Вы находитесь на странице: 1из 7

Chromalox Technical Documents

Technical

Technical Information
Determining Energy Requirements - Air & Gas Heating
Air & Gas Heating
Air and gas heating applications can be divided into two conditions, air or gas at normal atmospheric pressure and air or gas under low to high pressure. Applications at atmospheric pressure include process air, re-circulation and oven heating using duct or high temperature insert air heaters. Pressurized applications include pressurized duct heating and other processes using high pressures and circulation heaters. Procedures for determining heat energy requirements for either condition are similar except the density of the compressed gas and the mass velocity of the ow must be considered in pressurized applications. Selection of equipment in both conditions is critical due to potentially high sheath temperatures that may occur.

Graph G-176S Air Heating


Based on Air Density of 0.08 Lbs/Ft3 and a Specic Heat of 0.237 Btu/Lb/F

150

130

110

600 F R 550 ise 50 F Ri 0F se Ris 45 35 e 40 0 0 0 F FR FR Ri se ise ise


F 0 30
0 25

170

se Ri

Low Temperature Heater Selection A ypical heater selection for the previous example might be a type CAB heater with nstrip elements. Available 15 kW stock heaters include a CAB-1511 with chrome steel elements or a CAB-152 with iron sheath elements, both rated at 26 W/in2. From the product page, the face area of a 15 kW CAB heater is 1.19 ft2: Velocity (fps) = 450 ACFM = 6.3 fps 1.19 ft2 x 60 sec.

Kilowatts

90

ise FR

70

e Ris 0F 20
e Ris F 150
se F Ri 100 Rise 75F ise 50F R

50

Determining Heat Requirements for Atmospheric Pressure Gas Heating


The following formulas can be used to determine kW required to heat air or gas: Equation A kW = CFM x lbs/ft3 x 60 min x Cp x T x SF 3412 Btu/kW Where: CFM = Volume in cubic feet per minute Lbs/ft3 = Density of air or gas at initial temperature Cp = Specic heat of air or gas at initial temperature T = Temperature rise in F SF = Suggested Safety Factor For quick estimates of air heating requirements for inlet temperatures up to 120F, the following formula can be used. kW = SCFM x T x 1.2 SF 3,000 Where: SCFM = Volume of air in cubic feet per minute at standard conditions1 (70 F at standard atmospheric pressure) 3,000 = Conversion factor for units, time and Btu/lb/F 1.2 SF = Suggested safety factor of 20% Graph G-176S When airow (ft3/min) and temperature rise are known, kW requirements can be read directly from graph G-176S. Note Safety factors are not included. Note 1 Based on an average density of 0.08 lbs/ft3 and a specic heat of 0.24 Btu/lb/F. For greater accuracy, use Equation A and values from the Properties of Air Chart in this section. I-16

30

10 10 0 100

300 500 700 900 1100 Air Volume (Cubic Feet Per Minute)

Process Air Heating Calculation Example A drying process requires heating 450 ACFM of air1 from 70F to 150F. The existing duct- work measures 2 ft wide by 1 ft high and is insulated (negligible losses). To nd heating capacity required, use Equation A: kW = 450 ACFM x 0.08 x 60 x 0.24 x 80 x 1.2 SF 3412 Btu/kW kW = 14.58

Estimating Sheath Operating Temperature The maximum operating sheath temperatures for nstrips are 750F for iron and 950F for chrome steel. Using graph G-107S for iron sheath nstrips, a 150F outlet temperature and a watt density of 26 W/in2 requires a velocity in excess of 9 ft/sec to keep sheath temperatures below maximum permissible levels. With only 6.3 fps in the application, a CAB-152 heater with iron sheath elements is not suitable. Using graph G-108S for chrome sheath nstrips, approximately 3 ft/sec. air velocity results in a maximum of 900F sheath temperature. Since this is lower than the actual velocity of 6.3 fps, a CAB-1511 with chrome steel nstrips is an acceptable heater selection. (Use graphs G-100S, G-105S,G106S and G-132S for air heating with regular strip and nstrip heaters.) High Temperature Heater Selection Type TDH and ADHT heaters with tubular elements are recommended for high temperature applications. Steel sheath tubulars may be used where the sheath temperature will not exceed 750F. Finned tubulars can be used in applications up to a maximum sheath temperature of 1050F. INCOLOY sheath tubulars may be used for applications with sheath temperatures up to 1600F. Allowable watt densities for tubulars and nned tubulars can be determined by reference to graphs G-136S and G-151-1 through G-156-1. Estimating Sheath Operating Temperature Select a heater for a high temperature application with an inlet air temperature of 975F and a velocity of 4 ft/sec. Since the temperature is above 750F, an INCOLOY sheath must be used. Using graph G-152-1 the allowable watt density is 11 W/in2 for sheath temperatures of 1200F or 22 W/in2 for temperatures of 1400F. In this application, a stock ADHT heater2 with a standard watt density of 20 W/in2 can be used. Note 2 Special ADHT duct heaters, derated to the required watt density, can be supplied when element ratings less than the standard 20 W/in2 are needed.

