Armoured Power Cables, 600/1000V BS5467

BS 5467 Armoured Power Cables, 600/1000V


Application
These cables are used for power and control circuits, they can offer excellent protection through the use
of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside
buildings or for direct burial in the ground.

Construction
Conductor

Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS


6460, IEC 60228.

Insulation

XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6)

Colour Code

1 Core : Brown
2 Cores: Brown or Blue
3 Cores: Brown, Black, Grey
4 Cores: Blue, Brown, Black, Grey
5 Cores: Green/Yellow, Blue, Brown, Black, Grey
Above 5 Cores: White Cores with black numbers

Bedding

PVC (Polyvinyl Chloride)

Armour

Single Core: AWA (Aluminum Wire Armour)


Multi Core: SWA (Steel Wire Armour)

Outer Sheath

PVC(Polyvinyl Chloride), or anti-rodent and anti-termite PVC(optional)

Technical Information
Voltage rating

600/1000V

Temperature rating 0C to +90C


Bending radius

1.5mm to 16mm: 6 x overall diameter

25mm and above: 8 x overall diameter

Flame retardant

IEC60332 part 1, BS4066 part 1

www.caledonian-cables.co.uk

www.caledonian-cables.com

Addison Cables
BS5467 Armoured Power Cables, 600/1000V
Cable Parameter
Single-core 600/1000 V cables with circular stranded copper conductor
PVC bedding
XLPE insulation
Plain copper conductor
Aluminum wire armour
PVC jacket
Nominal
Crosssectional
Area
mm

Strand
Type

Nominal
Insulation
thickness

Nominal
bedding
thickness

Nominal
Alum
Wire dia.

