Вы находитесь на странице: 1из 10

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay

Scope of functions 50

51

50N

51N

49

Fig. 1 7SJ50 numerical overcurrenttime/overload protection relay

Application The 7SJ50 is a numerical protection relay which can be used for definitetime or inversetime overcurrent protection or for thermal overload protection. As an overcurrenttime and earthfault protection relay, the 7SJ50 can protect radial feeders as well as small or medium sized machines and transformers. It can be used as backup protection for differential and distance relays in HV and EHV feeder protection schemes. It can also be used as overload protection for motors, transformers and cables. By use of the directional relay 7SP20, the 7SJ50 can also be applied to ring feeders or to parallel lines with a single infeed. Construction All components, including the DC/DC converter are located on a single PCB. The device can be supplied in three case variations. The model for panel surface mounting is supplied with twotier terminals accessible from the front. The variants for panel flush mounting or cubicle mounting have rear connection terminals and are available with or without glass cover.

Implemented functions Overcurrent time protection with selectable characteristics (inverse or definitetime) D Directional overcurrenttime protection with directional relay 7SP20 D Overload protection selectable without or with memory (thermal replica) D Overload protection with startup time monitoring (locked rotor) D Additional high set (instantaneous) o/c elements available with all characteristics D Phasefailure protection D Earthfault protection
D

Settings Settings are performed by dualinline switches on the front panel. Self monitoring All important software components are monitored continuously. Any irregularities in the hardware or the program sequence are detected and alarmed. As a result, the security and availability of the protection relay are significantly improved.

Mode of operation The measuring quantities from the C.T.s are galvanically isolated, transformed and shunted by input transducers and resistor circuits. The current proportional analog measuring voltages are then converted into digital values and further processed by a microcomputer. Based on the measured values and the selected characteristic and settings, it computes the tripping time. Measurement is performed on all phases.

Siemens LSA 2.1.1 . March 1995

1 e Siemens AG 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay


Overcurrenttime protection The function is based on a common phase measurement. A definitetime or an inversetime characteristic can be selected. For the earth currents, the same type of characteristic is used as for the phase currents. For the definite time characteristic, the tripping time t is computed as follows:

100 100 70 70

t [s]

50 20 10 7 5

t [s] 50

20 10 7 5

t + C @ tp

tp = 1.6 tp = 1

Three different inversetime characteristics according to BS 142 resp. IEC 2554 are available: Normal inverse (Fig. 2) 0.14 t + @ tp (II p) 0.02 1 Very inverse (Fig. 3)

tp = 0.5
1 0.7 0.5 1 0.7 0.5

tp = 0.2 tp = 0.1

tp = 1.6 tp = 1

0.2

tp = 0.05
0.1 0.07 0.05

0.2

tp = 0.5
0.1 0.07 0.05

tp = 0.2

t +

13.5 @ t p II p 1

0.02 0.01 1 2 3 5 7 10 I/Ip 20 0.02

tp = 0.1 tp = 0.05
0.01 1 2 3 5 7 10 I/Ip 20

Extremely inverse (Fig. 4) 80 t + @ tp (II p) 2 1

Fig. 2 Tripping time characteristics normal inverse

Fig. 4 Tripping time characteristics extremely inverse

t tripping time tp time multiplier I fault current I p current setting C settable factor 1, 2 or 4

100 70

t [s]

50

20 10 7 5

2 1 0.7 0.5

tp = 1.6 tp = 1 tp = 0.5

0.2

tp = 0.2
0.1 0.07 0.05

tp = 0.1 tp = 0.05

0.02 0.01 1 2 3 5 7 10 I/Ip 20

Fig. 3 Tripping time characteristics very inverse

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay


Overload protection If the overload protection without thermal memory feature is selected the characteristic shown in Fig. 5 is valid for fault currents I w1.1 @ Ip For different settings of tp, the tripping time t can be computed as follows

t [s]

t [s]

1000 700 500 300 200 150 100 70 50 30 20 15 10 7 5 3 2 1,5 1 0,7 0,5 0,3 0,2 0,15 0,1

