GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

CATALOGUE
ELECTRAK EXPORT
TM

2010/12

P. 14 Selection chart

Power track

P. 16 Electrak 24 standard system (white)

Floor boxes and grommets

P. 28 Empty boxes and accessory plates selection chart

P. 29 Pre-wired boxes selection chart

RotasocTM desk modules

P. 38 NEW Standard power distribution

P. 40 NEW Low noise / clean earth power distribution

IntersocTM desk modules

P. 54 NEW Under-desk modular system

P. 57 International under-desk modules

Busbar / buscom

P. 70 Busbar / buscom trunking selection charts

P. 74 Busbar / buscom trunking tap-offs selection charts

Lighting control

P. 68 Introduction to lighting control

P. 94 KNX lighting control system

Catalogue number index P. 102

Index of protection IP-IK P. 104

P. 17 Electrak 25 low noise / clean earth system (light green)

P. 18 Electrak 26 dual circuit system (dark green)

P. 19 Electrak 27 3 phase system (grey)

P. 20 Electrak 28 auxiliary earth system (red)

P. 30 2 and 3 compartment boxes

P. 31 4 compartment boxes

P. 32 Slab floor boxes

NEW P. 32 Floor grommets

P. 42 NEW Dual circuit power distribution

P. 44 Communications distribution

P. 45 Horizontal desktop units

P. 45 Vertical desktop units

P. 59 16 A popular starter modules

P. 60 16 A popular starter modules add-on options

P. 61 Horizontal desktop units

P. 61 Vertical desktop units

P. 76 Electrak 30 2P + E system

P. 78 Electrak 31 3P + E system

P. 80 Electrak 32 dual circuit system

P. 82 Electrak 33 3 phase system

P. 95 KNX sub-cabling and switching devices

P. 96 NEW Distribution box for DALI lighting installations

P. 96 Tap-offs for use with distribution box

P. 97 System components and tap-off units

Together, let's try to make

1+1+1 +1+1= LESS


SUSTAINABILITY COMMITMENT From design through to manufacturing, the Legrand Group favours materials and processes that respect people and the environment. By doing so, the Group reduces the impact of its activities whilst reinforcing its economic performance and the attractiveness of its products and services. The Legrand Groups commitment to reducing greenhouse gas emissions and its impact on the environment can be demonstrated at three levels... Management of manufacturing and logistics sites Efcient and environmentally aware product design Product functions that help to avoid energy waste
2

ELECTRAKTM LIGHTING CONTROL SYSTEM

ensuring the right level of light when and where it's needed

energy saving

Typically, up to 20% of a building's electricity bill can be attributed to lighting. Lightrak is an energy efcient lighting control solution. All parts are supplied pre-wired and pre-commissioned, making the system easy to install which means less time on site.

PRESENCE DETECTION Saves energy and ensures that lighting is only on when needed

TIMED EVENT CONTROLLER Operates across building and is programmed to optimise energy savings

BENEFITS Labour efcient. Pre-wired and pre-commissioned Energy efcient. Presence detection and auto-switching Fast, easy installation. Clip on / plug in Interface with other building control systems Fully addressable. Switching, dimming, corridor hold Load shed and emergency lighting test facilities Comprehensive design and commissioning service

nd out more at www.legrandgroup.com


3

Specialists in power distribution throughout the workplace


Electrak, part of the Legrand Group, is a leading manufacturer of power distribution and lighting control solutions. Its power track, floor boxes, grommets and desk module ranges are installed in high specification offices around the world. Electraks products can be broken down into two simple ranges: Office power Power track, floor boxes, grommets, desk units Lighting control Buscom/busbar trunking and Lightrak lighting control

Complete solutions for every building


The Legrand Group is the global specialist in electrical and digital building infrastructures. Legrands complete offer, tailored to commercial, industrial and residential markets, is sold in more than 180 countries around the world. Control and monitoring of installations, cable management, power distribution, distribution of voice-data-image systems Legrand has numerous solutions for managing lighting, heating, energy, networks and access in buildings. With a presence in more than 70 countries and a workforce of close to 30,000 people, Legrand made sales of 3.57 billion euros in 2009. Close to 60% of these sales were made in the commercial and industrial business sectors, with 60% of the Groups business also coming from maintenance and renovation projects.

FIND OUT MORE ABOUT ELECTRAK :


/// Website : for information about Electraks power distribution and lighting control solutions, visit www.electrak.co.uk /// Contact us : for any questions about Electraks product ranges, tel : + 44 (0) 845 600 6266 email : powersales.uk@legrand.co.uk

Offices

FIND OUT MORE ABOUT LEGRAND :


/// Website : for information about the Legrand Group Worldwide, visit www.legrandgroup.com

Car park

PRODUCTS AND SYSTEMS I

Rotasoc under-desk modules See page 38

Intersoc desktop modules See page 54

Power track system See page 14

Access floor grommets and boxes See page 28

Office power
Electrak products are designed and built to the highest standards, ensuring efficient delivery of power throughout the workplace. The office power ranges are all modular in design, making them quick and easy to install, whilst ensuring the flexibility required to cope with evolving office layouts.

SECTION CONTENTS :
Power track systems (see p. 14) Access floor service outlet boxes (see p. 28) Access floor grommets (see p. 32) Rotasoc desk modules (see p. 38) Intersoc desk modules (see p. 54)

FIND OUT MORE ABOUT ELECTRAK :


/// Website : for information about Electraks power distribution and lighting control solutions, visit www.electrak.co.uk /// Contact us : for any questions about Electraks product ranges, tel : + 44 (0) 845 600 6266 email : powersales.uk@legrand.co.uk

Offices

FIND OUT MORE ABOUT LEGRAND :


/// Website : for information about the Legrand Group Worldwide, visit www.legrandgroup.com

Car park

PRODUCTS AND SYSTEMS I

Buscom trunking See page 70

Lightrak KNX See page 94

Lighting control
With increasing demand for pre-fabricated lighting control systems that help save energy, Electrak offers a range of solutions designed to integrate perfectly with key industry protocols, including KNX and DALI. Fast and simple installation combines with total flexibility to satisfy all power and control requirements for any lighting scenarios.

SECTION CONTENTS :
Busbar and buscom trunking (see p. 70) Lightrak KNX (see p. 94) Distribution boxes for DALI installations (see p. 96) Buscom trunking for DALI installations (see p. 97)

FIND OUT MORE ABOUT ELECTRAK :


/// Website : for information about Electraks power distribution and lighting control solutions, visit www.electrak.co.uk /// Contact us : for any questions about Electraks product ranges, tel : + 44 (0) 845 600 6266 email : powersales.uk@legrand.co.uk

Offices

FIND OUT MORE ABOUT LEGRAND :


/// Website : for information about the Legrand Group Worldwide, visit www.legrandgroup.com

Car park

PRODUCTS AND SYSTEMS I

P. 6 Office power systems overview

ElectrakTM power track systems

P. 18 Electrak 26 dual circuit system (dark green)

Power track

10

P. 12 Introduction to Electrak power track

P. 14 Selection chart

P. 16 Electrak 24 standard system (white) P. 21 Design and installation

P. 17 Electrak 25 low noise / clean earth system (light green) P. 25 Standards and technical information

P. 19 Electrak 27 3 phase system (grey)

P. 20 Electrak 28 auxiliary earth system (red)

11

Electrak power track underfloor distribution system


Electrak has led the power distribution market for cavity floor solutions since 1984 when it launched the first small power track system. With minimal parts and push-fit assembly, this flexible system is easy to install and minimises disruption as office layouts evolve.

TM

DESIGN AND INSTALLATION The system consists of continuous lengths of track (generally arranged in parallel format) which are fed from the distribution board via track feed boxes and can be installed in floor voids as low as 48 mm. Track lengths fit together using integral track connectors for quick assembly with access to power via tap-offs from the shuttered outlets.

12

Tap-off units plug into shuttered socket outlets and lock on to track body. Remove by compressing side clips and pulling out.

Integral track connector plugs into track feed unit.

Integral fixing brackets fixed to track 2 on 1.2 m track 2 on 2.4 m track 3 on 3.6 m track

Lengths of track fit together by simply plugging the integral track connector into the end of the previous fitted track length.

EXTENDED RANGE Available in five versions to meet all power requirements in today's modern offices... standard, low noise / clean earth, dual circuit, three phase and auxiliary earth.

13

ElectrakTM power track systems

Description
Track lengths with 300 mm socket centres

Length (m)

4 sockets 6 sockets 8 sockets 12 sockets

12 18 24 36

Track feed

Flexible interlink / corner

Excluding cables and conduit Flexible metal conduit Flexible metal conduit

12 24

Standard tap-off / auxiliary earth tap-off

32 A unfused 16 mm L, N, PE 13 A fused 16 mm L, N, PE 13 A 5437 fused 16 mm L, N, PE


Low noise / clean earth tap-off

3 5 3 5 3 5 3 5 3 5 3 5

32 A unfused 16 mm CE, L, N, PE 13 A fused 16 mm CE, L, N, PE 13 A 5437 fused 16 mm CE, L, N, PE


Dual circuit tap-off

3 32 A unfused 20 mm CE, L1, N1 L2, N2, PE 5


3 phase tap-off

32 A 415 V 3 phase 20 mm L1, L2, L3, N, PE 32 A L1 unfused reconfigurable live pin 16 mm L1, N, PE 32 A L2 unfused reconfigurable live pin 16 mm L2, N, PE 32 A L3 unfused reconfigurable live pin 16 mm L3, N, PE

3 5 3 5 3 5 3 5

Key code / Busbar arrangement

14

ELECTRAK 24
Standard system (white)

ELECTRAK 25
Low noise / clean earth system (light green)

ELECTRAK 26
Dual circuit system (dark green)

ELECTRAK 27
3 phase system (grey)

ELECTRAK 28
Auxiliary earth system (red)

DA1123 DA1183 DA1243 DA1363

JA2123 JA2183 JA2243 JA2363

KA3123 KA3183 KA3243 KA3363

NA4123 NA4183 NA4243 NA4363

YA5123 YA5183 YA5243 YA5363

DF1010

JF2010

KF3010

NF4010

YF5010

DW1000 DW1010 DW1020

JW2000 JW2010 JW2020

KW3000 KW3010 KW3020

NW4000 NW4010 NW4020

YW5000 YW5010 YW5020

DP1332 DP1532 DP1313 DP1513 DP1327 DP1527

JP2332 JP2532 JP2313 JP2513 JP2327 JP2527

DP1332 DP1532 DP1313 DP1513 DP1327 DP1527 JP2332 JP2532 JP2313 JP2513 JP2327 JP2527

YP5332 YP5532 YP5313 YP5513 YP5327 YP5527

KP3328

KP3528

NZ4331 NZ4531 NP4332


(1)

NP4532(1) NP4302(1) NP4502(1) NP4303


(1)

NP4503(1)

PE

N2 L2

PE CE N1 L1

PE CE N1 L1 N2 L2

PE N L1 L2 L3

PE N1 L1

(1) All NP tap-offs are reconfigurable between L1, L2 or L3 for 3 phase track

15

ElectrakTM 24 power track system


standard system (white)

DF1010 DW1010

DA1123

- - -/ ---

DP1332

Selection chart (p. 14-15) Dimensions and technical information (p. 21-25) Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos.

Track system components


Electrak 24 standard track lengths Track lengths fit together using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets 300 mm socket centres 12 m, 4 sockets, 2 floor fixing brackets 18 m, 6 sockets, 2 floor fixing brackets 24 m, 8 sockets, 2 floor fixing brackets 36 m, 12 sockets, 3 floor fixing brackets Track feed unit

Pack

Cat. Nos.

Tap-off units
Tap-off length is determined by the cable and not the conduit length, e.g. a 3 m tap-off has 3 m of cable and 28 m of flexible metal conduit(1) Tap-off units in excess of 3 m should only be used if they contain a fuse or if the power track is protected by a 32 A rated protective device 32 A unfused

1
1 1

DA1123 DA1183 DA1243 DA1363

1 1

16 mm L, N, PE DP1332 3 m DP1532 5 m 13 A fused 16 mm L, N, PE DP1313 3 m DP1513 5 m 13 A 5437 fused - high integrity 16 mm L, N, PE DP1327 3 m DP1527 5 m

DF1010 With one 25 mm diameter hole suitable for MICC, armoured cables or single core cables in conduit Flexible interlinks Can be used to overcome obstructions or as corners where required DW1000 Excluding cables and conduit DW1010 12 m flexible metal conduit DW1020 24 m flexible metal conduit Special fixing brackets Required when track is raised off surface level Brackets raise track by 21 mm and should be spaced 600 mm apart DZ1210 For fitting under track body and track feed DZ1230 For fitting under integral track connectors
1 1

1 1 1

1 1

1 1

(1) Tap-offs are supplied as standard with flexible metal conduit For alternative wiring solutions, contact us on +44 (0) 845 600 6266

16

ElectrakTM 25 power track system


low noise / clean earth system (light green)

JF2010 JW2010

JA2123

- - -/ ---

JP2332

Selection chart (p. 14-15) Dimensions and technical information (p. 21-25) Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos.

Track system components


Electrak 25 low noise / clean earth track lengths Track lengths fit together using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets 300 mm socket centres 12 m, 4 sockets, 2 floor fixing brackets 18 m, 6 sockets, 2 floor fixing brackets 24 m, 8 sockets, 2 floor fixing brackets 36 m, 12 sockets, 3 floor fixing brackets Track feed unit

Pack

Cat. Nos.

Tap-off units
Tap-off length is determined by the cable and not the conduit length, e.g. a 3 m tap-off has 3 m of cable and 28 m of flexible metal conduit(1) Tap-off units in excess of 3 m should only be used if they contain a fuse or if the power track is protected by a 32 A rated protective device 32 A unfused

1 1 1 1

JA2123 JA2183 JA2243 JA2363

1 1

16 mm CE, L, N, PE JP2332 3 m JP2532 5 m 13 A fused 16 mm CE, L, N, PE JP2313 3 m JP2513 5 m 13 A 5437 fused - high integrity 16 mm CE, L, N, PE JP2327 3 m JP2527 5 m

JF2010 With one 25 mm diameter hole suitable for MICC, armoured cables or single core cables in conduit Flexible interlinks Can be used to overcome obstructions or as corners where required JW2000 Excluding cables and conduit JW2010 12 m flexible metal conduit JW2020 24 m flexible metal conduit Special fixing brackets Required when track is raised off surface level Brackets raise track by 21 mm and should be spaced 600 mm apart DZ1210 For fitting under track body and track feed DZ1230 For fitting under integral track connectors
1 1

1 1 1

1 1

1 1

(1) Tap-offs are supplied as standard with flexible metal conduit For alternative wiring solutions, contact us on +44 (0) 845 600 6266

17

ElectrakTM 26 power track system


dual circuit system (dark green)

KF3010 KW3010

KA3123

- - -/ ---

KP3328

Selection chart (p. 14-15) Dimensions and technical information (p. 21-25) Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos.

Track system components


The dual power track system has both standard and low noise / clean earth systems incorporated Electrak 26 dual circuit track lengths Track lengths fit together using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets 300 mm socket centres 12 m, 4 sockets, 2 floor fixing brackets 18 m, 6 sockets, 2 floor fixing brackets 24 m, 8 sockets, 2 floor fixing brackets 36 m, 12 sockets, 3 floor fixing brackets Track feed unit

Pack

Cat. Nos.

Tap-off units
Tap-off length is determined by the cable and not the conduit length, e.g. a 3 m tap-off has 3 m of cable and 28 m of flexible metal conduit(1) Tap-off units in excess of 3 m should only be used if they contain a fuse or if the power track is protected by a 32 A rated protective device Standard 32 A unfused

1 1 1 1

KA3123 KA3183 KA3243 KA3363

1 1

16 mm L, N, PE DP1332 3 m DP1532 5 m Standard 13 A fused 16 mm L, N, PE DP1313 3 m DP1513 5 m Standard 13 A 5437 fused 16 mm L, N, PE DP1327 3 m DP1527 5 m Low noise / clean earth 32 A unfused 16 mm CE, L, N, PE JP2332 3 m JP2532 5 m Low noise / clean earth 13 A fused 16 mm CE, L, N, PE JP2313 3 m JP2513 5 m Low noise / clean earth 13 A 5437 fused 16 mm CE, L, N, PE JP2327 3 m JP2527 5 m Dual circuit 32 A unfused 20 mm CE, L1, N1, L2, N2,PE KP3328 3 m KP3528 5 m

KF3010 With one 25 mm diameter hole suitable for MICC, armoured cables or single core cables in conduit Flexible interlinks Can be used to overcome obstructions or as corners where required KW3000 Excluding cables and conduit KW3010 12 m flexible metal conduit KW3020 24 m flexible metal conduit Special fixing brackets Required when track is raised off surface level Brackets raise track by 21 mm and should be spaced 600 mm apart DZ1210 For fitting under track body and track feed DZ1230 For fitting under integral track connectors

1 1

1 1 1

1 1

1 1

1 1

1 1

1 1

1 1

(1) Tap-offs are supplied as standard with flexible metal conduit For alternative wiring solutions, contact us on +44 (0) 845 600 6266

18

ElectrakTM 27 power track system


3 phase system (grey)

NF4010 NW4010

NA4123

- - -/ ---

NZ4331

Selection chart (p. 14-15) Dimensions and technical information (p. 21-25) Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos.

Track system components


Electrak 27 3 phase track lengths Track lengths fit together using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets 300 mm socket centres 12 m, 4 sockets, 2 floor fixing brackets 18 m, 6 sockets, 2 floor fixing brackets 24 m, 8 sockets, 2 floor fixing brackets 36 m, 12 sockets, 3 floor fixing brackets Track feed unit

Pack

Cat. Nos.

Tap-off units
Tap-off length is determined by the cable and not the conduit length, e.g. a 3 m tap-off has 3 m of cable and 28 m of flexible metal conduit(1) Tap-off units in excess of 3 m should only be used if they contain a fuse or if the power track is protected by a 32 A rated protective device 32 A 415 V 3 phase

1 1 1 1

NA4123 NA4183 NA4243 NA4363

1 1

20 mm L1, L2, L3, N, PE NZ4331 3 m NZ4531 5 m 32 A L1(2) unfused Unfused Reconfigurable live pin 16 mm L, N, PE NP4332 3 m NP4532 5 m 32 A L2(2) unfused Unfused Reconfigurable live pin 16 mm L, N, PE NP4302 3 m NP4502 5 m 32 A L3(2) unfused Unfused Reconfigurable live pin 16 mm L, N, PE NP4303 3 m NP4503 5 m

NF4010 With one 25 mm diameter hole suitable for MICC, armoured cables or single core cables in conduit Flexible interlinks Can be used to overcome obstructions or as corners where required NW4000 Excluding cables and conduit NW4010 12 m flexible metal conduit NW4020 24 m flexible metal conduit Special fixing brackets Required when track is raised off surface level Brackets raise track by 21 mm and should be spaced 600 mm apart DZ1210 For fitting under track body and track feed DZ1230 For fitting under integral track connectors
1 1 1 1

1 1 1

1 1

1 1

(1) Tap-offs are supplied as standard with flexible metal conduit For alternative wiring solutions, contact us on +44 (0) 845 600 6266 (2) All NP tap-offs are reconfigurable between L1, L2, or L3 for 3 phase track

19

ElectrakTM 28 power track system


auxilary earth system (red)

YF5010 YW5010

YA5123

- - -/ ---

YP5332

Selection chart (p. 14-15) Dimensions and technical information (p. 21-25) Approved to ASTA Standard 138 and ISO 9001 : 2008 Conforms to BS EN 60439-2 : 2008. Fully complies with the requirements of BS 7671 : 2008 IEE Wiring Regulations A compact system that can be installed in floor voids as low as 48 mm
Pack Cat. Nos.

Track system components


Electrak 28 auxiliary earth track lengths Track lengths fit together using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets 300 mm socket centres 12 m, 4 sockets, 2 floor fixing brackets 18 m, 6 sockets, 2 floor fixing brackets 24 m, 8 sockets, 2 floor fixing brackets 36 m, 12 sockets, 3 floor fixing brackets Track feed unit

Pack

Cat. Nos.

Tap-off units
Tap-off length is determined by the cable and not the conduit length, e.g. a 3 m tap-off has 3 m of cable and 28 m of flexible metal conduit(1) Tap-off units in excess of 3 m should only be used if they contain a fuse or if the power track is protected by a 32 A rated protective device 32 A unfused

1 1 1 1

YA5123 YA5183 YA5243 YA5363

1 1

16 mm L, N, PE YP5332 3 m YP5532 5 m 13 A fused 16 mm L, N, PE YP5313 3 m YP5513 5 m 13 A 5437 fused - high integrity 16 mm L, N, PE YP5327 3 m YP5527 5 m

YF5010 With one 25 mm diameter hole suitable for MICC, armoured cables or single core cables in conduit Flexible interlinks Can be used to overcome obstructions or as corners where required YW5000 Excluding cables and conduit YW5010 12 m flexible metal conduit YW5020 24 m flexible metal conduit Special fixing brackets Required when track is raised off surface level Brackets raise track by 21 mm and should be spaced 600 mm apart DZ1210 For fitting under track body and track feed DZ1230 For fitting under integral track connectors
1 1

1 1 1

1 1

1 1

(1) Tap-offs are supplied as standard with flexible metal conduit For alternative wiring solutions, contact us on +44 (0) 845 600 6266

20

ElectrakTM power track systems


design and installation

General installation notes


Electrak power track is a compact system that can be installed in floor voids as low as 48 mm Track feed boxes are provided with one or two 25 mm diameter holes suitable for MICC, armoured cables or single core cables in conduit Track lengths connect together and to track feeds using the integral connectors on each length Track lengths should always be secured using the integral floor fixing brackets ; three on the 36 m length and two on 24 m, 18 m or 12 m lengths Access to power is provided along the track length by simply plugging tap-off units into shuttered socket outlets. These tap-off units feed all types of conventional floor service outlet boxes or feed workstations directly through the floor via 4 mm2 or 15 mm2 insulated conductors contained in flexible metal or VO rated nylon conduit. When connecting tap-offs directly through the floor via grommet outlets to workstations care must be taken to ensure that the tap-off length is adequate The dual power track system has both standard and low noise / clean earth systems incorporated. As well as dual tap-offs, both standard and low noise / clean earth tap-offs can be plugged into any socket outlet along the track length. The dual tap-off incorporates both standard and low noise cables Optimum layout flexibility is achieved by positioning track lengths a maximum of 52 m apart and 25 m from the wall, and by connecting the 3 m tap-off units to floor outlet boxes. This means every part of the floor area can be served. Flexible interlinks can be used to overcome obstructions or used as corners if required

Special fixing brackets


When installing track off-floor, Electrak special fixing brackets raise track by 21 mm. Ensure brackets are spaced 600 mm apart and always have support under the integral track connector and track feed. Failure to do so may undermine the integrity of the system DZ1210 raised off-floor fixing brackets are spaced at 600 mm centres along track. Also use bottom half of bracket under track feed and flexible interlink DZ1230 raised off-floor fixing brackets are always used under integral track connectors. Track is secured to raised brackets using the tracks integral fixing bracket

Integral track fixing bracket screws to special bracket 50 mm 7 mm Integral track connector 185 mm 7 mm

99 mm

DZ1210

21 mm to underside of track 36 mm to top of track

DZ1210

Dimensions

93 46 2 x 25

75 46 25

250 47

109

118 32 15

68

65

End view A

End view B

92

Integral fixing bracket fixing centres

Example floor layout


25 m

socket outlet points ever y 300 or 600 mm along track length

52 m

52 m

3 m flexible tap-off unit

floor ser vice outlet box

52 m

track feed

integral track connectors

All dimensions (mm) are nominal

21

ElectrakTM power track systems


design and installation (continued)

Product configuration
Flexible interlink
Track and flexible interlink boxes must be securely fixed inline to surface so no movement can take place after fixing

Tap-off connection
Depress tap-off side clips and push down Tap-off

Side clip Push down

Interlink feed entry socket. Remove dust cover label Remove dust cover from power track end entry socket before use

Power track Make sure both tap-off side clips are fully pushed home on both sides of track

Screw fix to surface

Track feed DF1010 Sub-cabling

Tap-off connection
Tap-off metal flexible conduit Track feed protective earth terminal and earth bond

Protective earth must always be connected via the earth terminal block Connector terminals

Lift lid

20 mm conduit fitting. Tighten back nut securely

Lift terminal tab to access terminal screws and close after use

25 mm cable conduit fixing hole Close lid and secure with lid fixing screw before power up

Track feed JF2010 Sub-cabling

Tap-off connection
Tap-off metal flexible conduit Track feed protective earth terminal and earth bond

Protective earth must always be connected via the earth terminal block Connector terminals

Lift lid

20 mm conduit fitting Tighten back nut securely

Lift terminal tab to access terminal screws and close after use Clean earth 25 mm cable conduit fixing hole Close lid and secure with lid fixing screw before power up

22

Track feed KF3010 Sub-cabling

Dual tap-off connection (dark green)


Tap-off metal flexible conduit Lift terminal tab to access terminal screws and close after use

Protective earth must always be connected via the earth terminal block

Track feed protective earth terminal and earth bond

Lift lid

20 mm conduit fitting Tighten back nut securely

Connections L1, N1, CE = low noise L2, N2, PE = standard

Connections L1, N1, CE = low noise L2, N2, PE = standard Connector terminals Clean earth 2 x 25 mm cable conduit fixing hole Close lid and secure with lid fixing screw before power up

Track feed NF4010 Sub-cabling

3 phase tap-off connection


Tap-off metal flexible conduit Track feed protective earth terminal and earth bond

Protective earth must always be connected via the earth terminal block Connector terminals

Lift lid

20 mm conduit fitting Tighten back nut securely

Lift terminal tab to access terminal screws and close after use

25 mm cable conduit fixing hole Close lid and secure with lid fixing screw before power up

