Академический Документы
Профессиональный Документы
Культура Документы
MftttlMKtJMNr
OCEAN ENGINEER
AND
Submitted to the Department of Ocean Engineering on May 12, 1977 in partial fulfillment of the requirements for the degrees of Ocean Engineer and Master of Science in Mechanical Engineering.
The finned tube contactor of a liquid desiccant (triethylene glycol) dehumidifier system is modeled with a fifth order differential equation to simulate the simultaneous heat and mass transfer associated with conditioning the air. Potential energy saving aspects of the sysComputer simulation results presented on psychrotem are discussed. metric charts show that significant performance is possible with contacThe cycle may be regenerated at tors of one half the recommended size. 120 to 140F depending on the system design requirements.
ACKNOWLEDGEMENTS
TABLE OF CONTENTS
PAGE
TITLE PAGE
1
2
ABSTRACT
ACKNOWLEDGEMENTS
LIST OF FIGURES AND TABLE
7
.
INTRODUCTION
13 19 26 35
39
II.
PSYCHROMETRY
LIQUID DESICCANT DEHUMIDIFICATION SYSTEM
III.
IV.
V.
METHOD OF ANALYSIS
RESULTS OF SIMULATION
VI.
CONCLUSIONS
53
REFERENCES
5A
APPENDICES
A.
B. C.
57
70
78
D. E.
85
FIGURE
1
2
PAGE
Conventional Air Conditioner with Reheat Conventional Air Conditioner with Bypass Mixing
Liquid Desiccant Dehumidification System
14
15 16
3 4
20
27
5 6
7
29
30
Dimensions for Determining Free Flow Area of Contactor Locations of Representative Temperatures and Sources
31 35
10a
Dehumidifier Operating Lines for Three TEG Concentrations and Three Cooling Water Temperatures on Psychrometric Chart Dehumidifier TEG Concentration vs. Flow Distance
Mass Transfer Flux vs. Flow Distance
Gas, Interface and Liquid Temperatures vs. Flow
40
42
10b
11 12
44
Distance
13
45
46
48 49
14 15
16a
Regenerator TEG Concentration vs. Flow Distance for Two TEG Inlet Concentrations and Two Heating Water Temperatures
Regenerator Operating Lines on Psychrometric Chart
->1
16b
17
53
18
71
19
^3
20
21
74
83
TABLE
1
75
Abbreviations
LDD
TEG
a^
a^
c,C
C
q
D
r
defined by Eq.
(C.l)
2
(C.2)
h'
(A. 15)
and
by Eq. h
(C.13)
(C.ll)
H Hp k
1
Enthalpy, BTU/lb
(f t) (F)
defined by Eq.
p *
(A. 14)
Total pressure, mm Hg
P Q
pressure
(ft
2
)
Chapter II:
Appendix
s
B:
S
t
Interfacial surface, ft
/f
T T T
Chapter II
temperature
(F)
10
lb TEG)
y*
Mole fraction concentration in the gas in equilibrium with the bulk liquid, moles water vapor/
(moles water vapor + moles dry air)
air)
Y
n.
u
p
Chapter II:
Dlmensionless Groups
Pr
Sc
Subscripts
A AL
B
C
Substance
C,
TEG
D
f
Cooling water
Gas
Interface
1,L
o
Liquid
At the reference temperature
R R
Diffusion resistance
Interfacial resistance to mass transfer
Reaction resistance
Heat of dilution flow source
Latent heat flow source
S^, fd
S t
f
Temperature Transformer
Parallel junction, flows sum to zero
Power bond
>
Signal bond
I.
INTRODUCTION
vapor content of a given volume of air by a liquid sorbent which has the
property of extracting and holding water vapor brought into contact with
it.
The terms sorbent and desiccant refer to materials with a large caThe amount of
than the partial pressure of water vapor in the air in contact with it.
Applications
Dehumidif ication, whether by liquid desiccants or by other means,
has important commercial applications.
and other surplus equipment which would otherwise deteriorate, and pre-
Both hospitals and the food processing industry use LDD not only
for temperature and humidity control but also for the bactericidal prop-
prevents wider application of LDD for the general purpose of space de-
14
per square foot of contactor in typical LDD systems which remove about
500 pounds of water per hour with dehumidification and regeneration con-
Potential Savings
If the potential to regenerate an LDD cycle at low temperatures is
(Refer
CHILLED WATER
ENERGY
1
COOLING
COIL
REHEAT
COIL
T
Figure
1.
15
Additional energy is used as this very cool, dry air is then reheated
to the desired space temperature.
from the previously low cost of energy and the simple control system required.
trolled by the chilled water temperature through the condensation of excess moisture above the dew point temperature.
The other dependent vari-
COOLING
COIL
BYPASS AIR
Figure
2.
Both of the two independent variables, chilled water temperature and bypass
air flow rate, simultaneously modify both of the dependent variables,
Re-
CONCENTRATED
LIQUID DESICCANT
COOLING WATER
AIR-LIQUID
* CONTACTOR
DILUTE
LIQUID DESICCANT
Figure
3.
The dehumidif ication contactor of the LDD system, a three fluid heat ex-
changer in which mass transfer between two of the fluids occurs, can
supply cool, dry air without further heating or cooling. heat energy can also be saved.
In the LDD contactor the two dependent variables, air temperature
A tradeoff for
2.
While the
absorption cycle is closed and the desiccant cycle is open, both systems
have coefficients of performance on the order of 0.6 [11].
The absorp-
17
Of these
two systems the absorption system has been the subject of considerable
analysis and simulations [9]; however, there is no well-established technique for space cooling or dehumidification with low temperature regeneration.
Purpose
In view of the above, a model for analysis of the liquid desiccant
3 is
Empirical equipment selection of the contactors is standard practice and can result in overspecification to ensure proper operation.
Manufacturers' application recommendations specify equipment which operates with the exit conditions of air and liquid temperatures, humidity
ratio, and desiccant concentration at equilibrium.
oped is based on a complete set of energy balances, material balances, rate equations, and equilibrium relationships.
lation of the heat and mass transfer in the contactor, the rate at which
the temperatures, humidity ratio, and desiccant concentration approach
With a speci-
fic design the contactor flow length and associated cost can be compared
18
length increments.
19
II
PSYCHROMETRY
humidity ratio, wet bulb temperature, saturation temperature, and relative humidity for the air-water vapor mixture.
Dry bulb temperature represents the air and liquid contact temperature and is the abscissa.
Wet bulb temperature lines run upward and to the left to the satu-
ration curve and very nearly represent the path followed by adiabatic
(spray) cooling.
aiv
aiv
21
easily measured and has significance to people; and (2) the humidity
ratio directly represents the water content of the air and is based on
one pound of dry air which is a constant in any psychrometric process.
ration curve where the process follows the curve to a lower humidity
ratio.
conditioning.
A downward vertical line on the chart represents an isothermal dehu-
by the LDD system with cooling to remove only the latent heat of condensation.
Liquid Desiccants
A liquid desiccant removes water vapor from the air at a rate direc-
22
sure of water vapor in the air is reduced and the liquid desiccant is
Humectant Values
ture at equilibrium.
These equilib-
rium humectant values give an indication of the TEG concentration necessary to dehumidify to a specified outlet condition with a constant TEG
concentration.
The solid lines which are the TEG equilibrium humectant values rep-
A third source [12], presented data for only three concentrations, 40%,
23 60%, and 80% and these were consistent with the first two sources within
5%.
