Вы находитесь на странице: 1из 2

www.intertec.

info

Self-Limiting Heat Tracing Cable Type PSB/ HSB


1 Application

Combined with a suitable insulation self-limiting heat tracing cables are designed to protect the medium in pipe lines and fittings against freezing, condensation and solidification. To maintain the temperature at a defined setpoint a temperature controller with sensor can be connected in series with the heating circuit.

Application

Features

Power output dependent on pipe temperature. No temperature limiter required. Heating circuits from 1 m length can be connected directly to the operating voltage Simple on-site installation even in hazardous areas

All types of heat tracing cables with associated installation fittings can be used in hazardous areas up to zone 1: PSB .. - 5 for humid areas and exposure to organic chemicals PSB .. - 6 for humid areas and exposure to inorganic chemicals HSB .. - 5 for humid areas and exposure to organic chemicals as well as pipe lines periodically subjected to steam cleaning

Description

6
30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 5 10

Power Characteristics
a: PSB 10-5 and PSB 10-6 b: PSB 13-5 and PSB 13-6 c: PSB 26-5 and PSB 26-6 d: HSB 10-5 e: HSB 15-5 f : HSB 25-5

The synthetic heating element between the parallel copper wires has the same effect as temperaturedependent resistors laid parallel to each other. Consequently, the power output on the piece of pipe line that has to be heated can differ locally. In areas of heat dissipation caused by pipe supports, higher current flows through the heating element than in areas that are better insulated and are exposed to strong sunlight. These temperature characteristics prevent overheating even when the cable is overlapped. The copper braiding guarantees electric safety to VDE 0100 and also increases the mechanical stability of the cable. The outer protective jacket of fluoropolymer or polyolefin (PSB-..-6) provides resistance to corrosion and the effects of chemicals.

Heat-Output [W/m]

Heat-Output tested for isolated steel pipe on 230 V

b a

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100 105 110 115 120

Pipe temperature[C]

4
Type
PSB 10-5 PSB 13-5 PSB 26-5 PSB 10-6 PSB 13-6 PSB 26-6 HSB 10-5 HSB 15-5

Types and Technical Data


Heat-Output at +10C
9,2 W/m 12,3 W/m 24,9 W/m 9,2 W/m 12,3 W/m 24,9 W/m 9,1 W/m 15,1 W/m 24,4 W/m ** Heater off

Ignition Protection class


II 2G EEx e II T6 II 2G EEx e II T6 II 2G EEx e II T6 II 2G EEx e II T6 II 2G EEx e II T6 II 2G EEx e II T6 II 2G EEx e II T3 II 2G EEx e II T3

Max. Permissible Amb. Temp. Permanently* cumulative 1000 hrs.**


+65C +65C +65C +65C +65C +65C +120C +120C +120C +85C +85C +85C +85C +85C +85C +190C +190C +190C

max. Length***
198 m 164 m 92 m 198 m 164 m 92 m 200 m 153 m 107 m

EC Typeexamination certifacte
KEMA 02 ATEX 2326 U KEMA 02 ATEX 2326 U KEMA 02 ATEX 2326 U KEMA 02 ATEX 2326 U KEMA 02 ATEX 2326 U KEMA 02 ATEX 2326 U KEMA 02 ATEX 2327 U KEMA 02 ATEX 2327 U KEMA 02 ATEX 2327 U

HSB 25-5 * Heater on

II 2G EEx e II T3 *** at Setpoint +10C

HD391-3e-PSB / HSB

Page 1 from 2

www.intertec.info

Self-Limiting Heat Tracing Cable Type PSB/ HSB


the heat conection cable is not included in the scope of suply

Heat Tracing Connection System

The connection between the heat tracing cable and the power supply cable consists of a plug and a sleeve of high temperature-steady Thermoplast. For using plug-in technique for hazardous areas two remarks are available. - PLEXO P-CW (for Heatincable PSB...) - PLEXO H-CW (for Heatincable HSB...) The end of the heat tracing cable from same material has the ordering example: - PLEXO P-1S (fr Heizband PSB...) - PLEXO H-1S (fr Heizband HSB...) Connection port TWISTO-B-S is certified only for non harzardous areas in combination with heating cable PSB... For applications of high temperatures PLEXO-H-CW with Heat tracing cable HSB... must be used also here. End of heat tracing cable with 1,5 m heat tracing cable pre assembled PLEXO P-CW PLEXO H-CW PLEXO P-1S PLEXO H-1S

Special Advantages
TWISTO-B-S (Connection-port)

Quick and easy installation on site with no need for special tools. Putting technology reliable in service for connection and final conclusion. (plug and socket)

Technical Data
PLEXO P-CW PLEXO P-1S PLEXO H-CW PLEXO H-1S II 2G EEx e II T3 KEMA 00 ATEX 2018 TWISTO-B-S Connection and end of heat

tracing cable Ignition protection class II 2G EEx e II T6


EC Type-examination certifacte Temperature Resistance Mains Voltage Protection Degree KEMA 00 ATEX 2017 VDE Reg.-Nr. A 405

+65C (C) * +120C (V) * +80C +85C cumulative 1000h** +180C cumulative 1000h ** short time to +100C AC/DC 254 V AC/DC 254 V AC 250 V IP 66 IP 66 IP 66

* Heater on **Heater off

HD391-3e-PSB / HSB

Page 2 from 2

Вам также может понравиться