Heater Selection
Finstrip (CAB heaters), Fintube (DH heaters) or tubular elements (TDH, ADH and ADHT heaters) will all work satisfactorily in low temperature applications. Finstrips or nned tubular elements are usually the most cost effective. Tubular elements are recommended for high temperatures. Once the desired type of heating element is selected, the next step is to calculate the air velocity and estimate sheath temperatures to verify that maximum operating temperatures are not exceeded. Calculate the air velocity over the elements and refer to allowable watt density graphs for estimated operating temperature. Calculating Air Velocity Air velocity can be calculated from the following formula: Velocity (fps) = Flow (ACFM) Area of Heater (ft2) x 60 sec.

Technical

Technical Information
Allowable Watt Density & Heater Selection - Air Heating
Air & Gas Heating with Strip and Finstrip Heaters
Custom Designs Strip and nstrip heaters are frequently mounted in banks by the end user. Graphs G-105S and G-106S on this page can be used in conjunction with other graphs to determine maximum watt density for virtually any custom design low temperature heating application. Graph G-105S Strip Heaters To use this graph: 1. Select maximum desired outlet air temperature on line A. 2. Choose either chrome steel sheath or rust resisting iron sheath (points B) on the basis of operating conditions. 3. Select minimum anticipated air velocity on B. Note natural circulation is equal to approximately one foot per second. 4. Draw a straight line through points A and B to a reading on C. Read maximum allowable watts per square inch from line C. 5. Select desired length heater with an equivalent watt density or less from the product page in this catalog. Graph G-106S Finstrip Heaters To use this graph: 1. Select maximum desired outlet air temperature on line D. 2. Choose either chrome steel sheath or rust resisting iron sheath (points E) on the basis of operating conditions. 3. Select minimum anticipated air velocity on B. Note natural circulation is equal to approximately one foot per second. 4. Draw a straight line through points D and E to a reading on F. Read maximum allowable watts per square inch from line F. 5. Select desired length heater with an equivalent watt density or less from the product page in this catalog. Recommendations for Custom Installations Strip heaters should always be mounted sideways in the ductwork with the narrow edges facing the air stream. The total number of elements installed should be divisible by 3 so that the heater load will be balanced on a three phase circuit.
Outlet Air Temperature (F) 500 600

Graph G-105S Strip Heater Air Heating-Selection of Watt Density


20 700

Ai .) .S F.P y( 1 cit 4 elo rV 9


15

600 Outlet Air Temperature (F)

16

Chrome Steel Sheath

500
Air

10
Ve lo

400

16

Iron Sheath
300 200 100 0 A

cit

y(

F.P .

S.)

0 B C

Graph G-106S Finstrip Heater Air Heating-Selection of Watt Density


700

30

Chrome Steel Sheath


400

25

20 W/In2 15 10

300

Iron Sheath

200

W/In2

.) P.S (F. ity loc 4 Ve Air 9 1


. F.P S. ) 1

100

0 D E F

I-17

TECHNICAL INFORMATION

16

y( cit elo rV 9 Ai 16 4

Technical

Technical Information
Allowable Watt Density & Heater Selection - Air Heating
Graph G-132S Strip Heater (Iron) Air Heating Allowable Watt Densities for 700F Sheath Temp.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Wattage Rating of Strip Heater = W/In2 x Heated Area Strip Heaters < 30-1/2", Heated Length = Overall Length - 4" Strip Heaters 30-1/2", Heated Length = Overall Length - 5" 1-1/2" Wide Strip Heater = 3.45 in2/in. 16 F. 1" Wide Strip Heater = 2.31 in2/in. P.S. Dist ribu ted 9 F.P. Air S. Vel oci ty 4 F.P. S. 1 F.P.S. or Free Air

