Model No. MY7045A2001 Specification Direct-coupled damper actuator (Voltage input, spring return)
Specifications
Item Power supply Angle of rotation Power consumption Torque Holding torque Input signal Specification 24V AC 20 %, 50/ 60 Hz max. 95 (adjustable 25 to 95 with a supplied mechanical stopper) 6 W (motoring) 2.5 W (holding) 15 Nm (motor : at rated voltage) 15 Nm (spring return)
(1/2) Item Ambient operating conditions Ambient shipment conditions Protection Wiring Weight Ordering specifications Parts included
(2/2) Specification Temperature: -20 to +50 C Humidity: 10 to 90 %RH (non-condensing) Vibration: 4.9 m/s Temperature: -40 to +80 C Humidity: 5 to 90 %RH (non-condensing) Vibration: 9.8 m/s Dust proof, Drip proof IP42 0.75 mm, 5-core, approx.1 m long Approx. 2.7 kg 1. Model No. 2. Whether the AT72-J1 transformer is required or not. 1. Universal bracket (10093) 2. Vinyl cover for curing during work 3. M4 tapping screw (2) 4. Mechanical stopper ZDB-AF 5. Hexagonal wrench for manual open/close
15 Nm 2 to 10V DC (Linearly proportional to 0 to 100% openings) Input resistance 100 k Feedback 2 to 10V DC signal (Linearly proportional to 0 to 100% openings) Timing Approx. 150 seconds (fully closed fully open, when motor driven) Approx. 16 seconds (fully open fully closed, spring return) Applicable 10 to 20 mm, 10 to 16mm damper shaft
Dimensions
92.5 23 57
10 to16mm 10 to20mm
10
12.5
20 115
10 9
98 80
50
Slotted Tapping Screws, flat, JIS B 1115-1976 equivalent M4, pitch1.4, 12 mm long
(2)
Safety Instructions
Please read instructions carefully and use the product properly. Please keep this instruction on hand for reference at any time. Usage Restrictions This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in clean rooms or places where reliability or control accuracy is particularly required, please contact Yamatakes sales representatives. Yamatake Building Systems Co., Ltd. bears no responsibility for any benefit, or lack of benefit, derived from the operation by the customer. CAUTION
Do not do withstand pressure test or insulation resistance measurement to prevent equipment damage or accidents. Installer must be a trained, experienced technician. Check the ratings given in this instructions to prevent equipment damage. Check the environment given in this instructions to prevent equipment damage. All wiring must comply with applicable codes and ordinances. Use crimp contacts with insulation jackets for wire terminals. Disconnect the power supply before wiring to prevent electrical shock and equipment damage.
AB-5467
(Change the direction of rotation) Remove the C-clip. Take out the clamp and refit in on the other side. Replace the clip.
Not-Used
Figure 6
* Cable 1 is power supply, system common line * Insulate unused cable terminals. Figure 3 Wiring
If the damper spindle is 20 mm to 90 mm long Set the hexagonal nut side of the damper bracket to the damper side before installation (refer to Fig. 7 to 9).
Installation
If the damper spindle is 90 mm or more long Run the damper spindle through the output spindle of the actuator and fasten it using the hexagonal nut. To prevent the actuator from wobbling, install the attached bracket on the duct to fasten the actuator (refer to Fig. 4 and 5).
20 to 90mm Figure 7
min. 90 mm
Figure 4 Figure 8
Figure 5 Figure 9
AB-5467
Manual operation
Use the included hexagonal wrench to open and close the actuator (damper) and hold it in the desired position. Set the opening from close to open by inserting and turning the hexagonal wrench into the hexagonal hole on the top and bottom of the actuator. To lock the position, turn the wrench in the reverse direction immediately after the opening reaches the designated angle.
AB-5467
Printed in Japan. AB-5467 0.5H-H(W)