Nominal
Sheath
thickness

Approx.
Overall
Diameter

Aprrox
Weight

No./mm

mm

mm

mm

mm

mm

kg/km

1x50

19/1.78

1.0

0.8

0.9

1.5

17.5

800

1x70

19/2.14

1.1

0.8

1.25

1.5

20.2

990

1x95

19/2.52

1.1

0.8

1.25

1.6

22.3

1280

1x120

37/2.03

1.2

0.8

1.25

1.6

24.2

1550

1x150

37/2.25

1.4

1.6

1.7

27.4

1900

1x185

37/2.52

1.6

1.6

1.8

30.0

2320

1x240

61/2.25

1.7

1.6

1.8

32.8

2930

1x300

61/2.52

1.8

1.6

1.9

35.6

3580

1x400

61/2.85

2.0

1.2

2.0

2.0

40.5

4600

1x500

61/3.20

2.2

1.2

2.0

2.1

44.2

5680

1x630

127/2.52

2.4

1.2

2.0

2.2

48.8

7160

1x800

127/2.85

2.6

1.4

2.5

2.4

55.4

9315

1x1000

127/3.20

2.8

1.4

2.5

2.5

60.6

11490

Single-core 600/1000 V cables with solid aluminum conductor


PVC bedding
XLPE insulation
Aluminum conductor
Aluminum wire armour
PVC jacket

www.addison-tech.com

www.addison-cables.com

Caledonian Cables
Armoured Power Cables, 600/1000V BS5467

Nominal
Crosssectional
Area
mm

Nominal Nominal Nominal


Insula- bedding
Alum
tion
Wire
thickthickArmor
ness
ness
dia.
mm
mm
mm

thickness
mm

width

Nominal
Sheath
thickness

mm

mm

Armour strip

Approx.
Overall
Diameter
wire
strip
armor armor
mm
mm

Aprrox
Weight
kg/km

1x50

1.0

0.8

0.9

0.6

2.4

1.5

16.3

15.7

460

1x70

1.1

0.8

1.25

0.6

2.4

1.5

18.7

17.4

560

1x95

1.1

0.8

1.25

0.6

2.4

1.6

20.6

19.3

690

1x120

1.2

0.8

1.25

0.6

2.4

1.6

22.1

20.8

800

1x150

1.4

1.6

0.6

2.4

1.7

25.2

23.2

970

1x185

1.6

1.6

0.6

2.4

1.8

27.4

25.4

1150

1x240

1.7

1.6

3.6

1.8

29.9

28.7

1380

1x300

1.8

1.6

3.6

1.9

32.4

31.2

1640

Two-core 600/1000 V cables with stranded copper conductors


PVC bedding
XLPE insulation
Plain copper conductor
Steel wire armour
PVC jacket

Nominal
Sheath
thickness

Extruded
bedding

Taped
bedding

mm

Nominal
Steel
Wire
Armor
dia.
mm

mm

mm

mm

kg/km

0.6

0.8

0.9

1.4

12.1

320

7/0.67

0.7

0.8

0.9

1.4

13.6

365

2x4

7/0.85

0.7

0.8

0.9

1.4

14.7

440

2x6

7/1.04

0.7

0.8

0.9

1.4

15.9

470

2x10

7/1.35

0.7

0.8

0.9

1.5

18.0

800

2x16

7/1.70

0.7

0.8

1.25

1.5

20.4

20.4

900

2x25

7/2.14

0.9

0.8

1.25

1.6

24.1

24.1

1240

2x25*

7/2.14

0.9

0.8

1.25

1.6

20.4

20.4

1240

2x35

7/2.52

0.9

1.6

1.7

27.7

27.3

1710

2x35*

7/2.52

0.9

1.6

1.7

23.3

22.9

1710

Nominal
Crosssectional
Area

Strand
Type

Nominal
Insulation
thickness

Nominal
bedding
thickness

mm

No./mm

mm

2x1.5

7/0.53

2x2.5

www.caledonian-cables.co.uk

www.caledonian-cables.com

Approx. Overall
Diameter

Aprrox
Weight

Addison Cables
BS5467 Armoured Power Cables, 600/1000V

Nominal
Sheath
thickness

Extruded
bedding

Taped
bedding

mm

Nominal
Steel
Wire
Armor
dia.
mm

mm

mm

mm

kg/km

1.0

1.6

1.8

25.8

25.4

1800

19/2.14

1.1

1.6

1.9

29.0

28.6

2320

2x95*

19/2.52

1.1

1.2

2.0

2.0

33.1

32.3

3150

2x120*

37/2.03

1.2

1.2

2.0

2.1

36.1

35.3

3880

2x150*

37/2.25

1.4

1.2

2.0

2.2

39.3

38.5

4820

2x185*

37/2.52

1.6

1.4

2.5

2.4

44.7

43.5

5920

2x240*

61/2.25

1.7

1.4

2.5

2.5

49.0

47.8

7300

2x300*

61/2.52

1.8

1.6

2.5

2.6

53.5

51.9

8770

2x400*

61/2.85

1.6

2.5

2.8

59.0

57.4

10905

Nominal
Crosssectional
Area

Strand
Type

Nominal
Insulation
thickness

Nominal
bedding
thickness

mm

No./mm

mm

2x50*

19/1.78

2x70*

Approx. Overall
Diameter

Aprrox
Weight

* D-Shaped stranded conductor (class 2)

Two-core 600/1000 V cables with solid aluminum conductors


PVC bedding
XLPE insulation
Aluminum conductor
Steel wire armour
PVC jacket
Armour strip Nominal
Nominal Nominal
Nominal Nominal
InsulaSteel
Crossbedding
Sheath
tion
Wire
thick- width
sectional
thickthickthickArmor
ness
Area
ness
ness
ness
dia.
mm
mm
mm
mm
mm
mm
mm

Approx. Overall Diameter


wire armor
Extruded
Taped
bedding bedding
mm
mm

strip
armor
mm

kg/km

2x16

0.7

0.8

1.25

0.6

2.4

1.5

19.1

19.1

17.8

650

2x25

0.9

0.8

1.25

0.6

2.4

1.5

22.4

22.4

21.1

915

2x25*

0.9

0.8

1.25

0.6

2.4

1.6

18.7

18.7

17.4

1255

2x35

0.9

1.6

0.6

2.4

1.6

25.7

25.3

23.3

1255

2x35*

0.9

1.6

0.6

2.4

1.7

21.4

21.0

19

1430

2x50*

1.0

1.6

0.6

2.4

1.8

23.5

23.1

21.1

1430

2x70*

1.1

1.6

3.6

1.9

26.3

25.9

24.7

1780

2x95*

1.1

1.2

2.0

3.6

30

29.2

27.2

1950

*Solid shaped conductor (class 1)