The
regeneration can take place, the ratio is about 0.2% /F which indicates
that TEG regeneration should
ation temperatures.
Vapor Pressure Prediction
tration were developed with the aid of a curve fitting program and a
programmable calculator:
From Dow Chemical data,
21.36(98-P_)
p* [mm Hg] = exp
98-P T
2
460 U T 1 + *
*-"'"
625 + (98-P_)
495 ^ yD
(
-
&
0.6024 13 5 13.5,
'
(2.1)
0.28294
-9259 T + 460
(i -
A)
"
167
(2.2)
0.26921
75,
where v
L
X =
dtaP -ffi-i
RT
If X is fairly constant over the temperature range
(2.4)
In P = -
+ constant
(2.5)
25
will
be linear
three-constant
(a, b,
and c) equation.
III.
Operating Cycle
One
(LDD)
is shown
in Figure 5.
air from the atmosphere and contacts the air with the liquid desiccant
in the dehumidif ier contactor.
desiccant over a large area occurs through the formation of a thin film
of desiccant as it is sprayed over the extended surface contactor.
The
heat of condensation and the heat of dilution flow through the liquid to
the cooling water which can be sea water, well water, or water from a
cooling tower.
pendent on the sensible and latent heat removed from the air by the
liquid desiccant and weakly dependent on the desiccant circulation rate
The re-
mainder of the entrained liquid is eliminated as the cool, dry air flows
upward to the controlled space.
The dry bulb temperature of this cool, dry air is weakly dependent
on the water removed from the air but is strongly dependent on the temp-
S2
0=!
88
28
dry air which would normally be exhausted from the dehumidified space,
but can also be achieved with outside air. The heat of vaporization
exhaust.
Figure
also shows the four pumps necessary for the liquid desic-
cant movement
two
The liquid-to-liquid
cooler than the heating water, improves the system thermal efficiency.
An air-to-air heat exchanger between the hot wet exhaust and the cooler
inlet air of the regenerator will also increase the system thermal efficiency.
lation rates the sump operates as a counter flow heat exchanger with an
tO
!a8
5=:
8
S.S^
rS rOi!S 0"
I---Q.
/\ ^ _ z" I
Ui -J
|
* z S o
u..
CC
===:
<
CD
rO,:l
/
o
z
Ills
88
Air-Desiccant Contactor
The contactor is the part of the system in which the air is brought
The contactor should have high heat and mass transfer coefficiThe contactor
should also be light, compact, inexpensive and retain its heat and mass
Although the contactor may consist of a simple spray with the resulting air-desiccant interface being the surface of droplets, entrap-
and
8,
cant and has a better mass transfer capacity per volume than a simple
spray [33].
1
:
CONTACTOR LENGTH
Figure
7.
T t = 2.00 in sh
sv
1,73 in
Width = 48 in
Length = 127 in
'
ii
J**
r*i
L to
h.
%
^g
UNIT AREA
^^
*
5in
I
P = 5 fins per inch
t
=0.75
= 0.010 in
Figure
8.
32
flow configuration with an even number of tube passes, while the air and
liquid desiccant flow over the extended surface.
Thus, the dehumidifi-
cation contact surface and cooling coil are conveniently packaged in one
unit.
(1)
may differ because of different air flow and liquid desiccant recirculation rates.
Therefore, the computer model presented later simulates
the heat and mass transfer of both the dehumidifier and regenerator con-
tactors.
The air flow can be either parallel with or counter to the liquid
Due
tor, the exit humidity ratio is not as low as can be achieved with the
ration does not inhibit spraying the liquid on the contactor and allows
some separation of the liquid and air by a reversal of flow direction.
The parallel flow configuration is best suited for the processing of
large volumes of air, while the counter flow configuration can deliver
the very dry air needed in manufacturing operations such as the handling
of hygroscopic materials.
33
desiccant
4.
fication contactor.
8.
by spray cooling.
34
4.
condensation [10].
IV.
METHOD OF ANALYSIS
Mathematical Model
The analysis of the contactor is based on the development of a
The substance
three heat transfer state variables are the gas, liquid, and cooling
9.
M
J:
TEG SOLUTION
ALUMINUM
FIN
*
f
'//////////////////////////A
Figure 9.
36
0.007 to 0.010 in
0.010 in
0.035 in
Tube diameter
0.750 in O.D.
9.
The two mass transfer state variables are the masses of the gas,
(water
Thus, the
G, and L.
All
the other variables are dependent variables and can be calculated from
Appendix A presents a derivation using the traditional method for analyzing mass transfer operations based on material and energy balances in
Appendix B
The
dt dZ
R C
g g
(4.1)
V^D
(4.2)
(4.3)
Vm
dZ A M
(4.4)
(4.5)
A _A
+ =& + = R R
g
i
(4.6)
+^ R.R A
A
Rn + R
1 g
8-
Simulation
These five differential equations and the other supporting equations listed in Appendix B which calculate variables such as the mass
form a subroutine.
eleven inputs.
concentrations each take two inputs and a final input controls the in-
38
Each of
the five state variables is calculated four times per increment while the auxiliary variables are calculated only once per increment.
and the
auxiliary variables:
Y, humidity ratio; P
plots of P
V.
RESULTS OF SIMULATION
Dehumidifier Contactor
In assessing the performance of the dehumidifier contactor, the
The
psychrometric chart, Figure 10a, displays a parametric study of dehumidifier operating lines for three TEG inlet concentrations, 92%, 94% and
96% and for three cooling water temperatures, 60, 70 and 80F.
All
which represents conditions two rows (3.34 inches) from the inlet (top
of figure).
to 4F
to 4 grains)
cost.
can be the basis for optimizing cooling water operating costs and equip-
HIV
41
tiotis of
In Figure 10b
for the same inlet TEG concentrations, the lowest exit concentrations
For example, from Figure 10b an exit TEG solution concentration of 90%
On Figure
4 a
dry bulb
humectant value of 90% (the Union Carbide data base is used in the computer simulation), which is the exit TEG concentration of Figure 10b.
When psychrometric processes are graphically displayed in the literature the path lines are often straight.
The path lines for the liquid
desiccant dehumidif ication simulation are not straight and can be divided
into two regions (Refer to Figure 10a.)
mately the first two rows of a 16 row finned tube contactor or approxi-
L *
"J
I
1 I
2*
L<
UiS
(CO.
XH
S
1
-Jfju.u.u.
III
1
9clll
WATE EHUM
QO 55 O-i CO s8
11
;
|
j
1
/ /
/
1
1
/
'
ill
/
1
1
.
II '*'
mrf**^
i^t^^
100A10 3N31AH13IU1
43
The combin-
ation of a high rate of mass transfer at the inlet (see Figure 11) and
the associated heat of condensation partially explain the nearly iso-
thermal region.
in Figure 12 which shows the variation of the liquid, interface, and air
However, for
the LDD system these lines are not straight because of the temperature
lation is required.
The operating line of Figure 13 represents the local mole fraction
of water vapor in the air at the local mole fraction of water in the TEG
solution.
water vapor in air at the local mole fraction water in the TEG solution.
The simulations for Figure 10a were iterated to achieve identical
for each simulation is slightly less than the air outlet temperature.
Figure 12) so that the liquid temperature at the 8 row point of a 16 row
For
mi
ii
ii
xmd
3dSNva ssvw
d B9Q
'3niVd3dW31
46
ass
aiV Nl bOdVA
47
this reason the 8 and 12 row points may be accepted as exit conditions
exit marks obtained by iterating the simulation for equal inlet and exit
liquid temperatures nearly coincide with the 8 row marks of Figure 10a,
the 16 row contactor.