Graph G-100S Strip Heater (Chrome) Air Heating Allowable Watt Densities for 1000F Sheath Temp. 26
24 22 20 18 Watts Per Square Inch (W/In2) 16

Watts Per Square Inch (W/In2)

16 F.P .S. Di str ibu 9 F. te d P.S Ai . r

y ci t lo Ve

4 F. P.S .
1 F.P .S. o r

When Calculating Heater Capacity, Use the Maximum Outlet Temperature and the Lowest Air Velocity. For Close Grouping of Heaters, Use 80% of the Calculated Value. 100 200 300 400 Outlet Air Temperature (F)

14 12 10 8 6 4 2 0 0

Free

Air

500

600

700

Graph G-107S Finstrip (Iron Sheath) Air Heating Allowable Watt Densities for 700F Sheath Temp.
32
16

Wattage Rating of Finstrip = W/In2 x 3.60 x Heated Length


F.P .S. Dis trib ute dA ir V elo cit y

28 Watts Per Square Inch (W/In2) 24 20 16 12 8

9 F.P .S.
4 F.P.S .
1 F.P.S

or Free

Air

When Calculating Heater Capacity, Use the Maximum Outlet Temperature and the Lowest Air Velocity. For Close Grouping of Heaters, Use 80% of the Calculated Value. 100 200 300 400 500 600 700 800 900 1000

Outlet Air Temperature (F)

When Calculating Heater Capacity, Use the 4 Maximum Outlet Temperature and the Lowest Air Velocity. For Close Grouping of Heaters, Use only 80% of the Calculated Value 0 0 100 200 300 400 Outlet Air Temperature (F)

500

600

Notes Strip Heaters < 30-1/2", Heated Length = Overall Length - 4" Strip Heaters 30-1/2", Heated Length = Overall Length - 5" 1-1/2" Wide Strip Heater = 3.45 in./in. 1" Wide Strip Heater = 2.31 in./in.

Graph G-108S Finstrip (Chrome Steel) Air Heating Allowable Watt Densities for 900F Sheath Temp.
36 32 Watts Per Square Inch (W/In2) 28 24 20 16 12 8 When Calculating Heater Capacity, Use the 4 Maximum Outlet Temperature and the Lowest Air Velocity. For Close Grouping of Heaters, 0 Use 80% of the Calculated Value. 0 100 200 300 400 500 Outlet Air Temperature (F) 600 700
4 F.P. S.
9 F. P.S.

Graph G-136S Tubular Heater Air Heating


50 Sheath Temperature of Tubular Elements at Various Watt Densities in Free or Forced Air at 80F
16 F.P 9 F .S. .P. S 4F . .P. S. 1F .P. S. St ill Air

Wattage Rating of Finstrip = W/In2 x 3.60 x Heated Length 40 Watts Per Square Inch (W/In2)
16 F.P .S. Dis trib ute d

1 F.P.S.

or Free A

Air

30

ir

Ve loc ity

20

10

0 0 200 400 600 800 1000 Sheath Temperature (F) 1200 1400

I-18

Technical

Technical Information
Allowable Watt Density & Heater Selection - Air Heating
Graph G-151-1 Fintube & Tubular Heaters Sheath Temperatures with 1 FPS Distributed Air Velocity
Watt Density in W/In2 of Effective Length Finned Tubular Units
1400F

Graph G-154-1 Fintube & Tubular Heaters Sheath Temperatures with 16 FPS Distributed Air Velocity
40 Watt Density in W/In2 of Effective Length Finned Tubular Units 35 30
100 0F
120 0F
14 00 F

Limit for Finned Tubular for Normal Life Expectancy

Limit for Finned Tubular for Normal Life Expectancy

40 35 30 Tubular Units Tubular Units Tubular Units 25 20 15 10 5

1200F

Tubular Units

25 20

80 70 60 50 40 30 20 10 0

1000F 910F 800F


600F 400F 200F

15 10 5

200

400 600 800 1000 Outlet Air Temperature (F)