Aprrox
Weight

www.addison-tech.com

www.addison-cables.com

Caledonian Cables
Armoured Power Cables, 600/1000V BS5467
Three-core 600/1000 V cables with stranded copper conductors
PVC bedding
XLPE insulation
Plain copper conductor
Steel wire armour
PVC jacket

Nominal
Crosssectional
Area

Nominal Nominal
Steel
Sheath
Wire
thickArmor
ness
dia.
mm
mm

Strand
Type

Nominal
Insulation
thickness

Nominal
Bedding
thickness

mm

No./mm

mm

mm

3x1.5

7/0.53

0.6

0.8

0.9

3x2.5

7/0.67

0.7

0.8

3x4

7/0.85

0.7

3x6

7/1.04

3x10

Approx. Overall
Diameter

Aprrox
Weight

Extruded
bedding

Taped
bedding

mm

mm

kg/km

1.3

12.6

340

0.9

1.4

14.1

408

0.8

0.9

1.4

15.3

498

0.7

0.8

0.9

1.4

16.6

600

7/1.35

0.7

0.8

1.25

1.5

19.5

915

3x16

7/1.70

0.7

0.8

1.25

1.6

21.6

21.6

1130

3x25

7/2.14

0.9

1.6

1.7

26.7

26.3

1710

3x25*

7/2.14

0.9

1.6

1.7

23.6

23.2

1710

3x35

7/2.52

0.9

1.6

1.8

29.4

29.0

2100

3x35*

7/2.52

0.9

1.6

1.8

25.7

25.3

2100

3x50*

19/1.78

1.0

1.6

1.8

28.5

28.1

2450

3x70*

19/2.14

1.1

1.6

1.9

32.2

31.8

3120

3x95*

19/2.52

1.1

1.2

2.0

2.1

37.0

36.2

4310

3x120*

37/2.03

1.2

1.2

2.0

2.2

40.4

39.6

5160

3x150*

37/2.25

1.4

1.4

2.5

2.3

45.5

44.3

7160

3x185*

37/2.52

1.6

1.4

2.5

2.4

49.8

48.6

8600

3x240*

61/2.25

1.7

1.4

2.5

2.6

55.1

53.9

10755

3x300*

61/2.52

1.8

1.6

2.5

2.7

60.2

58.6

13080

3x400*

61/2.85

1.6

2.5

2.9

66.6

65.0

15810

*Shaped stranded conductor (class 2)

www.caledonian-cables.co.uk

www.caledonian-cables.com

Addison Cables
BS5467 Armoured Power Cables, 600/1000V
Three-core 600/1 000 V cables with solid aluminum conductors
PVC bedding
XLPE insulation
Aluminum conductor
Steel wire armour
PVC jacket
Nominal Nominal
Nominal Nominal
InsulaSteel
Crossbedding
tion
Wire
sectional
thickthickArmor
Area
ness
ness
dia.
mm
mm
mm
mm

Armour strip
thickness

Nominal
Sheath
thickwidth
ness

mm

mm

mm

Approx. Overall Diameter


wire armor
Extruded
Taped
bedding bedding
mm
mm

strip
armor

Aprrox
Weight

mm

kg/km

3x16

0.7

0.8

1.25

0.6

2.4

1.6

20.3

20.3

19

760

3x25

0.9

1.6

0.6

2.4

1.7

22.5

22.1

20.1

1020

3x25*

0.9

1.6

0.6

2.4

1.7

24.9

24.5

22.5

1020

3x35

0.9

1.6

0.6

2.4

1.8

24.4

24.9

22

1200

3x35*

0.9

1.6

0.6

2.4

1.8

27.3

26.9

24.9

1200

3x50*

1.0

1.6

0.6

2.4

1.8

26.8

26.4

24.9

1380

3x70*

1.1

1.6

3.6

1.9

30.2

29.8

28.6

1750

3x95*

1.1

1.2

2.0

3.6

2.1

34.8

34.0

32

2420

3x120*

1.2

1.2

2.0

1.4

4.8

2.2

37.8

37.0

35.8

2820

3x150*

1.4

1.4

2.5

1.4

4.8

2.3

42.7

41.5

39.3

3660

3x185*

1.6

1.4

2.5

1.4

4.8

2.4

46.7

45.5

43.3

4350

3x240*

1.7

1.4

2.5

1.4

4.8

2.6

51.5

50.3

48.1

5220

3x300*

1.8

1.6

2.5

1.8

6.4

2.7

56.2

54.6

53.2

6200

*Solid shaped conductor (class 1)

