Вы находитесь на странице: 1из 35

SOCIALIST REPUBLIC OF VIETNAM

Independence - Freedom - Happiness





QCVN 09:2013/BXD





NATIONAL TECHNICAL
REGULATION ON ENERGY
EFFICIENCY BUILDINGS











Hanoi - 2013
Unofficial translation - QCVN 09: 2013/BXD
2
CONTENTS

INTRODUCTION ....................................................................................................................................... 3
I. GENERAL REQUIREMENTS .................................................................................................................... 4
1.1. Scope ................................................................................................................................................ 4
1.2. Coverage ........................................................................................................................................... 4
1.3. Normative references....................................................................................................................... 4
1.4. Terms, definitions and symbols ........................................................................................................ 4
II. TECHNICAL REQUIREMENTS ................................................................................................................ 6
2.1.Building envelope .............................................................................................................................. 6
2.2.Ventilation and air conditioning ........................................................................................................ 9
2.3. Lighting ........................................................................................................................................... 15
2.4. Escalators and elevators ................................................................................................................. 18
2.5. Electric power consumption ........................................................................................................... 18
2.6.Service water heating system ......................................................................................................... 20
III.MANAGEMENT REGULATIONS .......................................................................................................... 23
IV.IMPLEMENTATION ARRANGMENT ................................................................................................... 23
ANNEXES ................................................................................................................................................ 24

QCVN 09:2013/BXD
3
INTRODUCTION

QCVN 09:2013/BXD - Energy Efficiency Building Code was developed by the Vietnam Association of
Civil Engineering Environment, put forward by the Department of Science, Technology and
Environment Department, and enacted by the Ministry of Construction under Circular 15 /2013/TT-
BXD, dated on September 26, 2013. The National Energy Efficiency Building Code QCVN
09:2013/BXD shall supersede the Vietnam Energy Efficiency Building Code QCXDVN 09:2005 ratified
under the Minister of Constructions Decision 40/2005/Q-BXD of November 17, 2005.

The National Energy Efficiency Building Code QCVN 09:2013/BXD was developed with research inputs
and contributions of international consultants from various external donors, including the
International Finance Corporation (IFC), the United States Agency for International Development
(USAID) and the Danish Energy Agency (the Kingdom of Denmark).











Unofficial translation - QCVN 09: 2013/BXD
4
National Technical Regulation on Energy Efficiency Buildings

(NATIONAL TECHNICAL ENERGY EFFICIENCY BUILDING CODE)


I. GENERAL REQUIREMENTS
1.1. Scope
1.1.1 This National Technical Building Energy Efficiency Building Code provides mandatory technical
standards to achieve energy efficiency in the design, new construction or retrofit of civil buildings
(office buildings, hotels, hospitals, schools, commercial buildings,, services buildings, apartments
buildings, among others), with a gross floor area of 2,500 m
2
or larger.

1.1.2 The requirements of this Code apply to:
1) The building envelope, except envelopes of non-air conditioned storage space or warehouses;
2) Equipment and systems in the building, including:
a) Interior lighting
b) Ventilation and air conditioning
c) Water heating
d) Energy management equipment, and
e) Elevators and escalators.

1.2. Coverage
This Code provides statutory technical requirements applicable to all entities and individuals involved
in activities pertaining to energy efficient buildings.

1.3. Normative references
1) ARI 340/360 Performance rating of commercial and industrial unitary air-conditioning and heat
pump equipment.
2) ARI 365 Performance rating of commercial and industrial unitary air-conditioning condensing
units.
3) ARI 550/590-2003 Performance rating of water-chilling packages using the vapor compression
cycle.
4) ASHRAE 90.1-2001 Standard 90.1-2001 (I-P Edition) -- Energy Standard for Buildings except
Low-Rise Residential Buildings (IESNA cosponsored; ANSI approved; Continuous Maintenance
Standard).
5) SHRAE 90.1-2004 Energy Standard for Buildings except Low-Rise Residential Buildings.
6) DIN 4702-1 Boilers for central heating; terms, requirements, testing, marking.
7) ISO 6946:2007 Building components and building element - Thermal resistance and thermal
transmittance - Calculation method.
8) TCVN 298:2003 Building components and parts Thermal resistance and thermal conductivity
Calculating methods.
9) TCVN 6307:1997 Cooling systems Testing methods.
10) TCVN 7830-1:2012 Air conditioning equipment Part 1: Energy efficiency.

1.4. Terms, definitions and symbols
1.4.1Terms and definitions

QCVN 09:2013/BXD
5
1) Cooling air saving system: including ducts and automatic controlling system that allow fans to
drive cool air from outside into the building in appropriate weather conditions to reduce energy
consumption for air cooling or when mechanical air conditioning is not needed.
2) Building energy cost: total annual cost of energy consumption for the building.
3) Coefficient of performance (COP) cooling: the ratio of the rate of heat removal to the rate of
energy input, in consistent units, to be verified based on existing national standards or
designated operating conditions. COP is used to rate the efficiency of electricity-powered
condenser air conditioner, including the compressor, evaporator coil and condenser coil. COP can
also be used to rate the efficiency of water-cooled chiller (not including chiller pumps, condensed
cooling water and cooling tower fans).
4) Coefficient of performance (COP) - heat pump: the ratio of the rate of heat output to the rate of
energy input, in consistent units, for a complete heat pump system under designated operating
conditions.
5) Overall thermal transfer value (OTTV): the total heat gain through the entire surface area of the
building envelope, including opaque walls and glazing by every square meter of the building
exterior surface area, W/m
2
.
6) Floor area of a particular space: the horizontal surface area of a specific space, measured from
the interior side of the circumference walls or partitions, at the elevation of the working plane
(0.8 m).
7) Radiation reduction coefficient of shading structures: the ratio of solar heat gain through
windows, in case a window external shading system is installed, to that of windows without
shading systems.
8) Overall heat transfer coefficient (U
o
): the intensity of a time-constant heat flux going through a
surface area unit of the enclosing structure when the temperature difference of the air on both
sides of the structure is 1 K, measured in W/m
2
.K.
9) Total thermal resistance (R
o
): the inverse of overall heat transfer coefficient U
o
:R
o
= 1/U
o
,
measured in m
2
.K/W.
10) Lamp efficiency: the ratio of rated light output to power consumption, measured in lumen/W.
11) Efficiency of the ventilation-air conditioning systems: the ratio of output energy (useful energy at
the time of use) to input energy, in consistent unit, for a specific length of time, measured in %.
12) Enthalpy recovery: the ability to recover cooling energy of air conditioning equipment, boilers
etc., resulting in energy efficiency.
13) Annual energy consumption efficiency: the annual ratio of energy output to energy input of a
building or piece of equipment.
14) Indirectly air-conditioned space: an enclosed space in a building that is indirectly cooled (rather
than directly cooled) and allows heat transfer therefrom to adjacent air-cooled spaces.
15) Lighting power density (LPD): the ratio of electric lighting output to the illuminated area,
measured in W/m
2
.
16) Daylight relay: a device that automatically turns on or off input energy for electric lighting,
located near windows to maintain appropriate working illuminance level when direct or indirect
daylight fails to provide the desired illuminance.
17) Temperature control relay: an automatic temperature-sensitive device.
18) Building envelope: building envelope or building enclosure consists of opaque or transparent
walls, windows, doors, skylights, among others, that form enclosed spaces within a building.