Track feed YF5010 Sub-cabling

Tap-off connection
Tap-off metal flexible conduit Track feed protective earth terminal and earth bond

Protective earth must always be connected via the earth terminal block Connector terminals

Lift lid

20 mm conduit fitting Tighten back nut securely

Lift terminal tab to access terminal screws and close after use

25 mm cable conduit fixing hole Close lid and secure with lid fixing screw before power up

23

ElectrakTM power track systems


installation

1 Fix track feed to surface


Plug-in key code Track feed Direction of track run Make chalk line to align track lengths

2 Connect track length to track feed


Remove dust cover Integral track connector Track length

Push down

Make sure track connector clips are fully pushed home on both sides of track Track feed

Push down

Power track and integral track connector

3 Connect additional track lengths


Remove dust cover before connecting track connector

First track fixing bracket

Track outlets reusable plastic dust covers

4 Secure track lengths to surface

Pull out track fixing bracket lugs and screw fix on both sides

All integral track fixing brackets must be fixed to surface at 12 m fixing centres from first bracket on each track length

24

ElectrakTM power track systems


technical data

Standards

Installations with high protective conductor currents


All unfused tap-offs comply with Regulation 5437 without the need for additional earth conductors. Regulation 543713 (ii) states a single copper protective conductor having a cross-sectional area of not less than 4 mm2, complying with the requirements of Regulations 5432 and 5433, the protective conductor being enclosed to provide additional protection against mechanical damage, for example, within a flexible conduit For 5437 installations with high protective conductor currents requiring fused tap-offs, a 5437 compliant tap-off must be used. Normally fused tap-offs incorporate 15 mm2 conductors, however in the fused 5437 tap-offs, the 15 mm2 earth conductor is replaced with a 4 mm2 conductor and therefore complies with Section 543713 (ii)

Approved to ASTA Standard 138 BS EN 60439-2 : 2000 Manufactured within an approved ISO 9001 : 2008 facility Assessed Quality Assurance Certificate No. 10679 Electrak fully complies with the requirements of BS 7671 : 2008 (IEE Wiring Regulations)

32 A tap-off unit
The 32 A tap-off unit comprises an unfused tap-off with either 28 m of 16 mm / 20 mm diameter flexible metal conduit or VO rated nylon conduit both with integral 4 mm2 LSOH conductors These units are designed to comply with regulation 43421 of the IEE Wiring Regulations by virtue of the following : maximum length of cable is 3 m it is factory assembled and fully tested item with cable installed in high quality flexible conduit Fault condition protection for the tap-off assembly and the floor box socket outlets is delivered by the circuit protection device Disconnection time for socket outlets is 04 seconds (Regulation 411322). The Electrak system meets this requirement Tap-off units in excess of 3 m should only be used if they contain a fuse or the power track is protected by a 32 A rated protective device Earth fault loop impedance

Earth fault loop impedance


BS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow the protective device to operate within the specified time, which for socket outlets is 04 seconds. The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite

Durability
Electrak systems are superbly designed and extremely robust. They can be expected to stand up to all normal site conditions. Electrak has been short circuit strength tested by ASTA

Volt drops (live and neutral) Busbars Cable connector Track connector 32 A tap-off + 4 mm2 cable Flexible corner assembly + 10 mm2 cable Mechanical data Number of conductors Busbar conductor cross sectional area Housing cross sectional area (copper equivalent) Cable terminal capacity Tap-off cable 32 A Tap-off cable 13 A fused Tap-off conduit, up to 4 conductors Tap-off conduit, 5 and 6 conductors Flexible corner cable (tri-rated, high temperature) Flexible corner conduit IP rating Material specifications Power track housing Busbars Busbar insulator Track connector/socket outlet/track feed connector Socket outlet entry shutter Tap-off housing Track connector blades Tap-off blades Tap-off/flexible corner conduit, metal Tap-off conduit, plastic Tap-off cable Flexible interlink cable Track feed box/flexible interlink boxes Track feed connector terminals/earth block Track fixing brackets 13 A tap-off, fuse 3 to 6 13 mm2 13 mm2 16 mm2 4 mm2 15 mm2 16 mm 20 mm 10 mm2 25 mm 40 30 mV/A/m 04 mV/A 04 mV/A 04 mV/A 11 mV/A/m 15 mV/A 40 mV/A/m

Phase busbar Earth busbar Earth housing Earth busbar and housing Cable connector Track connector 32 A tap-off + 4 mm2 cable Flexible corner assembly + 10 mm2 cable Rated conditional short-circuit current Ambient temperature Electrical test data Rated current Rated voltage Frequency Conductor resistance - live and neutral Conductor impedance

15 m/m 15 m/m 11 m/m 08 m/m 04 m 06 m 06 m 11 m/m 15 m 40 m/m 16 KA 25C

63 A 230/400 V~ 50/60 Hz 30 m/m 15 m/m

Galvanised steel, natural finish High conductivity copper PTFE Flame retardant polycarbonate Acetal Flame retardant polycarbonate Copper Copper Electro-galvanised steel VO rated LSOH to BS 7211 Tri-rated to BS 6231 Galvanised steel Brass Galvanised steel To BS 1362, ASTA approved

25

P. 6 Office power systems overview

ElectrakTM access floor service outlet boxes and grommets

P. 31 Ancillary items for service outlet boxes

Floor boxes and grommets


NEW IN 2010
Cleaners grommet
with switched RCD protected socket (p. 32)

26

P. 28 Empty boxes and accessory plates selection chart

P. 29 Pre-wired boxes selection chart

P. 30 2 and 3 compartment boxes

P. 31 4 compartment boxes

P. 32 Slab floor boxes

P. 32 NEW Floor grommets

P. 33 Technical information

27

Access floor service outlet boxes


empty boxes and accessory plates

2 compartment

3 compartment

4 compartment

To configure boxes as required, select : 1. Box depth 2. Number of compartments required 3. Desired accessory plates Empty boxes Single base 75 mm depth Example

mm 230
290 mm

230 mm
366 mm

230 mm
366 mm

112 mm width plates CR2001

100 mm width plates CR011

75 mm width plates CR4001

Single base 85 mm depth (standard box)

CR2002

CR012

CR4002

Single base 110 mm depth

CR2003

CR013

CR4003

Separate compartment base 75 mm depth

CR2004

CR014

CR4004

Separate compartment base 85 mm depth

CR2005

CR015

CR4005

Separate compartment base 110 mm depth Plates Blank plate 2 gang switched socket outlet 2 gang switched socket outlet, low noise / clean earth 2 gang unswitched socket outlet 3 gang unswitched socket outlet 3 gang unswitched socket outlet, low noise / clean earth 2 gang RCD socket outlet 2 gang RCD socket outlet, low noise / clean earth Punched plate for 2 x 1 gang accessories (603 mm fixing centres) Punched plate for 2 gang accessories (1206 mm fixing centres) Angled punched plate for 4 x RJ45 sockets (37 mm x 22 mm cut-outs) 2 x LJ2 accessory plate (50 mm fixing centres) 4 x BNC connector plate 4 x Data / Telecoms plate (37 mm x 22 mm cut-outs) 6 x Data / Telecoms plate (37 mm x 22 mm cut-outs)

CR2006

CR016

CR4006

For 2 compartment boxes For 3 compartment boxes For 4 compartment boxes CR2100 CR2101 CR2102 CR2104 CR2105 CR2116 CR2112 CR2115 CR2106 CR2107 CR2109 CR2113 CR2114 CR020 CR022 CR023 CR029 CR030 CR044 CR036 CR043 CR026 CR028 CR042 CR031 CR033 CR024 CR025 CR4100 CR4101 CR4102 CR4104 CR4105 CR4118 CR4111 CR4117 CR4115 CR4106 CR4108 CR4112 CR4113

28

Access floor service outlet boxes


pre-wired boxes

3 compartment

4 compartment

Pre-wired service outlet boxes with Electrak tap-offs 1. Select box depth and desired configuration 2. Select additional accessory plates (if required)
230 230 mm
366 mm

Pre-wired boxes Single base 85 mm depth, pre-wired with 3 m Electrak 24 standard tap-off Single base 85 mm depth, pre-wired with 5 m Electrak 24 standard tap-off Single base 85 mm depth, pre-wired with 3 m Electrak 25 low noise / clean earth tap-off Single base 85 mm depth, pre-wired with 5 m Electrak 25 low noise / clean earth tap-off Single base 85 mm depth, pre-wired with 3 m Electrak 28 auxiliary earth tap-off Single base 85 mm depth, pre-wired with 5 m Electrak 28 auxiliary earth tap-off Additional plates Blank plate

Example

Includes 1 x twin switched socket outlet CR100 CR101 CR110 CR111 CR104 CR105

Includes 2 x twin switched socket outlets CR122 CR123 CR132 CR133 CR124 CR125

For 3 compartment boxes For 4 compartment boxes CR020 CR4100

mm
366 mm

2 gang switched socket outlet(1) 2 gang switched socket outlet, low noise / clean earth(1) 2 gang unswitched socket outlet(1)

CR022

CR4101

CR023

CR4102

CR029

CR4104

3 gang unswitched socket outlet(1) 3 gang unswitched socket outlet, low noise / clean earth(1) 2 gang RCD socket outlet(1) 2 gang RCD socket outlet, low noise / clean earth(1) Punched plate for 2 x 1 gang accessories (603 mm fixing centres) Punched plate for 2 gang accessories (1206 mm fixing centres) Angled punched plate for 4 x RJ45 sockets (37 mm x 22 mm cut-outs) 2 x LJ2 accessory plate (50 mm fixing centres)

CR030

CR4105

CR044

CR4118

CR036

CR4111

CR043

CR4117

CR026

CR028

CR042

CR4115

CR031

CR4106

4 x BNC connector plate 4 x Data / Telecoms plate (37 mm x 22 mm cut-outs) 6 x Data / Telecoms plate (37 mm x 22 mm cut-outs)
(1) Additional sockets will require wiring on site

CR033

CR4108

CR024

CR4112

CR025

CR4113

29

Access floor service outlet boxes


2 and 3 compartment boxes

CR2002 CR100

CR012

Selection chart (p. 28-29) Dimensions and technical information (p. 33) Lid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a Zintec coated mild steel plate Mounting frame and box base - 09 mm thick galvanised steel Each compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits Grey mouldings. Alternative colours available to special order. Goosewing grey plates 2, 3 and 4 compartment boxes are also available with separate individual compartment base units for convenient offsite pre-wiring Supplied in parts or fully assembled and configured to customer specification Conform to IEC-61534-22
Pack Cat. Nos.

2 compartment
Empty boxes 112 mm compartment widths

Pack

Cat. Nos.

3 compartment (continued)
Accessory plates 100 mm width Blank plate 2 gang switched socket outlet 2 gang switched socket outlet, low noise / clean earth 2 gang unswitched socket outlet 3 gang unswitched socket outlet 3 gang unswitched socket outlet, low noise / clean earth 2 gang RCD socket outlet 2 gang RCD socket outlet, low noise / clean earth Punched plate for 2 x 1 gang accessories (603 mm fixing centres) Punched plate for 2 gang accessories (1206 mm fixing centres) Angled punched plate for 4 x RJ45 (37 mm x 22 mm cut-outs) 2 x LJ2 accessory plate (50 mm fixing centres) 4 x BNC connector plate 4 x Data / Telecoms plate (37 mm x 22 mm cut-outs) 6 x Data / Telecoms plate (37 mm x 22 mm cut-outs)

1 1 1 1 1 1

CR2001 CR2002 CR2003 CR2004 CR2005 CR2006 CR2100 CR2101 CR2102 CR2104 CR2105 CR2116 CR2112 CR2115 CR2106 CR2107 CR2109 CR2113 CR2114

Single base - 75 mm depth Single base - 85 mm depth (standard box) Single base - 110 mm depth Separate compartment base - 75 mm depth Separate compartment base - 85 mm depth Separate compartment base - 110 mm depth Accessory plates 112 mm width Blank plate 2 gang switched socket outlet 2 gang switched socket outlet, low noise / clean earth 2 gang unswitched socket outlet 3 gang unswitched socket outlet 3 gang unswitched socket outlet, low noise / clean earth 2 gang RCD socket outlet 2 gang RCD socket outlet, low noise / clean earth Punched plate for 2 x 1 gang accessories (603 mm fixing centres) Punched plate for 2 gang accessories (1206 mm fixing centres) 4 x BNC connector plate 4 x Data / Telecoms plate (37 mm x 22 mm cut-outs) 6 x Data / Telecoms plate (37 mm x 22 mm cut-outs)

1 1 1 1 1

CR020 CR022 CR023 CR029 CR030 CR044 CR036 CR043 CR026 CR028 CR042 CR031 CR033 CR024 CR025

1 1 1 1 1

1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1

3 compartment pre-wired boxes


100 mm compartment widths 1 1 1 1 1 1 Single base 85 mm depth, pre-wired with : CR100 2 gang switched socket outlet and 3 m Electrak 24 standard tap-off CR101 2 gang switched socket outlet and 5 m Electrak 24 standard tap-off CR110 2 gang switched socket outlet (low noise / clean earth) and 3 m Electrak 25 low noise / clean earth tap-off CR111 2 gang switched socket outlet (low noise / clean earth) and 5 m Electrak 25 low noise / clean earth tap-off CR104 2 gang switched socket outlet and 3 m Electrak 28 auxiliary earth tap-off CR105 2 gang switched socket outlet and 5 m Electrak 28 auxiliary earth tap-off

3 compartment
Empty boxes 100 mm compartment widths
1 1 1 1 1 1

CR011 CR012 CR013 CR014 CR015 CR016

Single base - 75 mm depth Single base - 85 mm depth (standard box) Single base - 110 mm depth Separate compartment base - 75 mm depth Separate compartment base - 85 mm depth Separate compartment base - 110 mm depth

Electrak tap-offs (see p. 16-20)

30

Access floor service outlet boxes


4 compartment boxes and ancillary items

CR122 CR4002

Selection chart (p. 28-29) Dimensions and technical information (p. 33) Lid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a Zintec coated mild steel plate Mounting frame and box base - 09 mm thick galvanised steel Each compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits Grey mouldings. Alternative colours available to special order. Goosewing grey plates 2, 3 and 4 compartment boxes are also available with separate individual compartment base units for convenient offsite pre-wiring Supplied in parts or fully assembled and configured to customer specification Conform to IEC-61534-22
Pack Cat. Nos.

4 compartment
Empty boxes 75 mm compartment widths

Pack

Cat. Nos.

4 compartment pre-wired boxes


75 mm compartment widths

1 1 1 1 1 1

CR4001 CR4002 CR4003 CR4004 CR4005 CR4006 CR4100 CR4101 CR4102 CR4104 CR4105 CR4118 CR4111 CR4117 CR4115 CR4106 CR4108 CR4112 CR4113

Single base - 75 mm depth Single base - 85 mm depth (standard box) Single base - 110 mm depth Separate compartment base - 75 mm depth Separate compartment base - 85 mm depth Separate compartment base - 110 mm depth Accessory plates 75 mm width Blank plate 2 gang switched socket outlet 2 gang switched socket outlet, low noise / clean earth 2 gang unswitched socket outlet 3 gang unswitched socket outlet 3 gang unswitched socket outlet, low noise / clean earth 2 gang RCD socket outlet 2 gang RCD socket outlet, low noise / clean earth Angled punched plate for 4 x RJ45 (37 mm x 22 mm cut-outs) 2 x LJ2 accessory plate (50 mm fixing centres) 4 x BNC connector plate 4 x Data / Telecoms plate (37 mm x 22 mm cut-outs) 6 x Data / Telecoms plate (37 mm x 22 mm cut-outs)

1 1 1

1 1 1 1 1

1 1

Single base 85 mm depth, pre-wired with : CR122 2 x 2 gang switched socket outlets and 3 m Electrak 24 standard tap-off CR123 2 x 2 gang switched socket outlets and 5 m Electrak 24 standard tap-off CR132 2 x 2 gang switched socket outlets (low noise / clean earth) and 3 m Electrak 25 low noise / clean earth tap-off CR133 2 x 2 gang switched socket outlets (low noise / clean earth) and 5 m Electrak 25 low noise / clean earth tap-off CR124 2 x 2 gang switched socket outlets and 3 m Electrak 28 auxiliary earth tap-off CR125 2 x 2 gang switched socket outlets and 5 m Electrak 28 auxiliary earth tap-off

Ancillary items for service outlet boxes


1 1 10 10 50 1 1 1 1 10

1 1 1 1 1 1 1

CR0001 CR0003 CR0000 CR0010 CR0011 CR0002 CR0004 CR0005

Floor tile cut-out template 2 compartment Floor tile cut-out template 3/4 compartment Cable outlet flap Cable routers Screws for accessory plates Lid 2 compartment box Lid 3/4 compartment box Mounting frame for vinyl floor. For 2 compartment box Replaces mounting frame attached to base CR0006 Mounting frame for vinyl floor. For 3/4 compartment box. Replaces mounting frame attached to base CR0007 Floor box lid handle

Electrak tap-offs (see p. 16-20)

For other floor box configurations Contact us on +44 (0) 845 600 6266 31

Access floor service outlet boxes


slab floor boxes

Access floor grommets


quick fit floor grommets

NEW

CR5302

EG0010

3 compartment slab floor box shown with two twin switched socket outlets, punched data plate and a power-track tap-off CR5102

EG0055

EG0020

Dimensions and technical information (p. 33) Electrak slab floor boxes are an ideal solution for underfloor power and data requirements Used in conjunction with Electrak floor grommets, slab boxes prevent unwanted access to power and data connections
Pack Cat. Nos.

Quick fit installation from floor tile fixing to cable deployment Precision engineered from hard wearing durable flame retardant PC/ABS Grey mouldings. Other colours available to special order UL 94 VO flame class rating. Grommets conform to IEC-61534-22
Pack Cat. Nos.

Slab floor boxes


Fast and efficient installation with integrated fixing plates Wide range of power and data accessory plates Manufactured from 09 mm thick galvanised steel Each compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits 100 mm compartment widths

Floor grommet 144 mm

1 1

Use plates from the 3 compartment floor box section CR5102 1 compartment slab floor box CR5302 3 compartment slab floor box 112 mm compartment widths Use plates from the 2 compartment floor box section

1 1 1

Can accommodate all cable types or three metal conduits up to a 20 mm diameter or 25 mm without foam Simply secured by pushing down the spring-loaded screws and rotating a quarter turn EG0010 Empty grommet EG0020 Cleaners grommet with unswitched socket outlet EG0031 144 mm grommet with punched plate for 4 x RJ45
NEW EG0050 Cleaners grommet with switched RCD protected socket EG1111 Cleaners grommet lid EG1112 144 mm grommet lid

1 1 1

CR5202 2 compartment slab floor box 75 mm compartment widths Use plates from the 4 compartment floor box section

Floor grommet 232 mm


1 Recommended for installation in light traffic areas EG0055 232 mm grommet

CR5402 4 compartment slab floor box

For information on slab box configurations Contact us on +44 (0) 845 600 6266 32

For information on grommet configurations and RCD protection Contact us on +44 (0) 845 600 6266

Access floor service outlet boxes and grommets


technical information

Floor boxes
Dimensions Lid can accommodate carpets up to 6 mm depth Accessory plates are 172 mm long, with 162 mm fixing centres Materials Lid and trim mouldings are precision engineered from hard wearing durable ABS. Lid is reinforced with a Zintec coated mild steel plate Mounting frame and box base 09 mm thick galvanised steel Floor service unit conforms to IEC-61534-22 Wiring Each compartment has 2 entries for 20 mm and 2 entries for 25 mm flexible conduits Colour Grey mouldings. Alternative colours available to special order Goosewing grey plates Dimensions from top of floor tile into floor void

Floor grommet 144 mm


Dimensions 144 mm Grommet EG0010
144 mm

55 mm

Cleaners grommet EG0020 Complete with unswitched socket outlet


125 mm m i n 127 mm m i n

90 mm

Recommended hole cutter is a 5"/127 mm hole saw blade

Floor panel cut-out diameter

Carpet aperture

C A B
3825 mm
6685 mm

6685 mm
8 mm

A (mm)

B Accessory box depth (mm)

C Underside lid to top of accessory (plug clearance) (mm)

Large floor grommet 232 mm


Dimensions Large quick fit grommet EG0055
232 mm

75 85 110

35 45 45

35 35 60

To install box
58 mm

Cut hole in raised floor tile, lower complete box into aperture and push firmly down
213 mm min 215 mm max

Floor panel cut-out diameter Recommended hole cutter is a adjustable hole saw blade with range of 40 mm - 300 mm

To install floor grommet


A Floor tile cut-out dimensions 2 compartment : 263 mm x 203 mm(1) 3 and 4 compartment : 340 mm x 203 mm(1) Floor cut-out aperture is the same for single base or separate compartment base To fit carpet : Detach lid and trim assembly by lifting the blue locking handles and lifting out. Cut and fit carpet. Push lid and trim assembly back into place
Wing Lift handle and pull to remove lid Push grommet into raised floor tile aperture Push down spring loaded screws and rotate quarter turn to secure Ensure wings are located under floor panel For honeycombed floor panels one wing should face downwards and one wing should face upwards

(1) The aperture dimension 203 mm has a fixing tolerance between 203 to 205 mm

Cable access insert Drop cable access insert into housing opening

Slide lid into lug holes

(1) Push down lid to close (2) If grommet is not in use, replace cable access insert

33

P. 6 Office power systems overview

ElectrakTM RotasocTM desk modules

P. 44 Communications distribution

Rotasoc
NEW IN 2010
RCD

TM

protection modules (p. 39)

34

P. 36 Introduction to Rotasoc

P. 38 NEW Standard power distribution

P. 40 NEW Low noise / clean earth power distribution P. 46 Technical information

NEW P. 42 Dual circuit power distribution

P. 45 Horizontal desktop units

P. 45 Vertical desktop units

35

Rotasoc - the industry standard for versatile workstation power


TM

Available in 16 and 32 A versions, Rotasoc offers a comprehensive selection of modular multi-socket power distribution outlets with 360 rotatable socket outlets.

ROTASOC

TM

A comprehensive modular power system designed to meet the increasing power and communication needs of the workstation... Integrating Rotasoc with other products from the Electrak range enables you to create ofce power solutions from a single source.

36

Desktop units Personal power points, available in either horizontal or vertical orientation, simply t on to the desktop and connect directly to the under-desk system or to the mains via a standard plug.

Under-desk modules Power, data and telecoms modules can easily be recongured to meet the increasing demands of the workstation. Standard, low noise / clean earth and dual circuit options are suitable for any ofce environment, including those where an uninterrupted power supply is critical.

Integrated protection RCD and RCBO protection modules allow any modications to existing installations to comply with the latest edition of the Wiring Regulations, as well as delivering immediate 17th Edition compliance to new installations.

TM

FEATURES INCLUDE : Fully 360 rotatable sockets (on or off load) Totally modular system (easy to add modules) Busbar interconnection with push-t and cam-lock (no wiring required) Integrated comms and data modules Manufactured from high quality materials Standard, low noise / clean earth and dual circuit options Conforms to BS 7671 : 2008 section 543.7 for high protective conductor currents

37

RotasocTM desk modules


standard power distribution (grey socket outlets) 2P + E

RAB301A RAB201A RAB202A

--/---/--

RAB312A

RAB204A

RAZ020A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

--/---/--

RAB323A

16 A in-feed modules rewirable


Modules can accept a 3 core flexible cable MCB and RCD protection modules can also be used with 16 A in-feeds Unswitched / unfused Neon power indication With switched neon With switched neon / 63 A fused 63 A fused

Pack

Cat. Nos.

32 A in-feed module rewirable


To be wired on site. Metal face plate accepts most electrical terminations. Unswitched and unfused with an additional earth connection for bonding 32 A 2P + E

1 1 1 1 1

RAB201A RAB202A RAB203A RAB204A RAB205A

RAB301A

32 A in-feed modules pre-wired


Modules connect to power track via a tap-off and have an additional external earth connection for bonding Standard earth tap-offs (E24)
1 1 1 1 1 1 1 1

16 A in-feed modules pre-wired


Supplied with a 3 core flexible cable with a BS 1363 13 A plug. MCB and RCD protection modules can also be used with 16 A in-feeds Unswitched and unfused : 13 A BS 1363 plug to RAB201A
1 1 1 1

RAB311A RAB312A RAB315A RAB316A RAB340A RAB341A RAB344A RAB345A RAB322A RAB323A RAB326A RAB327A

RAB002A RAB003A RAB004A RAB005A

2m 3m 4m 5m Neon indication : 13 A BS 1363 plug to RAB202A

3 m unfused metal tap-off Cat. No. DP1332 5 m unfused metal tap-off Cat. No. DP1532 3 m 13 A fused 5437 metal tap-off Cat. No. DP1327 5 m 13 A fused 5437 metal tap-off Cat. No. DP1527 3 m unfused VO nylon tap-off 5 m unfused VO nylon tap-off 3 m 13 A fused 5437 VO nylon tap-off 5 m 13 A fused 5437 VO nylon tap-off Auxiliary earth tap-offs (E28) 3 m unfused metal tap-off Cat. No. YP5332 5 m unfused metal tap-off Cat. No. YP5532 3 m 13 A fused 5437 metal tap-off Cat. No. YP5327 5 m 13 A fused 5437 metal tap-off Cat. No. YP5527

1 1 1 1

RAB006A RAB007A RAB008A RAB009A

2m 3m 4m 5m Switched with neon : 13 A BS 1363 plug to RAB203A

1 1 1 1

1 1 1 1

RAB010A RAB011A RAB012A RAB013A

2m 3m 4m 5m Switched with neon and 63 A fused : 13 A BS 1363 plug to RAB204A

16 A and 32 A external earth kit


1 1

1 1 1 1

RAB014A RAB015A RAB016A RAB017A

2m 3m 4m 5m 63 A fused : 13 A BS 1363 plug to RAB205A

RAZ010A RAZ020A

For bonding in-feed to furniture 250 mm x 15 mm2 earth cable kit with fixings for 16 A in-feed 250 mm x 40 mm2 earth cable kit with fixings for 32 A in-feed

1 1 1 1

RAB018A RAB019A RAB020A RAB021A

2m 3m 4m 5m

38

RotasocTM desk modules


standard power distribution (grey socket outlets) 2P + E (continued)

RAB401A

RAB402A

RAB450A

RAB705A

RAB502A

RAB504A

RAZ001A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

Protection and switching modules


Used for the protection and switching of circuits where required With 13 A BS 1362 fuse With 13 A BS 1362 fuse and switched neon With 13 A BS 1362 fuse and neon With 32 A max. single isolation With 30 mA RCD With 6 A MCB With 16 A MCB With 20 A MCB With 32 A MCB With 16 A RCBO With 20 A RCBO With 32 A RCBO With 16 A filter With 32 A filter

Pack

Cat. Nos.

