DATASHEET DTRCO

CC62P

DE 240309

SIEMENS CC62P. CO detector


Detector for carbon monoxide using electrochemical technology

Specially designed for SIEMENS CC62P toxic and explosive gas detection system. Electrochemical sensor provided of a filter for SOx, NOx y H2S. Calibrated at factory with target gas.

Siemens Building Technologies

Application
Carbon Monoxide (CO) is a poisonous, odourless and colourless gas produced by the incomplete combustion of fossil fuels (petrol, butane, propane, natural gas, kerosene, carbon and wood). It is very dangerous when inhaled, even in small quantities. It inhibits the blood capacity to carry oxygen and can cause death in a few seconds. Some of the CO emission sources are fuel burners in a bad condition or wrongly installed, water heaters, chimneys, petrol vehicles, etc CO detection in underground cark parks The detector has been specially designed for underground cark parks, road tunnels, garages and, in general, for those installations where there is presence of carbon monoxide.

Features & Characteristics


Special features SIEMENS CC62P carbon monoxide detector uses electrochemical cells that incorporates a filter for SOx, NOx y H2S. The recommended coverage area is 200m2 As carbon monoxide molecular weight is similar to air, It goes up quickly depending on temperature and humidity. It tends to accumulate in gas bags because its slow dissolution in the air. The recommended height of installation is 1,8 to 2 meters from floor protecting peoplein walls and columns. Maintenance It is recommended to check the status of the detectors every year and adjust to zero those detectors that require it (the system discriminates automatically) The life expectancy of the sensor is 4 years -following manufacturer indications-. After this time, the sensor should be replaced if necessary. Stabilised functioning Reliable detection during the detectors years of useful life. The system uses sensors with a range of 0-1000 ppm (with occasional overflows of up to 2000 ppm) while the equipments lowest scale is fixed at 400 ppm. In this way the detectors foreseeable annual loss of sensitivity is guaranteed not to affect the systems functioning.

Coverage area Height of installation

Recommendations

Do not install the detectors unless the construction and painting works are finalised. Avoid connecting the detectors close to sources that generate electromagnetic disturbances (fluorescents lights, motors, counters, etc.) or use shield cable. Do not paint nor drill holes on the detector housing. We recommend not storing the detector for more than six months.

2 Siemens Building Technologies

Technical characteristics
Detector SIEMENS for carbon monoxide (RS485) Technology Voltage Consumption Measurement range Resolution Reproductiveness Linearity Calibration gas Sensor life expectancy Relative humidity Atmospheric pressure Working temperature Time response Cable entry Communication Protection grade Presentation Weight (gr) & Dimensions (mm) Height of installation Cover 8 bits microprocessor and electrochemical sensor with filter for SOx/NOx/H2S From 9V to 15V DC 8mA (stand-by) 15mA (alarm). From 0 to 400 ppm 2 ppm 1% bottom of scale Linear in all the scale Precise mixture 200 ppm CO + N2 150 ml / min 4 years in normal working conditions From 15% to 90% (continuous) & from 0% to 99% (intermittent). 10%. From 15C to +50C T90 < 40 s. PG9 stopping plug IP67 self-blocking RS485 addressable (1 to 16). IP65 ABS & Makrolon 325 grs. 120-150-63 (including sensor head & cable entry) 1,8 - 2 m from floor 200 m2 (according with current standard).

Other available gases in this format: NO2, NO, O2, HCl, Cl2, SO2, H2S, Exp

Control Unit & module lines


Technology Voltage Maximum consumption Maximum length C.U. / dtrs Cable Maximum capacity per line Reading modes Data presentation Reading speed Ventilation outputs Microprocessor 16 bits From 9V to 15V DC 180 mA per module line 1,000 m Shield cable 4 wires for main power 2 x 1.5mm2 & 2 x 0,25 mm2 twisted pair for communicationsUp to 16 detectors Sequential or Maximum reading LCD display 16 x 2 lines of back-lit alphanumeric characters 2 s per detector -sequential mode- & 2 s -maximum reading4 independent outputs per module line 3A 250V AC or 3A 30V DC dry contact fuse-protected with optical status indicator and de-parasiting circuit and ground branching 1 general. Dry contact relay 5A 250V AC or 8A 30V DC dry contact and fuse-protected 1 general. Dry contact C, NO Up to 2 batteries 12V DC 7,5Ah 13,8V 4,5A voltage stabilized and limited current 220V-240V AC with incorporated power filter 370 x 315 x 145 (1-2 module line C.U.) 600 x 315 x 145 (3-4 module line C.U.) 9 (1-2 module line C.U.) 14 (3-4 module line C.U.)