1.4.2 Symbols, measurement units and acronyms
1) SHGC (Solar Heat Gain Coefficient): heat gain coefficient of glazing, published by manufacturers
or determined in accordance with prevailing standards, dimensionless. In case manufacturers
avails of the shading coefficient SC, SHGC = SC 0.87.
2) SC: Shading coefficient;
3) T: Absolute temperature, K;
4) R
O
: Total thermal resistance (inverse of heat transfer ratio Uo) of enclosing assembly m
2
K/W;
Unofficial translation - QCVN 09: 2013/BXD
6
5) U
o
: Heat transfer coefficient (including heat transfer through ambient air layers on both sides of
the structure), W/m
2
K;
6) U
o,M
: Overall heat transfer coefficient of the roof assembly, W/m
2
K;
7) U
o,T
: Overall heat transfer coefficient of walls, W/m
2
K;
8) AHU: Air handling unit;
9) ARI: Air-conditioning and Refrigeration Institute;
10) ASHRAE: American Society of Heating, Refrigerating and Air-Conditioning Engineers;
11) BEF: Ballast efficacy factor for fluorescent lamps, %/W;
12) BF: Ballast factor, %;
13) COP
cooling
: Air conditioner coefficient of performance ratio of air cooling output to electricity
input, kW/kW;
14) COP
heating
: Heat pump coefficient of performance ratio of heat gain to electricity input, kW/kW;
15) EER: Energy efficiency ratio of air conditioners ratio of cooling output and electricity input,
kW/kW;
16) FCU: Fan coil unit thermal exchange system consisting of multiple plain or fanned tubal rows;
thermal carriers being cooled or heated water running inside the tubes to provide
cooling/heating effects for a space; the FCU is the end-of-the-line component of a water-cooled
central air-conditioning system with chillers;
17) IEER: Integrated energy efficiency ratio, kW/kW;
18) IPLV: Integrated part load value, or in full term, integrated energy efficiency part load value;
kW/kW;
19) OTTV
T
: Overall thermal transfer value for walls the mean intensity of the heat flux transferred
through 1 m
2
of exterior walls, W/m
2
;
20) OTTV
M
: Overall thermal transfer value for roofs the mean intensity of the heat flux transferred
through 1 m
2
of roofing, W/m
2
;
21) PIC: Power input per capacity the ratio of energy input, in kW, to cooling output, in RT (ton of
refrigeration), kW/RT;
22) VLT (Visible Light Transmission): the ratio of light passing through glazing materials, measured in
the amount of light energy that passes through glazing as a percentage of the light energy that
directs on the glazing surface, %;
23) VRV/VRF: Air conditioning systems with variable refrigerant volume/flow;
24) VSD: Variable speed driver;
25) WWR: Window-to-wall ratio, dimensionless;


II. TECHNICAL REQUIREMENTS
2.1.Building envelope
2.1.1 General requirements
The building envelope shall be designed and constructed in ways shall guarantee:
1) Natural ventilation whenever exterior climate conditions allow;
2) Sufficient insulation and minimum exposure to cold wind;
3) Sufficient day lighting under normal conditions, while reducing solar heat gain into the
building;
4) Choice of appropriate materials to improve energy efficiency for the building.

2.1.2 Requirements for building exterior walls and roofs
1) All ground exterior walls (opaque parts of the walls) shall maintain a maximum overall heat
transfer value U
o.max
no greater than, or a minimum overall heat transfer value R
o.min
no
smaller than the values specified in Table 2.1.


QCVN 09:2013/BXD
7
Table 2.1. Thermal performance requirements for exterior walls

Areas Wall orientation U
o.max
, W/m
2
.K R
o.min
, m
2
.K/W
All areas All orientations 1.80 0.56

2) Requirements for flat roofs and roofs with gradient of less than 15 degrees:
All roofs, including those with insulation, metal roofs and others shall possess an overall heat
transfer value U
o
no greater than, or total thermal resistance Ro no smaller than the values
specified in Table 2.2.

Table 2.2. Thermal performance requirements for flat roofs

Area U
o.max
, W/m
2
.K R
o.min
, m
2
.K/W
All areas 1.00 1.00
Notes:
1) Shaded roofs: If more than 90% of the roof is covered with a fixed
sunshade with ventilation, there is no need for insulation for such
roof. The sunshade must be installed at a minimum clearance of 0.3 m
from the roof surface to be recognized as having ventilation between
the roof and sunshade (double-layer roof with an air cushion in
between).
2) Flat roofs with reflective materials: Thermal resistance values R
o,min
provided in Table 2.2 may be multiplied by a coefficient of 0.80 for
roofs designed with reflective materials, within a range of 0.70 0.75,
to increase heat inflection for the exterior roof surface.
3) Roofs with gradient of 15 degrees or above: The minimum total
thermal resistance or maximum overall thermal transfer value for
roofs may be identified by multiplying R
o.min
and U
o.max
values in Table
2.2 with a coefficient of 0.85 and 1.18, respectively.

3) Sizes of windows and skylight
a) The gross area of vertical openable and fixed windows shall guarantee good ventilation and
day lighting.
b) The overall thermal transfer value of walls and roofs shall guarantee:
- OTTV
T
for walls no greater than 60 W/m
2
;
- OTTV
M
for roofs no greater than 25 W/m
2
.
c) OTTV values are determined using prevailing standards and technical guidelines.

4) Glazed windows shall be designed with applicable SHGC coefficients in lieu of the OTTV
T

referred to in 2.1.2 3) b) above. SHGC of glazing shall be smaller or equal to the maximum
allowed value, and glazing VLT shall not be lower than the VLTmin in Table 2.3.

Table 2.3. WWR-related SHGC for glazing


WWR, %
SHGCmax on 8 main orientations

VLT
min

N E or W
NE, NW or SE,
SW
S
20 0.90 0.80 0.86 0.90 0.70
Unofficial translation - QCVN 09: 2013/BXD
8
30 0.64 0.58 0.63 0.70 0.70
40 0.50 0.46 0.49 0.56 0.60
50 0.40 0.38 0.40 0.45 0.55
60 0.33 0.32 0.34 0.39 0.50
70 0.27 0.27 0.29 0.33 0.45
80 0.23 0.23 0.25 0.28 0.40
90 0.20 0.20 0.21 0.25 0.35
100 0.17 0.18 0.19 0.22 0.30
Notes:
1) If WWR does not match the values in column 1, Table 2.3, SHGC shall be determined through
linear interpolation using the nearest higher and lower WWR values.
2) Glazing materials with SHGC values higher than the reference SHGC providing that sunshades
with appropriate A coefficients are used to insure that the selected SHGC is smaller or equal to
the reference SHGC multiplied by the A coefficient see 2.1.2 5).

5) In case of building facades being installed with sunshades, SHGC values in Table 2.3 may be
adjusted by multiplying them with the A coefficients in Tables 2.4 and 2.5.

Table 2.4. A coefficient for consistent horizontal sunshades placed on or above the upper window
edge by a clearance d, with d/H < 0.1

R=b/H
On walls, facing 8 main orientations
N NE or NW E or W SE or SW S
0.10 1.23 1.11 1.09 1.14 1.20
0.20 1.43 1.23 1.19 1.28 1.39
0.30 1.56 1.35 1.30 1.45 1.39
0.40 1.64 1.47 1.41 1.59 1.39
0.50 1.69 1.59 1.54 1.75 1.39
0.60 1.75 1.69 1.64 1.89 1.39
0.70 1.79 1.82 1.75 2.00 1.39
0.80 1.82 1.89 1.85 2.13 1.39
0.90 1.85 2.00 1.96 2.22 1.39
1.00 1.85 2.08 2.08 2.27 1.39
Notes:
1) Dimensions:
b reach of sunshade;
H window height;
d clearance from upper window edge to lower sunshade contact;
b, d and H share the same dimension for length.
2) Applicable for sunshades placed above the upper window edge by a clearance d, with d/H 0.1
tolerance of less than 10%.

Table 2.5. A coefficient for consistent vertical sunshades placed on or next to a window side by a
clearance e, with e/B < 0.1

R=b/B
On walls, facing 8 main orientations
N NE or NW E or W SE or SW S
0.10 1.25 1.06 1.01 1.09 1.11
0.20 1.52 1.12 1.03 1.19 1.19
0.30 1.75 1.19 1.05 1.32 1.22

QCVN 09:2013/BXD
9
0.40 1.82 1.28 1.06 1.45 1.25
0.50 1.85 1.37 1.09 1.64 1.28
0.60 1.85 1.47 1.10 1.82 1.30
0.70 1.89 1.59 1.12 1.96 1.30
0.80 1.89 1.69 1.14 2.13 1.30
0.90 1.89 1.82 1.16 2.22 1.30
1.00 1.89 1.96 1.18 2.33 1.30
Notes:
1) Dimensions:
b reach of vertical sunshade;
B window width;
e clearance from window side to vertical sunshade inner contact;
b, e and B share the same dimension for length.
2) Applicable also for vertical sunshades placed by a clearance e from the window side, with e/B
0.1, tolerance of less than 10%.

2.2.Ventilation and air conditioning
2.2.1 General requirements
1) Natural ventilation and mechanical ventilation
For every specific space, natural (passive) ventilation systems or coerced (active mechanical)
ventilation systems may be used. Natural ventilation systems used shall meet the requirements of
2.2.1 2).
2) Natural ventilating system
Spaces are considered naturally ventilated if the following requirements are met:
a) Vent holes and windows may be opened outward with sizes no less than 5% of the floor area.
Users may easily get access to these ventilation openings.
b) There are vent holes that may be opened on the roofs or walls that face the external on-
coming wind sources. The ventilation openings have ventilating sizes of no less than 5% of
the floor area. Users may easily get access to these vent holes which connect to the external
air through openings with similar or larger sizes.
c) The accumulated size of the vent openings is no smaller than the gross area of the wind
catchers.
3) Mechanical ventilating system
Spaces without natural ventilation shall be installed with mechanical ventilating systems to provide
external air to every frequently occupied area through anair distribution piping system.