16 A flexible interconnection modules


Supplied with 15 mm2 x 3 core flexible cable and used to interconnect between units within the 16 A range of products 03 m 05 m 1m 2m 3m 4m 5m

1 1 1 1 1 1 1 1 1 1 1 1 1 1

RAB401A RAB402A RAB403A RAB404A RAB405A RAB410A RAB420A RAB430A RAB440A RAB450A RAB460A RAB470A RAB480A RAB490A

1 1 1 1 1 1 1

RAB603A RAB605A RAB610A RAB620A RAB630A RAB640A RAB650A

32 A flexible interconnection modules


Supplied with 4 mm2 x 3 singles in conduit and are used to interconnect between units within the 32 A range of products 03 m 05 m 1m 2m 3m 4m 5m

Socket modules
Individual socket outlets can rotate 360 in either direction, on or off load, accommodating bulky cables and transformers Available in 2, 3 and 4 gang options Modules can be connected to one another to give any combination of sockets. Sockets are available with individual 315 A or 5 A fuses to meet the requirements of BS 6396, or unfused Socket colour : grey Unfused sockets
1 1 1

1 1 1 1 1 1 1

RAB703A RAB705A RAB710A RAB720A RAB730A RAB740A RAB750A

End cap
1

RAZ001A

Used to cover the end of the system

RAB502A RAB503A RAB504A RAB532A RAB552A RAB533A RAB553A RAB534A RAB554A

2 gang 3 gang 4 gang Individually fused sockets 2 gang, 315 A fused 2 gang, 5 A fused 3 gang, 315 A fused 3 gang, 5 A fused 4 gang, 315 A fused 4 gang, 5 A fused

1 1 1 1 1 1

For international socket modules Contact us on +44 (0) 845 600 6266 39

RotasocTM desk modules


low noise / clean earth power distribution (red socket outlets) 16 A : 2P + CE, 32 A : 2P + E + CE

RAC201A

RAC202A

--/---/--

RAC312A

RAC204A

RAC301A

RAZ020A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

16 A in-feed modules rewirable


Modules can accept a 3 core flexible cable MCB and RCD protection modules can also be used with 16 A in-feeds Unswitched / unfused Neon power indication With switched neon With switched neon / 63 A fused 63 A fused

Pack

Cat. Nos.

32 A in-feed module rewirable


To be wired on site. Metal face plate accepts most electrical terminations. Supplied with an additional earth connection for dirty earth bonding 32 A 2P + E + CE

1 1 1 1 1

RAC201A RAC202A RAC203A RAC204A RAC205A

RAC301A

32 A in-feed modules pre-wired


Modules connect to power track via a tap-off and have an additional external earth connection for dirty earth bonding Low noise / clean earth tap-offs (E25)
1 1 1 1 1 1 1 1

16 A in-feed modules pre-wired


Supplied with a 3 core flexible cable with a BS 1363 13 A plug. MCB and RCD protection modules can also be used with 16 A in-feeds Unswitched and unfused : 13 A BS 1363 plug to RAC201A
1 1 1 1

RAC311A RAC312A RAC315A RAC316A RAC340A RAC341A RAC344A RAC345A

RAC002A RAC003A RAC004A RAC005A

2m 3m 4m 5m Neon indication : 13 A BS 1363 plug to RAC202A

3 m unfused metal tap-off Cat. No. JP2332 5 m unfused metal tap-off Cat. No. JP2532 3 m 13 A fused 5437 metal tap-off Cat. No. JP2327 5 m 13 A fused 5437 metal tap-off Cat. No. JP2527 3 m unfused VO nylon tap-off 5 m unfused VO nylon tap-off 3 m 13 A fused 5437 VO nylon tap-off 5 m 13 A fused 5437 VO nylon tap-off

1 1 1 1

RAC006A RAC007A RAC008A RAC009A

2m 3m 4m 5m Switched with neon : 13 A BS 1363 plug to RAC203A

16 A and 32 A external earth kit


1 1

RAZ010A RAZ020A

1 1 1 1

RAC010A RAC011A RAC012A RAC013A

2m 3m 4m 5m Switched with neon and 63 A fused : 13 A BS 1363 plug to RAC204A

For bonding in-feed to furniture 250 mm x 15 mm2 earth cable kit with fixings for 16 A in-feed 250 mm x 40 mm2 earth cable kit with fixings for 32 A in-feed

1 1 1 1

RAC014A RAC015A RAC016A RAC017A

2m 3m 4m 5m 63 A fused : 13 A BS 1363 plug to RAC205A

1 1 1 1

RAC018A RAC019A RAC020A RAC021A

2m 3m 4m 5m

40

RotasocTM desk modules


low noise / clean earth power distribution (red socket outlets) 16 A : 2P + CE, 32 A : 2P + E + CE (continued)

RAC401A

RAC402A

RAC405A

RAC420A

RAC450A

RAC502A

RAC504A

RAZ001A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

Protection and switching modules


Used for the protection and switching of circuits where required With 13 A BS 1362 fuse With 13 A BS 1362 fuse and switched neon With 13 A BS 1362 and neon With 32 A max. single isolation With 30 mA RCD With 6 A MCB With 16 A MCB With 20 A MCB With 32 A MCB With 16 A RCBO With 20 A RCBO With 32 A RCBO With 16 A filter With 32 A filter

Pack

Cat. Nos.

16 A flexible interconnection modules


Supplied with 15 mm2 x 3 core flexible cable and used to interconnect between units within the 16 A range of products 03 m 05 m 1m 2m 3m 4m 5m

1 1 1 1 1 1 1 1 1 1 1 1 1 1

RAC401A RAC402A RAC403A RAC404A RAC405A RAC410A RAC420A RAC430A RAC440A RAC450A RAC460A RAC470A RAC480A RAC490A

1 1 1 1 1 1 1

RAC603A RAC605A RAC610A RAC620A RAC630A RAC640A RAC650A

32 A flexible interconnection modules


Supplied with 4 mm2 x 3 singles in conduit and are used to interconnect between units within the 32 A range of products 03 m 05 m 1m 2m 3m 4m 5m

Socket modules
Individual socket outlets can rotate 360 in either direction, on or off load, accommodating bulky cables and transformers Available in 2, 3 and 4 gang options Modules can be connected to one another to give any combination of sockets. Sockets available with individual 315 A or 5 A fuses to meet the requirements of BS 6396, or unfused Socket colour : red Unfused sockets
1 1 1

1 1 1 1 1 1 1

RAC703A RAC705A RAC710A RAC720A RAC730A RAC740A RAC750A

End cap
1

RAZ001A

Used to cover the end of the system

RAC502A RAC503A RAC504A RAC532A RAC552A RAC533A RAC553A RAC534A RAC554A

2 gang 3 gang 4 gang Individually fused sockets 2 gang, 315 A fused 2 gang, 5 A fused 3 gang, 315 A fused 3 gang, 5 A fused 4 gang, 315 A fused 4 gang, 5 A fused

1 1 1 1 1 1

For international socket modules Contact us on +44 (0) 845 600 6266 41

RotasocTM desk modules


dual circuit power distribution (standard and low noise) 4P + E + CE

RAD201A

RAD202A

--/---/--

RAD312A

RAD301A

RAZ020A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

16 A in-feed modules rewirable


Modules can accept 2 x 3 core flexible cables MCB protection modules can also be used with 16 A in-feeds Unswitched / unfused With 2 x neon power indicators With 2 x switched neon With 2 x 63 A fuses

Pack

Cat. Nos.

32 A in-feed module rewirable


Can accept 2 x power track tap-offs and have an additional external earth connection for bonding 32 A 4P + E + CE

1 1 1 1

RAD201A RAD202A RAD203A RAD204A

RAD301A

32 A in-feed modules pre-wired


Modules connect to power track via one dual or two separate tap-offs and have an additional external earth connection for dirty earth bonding Separate tap-offs (E24 + E25)
1 1 1 1 1 1 1 1

16 A in-feed modules pre-wired


Supplied with 2 x 3 core flexible cables with BS 1363 13 A plugs. MCB protection modules can also be used with 16 A in-feeds Unswitched and unfused : 2 x 13 A BS 1363 plugs to RAD201A
1 1 1 1

RAD313A RAD314A RAD319A RAD320A RAD342A RAD343A RAD348A RAD349A

RAD002A RAD003A RAD004A RAD005A

2x2m 2x3m 2x4m 2x5m Neon indication : 2 x 13 A BS 1363 plugs to RAD202A

1 1 1 1

RAD006A RAD007A RAD008A RAD009A

2x2m 2x3m 2x4m 2x5m Switched with neon : 2 x 13 A BS 1363 plugs to RAD203A

3 m unfused metal tap-offs Cat. Nos. DP1332+JP2332 5 m unfused metal tap-offs Cat. Nos. DP1532+JP2532 3 m fused 5437 tap-offs Cat. Nos. DP1327+JP2327 5 m fused 5437 tap-offs Cat. Nos. DP1527+JP2527 3 m unfused VO nylon tap-offs 5 m unfused VO nylon tap-offs 3 m 13 A fused 5437 tap-offs Cat. Nos. DV1327+JV2327 5 m 13 A fused 5437 tap-offs Cat. Nos. DV1527+JV2527 Dual circuit tap-offs (E26) 3 m unfused metal tap-off Cat. No. KP3328 5 m unfused metal tap-off Cat. No. KP3528 3 m unfused VO nylon tap-off 5 m unfused VO nylon tap-off

1 1 1 1

RAD010A RAD011A RAD012A RAD013A

2x2m 2x3m 2x4m 2x5m 63 A fused : 2 x 13 A BS 1363 plugs to RAD204A

1 1 1 1

RAD311A RAD312A RAD340A RAD341A

16 A and 32 A external earth kit


1 1

1 1 1 1

RAD014A RAD015A RAD016A RAD017A

2x2m 2x3m 2x4m 2x5m

RAZ010A RAZ020A

For bonding in-feed to furniture 250 mm x 15 mm2 earth cable kit with fixings for 16 A in-feed 250 mm x 40 mm2 earth cable kit with fixings for 32 A in-feed

42

RotasocTM desk modules


dual circuit power distribution (standard and low noise) 4P + E + CE

RAD401A

RAD402A

RAD420A

RAD543A

RAD504A

RAZ001A

Dimensions and technical information (p. 46-49) Approved to BS 5733 and BS 1363 part 2. The 32 A system meets the requirements of regulation 543.7 within BS 7671 : 2008 Flame retardant ABS modules. The system can be factory-configured or assembled on-site All modules are busbar interconnected and simply push-fit and lock together Modules are colour-coded to distinguish the 3 system types; standard, low noise / clean earth and dual circuit
Pack Cat. Nos.

Protection and switching modules


Used for the protection and switching of circuits where required With 2 x 13 A BS 1362 fuse With 2 x switched neon (16 A only) With 2 x neon With 2 x 6 A MCB With 2 x 16 A MCB With 2 x 20 A MCB With 2 x 32 A MCB

Pack

Cat. Nos.

16 A flexible interconnection modules


Supplied with 2 x 15 mm2 3 core cables and used to interconnect between units within the 16 A range of products 03 m 05 m 1m 2m 3m 4m 5m

1 1 1 1 1 1 1

RAD401A RAD402A RAD403A RAD410A RAD420A RAD430A RAD440A

1 1 1 1 1 1 1

RAD603A RAD605A RAD610A RAD620A RAD630A RAD640A RAD650A

Socket modules
Individual socket outlets can rotate 360 in either direction, on or off load, accommodating bulky cables and transformers Available in 2, 3 and 4 gang options Modules can be connected to one another to give any combination of sockets. Sockets available with individual 315 A or 5 A fuses to meet the requirements of BS 6396, or unfused Unfused sockets standard / clean bypass
1 1 1

32 A flexible interconnection modules


Supplied with 2 x conduits each containing 4 mm2 x 3 singles, used to interconnect between units within the 32 A range of products 03 m 05 m 1m 2m 3m 4m 5m

RAD502A RAD503A RAD504A

Socket colour : grey 2 gang 3 gang 4 gang Unfused sockets clean / standard bypass Socket colour : red 2 gang 3 gang 4 gang Individually fused sockets standard / clean bypass

1 1 1 1 1 1 1

RAD703A RAD705A RAD710A RAD720A RAD730A RAD740A RAD750A

End cap
1

RAZ001A

Used to cover the end of the system

1 1 1

RAD512A RAD513A RAD514A

1 1 1 1 1 1

RAD532A RAD552A RAD533A RAD553A RAD534A RAD554A

Socket colour : grey 2 gang, 315 A fused socket 2 gang, 5 A fused sockets 3 gang, 315 A fused sockets 3 gang, 5 A fused sockets 4 gang, 315 A fused sockets 4 gang, 5 A fused sockets Individually fused sockets clean / standard bypass

1 1 1 1 1 1

RAD542A RAD562A RAD543A RAD563A RAD544A RAD564A

Socket colour : red 2 gang, 315 A fused sockets 2 gang, 5 A fused sockets 3 gang, 315 A fused sockets 3 gang, 5 A fused sockets 4 gang, 315 A fused sockets 4 gang, 5 A fused sockets

For international socket modules Contact us on +44 (0) 845 600 6266 43

RotasocTM desk modules


communications distribution

RAF101A

RAF210A

RAF107A

RAF214A

RAF104A

RAF213A

RAF108A

RAF215A

Dimensions and technical information (p. 46-47) Flame retardant ABS modules For connection within a power distribution system or for use as a stand-alone system
Pack Cat. Nos.

CAT 5 communications modules


In-line 4 way communications modules For in-line connection with Rotasoc socket modules. Rewirable For 50 / 25 mm face plate For 50 / 25 mm face plate with conduit entry For 37 / 22 mm face plate For 37 / 22 mm face plate with conduit entry Standalone 4 way communications modules Not compatible with Rotasoc socket modules Rewirable For 50 / 25 mm face plate For 50 / 25 mm face plate with conduit entry For 37 / 22 mm face plate For 37 / 22 mm face plate with conduit entry

Pack

Cat. Nos.

CAT 6 communications modules


In-line 4 way communications modules For in-line connection with Rotasoc socket modules. Rewirable For 37 / 22mm face plate For 37 / 22mm face plate with conduit entry Standalone 4 way communications modules Not compatible with Rotasoc socket modules Rewirable For 37 / 22 mm face plate For 37 / 22 mm face plate with conduit entry

1 1 1 1

RAF101A RAF102A RAF103A RAF104A

1 1

RAF107A RAF108A

1 1

RAF214A RAF215A

1 1 1 1

RAF210A RAF211A RAF212A RAF213A

44

RotasocTM desk modules


desktop units

RAK001

RAK011

RAL001

RAL002

RAL010

RAL011

Dimensions and technical information (p. 47-49) Rotasoc offers a complementary range of desktop units which are shrouded in aluminium Units connect to the under-desk system with an interconnection lead, or stand alone with a BS 1363 13 A fused plug
Pack Cat. Nos.

Horizontal desktop units


Units clamp on to desktop Pre-wired with 1m 16 A Rotasoc interconnection lead

Pack

Cat. Nos.

Vertical desktop units


Units secured with M 10 bolt through desktop Standard grey sockets 2P + E

1 1

RAL001 RAL002

1 1 1 1 1 1

RAK001 RAK002 RAK003 RAK010 RAK011 RAK012

2 gang individually 315 A fused sockets 3 gang individually 315 A fused sockets 4 gang individually 315 A fused sockets 2 gang unfused sockets 3 gang unfused sockets 4 gang unfused sockets Pre-wired with 3m power cable and BS 1363 plug

2 gang individually 315 A fused sockets with 3 m power cable and BS 1363 plug 3 gang individually 315 A fused sockets with 1 m interconnection lead Low noise red sockets 2P + CE 2 gang individually 315 A fused sockets with 3 m power cable and BS 1363 plug 3 gang individually 315 A fused sockets with 1 m interconnection lead

1 1

RAL010 RAL011

1 1 1 1 1 1

RAK020 RAK021 RAK022 RAK030 RAK031 RAK032

2 gang individually 315 A fused sockets 3 gang individually 315 A fused sockets 4 gang individually 315 A fused sockets 2 gang unfused sockets 3 gang unfused sockets 4 gang unfused sockets

45

RotasocTM desk modules


technical information

Power distribution modules


16 A in-feed module 32 A in-feed module 16 A and 32 A filter module

953 331 high

117 36 high

1625 52 high

BS 1362 protection module

MCB, RCD protection module

End cap

16 A and 32 A interconnection

793 561 high

1625 816 high

245 31 high

448 357 high

445

2 gang socket module

3 gang socket module

4 gang socket module

131 329 high

1909 329 high

2508 329 high

Communications distribution modules


Standalone data module Data module (Connects to power module)

Data module fixing hole under cable / conduit grip

246

1622 1953 413 High

85

1622 1717 413 high

85

Example
16 A unit comprising 16 A in-feed, 4 gang and 2 gang socket modules and end cap

953(1)

2508(1) 5016 (1) Fixing hole dimensions

131(1)

245

integral touch-proof fusing

BS 5733
BSI Kitemark Certified KM 56418
All dimensions (mm) are nominal Patented rotational socket (GB 2330700) and patented locking fuse (GB 2330955) Other international patents pending

46

Product configuration
1. Select the type of distribution system standard, or low noise / clean earth or dual circuit 2. Select the means of powering the system cable or power track tap-off 3. Select the type of in-feed module to match the cable capacity 16 A or 32 A 4. Select the means of protection, if required 5. Select the number of socket modules from the 2, 3 or 4 gang range (individually fused or non-fused) 6. Select the interconnection units if required 7. Finish system with the end cap (All modules push fit and lock together on-site or can be factory assembled to customer requirement)
Raised floor Floor grommet

lllllllllllllllll
1 2

lllllll

iiiiiil

llllllllllllllllllllllllll llllllll lllllllllllllll


Underfloor power track

lllll
32 A in-feed connected to tap-off and left underfloor until required

l l ll ll l

l l ll l ll ll l

l ll l

Desktop units
Horizontal units

Desktop unit connecting directly into under-desk socket module Brackets fit desktop thickness 20 mm to 35 mm Other brackets to customer specification Desktop unit connecting to power via BS 1363 plug

Vertical units

2 gang 205 mm high 3 gang 265 mm high

Vertical desktop unit is secured with M 10 bolt through desktop

l l ll

Tap-off

l ll l

In-feed and power module push together and lock with cam lock lever

llll l

Tap-off and in-feed pulled through floor grommet after testing and when required

47

RotasocTM desk modules


installation and configuration

Installation
To connect and disconnect Rotasoc modules 1. Connection / disconnection to be made by a competent person 2. Check that both male and female ends have the same colour coded busbar shield 3. Turn modules over and release the red cam-lock lever with a small screwdriver into the upright position 4. Locate male and female ends and push together until fully closed

5. Press the red cam-lock lever over until flush with the casing to lock the modules together 6. To disconnect, reverse the procedure

To fix modules to surface 1. Flip up all rubber screw cover caps with a flat blade screwdriver 2. Insert through all fixing holes no. 8 pozi-pan screw or M4 bolt to required length 3. Tighten screw / bolt down to mounting surface 4. Push rubber screw cover caps down

Coloured busbar shield system


Standard system Low noise / clean earth system Dual circuit system

Important warnings A. Isolation Isolate the circuit supply from mains Isolate circuit if connecting and disconnecting modules to live infeed B. Installation and testing The system should be installed, tested and maintained by a qualified electrician or competent person in accordance with BS 7671 : 2008 (IEE Wiring Regulations) and BS 6396 Electrical Equipment within Office Furniture C. Protection The circuit must be protected by a suitably rated fuse or circuit breaker in accordance with the above

White

White

Red

Red

Red

White

When connecting modules together, ensure that the coloured busbar shields are colour matched and correctly aligned. Do not connect modules if shields are of different colours

48

RotasocTM desk modules


technical information

Testing and accreditation


Electrical test data Rated current Rated voltage Frequency up to 32 A 230 V ~ 50/60 Hz

British standards
BS 6396 : 2008 Electrical Systems in Office Furniture and Office Screens BS 7671 : 2008 Requirements for Electrical Installation (IEE Wiring Regulations 17th Edition) Electricity at Work Regulations 1989 Health and Safety Legislation

Conductor resistance at 20C 2 socket module 3 socket module 4 socket module 06 m 09 m 12 m

Below is a brief outline of the main criteria within the standards : BS 6396 : 2008 was published with regard to the use of electrical equipment within general office furniture and screens. This standard sets out in its scope the use and testing of electrical socket outlets and associated wiring when used together with a 13 A BS 1363 fused plug and makes provision for the routing of cables through furniture A note on individual socket fusing - BS 6396 Compliance : The standard requires individual socket fusing (as per the table below) Total number of sockets 2, 3 or 4 5 or 6 Individually fused at 5A 315 A

Volt drop Live and neutral 2 socket module 3 socket module 4 socket module Protection module In-feeds : 16 A +15 mm2 32 A +4 mm2 Interconnections : 16 A / 32 A +15 mm2 +4 mm2 12 m V/A 18 m V/A 24 m V/A 40 m V/A 60 m V/A 29 m V/Am 25 m V/A 11 m V/Am 20 m V/A 29 m V/Am 11 m V/Am

BS 7671 : 2008 (17th Edition). The Health and Safety Executive states that installations which conform to the standards laid down in BS 7671 : 2008 are regarded by the HSE as likely to achieve conformity with the relevant parts of The Electricity at Work Regulations 1989 Special note should be taken of Regulation 543.7 within BS 7671 : 2008 earthing requirements for the installation of equipment having high protective conductor currents Regulation 543.7 has particular importance when there is a requirement for a quantity of information technology equipment being supplied from a final circuit in a location where the protective current exceeds 10 mA in normal use. Due to current in the protective conductor arising from the use of IT equipment, there is a requirement to provide a mechanically protected 4 mm2 conductor (543.7.1.3(ii)). Rotasoc achieves this when wired in accordance with the installation sheets by providing mechanically protected 5 mm2 earth conductors within the product NOTE : Rotating sockets are for direction use only, not continuous rotation

Earth fault loop impedance 2 socket module 3 socket module 4 socket module Protection module In-feeds : 16 A +15 mm2 32 A +4 mm2 Interconnections : 16 A/32 A +15 mm2 +4 mm2 12 m 18 m 24 m 40 m 60 m 29 m/m 25 m 11 m/m 20 m 29 m/m 11 m/m

BS 5733
Conform to BS 5733 and the relevant parts of BS 1363 part 2 Manufactured within an approved ISO 9001 : 2008 facility Quality assurance certificate No. 10270

Material specification Module housing Socket outlets Busbars and socket rings Other metalwork V flame retardant ABS polycarbonate high conductivity copper C101 phosphor bronze PB102

Mechanical data Number of conductors Busbar conductor cross-sectional area 16 A rewirable in-feed terminal capacity 32 A rewirable in-feed terminal capacity 3-6 5 mm2 15 mm2 6 mm2

49

P. 6 Office power systems overview

ElectrakTM IntersocTM desk modules

P. 60 16 A popular starter modules add-on options

Intersoc
NEW IN 2010

TM

IntersocTM desk modules


Under-desk modular system (p. 54)

50

P. 52 Introduction to Intersoc desk modules

NEW P. 54 Under-desk modular system

P. 57 International under-desk modules

P. 59 16 A popular starter modules

P. 61 Horizontal desktop units

P. 61 Vertical desktop units

P. 62 Under-desk and desktop range technical information

P. 64 Under-desk installation and configuration

51

Electrak Intersoc modular desk power system


Intersoc is a complete modular desk power system designed to meet the increasing power and communication needs of the modern workplace. Available in standard and clean earth versions, its unique design features enable rapid conguration and workstation relocation.

TM

TM

INTERSOC UNDER-DESK Intersoc modules have been designed with speed of installation and exibility in mind. Modular conguration enables thousands of different combinations to be made. Simple push-t connection means that, if expansion is required, modules can simply be disconnected and additional modules inserted. The range can be factory congured or assembled on site. And with simple screw holes in the feed units and end caps, Intersoc can be easily installed on to any xing surface.

TM

INTERSOC DESKTOP Intersoc desktop units offer all you will ever need in a sleek aluminium nish. With a range of mounting options to complement furniture arrangement, the range provides a quality solution for easy access to desktop power and data.

TM

52

QUALITY CONNECTIONS All sockets push-t together with busbar interconnection that needs no wiring.

