Voltage 415V+/-10%
Frequency 50Hz+/-5%
Combined Voltage & Frequency
variation +/-10% ( absolute sum )
Ambient temperature:- 50 deg /45 deg
Altitude:-1000m
IS:4722
IS:2223
IEC:60034-1
100%
50
95%
55
Motor Selection Procedure:FOR DOL :The motors are selected from the chart
after matching the required starts stops
per hour & corresponding CDF .
FOR VFD :The motors are selected from the chart
based on the given mechanical KW .The
final motor KW is selected based on the
starts stops per hour , CDF & deration
on account of Drive. Depending upon
the type of crane employed , user has to
take applicable service factor as per IS
2231& IS4137 & correct the mechanical
KW accordingly. The permissible
temperature rise i.e, Class B will be
corresponding to the given mechanical
KW .
90%
60
S3
Intermittent duty
A sequence of identical cycles, each
including a period of operation at
constant
S5
Intermittent duty with starting and
electrical braking .
A sequence of identical duty cycles,
each cycle consisting of a significant
period of starting, a period of operation
at constant load, a period of rapid
electric braking and a rest and deenergised period. The period is too short
for thermal equilibrium to be
obtained.After the duty type the
following factors must be indicated: the
cyclic duration factor; the number of
duty types per hour (c/h); the factor of
inertia FI; the moment of inertia J, of
the motor, and the Mpermissible
moment of resistance T (see duty type
S4.)V2Designation e.g. S5-40% -120
c/h- FI.3 - J= 1,3 kgm - T = 0,3 T.
Enquiries :
The following information should be
included during enquiry stage: a)Application.
b)Voltage and frequency variations.
c)Ambient temperature, and type of
protection
d)Mechanical KW with service factor as
applicable according to crane employed
e)No. of starts/stops per hour with duty
and CDF.
f)Type of starting
g)Load GD2 at motor speed.
h)Load torque ; or Torque/Speed curve
of driven equipment.
i) Duty cycle diagram, if other than those
described earlier.
415V10%
50Hz5%
Pole-4
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
Frame
KHX71C4
KHX80D4
KHX80D4
KHX90SLE4
KHX90SLE4
KHX100LC4
KHX112MC4
KHX132SME4
KHX132SME4
KHX160MLD4
KHX160MLE4
KHX160MLE4
KHX180MLC4
KHX200MLD4
60 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
30
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
53.3
0.55
0.75
1.1
1.5
2.2
7.9
5.5
7.5
9.3
11
15
18.5
22
30
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
53.3
150 Starts
25% OR 40 % CDF
Kw
In (A)
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
30
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
53.3
60 % CDF
Kw
In (A)
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
30
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
53.3
300 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
26
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
46
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
26
1.6
2.0
3.1
3.4
5.2
7.9
11.3
14.5
18.7
21
28
35.6
40.5
46
Motor GD Sq.
Weight
Kgm.sq
Kg
0.0035
0.007
0.007
0.017
0.017
0.028
0.062
0.112
0.112
0.252
0.302
0.302
0.54
1.344
13.5
15
15
27
27
39.5
49
80
80
145
160
160
185
265
Series Name-KHX
415V10%
Enclosure-TEFC
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
Frame
KHX80B6
KHX80D6
KHX80D6
KHX90SLE6
KHX90SLE6
KHX100LB6
KHX112MC6
KHX132SME6
KHX132SME6
KHX160MLD6
KHX160MLE6
KHX160MLE6
KHX200MLC6
KHX200MLC6
60 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
36
42
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
36
42
25% OR 40 % CDF
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
36
42
50Hz5%
Ambient -45 deg
Duty -S4 & S5 (equivalent)
150 Starts
60 % CDF
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
36
42
300 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
17
18.5
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
33
36
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
17
18.5
1.2
1.6
2.3
2.9
4.1
5.9
10.5
12.5
18.2
19
23
34.7
33
36
Motor GD Sq.
Weight
Kgm.sq
Kg
0.006
13
0.008
0.008
0.017
0.017
0.017
0.62
0.12
0.12
0.372
0.446
0.446
1.8
1.8
15
15
28
28
28
48
80
80
155
170
170
300
300
Series Name-KHX
Enclosure-TEFC
Pole-8
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
Frame
KHX90SLA8
KHX90SLD8
KHX90SLD8
KHX100LB8
KHX100LB8
KHX112MB8
KHX132SMC8
KHX160MLD8
KHX160MLE8
KHX160MLE8
KHX180MLB8
KHX200MLC8
60 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
415V10%
50Hz5%
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
23.5
28
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
23.5
28
150 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
23.5
28
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
23.5
28
300 Starts
25% OR 40 % CDF
60 % CDF
Kw
In (A)
Kw
In (A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
23.5
28
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
10
11
1.4
1.9
2.7
3.9
6
7.8
10.5
12
16
19.8
22
24
Kgm.sq
Kg
0.012
22
0.015
0.015
0.026
0.026
0.048
0.08
0.372
0.446
0.446
0.72
2.21
25
25
35
35
48
65
155
170
170
200
250
Note: 1..All crane duty motors are suitable for VFD supply subject to proper selection using ABB Drive Size Software considering required BKW, speed range and constant torque appln.