2.2.2 Requirements for ventilation-air conditioning systems and equipment
1) General requirements
a) Equipment performance: air conditioning and water cooling equipment and systems shall
ensure the minimum coefficients of performance (COP) in standard rating conditions, and
not lower than the values provided in the following tables.
- Table 2.6: for electric air conditioners and condenser coils;
- Table 2.7: for water cooling equipment;
- Table 2.8a: for cooling towers;
- Table 2.8b: for condenser units.
Notes:
Apart from the cooling coefficient of performance (COP), refrigeration equipment is also reviewed for
energy efficiency through the integrated part load value (IPLV) and integrated energy efficiency ratio
(IEER).

Unofficial translation - QCVN 09: 2013/BXD
10
b) Automatic timer: the following equipment must come with a timer or other control devices
that may automatically turn the equipment on or off as set up.
- Chillers;
- Hot air systems;
- Cooling tower fans;
- Pumps with capacity equal or greater than 5 HPs (3.7 kW).

c) Piping insulation of cooling systems:
Coolant ducts of air conditioning systems and chilled water piping of central air conditioning
systems shall be affixed with a thermal insulating layer with thickness equal or greater than the
insulation thickness values specified in Tables 2.9 and 2.10.

The insulating thickness (mm) provided in Tables 2.9 and 2.10 apply to thermal insulating
materials with heat conductivity of 0.0320.04 W/m.K at a mean temperature of 24C. The
minimum insulation thickness increases for materials with heat conductivity greater than 0.04
W/m.K or may decrease for materials with thermal conductivity lower than 0.032 W/m.K.

For insulating materials with conductivity outside the above mentioned range, the minimum
thickness (bmin) is determined using the following formula:
(

+ = 1 ) 1 (
04 . 0 /
0
min

r
b
r b
(2.1)
where,
b
min
minimum thickness of the insulating layer, mm;
r actual duct external radius, mm;
b
0
the thickness of the insulating layer listed in Tables 5.4, 5.5 and 5.6, with applicable
piping sizes,mm;
thermal conductivity coefficient of replacement materials at the liquid applicable
temperatures, W/m.K.

d) Inlet and outlet air duct system insulation: inlet and outlet air ducts shall be affixed with an
insulating layer with thickness equal or greater than the thickness values specified in Table
2.11. No insulation is required for air exhausts.

e) Testing and calibration: fans or pumps with capacity of 5 HPs (3.7kW) or higher shall have
their designed flows calibrated in by calibrating speeds using multi-speed drives, twin-speed
drives or variable speed drives (VSDs). Adjustment of fan and pump flow using flow-
regulating valves shall be restricted.
f) Cooling tower fan control: heat extraction towers with fan motors of 5 HPs (3.7 kW) or
higher shall be equipped with multi-speed drives, twin-speed drives or variable speed drives
(VSDs).

g) Water cooling chiller system: water-cooled air conditioning systems shall be designed with
variable flow rates using pumps with variable speed drives.

h) Buildings with central air conditioning must be equipped with enthalpy recovery systems.
Equipment energy recovery efficiency shall be no smaller than 50%.

2) Supplementary requirements for mechanical ventilating and air conditioning systems
To be qualified, mechanical ventilating and air conditioning systems shall meet the following
additional requirements.

QCVN 09:2013/BXD
11
a) CO
2
sensor: installed to increase the inlet air flow for standard zones with design area of less
than 3 m
2
/occupant.
b) Automatic timer: intermittent ventilating fans shall be equipped with timers or automatic
controls that are able to set their own on/off and operational timings.
c) Piping welding and joining: inlet and circulating air ducts shall meet the requirements for
joining air and fluid piping in line with existing regulations.

Table 2.6. Coefficient of performance for direct electric air conditioners

Type of equipment Cooling output
Min COP of air
conditioners.
kW/kW
Test procedures
Unitary air-conditioner

-
2.30
TCVN 7830:2012
and
TCVN 6307:1997
Split air-conditioner

<4.5 kW
2.60
> 4.5 kW and < 7.0 kW
2.50
> 7.0 kW and < 14.0
kW
2.40
Air-cooled air-
conditioner
>14.0 kW and < 19 kW

2.93
TCVN 6307:1997
or
ARI 210/240
> 19 kW and < 40 kW 3.02
ARI 340/360
> 40 kW and < 70 kW 2.84
> 70 kW and < 117 kW 2.78
> 117 kW 2.70

Water-cooled and
evaporating air-
conditioner

<19 kW 3.35 ARI 210/240
>19 kW and <40 kW 3.37
ARI 340/360
> 40 kW and < 70 kW 3.32
> 70 kW 2.70
Air-cooled condenser
units
> 40 kW 2.96

ARI 365

ARI 365
Water-cooled or
evaporating condenser
units
> 40 kW

3.84
Unofficial translation - QCVN 09: 2013/BXD
12
Notes:
1) Coefficient of performance of air-conditioners: COP = refrigerant output/power input (kW/ kW);
2) Condenser units, including the compressor and condenser coils;
3) Minimum coefficients of performance listed in the Table are calculated at 100% of refrigerant
output. To calculate the coefficient of performance for AC units running for one year, ARI 340/360 uses
the following equation:
IEER = 0.020A + 0.617B + 0.238C + 0.125D (W/W)
where,
IEER Integrated energy efficiency ratio: coefficient of performance of AC units running for one
year at various loads.
A = EER coefficient of performance of the AC unit (W/W) at full load;
B = EER coefficient of performance of the AC unit (W/W) at 75% load;
C = EER coefficient of performance of the AC unit (W/W) at 50% load;
D = EER coefficient of performance of the AC unit (W/W) at 25% load.

Table 2.7. Coefficient of performance for chillers


Type of equipment

Cooling output (kW) Chiller
coefficient of
performance.
COP
MIN
. kW/kW
Input energy
consumption
PIC
MAX
. kW/RT
Electricity Heat
Air-cooled chiller, electric
Attached or separated
condenser
All capacities 3.10 1.133 -
Reciprocating water-cooled
chiller, electric
All capacities 4.20 0.836 -
Water-cooled rotary
screw/scroll chiller, electric
< 528 4.45 0.789 -
528 and < 1055 4.90 0.717 -
1055 5.50 0.639 -
Centrifugal water-cooled
chiller, electric
< 528 5.00 0.702 -
528 and < 1055 5.55 0.633 -
1055 6.10 0.576 -
Air-cooled absorption
chiller,
single effect
All capacities 0.60 (*) - 5.860
Water-cooled absorption
chiller, double effects
All capacities 0.70 (*) - 5.022
Absorber chiller, double
effects, indirectly fired
All capacities 1.00 (*) - 3.516
Absorber chiller, double
effects, directly fired
All capacities 1.00 (*) - 3.516
Notes:
1) Source: ASHRAE Standard 90,1-2001; ASHRAE Standard 90,1-2004;
2) (*) For absorption chillers, COP = Cooling output/Heat input;
- Power input consumption: PIC = electricity input/cooling output in RT;
- Refrigerant Ton (RT):1RT = 3.516 kW = 12000 Btu/h;
3) To calculate the coefficient of performance for chillers operating in one year, ARI 550/590-2003
provides the following equation:
IPLV = 0.01A + 0.42B + 0.45C + 0.12D (kW/kW)
where,
IEER Integrated energy efficiency ratio: coefficient of performance of cooling equipment for

QCVN 09:2013/BXD
13
the accumulated operational time in one year on various loads.
A COP (kW/kW) at full load;
B COP (kW/kW) at 75% load;
C COP (kW/kW) at 50% load;
D COP (kW/kW) at 25% load.

Table 2.8a. Performance specifications for cooling towers

Type of
equipment
Cooling
output
range
Rating criteria
Rated specifications
Test
procedure

Water flow
throughput
Supplementary
water flow
Fan
output

Cooling
tower with
draft fans
and
centrifugal
fans
All
capacities
Input water
temperature:37
0
C
Output water
temperature:
32
0
C
Moist air
temperature:27
0
C
13
l/minute,
Tc
1.0 1.4 %
Water flow
through
condenser
35 40
W/Tc
CTI
Notes:
1) CTI Cooling Technology Institute;
2) Tc: condenser ton; Tc = RT 1.25 = 3.516 1.25 = 4.395 Kw.