INTERNATIONAL SOCKETS
BRITISH STANDARD Cyprus, Hong Kong, Ireland, Kuwait, Malaysia, Oman, Qatar, Singapore, UAE, UK SCHUKO Austria, Finland, Germany, Greece, Holland, Hungary, Iceland, Latvia, Luxembourg, Norway, Poland, Portugal, Romania, Russia, Sweden, Turkey

15 A ROUND PIN India, South Africa, Sri Lanka 5 A ROUND PIN India, Sri Lanka 15 A & 20 A NORTH AFRICA USA, Brazil, Canada, Philippines, Saudi Arabia, Thailand

CHINESE & AUSTRALIAN Argentina, Australia, China

53

IntersocTM desk modules


under-desk modular system

NEW

Dimensions and technical information (p. 62-65) The Intersoc 32 A under-desk range is a complete modular power system. All modules are busbar interconnected with no terminals and simply push-fit and lock together enabling rapid configuration and easy workstation reconfiguration The Intersoc modular system meets the requirements of BS 7671 : 2008, and relevant components are available in both standard and low noise / clean earth versions. Individually fused sockets are also available to meet the requirements of BS 6396 : 2008
Pack Cat. Nos.

Pre-wired Intersoc feed modules


BS 1363 13 A fused plug 13 A fused plug with 2 m 15 mm2 cable 13 A fused plug with 3 m 15 mm2 cable 13 A fused plug with 4 m 15 mm2 cable 13 A fused plug with 5 m 15 mm2 cable Standard earth tap-offs (E24) 3 m unfused metal tap-off DP1332 5 m unfused metal tap-off DP1532 3 m 13 A fused 5437 metal tap-off DP1327 5 m 13 A fused 5437 metal tap-off DP1527 3 m unfused VO nylon tap-off DV1332 5 m unfused VO nylon tap-off DV1532 3 m 13 A fused 5437 VO nylon tap-off DV1327 5 m 13 A fused 5437 VO nylon tap-off DV1527 Low noise / clean earth tap-offs (E25) 3 m unfused metal tap-off JP2332 5 m unfused metal tap-off JP2532 3 m 13 A fused 5437 metal tap-off JP2327 5 m 13 A fused 5437 metal tap-off JP2527 3 m unfused VO nylon tap-off JV2332 5 m unfused VO nylon tap-off JV2532 3 m 13 A fused 5437 VO nylon tap-off JV2327 5 m 13 A fused 5437 VO nylon tap-off JV2527 Auxiliary earth tap-offs (E28) 3 m unfused metal tap-off YP5332 5 m unfused metal tap-off YP5532 3 m 13 A fused 5437 metal tap-off YP5327 5 m 13 A fused 5437 metal tap-off YP5527

- - /- - - /- IAB340A IAB301A Pack Cat. Nos.

Pre-wired connectors
BS 1363 13 A fused plug pre-wired to GST 18/3 connector

1 1 1 1

IAB002A IAB003A IAB004A IAB005A IAB311A IAB312A IAB315A IAB316A IAB340A IAB341A IAB344A IAB345A IAC311A IAC312A IAC315A IAC316A IAC340A IAC341A IAC344A IAC345A IAF311A IAF312A IAF315A IAF316A

1 1 1 1

IAB002B IAB003B IAB004B IAB005B

13 A fused plug with 2 m 15 mm2 cable 13 A fused plug with 3 m 15 mm2 cable 13 A fused plug with 4 m 15 mm2 cable 13 A fused plug with 5 m 15 mm2 cable BS 1363 13 A fused plug pre-wired to ST 18/3 connector

1 1 1 1 1 1 1 1

1 1 1 1

IAB002C IAB003C IAB004C IAB005C

13 A fused plug with 2 m 15 mm2 cable 13 A fused plug with 3 m 15 mm2 cable 13 A fused plug with 4 m 15 mm2 cable 13 A fused plug with 5 m 15 mm2 cable BS 1363 13 A fused plug pre-wired to 20 A Neutrik connector

1 1 1 1 1 1 1 1

1 1 1 1

IAB002D IAB003D IAB004D IAB005D

13 A fused plug with 2 m 15 mm2 cable 13 A fused plug with 3 m 15 mm2 cable 13 A fused plug with 4 m 15 mm2 cable 13 A fused plug with 5 m 15 mm2 cable Standard earth tap-offs (E24) pre-wired to 32 A Neutrik connector

1 1 1 1

1 1 1 1 1 1 1 1

IAB311E IAB312E IAB315E IAB316E IAB340E IAB341E IAB344E IAB345E

3 m unfused metal tap-off DP1332 5 m unfused metal tap-off DP1532 3 m 13 A fused 5437 metal tap-off DP1327 5 m 13 A fused 5437 metal tap-off DP1527 3 m unfused VO nylon tap-off DV1332 5 m unfused VO nylon tap-off DV1532 3 m 13 A fused 5437 VO nylon tap-off DV1327 5 m 13 A fused 5437 VO nylon tap-off DV1527 Low noise / clean earth tap-offs (E25) prewired to 32 A Neutrik connector

Intersoc feed modules


Standard earth
1 1 1 1 1 1

IAB201A IAB201B IAB201C IAB201D IAB301A IAB301E IAC201A IAC201B IAC201C IAC201D IAC301A IAC301E

Rewirable feed module (for cable) Feed module with male GST connector Feed module with male ST connector Feed module with 20 A Neutrik connector 32 A rewirable feed module (for flexible conduit) Feed module with 32 A Neutrik connector Low noise / clean earth Rewirable feed module (for cable) Feed module with male GST connector Feed module with male ST connector Feed module with 20 A Neutrik connector 32 A rewirable feed module (for flexible conduit) Feed module with 32 A Neutrik connector

1 1 1 1 1 1 1 1

IAC311E IAC312E IAC315E IAC316E IAC340E IAC341E IAC344E IAC345E

3 m unfused metal tap-off JP2332 5 m unfused metal tap-off JP2532 3 m 13 A fused 5437 metal tap-off JP2327 5 m 13 A fused 5437 metal tap-off JP2527 3 m unfused VO nylon tap-off JV2332 5 m unfused VO nylon tap-off JV2532 3 m 13A fused 5437 VO nylon tap-off JV2327 5 m 13A fused 5437 VO nylon tap-off JV2527

1 1 1 1 1 1

54

IntersocTM desk modules


under-desk modular system (continued)

NEW

IAB401A

IAB420A

IAC502A

IAB403A

IAB502B

IAC504A

IAB408A

IAB504E

IAC504D

Dimensions and technical information (p. 62-65) The Intersoc 32 A under-desk range is a complete modular power system. All modules are busbar interconnected with no terminals and simply push-fit and lock together enabling rapid configuration and easy workstation reconfiguration The Intersoc modular system meets the requirements of BS 7671 : 2008, and relevant components are available in both standard and low noise / clean earth versions. Individually fused sockets are also available to meet the requirements of BS 6396 : 2008
Pack Cat. Nos.

Protection and switching modules


Suitable for standard and low noise / clean earth systems With fuse With fuse and sw/neon With fuse and neon With neon With 30 mA RCD With 6 A MCB With 16 A MCB With 20 A MCB With 32 A MCB With 16 A RCBO With 20 A RCBO With 32 A RCBO 32 A max. single isolation module

Pack

Cat. Nos.

Socket modules low noise / clean earth (green)


2 gang unfused 90 angled sockets 45 angled sockets 135 angled sockets 2 gang individually fused 315 A 90 angled sockets 315 A 45 angled sockets 315 A 135 angled sockets 5 A 90 angled sockets 5 A 45 angled sockets 5 A 135 angled sockets 4 gang unfused 90 angled sockets 45 angled sockets 135 angled sockets 45/45/135/135 angled sockets 45/90/90/135 angled sockets 4 gang individually fused 315 A 90 angled sockets 315 A 45 angled sockets 315 A 135 angled sockets 315 A 45/45/135/135 angled sockets 315 A 45/90/90/135 angled sockets 5 A 90 angled sockets 5 A 45 angled sockets 5 A 135 angled sockets 5 A 45/45/135/135 angled sockets 5 A 45/90/90/135 angled sockets

1 1 1 1 1 1 1 1 1 1 1 1 1

IAB401A IAB402A IAB403A IAB408A IAB405A IAB410A IAB420A IAB430A IAB440A IAB450A IAB460A IAB470A IAB404A

1 1 1

IAC502A IAC502B IAC502C IAC532A IAC532B IAC532C IAC552A IAC552B IAC552C IAC504A IAC504B IAC504C IAC504D IAC504E IAC534A IAC534B IAC534C IAC534D IAC534E IAC554A IAC554B IAC554C IAC554D IAC554E

1 1 1 1 1 1

Socket modules standard (black)


2 gang unfused
1 1 1

IAB502A IAB502B IAB502C IAB532A IAB532B IAB532C IAB552A IAB552B IAB552C IAB504A IAB504B IAB504C IAB504D IAB504E IAB534A IAB534B IAB534C IAB534D IAB534E IAB554A IAB554B IAB554C IAB554D IAB554E

90 angled sockets 45 angled sockets 135 angled sockets 2 gang individually fused 315 A 90 angled sockets 315 A 45 angled sockets 315 A 135 angled sockets 5 A 90 angled sockets 5 A 45 angled sockets 5 A 135 angled sockets 4 gang unfused 90 angled sockets 45 angled sockets 135 angled sockets 45/45/135/135 angled sockets 45/90/90/135 angled sockets 4 gang individually fused 315 A 90 angled sockets 315 A 45 angled sockets 315 A 135 angled sockets 315 A 45/45/135/135 angled sockets 315 A 45/90/90/135 angled sockets 5 A 90 angled sockets 5 A 45 angled sockets 5 A 135 angled sockets 5 A 45/45/135/135 angled sockets 5 A 45/90/90/135 angled sockets

1 1 1 1 1

1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1

1 1 1 1 1

1 1 1 1 1 1 1 1 1 1

55

IntersocTM desk modules


under-desk modular system (continued)

NEW

IAZ001A

IAB603A

Dimensions and technical information (p. 62-65) The Intersoc 32 A under-desk range is a complete modular power system. All modules are busbar interconnected with no terminals and simply push-fit and lock together enabling rapid configuration and easy workstation reconfiguration A wide range of interconnection solutions are available with various cabling types. When 16 A cabling interconnection is used with 32 A under-desk solutions, suitable de-rating protection devices must be incorporated to protect the cables
Pack Cat. Nos.

Interconnection power out (male)


16 A components Rewirable male interconnect Male interconnect with female GST connector Male interconnect with female ST connector Male interconnect with 20A Neutrik connector 32 A components Rewirable male interconnect

Pack

Cat. Nos

Pre-wired interconnection (continued)


16 A male Intersoc to female GST 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 16 A male Intersoc to female ST 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 16 A male Intersoc to 20 A Neutrik connector 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 16 A male to female GST connection leads 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 16 A male to female ST connection leads 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 20 A Neutrik to Neutrik connection leads To be used as part of a 16 A system 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length

1 1 1 1

IAB600A IAB600B IAB600C IAB600D IAB700A

1 1 1 1 1 1 1

IAB603B IAB605B IAB610B IAB620B IAB630B IAB640B IAB650B IAB603C IAB605C IAB610C IAB620C IAB630C IAB640C IAB650C IAB603D IAB605D IAB610D IAB620D IAB630D IAB640D IAB650D IAB603BB IAB605BB IAB610BB IAB620BB IAB630BB IAB640BB IAB650BB IAB603CC IAB605CC IAB610CC IAB620CC IAB630CC IAB640CC IAB650CC

Interconnection power in (female)


16 A components
1 1 1 1

IAB201A IAB660B IAB660C IAB660D IAB301A

Rewirable female interconnect Female interconnect with male GST connector Female interconnect with male ST connector Female interconnect with 20A Neutrik connector 32 A components Rewirable female interconnect

1 1 1 1 1 1 1

Pre-wired interconnection
16 A male to female Intersoc 2P + E
1 1 1 1 1 1 1

IAB603A IAB605A IAB610A IAB620A IAB630A IAB640A IAB650A IAB703A IAB705A IAB710A IAB720A IAB730A IAB740A IAB750A

03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length 32 A male to female Intersoc 2P + E 03 m length 05 m length 1 m length 2 m length 3 m length 4 m length 5 m length

1 1 1 1 1 1 1

1 1 1 1 1 1 1

1 1 1 1 1 1 1

1 1 1 1 1 1 1

1 1 1 1 1 1 1

IAB603DD IAB605DD IAB610DD IAB620DD IAB630DD IAB640DD IAB650DD

End cap
1

IAZ001A

Blank end cap

56

IntersocTM desk modules


international under-desk modules

IAB5N4A

IAB5P4A

IAF5N2A

IAC5P2A

Dimensions and technical information (p. 62-65) Summary of socket standards by country (p. 53) The Intersoc 32 A under-desk range is a complete modular power system All modules are busbar interconnected with no terminals and simply push-fit and lock together enabling rapid configuration and easy workstation reconfigurations Intersoc offers a wide range of international socket options
Pack Cat. Nos.

Pre-wired Intersoc feed modules


Schuko plug With 2 m 15 mm2 cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable 5 A Indian plug With 2 m 15 mm2 cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable 15 A Indian plug With 2 m 15 mm cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable Chinese plug With 2 m 15 mm2 cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable 15 A USA plug With 2 m 15 mm2 cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable 20 A USA plug With 2 m 15 mm2 cable With 3 m 15 mm2 cable With 4 m 15 mm2 cable With 5 m 15 mm2 cable
2

Pack

Cat. Nos.

5 A Indian socket modules


2 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

IAB002N IAB003N IAB004N IAB005N IAB002P IAB003P IAB004P IAB005P IAB002Q IAB003Q IAB004Q IAB005Q IAB002R IAB003R IAB004R IAB005R IAB002S IAB003S IAB004S IAB005S IAB002T IAB003T IAB004T IAB005T

1 1 1 1 1 1 1 1 1 1 1 1

IAB5P2A IAB5P2B IAB5P2C IAB5P4A IAB5P4B IAB5P4C IAC5P2A IAC5P2B IAC5P2C IAC5P4A IAC5P4B IAC5P4C

15 A Indian socket modules


2 gang grey socket outlets 1 1 1 1 1 1 1 1 1 1 1 1 IAB5Q2A IAB5Q2B IAB5Q2C IAB5Q4A IAB5Q4B IAB5Q4C IAC5Q2A IAC5Q2B IAC5Q2C IAC5Q4A IAC5Q4B IAC5Q4C 90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

Schuko socket modules


2 gang grey socket outlets 1 1 1 1 1 1 1 1 1 1 1 1 IAB5N2A IAB5N2B IAB5N2C IAB5N4A IAB5N4B IAB5N4C IAF5N2A IAF5N2B IAF5N2C IAF5N4A IAF5N4B IAF5N4C 90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang red socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang red socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

57

IntersocTM desk modules


international under-desk modules (continued)

IAB5R4A

IAB5S4A

IAC5R2A

IAC5S2A

Dimensions and technical information (p. 62-65) Summary of socket standards by country (p. 53) The Intersoc 32 A under-desk range is a complete modular power system All modules are busbar interconnected with no terminals and simply push-fit and lock together enabling rapid configuration and easy workstation reconfigurations Intersoc offers a wide range of international socket options
Pack Cat. Nos.

Chinese socket modules


2 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

Pack

Cat. Nos.

15 A USA socket modules


2 gang grey socket outlets

1 1 1 1 1 1 1 1 1 1 1 1

IAB5R2A IAB5R2B IAB5R2C IAB5R4A IAB5R4B IAB5R4C IAC5R2A IAC5R2B IAC5R2C IAC5R4A IAC5R4B IAC5R4C

1 1 1 1 1 1 1 1 1 1 1 1

IAB5S2A IAB5S2B IAB5S2C IAB5S4A IAB5S4B IAB5S4C IAC5S2A IAC5S2B IAC5S2C IAC5S4A IAC5S4B IAC5S4C

90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

20 A USA socket modules


2 gang grey socket outlets 1 1 1 1 1 1 1 1 1 1 1 1 IAB5T2A IAB5T2B IAB5T2C IAB5T4A IAB5T4B IAB5T4C IAC5T2A IAC5T2B IAC5T2C IAC5T4A IAC5T4B IAC5T4C 90 angled sockets 45 angled sockets 135 angled sockets 4 gang grey socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 2 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets 4 gang green socket outlets 90 angled sockets 45 angled sockets 135 angled sockets

58

IntersocTM desk modules


16 A popular starter modules

TAAA052B TACA034B

TACB032B TADB054B

Dimensions and technical information (p. 62-65) Mains connection to these modules will be via an integral GST 18/3 connector or rewirable terminals. Starter modules can be used independently by adding a blank end cap (Cat. No. IAZ001A) or extended by adding additional socket modules. Can also be linked to other modules via flexible cable The last module in any run or combination must have a blank end cap to cover the open end
Pack Cat. Nos.

Rewirable feed and open end


2 gang modules without master switch or fuse

Pack

Cat. Nos.

GST 18/3 feed and open end


2 gang modules without master switch or fuse

1 1 1 1

TAAA032A TAAA032B TAAA052A TAAA052B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules without master switch or fuse

1 1 1 1

TAAB032A TAAB032B TAAB052A TAAB052B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules without master switch or fuse

1 1 1 1

TAAA034A TAAA034B TAAA054A TAAA054B TACA032A TACA032B TACA052A TACA052B TACA034A TACA034B TACA054A TACA054B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 2 gang modules with master switch / neon 90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules with master switch / neon 90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 2 gang modules with master 13 A fuse and switch / neon

1 1 1 1

TAAB034A TAAB034B TAAB054A TAAB054B TACB032A TACB032B TACB052A TACB052B TACB034A TACB034B TACB054A TACB054B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 2 gang modules with master switch / neon 90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules with master switch / neon 90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 2 gang modules with master 13 A fuse and switch / neon

1 1 1 1

1 1 1 1

1 1 1 1

1 1 1 1

1 1 1 1

TADA032A TADA032B TADA052A TADA052B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules with master 13 A fuse and switch / neon

1 1 1 1

TADB032A TADB032B TADB052A TADB052B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A 4 gang modules with master 13 A fuse and switch / neon

1 1 1 1

TADA034A TADA034B TADA054A TADA054B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A

1 1 1 1

TADB034A TADB034B TADB054A TADB054B

90 angled sockets individually fused at 315 A 45 angled sockets individually fused at 315 A 90 angled sockets individually fused at 5 A 45 angled sockets individually fused at 5 A

59

IntersocTM desk modules


16 A popular starter modules add-on options

Mains power lead IAB002B

4 socket in-feed module (see p. 59) TACB034B

Interlink GST connectors and flexible lead IAB603BB

2 socket module IAB532B

- -/---- -/
Power out interconnect with GST connector IAB600B Power in interconnect with GST connector IAB660B Blank end cap IAZ001A IAB502B IAB504B IAB534B IAB600A IAB201A

Dimensions and technical information (p. 62-65) Mains connection to these modules will be via an integral GST 18/3 connector or rewirable terminals. Starter modules can be used independently by adding a blank end cap (IAZ001A) or extended by adding additional socket modules. Modules can also be interlinked via flexible cable The last module in any run or combination must have a blank end cap to cover the open end
Pack Cat. Nos.

Mains power leads


2 m 13 A fused BS 1363 plug to female GST connector with 15 mm2 cable 3 m 13 A fused BS 1363 plug to female GST connector with 15 mm2 cable 5 m 13 A fused BS 1363 plug to female GST connector with 15 mm2 cable

Pack

Cat. Nos.

End caps / interconnection


Blank end cap Power out - male interconnect with female GST connector Power in - female interconnect with male GST connector Power out - male interconnect rewirable 16 A rewirable feed module (please note : also used as female interconnect rewirable power in) 03 m 16 A male to female GST connectors with 15 mm2 cable 05 m 16 A male to female GST connectors with 15 mm2 cable 1 m 16 A male to female GST connectors with 15 mm2 cable 2 m 16 A male to female GST connectors with 15 mm2 cable 3m 16 A male to female GST connectors with 15 mm2 cable

1 1

IAB002B IAB003B IAB005B

1 1 1 1

IAZ001A IAB600B IAB660B IAB600A IAB201A IAB603BB IAB605BB IAB610BB IAB620BB IAB630BB

Additional socket modules


2 gang unfused
1 1 1

1 1 1 1 1 1

IAB502B IAB502C IAB502A IAB504B IAB504C IAB504A IAB532B IAB532C IAB532A IAB534B IAB534C IAB534A

45 angled sockets 135 angled sockets 90 angled sockets 4 gang unfused 45 angled sockets 135 angled sockets 90 angled sockets 2 gang individually fused 315 A 45 angled sockets 315 A 135 angled sockets 315 A 90 angled sockets 4 gang individually fused 315 A 45 angled sockets 315 A 135 angled sockets 315 A 90 angled sockets

1 1 1

1 1 1

1 1 1

60

IntersocTM HDU and VDU modules


horizontal and vertical desktop units

HA1952AC Horizontal on-desk unit VA1452AC Vertical on-desk unit

Dimensions and technical information (p. 62-63) Desktop units offer power and data solutions with a range of mounting options to compliment your furniture arrangements All units are housed in an aluminium extrusion and are available in either horizontal or vertical orientation Any combination of socket outlets and other services can be integrated into the aluminium housing to suit individual customer requirements including switching of individual sockets
Pack Cat. Nos.

16 A horizontal desktop units (HDU)


All units are supplied with sockets angled at 90 Where data is offered, units come complete with 3 m data leads & RJ45 plugs 1 m power lead BS 1363 13 A fused plug

Pack

Cat. Nos.

16 A vertical desktop units (VDU)


All units are supplied with sockets angled at 45 Where data is offered, units come complete with 3 m data leads & RJ45 plugs 1 m power lead BS 1363 13 A fused plug

1 1 1 1 1

HA1952AA HA1952AB HA1952AC HA1953AA HA1954AA HA3952AA HA3952AB HA3952AC HA3953AA HA3954AA HB1932AA HB1932AB HB1932AC HB1933AA HB1934AA

2 sockets individually fused at 5 A 2 sockets individually fused at 5 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 5 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 5 A 4 sockets individually fused at 5 A 3 m power lead BS 1363 13 A fused plug 2 sockets individually fused at 5 A 2 sockets individually fused at 5 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 5 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 5 A 4 sockets individually fused at 5 A 1 m power lead male GST connector 2 sockets individually fused at 315 A 2 sockets individually fused at 315 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 315 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 315 A 4 sockets individually fused at 315 A Fixings

1 1 1 1 1

VA1452AA VA1452AB VA1452AC VA1453AA VA1454AA VA3452AA VA3452AB VA3452AC VA3453AA VA3454AA VB1432AA VB1432AB VB1432AC VB1433AA VB1434AA

2 sockets individually fused at 5 A 2 sockets individually fused at 5 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 5 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 5 A 4 sockets individually fused at 5 A 3 m power lead BS 1363 13 A fused plug 2 sockets individually fused at 5 A 2 sockets individually fused at 5 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 5 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 5 A 4 sockets individually fused at 5 A 1 m power lead male GST connector 2 sockets individually fused at 315 A 2 sockets individually fused at 315 A + 1 x RJ45 CAT 5e data outlet 2 sockets individually fused at 315 A + 2 x RJ45 CAT 5e data outlets 3 sockets individually fused at 315 A 4 sockets individually fused at 315 A Fixings

1 1 1 1 1

1 1 1 1 1

1 1 1 1 1

1 1 1 1 1

H001

Horizontal desktop unit fixing clamp

V001

Vertical desktop unit fixing clamp

10

H002

Desktop adhesive strip

Any combination of socket and service outlets can be configured on request (eg USB, IBM, Co-axial, SGVA, RJ45 etc.) Contact us on +44 (0) 845 600 6266 61

IntersocTM under-desk and desktop modules


technical information

Under-desk and popular range dimensions (mm)


2 socket in-feed module
60

4 socket in-feed module

Blank end cap

GST interconnect male

Rewirable interconnect male

2915

4115

23

50

67

GST interconnect female

Rewirable interconnect female


60

2 socket module

4 socket module
32

End view

60

75

1105

1565

2765

MCB, RCD protection module


60

Protection module
60

Interconnection
Rewirable infeed has 16 mm hole for flexible cable entr y cable restraint

1745

1155

50

775

Socket outlet orientation


Socket outlets are available in a selection of socket angles

45

90

135

Unfused

Individually fused 315 A or 5 A IEC fuses

Desktop range dimensions (mm)


2 socket individually fused unit
218

2 socket individually fused and 1 RJ45 unit


293

4 socket individually fused unit


368

2 socket individually fused and 2 RJ45 unit


348

Horizontal
40

Ver tical
40

3 socket individually fused unit


293

100

100

All dimensions (mm) are nominal

62

Under-desk and popular range testing and accreditation

Under-desk and desktop British Standards


BS 6396 : 2008 Electrical Systems in Office Furniture and Office Screens BS 7671 : 2008 Requirements for Electrical Installation (IEE Wiring Regulations 17th Edition) Electricity at Work Regulations 1989

Approved by ASTA to BS 5733 : 1995 incorporating amendment No. 1 and corrigendum No. 1 Conforms to the relevant parts of BS 1363 part 2 Manufactured within an approved ISO 9001 : 2008 facility Quality assurance certificate No. 10270 Electrical test data Rated current Rated voltage Frequency up to 32 A 250 V ~ 50/60 Hz

Health & Safety Legislation Below is a brief outline of the main criteria within the standards : BS 6396 : 2008 was published with regard to the use of electrical equipment within general office furniture and screens. This standard sets out in its scope the use and testing of electrical socket outlets and associated wiring when used together with a 13 A BS 1363 fused plug for mains supply and makes provision for the routing of cables through furniture For compliance with this standard, socket outlet configurations 2 or 4 outlets should be individually fused at 5 A and 6 outlets individually fused at 315 A A note on individual socket fusing BS 6396 Compliance :

Conductor resistance at 20C 2 socket module 4 socket module Volt drop Live and neutral 2 socket module 4 socket module Protection module In-feeds : 16 A +15 mm2 32 A +4 mm2 Interconnections : 16 A/32 A +15 mm2 +4 mm2 28 m V/A 56 m V/A 40 m V/A
(depending on device)