1200

1400

80 70 60 50 40 30 20 10 0

F 700 F 600 F
40

800

0F

20

0 F

200

400 600 800 1000 Outlet Air Temperature (F)

1200

1400

Graph G-152-1 Fintube & Tubular Heaters Sheath Temperatures with 4 FPS Distributed Air Velocity
Watt Density in W/In2 of Effective Length Finned Tubular Units
1400 F

Watt Density in W/In2 of Effective Length Finned Tubular Units

1200F

Limit for Finned Tubular for Normal Life Expectancy

40 35 30

Graph G-155-1 Fintube & Tubular Heaters Sheath Temperatures with 25 FPS Distributed Air Velocity
12 00 F
100 0F
800 F

Limit for Finned Tubular for Normal Life Expectancy

40 35 30 25 20 15 10 5

1000 F

20 15 10 5

80 70 60 50 40 30 20 10 0

840F 800F

Tubular Units

25

600F 400 F 200 F

200

400 600 800 1000 Outlet Air Temperature (F)

1200

1400

80 70 60 50 40 30 20 10 0

640 F 600 F 400 F

20 0

200

400

Graph G-153-1 Fintube & Tubular Heaters Sheath Temperatures with 9 FPS Distributed Air Velocity
Watt Density in W/In2 of Effective Length Finned Tubular Units
1200 F
140 0F

600 800 1000 Outlet Air Temperature (F)

1200

1400

Limit for Finned Tubular for Normal Life Expectancy

40 35

Graph G-156-1 Fintube & Tubular Heaters Sheath Temperatures with 36 FPS Distributed Air Velocity
Watt Density in W/In2 of Effective Length Finned Tubular Units
10 00 F

30 Tubular Units
1000 F

Limit for Finned Tubular for Normal Life Expectancy

40 35 30

25 20 15 10 5

200

400 600 800 1000 Outlet Air Temperature (F)

1200

1400

200

400 600 800 1000 Outlet Air Temperature (F)

1200

1400

I-19

TECHNICAL INFORMATION

80 70 60 50 40 30 20 10 00

840 F 800 F 600 F

80 0F

25 20 15 10 5

400 F 200 F

80 70 60 50 40 30 20 10 0

640 600 F F 40 0F
20 0

Technical

Technical Information
Determining Energy Requirements - Air & Gas Heating
Air & Gas Heating Cryogenics
Industrial gases are usually stored in a liquid state with heat being added to vaporize and boil off the gas as usage requires. General heat equations apply except that pipes, tubes and vessels containing the cryogenic uid or gas frequently represent a heat source rather than a heat loss. If the size and materials of the tanks or vessels are known, then heat calculations for the temperature rise can be performed as in standard vessel heating or boiler problems. The following example is typical of a cryogenic heating application. Problem Vaporize and preheat 30,000 SCFH of liquid Nitrogen (N2) from -345F to 70F at atmospheric conditions. The properties of N2 from Cryogenic Gas Tables are: Boiling point, -320F Specic heat Btu/lb/F = 0.474 (liq.), 0.248 (gas) Latent heat of vaporization = 85.7 Btu/lb Atm. density of N2 at 32F = 0.0784 lb/ft3. Solution Amount of liquid N2 to be vaporized 30,000 SCFH x 0.0784 lb/ft3 = 2,352 lbs/hr 1. Raise liquid from -345F to -320F (boiling point) T = 25F. kW =Wt x Cp x T x SF 3412 Btu/kW Where: Wt = Weight of material in lbs Cp = Specic heat of the liquid N2 T = Temperature rise in F SF = Suggested safety factor of 20% kW = 2,352 lbs x 0.474 x 25 x 1.2 = 9.8 kW 3412 Btu/kW 2. Vaporize the liquid N2 kW =2,352 lbs x 85.7 x 1.2 = 70.9 kW 3412 Btu/kW 3. Raise the temperature of the N2 from boiling point -320F to 70F T = 390F. kW = 2,352 lbs x 0.248 x 390 x 1.2 = 80 kW 3412 Btu/kW Total kW/hr required = 9.8 + 70.9 + 80 = 169.7 Equipment Recommendations Generally, cryogenic applications utilize both a vaporizer unit and a gas preheater. High watt density heaters immersed in the cryogenic uid can be used for the vaporizer. Standard circulation heaters and watt densities are recommended for gas preheating. Protect the heater terminals from frost and moisture with element seals and liquid tight terminal covers. I-20 Material Recommendations Ordinary carbon steel is subject to brittle fracture at temperatures below -20F and is generally not recommended. Stainless steel, high nickel bearing alloys or aluminum alloys may be used. Use Teon for gaskets asTeon remains pliable at low temperatures. 4. Total kW = 2.86 + 0.47 + 0.70 = 4.03 kW 5. For Oven Applications, add 30% to cover door losses and other contingencies. kWh required (including safety factor) is kWh = kW = 4.03 kW = 5.37 kW x 1.3 = 6.98 kW t 0.75 hrs Equipment Recommendations Several process air heaters, including strip heaters, nstrips, bare tubulars or type OV oven heaters, are suitable for oven heating applications.

