2) or 0.11gpm/m2

Absorber m2 2 3 4 5 6 8 10 12 15
surface area
Volume flow gpm 0.21 0.3 0.45 0.6 0.7 0.9 1.1 1.3 1.64
liters/min 0.8 1.2 1.7 2.1 2.5 3.3 4.2 5.0 6.2
Flow velocity ft./s 0.7 to 1.3
m/s 0.2 to 0.4
Pressure drop ft. of
in the head/ft. 0.11 to 0.27
pipework mbar/m 1.0 to 2.5
5167 156 v3.1

32
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump (continued)

Installation examples (hydraulic connection)

Vitosol 200-F, type SV2/SH2

High -flow operation

Installation of collectors, connection on Installation of collectors, single-sided


alternate sides, max. 12 connection, max. 10 collectors.
collectors.
Ø 28x1
C C
A
Ø 28x1
A
max. 12 Supply (hot)
max. 10 Return
B B Air vent valve (shut-off type)
Ø 28x1
Ø 28x1

Low-flow operation

Installation of collectors, connection on Installation of collectors, single-sided


alternate sides, max. 10 connection, max. 8 collectors.
collectors.
Ø 18x1
C C
A
A Ø 18x1

max. 10 max. 8
B Supply (hot)
B Return
Ø 18x1 Air vent valve (shut-off type)
Ø 18x1

Vitosol 300-T, type SP3

Installation on pitched roofs (max. 6 per


array)

Connection from the left (preferred Connection from the right


option)

C C
A A
B B
Ø 18x1 Ø 18x1

Supply (hot)
Return
Air vent valve (shut-off type)
5167 156 v3.1

33
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump (continued)

Collector pressure drop information (relative to water, approx. 30% higher for Tyfocor HTL @ 40ºC)

Vitosol 200-F, flat plate collector Vitosol 300-T vacuum tube collector
model SV2 and SH2

“ w.c.

mbar
” w.c. mbar
800 2000 80 200

400 1000 40 100

32 80

24 60
200 500
20 50
160 400 16 40
120 300
Pressure drop

12 30
80 200
Pressure drop

8 20

40 100
4 10

3.2 8
20 50
2.4 6
40 2 5
12 30
2 3 4 5 l/min 1.6 4
0.5 1
0.3 0.5 0.8 1.11.3 gpm
1.2 3

Waterflow 0.8 2

1
1 2 3 4 5 6 10 ltr/h

0.3 0.5 0.8 1.1 1.3 1.6 2.6 GPM


Waterflow

1 x 2m2
1 x 3m2
2 x model 2m2
1 x model 2m2 and 1 x model 3m2
2 x model 3m2

Calculating pressure drop


The total pressure drop of the solar For calculation of total pressure drop
heating system consists of: H Collectors connected in series:
H collector resistance values, Total pressure drop = sum of the
H pipe resistance values, individual resistance values
H individual resistance values of the H Collectors connected in parallel:
fittings and Total pressure drop = individual
H individual resistance values of the pressure drop (assuming all individual
fittings and resistance values are equal).
H resistance values of the heat
exchanger in the DHW tank.
5167 156 v3.1

34
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump (continued)

Sizing the circulation pump

If the flowrate and pressure drop of the Two models of Solar-Divicon are
entire system are known, the pump is available: IMPORTANT
selected on the basis of the pump Model DN 20
characteristics. H up to 12 Vitosol 200-F collectors The Solar-Divicon and the solar pump
Variable-speed pumps which can be H up to 20 m2 absorber surface area line are not suitable for direct contact
matched to the system by switching with Vitosol 300-T, with swimming pool water or potable
are the most suitable. water.
Model DN 25
To simplify the installation and selection H up to 18 Vitosol 200-F collectors
of the pumps and safety equipment, H up to 30 m2 absorber surface area IMPORTANT
Viessmann supplies the Solar-Divicon. with Vitosol 300-T.
The Solar-Divicon comprises Always install Solar-Divicon at a lower
H pre-assembled and sealed valves and Final determination of which height than the collectors to prevent
safety assembly, Solar-Divicon model to use must be steam from entering the expansion
H flow regulating valve with meter to based on system layout and pipe sizes vessel in the event of stagnation.
control the solar heating system used.
during commissioning and operation,
H flow check valves, IMPORTANT
H system pump (2 sizes available),
H pressure gage, For systems which are installed in the
H 2 thermometers, roof space or involve short pipe lengths,
H 2 isolation valves, a preliminary vessel should be provided
H pressure relief valve, 87 psig / 6 bar. if necessary.

1 Pressure relief valve, 87 psig/6 bar


2 Expansion tank connection
3 Pressure gage, 0-6 bar/0-87 psig
4 Temperature gage c/w integrated
shut-off valves and flow check
valves
5 Pump
6 Flow meter
7 Insulation door
8 Flush and fill manifold
9 Air separator (locked under
insulation)

VL Flow
RL Return

Shut-off valve
A Thermometer
B Non-return valve
Solar circuit circulation pump
C Flow rate indicator
D
A
5167 156 v3.1

VL RL

The solar circuit pump line is constructed as the pump line of the Solar-Divicon.

