Perforated damper blade for better damper characteristic Manually adjustable blade (standard) Provision for motorised regulation Quick connection enables simple access for cleaning (accessory) CRP
Quick facts
CRP
Technical description
Design
Circular commissioning damper consisting of a duct section with a damper, duct connections tted with a rubber seal ring. The damper has a damper knob shelf and a lockable damper knob with stamped indicating text for open to closed damper position. Inside the damper, there is a perforated damper blade; the smallest aperture diameter of the CRP damper is 10 mm. If motorised control is selected, the damper knob shelf is replaced by a larger actuator support shelf. The motorised regulation requires an actuating torque specied in the dimensions and weights table on page 5. As standard, the supporting shelves are 80 mm high to be ush with the outer surface of any possible duct insulation. Max. permissible ambient temperature: 60C.
Maintenance
Clean the damper whenever needed by means of a vacuum-cleaner and brush nozzle or by wiping surfaces with a cloth.
Environment
The Building Materials Declaration is available from www. swegon.com.
Figure 1. Installation.
Customizing
The damper can be made of other materials, such as stainless or epoxy-coated sheet steel. Contact your nearest sales ofce for information.
Accessories
Actuator: Sauter ASM115SF901, 24V AC is the standard actuator and kept in stock. Other actuators must be ordered; see the actuator selection table on page 5. Wiring diagrams can be found in the relevant MIS instructions (Installation Commissioning - Maintenance) available from www.swegon.com. Knob: CRTT-1 for manual control. Quick connection: FSR. Clamp with quick-acting lock.
Installation
Insert the damper into the connecting duct and x it in position with blind rivets or by means of an FSR clamp. See Figure 1.
Commissioning
The damper has no measurement function of its own. Turn the damper blade at the desired position and lock it.
2
Swegon reserves the right to alter specications. 20130522 www.swegon.com
CRP
Sizing
Sound power level
The diagrams for the various sizes show the total generated sound power (Lwtot dB), as a function of the airow and pressure drop across the damper. By correcting LWtot with the correction factors from Table 1, the sound power level for each octave band (LW = Lwtot + Kok)can be obtained.
Acoustic data
Sound power level Correction factor, Kok
Size 100 125 160 200 250 315 400 500 630 Tol. Mid-frequency (Octave band) Hz 63 125 250 500 1000 0 1 1 1 0 2 2 2 1 2 -1 -1 -1 -1 -1 -2 -3 -2 -4 2 -6 -7 -7 -7 -7 -8 -8 -9 -8 2 -13 -14 -13 -12 -12 -14 -12 -12 -8 2 -17 -18 -16 -14 -14 -15 -13 -14 -9 2 2000 -25 -25 -21 -18 -18 -19 -18 -18 -13 2 4000 -32 -32 -28 -25 -25 -26 -26 -26 -20 2 8000 -38 -38 -35 -32 -33 -33 -32 -31 -28 2
Sizing diagram
Airow Pressure drop Sound level
The diagrams should not be used for commissioning. The diagrams show pressure and ow lines at various damper angles. CRP 100
ps Pa LWtot70 dB 500 400 300 200 100 50 40 30 20 10 40 50 20 30 100 40 50 200 l/s m /h
3
CRP 125
0% % 33 5 0%
500 400 300 200 55 ps Pa LWtot70 dB 65 60
67 % 0% 33 % 50 %
CRP
65 60 55 50
83 % 67 %
100 50 40 30 20
50
83
100
20
30 100
40
50 200 300
20130522
www.swegon.com
CRP
CRP 160
ps Pa 500 400 300 200 100 50 40 30 20 30 100 40 50 200 300 100 400 500 m /h
3
CRP 200
0% 33 % 5 0%
500 400 ps Pa LWtot70 dB 65 60 55 50
83 % % 67 0% % 33
LWtot70 dB 65 60 55 50
% 50
67
300 200
83
100 50 40 30 20
200 l/s
40
50 200 300
200
CRP 250
ps Pa 500 400 300 200 100 50 40 30 20 100 300 400 500 200 300 1000 400 l/s 500 m /h
3
CRP 315
0% % 33 % 50
500 400 300 200 55 50
83 %
ps Pa LWtot70 dB 65 60
0%
33
% 50 %
LWtot70 dB 65 60 55 50
83 % % 67
67
100 50 40 30 20
200
300 1000
400
CRP 400
ps Pa 500 400 300 200 100 50 40 30 20 200 300 1000 400 500 2000 3000 1000 l/s
3
CRP 500
0% 33 % 5 0%
0%
33
50
LWtot70 dB 65 60 55 50
83 % 6 7%
67
100 50 40 30 20 200
50
83
300 1000
400
1000 4000
l/s 5000 m /h
3
2000
4000 m /h
CRP 630
ps Pa 500 400 300 200 100 50 40 30 20 300 400 500 2000 3000 1000 4000 5000 2000 m /h
3
0%
% 50
LWtot70 dB 65 60 55 50
% 83
l/s
3000
4
Swegon reserves the right to alter specications. 20130522 www.swegon.com
CRP
Actuator tables
*)
Dimensions (mm) A 210 210 210 210 210 210 255 255 255 H 70 70 75 75 75 75 80 80 80
Weight (Kg) 0.7 0.8 0.9 1.0 1.2 1.5 2.6 4.2 6.0
Torque (Nm) <3 <3 <3 <3 <4 <4 <4 <8 <8
Actuator Sauter 24 V AC, ASM115SF901 is standard and kept in stock. All other actuators are order items. 2 or 3 point regulation 24 V AC
Size 100-315 400-630 Torque 5 Nm 10 Nm Designation Sauter Belimo ASM115SF901 LM24A ASM115SF901 NM24A
The torque refers to the recommended force necessary for secure control.
45
Electrical data
Actuators Supply voltage 24 V AC
Make / Model Sauter ASM115SF901 Belimo LM24A / -SR Belimo NM24A / -SR Ambient temp. -20...+55C -30...+55C -30...+55C Power Consumption 8.7 VA 2.0 VA 3.5 VA
CRP
45
20130522 www.swegon.com
CRP
Ordering key
Product
Commissioning damper, Class 0 Version: Dimension: 100, 125, 160, 200, 250, 315, 400, 500, 630 Control version: 1 = Manual damper knob (stocked item) 2 = Mounted actuator (incl. standard actuator) 4 = With provision for installing a actuator CRP c -aaa -b
Specication text
Swegonstype CRP circular commissioning damper with the following functions: Ductwork leakage Class 0, to VVS AMA 98 Perforated damper blade Lockable damper knob with damper blade position indicator Non-fouling design
Size: CRPc - bbb - c xx items
Accessories If a non-standard actuator is to be tted, the actuator designation must be specied in plain text. N.B: The type of actuator varies with the size. See actuator selection table on page 5.
Knob Quick connection Version: Size: Nominal duct size FSR c CRTT-1 -aaa
6