1 000 700 500 300 200 150 100 70 50 30 20 15 10 7 5 3 2 1,5 1 0,7 0,5 0,3 0,2 0,15 0,1 1 2 3 4 5 6 7 8

t +

35 @ tp (II p) 2 1

By using the overload protection with memory feature, the preload with all variations is taken into account. The tripping time t can be computed using the following equation (total memory according to IEC 2558)

tp = 80 tp = 40 tp = 20 tp = 10 tp = 5 tp = 2,5

tp = 80 tp = 40 tp = 20 tp = 10 tp = 5 tp = 2,5

t + t @ In

(II p (I preI p (II) 2 k 2 )2

)2

tripping time after start of overload 35.5 tp I p current setting Ipre previous current k 1 (acc. to IEC 255) tp time multiplier I overload current In natural logarithm Fig. 6 and Fig. 7 show the tripping time characteristics for total memory without (Fig. 6) and with (Fig. 7) 80 % preload.

t t

I/Ip
Fig. 5 Tripping time characteristics without memory feature

I/Ip
Fig. 7 Tripping time characteristics with memory feature (no preload)

t [s]

1000 700 500 300 200 150 100 70 50 30 20 15 10 7 5 3 2 1,5 1 0,7 0,5 0,3 0,2 0,15 0,1

tp = 80 tp = 40 tp = 20 tp = 10 tp = 5 tp = 2,5

I/Ip
Fig. 6 Tripping time characteristics with memory feature (80 % preload) Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay


Startup time monitoring In the overload protection mode, an additional settable time stage is available for monitoring the motor startup time. It becomes effective if the current exceeds a fixed value of 2.5 times the setting current Ip and the relay issues a tripping command. Instantaneous high set o/c element For shortcircuit protection, an instantaneous high set overcurrent element with a settable time is available to prevent response to inrush current. This element has always a definitetime characteristic. Phasefailure protection A phase unbalance function is available which detects a missing phase current if the current in the other phases is above 0.25 Ip. 10 s after the detection of a phase unbalance, a trip or an alarm is issued. Earthfault protection The implemented earthfault protection function can be applied if the earthfault current exceeds 10 % of the rated transducer current. This is normally valid for earthed systems e. g. in fourwire systems or lowvoltage motors. The earth current element (IE) has a separate timer.

Application examples

System conditions Solidly earthed Neutral insulated Fault detection L1, L2, L3 With current grading and time grading I>> I>> I>> (E)

Common measurement L1 L2 L3 resp. t

Application example I>> I> I I>

System conditions

Common measurement

Application example

t2
L1 Earthfault current smaller than rated current E L2 L3 resp. I> I>> IE>

t2 tE t1

t1

t
I> I> I> I> (E) L1 L2 L3 I> I>>

IE> I I> I

t2
Fault detection L1, L2, (E), L3

t1

Fault detection L1, L2, L3

L1 E L2 L3 Cable I> I

I>> IE>

t2 tE

t
L1 A B C D A B C D L2 I (E) L3 t I>>

t2

t
I

thermal

Infeed Fault detection L1, L2, L3

Fault detection L1, L2, L3

t
A B C D A B C D

L1 L1 E I L2 L3 I>>

t2
M Cable L2 L3 (E)

I>>

t2

t
I

IE> I> I

t
I

thermal

Infeed Fault detection L1, E, L3

Fault detection L1, L2, L3

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay


Technical data
Input circuits Rated current IN Rated frequency fN Thermal overload capability of current inputs continuous 10 s 1s Burden of current inputs at IN Rated auxiliary voltage Vaux/permissible ranges 1 or 5 A 50/60 Hz 4 x IN 30 x IN 300 x IN approx. 0.5 VA 24, 48 V DC 60, 110, 125 V DC 220, 250 V DC <12 % approx. 5 W approx. 7 W / 19 to 56 V DC / 48 to 144 V DC / 176 to 288 V DC

DC voltage supply via integrated DC/DC converter

Ripple content Power consumption, Setting ranges Definitetime overcurrent protection

quiescent energized

Settable in steps of: Current I> Response value of current Ip Tripping time tp Current I& Response value of current Ip Tripping time tp Earth current IE> Response value of earth current IE Tripping time tp Pickup tolerances for Ip, IE for tp 0.4 to 3.55 x IN 0.05 to 6.4 s 2 to 19 x Ip 1), R 0.025 to 3.2 s 0.1 to 3.2 x IN 0.05 to 6.4 s
"5 % of