35
Notes on Planning and Operation

Sizing Pipe Diameters and Circulation Pump (continued)

Technical information on the Solar-Divicon

Solar-Divicon Model DN 20 DN 25
Circulation pump (Model: Wilo) STAR S 16 U 15 STAR S 21 U 25
Rated voltage V AC 115 AC 115
Maximum delivery GPM 16 16.7

Maximum head ft. 20.7 21.1

Flow meter (setting range) USG/min 0.5 to 5 1 to 10


Flow meter (setting range) ltrs/min 1 to 20 5 to 40
Pressure relief valve psig, 87 87
bar 6 6
Maximum operating temperature °F, 248 248
°C 120 120
Maximum operating pressure psig, 87 87
bar 6 6
Connections (Compression fittings Ø):
Solar circuit inches 1/2 3/
4
mm 22 22
Solar expansion tank inches 3/ 3/
4 4
mm 22 22
Safety relief valve inches 3/ 3/
4 4
mm 22 22

Characteristics

Pump model DN 20 Pump model DN 25

5167 156 v3.1

36
Notes on Planning and Operation

Safety Equipment

Liquid capacity of solar heating system components

Vitosol 200-F, model SV2 USG 0.48


liters 1.83
Vitosol 200-F, model SH2 USG 0.65
liters 2.48
Vitosol 300-T, model 2m2 USG 0.32
liters 1.20
model 3m2 USG 0.47
liters 1.80

Solar-Divicon (pumping station for the USG 0.08


collector circuit) liters 0.30

Vitocell-B 100 Tank capacity USG 79 120


liters 300 450
Heating water capacity of bottom coil USG 2.6 3.3
liters 10 12.5

Vitocell-B 300 Tank capacity USG 79 79


liters 300 300
Heating water capacity of bottom coil USG 2.9 3.9
liters 11 15

Vitocell-V 300, Tank capacity USG 53 79 120


(with indirect coil/s) liters 200 300 450
Heating water capacity of coil USG 3.2 2.9 4
liters 11.9 11 15

Copper pipe, type M Dimension 3/ ” ½” ¾” 1” 1¼” 1½”


8
Water content USG/ft. pipe
0.0083 0.013 0.027 0.045 0.068 0.095
5167 156 v3.1

37
Notes on Planning and Operation

Safety Equipment

h Static height The solar heating system must be


T protected in respect to temperature,
RL Return A
pressure and discharge of liquid in
VL Flow
accordance with local regulations.
The collector circuit must be protected
in such a way that at the highest
possible collector temperature (= idle
temperature) no heat transfer medium

h
can escape from the safety valve.
This is achieved through the appropriate
sizing of the expansion vessel and
DHW B matching of the system pressure.
C For total pipework lengths shorter than
D
10m/32ft, we recommend the
installation of a pre-cooling vessel and
G diaphragm expansion vessel into the hot
supply pipe and only the pressure relief
valve into the return pipe.

Information regarding stagnation


System idle periods, e.g. due to defects
VL RL or incorrect operation, can never be
E ruled out. For this reason solar heating
systems must be protected according
to the current technical standards
against the potential difficulties which
T may arise from idle periods, i.e.
systems cannot be damaged or cause
F
KW damage if idle periods occur. Collectors
and connection pipes are designed for
Collector the maximum expected temperatures in
Safety valve case of stagnation. Temperatures over
Solar-Divicon 170ºC / 338ºF have a detrimental
Pre-cooling vessel (see below) effect on the process medium. When
Diaphragm expansion vessel designing the collector array it should
Dual-mode DHW cylinder be ensured that the system can
High limit safety cut-out (see
“breathe” properly (e.g. do not route
page 41)
solar pipes above the collector array).

Information regarding the heat transfer longer periods of stagnation are and the expansion vessel is lower than
medium prevented. System must be air-tight as 50% of the capacity of the correctly
Heat transfer media containing glycol glycol deterioration is always worse in sized expansion vessel. The reference
can be damaged, if they are subjected presence of O2 molecules. Check the value is the total volume which
for long periods of temperatures above glycol every 2 years. evaporates in idle conditions.
170ºC / 338ºF. This can lead to the Sizing:
system suffering from sludge and hard Information regarding pre-cooling Capacity of the correctly sized
deposits, particularly in conjunction vessels expansion vessel less the content of
with other contaminants (flux and Pre-cooling vessels or stratification the return line between the collector
oxidized deposits). cylinders in solar heating systems array and the expansion vessel.
Therefore, after completing the protect the diaphragm expansion vessel Determining the capacity of the
installation, thoroughly flush out the from over heating if stagnation occurs. pre-cooling vessel:
system. After filling the system with The installation of such vessels is 1.5 x collector content x number of
process medium, ensure that heat is recommended if the content of the collectors.
5167 156 v3.1

transferred inside the system, i.e. that pipework between the collector array

Content litres Number of collectors


Vitosol SV2 Vitosol SH2 Vitosol 300-T 2m2 Vitosol 300-T 3m2
12 4 3 6 4

38
Notes on Planning and Operation

Safety Equipment (continued)