Air & Gas Heating Batch Ovens


Most oven applications consist of heating work product inside an insulated enclosure. Heat loss calculations involve the determination of the heat requirements to heat the enclosure and work product using heated air circulated by natural or forced convection. Any make up or ventilation air must also be considered. The following example outlines the calculation of the heat required for a typical oven heating application. Problem An oven with inside dimensions of 2 ft H x 3 ft W x 4 ft D is maintained at 350F. The oven has sheet steel walls with 2 inches of insulation and is ventilated with 400 cfh (ft3/hr) of 70F air which exhausts to the outside to remove fumes. The oven is charged with 250 lbs of coated steel parts on a steel tray weighing 40 lbs. The process requires the parts to be heated from 70F to 350F in 3/4 hour. Weight of steel = 290 lbs Specic heat of steel 0.12 Btu/lb/F Weight of air = 0.080 lbs/ft3 at 70F Specic heat of air = 0.24 Btu/lb/F Temperature rise = 280F Surface losses with 2 inch insulation = 18 W/ ft2/hr at 280F temperature difference (Graph G-126S) Surface area of oven = 52 ft2 Time = 3/4 hr (0.75) Airow rate = 400 ft3/hr Solution 1. Calculate kWh required to heat metal. kW = 290 lbs x 0.12 Btu/lb/F x 280F = 2.86 kW 3412 Btu/kW 2. Calculate kWh required to heat ventilated air kW=400 cfh x 0.080 Lbs x 0.24 Cp x 280 T x 0.75 t = 0.47kW 3412 Btu/kW Where: cfh = Air ow rate (400) Lbs/ft3 = Density of air (0.080) Cp = Specic heat of air (0.24) T = Temperature rise (280) = Time in hours (0.75) 3. Calculate surface losses. Since the oven is already at temperature, losses are at full value. kW = 18 W/ft2/hr x 52 ft2 area x 0.75 hr = 0.70 kW 1,000 W/kW

Pressure Drop for Process Air Heaters


The pressure drop through TDH and ADH process air heaters with bare tubular or nned tubular elements, CAB heaters with nstrip elements, and ADH and DH air heaters with nned tubular elements will vary considerably depending on product design and construction. Chromalox sales engineering can provide pressure drop calculations for virtually any duct heater (or circulation heater) application. Graphs G-112S3, G-189S1, G-227-2, and G-227ADH on the following page provide guidance for estimating the pressure drop for many Chromalox process air heaters1. Graph G-189S1 can be used for most nned tubular applications providing the elements are mounted in a three or six row conguration. Transitions in Ducts In some air distribution systems, the duct heater may be considerably larger or smaller than the associated ductwork. The duct heater can be adapted to different size ductwork by installing a sheet metal transition. The transition must be designed so that the slope on the upstream side of the equipment is limited to 30 (see below). On the leaving side, the slope should not be more than 45. Note 1 Contact the factory for pressure drop calculations for duct heaters mounted lengthwise or in series and for GCH gas circulation heaters. These applications require special calculations for proper application and air handler sizing.