Table 2.8b. Required specifications for condenser units

Type of
equipment
Cooling
output
range
Rating
criteria
Rated specifications
Test
procedure
Wind flow Fan Compressor
Air-cooled
condenser
units, with
compressor
0.5500
RT
Input air
temperature:
35
0
C
1734
m3/minute
RT
75150
W/RT
1.01.3
kW/RT
CTC
Water-cooled
condenser units
101600
RT
Input water
temperature:
29.4
0
C
Output water
temperature:
35
0
C
Water flow
9.08 11.40 l/minute RT
CTC
Notes:
CTC Cooling towers and condensers
HVAC Equations, Data and Rules of Thumb, 2008, USA.

Table 2.9. Thickness of insulation for copper refrigerant conduits


Copper conduit
diameter, mm
Air conditioned space
Applicable conditions: t=26 2
o
C, = 60%
Refrigerant temperature
o
C
2 -18 -30
Unofficial translation - QCVN 09: 2013/BXD
14
Insulation thickness, mm
616 9 19 19
1925 9 19 19
3454 9 19 25
6680 13 19 25
105 - - 25

Copper conduit
diameter
mm
Non-air conditioned space
Applicable conditions: t =2632
o
C, = 85%
Refrigerant temperature
o
C
2 -18 -30
Insulation thickness, mm
616 25 38 50
1925 32 50 50
3454 32 50 57
6680 32 50 64
105 - - 70

Copper conduit
diameter
mm
Applicable conditions: t = 3237
o
C, = 60%
Refrigerant temperature
o
C
2 -18 -30
Insulation thickness, mm
616 25 38 50
1925 32 50 50
3454 32 50 64
6680 32 57 70
105 - - 76
Notes:
1) t Exterior air temperature,
o
C;
2) The above insulation thickness applies to copper refrigerant (fluid, gas) conduits;
3) The thickness of the insulation (mm) given in the Table apply to insulating materials with thermal
conductivity within a range of 0.032 0.04 W/m.K at an average temperature of 24C. The
minimum thickness of the insulating layer shall increase with materials having thermal conductivity
higher than 0.04 W/m.K or decrease with materials having thermal conductivity less than 0.032
W/m.K and is adjusted using equation (5.1).

Table 2.10. Thickness of insulation for cooled water conduits


Steel pipe diameter, mm
Air conditioned space
Applicable conditions: t=26 2
o
C, = 60%
Cooled water temperature,
o
C
712
Insulation thickness, mm
2050 16
5075 16
75150 19
150250 19
250600 25

Steel pipe diameter, mm
Non-air conditioned space
Applicable conditions: t =2637
o
C, = 85%
Cooled water temperature,
o
C
712

QCVN 09:2013/BXD
15
Insulation thickness, mm
2050 25
5075 25
75150 30
150250 30
250600 38
Notes:
1) For steel pipes with diameters listed in the table being rated diameters (IPS - Iron pipe
standard);
2) The insulation thickness of steel pipes may apply also to PE, PPR and PN16 plastic pipes. In case
of PE and PPR plastic pipes, the diameter values listed in the Table are outside diameters.
3) The thickness of the insulating layer (mm) given in Table 5.5 apply to insulating materials with
thermal conductivity within a range of 0.032 0.04 W/m.K at an average temperature of
24C. The minimum thickness of the insulating layer shall increase with materials having
thermal conductivity higher than 0.04 W/m.K or decrease with materials having thermal
conductivity less than 0.032 W/m.K and is adjusted using equation (2.1).

Table 2.11. Thickness of insulation for air ducts

Air conditioned space
Applicable conditions: t=26 2
o
C, = 60%
Cooled air temperature,
o
C 1216
Insulation thickness, mm 15
Non-air conditioned space
Applicable conditions: t =2637
o
C, = 85%
Cooled air temperature,
o
C 1216
Insulation thickness, mm 20
Notes:
The thickness of insulation (mm) given in the Table apply to porous polymer, close-compartment
structured insulating materials with thermal conductivity within a range of 0.032 0.04 W/m.K at
a mean temperature of 24C. The minimum thickness of insulation shall increase with materials
having thermal conductivity higher than 0.04 W/m.K or decrease with materials having thermal
conductivity less than 0.032 W/m.K and is adjusted using equation (2.1).

2.3. Lighting
2.3.1 General provision
1) Scope
This section provides limits for the maximum allowable lighting output needed for the building
lighting system as well as limits on the acceptable performance of commonly used lighting
components (lamps and ballasts) and lighting control systems. The following categories do not fall
under the requirements of this section:
a) Lighting designed for theatrical performance, television shows, different parts of recreation
facilities, including hotel ballrooms, dance clubs, and areas where lighting is a vital technical
part of the show functions;
b) Specialized medical lighting;
c) Special lighting for research laboratories;
d) Safety lighting that automatically switches on and off during operation;
e) Lighting in special security zones as required by the law or local governments;
f) Safety or security zones for humans that need auxiliary lighting.

Unofficial translation - QCVN 09: 2013/BXD
16
2) Minimum illuminance
The minimum illuminance (lux) for functional spaces shall meet the requirements of prevailing
technical standards.

3) Maximum lighting power density
a) The mean lighting power density (LDP) of an entire building shall not exceed the maximum
allowed limits listed in Table 2.12. The mean lighting power density of a building equals the
total lighting output of the building divided by the total occupied area.

Table 2.12. Mandatory requirements for lighting power density (LPD)

Type of building LPD (W/m
2
)
Offices
11
Hotels
11
Hospitals
13
Schools
13
Commercial and services buildings
16
Apartments
8
Enclosed, in-house, basement car parks 3
Outdoor or open (roofed only) car parks 1.6

b) Other types of buildings with sizes subject to the restrictions of this Code but not listed in
Table 2.12 above may apply maximum values of lighting power density of up to 13 W/m
2
.
c) For mixed-use buildings with sizes subject to the restrictions of this Code and various
different functional areas, the functional use of each area shall be accounted for, with each
of the areas complying with the maximum lighting power density values listed in Table 2.12
above.
d) The mean lighting power density for parking lots is calculated by dividing the total lighting
power by the gross area of the parking lot.

2.3.2 Requirements on lighting equipment performance
1) Minimum lamp performance is defined in Tables 2.13 and 2.14.

Table 2.13. Minimum illuminating performance of linear fluorescent lamps

Rated lamp power, W Rated illumination efficiency, lm/W
14-20 72
20-40 78

Table 2.14. Minimum illuminating performance of compact fluorescent lamps

Rated lamp power, W Rated illumination performance, lm/W
5-8 55

QCVN 09:2013/BXD
17
9-14 60
15-24 65
25-60 70

2) Ballast efficacy values are listed in Table 2.15.

Table 2.15. Electronic ballast efficacy

Nominal output, W Ballast efficacy factor (BEF), %/W
18 5.518
20 5.049
22 4.619
30 3.281
32 3.043
36 2.681
40 2.473

2.3.3 Lighting controls
1) Lighting controls for different building spaces
Every space enclosed with ceiling-height partitions is a separate space that needs at least one lighting
control device. Each of these lighting control devices shall be actuated manually or by automatic
sensors for occupants in such space. Each control device must:
a) Cover a maximum floor area of 100 m
2

b) The spaces specified in Table 2.16 shall to be installed with occupancy sensors, which directly
connect to and control the lighting system. Occupancy sensors controlling lamps shall not be
connected to the exit lighting and security lighting systems.

Table 2.16. Buildings for which occupancy sensors are required

Type of building Application To be used in
Offices Mandatory Conference rooms and
passageways
Hotels Mandatory Conference rooms and
passageways
Hospitals Optional
Schools Mandatory
In-house parking lots and
passageways
Commercial and services
buildings
Optional
Apartments Mandatory
Passageways and in-house parking
lots

d) For parking lots, at least 70% of the lighting system shall be controlled through occupancy
sensors (proportion of the system in terms of lighting consumption power).