Diaphragm expansion tank

Construction and operation


A diaphragm expansion tank is a
A A A sealed expansion vessel whose gas
space (nitrogen filling) is separated
from the liquid space (heat transfer
medium) by a diaphragm and whose
inlet pressure is subject to the system
height.
D E To safely prevent steam being
created during the operating stage,
collectors must indicate a pressure of
at least 15 psig / 1 bar in their cold
state.
The expansion tank inlet pressure is
then higher by an amount of
0.45 psig x static height (h) in ft.
B C C or 0.1 bar x static height (h) in m.
In hot conditions, the system pressure
rises by approx. 15 to 30 psig/1 to
Delivered Solar heating Under max. 2 bar.
condition system filled pressure at the
(3 bar/45 psig without highest process Maximum idle temperature of
pressure) heat effect medium temperature collectors:
Vitosol 200-F, Models SV2, SH2
Flat panel solar collector with 25 ft.2 /
Process medium Nitrogen buffer 2.3 m2 collector area.
Nitrogen filling Safety water seal, min. 3l/0.8gal Max. shutdown temperature
430°F / 221°C
Max. operating pressure
87 psig /6 bar
Specification - Viessmann expansion tank
A B Vitosol 300-T, SP3 Series
Øa Øa Vacuum tube solar collector with 22
and 32 ft.2 / 2 and 3 m2 collector
area.
Max. shutdown temperature
302°F / 150 °C
Max. operating pressure
87 psig /6 bar
b

To ensure that no heat transfer


b

medium can escape from the pressure


relief valve, the expansion tank must
be sufficiently large to accommodate
the liquid content of the collector
when steam forms (stagnation).

IMPORTANT
Expansion Content Operating Øa b Connection Weight
tank litres pressure mm mm R kg
The cold fill inlet pressure (gas space)
bar
must be adjusted on site as follows:
A 18 10 280 370 ¾” 7.5 15 psig + 0.45 psig x static height in
25 10 280 490 ¾” 9.1 ft
40 10 354 520 ¾” 9.9 1 bar + 0.1 bar x static height in m
B 50 10 409 505 1”
1 12.3 The system operating pressure must
80 10 480 566 1” 18.4 be 4.5 to 7.5 psig/0.3 to 0.5 bar
higher than the inlet pressure of the
5167 156 v3.1

diaphragm expansion tank. The


waterseal should be 0.005x the total
liquid content of the system but not
less than 3 liters.

39
Notes on Planning and Operation

Safety Equipment (continued)

Technical data for the expansion tank (continued)

The nominal capacity of the expansion Calculation example Selection table for expansion tanks,
vessel is calculated according to the Solar heating system with: subject to collector model (in
equation 2 Vitosol 200-F, type SV2 @ 1.83 litres conjunction with a 6 bar safety valve)
(V v + V 2 + z ⋅ V k) ⋅ (p e + 1) Liquid capacity: VA = 25 litres These details provide only guide values;
VN = pe − p Static head: h = 5 m a final calculation must be carried out.
st
Permissible final pressure: pe = 5.4 bar
(ü) Vitosol 200-F, model SV2
Whereby (Safety valve blow off pressure: 6 bar)
VN = nominal capacity of the Number of System Static Expansion
(V v + V 2 + z ⋅ V k) ⋅ (p e + 1) collectors capacity head tank
diaphragm expansion tank VN = p e − p st
in liters VA h (m) capacity
Vv =VA · 0.005 liters liters
Vv = safety water seal (here heat Vv =0.125 litres, selected 3 litres 2 20 5 25
transfer medium) in litres (see previoys page). 10
Vv = 0.005 · VA in litres V2 =VA · b
(min. 3 litres) V2 =3.25 litres 3 25 5 25
pst =1.5 bar + 0.1 bar/m · 5 m 10 40
VA = liquid capacity of the entire pst =2.0 bar 4 32 5 40
system (see page 42). 10
(3 + 3.25 + 2 ⋅ 1.83) ⋅ (5.4 + 1)
VN =
5.4 − 1.5 5 35 5 40
pst = nitrogen inlet pressure of
expansion vessel in bar VN =16.3 litres 10 50
pst =1 bar + 0.1 · h
h =static head of the system in Due to the possibility of steam Vitosol 200-F, model SH2
m (see drawing on page NO TAG) collecting in the solar circuit pipe, we
z = number of collectors recommend multiplying the calculated Number of System Static Expansion
Vk = collector capacity in litres value VN by a safety factor of 1.5. collectors capacity head tank
(see page 37). Select a 25 liter expansion vessel. VA h capacity
V2 = volume increase when the liters m liters
system heats up 2 20 5 25
10 40
V2 = VA · β 3 30 5 40
b =expansion quotient ( β= 0.13 10
for Viessmann heat transfer 4 35 5 40
medium from –20 to 120ºC)
pe = permissible end pressure in bar 10 50
pe =psi – 0.1 · psi 5 40 5 50
psi =safety valve blow off 10 80
pressure
Vitosol 300-T
Absorber System Static Expansion
WARNING surface capacity head tank
area VA h (m) capacity
Do not use expansion tanks that are m2 liters liters
not designed for solar heating
systems. Temperatures during 3 16 5 18
stagnation periods can reach 10
extremely high levels, which could 4 18 5 18
result in serious injuries from hot 10
system fluid discharging from 5 23 5 18
pressure relief valve.
10 25
6 25 5 25
10
WARNING
9 35 5 40
5167 156 v3.1