Recommended Dimensions for Duct Transitions


30 Max. 45 Max.

Air Flow

30 Max.

45 Max.

Technical

Technical Information
2.0 1.0 Pressure Drop Inches of Water (Psi = Inches of Water x 0.0361) 0.7 Air Flow 0.5 0.3 ADH or ADHT Mounted Crosswise in Duct

Determining Pressure Drop - Air and Gas Heating


Graph G-227ADH Pressure Drop Vs. Velocity ADH and ADHT Tubular Element Air Heaters
H " AD 9.5 M= T H .5" AD M=9 ADH
5" 8.37 M=1

Graph G-112S3 Pressure Drop Vs. Velocity Finstrip and CAB Air Heaters
1.0 0.5 0.3 Based on 1-5/8" spacing and 4.7 ns per linear inch Triple Row Double Row Single Row

Pressure Drop Inches of Water (Psi = Inches of Water x 0.0361) 0 0 5 fps 10 fps 300 fpm 600 fpm

0.1 0.07 0.05 0.03

0.1 0.07 0.05 0.03

0.01 0.007 0.005 0.003

0.01 15 fps 20 fps 25 fps 30 fps 35 fps 900 fpm 1200 fpm 1500 fpm 1800 fpm 2100 fpm Air Velocity (Std. Air) Note Contact factory for pressure drop calculations for ADH/ADHT air heaters mounted lengthwise in duct and ADHT heaters where M is greater than 9.5"

Graph G-189S1 Pressure Drop Vs. Velocity Fintube Elements and Air Heaters
0.7 Pressure Drop Inches of Water (Psi = Inches of Water x 0.0361) Finned Tubulars Mounted 0.5 Crosswise in Duct 0.3 Air Flow 0.1 0.07 0.05 Pressure Drop Inches of Water (Psi = Inches of Water x 0.0361) 0.03

0.001 0 0 5 fps 10 fps 300 fpm 600 fpm 15 fps 20 fps 25 fps 30 fps 35 fps 900 fpm 1200 fpm 1500 fpm 1800 fpm 2100 fpm Air Velocity (Std. Air)

" .375 =18 M s Row " Six =9.5 sM w o R ee Thr

Graph G-227-2 Pressure Drop Vs. Velocity TDH Tubular Element Air Heaters
0.20 0.18
TDH Mounted Lengthwise in Duct Air Flow

0.16 0.14 0.12 0.10 0.08 0.06 0.04 0.02 0 0 0

0.01 0 0 5 fps 10 fps 300 fpm 600 fpm 15 fps 20 fps 25 fps 30 fps 35 fps 900 fpm 1200 fpm 1500 fpm 1800 fpm 2100 fpm

Approximate Terminal Box Temperature (F)

500 400 300 200 100 0 0 200 Data only valid for ADH or ADHT air heaters installed in bottom or sides of duct 400 600 800 1000 1200 Outlet Air Temperature (F)

H AD

rs ate He r i A

s eater Air H T H D A

5 fps 10 fps 300 fpm 600 fpm

Th re e

600

Row

Graph ADHTB ADH/ADHT Terminal Box Temperatures Field Wiring Selection Guide

sC ro

s sw i se

Air Velocity (Std. Air) Note Contact factory for pressure drop calculations for nned tubular element air heaters mounted lengthwise in duct.

A ny

R a ti

ng

15 fps 20 fps 25 fps 30 fps 35 fps 900 fpm 1200 fpm 1500 fpm 1800 fpm 2100 fpm

I-21

TECHNICAL INFORMATION

Air Velocity (Std. Air)

eT DH -24 Le ng thw ise TD H18 Le ng thw ise TD H12


T ise thw g n Le
6 DH-

TDH-6 TDH-12 TDH-18 TDH-24 TDH Mounted Crosswise in Duct Air Flow

Len

gth

wis

Technical

Technical Information
Determining Energy Requirements - Air & Gas Heating
Air & Gas Heating with Circulation Heaters
To calculate the heat energy requirements for heating compressed air or gases, the rst step is to determine the ow rate in pounds per hour. If the density of the air or gas under the actual pressure is known, the kW requirements can be calculated directly. The following example illustrates this procedure. SCFM = 45 x (35 + 14.7) x (70 + 460) 14.7 psia (50 + 460) SFCM = 158.1 ft3/min Using the calculated SCFM in place of ACFM in equation A, the kW required is: kW = 158.1 x 0.073 x 60 x 0.2438 x (300 - 50) x 1.2 3412 kW = 14.8 kW