10

www.addison-tech.com

www.addison-cables.com

Caledonian Cables
Armoured Power Cables, 600/1000V BS5467
Four-core 600/1000 V cables with stranded copper conductors
PVC bedding
XLPE insulation
Plain copper conductor
Steel wire armour
PVC jacket

Nominal
Sheath
thickness

Extruded
bedding

Taped
bedding

mm

Nominal
Steel
Wire
Armor
dia.
mm

mm

mm

mm

kg/km

0.7

0.8

0.9

1.4

13.3

390

7/0.67

0.7

0.8

0.9

1.4

15.0

470

4x4

7/0.85

0.7

0.8

0.9

1.4

16.4

580

4x6

7/1.04

0.7

0.8

1.25

1.5

18.7

805

4x10

7/1.35

0.7

0.8

1.25

1.5

21.1

1090

4x16

7/1.70

0.7

0.8

1.25

1.6

23.4

23.4

1320

4x25

7/2.14

0.9

1.6

1.7

28.9

28.5

1840

4x25*

7/2.14

0.9

1.6

1.7

26.1

25.7

1840

4x35

7/2.52

0.9

1.6

1.8

31.9

31.5

2310

4x35*

7/2.52

0.9

1.6

1.8

28.6

28.2

2310

4x50*

19/1.78

1.0

1.6

1.9

32.0

31.6

2970

4x70*

19/2.14

1.1

1.2

2.0

2.1

37.7

36.9

4240

4x95*

19/2.52

1.1

1.2

2.0

2.2

41.7

40.9

5400

4x120*

37/2.03

1.2

1.4

2.5

2.3

47.1

45.9

7000

4x150*

37/2.25

1.4

1.4

2.5

2.4

51.4

50.2

8350

4x185*

37/2.52

1.6

1.4

2.5

2.6

56.6

55.4

10130

4x240*

61/2.25

1.7

1.6

2.5

2.7

63.0

61.4

12840

4x300*

61/2.52

1.8

1.6

2.5

2.9

68.8

67.2

15530

4x400*

61/2.85

1.8

3.15

3.2

78.1

76.1

19950

Nominal
Crosssectional
Area

Nominal Nominal
Insulation bedding
thickthickness
ness

Strand
Type

mm

No./mm

mm

4x1.5

7/0.53

4x2.5

Approx. Overall
Diameter

Aprrox
Weight

* Shaped stranded conductor (class 2)

www.caledonian-cables.co.uk

www.caledonian-cables.com

11

Addison Cables
BS5467 Armoured Power Cables, 600/1000V
Four-core 600/1000 V cables with solid aluminum conductors
PVC bedding
XLPE insulation
Aluminum conductor
Steel wire armour
PVC jacket
Nominal Nominal
Nominal Nominal
InsulaSteel
Crossbedding
tion
Wire
sectional
thickthickArmor
Area
ness
ness
dia.
mm
mm
mm
mm

Armour strip
thickness

width

mm

mm

Nominal Approx. Overall Diameter


Sheath
wire armor
strip
thickExtruded
Taped
armor
ness
bedding bedding
mm
mm
mm
mm