2. All crane duty motors shall be offered as MI motors
3. Load GD Sq value should not be more than motor GD sq value.
4. Motors for frame size 225 and higher can be offered against enquiry
5)For class H insulation & temperature rise limited to Class F , 15% higher KW can be considered.
415V10%
50Hz5%
Pole-6
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
FRAME
MOTOR
Current
RATING
Motor GD
Weight
(Kg m)
Kg
0.008
15
0.015
0.008
0.017
0.026
0.05
0.088
0.12
0.326
0.372
0.446
0.68
1.6
1.8
25
15
28
35
46
70
80
145
155
170
185
230
300
KHX+80D6
KHX+90SLD6
KHX+90SLE6
KHX90SLE6
KHX+100LB6
KHX+112MB6
KHX+132SMC6
KHX+132SME6
KHX+160MLC6
KHX+160MLD6
KHX+160MLE6
KHX+180MLC6
KHX+200MLB6
KHX+200MLC6
KW
25 OR 40
% CDF
In(A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
18.5
22
1.2
1.6
2.3
2.9
4.1
5.9
8.3
12.5
15.5
19
23
30
36
42
0.3
0.45
0.6
0.9
1.2
1.7
2.9
4.3
5.8
7.2
7.6
11.7
14.2
16.8
1.0
1.4
1.9
2.5
3.3
4.6
6.6
10
12.2
14.8
16
24
28
33
25 OR 40 %
CDF
In(A)
60 % CDF
In(A)
0.3
0.45
0.6
0.9
1.2
1.7
2.9
4.3
5.8
7.2
7.6
11.7
14.2
16.8
1.0
1.4
1.9
2.5
3.3
4.6
6.6
10
12.2
14.8
16
24
28
33
0.3
0.45
0.6
0.9
1.2
1.7
2.9
4.3
5.8
7.2
7.6
11.7
14.2
16.8
1.0
1.4
1.9
2.5
3.3
4.6
6.6
10
12.2
14.8
16
24
28
33
Note:-
1)Maximum permissible Mechanical KW has been calculated based on VVVF supply & duty cycles
2)Separate derations are required for different service factors for different cranes & ambient temperature
3)Speed range 10-100%
4)Load GD square is assumed to be equal to motor GD
5)For class H insulation & temperature rise limited to Class F , 15% higher mechanical KW can be considered.
100% CDF
0.25
0.4
0.5
0.8
1.0
1.4
2.5
3.7
4.9
6.1
6.5
9.9
12.1
14.3
In(A)
0.8
1.2
1.6
2.1
2.8
3.9
5.6
8.4
10.3
12.5
13.5
20.2
23.6
27.8
415V10%
50Hz5%
Pole-6
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
FRAME
MOTOR
Current
RATING
KHX+225SMC6
KHX+250MB6
KHX+280SMB6
KHX+280SMC6
M2BA315SMA6
M2BA315SMB6
M2BA315SMC6
M2BA315MLC6
M2BA355SMA6
M2BA355SMB6
M2BA355MLA6
M2BA355MLB6
M2BA400LA6
M2BA400LB6
KW
30
37
45
55
75
90
110
132
160
200
250
315
355
400
A
55.5
66
79.5
97
132
158
193
228
275
343
428
550
640
740
25 OR 40
% CDF
25
30
35
42
55
75
88
96
110
136
185
240
252
270
In(A)
50
55
65
68
110
135
165
180
200
260
340
450
500
610
60% CDF
23
27
33
39
53
69
83
92
107
133
177
227
243
260
In(A)
45
50
60
65
100
125
160
175
195
255
325
425
485
590
100% CDF
20
25
30
36
49
62
75
86
101
125
164
210
205
245
Motor
GD
Weight
(Kg m)
2.98
4.8
7.2
8.1
14.2
16.7
20
28.2
42
50.5
55
60.2
66
77
Kg
320
420
590
600
860
930
1005
1240
1595
1800
1940
2040
3000
3100
In(A)
40
46
55
60
92
118
150
165
185
240
305
395
410
560
25 OR 40
% CDF
21
27
31
36
47
68
77
83
92
114
160
210
212
237
Note:-
1)Maximum permissible Mechanical KW has been calculated based on VVVF supply & duty cycles
2)Separate derations are required for different service factors for different cranes & ambient temperature
3)Speed range 10-100%
4)Load GD square is assumed to be equal to motor GD square
5)For class H insulation & temperature rise limited to Class F , 15% higher mechanical KW can be considered.