Figure 15 shows the results of an air flow rate which is 75% of the air flow rate of the Figure 14 simulations.
and slightly cooler, 1F, air is the result of a reduced air flow rate
For
example, the 16 row contactor with a 48" by 127" face area could be
This high-
er aspect ratio contactor will process twice as much air assuming con-
stant TEG recirculation rates and air flow rates per unit face area to
exit conditions within 2 to 4 F and within
2
An indicative result of an
ures
4
and 10a) is that with 70F cooling water and 92% inlet TEG con-
centration the inlet air at 92F and 111 grains exits at 72.5F and 56
grains or a dew point temperature of 51F.
Regenerator Contactor
In assessing the performance of the regenerator contactor the exit
uiv
.,
nr _,
UJ cc
o \<
j
cc UJ a.
uj
\V
X2 Tuj oc
1
"
O uj
FFF
80 70 60
=
< Z
oc
X X
Vk
Vl
3h
W/S
INCR
5<
\V
,
DEHUMIDIFIER.
ROW
COOLING
/
1
ROW
2
AT TE
MARKS
INDICA
<Y
49
aiv
ahq do QNnod
a 3d
/
/
1
TEMPERATURE.
1
NTS
X127"
RATE
.
48'
UJ cc
N O FFF
80 70 60
= =
RECIRCULATI
Mi
RAT
WATE
INCREM
FLOW
=
INLET
DEHUMIDIFIER,
ROW
COOLING
O o
AIR
\
V
2
AT
TEG
AT
CFM
TEG
^
ROW
INDICATE
GPM
16500
MARKS
45
94%
\ \ \ \
C3
\ \
50
ability of the regenerator contactor to concentrate 90% and 92% TEG so-
generation the exit concentration variations are less than the inlet
concentration variations.
variation is 1/2%.
a psychrometric chart.
Both Figures 16a and 16b are for the same simu-
lations.
The regenerator exit conditions are nearly at equilibrium as a
95% exit concentration of Figure 10a for 90% TEG inlet concentration and
120F heating water corresponds in Figure 10b to 118F and 0.021 H.R. or
147 grains.
On Figure
4 a
pressure of 24.6 mm
Y =
0.622(
) /OU - p
/Jj.4
1>
heating water, and 95% to 96% TEG concentrations can be achieved with
120F heating water.
1
1
1
UJ 1r^
X
1
u. LL
< c z O
UJ
CO
o H
1 1 I
2*1
uj
11 11 11
1
1
\
1
II U e
u-
1*1
1
\ \
OS Si
l
UJ 1- u. -
2
_l
\
)
cr uj
* * \
ool
\ \
\ \ \
u
o u c O
\:\
i
i i
i
CO
^s
52
HIV
53
VI.
CONCLUSIONS
1.
sized contactors can provide 95% of the dehumidif ication and 90% of the
temperature is minimal.
4.
humectant value, and the sum of the air and liquid masses is constant,
the equilibrium point can be found.
54
REFERENCES
1.
ASRAE Equipment Handbook American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc., New York, 1975.
,
2.
ASRAE Handbook of Fundamentals American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc., New York, 1972.
,
3.
Auslander, D.M., Oster, G.F., Perelson, A. and Clifford, G., "On Systems with Coupled Chemical Reaction and Diffusion," Journal of Dynamic Systems, Measurement and Control, ASME pp. 239-248, September 1972.
Baumeister, T., Mark's Standard Handbook for Mechanical Engineers 7th Ed., McGraw Hill Book Co., New York, 1967.
Bird R. Stewart, W. and Lightfoot, E., Transport Phenomena Wiley and Sons, Inc., New York, 1960.
, , ,
,
4.
5.
John
6.
Carnahan, B. and Wilkes, J., Digital Computing and Numerical Methods John Wiley and Sons, Inc., New York, 1973.
Clark, W. Energy for Survival, The Alternative to Extinction Anchor Books, Garden City, New York, 1975.
,
,
7.
8.
Considine, D., Process Instruments and Controls Handbook McGraw Hill Book Co., New York, 1974.
Daniels, F. York, 1964.
,
2nd Ed.,
9.
10.
11.
Duffie, J. and Beakman, W. Solar Energy Thermal Processes Wiley and Sons, Inc., New York, 1974.
John
12.
Gallant, R. Physical Properties of the Hydrocarbons Publishing Co., Houston, Texas, 1968.
,
Vol. 1, Gulf
13.
Karnapp, D. and Rosenberg, R., Analysis and Simulation of Multiport Systems The Bond Graph Approach to Phyical System Dynamics The M.I.T. Press, Cambridge, Mass., 1968.
,
,
14.
Karnopp, D., Rosenberg, R., System Dynamics John Wiley & Sons, Inc., New York, 1975.
A Unified Approach
15.
Kays, W. and London, A., Compact Heat Exchangers Hill Book Co., New York, 1964.
16.
17.
Kern, D., Process Heat Transfer , McGraw Hill Book Co., New York, 1950.
18.
19.
Kothandaraman, C, and Subraraanyan, S,, Heat and Mass Transfer Data Book 2nd Ed., John Wiley & Sons, Inc., New York, 1975.
,
20.
Lapedes, D. McGraw-Hill Dictionary of Scientific and Technical Terms, McGraw Hill Book Co., New York, 1976.
,
21.
Lapades, D., McGraw Hill Encyclopedia of Energy Co., New York, 1976.
in Solar Energy Research ed. University of Wisconsin Press, 1955. Lof, G.,
,
22.
F.
23.
McCabe, W. and Smith, J., Unit Operations of Chemical Engineering 2nd Ed., McGraw Hill Book Co., New York, 1967.
24.
Oster, G. and Auslander, D; "Topological Representations of ThermoSome Elemental Subunits for Irreversible dynamic Systems-II. Thermodynamics,* Journal of the Franklin Institute Vol. 292, No. 2, pp. 77-92.
1
25.
Paynter, H., Analysis and Design of Engineering Systems Press, Cambridge, Mass., 1961.
Perry, R. and Chilton, C, Chemical Engineers Handbook McGraw Hill Book Co., New York, 1973.
,
The M.I.T.
26.
5th Ed.,
27.
Peters, M. and Timmerhaus, K., Plant Design and Economics for Chemical Engineers 2nd Ed., McGraw Hill Book Co., New York, 1968
,
28.
29.
Rohsenow, W. and Choi, H., Heat, Mass and Momentum Transfer 1961. Prentice-Hall Inc., Englewood Cliffs, N. J.
,
30.
Rohsenow, W. and Hartnett, J., Handbook of Heat Transfer Hill Book Co., New York, 1973.
McGraw
31.
Schultz, D. and Melsa, J., State Functions and Linear Control Systems, McGraw Hill Book Co., New York, 1967.
32.
Sherwood, T., Pigford, R. and Wilke, Book Co., New York, 1975.
C,
Mass Transfer
McGraw Hill
33.
Staniar, W. , Plant Engineering Handbook , 2nd Ed., McGraw Hill Book Co., New York, 1959.
34.
Thoma, J., "Bond Graphs for Thermal Energy Transport and EntropyFlow," Journal of the Franklin Institute , Vol. 292, No. 2, pp. 109120, August, 1971.
Thoma, J., Introduction to Bond Graphs and Their Applications mon Press, New York, 1975.
, ,
35.
Parga-
36.