Do not undersize expansion tank. 10

40
Notes on Planning and Operation

Safety Equipment (continued)

Pressure relief valve

The operating pressure of the pressure


relief valve is the maximum system IMPORTANT
pressure +10 %.
The pressure relief valve must comply When use is made of water containing
with all local codes. antifreeze or synthetic heat transfer
media which are miscible with water
The pressure relief valve must be (e.g. Viessmann heat transfer medium)
matched to the output of the collector and whose boiling point is higher than
or the collector assembly and be able to that of water, the blow off and
handle their maximum output of discharge pipes must be run to an open
900w/m2. container capable of accommodating
the total capacity of the collectors.

Use only pressure relief valves designed


for a maximum of 87 psig / 6 bar and
248ºF / 120ºC bearing the markings
”S” (solar) as part of the product
identification.

IMPORTANT
Solar-Divicon is equipped with a pressure
relief valve for max. 87 psig / 6 bar and
248ºF / 120ºC.

High limit safety cut-out

The Vitosolic 200 solar control unit is Example:


equipped with an electronic limit Vitosol 200-F flat collector x 4=,
thermostat which is preset in the approx. 7 m2 absorber surface area
factory to 167ºF / 75ºC and can be DHW cylinder with 300 litres capacity
adjusted.
For systems with a sufficiently large 300 = 40 litres/m2,
7.5
DHW capacity, this protection is
adequate, as the maximum operating e.g. no high limit safety cut-out
temperature does not exceed 23ºF / required.
11ºC.

An additional mechanical high limit


safety cut-out is required, if the DHW
tank capacity is less than 40 liters/m2
collector surface area.
5167 156 v3.1

41
Notes on Planning and Operation

Safety Equipment (continued)

Thermostatic mixing valve

Solar storage tank A thermostatic mixing valve is required


DHW
Thermostatic anti-scald mixing for all solar systems to prevent
valve domestic hot water temperatures higher
than 140 ºF / 60 ºC (local codes may
require different temperature settings).

Install an anti-scald mixing valve


designed for potable domestic hot
water systems.

DCW

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.

5167 156 v3.1

42
Notes on Planning and Operation

Accessories

Threaded elbow Quick-acting air-vent valve (with tee) Solar manual filling pump

R1”
.

approx. 166

22

22

R ½”
38
15
160 (220)
65 220
290
40
For replenishing and raising the
For installation at the highest point of pressure.
the system.
With shut-off valve and locking ring
connection.

For the installation of the DHW tank Flexible connection pipe


temperature sensor into the tank return.
Comes as standard equipment with
Vitocell-B 100 tanks and is an
accessory with Vitocell-B 300 tanks.

1000
22

Air separator

Stainless steel corrugated pipe with


thermal insulation and compression
approx. 225

fitting connection.
Comes with thermal insulation. Set of 2
per package.
22

22

111

For installation in the supply pipe of the


solar circuit, preferably upstream of the
inlet to the DHW tank.
With automatic air-vent valve, shut-off
valve and locking ring connection.
This is not required if a Solar Divicon
model DN 20 or DN 25 is used.
5167 156 v3.1

43
System Designs

General Information

For our climatic zone: dual systems

In our climatic zone, solar radiation is


insufficient to cover the entire
requirements for domestic hot water or
swimming pool heating as well as space
heating by means of solar energy.

Therefore, a solar heating system for


DHW or swimming pool water heating
and/or central heating should always be
combined with another heat generator.

In dual systems, for example, an oil or


gas-fired boiler supplies the additional
heat required.

How to implement the installation

Over the following pages, we have


WARNING described methods of operation and
used design suggestions to illustrate
With temperatures over 140°F / various installation ideas involving
60°C, the DHW temperature must be different equipment specifications. A
limited to 140°F / 60°C by installing summary is provided which lists
a mixing device, e.g. a thermostatic essential control equipment.
mixing valve (DHW tank accessory). The temperatures stated are guide
values; other values may be set to meet
particular requirements.
The circulation pumps referred to in
these examples (standard delivery with
Solar-Divicon) are AC pumps.

DHW tank backup by the boiler is


suppressed by the Vitosolic, when the
anticipated heat requirement for DHW
heating is expected to be covered by
the solar heating system. This may
require the use of the optional
expansion boards.
When connection between the Vitosolic
and the boiler control (Vitodens
programming unit, Vitotronic 300 or
Dekamatik) is made via the KM-BUS,
the setpoint temperature for boiler
backup of DHW is reduced, stopping
the boiler from coming on.