In(A)
40
50
58
60
90
128
155
164
180
220
300
395
420
550
60 % CDF
20
26
29
35
46
65
75
82
90
110
158
205
210
230
In(A)
40
48
55
57
85
122
150
160
178
215
295
390
415
540
100% CDF
19
24
28
34
45
60
71
79
88
108
152
195
185
210
In(A)
36
45
54
55
83
115
145
155
175
212
285
375
400
500
415V10%
50Hz5%
Pole-8
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
FRAME
MOTOR
Current
RATING
KHX+90SLA8
KHX+90SLD8
KHX+100LA8
KHX+100LB8
KHX+112MA8
KHX+132SMB8
KHX+160MLB8
KHX+160MLD8
KHX+160MLE8
KHX+180MLA8
KHX+180MLB8
KHX+200MLC8
KW
25 OR 40
% CDF
In(A)
60% CDF
In(A)
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
9.3
11
15
1.4
1.9
3.1
3.9
4.8
6.3
8
12
16
20
23.5
31.5
0.29
0.44
0.58
0.85
1.2
1.7
2.8
4.3
5.9
7.2
8.6
11.6
1.1
1.6
2.5
3.3
3.8
6.0
6.6
10
14
16
18
25
0.29
0.44
0.58
0.85
1.2
1.7
2.8
4.3
5.9
7.2
8.6
11.6
1.1
1.6
2.5
3.3
3.8
6.0
6.6
10
14
16
18
25
100% CDF
0.26
0.40
0.52
0.77
1.1
1.5
2.5
3.9
5.3
6.5
7.7
10.4
Motor
GD
Weight
(Kg m)
Kg
0.012
22
0.015
0.02
0.026
0.044
0.06
0.288
0.372
0.446
0.64
0.72
1.98
25
35
35
45
60
125
155
170
160
170
240
In(A)
1.0
1.5
2.4
3.1
3.6
5.7
6.2
9.5
13.2
15.1
17.0
23.6
25 OR 40
% CDF
In(A)
60 % CDF
In(A)
0.29
0.44
0.58
0.85
1.2
1.7
2.8
4.3
5.9
7.2
8.6
11.6
1.1
1.6
2.5
3.3
3.8
6.0
6.6
10
14
16
18
25
0.29
0.44
0.58
0.85
1.2
1.7
2.8
4.3
5.9
7.2
7.8
8.6
1.1
1.6
2.5
3.3
3.8
6.0
6.6
10
14
16
16.6
25
Note:-
1)Maximum permissible Mechanical KW has been calculated based on VVVF supply & duty cycles
2)Separate derations are required for different service factors for different cranes & ambient temperature
3)Speed range 10-100%
4)Load GD square is assumed to be equal to motor GD square
5)For class H insulation & temperature rise limited to Class F , 15% higher mechanical KW can be considered.
100% CDF
0.2
0.4
0.5
0.7
1.0
1.4
2.4
3.7
5.0
6.1
6.6
7.3
In(A)
1.0
1.4
2.2
2.9
3.4
5.4
5.9
8.9
12.5
14.3
14.8
22.3
415V10%
50Hz5%
Pole-8
Protection/Cooling-IP55 / IC411
Insulation class-F
Temperature rise Class-B
FRAME
MOTOR
Current
RATING
Motor GD
Weight
(Kg m)
3.32
3.5
4.54
7.64
7.75
13
18.8
22
23.6
42
55
64.2
66
68.8
80
Kg
320
340
520
590
600
830
975
1055
1125
1590
1945
2090
2100
2800
3100
KHX+225SMB8
KHX+225SMC8
KHX+250MB8
KHX+280SMB8
KHX+280SMC8
M2BA315SMA8
M2BA315SMB8
M2BA315SMC8
M2BA315MLB8
M2BA355SMA8
M2BA355MLA8
M2BA355MLB8
M2BA355MLB8K
M2BA400LA8
M2BA400LB8
KW
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
355
A
38.5
45.5
60
73.5
89
101
135
162
197
239
289
360
470
600
670
25 OR 40
% CDF
15
19
25.5
30
38
42.5
55
77
87
100
120
155
194
238
308
In(A)
34
42
55
62
78
87
110
150
165
205
240
310
405
510
610
25 OR 40 %
CDF
14
17
23
27
34
38
52
68
78
87
104
136
171
208
257
In(A)
32
38
50
56
70
78
105
130
150
180
210
280
360
450
520
Note:-
1)Maximum permissible Mechanical KW has been calculated based on VVVF supply & duty cycles
2)Separate derations are required for different service factors for different cranes & ambient temperature
3)Speed range 10-100%
4)Load GD square is assumed to be equal to motor GD
5)For class H insulation & temperature rise limited to Class F , 15% higher permissible mechanical KW can be considered.
60 % CDF
13.5
16
22.5
26
33
36
50
66
76
86
103
133
167
204
250
In(A)
31
36
48
54
68
75
100
125
146
175
208
275
355
445
510
100% CDF
12
15
20.5
24
30
34
45
60
70
82
98
126
157
195
245
In(A)
28
35
44
50
62
72
90
115
135
168
200
262
335
428
500