Treybal, R. Mass Transfer Operations, 2nd Ed., McGraw Hill Book Co., New York, 1968.
37.
Triethylene Glycol-Water various graphs, Union Carbide Corp., Research and Development Dept., Tarrytown, N.Y., No. A-11A3, 1958-59.
,
APPENDIX A
CONTROL VOLUME DERIVATION OF RATE RELATIONSHIPS
The equations derived in this appendix are concerned with the inter-
phase transfer of mass (water vapor) and energy which occurs during dehumidif ication of the humid air by the concentrated liquid desiccant.
Fur-
adiabatic operation.
Figure 17 represents the direct contact of the gas (dry air and
water vapor) and liquid (TEG and water) flowing side by side in parallel
flow and separated by the gas-liquid interface.
The changes in tempera-
sequence is presented.
*L
GS *G Y
INTERFACE
dS
X
L
HL
y
y
III
,,
""1
i
i
<
1 I 1 1
r
ii
I
1 1
V
NA
1 1 1
Qd
j
i 1
i
dI
<*sL
1 1
n
{
1
1
j i
1 1
L_
i
LIQUID
_J
GAS
I...
_J
GS
x-
:&
+dL
+dx
1
tG
Y
H
H L +dH L
L
x
G
V
i
Figure 17.
tube contactor the heat transfer area per unit volume, a^, is known
from calculations.
tion complete wetting of the heat transfer area may be assumed so that
the mass transfer area per unit volume, a^, is equal to the heat transfer area:
and, dS =
a^Z
(A. 2)
conducted in
and G
ficial mass flow rate of the non-diffusing pure TEG and dry air respectively.
and G
= G(l-y) =
YTT
(A * 3)
Y = zr* 1 -
(A. 4)
60
y -
+ Y
(a. 5)
diffusing TEG.
L
s
L< Cl-x)
(A. 6)
X
1 -
(A. 7)
X
1
+ X
(A. 8)
In
Out
(A. 9)
(A. 10)
61
The mass transfer rate in lb vapor/(hr) (sq ft) of dehumidif ier cross
section) is [36]
(A.13)
(A. 14)
efficient for large mass transfer rates and is defined by Eq. (C.l).
Equation
(A. 14)
BTU/(hr)
or
t
)a dZ
i
(A. 16)
where C
BTU/(lb mass)
h
=
(C.2).
accounting for the sensible heat carried by the diffusing water vapor.
a dZ = sL H
VH
(t i
" C )dZ
(A 17)
'
now be developed.
Envelope
In
Energy Balance
=
Out
G H
S G
" G S (H G + dH G ) +
"sgV 2
+ N a dZ(C ( A M A
)+X
(A 18 >
'
where the last term is the enthalpy of the transferred vapor relative
to a reference state at
t
where
at t
Since
N^dZ
= -d(Gy) = -d
[j^] m
= "GgdY
(A. 19)
substitution yields
= G dH
S
VH
(C
G- l
)dZ " G (C ( S A
)+X )dY o
(A - 20)
The enthalpy of the air-water vapor mixture per pound of dry air is
(A. 21)
where C
BTU/(lb)(F)
Define
C
S
=C B+
YC
(A. 22)
(A. 23)
Differentiating equation
(A. 21)
dH^
AG
)dY
(A. 24)
(A. 25)
energy balance
- G C dt
S S
G "
Vh
dZ
(A. 26)
Out
(A. 27)
=
C
^C^L^f^ 2
= heat removed by cooling coil, BTU/hr
(A. 28)
where
sq ft/cu ft
t
Substituting equations
(A. 17)
%
Here
Vil/W" +
Q
LH
(t
i- L
)dZ = L dH
S
+ Q C
(A " 29 >
= N
aV ZH D
= -G
sVY
,
(A - 30 >
BTU/hr
where H
Substituting equations
(A. 28)
"VVCai/VV^
+ h a
L H
(t
i- L
)dZ =
VV^VVV**
(A 31)
'
WV
+ XC
AL
(A - 32)
heat capacity
BTU/(lb)(F)
= heat capacity of liquid water at constant pressure
T
C.
BTU/(lb)(F) Define
C C + XC SL " C AL
= the humid heat of the TEG-water solution, (A - 33)
BTU/(lb TEG)(F)
Differentiating equation
(A. 32)
(A. 34)
r
-
dH = C dt = C (t C )dX AL L- o L SL L
<
A ' 35 >
SL
dt
L-^ L
S
AL
(t
L- o
)dY
(A. 36)
L C
S
SL
dt
L=
(A - 37 >
Out
L H
S
H + Q " L (H + dH + G (H + D S L L> S G S G
"V
+ Q C
(A.38)
Rearranging
(A. 39)
(A. 37)
Ua (t -t )dZ
c
(A. 40)
Out
'iWM''
2 "
VMdZ(CAL r
(t
))
SlV Z
(A " 41)
Rearranging,
A M
(C (t
+ t C (t t G- o>- AL i- o )
t.
'
WW-W'i"
(A - 42 >
Solving for
t,
"aWW^AlW+Wl^gV
N
AVAL
+ a
(A. A3)
Parameter Classification
1.
2.
Constants
U,
3.
VVVVVV
y *' y m
By starting at the top of the dehumidif ier with the known quantities
and solving the equations at each incremental step, dZ, the following
Y, H G>
G, y, Cg.
VVV VV
Solution Sequence
'
and will be obtained after each step and at the exit of the dehumidif ier
V = r^1-y
(A. 44)
z~1-x
(A. 45)
humid heat,
C
s
= C
+ YC
(A.46)
+ XC C SL " C AL
(A - 47)
gas enthalpy,
H p = C_(t -t ) + YA^ b o G G o
(A. 48)
liquid enthalpy,
"l
+ C
SL (
<A - 49)
(A. 43);
(2.2);
2-
(A. 50)
ym
0.622 + 0.378 y
(A " 52)
AA _ " l-exp(-N C /h A A
(A. 53)
The
^G
dZ
-Vh
G C
S S
W
f
(A - M)
dZ
bL L
))
Ua (t -t
c
(A. 55)
Ua(t-t.) v
C
dZ
A
f
(A. 56)
AL
(A. 57)
dY
NA
(A. 58)
dy_
dY
(A. 59)
dZ
dx dZ
dX
(.60)
d(Gy) dZ d(Lx) -
dZ
(A. 61)
^
dy_
(A. 62)
dG = 1 dZ y
dL _ 1
djGyl_
V
dZ
^ dZ ;
m _
TM
(A.63)
,d(Lx)
(
dz " x
~dT-
dx. = - L dZ>
^^
(a - 64)
sical system;
a ra-
Equations
(A. 54)
The
results of Appendix B indicate that differential equationa (A. 54), (A. 55),
(A. 56),
(A.63),
(A. 64)
APPENDIX B
BOND GRAPH CONTACTOR MODEL
Introduction
The bond graph method developed by Professor H.M. Paynter of MIT for systematic derivation of differential equations for the transport of
ation of the sign of positive power flow and distinction between dependent and independent variables.
its own calculation methods, bond graphing is compatible with all dis-
[25],
[34],
[35].
A bond graph representation of a control volume around the gasliquid interface is shown in Figure 18.
Dynamic simulation in
GAS,
THERMAL
LIQUID,
THERMAL
CL
*
-0
\
\
A
\
GAS, MASS
TRANSFER
-R d
0-+-
-R d
-0
Rr
1/
LIQUID,
MASS TRANSFER
d-
Rd-
Figure 18.