Abbreviations used in the examples:

DCW Domestic cold water


DHW Domestic hot water
R Return
S Supply
5167 156 v3.1

44
System Designs

System Design 1

Dual-mode DHW heating with Vitocell-B100 or Vitocell-B 300 DHW tanks


- with Vitosolic 200 or GL 30 control

DHW heating without solar energy DHW heating with solar energy

The top part of the DHW tank is heated When a temperature difference higher When the preset temperature is
by the boiler. than the value set in control unit is exceeded, these devices switch OFF
The DHW tank temperature sensor measured between collector solar circuit circulation pump . The
of the boiler control unit switches tank temperature sensor and tank electronic temperature limit is set at the
heating circulation pump . temperature sensor , solar circuit factory.
circulation pump is switched ON
and the DHW tank is heated up.
The temperature in the DHW tank is
limited by the electronic limit
thermostat in control unit or by
high limit safety cut-out (if
required).

Installation diagram
2

B
1

DHW

C 4

D
28 E

F 5 S R
5
6

21

3
G H DCW

Solar collector DHW circulation Heating circuit


Solar-Divicon DHW circulation output of the boiler Oil/gas-fired boiler
5167 156 v3.1

Taps control unit or timer installed on site DHW cylinder


*1 High limit safety cut-out, see page 41.

45
System Designs

System Design 1 (continued)

Dual-mode DHW heating with Vitocell-B100 or Vitocell-B 300 DHW tanks


- with Vitosolic 200 or GL 30 control (continued)

Control equipment required

Item Description Number Part no.


Control of DHW cylinder loading by solar energy
1 Vitosolic 200 1 7134 552
or
GL 30 control 7134 450
2 Collector temperature sensor 1 Included in
standard
equipment for
item 1
3 DHW tank temperature sensor*1 1 Included in
standard
equipment for
item 1
4 Solar circuit circulation pump 1 7133 454
(standard equipment of Solar-Divicon, see page 35) or
7133 455
5 High limit safety cut-out (see page 41)*2 1 Supplied on site
Control of DHW tank loading by the boiler
6 DHW tank temperature sensor 1 Included in
standard
equipment of boiler
control unit *2
7 Circulation pump for DHW tank loading 1 DHW tank
accessory
*1Installation requires a threaded elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300 ).
*2Accessory with Vitodens.

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.

5167 156 v3.1

46
System Designs

System Design 2

Dual-mode DHW heating and space heating backup with heating water storage tank
- with Vitosolic 200

DHW heating without solar energy Space heating without solar energy Space heating with solar energy

The upper indirect coil of the DHW tank Diverter valve remains at zero volts Heating water storage tank circuit
is heated by a boiler. The DHW tank (setting ”AB-B”), if the differential circulation pump and circulation
temperature sensor of the boiler temperature between heating water pump for storage tank heating are
control unit switches circulation pump storage tank temperature sensor switched ON and the heating water
to heat up the DHW tank. (discharge) and space heating return storage tank is heated up, when a
temperature sensor falls below the temperature difference higher than the
value set at control unit . No flow differential temperature preset in
DHW heating with solar energy through the heating water storage tank control unit is measured between
takes place. collector temperature sensor and
Solar circuit circulation pump is The boiler provides heat to the heating storage tank temperature sensor
switched ON and the DHW is heated circuit according to the heating curve (re-loading) . The temperature inside
up, when a temperature difference set at the boiler control unit. the heating water storage tank will be
higher than the value set in control unit limited by the electronic limit
is measured between collector thermostat in control unit .
temperature sensor and DHW When the preset temperature is
temperature sensor . exceeded, this device switches the
The temperature in the DHW is limited storage tank circuit circulation pump
by the electronic limit thermostat in and OFF.
control unit or by high limit safety Circulation pump is switched OFF
cut-out (if required). for approx. 2 minutes, roughly every
When the preset temperature is 15 minutes (adjustable time), to check
exceeded, these devices switch OFF whether the temperature at the
solar circuit circulation pump . collector temperature sensor is high
The electronic temperature limit is set enough to change over to DHW tank
at the factory. loading.

Control unit switches diverter valve


to position ”AB-A” and the space
heating return water will be channelled
into the boiler via the storage tank, if
the temperature differential between
storage tank temperature sensor
(discharge) and space heating return
temperature sensor exceeds that set
at control unit . If the temperature of
the pre-heated return water is
insufficient, the boiler re-heats the
water to the necessary flow
temperature level.
5167 156 v3.1

47
System Designs

System Design 2 (continued)

Installation diagram
2

Refer to Viessmann sample layout drawing #5 for


alternate layout. (contact Viessmann sales rep. for
details) A

B C

4
qE

DHW

S R

5
5

6
qP
21

9
7
qR AB

qT A B
3
qQ qW DCW
G H K

Solar collector DHW circulation Heating water storage tank


Solar-Divicon DHW circulation output of the boiler Oil/gas-fired boiler
Solar pump line control unit or timer installed on site DHW tank
Taps
5167 156 v3.1

*1High limit safety cut-out, see page 41.

48
System Designs

System Design 2 (continued)

Dual-mode DHW heating and space heating backup with heating water storage tank
- with Vitosolic 200 (continued)

Control equipment required

Item Description Number Part no.