Chart 236 Circulation Heaters Free Internal Cross Sectional Area


Pipe Body Nom. IPS (Std.) 2 3 5 8 10 12 14 16 18 Total Area (Ft2) 0.023 0.051 0.139 0.355 0.566 0.785 0.957 1.268 1.622 Free Area (Ft2) 0.018 0.044 0.124 0.303 0.481 0.696 0.847 1.091 1.357 No. 0.475" Elements 2 3 6 18 27 36 45 72 108

Example Heat 20 ACFM of air at 30 psig from Determining Maximum Sheath 60F to 210F. From the Properties of Air Chart, & Chamber Temperatures the density of air at 60F and 30 psig is 0.232 When heating air or gases in insulated pipe lb/ft3 with a specic heat of 0.24 Btu/lb/F. The kW required can be calculated from the formula: chambers or circulation heaters, the pipe wall temperature will normally exceed the outlet kW = ACFM x lbs/ft3 x 60 min x Cp x T x SF gas temperature. Excessively high wall and/or 3412 Btu/kW sheath temperatures can create an unsafe or dangerous condition. Maximum sheath and Where: chamber temperatures can be estimated using 3 ACFM = Actual ow in ft /min at inlet the mass velocity of the gas and Graph G-237. temperature and gauge pressure (psig) In the above air heating example, assume a 3 Lbs/ft = Actual density at inlet temperature 4.5 kW Series 3 heater rated 23 W/in2 has and gauge pressure (psig) been selected. From Chart 236, the free cross Cp = Specic heat of air or gas at inlet sectional area of a Series 3 (3 inch) heater is temperature and gauge pressure (psig) 0.044 ft2. Calculate mass velocity from the T = Temperature rise in F following equation: SF = Suggested Safety Factor kW = 20 x 0.232 x 60 x 0.24 x (210 - 60F) x 1.2 3412 kW = 278.4 lbs/hr x 24 x 150 x 1.2 = 3.52 kW 3412 When the density and specic heat of a gas at a specic temperature and pressure are unknown, the actual ow rate can be converted to a known pressure and temperature using the physical laws of gases. Example Heat 45 ACFM of Nitrogen (N2) at 35 psig from 50F to 300F. From the Physical and Thermodynamic Properties of Common Gases Chart, the density of Nitrogen at 70F is 0.073 lb/ft3 with a specic heat of 0.2438 Btu/lb/F. Convert 45 ACFM at 35 psig and 50F to SCFM of Nitrogen at 70F using the following formula: SCFM = ACFM x Actual psia x Standard T 14.7 psia Actual T SCFM = Std. ft3/min at 14.7 psia and 70F ACFM = Actual ow in ft3/min at inlet temperature and gauge pressure (psig) Actual psia = gauge pressure in lb/in2 + 14.7 psia 14.7 psia = absolute pressure in lb/in2 T = Rankine (F + 460) I-22 Mass Velocity = Flow lbs/hr 3,600 sec (lbs/ft2/sec) Free area ft2 hr Mass Velocity = 278 lbs/hr 3,600 sec 0.044 ft2 hr

Mass Velocity = 1.75 lbs/ft2/sec On Graph G-237, locate the mass velocity (1.75) on the horizontal axis. From that point, locate a 23 W/in2 curve. Read across to the vertical axis (sheath temperature rise above outlet temperature) to 880F. Adding 880F + 210F (outlet temp.) = 1090F sheath temperature. Averaging the sheath and outlet temperatures (1090F + 210F 2), yields a maximum chamber temperature of 650F. Since the maximum chamber wall temperature is less than 750F, a stock GCH heater with a carbon steel vessel and INCOLOY elements rated 23 W/in2 can be used.

Graph G-237 Sheath Temperature Vs. Mass Velocity


1400

1200 Maximum Sheath Temperature Rise Above Outlet Gas Temp. (F)

30
28

W / In 2

1000 Not Recommended

800

600

400

200

W 25 /In 2 W/ 2 3 In 2 W 2 0 / In 2 W/ 1 8 In 2 W/ I 15 n 2 W/ In 2 12 W /I n2 9W /In 2 6W /I n 2 3W /In 2

0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 Mass Velocity (Lbs/Ft2/Sec)

Вам также может понравиться