Bond Graph Representation of Coupled Thermal and Mass Transfer Operations in Liquid Desiccant Dehumidif ication
72
of the
thermal, C
t
and mass, C
There
is also of twc
sistance, R
The dotted line is a reaction coupling from the mass transfer portion of the bond graph to the heat transfer portion of the bond graph
fic simplified model with the addition of a cooling medium with heat
capacity C
and temperature
The
and
differences.
73
O jj-.
X r->-
At c
-
interface -
cooling water
interfacial resistance
fct(t.)
liquid mass
Figure 20.
bonds represent the power flow associated with heat or mass transfer.
Ones represent series junctions at which the sum of the efforts, either
Figure 19 is a
pseudo bond graph because the concentrations are used as the mass transfer efforts rather than chemical potential and because heat flux is used
as the thermal flow rather than entropy.
selected for the physical significance of the effort and flow variables. [14]
Two
mass flux controlled heat sources, S. 1 and S_, represent the latent heat
rd
Heat flux in BTU/(hr)(sq ft) and mass flux in lb water/ (hr) (sq ft)
are the flow variables used in Figure 19.
the thermal bond graph.
Table
Variable
Effort
Units
F
Flow
Resistance
BTU
Capacitance
BTU (hr)(ft)(F)
Table
1.
through
The com-
(1)
76
x=
L
s =
(B.l)
(B.2)
= fct<t
g>V NA
(2.2),
p* = fct(t.,P
Henry's Law for the mole fraction concentration in the gas in equilibrium
y*=^
Pi-
(B.3)
(B.5)
0.622 + 0.378y
is derived in Appendix C)
1
- y*
)
= F
ln(
1 - ym
(B.6)
heat of dilution taken as 10% of the heat of condensation and sensible heat associated with the transfered mass,
Q D = N A (100
(t.
- t ))
(B.7)
xm =
(B.8)
8.334 - 7.334 x
j^j
(B.9)
APPENDIX C
FLUID PROPERTIES AND TRANSFER PARAMETERS
This appendix presents the essential but less than obvious relationships.
Appendix
E.
Essential to the model is a numerical value for the mass transfer coefficient, F
.
0.667
Fp-^-S-) G C Sc
fi
(CD
(lb water) /(hr) (sq ft)
where
BTU/(lb mass)
Pr = Prandtl number
Sc = Schmidt number
h
= heat transfer coefficient between the gas and
f t)
(F)
to/ 1, n k 0.134
r
n D r G r max
y B
- 681
,n x (Pr)
- 333
,s N (j)
- 2
,s.
0.113
(C.2)
(-)
where
D
k
= root
r
diameter of tube, ft
= thermal conductivity of air, BTU/(hr) (ft) (F) = mass flow rate at minimum cross section,
max
lb/(hr)(sq ft)
s =
1 = fin
between tubes, in
t
= fin thickness, in
=
Eq.
[15]
lar tube data but which geometry differs from the modeled contactor.
(C.3)
JL_
v
(c.4)
(C5)
(C.6)
80
[2]
2
'
+ 460)
Soi
r- +
g
(c
7)
P D g
where
6 =
film thickness, ft
lb/(hr)(.ft)
1-L
r =
The mass flow rate per unit width r can be calculated from the liquid
and p
= 4.46 E-7(P
f lD
(1.487 - 0.727- In P
-
0:5
(C.9)
= 54.88 + 3.73 In P
0.0262
(G.10)
was approximated as
conduction dominated between the air-liquid interface and the liquid mid-point by
81
-y
(Cll)
= 0.789 - 0.14 In P
- 131E-6
(C.12)
" p 1,33c
j
'
k4-
m
(C13)
for
4 r
<
2100
= C
SL
defined ln
Ecl'
A 33 >
-
+ XC AT AL
[26]
(C.14)
(C.13),
for h
may not be used since the heat transfer coefficient can not be less
than that of pure conduction.
is correct.
produces slightly
82
overall heat transfer coefficient from the liquid to the cooling water
6 to 7.
The comparison in Figure 21 shows that the simulation results are not
materially affected.
A curve fit was developed from tube side water heat transfer coefficient data [17]
D
- 2 6
(0.905 - 0.1863 In
(C * 15)
where
6
ft
solution film thickness so that the ratio of free flow area to face
area is
l-P(t + 26)(T T sh
-12D r
(cl6)
sh
sh
in
The overall heat transfer coefficient from the gas to the cooling
water is calculated by
1
U = _i_ + _J_ nh nh
a
,
(C.17)
aiv
AiiaiiAinH
"1
r-
e O
4-
en
C COO) 3 -H
O
H 13
4-1
o CUiw
co
4-i
U
4J
CO
-H
u
e
0)
OJ
v^
^> ^cv
^^^^
h X> T3
a>
pa
O
<U
e c O rt
iH
crj
o
M
<U
e o
H
U-l
CD
^^ ^s>^
D
1LU CC
^^w
>S> X\ \\
^^^w^jta ^^. r\
l
iw
K'H C
,C
PL,
)-l
XI
w
H rH
-H Cl
W
*4-i
B o
M
CO
0)
O o 3 u C u o <u
y-l
4-1
0)
e
CO
<
CC LU
^ A\
LU tCC
a w
|
<u
3
P-,
pa
< z
^kAs
1
EIMTS
V \k>
\\
\\
\\
1 1 1
RTEMI
"
X127
coS
<*tulWA
F F
80
R
LOW
I
DEHUMIDIFIER,
60
4ROWINCR
[J
=
COOLING
O DUU
E2
o
(-sf
\\ \\
\\
AT
TE
CO
<
V
-
>4
G>
1 1
84
k
6
(f t) (F)
The calculations were done with the fin efficiency applied to both
the fin area and the tube area.
Applying the fin efficiency to the total area instead of just the
fin area accounts for 97% of the heat transfer:
' 66 .66(.93)+.07
fc
- .97
(C.18)
Appendix E.
APPENDIX D
TRIETHYLENE GLYCOL PROPERTIES
Triethylene glycol is a colorless, combustible, hygroscopic watersoluble liquid used as a chemical intermediate, solvent, bactericide,
[28]:
- CH
- CH
- CH
- OH
CH
- CH
- OH
Molecular Weight
Boiling Point at
1
150.2
atm
545.9 F
<0.01 mm Hg
1.119 g/cc
19 F
-73 F
37.3 centipoises
45 dynes/cm
Viscosity at 77F
Surface Tension at 77 F
0.53 BTU/(lb)(F)
320 F
330 F
Conductivity at 77F
0.13 BTU/(hr)(ft)(F)
[33]
Noncorrosive
Odorless
Chemical stability; should not break down or vaporize in the range
of interest
3.
4.
5.
6. 7.
contamination is acceptable.
TEG is practically odorless. TEG is a superior choice considering both its hygroscopicity (item 1)
and its high boiling point.
4.
5. 6.
determined by the ASTM Cleveland Open Cup method for pure TEG are
320 F and 330 F respectively.
in storage or handling.
7.
APPENDIX E
*-
r-
o
v.
4J
iJ
>-.
PM
<f in vD
l^
00
>-,
^
*M
>H >H
>-,
>H
to
<3
^c
ro
i-j
M
BE
cr
t~3
VO
o
in in
c\i
m
t^
II
o
rvr>
o>
II
CM LO
II II
i-l
-3
ui3
t-
at:
II
in
r><
O fN O M r-3 O ^
rrr
II
aII 01 01 o. :* r.j
m Nro X
r~ in a>
jII
11
rsi
<T
II
=
II
>
(X,
II
II
II
oc A,
,-j
il
a;
monoQ
** u,
i-t
LQ
n.,
F-i rv,
Cj Pn u<
a. e>
ii ,-J
<^H
F-t
Ci.