14 m 28 m

The standard requires individual socket fusing (as per the table below) Total number of sockets 2 or 4 sockets 5 or 6 sockets Individually fused at 5A 315 A

BS 7671 : 2008 (17th Edition). The Health and Safety Executive states that installations which conform to the standards laid down in BS 7671 : 2008 are regarded by the HSE as likely to achieve conformity with the relevant parts of the Electricity at Work Regulations 1989 Special note should be taken of regulation 5437 within BS 7671 : 2008 - Earthing requirements for the installation of equipment having high protective conductor currents Regulation 5437 has particular importance when there is a requirement for a quantity of information technology equipment being supplied from a final circuit in a location where the sum of their protective currents exceeds 10 mA in normal use. Due to current in the protective conductor arising from the use of IT equipment, there is a requirement to provide mechanically protected 4 mm2 conductor (543713(ii)). Intersoc achieves this when wired in accordance with the installation sheets by providing mechanically protected 5 mm2 protective conductors within the product

20 m V/A 29 m V/Am 20 m V/A 11 m V/Am 20 m V/A 29 m V/Am 11 m V/Am

Earth fault loop impedance 2 socket module 4 socket module Protection module In-feeds : 16 A +15 mm2 32 A +4 mm2 Interconnections : 16 A/32 A +15 mm2 +4 mm2 28 m 56 m 40 m
(depending on device)

Material specification Under desk : Module housing Socket outlets Busbars Other metalwork

20 m 29 m/m 20 m 11 m/m 20 m 29 m/m 11 m/m

V flame retardant ABS polycarbonate high conductivity copper C101 phosphor bronze PB102 PB103, brass CZ108 high conductivity copper C101 aluminium V flame retardant ABS polycarbonate V flame retardant ABS

On desk : Module housing Module fascia Socket outlets End caps

Mechanical data Number of conductors Busbar conductor cross-sectional area 16 A rewirable in-feed terminal capacity 32 A rewirable in-feed terminal capacity 3 5 mm2 10 mm2 10 mm2

63

IntersocTM under-desk modules


installation and configuration

Installation
To connect and disconnect Intersoc modules 1. Connection / disconnection to be made by a competent person 2. Before connecting modules ensure they are the correct way up and in line 3. Push modules together one at a time 4. Modules self-lock when fully pushed together 5. To disconnect modules slide green latch to unlock module and pull apar t 6. Always end module run with blank end cap or interconnect

Module self-locking latch

Underside of modules shown

To fix modules to surface 1. Inser t through all fixing holes no. 8 pozi-pan screw or M4 bolt to required length 2. Tighten screw / bolt down to mounting surface

Slide green latch

Blank end cap

2 socket module

4 socket in-feed module shown, extended to 6 sockets by adding a 2 socket module and closed by a blank end cap

16 A 4 socket in-feed module

64

Product configuration
1. Select the type of distribution system - standard, or low noise / clean earth 2. Select the means of powering the system - cable or power track tap-off 3. Select the type of in-feed module to match the cable capacity - 16 A or 32 A 4. Select the means of protection 5. Select the number of socket modules from the 2 or 4 gang range (individually fused or non-fused) 6. Select the orientation of the sockets (socket angle) 7. Select the interconnection units if required 8. Finish system with the end cap (All modules push fit and lock together on-site or can be factory assembled to customer requirement)

Raised floor

Floor grommet

lllllllllllllllll
1 2

lllllll

iiiiiil

llllllllllllllllllllllllll llllllll lllllllllllllll


Underfloor power track

lllll
32 A in-feed connected to tap-off and left underfloor until required

l l ll ll l

l l ll l ll ll l

l ll l

l l ll

Tap-off

l ll l

In-feed and power module push together and lock with cam lock lever

llll l

Tap-off and in-feed pulled through floor grommet after testing and when required

65

P. 8 Lighting control systems overview

ElectrakTM busbar / buscom trunking systems

P. 78 Electrak 31 3P + E system

P. 88 Dimensions

Busbar / buscom trunking systems

66

P. 68 Introduction to lighting control

P. 70 Busbar / buscom trunking selection charts

P. 74 Busbar / buscom trunking tap-offs selection charts

P. 76 Electrak 30 2P + E system

P. 80 Electrak 32 dual circuit system

P. 82 Electrak 33 3 phase system

P. 85 Fixings and ancillary items

P. 86 Technical information

P. 90 Installation

67

Electrak Lightrak KNX Proprietary lighting control


Designed to work in any circuit conguration alongside Electrak's 25 and 40 A buscom trunking with integral communications bus.

TM

TM

LIGHTING CONTROL SYSTEMS Lightrak employs the tried and tested KNX (European Installation Bus) protocol. It provides power distribution for lighting, fan coil units and other small power needs, whilst also offering signal bus distribution by means of its integral twisted pair communications control circuit. The system is suitable for both dimmable (1-10 V analogue and DSI) and non-dimmable applications. By employing the KNX protocol, Lightrak can be integrated seamlessly with other KNX building controls. High speed installation... control units clip on to busbar Simple plug-in connection for power and control
68

LIGHTING CONTROL UNITS All lighting control units are supplied pre-programmed and simply plug into Electrak's buscom trunking

BUSCOM TRUNKING Modular power and data distribution that couples high quality engineering with robust design

EMERGENCY TEST Simple plug-in key switch to enable testing of emergency luminaires PRESENCE DETECTION Saves energy and ensures that lighting is only on when needed TIMED EVENT CONTROLLER Operates across building and is programmed to optimise energy savings

MULTI-GANG SWITCHES 1, 2, 4 and 8 gang options connect directly to interface via Cat. 5 cable and RJ45 plugs SCENE SETTING SWITCH Connected directly into buscom trunking to activate pre-set lighting scenarios

BENEFITS Labour efcient. Pre-wired and pre-commissioned Energy efcient. Presence detection and auto-switching Fast, easy installation. Clip on / plug in Interface with other building control systems Fully addressable. Switching, dimming, corridor hold Load shed and emergency lighting test facilities Comprehensive design and commissioning service

FIND OUT MORE


Buscom trunking See p. 70 KNX Association visit: www.knx.org

69

TM pour exemple XXXXXXxxxxxx Electrak busbar / buscom trunking

xxxxxxxx 2P + E and 3P + E systems

3 m track 05 m spacings

2 m track 05 m spacings

3 m track 10 m spacings

2 m track 10 m spacings

SYSTEM

IP RATING

POWER/ COMMS

RATING

OUTLETS

Single sided

BBA3145 BBA3245 CCA3145 CCA3245 BBA3145C BBA3245C CCA3145C CCA3245C BBA3155 BBA3255 CCA3155 CCA3255 BBA3155C BBA3255C CCA3155C CCA3255C BBB3145 BBB3245 CCB3145 CCB3245 BBB3145C BBB3245C CCB3145C CCB3245C BBB3155 BBB3255 CCB3155 CCB3255 BBB3155C BBB3255C CCB3155C CCB3255C

BBA2145 BBA2245 CCA2145 CCA2245 BBA2145C BBA2245C CCA2145C CCA2245C BBA2155 BBA2255 CCA2155 CCA2255 BBA2155C BBA2255C CCA2155C CCA2255C BBB2145 BBB2245 CCB2145 CCB2245 BBB2145C BBB2245C CCB2145C CCB2245C BBB2155 BBB2255 CCB2155 CCB2255 BBB2155C BBB2255C CCB2155C CCB2255C

BBA3141 BBA3241 CCA3141 CCA3241 BBA3141C BBA3241C CCA3141C CCA3241C BBA3151 BBA3251 CCA3151 CCA3251 BBA3151C BBA3251C CCA3151C CCA3251C BBB3141 BBB3241 CCB3141 CCB3241 BBB3141C BBB3241C CCB3141C CCB3241C BBB3151 BBB3251 CCB3151 CCB3251 BBB3151C BBB3251C CCB3151C CCB3251C

BBA2141 BBA2241 CCA2141 CCA2241 BBA2141C BBA2241C CCA2141C CCA2241C BBA2151 BBA2251 CCA2151 CCA2251 BBA2151C BBA2251C CCA2151C CCA2251C BBB2141 BBB2241 CCB2141 CCB2241 BBB2141C BBB2241C CCB2141C CCB2241C BBB2151 BBB2251 CCB2151 CCB2251 BBB2151C BBB2251C CCB2151C CCB2251C

25 A

Busbar
(Power only) 40 A

Double sided Single sided Double sided

IP 4X
Single sided

25 A

Buscom

Double sided Single sided

Electrak 30

2P + E system

(Power and comms) 40 A

Double sided Single sided

25 A

Busbar
(Power only) 40 A

Double sided Single sided Double sided Single sided

IP 54
25 A

Buscom
(Power and comms) 40 A

Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided

25 A

Busbar
(Power only) 40 A

IP 4X
25 A

Buscom

Electrak 31

3P + E system

(Power and comms) 40 A

25 A

Busbar
(Power only) 40 A

IP 54
25 A

Buscom
(Power and comms) 40 A

70

Centre feed

Suspended feed unit left hand

Suspended feed unit right hand

Surface feed unit left hand

Surface feed unit right hand

Suspended flexible corner 05 m

Suspended flexible corner 20 m

Surface flexible corner 05 m

Surface flexible corner 20 m

BBA44F CCA44F BBA44FC CCA44FC BBB44F CCB44F BBB44FC CCB44FC

BBA14LF BBA24LF CCA14LF CCA24LF BBA14LFC BBA24LFC CCA14LFC CCA24LFC BBA15LF BBA25LF CCA15LF CCA25LF BBA15LFC BBA25LFC CCA15LFC CCA25LFC BBB14LF BBB24LF CCB14LF CCB24LF BBB14LFC BBB24LFC CCB14LFC CCB24LFC BBB15LF BBB25LF CCB15LF CCB25LF BBB15LFC BBB25LFC CCB15LFC CCB25LFC

BBA14RF BBA24RF CCA14RF CCA24RF BBA14RFC BBA24RFC CCA14RFC CCA24RFC BBA15RF BBA25RF CCA15RF CCA25RF BBA15RFC BBA25RFC CCA15RFC CCA25RFC BBB14RF BBB24RF CCB14RF CCB24RF BBB14RFC BBB24RFC CCB14RFC CCB24RFC BBB15RF BBB25RF CCB15RF CCB25RF BBB15RFC BBB25RFC CCB15RFC CCB25RFC

BBA34LF CCA34LF BBA34LFC CCA34LFC BBA35LF CCA35LF BBA35LFC CCA35LFC BBB34LF CCB34LF BBB34LFC CCB34LFC BBB35LF CCB35LF BBB35LFC CCB35LFC

BBA34RF CCA34RF BBA34RFC CCA34RFC BBA35RF CCA35RF BBA35RFC CCA35RFC BBB34RF CCB34RF BBB34RFC CCB34RFC BBB35RF CCB35RF BBB35RFC CCB35RFC

BBA140X BBA240X CCA140X CCA240X BBA140XC BBA240XC CCA140XC CCA240XC BBA150X BBA250X CCA150X CCA250X BBA150XC BBA250XC CCA150XC CCA250XC BBB140X BBB240X CCB140X CCB240X BBB140XC BBB240XC CCB140XC CCB240XC BBB150X BBB250X CCB150X CCB250X BBB150XC BBB250XC CCB150XC CCB250XC

BBA142X BBA242X CCA142X CCA242X BBA142XC BBA242XC CCA142XC CCA242XC BBA152X BBA252X CCA152X CCA252X BBA152XC BBA252XC CCA152XC CCA252XC BBB142X BBB242X CCB142X CCB242X BBB142XC BBB242XC CCB142XC CCB242XC BBB152X BBB252X CCB152X CCB252X BBB152XC BBB252XC CCB152XC CCB252XC

BBA340X CCA340X BBA340XC CCA340XC BBA350X CCA350X BBA350XC CCA350XC BBB340X CCB340X BBB340XC CCB340XC BBB350X CCB350X BBB350XC CCB350XC

BBA342X CCA342X BBA342XC CCA342XC BBA352X CCA352X BBA352XC CCA352XC BBB342X CCB342X BBB342XC CCB342XC BBB352X CCB352X BBB352XC CCB352XC

71

ElectrakTM busbar / buscom trunking


4P + E systems : dual circuit and 3 phase

3 m track 05 m spacings

2 m track 05 m spacings

3 m track 10 m spacings

2 m track 10 m spacings

SYSTEM

IP RATING

POWER/ COMMS

RATING

OUTLETS

Single sided

BBC3145 BBC3245 CCC3145 CCC3245 BBC3145C BBC3245C CCC3145C CCC3245C BBC3155 BBC3255 CCC3155 CCC3255 BBC3155C BBC3255C CCC3155C CCC3255C BBD3145 BBD3245 CCD3145 CCD3245 BBD3145C BBD3245C CCD3145C CCD3245C BBD3155 BBD3255 CCD3155 CCD3255 BBD3155C BBD3255C CCD3155C CCD3255C

BBC2145 BBC2245 CCC2145 CCC2245 BBC2145C BBC2245C CCC2145C CCC2245C BBC2155 BBC2255 CCC2155 CCC2255 BBC2155C BBC2255C CCC2155C CCC2255C BBD2145 BBD2245 CCD2145 CCD2245 BBD2145C BBD2245C CCD2145C CCD2245C BBD2155 BBD2255 CCD2155 CCD2255 BBD2155C BBD2255C CCD2155C CCD2255C

BBC3141 BBC3241 CCC3141 CCC3241 BBC3141C BBC3241C CCC3141C CCC3241C BBC3151 BBC3251 CCC3151 CCC3251 BBC3151C BBC3251C CCC3151C CCC3251C BBD3141 BBD3241 CCD3141 CCD3241 BBD3141C BBD3241C CCD3141C CCD3241C BBD3151 BBD3251 CCD3151 CCD3251 BBD3151C BBD3251C CCD3151C CCD3251C

BBC2141 BBC2241 CCC2141 CCC2241 BBC2141C BBC2241C CCC2141C CCC2241C BBC2151 BBC2251 CCC2151 CCC2251 BBC2151C BBC2251C CCC2151C CCC2251C BBD2141 BBD2241 CCD2141 CCD2241 BBD2141C BBD2241C CCD2141C CCD2241C BBD2151 BBD2251 CCD2151 CCD2251 BBD2151C BBD2251C CCD2151C CCD2251C

25 A

Busbar
(Power only) 40 A

Double sided Single sided Double sided

IP 4X
Single sided

25 A

Buscom Dual circuit system

Double sided Single sided

Electrak 32

(Power and comms) 40 A

Double sided Single sided

25 A

Busbar
(Power only) 40 A

Double sided Single sided Double sided

IP 54
Single sided

25 A

Buscom
(Power and comms) 40 A

Double sided Single sided Double sided Single sided

25 A

Busbar
(Power only) 40 A

Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided Single sided Double sided

IP 4X
25 A

Buscom 3 phase system

Electrak 33

(Power and comms) 40 A

25 A

Busbar
(Power only) 40 A

IP 54
25 A

Buscom
(Power and comms) 40 A

72

Centre feed

Suspended feed Suspended feed unit left hand unit right hand

Surface feed unit left hand

Surface feed unit right hand

Suspended flexible corner 05 m

Suspended flexible corner 20 m

Surface flexible corner 05 m

Surface flexible corner 20 m

BBC44F CCC44F BBC44FC CCC44FC BBD44F CCD44F BBD44FC CCD44FC

BBC14LF BBC24LF CCC14LF CCC24LF BBC14LFC BBC24LFC CCC14LFC CCC24LFC BBC15LF BBC25LF CCC15LF CCC25LF BBC15LFC BBC25LFC CCC15LFC CCC25LFC BBD14LF BBD24LF CCD14LF CCD24LF BBD14LFC BBD24LFC CCD14LFC CCD24LFC BBD15LF BBD25LF CCD15LF CCD25LF BBD15LFC BBD25LFC CCD15LFC CCD25LFC

BBC14RF BBC24RF CCC14RF CCC24RF BBC14RFC BBC24RFC CCC14RFC CCC24RFC BBC15RF BBC25RF CCC15RF CCC25RF BBC15RFC BBC25RFC CCC15RFC CCC25RFC BBD14RF BBD24RF CCD14RF CCD24RF BBD14RFC BBD24RFC CCD14RFC CCD24RFC BBD15RF BBD25RF CCD15RF CCD25RF BBD15RFC BBD25RFC CCD15RFC CCD25RFC

BBC34LF CCC34LF BBC34LFC CCC34LFC BBC35LF CCC35LF BBC35LFC CCC35LFC BBD34LF CCD34LF BBD34LFC CCD34LFC BBD35LF CCD35LF BBD35LFC CCD35LFC

BBC34RF CCC34RF BBC34RFC CCC34RFC BBC35RF CCC35RF BBC35RFC CCC35RFC BBD34RF CCD34RF BBD34RFC CCD34RFC BBD35RF CCD35RF BBD35RFC CCD35RFC

BBC140X BBC240X CCC140X CCC240X BBC140XC BBC240XC CCC140XC CCC240XC BBC150X BBC250X CCC150X CCC250X BBC150XC BBC250XC CCC150XC CCC250XC BBD140X BBD240X CCD140X CCD240X BBD140XC BBD240XC CCD140XC CCD240XC BBD150X BBD250X CCD150X CCD250X BBD150XC BBD250XC CCD150XC CCD250XC

BBC142X BBC242X CCC142X CCC242X BBC142XC BBC242XC CCC142XC CCC242XC BBC152X BBC252X CCC152X CCC252X BBC152XC BBC252XC CCC152XC CCC252XC BBD142X BBD242X CCD142X CCD242X BBD142XC BBD242XC CCD142XC CCD242XC BBD152X BBD252X CCD152X CCD252X BBD152XC BBD252XC CCD152XC CCD252XC

BBC340X CCC340X BBC340XC CCC340XC BBC350X CCC350X BBC350XC CCC350XC BBD340X CCD340X BBD340XC CCD340XC BBD350X CCD350X BBD350XC CCD350XC

BBC342X CCC342X BBC342XC CCC342XC BBC352X CCC352X BBC352XC CCC352XC BBD342X CCD342X BBD342XC CCD342XC BBD352X CCD352X BBD352XC CCD352XC

73

TM pour exemple XXXXXXxxxxxx Electrak busbar / buscom trunking tap-offs

xxxxxxxx

13 A FUSED TAP-OFFS
Rewirable 08 m 2m 3m 5m

2P + E system

IP RATING
With comms No comms

SYSTEM

PHASE

Electrak 30

IP 4X L+ N IP 54 IP 4X L1 N

DDF4F DDF5F DDF4F DDF5F DDH4F DDH5F DDF4F DDF5F DDK4F DDK5F DDN4L1F DDN5L1F DDN4L2F DDN5L2F DDN4L3F DDN5L3F DDP4SF DDP5SF

DDE408FC DDE408F DDE508FC DDE508F DDE408FC DDE408F DDE508FC DDE508F DDG408FC DDG408F DDG508FC DDG508F DDE408FC DDE408F DDE508FC DDE508F DDJ408FC DDJ408F DDJ508FC DDJ508F DDM408L1FC DDM408L1F DDM508L1FC DDM508L1F DDM408L2FC DDM408L2F DDM508L2FC DDM508L2F DDM408L3FC DDM408L3F DDM508L3FC DDM508L3F

DDE42FC DDE42F DDE52FC DDE52F DDE42FC DDE42F DDE52FC DDE52F DDG42FC DDG42F DDG52FC DDG52F DDE42FC DDE42F DDE52FC DDE52F DDJ42FC DDJ42F DDJ52FC DDJ52F DDM42L1FC DDM42L1F DDM52L1FC DDM52L1F DDM42L2FC DDM42L2F DDM52L2FC DDM52L2F DDM42L3FC DDM42L3F DDM52L3FC DDM52L3F

DDE43FC DDE43F DDE53FC DDE53F DDE43FC DDE43F DDE53FC DDE53F DDG43FC DDG43F DDG53FC DDG53F DDE43FC DDE43F DDE53FC DDE53F DDJ43FC DDJ43F DDJ53FC DDJ53F DDM43L1FC DDM43L1F DDM53L1FC DDM53L1F DDM43L2FC DDM43L2F DDM53L2FC DDM53L2F DDM43L3FC DDM43L3F DDM53L3FC DDM53L3F

DDE45FC DDE45F DDE55FC DDE55F DDE45FC DDE45F DDE55FC DDE55F DDG45FC DDG45F DDG55FC DDG55F DDE45FC DDE45F DDE55FC DDE55F DDJ45FC DDJ45F DDJ55FC DDJ55F DDM45L1FC DDM45L1F DDM55L1FC DDM55L1F DDM45L2FC DDM45L2F DDM55L2FC DDM55L2F DDM45L3FC DDM45L3F DDM55L3FC DDM55L3F

With comms No comms With comms No comms

3P + E system

Electrak 31

IP 54 IP 4X IP 54 IP 4X IP 54 IP 4X IP 54

With comms No comms With comms No comms With comms No comms With comms No comms With comms No comms With comms No comms With comms No comms

Dual circuit system

Electrak 32

L2 N2

L1 N1

L1 L2 N

IP 4X L1 N IP 54 IP 4X L2 N IP 54
3 phase system

With comms No comms With comms No comms With comms No comms With comms No comms

Electrak 33

IP 4X L3 N IP 54 Phase selectable IP 4X IP 54 IP 4X IP 54

With comms No comms With comms No comms With comms No comms With comms No comms With comms No comms With comms No comms

74

L+L+L+N

16 A UNFUSED TAP-OFFS
Rewirable 08 m 2m 3m 5m

DDF4 DDF5 DDF4 DDF5 DDH4 DDH5 DDF4 DDF5 DDK4 DDK5 DDN4L1 DDN5L1 DDN4L2 DDN5L2 DDN4L3 DDN5L3 DDP4S DDP5S

DDE408C DDE408 DDE508C DDE508 DDE408C DDE408 DDE508C DDE508 DDG408C DDG408 DDG508C DDG508 DDE408C DDE408 DDE508C DDE508 DDJ408C DDJ408 DDJ508C DDJ508 DDM408L1C DDM408L1 DDM508L1C DDM508L1 DDM408L2C DDM408L2 DDM508L2C DDM508L2 DDM408L3C DDM408L3 DDM508L3C DDM508L3 DDR408 DDR508

DDE42C DDE42 DDE52C DDE52 DDE42C DDE42 DDE52C DDE52 DDG42C DDG42 DDG52C DDG52 DDE42C DDE42 DDE52C DDE52 DDJ42C DDJ42 DDJ52C DDJ52 DDM42L1C DDM42L1 DDM52L1C DDM52L1 DDM42L2C DDM42L2 DDM52L2C DDM52L2 DDM42L3C DDM42L3 DDM52L3C DDM52L3 DDR42 DDR52

DDE43C DDE43 DDE53C DDE53 DDE43C DDE43 DDE53C DDE53 DDG43C DDG43 DDG53C DDG53 DDE43C DDE43 DDE53C DDE53 DDJ43C DDJ43 DDJ53C DDJ53 DDM43L1C DDM43L1 DDM53L1C DDM53L1 DDM43L2C DDM43L2 DDM53L2C DDM53L2 DDM43L3C DDM43L3 DDM53L3C DDM53L3 DDR43 DDR53

DDE45C DDE45 DDE55C DDE55 DDE45C DDE45 DDE55C DDE55 DDG45C DDG45 DDG55C DDG55 DDE45C DDE45 DDE55C DDE55 DDJ45C DDJ45 DDJ55C DDJ55 DDM45L1C DDM45L1 DDM55L1C DDM55L1 DDM45L2C DDM45L2 DDM55L2C DDM55L2 DDM45L3C DDM45L3 DDM55L3C DDM55L3 DDR45 DDR55

75

ElectrakTM 30 2P + E busbar / buscom trunking


power and communication distribution

CCA3145C

CCA2145C

CCA14RFC

CCA142XC

CCA14LFC Selection chart (p. 70-71) Dimensions and technical information (p. 86-91) Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 30 2 pole + earth single sided system


2P + E busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on just one side of the bar 2P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options

Pack

Cat. Nos.

Flexible lengths for single sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Tap-off outlets Weight (kg)(1)

25 A

1 1 1 1

BBA140XC BBA142XC CCA140XC CCA142XC

05 2 05 2
Length (m)

25 25 40 40
Tap-off outlets

291 321 294 333


Weight (kg)(1)

Surface mounted right to left


25 A

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBA3145C BBA2145C BBA3141C BBA2141C


40 A

3 2 3 2 3 2 3 2

6 4 3 2 6 4 3 2

447 327 442 324 457 336 452 331

C L N PE

1 1 1 1

BBA340XC BBA342XC CCA340XC CCA342XC

05 2 05 2

25 25 40 40

299 305 302 341

CCA3145C CCA2145C CCA3141C CCA2141C

Feed units for single sided system


Feed units come with 2 x 25 mm cable entry holes and single screw cable terminals for power and also data for buscom varieties Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops Suspended
Weight (kg)(1)

1 1 1 1

BBA14LFC BBA14RFC CCA14LFC CCA14RFC

25 A left 25 A right 40 A left 40 A right

122 149 127 149


Weight (kg)(1) (1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

Surface mounted
1 1 1 1

BBA34LFC BBA34RFC CCA34LFC CCA34RFC

25 A left 25 A right 40 A left 40 A right Centre feed

131 154 131 154


Weight (kg)(1)

1 1

BBA44FC CCA44FC

25 A 40 A

18 18

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

76

ElectrakTM 30 2P + E busbar / buscom trunking


power and communication distribution

CCA3245C

CCA2245C

DDE408C Selection chart (p. 70-71) Dimensions and technical information (p. 86-91)

DDE408

DDE408F

Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 30 2 pole + earth double sided system


2P + E busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on just one side of the bar 2P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets

Pack

Cat. Nos.