0.05 x IN C1 @ 0.05 s, C1 = 1, 2, 4 1 x Ip C3 . 0.025 s, C3 = 1, 2, 4 0.1 x IN C2 . 0.05 s, C2 = 1, 2, 4 0.05 x IN 0.05 s 1 x Ip 0.025 s 0.1 x IN 0.05 s 0.05 x IN 2.5 s 1 x Ip 0.025 s 0.1 x IN 0.05 s 1.25 s

set value Ip, IE "3 % or "10 ms 0.4 to 3.55 x IN 0.05 to 1.6 s "5 % at 1.1 x Ip "5 % at 10 x Ip "7.5 % at 10 x Ip 2 to 19 x Ip 1), R 0.025 to 0.8 s "5 % of set value Ip "3 % or "10 ms 0.1 to 3.2 x IN 0.05 to 1.6 s "5 % of set value "5 % at 10 x Ip "7.5 % at 10 x Ip 0.4 to 3.55 x IN 2.5 to 80 s "5 % at 1.1 x Ip "7.5 % at I = 6 x Ip 2 to 19 x Ip 1) , R 0.025 to 0.8 s 2) 0.1 to 3.2 x IN 0.05 to 1.6 s "5 % of set value "3 % or "10 ms I> 2.5 x Ip 1.25 to 40 s

Inversetime overcurrent protection

Current I> Setting value of current Ip Time multiplier tp Pickup tolerances for Ip for tp

normal and very inverse extremely inverse Current I& (definitetime characteristic) Response value of current Ip Tripping time tp Pickup tolerances for Ip for tp Earth current IE> Setting value of earth current IE Time multiplier tp Pickup tolerances for IE for tp normal and very inverse extremely inverse Overload protection without/with memory feature Current I> Setting value of current Ip Time multiplier tp corresponds to t6 time (to IEC 255) Pickup tolerances for Ip for tp Current I& (definitetime characteristic) Response value of current Ip Tripping time tp& Earth current IE> (definitetime characteristic) Response value of earth current Ip Tripping time tE Pickup tolerances for I&, IE> for tp, tE Start time monitoring Operating criteria Start time tSTA

1) Maximum setting value = 60 IN. 2) By using locked rotor: ON tp = 50 ms. Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay


Technical data (continued)
Phasefailure protection Operating criteria Delay tph Influence on the current paths Auxiliary voltage 0.8 vVaux/Vaux N v1.15 Frequency 0.95 vf/fN v1.05 Harmonics up to 10 % of 3rd harmonic up to 10 % of 5th harmonic Temperature 5 to 20 C 20 to 55 C Influence on operating time Number of trip relays Contacts per relay Switching capacity Switching voltage Permissible current Failure of one phase and I/Ip 0.25 0.05 10 s 0.5 s
v0.6 % v0.1 % per Hz v1.3 % per 1 % of 3rd harmonic v1 % per 1 % of 5th harmonic v0.6 % per 10 K v1.4 % per 10 K

Pickup tolerances

not measurable 2 2 NO 1 000 W/VA 30 W/VA 250 V AC/DC 5A 30 A 3/1 1 NO/ 1 NC 20 W/VA 250 V AC/DC 1A 7XP20 20 housing 6 kg 7XP20 20 housing 5 kg 1 0.075 to 1.7 W, depending on DC operating voltage 24 to 60 V 110 to 250 V

Contacts

make break

continuous 0.5 s Number of alarm relays/malfunction alarm relays Contacts per relay Switching capacity make/break Switching voltage Permissible current Construction For panel surface mounting Weight approx. For panel flush mounting/cubicle mounting Weight approx. Number of input relays Power consumption, energized DC operating voltage

Input

Selection and ordering data


7SJ50 numerical overcurrenttime/ overload protection relay Rated current IN 1A 5A Rated auxiliary voltage Vaux for the builtin converter 24, 48 V DC 60, 110, 125 V DC 220, 250, V DC Construction Panel flush mounting Panel surface mounting Panel surface mounting (without glass cover) Directional relay interface without termination connector with termination connector Order No. 7SJ50 0 V V V V V 0 1 5