O-
tr.
CO
HH
rr
-J
E-i
D33
f- En -
CO oo rs
Q * m x: T~ u. C ou co &. H < ai a CO c
LD ,n
cr.
II
II
p:
^o
E- E(X =)
t- CJ
t-1
to
rj CO
U
-i
C
fN
Eh <x IX CX
2:
c
IX
H
00 CU
t-A
E-<
IX UP a:
hICOH
3: on
oc
w
a:w
oo
hK CO * \ 01
a: Dt
Pn
or.
E5 Eh
m a
_3
u a. o oo 05 ^hl/l o O
..
O O y
3C (X
>-j
II
^ ^ ^ CN
II
II
II
a:
II
II
a w
f.0
E-1
II
II
Oi 00 tx ZD
;j s:
Eh
II
a: Eh
C.J
1U.
r~-
Eh
3: fV c (X 00 01 -X Eh tX -* Eh :=> "x Eh * 00 CO .-J O^ Eh Eh FH ^> CC Eh E* 00 + "v 01 E-i Eh oo a + 3 E^ CO <C ttr Eex sc O) IX u< + lN< * HH U. IX fX *Eh - 3- (X hh a: II CO II II II E> * to: cr II -3 II II a: r< E EII h-1 ac : TK || A. II CO Eh II ki ex O- se; ti -< Eh (X n F-h =3 n fX n 01 0C Eh 3t t-i rx Eh :X fn LX * E^ CJ5
I
Eh * CM jr rx as Eh ex Cl, ex *r CX 3. C: CXi -)
;*.
w
c
t-3
Eh
D
.
HDP, QH w WV
, EX H/ c.
5
u
ex cc
Hh
U C H s M S M (X3 U u H
X w D Eh Q X H h :*
Cii
OOl o
Q
ST.
\ \ a:
rx:
a-
p-
bZ
O
u:
ah a
IX _4
II
to<
<
i tx
M
t-
Cr
Ct'.
^>
i-
C CL * . cr
M
1
i
s^
CO
\
LP
CN'
i-5
(N cn
<-> <-
+
in oo
LO
u Q< w Uj a \ >^
e-i
O ^ Pu M \ CO
O w
v.
ce
t-A rsj
l-:
* *
r- CD
-*
-.
M
a
""^ tX.
t- E-
*
vJ
cn
CO cn
CO ^ V
~
CO
1
O
<~ C7\ UP
vo a: r- (i; s, CO r- 2r
^
OJ
o
*
*
CO
CO
o^ O
b-t
(
r~
w
E-.
t-J
*=
oM Q
*
*
e-t
E--
CnU.CN O CO +
a
t
\m
\>
<^
H o
* *
5J UC
1
\HX
a:
ro a;
V
rvO vO
c
vC cr
(X
P")
\ r- m CO uu ~ W + Ph * oo
r-
M
2,
r>
eo on
E-
<* -<
a. to w O
\
-
wo V C) *s ^D
cC'
CN r- \c r
U-
.-3
rs +
r1
a, co
(X
II
rVD OO CM
.3-
o* o*
-<
U*
m
. to
Z* +
CD
E-i
1
on LT no
a, as > CO CO
M
cc
f7>
C3 CO
H
*
*-*
Ct, >-,
|
L0
>- *
X. co >~ CO
CN a-
v^ T- CN
< M ^Q
+
CN
> Q
CJ
o
a
II
+
en
II
C9
o
II
a
ll
ain in
il
ii
II
X 'Dt < \ \ w t) to ct ct
O^x\
i
Cu Ui CO *
U' rP4 ii CO r*
f-H
CO ta
CO c C5 r-
\
*
>H CO
< V
CO to
Ocv,
0-i
+ cn S3
P-i
o
II
x
<c
H
ac
O
ur
II
e-
*
Eh
o CO \ W vO 01
cr
i
<-. "*>
r*
en
o o> MM
>-3
--r
II
c^^i;
E-i
**
3-
U> -3
>~ >H
> O
hh
.-5
fiJ
L.1
cc O-
E-<
>
U M
wx a
II
II
II
Cm
CO cc
>> >h
O
CO
V.
C5
II
+ CO
CJ
II
G Q
>
o
P3
II
CO
C
> X
U'<
to CO
^r *
>
II
CJ C7 CO Pn
'
<T
w
W O
as
<-*
*
t)
<^
r-
cr
CD CX (H P.
\ >H
CD
1
ac -;
i- r- t- * 00 w 00 >m 3-
+
E-i
Or-
k-3
r-
tx
Q CO Eh O O o ^
+
l-i
03
u
CJ5
<-
vO + U3 t- hJ IP
u
CJ
a.
w : o> ST. * T-
U O
.-J
*
r
1
E-*
a- U.
O W
EON\S cc ^
>OU4lB iHri -1 w
II
OhJ
V.
II
CJ _5 En
Eh >^ Eh * * (N Cm X. IX, CN ^ r"v -n ""* V> + *-* Oi * cr as >-i 00 J* u: r-3 * -J * Eh Eh + u, E-< Vlt-^H >H * i-i (^ * >H * m 25 os * %1 CJ fX + C Hi V. EC <N IX CO Ui .p * J- + f- * r- F- -w + * CN CN a- r r^C CN Eh r> E-< c/> ac vO C Eh + en II 3- =! Eh -3 LP CO a- as + i-JOiO II H II (N II II II "- ^ CO SR * E-h (X II CO as u, iX3 .-> Ln ii II || II n a.-J II in co Cm 3- Si CJ (X IX IX aj or, >-* -3 >" 1-J rr:
<-
rw * ^m\ 3Hf
>
u- * w ro
5
>1
as
c?>
VD u*
wO
O o
ww
HZ
00 r
-J ^.
^N
v^ LP ^ V \ >* o cm
0>
w o
hJI*
wo >X\
^ ^O
o x~
wO^
s
cr>
II
LX CX -* IX cci as C3 Oi Uj Eh =T
If)
\
>
CO v. -J
at: co : CJ
r-
m
+
r^
T-
N^
N.
C3
r
; j
* + \ H'vS
CO CO c CJ
V ID
Z2 U.
a^o c
re
r-
lp
V j
r3
w\ \
h;
II
OU
M wW< O ^
rx *A cx
rr>
* * c CO CJ IX IX rx Eh CJ CO rr Eh II IP h-l ii
\o
E
II II
<Ti
3
-
u
II
II
-*
C J
ac rII
E-h
EC rx
^5
U ^oOU
15 1 PC cx
rw w
>
^X
3.
