MITSUBISHI

ELECTRONIC MULTI-MEASURING INSTRUMENT

ME96NSR

Small & Flexible

1. Lineup
Basic Device Model Name ME96NSR ME96NSR-MB Transmission ModBus Communication

Optional Plug-in Module Model Name ME-4201-NS96 ME-0040C-NS96 ME-0052-NS96 Analog Output 4 Pulse Output 2 Contact Input 4 5 Contact Output 1 2 Transmission Function CC-Link -

2. Features
Variety of Measuring Items Variety of Display Functions
Large Bar Graph + Tri-level Digital Display 96 mm 96 mm A,DA,V,W,var,VA,PF,Hz,Wh,varh,HI,HV

Remote Input/Output Function 3P4W/3P3W Common Use


No need to specify phase-wire when ordering

VT, CT Set Freely Instrument Rated Current 5A/1A Common Use DIN 9696mm Size Option Module Plug-in Add-on Type

3. Functions
Variety of Display Functions
All Phase Simultaneous Display
Average Voltage Voltage Current Electricity Power Factor

4 Measuring Elements Simultaneous Display

Special Display Pattern


UpperSelect from A,V,W,var,VA,PF,Hz MiddleSelect from A,V,W,var,VA,PF,Hz
LowerSelect from A,V,W,var,VA,PF,Hz,Wh,varh

Maximum of 4 displays are settable

Functions Available Keep the display unchanged Keep the display unchanged when even when the DISPLAY button is pushed Please set only 1 display Use ME96NSR instead of electric energy meter by displaying electric power

Maximum/Minimum Value Display


Min. Value

Cyclic Display
Automatically changes display every 5 seconds Cyclic Display continues even after the power
is turned ON/OFF

Max. Value Max. Value Current Value Min. Value

Alarm Indicator
Displays Alarm Indicator in bar graph Enable to grasp the percentage against the Alarm Indicator instantly
Alarm Indicator

Remote Input/Output Function


ME-0040C-NS96 Contact Input: 4 points ME-0052-NS96 Contact Input: 5 points Contact Output: 2 points Latch Function (Over 30ms)

Test Function
Even during a setup of a facility, where no input current/voltage is found, analog output, pulse output, alarm output, and communication data is replied. This allows for easy checking of systems wiring and monitoring program.

4. Specifications
Measuring Items
Current (A) Current Demand (DA) Voltage (V) Active Power (W) Reactive Power (var) Apparent Power (VA) Frequency (Hz) Power Factor (PF) Active Energy (Wh) Reactive Energy (varh) Harmonics Current (HI) Harmonics Voltage (HV) PF,PF1,PF2,PF3 Imported, Exported Imported Lead, Imported Lag, Exported Lead, Exported Lag HI1,HI2,HI3,HIN HV1N,HV2N,HV3N HI1,HI2,HI3 HV12,HV23 THD, h1, h13 RMS Value and Distortion Ratio THD, h1, h13 RMS Value and Distortion Ratio

3P4W
A1,A2,A3,AN,AAVG DA1,DA2,DA3,DAN,DAAVG V12,V23,V31,VLLAVG or V1N,V2N,V3N,VLNAVG W,W1,W2,W3 var,var1,var2,var3 VA,VA1,VA2,VA3 Hz

3P3W
A1,A2,A3,AAVG DA1,DA2,DA3,DAAVG V12,V23,V31,VLLAVG W var

PF

Measuring Accuracy
Measuring Items
Current (A) Current Demand (DA) Voltage (V) Active Power (W) Reactive Power (var) Apparent Power (VA) Frequency (Hz) Power Factor (PF) Active Energy (Wh) Reactive Energy (varh)
Harmonics Current (HI)

Display
AC5A AC1A

Analog Output, Pulse Output


AC5A AC1A

0.5

1.0

0.5

1.0

2.0 1.0 2.0 2.5 2.5

3.0 2.0 2.0

2.0 1.0 2.0 2.5

3.0 2.0 2.0

(RMS Value, 0Rating60)

Harmonics Voltage (HV)

2.5
(Total Distortion Ratio, 020)

Direct Input
3P4W
(Phase Voltage (L-N)/Line Voltage (L-L))

3P3W (Line Voltage) 110V,220V

63.5V/110V, 100V/173V, 110V/190V 220V/380V, 240V/415V, 254V/440V 277V/480V

VT Primary Voltage, CT Primary Voltage


VT60V750kV CT5A30kA

Power Failure Compensation


Setting Value, Max./Min. Value, Active Energy, Reactive Energy is memorized

CE Marking
EMC : EN61326-1/2006 Safety : EN61010-1/2001