Alarm output Fault output Battery output Power supply Mains entrance Dimensions -mmWeight -kg-

3 Siemens Building Technologies

DATASHEET DTRNO2

CC62P

DE 240309

NO2

SIEMENS CC62P. NO2 detector


Detector for Nitrogen Dioxide using electrochemical technology

Specially designed for SIEMENS CC62P toxic and explosive gas detection system. Designed for detection of Nitrogen Dioxide in closed areas.

Siemens Building Technologies


Application Nitrogen Dioxide (NO2) is a toxic, corrosive, strong oxidising and non inflammable gas, very dangerous, that in concentrations higher than 4 ppm causes intoxication symptoms: eye, nose and bronchial tubes irritation and even death. The major sources of NO2 are diesel motor vehicles and combustion associated processes in petrochemical industries and power plants, as well as any high temperature combustion process used in industrial work.

Features & Characteristics Maximum features Last generation of electrochemical sensor The recommended coverage area is 200m2

Coverage area

Height of installation

The recommended height of installation is 1 meter from floor.

Maintenance

It is recommended to check the status of the detectors every year and adjust those detectors that require it. The life expectancy of the sensor is 2 years -following manufacturer indications-. After this time, the sensor should be replaced if necessary.

Recommendations

Do not install the detectors unless the construction and painting works are finalized. Avoid connecting the detectors close to sources that generate electromagnetic disturbances (fluorescents lights, motors, counters, etc.) or use shield cable. Do not paint nor drill holes on the detector housing. We recommend not storing the detector for more than six months.

2 Siemens Building Technologies

Technical characteristics SIEMENS detector for Nitrogen Dioxide (RS485)


Technology Voltage Consumption Measurement range Resolution Reproductiveness Linearity Calibration gas Sensor life expectancy Atmospheric pressure Relative Humidity Working temperature Time response Cable entry Communication Protection grade Presentation Weight (gr) & Dimensions (mm) Height of installation Coverage Microprocessor and electrochemical sensor From 9V to 15V DC 8mA From 0 to 20 ppm. 0,1 ppm. 0,5% bottom of scale All the scale Precise mixture 10 ppm NO2 - N2 1000 ml / min 2 years in normal working conditions 10%. From 15% to 90% (continuous) & from 0% to 99% (intermittent). From 15C to +50C T90 < 40 s. PG9 stopping plug IP67 self-blocking RS485 addressable (1 to 16). IP65 ABS & Makrolon 325 gr. 120-150-63 (including sensor head & cable entry) 1 m from floor 200 m2 (recommended).

Other available gases in this format: CO, O2, NO, HCl, Cl2, SO2, H2S, Exp

Control Unit & module lines


Technology Voltage Maximum consumption Maximum length C.U. / dtrs Cable Maximum capacity per line Reading modes Data presentation Reading speed Ventilation outputs Microprocessor 16 bits From 9V to 15V DC 180 mA per module line 1,000 m Shield cable 4 wires for main power 2 x 1.5mm2 & 2 2 x 0,25 mm twisted pair for communicationsUp to 16 detectors Sequential or Maximum reading LCD display 16 x 2 lines of back-lit alphanumeric characters 2 s per detector -sequential mode- & 2 s -maximum reading4 independent outputs per module line 3A 250V AC or 3A 30V DC dry contact fuse-protected with optical status indicator and de-parasiting circuit and ground branching 1 general. Dry contact relay 5A 250V AC or 8A 30V DC dry contact and fuse-protected 1 general. Dry contact C, NO Up to 2 batteries 12V DC 7,5Ah 13,8V 4,5A voltage stabilized and limited current 220V-240V AC with incorporated power filter 370 x 315 x 145 (1-2 module line C.U.) 600 x 315 x 145 (3-4 module line C.U.) 9 (1-2 module line C.U.) 14 (3-4 module line C.U.)

Alarm output Fault output Battery output Power supply Mains entrance Dimensions -mmWeight -kg-

3 Siemens Building Technologies

DATASHEET DTRO2

CC62P

DE 240309

SIEMENS CC62P. O2 detector


Detector for Oxygen using electrochemical technology

Specially designed for SIEMENS CC62P toxic and explosive gas detection system. Designed for detection of lack of Oxygen in closed areas.

Siemens Building Technologies

Application SIEMENS CC62P detectors for Oxygen using electrochemical technology have been designed for closed areas. The excess or lack of Oxygen in air can cause in the human being from euphoria to death. Their main applications are: cellars, food processing, grain storage, greenhouse, incubators, mining, nuclear industry, oil rings and sewage industry. The lack of Oxygen at work places may cause anoxy symptoms.

Features & Characteristics

Levels of ventilation & alarm

The ventilation level has been programmed to act when the Oxygen level goes down 15%, otherwise the alarm level will act when the Oxygen level goes up 24%. Both levels, ventilation & alarm, are totally programmable from the Control Unit SIEMENS CC62P. The recommended coverage area is 100m2

Coverage area

Height of installation

The recommended height of installation is 1,7 to 2 meters from floor established following the average height of the human being.