* Eh
*
-a:
O
L
* O r
X
*a-
^
XJ
a:
*-
SC
Cj.
il
H^Xh H WX
X
CM PJ
* <
F--<
Cm
.o
BS
t>3
[Li3
O
r-j
XX ox x - to ce cni/iH a PJ x- CO 33 ^O x *o 33 Cm O M lpco nn\zr):HCDX^ O X Cm x to u, zx uNirimz V -} X 3e KVOd ^ Ou * o> * X * Cm rHE O nhnmu r Eh \DCi4XhlMOti] *t0 t- to X CO m O M - lP Cm > ^Eh v on it h c pJ h uj n X, Xo kt-a au < hu N Cm * * to *;x X C5 cr o r- >. o : a* o r* * C o> X CO x x a: cc on x * PI X it < to Cm x to CO CO XCOT-mm: ^a: cc v: a- m cc a co o X P PI CX r-a aX 00 3 a: r- CO lp vrH *LPO<cn N LP a: * * to C>->i-!^ O X VC Cm K *0 * o r P4 a: as O H I r- X rLP W Cm Cm X to r- H HCO v X * OS 33 X ^3\XIuHE< t- LP * SC H kt)cr OtN? r lp to * cj uP c x Ti pj - m o lp V Eh c H WMI * CO X X 25 H COEhUhO * * C/OoCStCm X V as E O C2 W 0053 fM * Q Huwxxinswa.j CO Eh an pi C r- r- M X H001DOP^3<i<HX ff U W X n =t * M -U * x r* CLXnlh'CO rr c * ini CJ Eh ru. U. Hi X u- r- f f, : KHX ff - \ ^v*XUCmv> x rn C 3 ^ n * t Q r3e * a t to I fu r m tu 3 ni u * X P4 Cm * X rPI x * * O X X H CP >cc *t-t-Cmkh Cm X tw Kr- X ^EhLP ^>i * vh A * LP CO \o X X r(T CCS * VO r. sLTxUiCMCcrvxxxc; X O -) xt-oP * 3) 35 Eh C * r- u, u: \ ^Picr>aNcox T- tO U M r- m t- K u < 10 H tn tJ JS * oaoh X aui ccxiri >* 0CH3 O Cm cr* m >h >- x m a; \ \ * ^ \ CO u x: cc ce o fN c < 3 \ H V f U(NrXK Eh hJ CO o m < ,K CO * c\cri X W M > ce w x o MCKMMX ^XC3 Eh Q X o CMCiTtOUEHrpLPacLPpffiS w * r- sr Cm O as a: os >20hlP PIX.CmCm'VQ .X =t I In 2. C x ^r x x o pi rn CHhW * M LP CO X X LP Cm vDccoc3-,a:LP *z * ^oca x h Cm x ^a 2 O * r- 3 Q rf - OS XX Cl < ro ^ XCJt- vcozcrcrcoSK o a 5I00D 33 PJ X X r- ( LP fh 5 .xxot-^-cmco rUlllKOaoorH to a \ a u X * V 33 tn itnw - \ * sauce h' Ci Hxnrh * a. V. , CT X as * t- Cm cc <r + Mx<<o<r-xa:rnoxto ^ W \ \ xX O O Cm X i~ *33 X M Eh lOCMJr- .SS^ P133 Cm \ >v S r M I > X H r- LP X (NO X >h ^H E-LPLPr-t0 to CC x n a- a w i LO x lp a: PI Cm o w O \ Cm tO tO Cm Cm X CO tX * M LPO^ Eh OX>*00 P> Eh (N * * m m je pi to vo * m > as w x ^ C .3 U iJr \ a- X ro ^XT-arMcrh-Ja-xx co oC vD m z. q m u xn-. LP>xo<-voiPr--EH m f~ 3E Cm I LP as x 00 as : * X H Cm 00 33 MUX Cm m t- X 0L)t-LOr-t-'\as *~t-CmX LP X LP M M * * SE *FH * ^3 * *Cm *EHcn>HX * * * rn O O X M r- \ r- a: < X 33 O PJ r- LP *C OX *X(_).-?COC*PJOXTm X X \ Cm U3 X O x r~ x a x in in up 5 a- -J 3: Cm - ^-i f- o X- LO Eh O' VO tMP N C ai 3 4-J W ^lPlp-x * Cu U. *Cft LP > Cm X <C w o - tO PI * as \ * c n u * *o a: aM>^ O X rH CC (J H d] (Nllt- r* co n fn D N d- O m <OXX "V FH X t3 PI ^ ^ PJ m lp ^Cmx^-xu, to crr^r*C X n *g c co u rtO ^m HKU< LP (Nt^< pi *:H- *Psl *cjn * r- *CmLP m ip * hi K K I Cm u CO Cm ^ a J xt->h x X LP - Cm OTtfUO fH\O\t)daX0[) a < r< ro o m rtl <n ac x ccCm iu x H e- U/ t- p, r~ U( v: ^ cr CmvCCm- H m (N x tn in\H ^ ~ Pi m t- cm m 3" tc r- t- pi m cr r~ OO VO P- CD * ~
>
X X t~
OMM * to ce
in a: *
pj >: * cr >.
MX ^ < O O3
h-3
M
CtJ
SD LP * Cm SK
ZC (\ (N
R(\
h
X O Cm Fh s CO Cm a CK X rO n x c- a: x x lp ^av^cr^vc^v.T-, ^CmCm'-.XPJCO MS D ^ OX *x3> ZX^E-ih Xr-XLP Crt if 3 tT Cv m kmrxuhrrli ^Xr- CTi CD Q *-ODPg xin*cn EH>H r*CT D h X X
r-*
Olfl
*VC0Cm
cr,
xn
fT
* ip Cm Cm
T- a.i r.t
^Ti
tr.
!f:
F--
(-H
E-<
cr>
*-
C_)
CL.
".
(-'
Cij
.'
e-t
at:
c/j
cj\
or,
tf)
CiJ
E-t
a:'
h-i
txJ
i=C
(Ti
Ps'
ex.
a-.
t.
ex:
>-A
E-i
3f:
ffl
or: vr-
cr.
[i,
st>
<r>
cf>
V3
**>
r*>
>
-5
-4
1
i
^-s
ST.
Cxi
125
--C
f-i
PvJ
f-t
g-.
E-i
a:.
sr.
l"i
>
*:
*?.
t-H
SEJ
.e-<
-)
(j!
u")
^>
l/">
O".
'
fH to ir to to CO
vC
to
V
V.
*
X m
CN
\ \ X Nv \ \ CT \ r- CN \ o vn to
CJ-
<r-
>
to
toto
0r
CN
xccanor\^ a - *- to r- tt.
XX
X
CD
t) to a:
Eh LO
\ \
O >
to
UM
Eh
DC to
to
\ V.
H 35 o
vr> on CD vO to to v UT U3 t- to * * \C to to to * * rin in
s *. r- cn
*,
to T4 Eh
CO
T-
0..
^ c
O
an
\c r- vo t35 VO CN CN to to CN *
Xx
XX
j-
* to * to * to t9 Eh * to to to * to CO ^rt to t5 to rx to *
3 O
d MO 3
<C x: to * to CO
35
M> M
U O to ^ O * CO U to
U
Eh SK * De
r>-H
o o
+
LP
U3 r-
t-~
UOH
* Eh to SC _)
* to to * to t5 rr to to : CJ
to
to
X
VO CM
re to rr
Cl
U X
V
m
rrs
rVO
3
CN
* to * *
+ * ro
3 to X
a.
rj cj 33
\)
C-:
rr to a\ r- 3.
p-
u. a-
mo\
ro CO
>H X C to a CT x U\
to
\ V
CTi
Eh
o
to
rr:
C J
&
* to
to
to to to
X r^
r-
frt
>i
CO
X 3-
*
7.
in
C a: o Hr
KKT
a
rr.