Control of DHW tank loading by solar energy
1 Vitosolic 200 1 7134 450
2 Collector temperature sensor 1 Included in
standard
equipment for
item 1
3 DHW tank temperature sensor*1 1 Included in
standard
equipment for
item 1
4 Solar circuit circulation pump 1 7133 454
(standard equipment of Solar-Divicon, see page 35) or
7133 455
5 High limit safety cut-out (see also page 41) 1 Supplied on site
8 Circulation pump (relayering) 1 Supplied on site
Control of DHW tank loading by the boiler
6 DHW tank temperature sensor 1 Included in
standard
equipment of the
boiler control unit
7 Circulation pump for DHW tank loading 1 DHW tank
accessory
Space heating control with solar energy
9 Return temperature sensor (heating circuit) 1 7170 965
qP Temperature sensor (storage tank), discharge 1 7170 965
qQ Temperature sensor (storage tank, re-loading) 1 Included in
standard
equipment for
item 1
qW Three-way diverter valve 1 Supplied on site
qE Solar circuit circulation pump for storage tank heating 1 Supplied on site
(part of the solar pump line, see page 35)
qR Circulation pump for storage tank heating 1 Supplied on site
qT Heat exchanger 1 Supplied on site
*1A threaded elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300 ) is recommended for this installation.

Note:
Heating water storage tank , circulation pump for storage tank and heat exchanger can all be replaced with an
indirect-fired storage tank, c/w internal heat exchanger coil (e.g. Vitocell-V 100).

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.
5167 156 v3.1

49
System Designs

System Design 3

Dual-mode DHW heating with two DHW tanks


- with Vitosolic 200

DHW heating without solar energy DHW heating with solar energy

DHW tank 2 is heated by the boiler. The Solar circuit circulation pump is
DHW tank thermostat with connected switched ON and DHW tank 1 is heated
tank temperature sensor of the up, when a temperature difference
boiler control unit switches circulation higher than the value set in control unit
pump to heat up the DHW tank. is measured between collector
DHW circulation pump 8b (if installed) temperature sensor and tank
is switched ON and circulation pump temperature sensor .
8a
The temperature in DHW tank 1 is
is switched OFF, so that the DHW limited by the electronic limit
circulation only affects DHW tank . thermostat in control unit or by
high limit safety cut-out (if
required).
When the preset temperature is
exceeded, this device switches OFF
solar circuit circulation pump . The
electronic temperature limit is set at the
factory.

Circulation pump 8a is switched ON,


when the temperature at sensor in
DHW tank 1 exceeds that at sensor
in DHW tank 2.

The DHW circulation covers both DHW


tanks. This feeds the water heated in
DHW tank 1 into DHW tank 2. This
way, DHW tank 2 is also heated by
solar energy.
DHW circulation pump 8b (if installed)
for DHW tank 2 is controlled by the
boiler control unit.

Circulation pump 8a will be switched


OFF if the temperature in DHW tank 2
rises above that in DHW tank 1.

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.
5167 156 v3.1

50
System Designs

System Design 3 (continued)

Installation diagram (system with two DHW cylinders with indirect coils)

8a

D
E 28
8b
F
5
5 S R
DHW

DCW qP
21 2 1
6 9

7 3

DCW
G H K

Solar collector DHW circulation output of the boiler Oil/gas-fired boiler


Solar-Divicon control unit or timer installed on site DHW tank 2
Taps Heating circuit DHW tank 1
DHW circulation
5167 156 v3.1

*1High limit safety cut-out, see page 41.

51
System Designs

System Design 3 (continued)

Dual-mode DHW heating with two DHW tanks


- with Vitosolic 200 (continued)

Control equipment required

Item Description Number Part no.


Control of DHW tank 1 loading by solar energy
1 Vitosolic 200 1 7134 552
2 Collector temperature sensor 1 Included in
standard
equipment for
item 1
3 DHW tank temperature sensor*1 1 Included in
standard
equipment for
item 1
4 Solar circuit circulation pump 1 7133 454
(standard equipment of Solar-Divicon, see page 35) or
7133 455
5 High limit safety cut-out (see also page 41) 1 Supplied on site

Control of DHW tank 2 loading by the boiler


6 DHW tank temperature sensor 1 Included in
standard
equipment of boiler
control unit *2
7 Circulation pump for DHW tank loading*3 1 Accessories
DHW tank

DHW circulation changeover


8 DHW circulation pump or circulation pump (relayering) 1 Supplied on site

9 Temperature sensor tank 1 1 Included in


standard
equipment for
item 1
qP Temperature sensor tank 2 1 7170 965
*1The screw-in elbow which is available as an accessory for the DHW cylinder is recommended for installation purposes.
*2Accessory with Vitodens.
*3Part of the standard delivery with Vitodens (for types with DHW heating).