2) Controls for day-lit areas
Artificial lighting designs for day-lit enclosed spaces need to take into account the following
considerations:
a) Potentially day-lit areas are spaces parallel to windows/exterior glazing within a distance
from the window/exterior glazing of up to 1.5 times the height from the floor to the tip of
the window glass area or exterior glazing.
Unofficial translation - QCVN 09: 2013/BXD
18
b) All lighting equipment in potentially day-lit areas may be installed with lighting control
devices in ways that allow:
- Automatic photosensor to be used to control lamp dimming or turn lamps on and off
depending on the level of natural illuminance received. Photosensor shall be positioned at
half the depth of potentially day-lit areas. When natural light measured by the sensors at
beyond the standard preset level for the occupant space (e.g. 300 lux for offices), the sensors
should trigger lamp switch-off.
- Stand-alone lamps to be turned on at potentially day-lit areas independently from the public
lighting system.
c) In respect of the design for areas using concurrently occupancy sensors and photosensors,
the occupancy sensors shall be prioritized over photosensors for lighting control.
d) Hospitals, apartment buildings and hotel rooms are not mandatorily required to apply the
requirements of 2.3.3.
e) Spaces designed for special uses are exempted from the requirements of 2.3.3 2), providing
that the designer presents detailed justification.

3) Auxiliary lighting controls
Auxiliary controls for light on/off switching installed in fixed positions underneath decks, shelves,
cabinets and so on shall be used in the following events:
a) Lighting for hotel, guesthouse rooms and luxurious guestrooms;
b) Display lighting in shops or for demonstration.

2.4. Escalators and elevators
2.4.1 Escalators
Escalators must be fitted with controls to reduce speed or to stop when no traffic is detected.
Escalators shall be designed with energy savings features as described below:
1) Reduced speed control: the escalator shall change to a slower speed when no activity has
been detected for a period of a maximum of three minutes. Detection shall be by photocell
activation at the top and bottom landing areas.
2) Use on demand: the escalator shall shut down when no activity has been detected for a
period of a maximum of fifteen minutes. Use on demand escalators must be designed with
energy efficient soft start technology. The escalator shall start automatically when required.
The activation shall be by photocells installed in the top and bottom landing areas.

2.4.2 Elevators (lifts)
Elevators (lifts) must be provided with controls to reduce the energy demand. To meet this
requirement, the following features must be incorporated in traction drive elevators:
1) Use of AC Variable-Voltage and Variable-Frequency drives on non-hydraulic elevators.
2) The lift car uses energy-efficient lighting and display lighting i.e. an average lamp efficacy,
across all fittings in the car, of >55 lamp lumens/circuit watt and lighting switches off after
the lift has been inactive for a maximum period of five minutes.
3) Elevators shall operate in a stand-by condition during off-peak periods. For example, the
power side of the lift controller and other operating equipment such as lift car lighting, user
displays and ventilation fans switch off when the lift has been inactive for a maximum period
of five minutes.

2.5. Electric power consumption
2.5.1 Electrical distribution system
1) Measurement

QCVN 09:2013/BXD
19
Building electrical distribution system shall be equipped with attached metering instruments to
record energy demand (kVA), power consumption (kWh), and total loads on electricity meters.
Electrical distribution systems in buildings shall be designed so that energy consumption at end-use
loads can be check-metered. Check-metering is required for load facilities with total installed power
consumption of over 100 kVA, including lighting and socket outlets, air conditioning system,
ventilation, hot water system and other load centers of over 100 kVA.
2) Submetering
Sub-metering for each tenant and a provision to permit check-metering the tenant load shall be in
place.

Notes: Shared (central) air-conditioning systems need not meet these tenant check-metering
requirements.

3) Power factor correction
All 3-phase electricity supplies exceeding 100 A shall maintain a power factor between 0.90 lag and
unity at the point of connection.

4) Adjustment of installed power
Electrical systems in a building shall be estimated, designed and operated to provide the maximum
concurrent load factor possible as specified in Table 2.17 and the highest allowed installed power as
specified in Table 2.18.

Table 2.17. Maximum concurrent load factor ks, by points of use

End-use load Concurrent load factor k
s

Lighting 0.9
Socket outlets 0.4
Air conditioning, ventilation 0.9
Hot water system 0.9
Other major load centers 0.9
Entire building 0.8

Table 2.18. Maximum allowed installed power

Type of building Installed power, W/m
2

Upscale apartment buildings 70
Hotels 80
Offices, public use buildings 75
Commercial, service, public service buildings 65
Schools, hospitals 65

2.5.2 Electric motors
All permanently wired 3-phase induction motors that are used in the building shall have a nominal
full-load motor efficacy of no less than the values required in Table 2.19. The manufacturers labels
on the motors must provide minimum efficacy, nominal efficacy and outputs at full load.

Table 2.19. Minimum efficacy for electric motors

Motor output, kW
kW
Required efficacy, %
2-pole 4-pole
Unofficial translation - QCVN 09: 2013/BXD
20
1.1 82.2 83.8
1.5 84.1 85.0
2.2 85.6 86.4
3.0 86.7 87.4
4.0 87.6 88.3
5.5 88.5 89.2
7.5 89.5 90.1
11.0 90.6 91.0
15.0 91.3 91.8
18.5 91.8 92.2
22.0 92.2 92.6
30.0 92.9 93.2
37.0 93.3 93.6
45.0 93.7 93.9
55.0 94.0 94.2
75.0 94.6 94.7
90.0 95.3 95.1
110.0 95.4 95.6
132.0 95.5 95.7
160.0 95.8 95.8
200.0 96.1 95.9
250.0 96.2 96.1
280.0 96.3 96.4
315.0 96.4 96.5
355.0 96.5 96.6
400.0 96.7 96.7
450.0 96.7 96.8
500.0 96.8 96.9
560.0 96.9 97.0
630.0 96.9 97.1
Notes: Motors with outputs in between two numbers shall adopt
the higher efficacy value.

2.6.Service water heating system
2.6.1 General requirements
Designed loads for service water heating systems shall be calculated based on system sizing and
follow the manufacturers recommendations.

In case other (non-resistance) service water heating solutions of higher efficiency are available,
resistance-based service water heating systems shall not be allowed.


QCVN 09:2013/BXD
21
Buildings in need of high, concentrated service water heating with installation input of over 50 kW or
power consumption of over 50,000 kWh/year are not allowed to use resistance-based service water
heating solutions.

Order of priority for civil buildings:
1) Temperature range 60
o
C
a) Service water heating using heat recovery air conditioning;
b) Service water heating using solar power combined with heat pumps/electric heaters;
c) Service water heating using heat pumps;
d) Service water heating using gas water heaters;
e) Service water heating using electric heaters for buildings with less than 25 rooms.

2) Temperature range 115
o
C (cooking, washing, disinfection, sauna)
For buildings in concurrent needs of hot water of 60
0
C (for household uses) and hot water/steam of
115
0
C (for cooking, laundering, sauna and disinfection), priorities shall be given to water heating up
to 60
0
C, before further heating the water or steam up to 115
0
C using gas or fuel oil-fired heaters.

2.6.2 Water heating equipment efficacy
All water heating and supply equipment used internally for heating potable water, keeping warm,
hot swimming pool and hot water storage tanks shall meet the requirements listed in Table 2.20. For
heat pump water heaters, refer to Table 2.21.

Table 2.20.Minimum efficacy for water heating equipment
Equipment type Minimum efficiency ET, %
1. Gas-fired storage water heaters 78
2. Gas-fired instantaneous water heaters 78
3. Gas-fired hot water supply boilers 77
4. Fuel oil-fired hot water heaters and supply systems 80
5. Duel fuel gas/oil-fired hot water supply boilers 80
6. Firewood/paper-fired boiler of 10350 kW output 60*)
7. Boilers of 102000 kW, burnt with molded brown coal 70*)
8.Pitcoal-fired boilers of 102000 kW 73*)
Notes:
1. The minimum efficiency for oil or gas-fired water heaters is given in terms of Thermal efficiency
(ET), which includes thermal losses from the heater shell.
2. *) According to DIN 4702 Part 1 (DIN German standards).

Efficacy for electric resistance-based water heaters in particular is given in terms of maximum
Standby loss (SL), where a 40C temperature difference between stored water and ambient
requirements exists, and is determined using the equation:
E
min
= 5.9 + 5.3V0.5, W (2.2)
Where
-V is volume in liters.

Table 2.21. Minimum coefficient of performance - COP for water heating heat pumps

Equipment type COP, kW/kW
Air-heated heat pumps 3.0
Water-heated heat pumps 3.5
Heat recovery air conditioners
Unofficial translation - QCVN 09: 2013/BXD
22
- Hot water supply only
- Air conditioning and hot water supply
3.0
5.5

Electric resistance-based water heating equipment is not recommended except for supporting solar
power systems. Electric heat pump water heating equipment with higher energy efficiency than
electric resistance-based water heaters is recommended.

Where eligible, solar powered service water heating systems may be used to meet all or part of
water heating needs for the building. Solar powered water heaters shall have at least 60% efficacy
and minimum thermal insulation R of 2.2 m
2
.K/W at the back of the solar panels.