OD ^MH
OC V:
,_j
r-
Hrci V. v
. c re to S3 p_ KK fc(J FH * to to * to to
to * to 35
> CJ to to > to
^\ a. ^* to ^
*
<^
r>-.
|
o 3 c o
in
* 3) CO Eh to
C-0
tor*
x X O O>H M D 3 ^ X * * X O to
l/}
V
to
T~
o
=t
V
?H
CT CT
w \
o
1
CN
Eh CO
o
+
\
1-^
t- rs r^
w
1
a.
x X V\ to O CN m H 3en
rr>
x
3
or,
CN
to
vT
* EC
OCO
co : SE to 3;
CO to
CN
LT:
m S3 Xto X H X to xoo
rsi
to 3:
>-
3X
*
to
to to in
r-<
< CN
*rcn to
3m
sD r-
O X
* to Eh
>-<
E-.
iTl
O O
to to to
>H
to
O
VD
on
>H
x o
to to * S3 to *
\
H o
1
\^
in *
3"
+
--3
OD
vn
o o
rrn
to
r-
X
+
3-
+
CN CN
\3
V
CN
to
HahHH
to CO CO to
to
to * 5K
^O
<r
3 3 3 3 * O
+
r-
an to 3: Eh : ct. ss =C to to to >h Eh CD k4 cr; to to to >h to . to Eh to hJ rr t-t to - vo r~ cs : cr. (N CN CN t- to 3: CN * * * * 3C * 3> r^ *~ cr cr> as cj\ ct> in vt> r as cn ro
X v
n
3"
m
CM
a-.
I
o-
\ to o
*
II
CO
CN >H
to
U3
11-
3
*
to
II
o
n
cr.
-^
X
li
r- >H CO
+
>"3
m
+
to -
Q X
II
CT cn rr
m
ii
si:
X
to
m
u>
o
>H
3 o
II
CO CO
II
<~*
to in
>-H >->
to to
UU
^
><
r-
C* Ex oo or
CN
w
^D
CxJ
& U
JC
o
CT\
Oo
Fx cr
^
3/
r> kJ IT
C*
O
to
<--
V
ex
o aO OO
CT.
u>
"~>
o
:r
ll
rn nn
r* LT
i
00
3C r^
H
1
\
3
-)
ip
o
r-
\
CM rCjq
01 Cm rx Ex Or. 01
O
*
w H
>' * c& 00
rvM
>x
u->
O, U! EX
^-n
4-
oo
^ cr
K_
a.
'-j
m
p..
x-
in
w \
CO <T
II
+ +
o
vD
t-1
w
^
r/>
t- >x fx
^wo
CN
.
>-
3 U U u
V,
o
in
>H
C.5
on
1
x;
a ''
w m
Ji;
*-*
EH CO CO 01
X
* en
T- CN Ex Ex W o o
o* :* r~ Cu
li
>x
CP r
\
n
o
VD
JC
>M CQ .<
1
Ex tn
^ff r
I I
VO
\ r- ^n w^
o
\ ^ sr
3: 03
^v
CN >H
1
o o m
>-<
ii
(T>
I
It
-T
^
II
CM SJ cr
^
II
+ 3 n +
>-}
o
\C \C
0? 00 Cj c >-.
II
+ +
cr>
*-->
rr
>-j
CN
II
m
ac
a:
+
oa
ii
SW V i
V HI
II
: rrj ** >x
^w o
II
"""
IT CT
*-
^ TID ~ w
*
CX>
-H _H
\C
M
II
^
II
o
r-~
u.
>x >w
II
>-<
r-~
00 >H
eft
O^^
<-<
,-N E-H
o
oo
II
II
Ex
cd (rt re Cm f~ x. P. P< Cj c. :*
u. u.
MM
n
p..
>H
>H >< >>-"
>"!
CN w _J >x Z3
en -
Cm
O S
II
T- r- CN
j-
>* Pk r^ tn Cm
l-H :e.
J
LI
J J
3e =D
LO =3 en s> h3
>
vC w an
=r
ex:
<s.
tn E" U,
>
Eh
*
itj
O
*
w
3C
x, OS
r-
o as M
OK
ro OH
f-t
e!3
*
* U ^a 01 O
-v
w
Eh a. *
-s
V>
in as EH << * cr fn cc > Cu
=C
C*-.
* K^
dr.
f-l
u UU w
hc
<.
E-*
l-l
CU * * *C 3c <<
^a
C;
*.
os
a,
H
a.
in a^ ua^^o l*Wv
u. a. * r/)
H UU *
f*.
.
>
rr>
o
o>
as
.-3
%5r
os eh
.o
HMtnh
m
O
_^ .rO
eh
a. Cs *
* Qj t-H" Cm s: t/o CD Eh [JM Cs * t/i re LO f-l CO ^-s * Oi Y- 't: i-J ffi ^d *A Bri Vi
F-H
* K:
-J
tl.
ft4
<c
a, U4 U.
Zi-
O
cr, a*,
rrr>
ww
-t
to in
W fnHH M O
c;>
O U3
cc cc :* a:
w O w _ w W D ran ar rj 05 W bi ^ W >h M Eh Eh SI Eh E H Eh M O M M OS M Eh a. as as os rr as D O as * as a Eh ra
li"i
iT,
CTi
s--
,-s
C*-i
to -
(_(
>
OS CD
Ct, -,
II
Eh
f.O
a. .*
(J 0.
SOOIO
o
o O
in
t- r VO
Mom
oo
co a-
oo
r-
<n
o-.
oo r*
oo
r-
-J
>Sr aCx.
OO >
t-4
ti
t-t
c\ co
2"
D(Cr
cr O
3: V; E-
cc
W HIWK h
E-"
ft SK
f-i
10 -; Ett
&.
-i.
e c
cc a;
i-
U. i
MMMMO
P.
is ar
>-.
Eu:
E-
U>
if
CM iD ns CN
(^
om
P-
O J
CM
00
rsi
O O
CN CN
t\ir
3-
ar
cc a>
n n o< w o
-'
>
04
:*
xn
w
Cjl,
M PC W H
i
a- cc to
o b^
rr
CT-
v.
Eh
\a
f-t
*
Eh as
5.:
wr.
a r
co
fl
<"h
oo to
a.
JmCTICCH
www CQ en a o n
j
00 tu ro cr.
pn ac C3 t^ 53
Eh 32 CO E-t
ar
k-1
ir>
ro ft
U, u*
Eh Eh Eh Eh
Q 3
W
;
i
.
>
m to to k: aa cc drr v. o
rr>
tx3
cc o:
^ ^ HUUQ < hm
f
cc
.X
<
3E 52
O hz W
re U. W uo
,il
-t
f(
00
Vr.
u- :xj Oh >: ft
OQ
HH DOQOHfnU ~ O hz Eh O U
Ui tO
fHV<HH,4QhZHPhi-lW HUUMH^QOH^HHD
U
.
3E *. >- 2-j-
:"-
ZWWOHE
*
to
r>H
---:
r-t
Haso>tt-a:wio>s:!JHH
ni
UH
CO <C oo -u
Lil<
^ W
me.
r
fe,
wO in
U*
CI-
SC Cn
t- E-"
UJ w Mh uu H
Ci_
SR
SB
\
C
05 a:
Ui
CM V.
WW Oo uu
05 pg
Li.
Cvi
Ci3
Cli
1/1
.'/I
05
f-
CO J5 05
O >
<
h-1
00 Ph
52-
*A S3
M O
o>
w a
'O
r
E-
> MH M O
SO
os rd
05
^W X
>-
W an
05
Eh
93
Vorthman of a An analysis deliquid desiccant regenerated humidifier solar or with waste powe r
The si
171193
Vorthman An analysis of a liquid desiccant dehumidifier regenerated wi th waste or solar powe r
7983