Maintenance

It is recommended to check the status of the detectors every year and adjust those detectors that require it. The life expectancy of the sensor is 2 years -following manufacturer indications-. After this time, the sensor should be replaced if necessary.

Recommendations

Do not install the detectors unless the construction and painting works are finalized. Avoid connecting the detectors close to sources that generate electromagnetic disturbances (fluorescents lights, motors, counters, etc.) or use shield cable. Do not paint nor drill holes on the detector housing. We recommend not storing the detector for more than three months.

2 Siemens Building Technologies

Technical characteristics SIEMENS detector for Oxygen (RS485)


Technology Voltage Consumption Measurement range Resolution Reproductiveness Linearity Calibration gas Sensor life expectancy Atmospheric pressure Relative humidity Working temperature Time response Cable entry Communication Protection grade Presentation Weight (gr) & Dimensions (mm) Height of installation Coverage Microprocessor and electrochemical sensor From 9V to 15V DC 8mA From 0 to 25% 0,25%. 0,5% bottom of scale Linear in all the scale Precise mixture O2 - N2 at 25% 250 ml / min 2 years in normal working conditions 10%. From 15% to 90% (continuous) & from 0% to 99% (intermittent). From 15C to +50C T95 < 15 s. PG9 stopping plug IP67 self-blocking RS485 addressable (1 to 16). IP65 ABS & Makrolon 325 gr. 120-150-63 (including sensor head & cable entry) 1,7 - 2 m from floor 100 m2 (recommended).

Other available gases in this format: NO2, NO, CO, HCl, Cl2, SO2, H2S, Exp

Control Unit & module lines


Technology Voltage Maximum consumption Maximum length C.U. / dtrs Cable Maximum capacity per line Reading modes Data presentation Reading speed Ventilation outputs Microprocessor 16 bits From 9V to 15V DC 180 mA per module line 1,000 m Shield cable 4 wires for main power 2 x 1.5mm2 & 2 2 x 0,25 mm twisted pair for communicationsUp to 16 detectors Sequential or Maximum reading LCD display 16 x 2 lines of back-lit alphanumeric characters 2 s per detector -sequential mode- & 2 s -maximum reading4 independent outputs per module line 3A 250V AC or 3A 30V DC dry contact fuse-protected with optical status indicator and de-parasiting circuit and ground branching 1 general. Dry contact relay 5A 250V AC or 8A 30V DC dry contact and fuse-protected 1 general. Dry contact C, NO Up to 2 batteries 12V DC 7,5Ah 13,8V 4,5A voltage stabilized and limited current 220V-240V AC with incorporated power filter 370 x 315 x 145 (1-2 module line C.U.) 600 x 315 x 145 (3-4 module line C.U.) 9 (1-2 module line C.U.) 14 (3-4 module line C.U.)

Alarm output Fault output Battery output Power supply Mains entrance Dimensions -mmWeight -kg-

3 Siemens Building Technologies

Details for ordering


SIEMENS DETECTORS (RS485) precalibrated Code CEDTR-CO CEDTRNO2 CEDTR-02 EUDT--NO EUDT-SH2 EUDT-CLH EUDT-CL2 EUDT-SO2 Description Carbon monoxide CO Nitrogen dioxide NO2 Oxygen O2 Nitrogen monoxide NO Hydrogen sulphide H2S Hydrochloric acid HCl Chlorine Cl2 Sulfur Dioxide SO2

For other gases, please consult

CONTROL UNITS Code SICT1**** SICT2**** SICT3**** SICT4**** SIMZ**** Description Control Unit 16 detectors Control Unit 32 detectors Control Unit 48 detectors Control Unit 64 detectors Module line

**** Add at the end of the code the five letters corresponding to the selected Keypad/Standard Ex: For German Standard / English Keypad, code would be SICT1IANAI

Code EENEI EESEI EPNEI EPSEI IPNIP IPSIP EPNPI EPSPI IANAI IENIE

Standard / Keypad Languages Spanish Standard / Spanish Keypad no integration Spanish and English languages Spanish Standard / Spanish Keypad with integration Spanish and English languages Port-International Standard / Spanish Keypad no integration Spanish and English languages Port-International Standard / Spanish Keypad w/ integration Spanish and English languages Port-International Standard / English Keypad no integration English and Portuguese languages Port-International Standard / English Keypad w/ integration English and Portuguese languages Port-International Standard / Spanish Keypad no integration English and Portuguese languages Port-International Standard / Spanish Keypad w/ integration English and Portuguese languages German Standard / English Keypad German Standard cannot be integrated English and Portuguese languages Spanish Standard / English Keypad no integration English and Spanish languages