Aprrox
Weight
kg/km

4x16

0.7

0.8

1.25

0.6

2.4

1.6

21.8

21.8

20.5

980

4x25

0.9

1.6

0.6

2.4

1.7

26.9

26.5

24.5

1220

4x25*

0.9

1.6

0.6

2.4

1.7

24.6

24.2

22.2

1220

4x35

0.9

1.6

0.6

2.4

1.8

29.5

29.2

27.1

1420

4x35*

0.9

1.6

0.6

2.4

1.8

27

26.6

24.6

1420

4x50*

1.0

1.6

2.4

1.9

30

29.6

28.4

1770

4x70*

1.1

1.2

2.0

3.6

2.1

35.3

34.5

32.5

2500

4x95*

1.1

1.2

2.0

1.4

3.6

2.2

39

38.2

37

2980

4x120*

1.2

1.4

2.5

1.4

4.8

2.3

44

42.8

40.6

3950

4x150*

1.4

1.4

2.5

1.4

4.8

2.4

47.9

46.7

44.5

4600

4x185*

1.6

1.4

2.5

1.4

4.8

2.6

52.7

51.5

49.3

5430

4x240*

1.7

1.6

2.5

1.8

4.8

2.7

58.5

56.9

55.5

6660

4x300*

1.8

1.6

2.5

1.8

6.4

2.9

63.8

62.2

60.8

7770

*Solid shaped conductor (class 1)

Five-core 600/1000 V cables with stranded copper conductors


PVC bedding
Plain copper conductor
XLPE insulation
Steel wire armour
PVC jacket

12

www.addison-tech.com

www.addison-cables.com

Caledonian Cables
Armoured Power Cables, 600/1000V BS5467

Nominal
Crosssectional
Area

Strand
Type

mm
5x1.5
5x2.5
5x4
5x6
5x10
5x16
5x25
5x35
5x50
5x70

No./mm
7/0.53
7/0.67
7/0.85
7/1.04
7/1.35
7/1.70
7/2.14
7/2.52
19/1.78
19/2.14

Nominal Nominal
Insulation bedding
thickthickness
ness
mm
0.6
0.7
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1

mm
0.8
0.8
0.8
0.8
0.8
1
1
1
1.2
1.2

Nominal
Steel
Wire
Armor
dia.
mm
0.9
0.9
0.9
1.25
1.25
1.6
1.6
1.6
2
2

Approx. Overall
Diameter

Nominal
Sheath
thickness

Extruded
bedding

Taped
bedding

mm
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.9
2
2.2

mm
14.3
16.1
17.8
20
22.9
26.6
31.5
34.8
40.4
46.3

mm
26.2
31.1
34.4
39.6
45.5

Aprrox
Weight
kg/km
430
545
680
840
1105
1450
2245
2840
3895
5145

Multi-core 600/1000 V cables with stranded copper conductors


Nominal
Crosssectional
Area
mm
7x1.5
12x1.5
19x1.5
27x1.5
37x1.5
48x1.5
7x2.5
12x2.5
19x2.5
27x2.5
37x2.5
48x2.5
7x4
12x4
19x4
27x4
37x4
48x4

Strand
Type

Nominal
Insulation
thickness

Nominal
bedding
thickness

Nominal
Steel Wire
Armor dia.

Nominal
Sheath
thickness

Approx.
Overall
Diameter

Aprrox
Weight

No./mm
7/0.53
7/0.53
7/0.53
7/0.53
7/0.53
7/0.53
7/0.67
7/0.67
7/0.67
7/0.67
7/0.67
7/0.67
7/0.85
7/0.85
7/0.85
7/0.85
7/0.85
7/0.85

mm
0.6
0.6
0.6
0.6
0.6
0.6
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7

mm
0.8
0.8
0.8
1
1
1
0.8
0.8
1
1
1
1.2
0.8
1
1
1
1.2
1.2

mm
0.9
1.25
1.25
1.6
1.6
1.6
0.9
1.25
1.6
1.6
1.6
2
1.25
1.6
1.6
1.6
2
2

mm
1.4
1.5
1.6
1.7
1.7
1.8
1.4
1.6
1.7
1.8
1.8
2
1.5
1.6
1.7
1.9
2
2.1

mm
15.2
19.4
22.2
26.7
29
32.7
17.1
22.4
26.6
30.7
33.8
39.3
19.7
25.7
29.3
34.4
39.2
44.1

kg/km
500
820
1080
1550
1850
2250
730
1020
1530
1960
2450
3260
840
1390
1850
2350
2800
3250

www.caledonian-cables.co.uk

www.caledonian-cables.com

13