2.6.3 Service water heating piping insulation
The following hot water piping shall be insulated.
1) Steam piping serving such needs as laundry, cooking etc.
2) Hot water piping for bath, keeping warm, cooking etc.

The insulation thickness of the piping shall be equal or greater than the insulation thicknesses listed
in Tables 2.22 and 2.23.

Table 2.22. Insulation thickness for hot water steel piping

Pipe size
Air temperature; t = 5 37
o
C
Hot water temperature (
o
C)
115 5090
mm Insulation thickness (mm)
2050 50 20
6580 50 20
90150 63 25
200250 63 25
Notes:
1. Insulating materials shall have conductivity of 0.06 0.07 W/m.K, applicable to 115
o
C.
2. Closed particle structured, porous polymer insulating materials with thermal conductivity of
0.032 0.04 W/m.K adopt the temperature range of 5090
o
C.
3. The insulation thicknesses in Table 2.22 shall ensure that the exterior temperature is lower
than 43
o
C.
4. For insulating materials with conductivity outside the above mentioned range, the minimum
thickness (b
min
) is determined using equation (2.1).

Table 2.23. Insulation thickness for PPR, PE hot water piping

Outer diameter of PN20/ PN25 plastic pipes
Conductivity 0.2 W/mK
Air temperature; t = 5 37
o
C
mm
Hot water temperature (
o
C)
5090
20 50 16

QCVN 09:2013/BXD
23
65 19
80 125 25
Notes:
1) For residential buildings, insulation may be optional for PPR hot piping.
2) Insulating materials shall maintain conductivity of 0.034 0.04 W/m.K.
3) For insulating materials with conductivity outside the above mentioned range, the minimum
thickness (b
min
) is determined using formula (2.1).

2.6.4 Service water heating system controls
1) Temperature controls shall be provided to limit point-of-use water temperatures not to
exceed 50C.

2) Temperature controls shall be provided to limit the maximum temperature of water
delivered to wash basin faucets in public restrooms up to 43C.

3) Systems designed to maintain usage temperatures in hot water pipes shall be equipped with
automatic ON/OFF switches that can be set to maintain desirable temperatures for
recirculating hot water.

4) Recirculating pumps used to maintain storage tank water temperatures shall be controlled in
ways to operate in harmony with the operating mode of the service water supply system.


III.MANAGEMENT REGULATIONS
3.1. Design documentations of newly developed, reconditioned and retrofitted buildings with sizes
subject to the scope of QCVN 09:2013/BXD shall include a narrative demonstration of compliance
with the requirements of this Code.

3.2. Review and assessment of building designs shall be done in accordance with prevailing rules,
including verification of compliance with the requirements of QCVN 09:2013/BXD for buildings that
fall under the scope of this Code.


IV.IMPLEMENTATION ARRANGMENT
4.1. The Department of Science,-Technology and Environment (Ministry of Construction) is
responsible for popularizing and providing the implementation guidelines for QCVN 09:2013/BXD to
interested parties.

4.2. Local regulators shall monitor compliance with the requirements of QCVN 09:2013/BXD for
building design and construction works taking place in their jurisdictions and in accordance with the
existing laws.

4.3. Any concerns that may arise during the adoption of this Code may be relayed to the Department
of Science, Technology and Environment (Ministry of Construction) for guidance and responses.

Unofficial translation - QCVN 09: 2013/BXD
24
ANNEXES
(For reference)

PHYSICAL SPECIFICATIONS OF MATERIALS, COMPOSITION AND THERMAL RESISTANCE
CALCULATION FOR ENCLOSING ASSEMBLIES

1. Equation for the calculation of thermal resistance and overall heat transfer coefficient (U-value)
of enclosing assembly
T
a
n
i
i
N
o
h
R
b
h
R
1 1

1
+ + + =

, m2.K/W (1)
where:
h
N
, h
T
respectively, the heat transfer coefficients of outer and inner surfaces of building
envelope, W/m
2
.K ;
bi - thickness of i
th
material layer, m;
i - thermal conductivity of the i
th
material layer of the enclosing assembly, W/m.K;
n - number of material layers in the enclosing assembly;
Ra - thermal resistance of the air layer inside the enclosing assembly, if any, m
2
.K/W .
o
o
R
U
1
=
, W/m2.K (2)
where:
Thermal conductivity
I
listed in Table 1.
See Table 3 for h
N
and h
T
.
See Table 4 for the thermal resistance of air layer R
a
.

2. Key parameters needed for building envelope calculations

Table 1. Physical specifications of building materials
Name of materials
Unit
weight
, kg/m
3

Thermal
conductivity
,W/m.K
Specific
heat
capacity,
kJ/kg.K
Moisture
conductivity
mg/m.h.kP
a

I. Asbestos-based materials
Asbestos-cement boards and panels
1900 0.35 0.84 0.03
Asbestos-cement insulating boards
500 0.13 0.84 0.39
Asbestos-cement insulating boards
300 0.09 0.84 -
II. Concrete panels
Steel-net cement roof tile
2500 - 0.84 0.00
Reinforced concrete
2400 1.55 0.84 0.03
Broken rock and macadam concrete
2200 1.28 1.21 0.05
Broken brick concrete
1800 0.87 0.84 0.07
Light concrete (cinder concrete)
1500 0.70 0.80 0.09
Light concrete (cinder concrete)
1200 0.52 0.75 0.11
Light concrete (cinder concrete)
1000 0.41 0.75 0.14
Heat absorbing sponge concrete
1000 0.40 0.84 0.08
Heat absorbing sponge concrete
800 0.29 0.84 0.08
Heat absorbing sponge concrete
600 0.21 0.84 0.13
Heat absorbing sponge concrete
400 0.15 0.84 0.20

QCVN 09:2013/BXD
25
Heat absorbing silicate sponge concrete
800 0.29 0.84 0.18
Heat absorbing silicate sponge concrete
600 0.21 0.84 0.21
Heat absorbing silicate sponge concrete
400 0.15 0.84 0.24
III. Gypsum-based materials
Drywall
1000 0.23 0.84 0.05
Pure gypsum boards and pieces
1000 0.41 0.84 0.11
Kiln cinder gypsum concrete
1000 0.37 0.80 0.15
IV. Terracotta materials, cushion materials, building brick blocks and coating layers
Rammed clay and clay bricks
2000 0.93 0.84 0.10
Adobe
1600 0.70 1.05 0.17
Underneath humus
1800 1.16 0.84 -
Dry sand used as a cushion material
1600 0.58 0.84 0.17
Cushion materials made of sifted dry humus
1400 0.52 0.84 0.19
Silicate soil used as a cushion layer
600 0.17 0.84 0.30
Common bricks laid with heavy mortar
1800 0.81 0.88 0.11
Common bricks laid with light mortar
1700 0.76 0.88 0.12
Silicate bricks laid with heavy mortar
1900 0.87 0.84 0.11
Multi-hole bricks ( = 1300) laid with light
mortar ( = 1400) 1350 0.58 0.88 0.15
Multi-hole bricks laid with heavy mortar
1300 0.52 0.88 -
Heavy mortar and coating cement mortar
1800 0.93 0.84 0.09
3-constituent mortar and 3-constituent coating
mortar 1700 0.87 0.84 0.10
Lime mortar
1600 0.81 0.84 0.12
V. Non-fired brick, autoclaved aerated concrete
AAC non-fired brick 400-900 0.12-0.13 - -
Autoclaved aerated concrete (AAC lightweight
brick)
400-800 0.153 - -
Autoclaved aerated concrete brick 400-1000 0.11-0.22 - -
Autoclaved aerated concrete (Chinese standard
GB-11968:2006)
300 0.10 - -
400 0.12 - -
500 0.14 - -
600 0.16 - -
700 0.18 - -
800 0.20 - -
VI. Coal and cinder materials
Peat-based insulating board
225 0.07 1.67 0.19
Kiln cinder
1000 0.29 0.75 0.20
Kiln cinder
700 0.22 0.75 0.22
Blast furnace cinder in particle state
500 0.16 0.75 0.23
Cinder brick
1400 0.58 0.75 -
Light cinder mortar
1400 0.64 0.75 0.11
Light cinder mortar
1200 0.52 0.75 0.14
Unofficial translation - QCVN 09: 2013/BXD
26
External coating lime mortar
1600 0.87 0.84 0.14
Internal coating lime mortar
1600 0.70 0.84 0.14
External coating mortar for wood lath
1400 0.70 1.05 0.12
Internal coating mortar for wood lath
1400 0.52 1.05 0.12
Lime coating mortar mixed with slag
1200 0.47 0.80 0.14
Surface coating hard wood fiber board
700 0.23 1.47 0.08
VII. Scrolling materials
Quality paperboard
1000 0.23 1.47 -
Normal paperboard
700 0.17 1.47 -
Corrugated paperboard
150 0.06 1.47 -
Resin paper, bitumen paper
600 0.17 1.47 -
VIII. Agricultural products
Rice husk
250 0.21 1.88 -
Rush
400 0.14 1.47 -
Straw
320 0.09 1.51 -
Straw-based panel
300 0.10 1.47 -
Rush-based panel 1900
360 0.10 1.51 -
IX. Glass materials