Tap-off units
16 A unfused tap-off units Pre-wired tap-off units to pick-up L1+N, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

1 1 1 1

DDE408C DDE42C DDE43C DDE45C

08 2 3 5

L+N

02 04 05 07

13 A fused tap-off units Pre-wired tap-off units to pick-up L1+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBA3245C BBA2245C BBA3241C BBA2241C


40 A

3 2 3 2 3 2 3 2

11 7 6 4 11 7 6 4

485 352 470 347 505 365 496 361

PE N L

C L N PE

CCA3245C CCA2245C CCA3241C CCA2241C

1 1 1 1

DDE408FC DDE42FC DDE43FC DDE45FC

08 2 3 5

L+N

02 04 05 07

Tap-off units rewirable


16 A unfused tap-off unit Pre-wired tap-off units to pick-up L1+N, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

Feed units for double sided system


Double sided feed units come with 2 x 25 mm cable entry holes for each side. Single screw cable terminals are provided for power and also data for buscom varieties Suspended
Weight (kg)(1)

DDF4

L+N

014

13 A fused tap-off unit Pre-wired tap-off units to pick-up L1+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

BBA24LFC BBA24RFC CCA24LFC CCA24RFC

25 A left 25 A right 40 A left 40 A right

129 151 139 161

DDF4

L+N

014

Flexible lengths for double sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
25 A Length (m) Tap-off outlets Weight (kg)(1) (1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

1 1 1 1

BBA240XC BBA242XC CCA240XC CCA242XC

05 2 05 2

25 25 40 40

314 367 325 391

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

77

ElectrakTM 31 3P + E busbar / buscom trunking


power and communication distribution

CCB3145C

CCB2145C

CCB14RFC

CCB142XC

CCB14LFC Selection chart (p. 70-71) Dimensions and technical information (p. 86-91) Integral communication bus suitable for KNX, Lonworks, DALI, protocols etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 31 3 pole + earth single sided system


3P + E busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on just one side of the bar 3P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options

Pack

Cat. Nos.

Flexible lengths for single sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1)

1 1 1 1

BBB140XC BBB142XC CCB140XC CCB142XC

05 2 05 2
Length (m)

25 25 40 40
Rating (A)

304 340 308 356


Weight (kg)(1)

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

Surface mounted right to left


1 1 1 1

1 1 1 1 1 1 1 1

BBB3145C BBB2145C BBB3141C BBB2141C


40 A

3 2 3 2 3 2 3 2

6 4 3 2 6 4 3 2

462 337 458 334 477 347 473 344

CCB3145C CCB2145C CCB3141C CCB2141C

C L2 L1 N PE

BBB340XC BBB342XC CCB340XC CCB342XC

05 2 05 2

25 25 40 40

299 332 300 348

Feed units for single sided system


Feed units come with 2 x 25 mm cable entry holes and single screw cable terminals for power and also data for buscom varieties Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops Suspended
Weight (kg)(1)

1 1 1 1

BBB14LFC BBB14RFC CCB14LFC CCB14RFC

25 A left 25 A right 40 A left 40 A right

125 148 133 155


Weight (kg)(1)

Surface mounted
1 1 1 1

BBB34LFC BBB34RFC CCB34LFC CCB34RFC

25 A left 25 A right 40 A left 40 A right Centre feed

129 152 137 159


Weight (kg)(1)

1 1

BBB44FC CCB44FC

25 A 40 A

18 18

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

78

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

ElectrakTM 31 3P + E busbar / buscom trunking


power and communication distribution

CCB3245C

CCB2245C

DDE408C Selection chart (p. 70-71) Dimensions and technical information (p. 86-91)

DDE408

DDE408F

Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 31 3 pole + earth double sided system


3P + E busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on both sides of the bar 3P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets

Pack

Cat. Nos.

Tap-off units
16 A unfused tap-off units Pre-wired tap-off units to pick up L1, L2+N, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

1 1 1 1 1 1 1 1

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBB3245C BBB2245C BBB3241C BBB2241C


40 A

3 2 3 2 3 2 3 2

11 7 6 4 11 7 6 4

515 372 506 368 545 392 536 388

DDE408C DDE42C DDE43C DDE45C DDG408C DDG42C DDG43C DDG45C

08 2 3 5 08 2 3 5

L+N

L1 + L2 + N

02 04 05 07 02 04 05 07

PE N L1 L2

13 A fused tap-off units


C L2 L1 N PE

CCB3245C CCB2245C CCB3241C CCB2241C

Pre-wired tap-off units to pick-up L1, L2+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

Feed units for double sided system


Double sided feed units come with 2 x 25 mm cable entry holes for each side. Single screw cable terminals are provided for power and also data for buscom varieties Suspended
Weight (kg)(1)

1 1 1 1 1 1 1 1

DDE408FC DDE42FC DDE43FC DDE45FC DDG408FC DDG42FC DDG43FC DDG45FC

08 2 3 5 08 2 3 5

L+N

L1 + L2 + N

02 04 05 07 02 04 05 07

Tap-off units rewirable


16 A unfused tap-off unit Rewirable tap-off units to pick-up L1, L2+N, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

BBB24LFC BBB24RFC CCB24LFC CCB24RFC

25 A left 25 A right 40 A left 40 A right

135 158 149 172


1

Flexible lengths for double sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1)

DDH4

L1 L2 N1

014

13 A fused tap-off unit Rewirable tap-off units to pick-up L1, L2+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

BBB240XC BBB242XC CCB240XC CCB242XC

05 2 05 2

25 25 40 40

345 403 353 435

DDH4F

L1 L2 N1

014

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

79

ElectrakTM 32 4P + E (dual circuit) busbar / buscom trunking


power and communication distribution

CCC3145C

CCC2145C

CCC14RFC

CCC142XC

CCC14LFC Selection chart (p. 72-73) Dimensions and technical information (p. 86-91) Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 32 4 pole + earth (dual circuit) single sided system


Dual circuit busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on just one side of the bar 4 P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options

Pack

Cat. Nos.

Flexible lengths for single sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1)

1 1 1 1

BBC140XC BBC142XC CCC140XC CCC142XC

05 2 05 2
Length (m)

25 25 40 40
Rating (A)

317 359 322 379


Weight (kg)(1)

Surface mounted right to left


1 1 1 1

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBC3145C BBC2145C BBC3141C BBC2141C


40 A

3 2 3 2 3 2 3 2

6 4 3 2 6 4 3 2

477 347 473 344 497 361 493 358

CCC3145C CCC2145C CCC3141C CCC2141C

C L2 N2 L1 N1 PE

BBC340XC BBC342XC CCC340XC CCC342XC

05 2 05 2

25 25 40 40

309 351 314 371

Feed units for single sided system


Feed units come with 2 x 25 mm cable entry holes and single screw cable terminals for power and also data for buscom varieties Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops Suspended
Weight (kg)(1)

1 1 1 1

BBC14LFC BBC14RFC CCC14LFC CCC14RFC

25 A left 129 25 A right 152 40 A left 138 40 A right 161 Surface mounted
Weight (kg)(1)

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

1 1 1 1

BBC34LFC BBC34RFC CCC34LFC CCC34RFC

25 A left 25 A right 40 A left 40 A right Centre feed 25 A 40 A

133 156 142 165


Weight (kg)(1)

1 1

BBC44FC CCC44FC

18 18

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

80

ElectrakTM 32 4P + E (dual circuit) busbar / buscom trunking


power and communication distribution

CCC3245C

CCC2245C

DDE408C Selection chart (p. 72-73) Dimensions and technical information (p. 86-91)

DDE408

DDE408F

Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 32 4 pole + earth (dual circuit) double sided system


Dual circuit busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded white and are located on just one side of the bar 4 P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets

Pack

Cat. Nos.

Tap-off units
16 A unfused tap-off units Pre-wired tap-off units to pick up L1, L2+N, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

1 1 1 1 1 1 1 1

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

DDE408C DDE42C DDE43C DDE45C DDJ408C DDJ42C DDJ43C DDJ45C

08 2 3 5 08 2 3 5

L1 + N1

L2 + N2

02 04 05 06 02 04 05 06

1 1 1 1 1 1 1 1

BBC3245C BBC2245C BBC3241C BBC2241C


40 A

3 2 3 2 3 2 3 2

11 7 6 4 11 7 6 4

546 392 537 388 586 470 577 415

PE N1 L1 N2 L2

13 A fused tap-off units


C L2 N2 L1 N1 PE

Pre-wired tap-off units to pick up L1, L2+N, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

CCC3245C CCC2245C CCC3241C CCC2241C

1 1 1 1 1 1 1 1

Feed units for double sided system


Double sided feed units come with 2 x 25 mm cable entry holes for each side. Single screw cable terminals are provided for power and also data for buscom varieties Suspended
Weight (kg)(1)

DDE408FC DDE42FC DDE43FC DDE45FC DDJ408FC DDJ42FC DDJ43FC DDJ45FC

08 2 3 5 08 2 3 5

L1 + N1

L2 + N2

02 04 05 06 02 04 05 06

Tap-off units rewirable


16 A unfused tap-off units Rewirable tap-off units to pick up required circuit, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

BBC24LFC BBC24RFC CCC24LFC CCC24RFC

25 A left 25 A right 40 A left 40 A right

142 164 160 183


1 1

Flexible lengths for double sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1)

DDF4 DDK4

L1 + N1 L2 + N2

014 014

13 A fused tap-off units Rewirable tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded white, can plug into any tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

BBC240XC BBC242XC CCC240XC CCC242XC

05 2 05 2

25 25 40 40

342 452 391 532

1 1

DDF4F DDK4F

L1 + N1 L2 + N2

014 014

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

81

ElectrakTM 33 4P + E (3 phase) busbar / buscom trunking


power and communication distribution

CCD3145C

CCD2145C

CCD14RFC

CCD142XC

CCD14LFC Selection chart (p. 72-73) Dimensions and technical information (p. 86-91) Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 33 4 pole + earth (3 phase) single sided system


3 phase busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded grey and are located on just one side of the bar 4 P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Trunking lengths can be surface mounted or suspended using the various bracket options

Pack

Cat. Nos.

Flexible lengths for single sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1)

1 1 1 1

BBD140XC BBD142XC CCD140XC CCD142XC

05 2 05 2
Length (m)

25 25 40 40
Rating (A)

317 359 322 379


Weight (kg)(1)

Surface mounted right to left


1 1 1 1

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBD3145C BBD2145C BBD3141C BBD2141C


40 A

3 2 3 2 3 2 3 2

6 4 3 2 6 4 3 2

477 347 475 344 497 361 493 358

CCD3145C CCD2145C CCD3141C CCD2141C

C L3 L2 L1 N1 PE

BBD340XC BBD342XC CCD340XC CCD342XC

05 2 05 2

25 25 40 40

309 351 314 371

Feed units for single sided system


Feed units come with 2 x 25 mm cable entry holes and single screw cable terminals for power and also data for buscom varieties Left feed units are supplied with right end stop Right feed units are supplied with left end stop Centre feed units are supplied with right and left end stops Suspended
Weight (kg)(1)

1 1 1 1

BBD14LFC BBD14RFC CCD14LFC CCD14RFC

25 A left 129 25 A right 152 40 A left 138 40 A right 161 Surface mounted
Weight (kg)(1)

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

1 1 1 1

BBD34LFC BBD34RFC CCD34LFC CCD34RFC

25 A left 25 A right 40 A left 40 A right Centre feed 25 A 40 A

133 156 142 165


Weight (kg)(1)

1 1

BBD44FC CCD44FC

180 180

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

82

ElectrakTM 33 4P + E (dual circuit) busbar / buscom trunking


power and communication distribution

CCD3245C

CCD2245C

DDM408L1C Selection chart (p. 72-73) Dimensions and technical information (p. 86-91)

DDM408L1

DDM408L1FC

Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Electrak 33 4 pole + earth (3 phase) double sided system


3 phase busbar trunking system available in IP 4X and IP 54 versions, with or without integral communications bus circuit Socket outlets are colour coded grey and are located on just one side of the bar 4 P + E trunking lengths Trunking lengths push fit into each other, and feed units or flexible lengths. Double sided trunking must be fixed using suspended fixing brackets

Pack

Cat. Nos.

Tap-off units
16 A unfused tap-off units Pre-wired tap-off units to pick up required circuit, colour coded grey, can plug into any Electrak 33 tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

1 1 1 1 1 1 1 1 1 1 1 1

25 A

Length (m)

Tap-off outlets

Weight (kg)(1)

1 1 1 1 1 1 1 1

BBD3245C BBD2245C BBD3241C BBD2241C


40 A

3 2 3 2 3 2 3 2

11 7 6 4 11 7 6 4

546 392 537 388 586 470 577 415

PE N L1 L2 L3 C L3 L2 L1 N PE

DDM408L1C DDM42L1C DDM43L1C DDM45L1C DDM408L2C DDM42L2C DDM43L2C DDM45L2C DDM408L3C DDM42L3C DDM43L3C DDM45L3C

08 2 3 5 08 2 3 5 08 2 3 5

L1 + N

L2 + N

L3 + N

02 04 05 06 02 04 05 06 02 04 05 06

CCD3245C CCD2245C CCD3241C CCD2241C

13 A fused tap-off units Pre-wired tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

Feed units for double sided system


Double sided feed units come with 2 x 25 mm cable entry holes for each side. Single screw cable terminals are provided for power and also data for buscom varieties Suspended
Weight (kg)(1)

1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1

BBD24LFC BBD24RFC CCD24LFC CCD24RFC

25 A left 25 A right 40 A left 40 A right

142 164 160 183

DDM408L1FC DDM42L1FC DDM43L1FC DDM45L1FC DDM408L2FC DDM42L2FC DDM43L2FC DDM45L2FC DDM408L3FC DDM42L3FC DDM43L3FC DDM45L3FC

08 2 3 5 08 2 3 5 08 2 3 5

L1 + N

L2 + N

L3 + N

02 04 05 06 02 04 05 06 02 04 05 06

Flexible lengths for double sided system


Flexible lengths can be used to change direction, change level or overcome obstructions Suspended right to left
Length (m) Rating (A) Weight (kg)(1) (1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

1 1 1 1

BBD240XC BBD242XC CCD240XC CCD242XC

05 2 05 2

25 25 40 40

342 452 391 532

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

83

ElectrakTM 33 4P + E (3 phase) busbar / buscom trunking


power and communication distribution

DDN4L1

DDN4L1F

Selection chart (p. 74-75) Dimensions and technical information (p. 89) Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems Outlets on one or two sides. IP 4X or IP 54 ingress protection Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack Cat. Nos.

Tap-off units rewirable


16 A unfused tap-off units Rewirable tap-off units to pick up required circuit, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed polarity Weight (kg)(1)

Pack

Cat. Nos.

Tap-off units 4P + E pre-wired (LSOH 5 x 15 mm2 cable)


16 A unfused tap-off units Pre-wired tap-off units to pick up required circuit, colour coded grey, can plug into any Electrak 33 tap-off outlet
Length (m) Fixed polarity Weight (kg)(1)

1 1 1

DDN4L1 DDN4L2 DDN4L3

L1 + N L2 + N L3 + N

014 014 014

13 A fused tap-off units Rewirable tap-off units to pick up required circuit, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed polarity Weight (kg)(1)

1 1 1 1

DDR408 DDR42 DDR43 DDR45

08 2 3 5

L+L+L+N L+L+L+N L+L+L+N L+L+L+N

02 036 050 063

1 1 1

DDN4L1F DDN4L2F DDN4L3F

L1 + N L2 + N L3 + N

014 014 014

Phase selectable tap-off units 2P + E terminals rewirable


16 A unfused tap-off unit Rewirable tap-off units, phase selectable, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed polarity Weight (kg)(1)

DDP4S

L+N

014

13 A fused tap-off unit Rewirable tap-off units, phase selectable, supplied with BS 1362 fuse, colour coded grey, can plug into any Electrak 33 tap-off outlet
Fixed polarity Weight (kg)(1)

DDP4SF

L+N

014

(1) Weights shown are for IP 4X rated buscom. For all other weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components All examples on this page show IP 4X buscom trunking IP rating and trunking type is dictated by the red letters 4 = IP 4X. For IP 54 version, replace 4 with 5 C = Buscom (with communications circuit). For busbar (power only), remove the C

84

ElectrakTM busbar / buscom trunking


fixings and ancillary items

EEA304

EEC348

EEC356

EEB340

EEB344

EEA308

EEA312

EEA328

EEA332

EEA324

EEC352

EEC360

EEC364

Dimensions and technical information (p. 89) Brackets are manufactured from robust galvanised steel, ensuring that the entire installation can be expected to stand up to all normal site conditions
Pack Cat. Nos.

Fixings
Trunking 57 mm edge surface mounting fixing bracket Trunking suspended fixing bracket Trunking suspended fixing bracket c/w cable duct stirrup. Used when running cable duct on top of busbar trunking Luminaire suspension fixing bracket Luminaire 45 mm edge suspension fixing bracket (clip on) Luminaire 57 mm edge suspension fixing bracket (clip on) Open hook luminaire suspended bracket Closed ring on luminaire Cable duct 3 m long x 50 mm(w) x 13 mm(h) Joint bracket cable duct Cable duct fixing bracket

Pack

Cat. Nos.

Ancillary items
2 m empty length for adjusting the length at the end of a run (to be cut) IP 54 outlet cover (spare or replacement) Joint sleeve is used if load is hung off trunking joint or near when joint is centre of a fixing span Left hand end stop spare Right hand end stop spare

1 1 1

EEA304 EEA308 EEA312

1 1 1 1 1

EEC356 EEC360 EEC364 EEC366 EEC368

1 1 1 1 1 1 1 1

EEA324 EEA328 EEA332 EEB340 EEB344 EEC348 EEC357 EEC352

85

ElectrakTM busbar / buscom trunking


technical information

Standards

Electrical test data

25 A

40 A

UOM

ASTA approved to BS EN 60439-2 and IEC 439-2 Manufactured within an approved ISO 9001 : 2008 facility Assessed Quality Assurance Certificate No. 10679 Electrak fully complies with the requirements of BS 7671 : 2008 (IEE Wiring Regulations)

Buscom trunking options


L N PE L2 L1 N PE L2 N2 L1 N1 PE L3 L1 L1 N PE
Communication bus

Derating factor for Electrak 32 single sided 08 Derating factor for Electrak 32 double sided 08 07 Derating factor for Electrak 33 double sided 08 Rated operational voltage (Ue) 230/400 230/400 V Rated insulation voltage (Ui) 500 500 V Frequency (f) 50/60 50/60 Hz Rated impulse withstand voltage 40 40 KV Busbar resistance (R20) 39 27 m/m 42 30 m/m Resistance (R1) Impedance (Z1) 48 34 m/m Reactance (X1) 25 16 m/m Protective conductor 15 15 m/m

Electrak buscom trunking can be used with Electraks cost effective lighting control system, Lightrak KNX, or any other systems using control protocols such as KNX, Lonworks, DALI, etc. Electraks overhead trunking couples high quality engineering with rigidity of design, and provides power for a variety of applications including lighting, heating and ventilation. The robust easy fix modular system permits loads to be suspended directly from the trunking using Electraks various fixing brackets Push fit connection keeps installation costs to a minimum Track lengths simply push fit together

Volt drops Live and neutral : busbars (R1+R2) Feed unit Tap-off 08 m Tap-off 20 m Flexible length assembly 05 m Flexible length assembly 2 m

25 A 90 30 220 520 50 200

40 A 60 24 220 520 35 140

UOM mV/A/m mV/A mV/A mV/A mV/A mV/A

Earth fault loop Impedance : busbar Earth housing Feed unit Tap-off 08m Tap-off 20m Flexible length assembly 05 m Flexible length assembly 2 m Rated conditional short-circuit current (Icc) Rated short time withstand current (Icw) at 1 sec Rated peak short-circuit current (Ipk) Ambient temperature

25 A 45 15 24 230 530 25 100 160 065 0975 350

40 A 30 15 24 230 530 175 70 160 10 15 350

UOM m/m m/m m m m mV/A mV/A KA KA KA C

Mechanical data Number of conductors Busbar conductor cross sectional area Cable terminal capacity Cable terminal capacity bus Tap-off cable 16 A Tap-off cable 13 A fused Tap-off entry Feed unit entry holes power Feed unit entry holes bus IP rating (optional)

25 A

40 A

UOM mm2 mm2 mm2 mm2 mm2 mm mm mm

Feed units
25 A rated - max. conductor size 6 mm2 40 A rated - max. conductor size 16 mm2 Double sided trunking feed units have power cable terminals on both sides. IP 4X galvanised steel IP 54 ABS

2-10 2-10 40 60 60 160 15 15 15 15 15 15 160 160 250 250 160 160 4 X (54) 4 X (54)

Direct protection by enclosure. Indirect protection by protective circuit

2 pole + earth + comms

Comms bus Max. conductor size 15 mm2 Red + Black -

86

ElectrakTM busbar / buscom trunking


technical data

Communication control circuit Type Construction Insulation - conductor Sheath Rated insulation voltage (Ui) (between power circuit and bus) Bus cable (LSOH) Sheathed 05 mm2 copper twisted pair Flame retardant low emission HCL LSOH material 500 V

Max. bus operating voltage 50 V Max. bus operating current 065 A Max. conductor resistance (@20C) 732 /km Max. mutual capacitance 100 nf/km Material specifications Busbar trunking housing Galvanised steel Busbars High conductivity copper Busbar insulator Flame retardant LSOH to BS 7211 Trunking connector / tap-off entry box / cable connector Flame retardant polycarbonate Tap-off housing Flame retardant polycarbonate Trunking connector blades / tap-off blades Copper Feed unit IP 4X Galvanised steel Feed unit IP 54 ABS Flexible length conduit Flame retardant LSOH nylon Feed unit terminals / earth block Brass Brackets Galvanised steel 13 A tap-off, fuse To BS 1362, ASTA approved Durability Electrak power distribution systems are well designed and extremely robust. They can be expected to stand up to all normal site conditions Electrak has been short circuit strength tested by ASTA Earth fault loop impedance BS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow the protective device to operate within the specified time, which for socket outlets is 04 seconds The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite Busbar trunking rating in ambient temperatures Average ambient air temperature Rating factor (K1) 25C 11 30C 105 35C 1 40C 095 45C 090 50C 085

For ambient temperatures other than 35C apply the multiplier factor K1 to the rated current Busbar trunking mechanical loading For point loads and evenly distributed loads the maximum weight that can be supported is given below Maximum loading for suspended busbar trunking Fixing distance (m) Max. point load (deflection = 1/500 x span) (Kg) Max. distributed load (deflection = 1/500 x span) (Kg) Max. point load (deflection = 1/350 x span) (Kg) Max. distributed load (deflection = 1/350 x span) (Kg) 15 20 33 33 55 2 17 28 24 40 25 13 22 18 30 3 12 20 16 26 35 9 15 10 16 4 7 12 9 15

Maximum loading for surface mounted busbar trunking Fixing distance in metres (m) Max. point load (deflection = 1/500 x span) (Kg) Max. distributed load (deflection = 1/500 x span) (Kg) Max. point load (deflection = 1/350 x span) (Kg) Max. distributed load (deflection = 1/350 x span) (Kg) 15 10 16 13 20 2 6 10 10 16 25 45 75 7 11 3 4 7 6 10 35 35 6 5 8 4 3 5 0 0

Notes 1. Where trunking joints occur in the middle of the suspension span, and weight is to be suspended from that point, it is recommened to use a strenghting bracket EEC364 over the joint to stop deflection 2. If the load requirements exceed the above figures, please contact us on +44 (0) 845 600 6266 For design information and technical specification, please contact us on +44 (0) 845 600 6266 Suspension rods and fixings should be of suitable size to carry the weight of both the track and suspended load

87

ElectrakTM busbar / buscom trunking


dimensions

Fixing dimensions
Busbar trunking 3 m
05 m outlet spacings 220 1955 500 500 3 000 500 500 500 3045

1955 1 m outlet spacings

1 000

1 000

8045

Busbar trunking 2 m
05 m outlet spacings 220 1955 500 2 000

Busbar trunking End view


45 500 500 3045 32

57

1955 1 m outlet spacings

1 000

8045

Suspended feed unit Feed unit right


34 57 60 54 4 x 25 4 x 25 52 104 148

Feed unit left

Single sided system

Double sided system

209

308

220

209

517

429

End view both have 2 x 16 mm holes extra in comms feed

End stop right

End stop left

Surface feed unit end view


148

52 220 10 320

2 x 25

Centre feed front view


50 2 x 25 755 57 218

220

300

308

828

All dimensions (mm) are nominal

88

Cat. No. EEA304 Surface trunking fixing bracket with trunking clipped in
107 75 15 60 92 75 30 7

Cat. No. EEA324 Luminaire suspended fixing bracket


82

997

945

22
57 85 38

8.5 12

21

Cat. No. EEA308 Suspended trunking fixing bracket


82 38 85 21 12

Cat. No. EEA328 Luminaire 45 mm edge suspension fixing bracket

85 130 125 108 13 30 60 6 6 35

Cat. No. EEA332 Luminaire 57 mm edge suspension fixing bracket Cat. No. EEA312 Suspended trunking fixing bracket cable duct stirrup
82 38 85 39 78 85 6

70

21

12

85
6 30

163

141

Fused tap-off

535

Cat. No. EEC352 Cable duct fixing bracket


77 50 35 13

Tap-off fuse removal

Fuse holder

Pre-wired tap-offs 33 mm deep


95 59

68

Cat. No. EEB344 Closed ring hook

Cat. No. EEB340 Open hook


96
M5

Rewirable and phase selection tap-offs 35 mm deep

70

70

M5

68

96

89

ElectrakTM busbar / buscom trunking


installation

Design and installation


Electraks busbar trunking system comprises continuous lengths of galvanised steel trunking in either a natural or painted finish available in 2 m and 3 m lengths with an integral connector and pitched tap-off outlets on one or both sides Each trunking run commences with a feed unit for electrical cable termination. The connection between the trunking, the feed unit and subsequent trunking lengths is push fit and requires no tools to terminate the connection or ensure good earthing. Each complete track run is finished with an end stop. Flexible lengths can be used to overcome obstructions or used as corners where required The trunking system is available with IP 4X or IP 54 ingress protection, fully factory tested and ASTA approved to BS EN 60439-2 : 2008 End stop Push fit connection

1 2

To install - push fit parts together To take apart - use a screwdriver to depress the locking catch

2 1
Left feed unit

2
Busbar trunking lengths

2 1

2
Push in to release

Considerations before installation Calculate the distance between fixing brackets - the maximum fixing distance should not exceed 4 m. If loads are to be hung, please consult loading charts on page 87. The maximum busbar trunking weight is 2 kg/m When fixing brackets to drop rods or surfaces, see mounting details below Suspended trunking fixing brackets

Cable duct clips into bracket EEA312 When using cable duct along trunking

EEA308

EEB344 Surface mounted trunking fixing brackets

EEC352 Cable duct bracket

2 1
EEA304 57 mm Edge surface fixing bracket Considerations before installation Ensure surface is level. Screw fix through both fixing holes of surface fixing brackets to surface with No. 8 fixing screws Hook trunking into place and push fit to close

90

Luminaire mounting fixing brackets : suspended trunking

EEA324 Luminaire fixing brackets

EEA328 45 mm Edge luminaire fixing brackets (maximum load 5 kg)

Luminaire mounting fixing brackets : surface trunking

EEA304

EEA304

EEA332 EEA332

EEB340

EEB344

EEA332 57 mm Edge luminaire fixing bracket (maximum load 5 kg) See maximum loading charts p. 87

91

P. 8 Lighting control systems overview

ElectrakTM LightrakTM KNX proprietary lighting control

P. 95 Switching devices

P. 8 Lighting control systems overview

ElectrakTM buscom trunking for DALI lighting installations

P. 97 Tap-off units

Lighting control
NEW IN 2010
Distribution box
for DALI lighting installations (p. 96)

92

P. 68 Introduction to lighting control

P. 94 System components

P. 94 Lighting control units

P. 95 Sub-cabling to luminaires

P. 98 Technical information

P. 68 Introduction to lighting control

NEW P. 96 Distribution box for DALI lighting installations

P. 96 Tap-offs for use with distribution box

P. 97 System components

P. 101 Technical information

93

LightrakTM KNX
lighting control system

- -/- -

Lighting control unit FFD054

- -/- -

Lighting control unit FFD054

- - - - - /- - - - -

- - - - /- - - -

Timed event controller FFA006

Dimensions and technical information (p. 98-100) Proprietory lighting control system to work alongside Electraks 25 and 40 A buscom trunking with integral communications bus High speed installation. Lighting control units factory configured Covers all lighting control requirements. Uses European standard KNX open protocol and KNX/EIB ETS software (PC configurable) Interoperable with other KNX devices. Designed and manufactured in the UK from robust galvanised steel
Pack Cat. Nos.