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.
5167 156 v3.1

52
System Designs

System Design 4

Dual-mode DHW and swimming pool water heating


- with Vitosolic 200

DHW heating without solar energy DHW heating with solar energy Swimming pool water heating

The top part of the DHW tank is heated Solar circuit circulation pump for DHW Solar circuit circulation pump for DHW
by the boiler. heating is switched ON and the heating is switched OFF, and solar
The DHW tank temperature sensor DHW tank is heated up, when a circuit circulation pump for
of the boiler control unit switches tank temperature difference higher than the swimming pool heating is switched ON,
heating circulation pump . value set in control unit is measured if the temperature at DHW tank
between collector temperature sensor temperature sensor is so high, that
and DHW tank temperature the temperature difference falls below
sensor . the set differential temperature for
DHW heating.
Solar circuit circulation pump for DHW The temperature at collector
heating is switched OFF, and solar temperature sensor must then be
circuit circulation pump for swimming higher by the temperature difference for
pool heating is switched ON (see swimming pool water heating set in
”Swimming pool water heating”), if the control unit than the temperature at
temperature at DHW tank temperature temperature sensor (swimming pool)
sensor is so high that the actual .
temperature difference falls below the Swimming pool water limit thermostat
set differential temperature. (max. limit) switches circulation
pump OFF when the desired set
The temperature in the DHW tank is water temperature has been reached.
limited by the electronic limit Circulation pump is switched OFF
thermostat in control unit or by for approx. 2 minutes roughly every
high limit safety cut-out (if 15 minutes (adjustable time), to check
required). whether the temperature at the
When the preset temperature is collector temperature sensor is high
exceeded, these devices switch OFF enough to change over to DHW tank
solar circuit circulation pump . The loading.
electronic temperature limit is set at the
factory. When the solar energy is insufficient to
heat the swimming pool water, the
heating of the swimming pool water will
be taken over by the oil/gas-fired boiler
via temperature sensor in heat
exchanger 2.

The filter time and any boiler backup


should fall outside those times when
heating by solar energy can be
expected.
5167 156 v3.1

53
System Designs

System Design 4 (continued)

Installation diagram
2

B C

4 qP

DHW

E
F 28
S R
G
5

5
6

21 8

H K DCW
qT

M qE qQ N 9
qR
2 1
L

Solar collector DHW circulation output of the boiler Swimming pool


Solar-Divicon control unit or timer installed on site Heat exchanger 2
Solar pump line Heating circuit Heat exchanger 1
Taps Oil/gas-fired boiler Filter system with pump
5167 156 v3.1

DHW circulation Dual-mode DHW tank

*1High limit safety cut-out, see page 41.

54
System Designs

System Design 4 (continued)

Dual-mode DHW and swimming pool water heating


- with Vitosolic 200 (continued)

Control equipment required

Item Description Number Part no.


Control of DHW tank loading by solar energy
1 Vitosolic 200 1 7134 552
2 Collector temperature sensor 1 Included in
standard
equipment for
item 1
3 DHW tank temperature sensor*1 1 Included in
standard
equipment for
item 1
4 Circulation pump for the solar circuit 1 7133 454
(standard equipment of Solar-Divicon, see page 35) or
7133 455
5 High limit safety cut-out (see also page 41) 1 Supplied on site
8 Circulation pump 1 Supplied on site

Control of DHW tank loading by the boiler


6 DHW tank temperature sensor 1 Included in
standard
equipment of the
boiler control unit
7 Circulation pump for DHW tank loading 1 DHW tank
accessory

Control of swimming pool heating by solar energy


9 Temperature sensor (swimming pool) 1 Included in
standard
equipment for
item 1
qP Solar circuit circulation pump for swimming pool heating 1 Supplied on site
(part of the solar pump line, see page 35)
qQ Swimming pool limit thermostat (max. limit) 1 Supplied on site
Control of swimming pool heating by the boiler
qE Temperature sensor (heat exchanger 2) 1 7170 965
qR Limit thermostat (max. limit) 1 Supplied on site
qT Circulation pump for swimming pool water heating 1 Supplied on site
*1A threaded elbow (standard delivery for Vitocell-B 100, accessory for Vitocell-B 300) is recommended for this installation.

WARNING
The domestic hot water temperature
must be limited to 140 °F / 60 °C by
installing a mixing device, e.g. a
thermostatic anti-scald mixing valve.
5167 156 v3.1

55
System Designs

System Design Extensions

Bypass circuit

To improve the start-up characteristics


of the system or for systems with
several collector arrays, operation with
a bypass circuit is feasible.

Version 1 - bypass circuit with collector temperature sensor and bypass sensor

The Vitosolic 200 records the collector cylinder sensor is exceeded, the bypass temperature sensor is exceeded by 2.5
temperature via the collector pump is switched ON. K the solar circuit pump is switched ON
temperature sensor. If the set If the temperature difference between and the bypass pump is switched OFF.
temperature difference between the the bypass sensor and the cylinder
collector temperature sensor and the

S1
Note
The pump of the Solar-Divicon is used
as the bypass pump and the pump of
the solar circuit pump line is used as
the solar circuit pump.

R5 R1
R1 Solar circuit pump
R3 Bypass pump
S3 S1 Collector temperature sensor
S3 Bypass sensor
VL RL

Version 2 - bypass circuit with solar cell (e.g. with an external heat exchanger)

For this system version, the solar circuit The solar circuit pump will be switched The pump will be switched OFF, if the
pump takes on this additional function. ON, if the set irradiation threshold is irradiation falls below the set switching
The Vitosolic 200 records the solar exceeded. threshold (shutdown delay approx.
intensity via the solar cell. 2 min).