Window glass
2500 0.78 0.84 0.00
Fiberglass
200 0.06 0.84 0.49
Vapor glass and bubble glass
500 0.16 0.84 0.02
Vapor glass and bubble glass
300 0.12 0.84 0.02
X. Wooden and cork materials

Pine and (cross the grain)
550 0.17 2.51 -
Pine and (along the grain)
550 0.35 2.51 0.32
Sawdust
250 0.09 2.51 0.26
Treated sawdust
300 0.13 2.30 0.26
Sawdust mixed with resin
300 0.12 1.88 0.25
Plywood
600 0.17 2.51 0.02
Fiberboard
600 0.16 2.51 0.11
-ditto
250 0.08 2.51 0.09
-ditto
150 0.06 2.51 0.34
Soft wood board (corkwood)
250 0.07 2.09 0.04
Boards made of corkwood waste
150 0.06 1.88 0.05
XI. Metals

Steel sheet metal
7850 58 0.48 0
Pig iron
7200 50 0.48 0
Aluminum
2600 220 0.48 0
XI. Other materials

Indoor matting (cotton rug)
150 0.06 1.88 0.34

QCVN 09:2013/BXD
27
Mineral cotton rug
200 0.07 0.75 0.49
Mineral cotton rug
250 0.08 0.75 0.45
Patterned silicate boards and patterned silicate
cement boards
600 0.23 2.30 -
Patterned silicate boards and patterned silicate
cement boards
400 0.16 2.30 -
Patterned silicate boards and patterned silicate
cement boards
250 0.12 2.30 -
Notes:
1 W/m.K=0.86 kcal/m.h.
o
C; 1 kJ/kg.K=0.24 kcal/kg.
o
C ;
For new building materials not listed in this table, designers may use other international standards.

Table 2. Solar heat gain coefficient of material surface

No Surface, materials and colors ratio
1. Materials
1 White paper 0.20
2 Dry peat 0.64
3 Particle ceramics 0.8 - 0.85
4 Cinder 0.81


2. Wall surface
5 Polished, bright colored limestone 0.35
6 Ditto, dark colored 0.50
7 Brownish yellow sandstone 0.54
8 Dark yellow sandstone 0.62
9 Red sandstone 0.73
10 Polished, white marble 0.30
11 Ditto, dark colored 0.65
12 Polished, light grey granite 0.55
13 Grey, polished granite 0.60
14 Enameled, white brick 0.26
15 Ditto, bright brown colored 0.55
16 Common, dusted bricks 0.77
17 Ditto, new red colored 0.70 - 0.74
18 Surface coating bricks, bright colored 0.45
19 Smooth, even concrete surface 0.54 - 0.65
20 Mortared surface, yellow-white painted 0.42
21 Ditto, dark colored 0.73
22 Ditto, white colored 0.40
23 Ditto, light blue colored 0.59
24 Ditto, light cement colored 0.47
25 Ditto, snow-white colored 0.32
26 Vapor silicate 0.56 - 0.59
27 Plain wood 0.59
28 Wood painted in dark colors 0.77
29 Wood painted in light yellow colors 0.60
30 Smooth polished bamboo 0.43
31 Normal bamboo 0.60
Unofficial translation - QCVN 09: 2013/BXD
28
3. Roofing surface
32 New, white fibrocement boards 0.42
33 Ditto, used for 6 months 0.61
34 Ditto, used for 12 months 0.71
35 Ditto, re-coated with cement water 0.59
36 Ditto, used for 6 years 0.83
37 Corrugated mineral cotton boards 0.61
38 Light brownish mineral cotton boards 0.53
39 Roofing oilpaper, coarse finish 0.91
40 Ditto, sprinkle-coated with mineral particles 0.84
41 Ditto, sprinkled with grey colored sand particles 0.88
42 Ditto, sprinkled with dark colored sand particles 0.90
43 Light colored sheet metal 0.26
44 Black sheet metal 0.86
45 Red or brown roof tile 0.65 - 0.72
46 Grey cement roof tile 0.65
47 Polished or white plated steel 0.45
48 Ditto, in blue color 0.76
49 Galvanized steel, new 0.30
50 Ditto, dusted 0.90
51 Unpolished aluminum 0.52
52 Polished aluminum 0.26
4. Paint coated surface
53 Painted in bright red (pink) color 0.52
54 Painted in blue color 0.64
55 Painted with cobalt-based materials, in bright blue color 0.58
56 Ditto, purple color 0.83
57 Painted in yellow 0.44
58 Painted in red 0.63
5. Sidewalk and road surface
59 New asphalt 0.89
60 Old asphalt 0.67
61 Cinder concrete 0.89
62 Granite macadam 0.80
63 Sand mixed with gravel 0.66
64 Wet sand 0.80
65 Granite rock and gravel 0.67
6. Transparent materials
66 Polyclovinil screen, thickness 0.1 mm 0.096
67 AFF polyamide screen, thickness 0.08 mm 0.164
68 Polyethylene screen, thickness 0.085 mm 0.109
69 7 mm-thick glass 0.076
70 4,5 mm-thick door glass 0.04
71 6 mm-thick glass with heat absorbing surface 0.306
72 17 mm-thick imaging glass 0.02
73 1.2 mm-thick colorless organic glass 0.123
74 Ditto, yellow colored, 2.7 mm in thickness 0.46
75 Ditto, blue colored, 1.4 mm in thickness 0.34


QCVN 09:2013/BXD
29

o
o
- L p va tr t =15 mm o
15 105 15
- L p va tr t =15 mm
- G ch t st nung =105 mm
Table 3. Surface heat transfer coefficient of envelope structures h, W/m
2
.K
(in accordance with TCVN 298:2003 and ISO 6946:1996 standards)


Name of coefficient
Heat flux direction
Horizontal
(for walls)
Upward
(for roofing)
Downward
(for roofing)
Outer surface heat
transfer coefficient hN,
W/m
2
.K
25 25 25
Inner surface heat
transfer coefficient hT,
W/m
2
.K
7.692 10 5.882

Table 4. Thermal resistance of unventilated air layer Ra, m
2
.K/W
(in accordance with TCVN 298:2003 and ISO 6946:1996 standards)


Air layer
thickness, mm
Heat flux direction
Horizontal
(for vertical air layer)

Upward
(for horizontal air layer)

Downward
(for horizontal air layer)

0 0.00 0.00 0.00
5 0.11 0.11 0.11
7 0.13 0.13 0.13
10 0.15 0.15 0.15
15 0.17 0.16 0.17
25 0.18 0.16 0.19
50 0.18 0.16 0.21
100 0.18 0.16 0.22
300 0.18 0.16 0.23
Notes: Intermediate values may be determined using linear interpolation.