System components
Statutory warning plaque Timed event controller (flush) Timed event controller (surface) Powered line coupler Track power supply unit Line power supply Signal cable 100 m Eib to RS232 interface USB to KNX interface

Pack

Cat. Nos.

1 1 1 1 1 1 1 1 1

FFA001 FFA004 FFA006 FFA008 FFA010 FFA012 FFA014 FFA016 FFA018

Lighting control units - 9 outputs (fully addressable)


Analogue dimming (1-10 V) Track mounted (standard buscom) L1 Key 'B' track mounted (3 phase buscom) L2 Key 'B' track mounted (3 phase buscom) L3 Key 'B' track mounted (3 phase buscom) Rewirable surface mounted Digital dimming (DSI) Track mounted (standard buscom) L1 Key 'B' track mounted (3 phase buscom) L2 Key 'B' track mounted (3 phase buscom) L3 Key 'B' track mounted (3 phase buscom) Rewirable surface mounted

1 1 1 1 1

FFD054 FFD054B1 FFD054B2 FFD054B3 FFD055 FFD056 FFD056B1 FFD056B2 FFD056B3 FFD057

Lighting control units - 6 outputs (2 switching channels)


Non-dimming units
1 1 1 1

1 1 1 1 1

FFD050 FFD050B1 FFD050B2 FFD050B3 FFD052 FFD052B1 FFD052B2 FFD052B3

Track mounted (standard buscom) L1 Key 'B' track mounted (3 phase buscom) L2 Key 'B' track mounted (3 phase buscom) L3 Key 'B' track mounted (3 phase buscom) Dimming units (analogue 1-10 V) Track mounted (standard buscom) L1 Key 'B' track mounted (3 phase buscom) L2 Key 'B' track mounted (3 phase buscom) L3 Key 'B' track mounted (3 phase buscom)

1 1 1 1

For Electrak buscom / busbar trunking

See p. 70-85 94

LightrakTM KNX
lighting control system

- -/- -

Multi-gang switch interface FFB020

- -/- -

5 m CAT 5 lead 1 gang key switch FFB032 Compact presence detector FFC047 4 gang switch FFB022-4 FFF205

- - - - - /- - - - -

- - - - /- - - -

5 m sub-cabling to luminaires FFE085

Dimensions and technical information (p. 98-100) Proprietory lighting control system to work alongside Electraks 25 and 40 A buscom trunking with integral communications bus High speed installation. Lighting control units factory configured Covers all lighting control requirements. Uses European standard KNX open protocol and KNX/EIB ETS software (PC configurable) Interoperable with other KNX devices. Designed and manufactured in the UK from robust galvanised steel
Pack Cat. Nos.

Sub-cabling to luminaires
Plugs (male)

Pack

Cat. Nos.

Switching devices
Compact presence detector Switches for 1 gang back box 1 gang switch 1 gang key switch 1 gang key switch - surface (including back box) 2 gang switch Switches for 2 gang back box 2 gang switch 3 gang switch 4 gang switch Switches for 2 x 2 gang back box 5 gang switch 6 gang switch 7 gang switch 8 gang switch Multi-gang switch interface 8 gang scene set switch Back boxes 1 gang 2 gang 2 x 2 gang

FFC047 FFB030 FFB032 FFB033 FFB034 FFB022-2 FFB022-3 FFB022-4 FFB024-5 FFB024-6 FFB024-7 FFB024-8 FFB020 FFC048 FFB036 FFB026 FFB028

1 1

FFE060 FFE080 FFE065 FFE075 FFE085 FFE095 FFE105 FFE115 FFE120 FFE125

4 pole rewirable plug (male) 6 pole rewirable plug (male) Leads (5 m LSOH) With 4 pole male plug to free end 3 core With 4 pole male plug to free end 4 core With 6 pole male plug to free end 5 core With 6 pole male plug to free end 6 core With 4 pole male plug to 4 pole female plug 4 core With 6 pole male plug to 6 pole female plug 6 core With 6 pole male plug to free end 3 core (no dimming) With 6 pole male plug to free end 4 core (no dimming)

1 1 1 1 1 1 1 1

1 1 1 1

1 1 1

1 1 1 1 1 1

1 1 1

CAT 5 cabling to switching


1 1

FFF205 FFF210

5 m CAT 5 lead plug to plug 10 m CAT 5 lead plug to plug

A dedicated Lightrak design, quotation and commissioning service is available to help you achieve the optimum use of the Lightrak system email : lightrak.uk@legrand.co.uk 95

Distribution box for DALI lighting installations


power and communication

Track mountable distribution box

- -/- -

DDB109

- -/- -

03 m tap-off with GST connector DDD406G

- - - - - /- - - - - - - - - /- - - -

- - - - - /- - - - - - - - - /- - - -

5c flex with 6 pole GST connector FFE085

Dimensions and technical information (p. 101) A simple and convenient marshalling box that enables power and DALI signalling to be distributed easily and cost effectively to the luminaires DALI switching devices can also be plugged in, enabling them to connect to the DALI network The distribution box can be used as a stand alone system or used in conjunction with the buscom system shown opposite
Pack Cat. Nos.

Distribution box
9 outputs and 4 switching inputs 6 pole GST connector

Pack

Cat. Nos.

Luminaire sub-cabling
Male plug only (to be wired on site) to blue/black 6 pole GST connector

1 1 1

FFE080 Pre-wired to blue/black 6 pole GST connector


Length (m) Conductors

DDB109 DDB209

Track mountable Surface mountable

Tap-offs for use with distribution box


Sky blue un-fused tap-off unit wired to blue/black 6 pole GST connector
16 A Length (m) Conductors Fuse

1 1

FFE085 FFE095

5 5

5c cable 6c cable

Switching sub-cabling
Sub-cabling to switches 2 pole GST connector
Length (m) Conductors

1 1 1

DDD406G DDD436G DDD456G

0.3 3 5

L1 + N1 and D+, D-

Unfused
1 1

13 A sky blue fused tap-off unit wired to blue/black 6 pole GST connector
13 A Length (m) Conductors Fuse

FFE200 FFE250

Plug only Prewired

2c cable

1 1 1

DDD406FG DDD436FG DDD456FG

0.3 3 5

L1 + N1 and D+, D-

Fused

96

Buscom trunking for DALI lighting installations


power and communication 40 A IP 4X

- -/- -

3 m buscom length CDC3145C

- -/- -

- - - - - /- - - - - - - - - /- - - -

- - - - - /- - - - - - - - - /- - - -

Dimensions and technical information (p. 101) Lighting busbar system complete with integral communication bus. Designed and configured to supply power and enable both KNX or LonWorks protocols to be used in conjunction with DALI lighting control. This high specification system is rated at 40 A

Pack

Cat. Nos.

System components
Outlets colour : sky blue Buscom trunking lengths
Length (m) No. of tap-off outlets

Pack

Cat. Nos.

Tap-off units
Power and DALI tap-offs free end 2 pole + E + DALI pair pre-wired (LSOH 5 x 15 mm2 cable) Colour : sky blue

1 1

CDC3145C CDC2145C

3 2

6 4

C DALI + DALI L N

16 A
1 1

Length (m)

Conductors

Fuse

Feed units suspended 40 A


1 1

DDD435 DDD455 5A

3 5
Length (m)

L1 + N1 and D+, DConductors

Unfused
Fuse

CDC14LFC Left CDC14RFC Right Feed units surface 40 A


1 1

DDD435F DDD455F

3 5

L1 + N1 and D+, D-

Fused

1 1

CDC34LFC Left CDC34RFC Right Flexible lengths suspended 40 A


Length (m)

Power and DALI tap-offs wired to GST 18/5 connectors 2 pole + E + DALI pair pre-wired (LSOH 5 x 15 mm2 cable) to GST18/5 (POWDER BLUE) Colour : sky blue 16 A
1 1
Length (m) Conductors Fuse

1 1

CDC140XC Right to left CDC142XC Right to left

05 2
Length (m)

Flexible lengths surface 40 A


1 1

DDD435G DDD455G 5A

3 5
Length (m)

L1 + N1 and D+, DConductors

Unfused
Fuse

CDC340XC Right to left CDC342XC Right to left

05 2
1 1

For fixings and ancillary items (see p. 85)

DDD435FG DDD455FG

3 5

L1 + N1 and D+, D-

Fused

Power only tap-offs free end 2 pole + E pre-wired (LSOH 3 x 15 mm2 cable) Colour : white 16 A
1 1 1 1
Length (m) Conductors Fuse

DDE408 DDE42 DDE43 DDE45 13 A

08 2 3 5
Length (m)

L1 + N1

Unfused

Conductors

Fuse

1 1 1 1

DDE408F DDE42F DDE43F DDE45F

08 2 3 5

L1 + N1

Fused

KNX only tap-offs free end KNX communications control circuit tap-offs Colour : sky blue
Length (m) Conductors

1 1

DDC405C DDC410C

5 10

KNX only

97

LightrakTM KNX
technical information

Technical specification
Each line coupler can support 64 bus devices (lighting control units and multi-gang switch interface units) A maximum of 15 line couplers may be linked with a main bus line together to form an area; therefore an area can support up to 960 devices The system may be further expanded with the addition of a backbone bus line which would allow the linking together of 15 main bus lines via 15 line couplers, therefore any single system could support 14 400 devices By utilising additional line couplers this total can exceed 64 000 devices (for additional details, if required, please contact us on +44 (0) 845 600 6266) Within any bus line the following cable lengths are permitted : Power supply unit to bus device 350 m maximum Bus device to bus device 700 m maximum Total bus line length 1 000 m maximum Minimum distance between 2 power supply units on one line is 200 m(1)

Line power supply FFA012


Connections 230 V : screw connection block Bus : screw connection block Physical specifications Housing : galvanised steel, natural finish Dimensions : length 358 mm, width 110 mm, depth 75 mm Weight : approximately 195 kg Technical specifications Supply voltage : 230 V 50/60Hz Protection (supply) : 13 A BS 362 fused spur Internal protection : 63 A fuse to IEC 127-2 Secondary output voltage : 30 Vdc +/- 2 V Secondary output current : 640 mA EMC complies with : EN 50090-2-2 : 1997, EN 55022B Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Powered line coupler FFA008


Connections 230 V : screw connection block Primary line : screw connection block Secondary line : screw connection block Physical specifications Housing : galvanised steel, natural finish Dimensions : length 358 mm, width 200 mm, depth 75 mm Weight : approximately 2750 kg Technical specifications Supply voltage : 230V 50/60Hz Protection (supply) : 13 A BS 1362 fused spur Internal protection : 63 A fuse to IEC127-2 Primary line load : 15 mW Secondary line load : 200 mW Secondary output voltage : 30Vdc +/- 2 V Secondary output current : 630 mA EMC complies with : EN 50090-2-2 : 1997, EN 55022B Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Lighting control unit FFD050


Connections 4 RJ45 inputs : CAT 5 providing switching input 6 GST/4 providing 230 V to luminaires L1 Switched live brown E Earth green / yellow N Neutral blue L2 Maintained live black Physical specifications Housing : galvanised steel, natural finish Dimensions : length 291 mm, width 144 mm, height 53 mm plus 9 mm bracket clearance from busbar trunking Weight : approximately 166kg Technical specifications Supply voltage : 230 V 50/60 Hz Maximum load : 10 A BS 1362 fuse fitted in tap-off Maximum power : 2 300 VA Bus voltage : 30 Vdc +/- 2 V Tap-off ASTA approved : BS EN 60439-2 : 2000 EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Busbar trunking mounted power supply unit FFA010


Connections 230 V : Electrak integrated plug Bus : Electrak integrated plug Physical specifications Housing : galvanised steel, natural finish Dimensions : length 330 mm, width 110 mm, height 60 mm 9 mm bracket clearance from busbar trunking Weight : approximately 190 kg Technical specifications Supply voltage : 230 V 50/60 Hz Protection (supply) : 13 A BS 1362 fuse fitted in tap-off Internal protection : 63 A fuse to IEC 127-2 Secondary output voltage : 30 Vdc +/- 2 V Secondary output current : 640 mA Tap-off ASTA approved : BS EN 60439-2 : 2000 EMC complies with : EN 50090-2-2 :1997, EN 55022B Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Lighting control unit - dimming FFD052


Connections 4 RJ45 inputs : CAT 5 providing switching input 6 GST/6 providing 230 V to luminaires L1 Switched live brown E Earth green / yellow N Neutral blue L2 Maintained live black 2 Dimming common white 3 Dimming red Physical specifications Housing : galvanised steel, natural finish Dimensions : length 291 mm, width 144 mm, height 53 mm plus 9 mm bracket clearance from busbar trunking Weight : approximately 166 kg Technical specifications Supply voltage : 230 V 50/60 Hz Maximum load : 10 A BS 1362 fuse fitted in tap-off Maximum power : 2 300 VA Bus voltage : 30 Vdc +/- 2 V Tap-off ASTA approved : BS EN 60439-2 : 2000 EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

(1) Electrak manufacture a busbar trunking mounted power supply unit for this application

98

Lighting control unit analogue dimming FFD054/FFD056


Connections 4 RJ45 inputs : CAT 5 providing switching input 9 GST/6 providing 230 V to luminaires L1 Switched live brown E Earth green / yellow N Neutral blue L2 Maintained live black 2 Dimming common white 3 Dimming red Physical specifications Housing : galvanised steel, natural finish Dimensions : length 377 mm, width 182 mm, depth 53 mm plus 9 mm bracket clearance from busbar trunking Weight : approximately 175 kg Technical specifications Supply voltage : 230 V 50/60Hz Maximum load : 10 A BS 1362 fuse fitted in tap-off Maximum power : 2 300 VA Bus voltage : 30 Vdc +/- 2 V Tap-off ASTA approved : BS EN 60439-2 : 2000 EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

4 gang switch FFB022-4


Physical specifications Housing : steel back box 132 mm x 72 mm minimum 48 mm deep Dimensions : length 125 mm, width 64 mm, height 41 mm Weight : approximately 0668 kg Technical specifications Supply voltage : 9 Vdc EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

8 gang switch FFB024-8


Physical specifications Housing : steel back box 136 mm x 136 mm minimum 52 mm deep Dimensions : length 127 mm, width 122 mm, height 41 mm Weight : approximately 130 kg Technical specifications Supply voltage : 9 Vdc EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Lighting control unit DSI dimming FFD055/FFD057


Connections 4 RJ45 inputs : CAT 5 providing switching input 9 GST/6 providing 230 V to luminaires L1 Switched live brown E Earth green / yellow N Neutral blue L2 Maintained live black 2 Dimming common white 3 Dimming red Physical specifications Housing : galvanised steel, natural finish Dimensions : length 370 mm, width 250 mm, depth 55 mm plus 9 mm bracket clearance from busbar trunking Weight : approximately 190 kg Technical specifications Supply voltage : 230 V 50/60 Hz Maximum load : 10 A Maximum power : 2 300 VA Bus voltage : 30 Vdc +/- 2 V EMC complies with : EN 50090-2-2 : 1997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

Multi-gang switch interface FFB020


Connections 230 V : Electrak integrated tap-off Bus : Electrak integrated tap-off Switch : CAT 5 lead (RJ45 to RJ45) Physical specifications Housing : galvanised steel, natural finish Dimensions : length 126 mm, width 102 mm, height 46 mm plus 45 mm mounting bracket Weight : approximately 066 kg Technical specifications Supply voltage : 230 V 50/60 Hz Protection : 3 A BS 1362 fuse fitted in tap-off Nominal load : 24 mA Maximum bus load : 12 mA Tap-off ASTA approved : BS EN 60439-2 : 2000 EMC complies with : EN 50090-2-2 : 997 Climatic condition class : 3K4 (5C to 40C) IP rating : 4x Certification : KNX certified

System topology schematic diagram


Bus line (max. 64 LCU) Repeater power line coupler 1.5.64

Bus line (max. 64 LCU)

1.5.128 EIB standard bus cable

Main line powered line coupler 1.1 .0 1.2.0 1.3.0 1.4.0 1.5.0 1.15.0 (maximum) AREA 1 main bus line

1.5.192 (maximum)

EIB standard bus cable interconnecting main line powered line coupler AREA 2 main bus line AREA 3 main bus line

Backbone powered line coupler 1.0. 1.0.1 1.0.2 1.0.3 1.0.4 1.0.15

AREA 4 main bus line AREA 15 main bus line (maximum)

Backbone power supply unit

Backbone bus line EIB standard bus cable interconnecting backbone powered line coupler

99

LightrakTM KNX
typical layout

Example of ceiling layout for Lightrak KNX fully addressable system


Layout key
Electrical distribution board Power cable EIB Bus cable Luminaires Outputs 1 to 9 Emergency luminaires K Multi-gang trunking interface 1 to 8 gang wall switch Emergency lighting key switch Presence detector Timed event controller Lightrak buscom trunking Feed unit Lighting control unit Powered line coupler 1/1 Lighting control unit number and position on trunking Scene setting

3/1

1/1

Buscom Trunking Run 1


K 2/1 4G

Plug in leads
2/2 1/2

3/2

Buscom Trunking Run 3

Plug in power leads

Buscom Trunking Run 2

1/3 1G

2/3 3/3

3/4

1/4

2/4

4G

3/5

100

Buscom and distribution box for DALI lighting installations


technical information

Distribution box - specification


General ratings Track current rating : 16 A Overload capability : 20% to BS5733 Rated voltage: 250 V a.c. Overvoltage category III to BS5733, BS EN 50090-2-2 Rated impulse withstand : 4 kV Dali control tracks : minimum cross-section 15 mm EMC requirements Immunity EN61000-6-1 Residential, commercial and light industrial Emission EN 61000-6-3 Residential, commercial and light industrial Lighting connection terminals 9 off sets 6 pole 92.031.0058.1 black PCB female GST18i3L B1V 92.031.0458.1 pastel blue PCB female GST18i3L B1V Device inputs 4 off sets 2 pole - 93.081.1558.0 white PCB female ST17/2 BFV1 Power and DALI input 1 off set 6 pole 92.031.0058.1 black PCB female GST18i3L B1V 92.031.0458.1 pastel blue PCB female GST18i3L B1V Live and switched live via 2 x 10 A 5 x 20 mm PCB mounted fuse holders

Standards

ASTA approved to BS EN 60439-2 and IEC 439-2 Manufactured within an approved ISO 9001 : 2008 facility Assessed Quality Assurance Certificate No. 10679 Electrak fully complies with the requirements of BS 7671 : 2008 (IEE Wiring Regulations)

Technical data
Communication control circuit Type Construction Insulation - conductor Sheath Rated insulation voltage (Ui) (between power circuit and bus) Max. bus operating voltage Max. bus operating current Max. conductor resistance (@20C) Max. mutual capacitance Material specifications Busbar trunking housing Busbars Busbar insulator Trunking connector / tap-off entry box / cable connector Tap-off housing Trunking connector blades / tap-off blades Feed unit IP 4X Flexible length conduit Feed unit terminals / earth block Brackets 13 A tap-off, fuse Bus cable (LSOH) Sheathed 05 mm2 copper twisted pair Flame retardant low emission HCL LSOH material 500 V 50 V 065 A 732 /km 100 nf/km Galvanised steel High conductivity copper Flame retardant LSOH to BS 7211 Flame retardant polycarbonate Flame retardant polycarbonate Copper Galvanised steel Flame retardant LSOH nylon Brass Galvanised steel To BS 1362, ASTA approved

Durability Electrak power distribution systems are well designed and extremely robust. They can be expected to stand up to all normal site conditions. Electrak has been short circuit strength tested by ASTA Earth fault loop impedance BS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow the protective device to operate within the specified time, which for socket outlets is 04 seconds The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite Busbar trunking rating in ambient temperatures Average ambient air temperature Rating factor (K1) 25C 11 30C 105 35C 1 40C 095 45C 090 50C 085

For ambient temperatures other than 35C apply the multiplier factor K1 to the rated current

101

Cat. Nos.

Page No.

Cat. Nos.

Page No. 77 76 77 76 78 79 78 79 78 80 81 80 81 80 82 83 82 97 31 30

Cat. Nos.

Page No. 30 31 30 31 32

Cat. Nos.

Page No. 77 77 79 97 77 77 79 97 77 97 77 97 77 81 79 81 83 84 16

Cat. Nos.

Page No. 85 32

Cat. Nos.