CS

R1
CS Solar cell
S1 R1 Solar circuit pump
S1 Collector temperature sensor
VL RL
5167 156 v3.1

56
System Designs

System Design Extensions (continued)

System with energy-saving mode

Version 3 - bypass circuit with solar cell and collector temperature sensor

The Vitosolic 200 records the solar and the solar circuit pump will be The bypass pump will also be switched
intensity via the solar cell. switched ON, if the set temperature OFF if the irradiation falls below the set
If the set irradiation threshold is difference between the collector switching threshold (shutdown delay
exceeded, the bypass pump is switched temperature sensor and cylinder approx. 2.5 min).
ON. The bypass pump is switched OFF temperature sensor is exceeded.

Note
CS
The pump of the Solar-Divicon is used
as the bypass pump and the pump of
the solar circuit pump line is used as
the solar circuit pump.

R5 R1
CS Solar cell
S1 R1 Solar circuit pump
R5 Bypass pump
VL RL S1 Collector temperature sensor
5167 156 v3.1

57
Appendix

Calculation Example Based on the Viessmann “ESOP” Program

Solar heating system with dual-coil DHW tank

2 x Vitosol 200-F

200 litres/day
45 °C
Azimuth: 0°
Inclination: 45°

300 litres

11 kW

Results of simulation over a one-year period

DHW solar fraction 59.8 %


System efficiency 36.2 %
Heat yield of collector circuit 2 214 kWh
Irradiation on reference surface 6.12 MWh
Heat requirement for DHW heating 2 975 kWh
Natural gas savings 274 m3
CO2 emissions avoided 520 kg
5167 156 v3.1

58
Appendix

Calculation Example Based on the Viessmann “ESOP” Program (continued)

Solar heating system with dual-coil DHW tank (continued)

Coverage 59.8%

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Period: 1.1. – 31.12.

System parameters
Collector circuit details
2 collectors Model: Vitosol 200-F
Total surface area, gross: 5.42 m2 Net: 4.99 m2
Angle of inclination: 45º Azimuth: 0º

DHW cylinder with two indirect coils


Capacity: 300 l Model: Vitocell-B 100 (300 litres)

DHW consumer
Type: Detached house 200 l per day at 45 ºC set temperature, 365 days

Cold water
February: 8 ºC August: 12 ºC

Weather statistics
A location at 49º latitude Total annual global radiation: 1101.08 kWh/m2
5167 156 v3.1

59
Appendix

Glossary

Absorber Heat loss coefficients k1 and k2 Selective surface


Device contained inside a solar collector k1 is the constant component of the The absorber in the solar collector has
for absorbing radiation energy and heat loss of a collector and is usually been given a highly selective coating to
transferring this as heat to a liquid. designated as k value (unit: W/(m2 · K)). improve its efficiency. This specially
k2 is the quadratic component of the applied coating enables the absorption
Absorption temperature-dependent heat loss to be maintained at a very high level for
Absorption of radiation. (unit: W/(m2 · K2)). the incident sunlight spectrum
Any informative statement about the (approx.94 %). The emission of the
Condenser heat losses of a collector requires both long-wave heat radiation is largely
Device in which vapour is precipitated values to be quoted. avoided.
as liquid. The high-selectivity black chromium
Heat pipe coating is very durable.
Convection Closed, capillary container which
Transfer of heat by a flowing medium. contains a small quantity of highly Stagnation
Convection creates energy losses volatile liquid. Condition of a collector when no heat is
caused by a difference in temperature, being conducted away by the heat
e.g. between the glass plate of the Heat transfer medium transfer medium.
collector and the hot absorber. Fluid which picks up the useful heat in
the absorber of the collector and Vacuum
Dispersion transfers it to a user (heat exchanger). A space devoid of air.
Interaction of radiation with matter by
which the radiation direction is altered; Photovoltaic effect
total energy and wavelength remain Gaining electrical energy from solar
unchanged. energy.

Efficiency Radiation energy


The efficiency of a solar collector is the Quantity of energy transmitted by
input/output ratio of the collector. radiation.
Relevant variables are, for example, the
ambient and absorber temperatures. Radiation level (irradiation)
Radiation power, impacting per unit
Emission surface, expressed in W/m2, or
Radiation of beams, e.g. light or Btu/h/ft.2.
particles.

Evacuation
Evacuating air from a container. This
reduces the air pressure and creates a
vacuum.

5167 156 v3.1

60
5167 156 v3.1

61
62
5167 156 v3.1
5167 156 v3.1

63
Printed on environmentally friendly
(recycled and recyclable) paper.
Technical information subject to change without notice.
5167 156 v3.1

Viessmann Manufacturing Company (U.S.) Inc. Viessmann Manufacturing Company Inc.


45 Access Road 750 McMurray Road
Warwick, Rhode Island • 02886 • USA Waterloo, Ontario • N2V 2G5 • Canada
Tel. (401) 732-0667 • Fax (401) 732-0590 Tel. (519) 885-6300 • Fax (519) 885-0887
www.viessmann-us.com • info@viessmann-us.com www.viessmann.ca • info@viessmann.ca
64

Вам также может понравиться