3. Select common exterior wall and roof designs, and total thermal resistance R
o
may be calculated
using equation (1).

3.1. WALLS
T1. Single-leaf wall (conventional thickness: 110 mm), fireclay solid
bricks

Unofficial translation - QCVN 09: 2013/BXD
30

105 15
6
0
1
0
- L p va tr t =15 mm
- G ch t st nung =105 mm
o
o
- Va ch n m ch =10 mm o
- G ch t st nung =105 mm o
- L p va tr t =15 mm o
10 105 15

- G ch rng =105 mm
15 105 15
- L p va tr t =15 mm o
- L p va tr t =15 mm o
o


No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Exterior plaster 0.015 0.93
0.332
R
o
<0.56 m
2
.K/W
Not qualified!
2
Fireclay solid brick and heavy
(cement) mortar brickwork
0.105 0.81
3 Interior plaster 0.015 0.93

T2. One brick thick wall (conventional thickness: 220 mm), fireclay solid bricks






No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Exterior plaster 0.015 0.93
0.474
R
o
<0.56 m
2
.K/W
Not qualified!
2
Fireclay solid brick and heavy
(cement) mortar brickwork
0.220 0.81
3 Interior plaster 0.015 0.93

T3. Single-leaf wall (conventional thickness: 110 mm), fireclay hollow bricks





- Plaster =15 mm
- Fireclay bricks =105 mm
- Joint mortar =10 mm
- Fireclay bricks =105 mm
- Plaster =15 mm
- Plaster =15 mm
- Hollow bricks =105 mm
- Plaster =15 mm
- Plaster =15 mm
- Fireclay bricks =105 mm
- Plaster =15 mm

QCVN 09:2013/BXD
31

10 105 15 105 15
6
0
1
0
- L p va tr t =15 mm o
- G ch rng =105 mm o
- V a ch n m ch =10 mm o
- G ch rng =105 mm o
- L p va tr t =15 mm o

15 105 15
- L p va tr t =15 mm o
- L p va tr t =15 mm o
- Bl c b tng nh =105 mm o
No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total thermal
resistance R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Exterior plaster 0.015 0.93
0.383
R
o
<0.56 m
2
.K/W
Not qualified!
2
Hollow bricks ( = 1300) and light
plaster ( = 1400) brickwork
0.105 0.58
3 Interior plaster 0.015 0.93

T4. Calculating thermal resistance for one brick thick walls (conventional thickness: 20 mm),
fireclay hollow bricks






No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not qualified
for Code requirements
1 Exterior plaster 0.015 0.93
0.584
or
0.625
R
o
>0.56 m
2
.K/W
Qualified
or
Qualified and over
qualified

2
Hollow bricks ( = 1300) and light
mortar ( = 1400) brickwork
or
Multi-hole bricks with heavy
(cement) mortar brickwork
0.220
0.58
or
0.52
3 Interior plaster 0.015 0.93

T5. Brick, porous concrete and single-leaf walls (conventional thickness: 110 mm)

- Plaster =15 mm
- Hollow bricks =105 mm
- Joint mortar =10 mm
- Hollow bricks=105 mm
- Plaster =15 mm
- Plaster =15 mm
- Autoclaved lightweight concrete=105 mm
- Plaster =15 mm
Unofficial translation - QCVN 09: 2013/BXD
32

10 105 15 105 15
- L p va tr t =15 mm
- Bl c b tng nh =105 mm
o
o
- Va ch n m ch =10 mm o
- L p va tr t =15 mm o
- Bl c b tng nh =105 mm o
6
0
1
0
No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements

1 Exterior plaster 0.015 0.93
0.486
R
o
<0.56 m
2
.K/W
Not qualified!
2 Porous concrete bricks 0.105 0.37
3 Interior plaster 0.015 0.93
T6. Brick, porous concrete and one brick thick walls (conventional thickness: 220 mm)






No Material layers, outside in
Thickness,
m
Thermal
conductivity,
, W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements

1 Exterior plaster 0.015 0.93
0.797
R
o
>0.56 m
2
.K/W
Qualified and over
qualified
2 Porous concrete bricks 0.220 0.37
3 Interior plaster 0.015 0.93

T7. 3D 180 mm thick panels




No Material layers, outside in Thickness, m
Thermal
conductivi
ty, ,
W/(m.K)

Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not qualified
for Code requirements
1 Exterior plaster 0.015 0.93 0.81 1.56

15 502050 15
c l - i thp
- L p va tr t =15 mm o
- L p xi m ng c t =50 mm o
- Tm pol ystyrol =20 - 50 mm o
c l - i thp
- L p xi m ng c t =50 mm o
- L p va tr t =15 mm o
- Plaster=15 mm
- Sand cement layer, with steel mesh =50 mm
- Polystyrol panel =20-50 mm
- Sand cement layer, with steel mesh =50 mm
- Plaster=15 mm
- Plaster=15 mm
- Autoclaved lightweight concrete =105 mm
- Joint mortar =10 mm
- Autoclaved lightweight concrete=105 mm
- Plaster =15 mm

QCVN 09:2013/BXD
33
- G ch l nem 200 200 15 mm
- V a l t =10 mm o
- G ch chng nng 200 200 105 mm, =105 mm o
- V a xi m ng l - i thp chng thm =20 mm o
- B tng ct thp m i =120 mm o
- V a tr t trn =15 mm o
2
Cement, sand and steel mesh
3D panels
0.05 0.93
R
o
>0.56 m
2
.K/W
Qualified and over
qualified
or excessively over
qualified
3
Porous polystyrol insulating
layer
0.02 0.05 0.04
4
Cement, sand and steel mesh
3D panels
0.05 0.93
5 Interior plaster 0.015 0.93
Notes: The total thermal resistance of exterior walls is calculated using the heat transfer coefficient of
the exterior surface - hN= 25 W/m2.K and heat transfer coefficient of the interior surface - hT= 7,692
W/m2.K see Table 3, Annexes.
3.2. ROOF

M1. Roofing with a 105 mm thick hollow brick insulating layer





No Material layers, top down
Thickne
ss, m
Thermal
conductivity
, , W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Terra cotta tile 0.015 0.81
0.640
R
o
< 1.0 m
2
.K / W
Not qualified
2 Tile plaster 0.01 0.93
3 Fireclay tile (continuous parts) 0.105 0.81
4 Fireclay tile (partition walls) 0.053 0.81
5
Aerated hollow holes, Ra = 0.22 m
2
. K
/ W
0.053
6 Vertical plaster lining 0.105 0.93
7 Cement and steel mesh plaster 0.02 0.93
8 Reinforced concrete 0.12 1.55
9 Interior plaster 0.015 0.93

M2. Roofing with a 105 mm thick hollow brick insulating layer and 150 mm thick porous concrete
=1000 kg/m3

With composition similar to the M1 roof, but with an additional 150 mm thick lightweight concrete
porous concrete layer =1000 kg/m3 - =0.41 W/(m.K) on top of the heat insulating tiles, resulting in
a total thermal resistance of the M2 roof of Ro=1.006 m
2
.K/W qualified.
- Terra cotta tile 200x200x15 mm
- Tiling mortar =10 mm
- Heat resistant brick 200x200x105 mm, =105 mm
- Damp resistant steel mesh cement mortar =20 mm
- Roof reinforced concrete =120 mm
- Ceiling plaster =15 mm
Unofficial translation - QCVN 09: 2013/BXD
34
- G ch l nem 200 200 15 mm
- V a l t =10 mm o
- Tm xp pol ystyrol =30 mm o
- V a xi m ng =5 mm o
- Xi m ng pol i mer chng thm =2 mm o
- B tng ct thp m i =120 mm o
- V a tr t trn =15 mm o
No Material layers, top down
Thicknes
s, m
Thermal
conductivit
y, ,
W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Terra cotta tile 0.015 0.81
1.006
R
o
> 1.0 m
2
.K / W
Qualified
2 Tile plaster 0.01 0.93
3
Lightweight-porous concrete layer
(=1000 kg/m3)
0.150 0.41
4 Fireclay tile (continuous parts) 0.105 0.81
5 Fireclay tile (partition walls) 0.053 0.81
6
Aerated hollow holes, R
a
= 0.22 m
2
. K /
W
0.053
7 Vertical plaster lining 0.105 0.93
8 Cement and steel mesh plaster 0.02 0.93
9 Reinforced concrete 0.12 1.55
10 Interior plaster 0.015 0.93

M3. Roofing with 30 mm thick polystyrol porous panels







No Material layers, top down
Thickne
ss, m
Thermal
conductivi
ty, ,
W/(m.K)
Total
thermal
resistance
R
o
,
m
2
.K/W
Qualified or not
qualified for Code
requirements
1 Terra cotta tile 0.015 0.81
1.140
Ro > 1.0 m
2
.K / W
Qualified
2 Tile plaster 0.01 0.93
3 Polystyol panel 0.03 0.04
4 Cement plaster 0.05 0.93
5
Damp resistance polymer cement
plaster
0.002 0.93
6 Reinforced concrete 0.12 1.55
7 Interior plaster 0.015 0.93
- Terra cotta tile 200x200x15 mm
- Tiling mortar =10 mm
- Polystyrol panel =30 mm
- Cement mortar =5 mm
- Damp resistant polymer cement =2 mm
- Roof reinforced concrete =120 mm
- Ceiling plaster =15 mm

QCVN 09:2013/BXD
35
Notes: The total thermal resistance of roofing is calculated using the heat transfer coefficient of the
exterior surface - hN= 25 W/m2.K and heat transfer coefficient of the interior surface - hT= 5,882
W/m2.K see Table 3, Annexes.

Вам также может понравиться