Page No. 57 54 57 54 57 54 57 54 55 57

B
BBA140XC BBA142XC BBA14LFC BBA14RFC BBA2141C BBA2145C BBA2241C BBA2245C BBA240XC BBA242XC BBA24LFC BBA24RFC BBA3141C BBA3145C BBA3241C BBA3245C BBA340XC BBA342XC BBA34LFC BBA34RFC BBA44FC BBB140XC BBB142XC BBB14LFC BBB14RFC BBB2141C BBB2145C BBB2241C BBB2245C BBB240XC BBB242XC BBB24LFC BBB24RFC BBB3141C BBB3145C BBB3241C BBB3245C BBB340XC BBB342XC BBB34LFC BBB34RFC BBB44FC BBC140XC BBC142XC BBC14LFC BBC14RFC BBC2141C BBC2145C BBC2241C BBC2245C BBC240XC BBC242XC BBC24LFC BBC24RFC BBC3141C BBC3145C BBC3241C BBC3245C BBC340XC BBC342XC BBC34LFC BBC34RFC BBC44FC BBD140XC BBD142XC BBD14LFC BBD14RFC BBD2141C BBD2145C BBD2241C BBD2245C BBD240XC BBD242XC BBD24LFC BBD24RFC BBD3141C BBD3145C BBD3241C BBD3245C BBD340XC BBD342XC BBD34LFC BBD34RFC BBD44FC 76 77 76 77 76 78 79 78 79 78 80 81 80 81 80 82 83 82 83 82

C
CCA140XC CCA142XC CCA14LFC CCA14RFC CCA2141C CCA2145C CCA2241C CCA2245C CCA240XC 76 77

CCA242XC CCA24LFC CCA24RFC CCA3141C CCA3145C CCA3241C CCA3245C CCA340XC CCA342XC CCA34LFC CCA34RFC CCA44FC CCB140XC CCB142XC CCB14LFC CCB14RFC CCB2141C CCB2145C CCB2241C CCB2245C CCB240XC CCB242XC CCB24LFC CCB24RFC CCB3141C CCB3145C CCB3241C CCB3245C CCB340XC CCB342XC CCB34LFC CCB34RFC CCB44FC CCC140XC CCC142XC CCC14LFC CCC14RFC CCC2141C CCC2145C CCC2241C CCC2245C CCC240XC CCC242XC CCC24LFC CCC24RFC CCC3141C CCC3145C CCC3241C CCC3245C CCC340XC CCC342XC CCC34LFC CCC34RFC CCC44FC CCD140XC CCD142XC CCD14LFC CCD14RFC CCD2141C CCD2145C CCD2241C CCD2245C CCD240XC CCD242XC CCD24LFC CCD24RFC CCD3141C CCD3145C CCD3241C CCD3245C CCD340XC CCD342XC CCD34LFC CCD34RFC CCD44FC CDC140XC CDC142XC CDC14LFC CDC14RFC CDC2145C CDC3145C CDC340XC CDC342XC CDC34LFC CDC34RFC CR0000 CR0001 CR0002 CR0003 CR0004 CR0005 CR0006 CR0007 CR0010 CR0011 CR011 CR012 CR013 CR014

CR015 CR016 CR020 CR022 CR023 CR024 CR025 CR026 CR028 CR029 CR030 CR031 CR033 CR036 CR042 CR043 CR044 CR100 CR101 CR104 CR105 CR110 CR111 CR122 CR123 CR124 CR125 CR132 CR133 CR2001 CR2002 CR2003 CR2004 CR2005 CR2006 CR2100 CR2101 CR2102 CR2104 CR2105 CR2106 CR2107 CR2109 CR2112 CR2113 CR2114 CR2115 CR2116 CR4001 CR4002 CR4003 CR4004 CR4005 CR4006 CR4100 CR4101 CR4102 CR4104 CR4105 CR4106 CR4108 CR4111 CR4112 CR4113 CR4115 CR4117 CR4118 CR5102 CR5202 CR5302 CR5402

D
DA1123 DA1183 DA1243 DA1363 DDB109 DDB209 DDC405C DDC410C DDD406FG DDD406G DDD435 DDD435F DDD435FG DDD435G DDD436FG DDD436G DDD455 DDD455F DDD455FG DDD455G DDD456FG DDD456G DDE408 DDE408C DDE408F 16 16 96 97 96 97 96 97 96 97 77 97

DDE408FC DDE42 DDE42C DDE42F DDE42FC DDE43 DDE43C DDE43F DDE43FC DDE45 DDE45C DDE45F DDE45FC DDF4 DDF4F DDG408C DDG408FC DDG42C DDG42FC DDG43C DDG43FC DDG45C DDG45FC DDH4 DDH4F DDJ408C DDJ408FC DDJ42C DDJ42FC DDJ43C DDJ43FC DDJ45C DDJ45FC DDK4 DDK4F DDM408L1C DDM408L1FC DDM408L2C DDM408L2FC DDM408L3C DDM408L3FC DDM42L1C DDM42L1FC DDM42L2C DDM42L2FC DDM42L3C DDM42L3FC DDM43L1C DDM43L1FC DDM43L2C DDM43L2FC DDM43L3C DDM43L3FC DDM45L1C DDM45L1FC DDM45L2C DDM45L2FC DDM45L3C DDM45L3FC DDN4L1 DDN4L1F DDN4L2 DDN4L2F DDN4L3 DDN4L3F DDP4S DDP4SF DDR408 DDR42 DDR43 DDR45 DF1010 DP1313 DP1327 DP1332 DP1513 DP1527 DP1532 DW1000 DW1010 DW1020 DZ1210 DZ1230

EEC364 EEC366 EEC368 EG0010 EG0020 EG0031 EG0050 EG0055 EG1111 EG1112

F
FFA001 FFA004 FFA006 FFA008 FFA010 FFA012 FFA014 FFA016 FFA018 FFB020 FFB022-2 FFB022-3 FFB022-4 FFB024-5 FFB024-6 FFB024-7 FFB024-8 FFB026 FFB028 FFB030 FFB032 FFB033 FFB034 FFB036 FFC047 FFC048 FFD050 FFD050B1 FFD050B2 FFD050B3 FFD052 FFD052B1 FFD052B2 FFD052B3 FFD054 FFD054B1 FFD054B2 FFD054B3 FFD055 FFD056 FFD056B1 FFD056B2 FFD056B3 FFD057 FFE060 FFE065 FFE075 FFE080 FFE085 FFE095 FFE105 FFE115 FFE120 FFE125 FFE200 FFE250 FFF205 FFF210 94 95 94 95 96 95

H
H001 H002 HA1952AA HA1952AB HA1952AC HA1953AA HA1954AA HA3952AA HA3952AB HA3952AC HA3953AA HA3954AA HB1932AA HB1932AB HB1932AC HB1933AA HB1934AA 61

E
EEA304 EEA308 EEA312 EEA324 EEA328 EEA332 EEB340 EEB344 EEC348 EEC352 EEC356 EEC357 EEC360 85

I
IAB002A IAB002B IAB002C IAB002D IAB002N 54 57

IAB002P IAB002Q IAB002R IAB002S IAB002T IAB003A IAB003B IAB003C IAB003D IAB003N IAB003P IAB003Q IAB003R IAB003S IAB003T IAB004A IAB004B IAB004C IAB004D IAB004N IAB004P IAB004Q IAB004R IAB004S IAB004T IAB005A IAB005B IAB005C IAB005D IAB005N IAB005P IAB005Q IAB005R IAB005S IAB005T IAB201A IAB201B IAB201C IAB201D IAB301A IAB301E IAB311A IAB311E IAB312A IAB312E IAB315A IAB315E IAB316A IAB316E IAB340A IAB340E IAB341A IAB341E IAB344A IAB344E IAB345A IAB345E IAB401A IAB402A IAB403A IAB404A IAB405A IAB408A IAB410A IAB420A IAB430A IAB440A IAB450A IAB460A IAB470A IAB502A IAB502B IAB502C IAB504A IAB504B IAB504C IAB504D IAB504E IAB532A IAB532B IAB532C IAB534A IAB534B IAB534C IAB534D IAB534E IAB552A IAB552B IAB552C IAB554A IAB554B IAB554C IAB554D IAB554E IAB5N2A IAB5N2B IAB5N2C IAB5N4A IAB5N4B

102

Cat. Nos.

Page No. 57 58 56 54

Cat. Nos.

Page No. 54 55 57 58 54 57 56

Cat. Nos.

Page No. 17

Cat. Nos.

Page No. 39 40 41 42

Cat. Nos.

Page No. 42 43 44 45 39 38

Cat. Nos.

Page No. 59

IAB5N4C IAB5P2A IAB5P2B IAB5P2C IAB5P4A IAB5P4B IAB5P4C IAB5Q2A IAB5Q2B IAB5Q2C IAB5Q4A IAB5Q4B IAB5Q4C IAB5R2A IAB5R2B IAB5R2C IAB5R4A IAB5R4B IAB5R4C IAB5S2A IAB5S2B IAB5S2C IAB5S4A IAB5S4B IAB5S4C IAB5T2A IAB5T2B IAB5T2C IAB5T4A IAB5T4B IAB5T4C IAB600A IAB600B IAB600C IAB600D IAB603A IAB603B IAB603BB IAB603C IAB603CC IAB603D IAB603DD IAB605A IAB605B IAB605BB IAB605C IAB605CC IAB605D IAB605DD IAB610A IAB610B IAB610BB IAB610C IAB610CC IAB610D IAB610DD IAB620A IAB620B IAB620BB IAB620C IAB620CC IAB620D IAB620DD IAB630A IAB630B IAB630BB IAB630C IAB630CC IAB630D IAB630DD IAB640A IAB640B IAB640BB IAB640C IAB640CC IAB640D IAB640DD IAB650A IAB650B IAB650BB IAB650C IAB650CC IAB650D IAB650DD IAB660B IAB660C IAB660D IAB700A IAB703A IAB705A IAB710A IAB720A IAB730A IAB740A IAB750A IAC201A IAC201B IAC201C IAC201D

IAC301A IAC301E IAC311A IAC311E IAC312A IAC312E IAC315A IAC315E IAC316A IAC316E IAC340A IAC340E IAC341A IAC341E IAC344A IAC344E IAC345A IAC345E IAC502A IAC502B IAC502C IAC504A IAC504B IAC504C IAC504D IAC504E IAC532A IAC532B IAC532C IAC534A IAC534B IAC534C IAC534D IAC534E IAC552A IAC552B IAC552C IAC554A IAC554B IAC554C IAC554D IAC554E IAC5P2A IAC5P2B IAC5P2C IAC5P4A IAC5P4B IAC5P4C IAC5Q2A IAC5Q2B IAC5Q2C IAC5Q4A IAC5Q4B IAC5Q4C IAC5R2A IAC5R2B IAC5R2C IAC5R4A IAC5R4B IAC5R4C IAC5S2A IAC5S2B IAC5S2C IAC5S4A IAC5S4B IAC5S4C IAC5T2A IAC5T2B IAC5T2C IAC5T4A IAC5T4B IAC5T4C IAF311A IAF312A IAF315A IAF316A IAF5N2A IAF5N2B IAF5N2C IAF5N4A IAF5N4B IAF5N4C IAZ001A

JW2020

K
KA3123 KA3183 KA3243 KA3363 KF3010 KP3328 KP3528 KW3000 KW3010 KW3020 18

N
NA4123 NA4183 NA4243 NA4363 NF4010 NP4302 NP4303 NP4332 NP4502 NP4503 NP4532 NW4000 NW4010 NW4020 NZ4331 NZ4531 19

R
RAB002A RAB003A RAB004A RAB005A RAB006A RAB007A RAB008A RAB009A RAB010A RAB011A RAB012A RAB013A RAB014A RAB015A RAB016A RAB017A RAB018A RAB019A RAB020A RAB021A RAB201A RAB202A RAB203A RAB204A RAB205A RAB301A RAB311A RAB312A RAB315A RAB316A RAB322A RAB323A RAB326A RAB327A RAB340A RAB341A RAB344A RAB345A RAB401A RAB402A RAB403A RAB404A RAB405A RAB410A RAB420A RAB430A RAB440A RAB450A RAB460A RAB470A RAB480A RAB490A RAB502A RAB503A RAB504A RAB532A RAB533A RAB534A RAB552A RAB553A RAB554A RAB603A RAB605A 38 39

J
JA2123 JA2183 JA2243 JA2363 JF2010 JP2313 JP2327 JP2332 JP2513 JP2527 JP2532 JW2000 JW2010 17

RAB610A RAB620A RAB630A RAB640A RAB650A RAB703A RAB705A RAB710A RAB720A RAB730A RAB740A RAB750A RAC002A RAC003A RAC004A RAC005A RAC006A RAC007A RAC008A RAC009A RAC010A RAC011A RAC012A RAC013A RAC014A RAC015A RAC016A RAC017A RAC018A RAC019A RAC020A RAC021A RAC201A RAC202A RAC203A RAC204A RAC205A RAC301A RAC311A RAC312A RAC315A RAC316A RAC340A RAC341A RAC344A RAC345A RAC401A RAC402A RAC403A RAC404A RAC405A RAC410A RAC420A RAC430A RAC440A RAC450A RAC460A RAC470A RAC480A RAC490A RAC502A RAC503A RAC504A RAC532A RAC533A RAC534A RAC552A RAC553A RAC554A RAC603A RAC605A RAC610A RAC620A RAC630A RAC640A RAC650A RAC703A RAC705A RAC710A RAC720A RAC730A RAC740A RAC750A RAD002A RAD003A RAD004A RAD005A RAD006A RAD007A RAD008A RAD009A RAD010A RAD011A RAD012A RAD013A RAD014A RAD015A RAD016A RAD017A

RAD201A RAD202A RAD203A RAD204A RAD301A RAD311A RAD312A RAD313A RAD314A RAD319A RAD320A RAD340A RAD341A RAD342A RAD343A RAD348A RAD349A RAD401A RAD402A RAD403A RAD410A RAD420A RAD430A RAD440A RAD502A RAD503A RAD504A RAD512A RAD513A RAD514A RAD532A RAD533A RAD534A RAD552A RAD553A RAD554A RAD542A RAD543A RAD544A RAD562A RAD563A RAD564A RAD603A RAD605A RAD610A RAD620A RAD630A RAD640A RAD650A RAD703A RAD705A RAD710A RAD720A RAD730A RAD740A RAD750A RAF101A RAF102A RAF103A RAF104A RAF107A RAF108A RAF210A RAF211A RAF212A RAF213A RAF214A RAF215A RAK001 RAK002 RAK003 RAK010 RAK011 RAK012 RAK020 RAK021 RAK022 RAK030 RAK031 RAK032 RAL001 RAL002 RAL010 RAL011 RAZ001A RAZ010A RAZ020A

TAAB032B TAAB034A TAAB034B TAAB052A TAAB052B TAAB054A TAAB054B TACA032A TACA032B TACA034A TACA034B TACA052A TACA052B TACA054A TACA054B TACB032A TACB032B TACB034A TACB034B TACB052A TACB052B TACB054A TACB054B TADA032A TADA032B TADA034A TADA034B TADA052A TADA052B TADA054A TADA054B TADB032A TADB032B TADB034A TADB034B TADB052A TADB052B TADB054A TADB054B

V
V001 VA1452AA VA1452AB VA1452AC VA1453AA VA1454AA VA3452AA VA3452AB VA3452AC VA3453AA VA3454AA VB1432AA VB1432AB VB1432AC VB1433AA VB1434AA 61

Y
YA5123 YA5183 YA5243 YA5363 YF5010 YP5313 YP5327 YP5332 YP5513 YP5527 YP5532 YW5000 YW5010 YW5020 20

T
TAAA032A TAAA032B TAAA034A TAAA034B TAAA052A TAAA052B TAAA054A TAAA054B TAAB032A 59

103

Protection classifications
Protection against solid bodies and liquids : Index of protection - IP xx
Degree of protection of enclosures of electrical equipment in accordance with standards IEC 60529, BS EN 60529 Up to 1 000 V and 1 500 V=

Protection against mechanical impact : Index of protection - IK


According to standards IEC 62262 and BS EN 62262

1st figure : protection against solid bodies IP 0


50 mm

2nd figure : protection against liquids IP tests


No protection

IK

Tests

tests
No protection

Impact energy (in Joules) 0

IK 00
0.2 kg

Protected against solid bodies of 50 mm and greater (e.g. accidental contact with the hand)

Protected against vertically falling drops of water (condensation)

IK 01
0.2 kg

75 mm

015 02 035 05 07 1 2 5 10 20

IK 02
15

100 mm 0.2 kg

125 mm

2
Protected against solid bodies of 125 mm and greater (e.g. finger)

Protected against drops of water falling up to 15 from the vertical

IK 03
0.2 kg

175 mm

60

Protected against water sprayed up to 60 from the vertical

IK 04
0.2 kg

250 mm

IK 05
0.5 kg

350 mm

25 mm Protected against solid bodies of 25 mm and greater (e.g. tools, wires)

Protected against splashing water from all directions

IK 06
0.5 kg

200 mm

IK 07 4
1 mm Protected against solid bodies larger than 1 mm (e.g. thin tools and fine wires)

400 mm 1.7 kg

Protected against jets of water from all directions

IK 08
5 kg

295 mm

6 5
Protected against dust (no harmful deposit)
15 cm min.

Protected against powerful jets of water from all directions

IK 09
5 kg

200 mm

IK 10
Protected against the effects of temporary immersion in water
1m

400 mm

(1) A product previously classed as IP xx-7 can be assumed to fulfill the conditions of an IP xx - IK 08

The contents of the Protection Classifications charts are for guidance only. If you have any doubt as to the interpretation of the information contained therein, please refer either to the standard itself or contact Legrand.

Health and Safety at Work, etc. Act. 1974


Statement to Purchasers and Prospective Purchasers
1. Section 6 of this Act provides that manufacturers, designers, importers or suppliers of articles for use at work have a duty to ensure so far as is reasonably practical, that the article will be safe and without risk to health when properly used. An article is not regarded as being properly used if it is used without regard to any relevant information or advice relating to its use made available by the manufacturer, designer, importer or supplier. 2. With regard to these provisions the following is given as a guide to the information which is readily available to you. This information relates to those products detailed in our catalogue(s) or associated literature or may be obtained by specific request to the Company. 3. All products should be installed and maintained in accordance with good engineering practice and relevant British or other applicable standards, regulations for the installation of equipment by the Institute of Electrical Engineers or any other applicable Codes of Practice.

Completely protected against dust

Protected against the continuous effects of immersion in water having regard to specific conditions

This table can be used to ascertain the resistance of a product to an impact given in Joules from the IK code (graduated from 00 to 10). It can also be used to ascertain the correspondence with the old IP code 3rd digit and the corresponding external Ag conditions.

For information concerning wiring device standards outside the UK contact : BSI Customer Services 09:00 to 17:00 Monday to Friday Tel : +44 (0) 20 8996 9001 Fax : +44 (0) 20 8996 7001 Email : cservices@bsi-global.com

Health and Safety at Work Act The Electricity at Work Regulations, 1989
1. All installations and maintenance should be carried out within the provision of the above Act and by persons so qualified as defined in the Act. 2. Information and advice on the suitability of our products can be obtained from Legrand Electric Limited on specific request. marking appears on electrical or electronic products from Legrand and enables the circulation of goods outside the UK.

Conditions of sale Please consult our current price list


In accordance with its policy of continuous improvement the Company reserves the right to change specifications and designs without notice. All illustrations, descriptions, dimensions and weights in this catalogue are for guidance and cannot be held binding on the Company.

104

LEGRAND WORLDWIDE
Algeria Legrand Tel. : (213) 21 91 38 32 Fax : (213) 21 91 26 39 Australia Legrand Tel. : (61) 2 87 19 43 33 Fax : (61) 2 87 19 43 45 Austria Legrand Osterreich Tel. : (43) 1 277 62 Fax : (43) 1 277 62 225 Belarus Legrand Tel. : (375) 17 205 04 78/79 Fax : (375) 17 205 04 78/79 Belgium Legrand Belgique S.A. Tel. : (32) 2 719 17 11 Fax : (32) 2 719 17 00 Bosnia-Herzegovina Legrand Tel. : (387) 33 71 10 25 Fax : (387) 33 52 17 84 Brazil GL Electro-Eletronicos Ltda Tel. : (55) 11 56 44 26 00 Fax : (55) 11 51 81 06 04/59 14 Bulgaria Legrand Tel. : (359) 2 489 92 97 Fax : (359) 2 489 94 70 Canada Pass & Seymour Canada Inc Tel. : (1) 905 738 91 95 Fax : (1) 905 738 97 21 Chile Legrand Electro Andina Ltda (EAL) Tel. : (56) 2 550 52 00 Fax : (56) 2 550 53 09 China Legrand China Tel. : (86) 21 52 11 01 11 Fax : (86) 21 52 11 00 86 Colombia Legrand Colombia S.A. Tel. : (57) 1 437 67 00 Fax : (57) 1 436 26 54 Costa Rica Bticino Costa Rica Tel. : (506) 22 98 56 00 Fax : (506) 22 39 04 72 Croatia Legrand Tel. : (385) 1 606 43 50 Fax : (385) 1 606 43 59 Cyprus Legrand Tel. : (357) 22 318 588 Fax : (357) 22 318 588 Czech Republic Legrand s.r.o. Tel. : (420) 2 46 00 76 68 Fax : (420) 2 46 00 76 69 Egypt EMB Electrical Industries SAE Tel. : (202) 23 78 61 50 Fax : (202) 23 80 70 32 Estonia Legrand SNC Tel. : (372) 67 99 110 Fax : (372) 67 99 113 France Legrand S.A. Tel. : (33) 5 55 06 87 87 Fax : (33) 5 55 06 88 88 Germany Legrand GmbH Tel. : (49) 29 21 10 40 Fax : (49) 29 21 10 42 02 Greece Helliniki Legrand S.A. Tel. : (30) 2 10 67 97 500 Fax : (30) 2 10 67 97 540 Hong Kong Legrand (HK) Ltd Tel. : (852) 26 87 42 00 Fax : (852) 26 87 43 00 Hungary Legrand Zrt Tel. : (36) 63 51 02 00 Fax : (36) 63 51 02 10 India Legrand (India) Pvt Ltd Tel. : (91) 22 30 41 62 00 Fax : (91) 22 24 93 31 58 Indonesia PT Legrand Indonesia Tel. : (62) 21 525 06 08 Fax : (62) 21 525 59 35 Iran Alborz Electrical Industries Ltd Tel. : (98) 218 873 94 57/86 70 Fax : (98) 218 873 79 03 Italy Bticino S.p.a. Tel. : (39) 03 32 27 91 11 Fax : (39) 03 32 26 56 61 Jordan Legrand Tel. : (962) 64 65 59 02 Fax : (962) 64 65 59 03 Kazakhstan Legrand Kazakhstan Tel. : (7) 32 72 26 03 63 Fax : (7) 32 72 26 03 63 Korea Anam Legrand Co. Ltd Tel. : (82) 25 50 32 00 Fax : (82) 25 50 32 99 Kuwait Legrand Tel. : (965) 22 25 18 20 Fax : (965) 22 25 18 19 Lebanon Legrand Tel. : (961) 1 422 166 Fax : (961) 1 422 167 Lithuania Legrand Tel. : (370) 523 56 500 Fax : (370) 523 56 700 Malaysia Legrand Tel. : (603) 62 04 06 88 Fax : (603) 62 04 07 88 Mauritius Legrand Tel. : (230) 249 14 00 Fax : (230) 249 15 00 Mexico Bticino Mexico S.A. of C.V. Tel. : (52) 442 238 04 00 Fax : (52) 442 238 04 82 Morocco Simapel Tel. : (212) 2 235 93 73 Fax : (212) 2 235 58 30 Netherlands Legrand Netherlands B.V. Tel. : (31) 411 653 111 Fax : (31) 411 653 158 New Caledonia Legrand Tel. : (687) 76 49 28 Fax : (687) 25 95 64 New Zealand HPM Legrand Tel. : (64) 9 442 08 000 Fax : (64) 9 442 08 003 Ouzbekistan Legrand Tel. : (998) 71 138 9948 Fax : (998) 71 138 9947 Peru Bticino del Peru S.A. Tel. : (51) 1242 60 00 Fax : (51) 1242 41 00 Philippines Bticino Philippines Inc. Tel. : (63) 2 89 28 972 Fax : (63) 2 89 28 971 Poland Legrand Polska Tel. : (48) 748 162 300 Fax : (48) 748 152 149 Portugal Legrand Electrica S.A. Tel. : (351) 21 454 88 00 Fax : (351) 21 454 88 86 Qatar Legrand Tel. : (974) 456 90 83 Fax : (974) 465 99 16 Reunion Legrand Indian Ocean Tel. : 02 62 90 01 80 Fax : 02 62 90 01 89 Romania Legrand Romania SRL Tel. : (40) 21 232 07 77 Fax : (40) 21 232 07 76 Russia Firelec Legrand P.T. Tel. : (7) 495 660 75 50/60 Fax : (7) 495 660 75 51/61 Saudi Arabia Legrand Tel. : (966) 2 651 28 48 Fax : (966) 2 651 74 34 Senegal Legrand Tel. : (221) 33 865 00 01 Fax : (221) 33 820 63 69 Serbia and Montenegro Legrand Tel. : (381) 11 26 05 308 Fax : (381) 11 26 05 267 Singapore Legrand (S) Pte Ltd Tel. : (65) 6416 1550 Fax : (65) 6416 1580 Slovakia Legrand Tel. : (421) 232 153 601 Fax : (421) 232 153 609 Slovenia Legrand SLV d.o.o Tel. : 386 (0) 1 562 01 70 Fax : 386 (0) 1 562 13 12 South Africa Legrand electrical accessories Tel. : (27) 11 444 79 71 Fax : (27) 11 444 79 80 Spain Legrand Group Espaa Tel. : (34) 91 656 18 12 Fax : (34) 91 656 67 88 Switzerland Legrand (Suisse) S.A. Tel. : (41) 56 464 67 67 Fax : (41) 56 464 67 60 Syria Legrand Tel. : (963) 11 33 22 920/970 Fax : (963) 11 33 22 512 Thailand Bticino (Thailand) Limited Tel. : (66) 2 656 91 62/67 Fax : (66) 2 656 91 97 Tunisia Legrand Tel. : (216) 71 964 022 Fax : (216) 71 963 297 Turkey Legrand Elektrik San. A.S. Tel. : (90) 262 648 90 00 Fax : (90) 262 751 12 67 U.A.E. Legrand SNC FZE Tel. : (971) 48 137 111 Fax : (971) 48 864 784 Ukraine Legrand Ukraine Ltd Tel. : (38) 044 494 00 10 Fax : (38) 044 490 67 56 United States Legrand North America Tel. : (1) 860 233 6251 Fax : (1) 860 570 2813 Venezuela Bticino De Venezuela C.A. Tel. : (58) 212 361 33 33 Fax : (58) 212 362 25 25 Vietnam Legrand Vietnam Tel. : (848) 9 307 448 Fax : (848) 9 307 449 West Indies Legrand Tel. : (0) 5 90 86 18 53 Fax : (0) 5 90 86 23 05 Other countries : www.legrandgroup.com International department direct : Tel. : 33 5 55 06 87 87 Fax : 33 5 55 06 74 55

Electrak contact details


Quotations and Technical Support: The Power Distribution Division of Legrand Electric Ltd. Arena Park, Dial Lane, West Bromwich West Midlands, B70 0EB Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6760 E-mail: powersales.uk@legrand.co.uk Customer Services: The Power Distribution Division of Legrand Electric Ltd. No. 1 Industrial Estate Medomsley Road, Consett, County Durham, DH8 6SR Tel: +44 (0) 845 600 6266 Fax: +44 (0) 845 600 6366 E-mail: powersales.uk@legrand.co.uk Accounts: The Power Distribution Division of Legrand Electric Ltd. Great King Street North, Birmingham, B19 2LF Tel: +44 (0) 870 608 9000 Fax: +44 (0) 870 608 9004

Distributor:

The Legrand logo is a registered trademark of the Legrand group of companies.

Electrak Export Cat 11/2010.4k

Head Office (UK and Ireland): Great King Street North, Birmingham, B19 2LF Tel: +44 (0) 870 608 9000 Fax: +44 (0) 870 608 9004 Website: www.legrand.co.uk