2 4 5 C D E A 0 A 1

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay

Version for panel surface mounting L1 L2 L3 N Version for panel flush mounting/cubicle mounting IL1 IL2 1 4 2 5 3 6 1A1 1A2 2A1 2A2 3A1 3A2

IL1 IL2 IL3

IN

IL3 IN

Input with increased E/F sensitivity

M
Signal contact 1 3B2 3B1 4B2 26 25 24 Phase failure IE> IPH>

7SJ50

Signal contact 2 Signal contact 3

Relay blocked 9 Remote reset or blocking I>> 10 4A3 4A4 Binary input Command relay 1 L+ Power supply L 22 23 8 4A1 4A2 Command relay 2

3B3 4B1

28 27

L+ Relay monitor

2B4 2B3 2B2 2B1 1B4 1B3 1B2 1B1

19 12 11 18 21 14 13 20

Tripping I>

Tripping I>>

Fig. 8 Connection diagram for motor overload and shortcircuit protection with sensitive detection of neutral current (fourwire system)

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

7SJ50 numerical overcurrenttime/overload protection relay

Version for panel surface mounting L1 L2 L3 Version for panel flush mounting/cubicle mounting IL1 IL2/E IL3 IL1 IL2/E 1 4 2 5 IN IL3 IN 3 6 1A1 1A2 2A1 2A2 3A1 3A2 Signal contact 2 16 17 L1 L2 L3 Optional directional relay 7SP20 18 19 20 21 5A1 5A3 5B1 5B3 5A2 5A4 2B4 2B3 2B2 2B1 1B4 Commant relay 2 22 23 8 4A1 4A2 14 1B2 1B1 1B3 13 I>> 12 11 IPH>, IE> 1) Relay blocked 3B3 4B1 28 L+ 27 Relay monitor Signal contact 3 3B1 4B2 25 I > E 24 I > PH Signal contact 1 3B2 26 Phase failure

7SJ50

Commant relay 1 Remote reset or blocking I>> 9 10 4A3 4A4 Binary input

L+ Power supply L

Fig. 9 Connection diagram for motor overload and shortcircuit protection with sensitive detection of neutral current (fourwire system)

1) Option (only with 7SJ50.0.. A10. connections for directional relay)

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

Dimension drawings in mm

7.3 75 30 172 29.5 70 13.2

56.3 30 5.4 Diam. 5 or M4

M5

Diam. 6

71

Front view

Side view

Rear view

Panel cutout

Fig. 10 7SJ50 with housing 7XP20202 (for panel flush mounting)

92
15 22 21 28

27

29.5

Cutout 20 x 60 (without paint)

280

344

39

1 8

7 14

71 77 Front view 260

Side view

Fig. 11 7SJ50 with housing 7XP20201 (for panel surface mounting)

266

40

255.8

244

266

245

Siemens LSA 2.1.1 . March 1995

Overcurrent and Distance Relays

Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions


Conditions of Sale and Delivery Subject to the General Conditions of Supply and Delivery for Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon with the recipients of catalogs.

The technical data, dimensions and weights are subject to change unless otherwise stated on the individual pages of this catalog. The illustrations are for reference only.

We reserve the right to adjust the prices and shall charge the price applying on the date of delivery.

A 9.91 a

Export Regulations In accordance with present German and US export regulations export licences (dated 02.95) are not required for the products listed in this catalog. Export and reexport are therefore

permissible without the approval of the relevant authorities except where current German export regulations contain countryspecific restrictions.

Subject to change. Relevant are the criteria stated in the delivery note and in the invoice. An export licence may be required due to countryspecific application of the product.

Trademarks All product designations used are trademarks or product names of Siemens AG or of suppliers.

Dimensions All dimensions in this catalog are given in mm

Responsible for Technical contents: Norbert Schuster, Siemens AG, EV S T11, Nrnberg General editing: Claudia KhnSutiono, Siemens AG, EV MK 2, Erlangen

Bereich Energiebertragung und -verteilung Geschftsgebiet Zhler, Sekundr- und Netzleittechnik P. O. Box 48 06 D-90026 Nrnberg 10 Siemens Aktiengesellschaft

Power Transmission and Distribution


Order No.: E50001-K5712A111-A17600 Siemens LSA 2.1.1 . March 1995 Printed in the Federal Republic of Germany

Вам также может понравиться