Академический Документы
Профессиональный Документы
Культура Документы
Summer 2000
5 Voltage Stability
or Load Stability Transient voltage stability Long term voltage stability (Partial) Voltage collapse Problems most articulated in developed power systems
Olof Samuelsson
Summer 2000
Basic phenomenon
1 High (reactive) loading reduces the voltage in an area 2 Temporary load reduction 3 Transfer capacity to the area is reduced 4 Load demand recovers 5 Voltage is further reduced 6 If there is no solution to load flow, the voltage collapses
Olof Samuelsson
Summer 2000
Olof Samuelsson
Summer 2000
PV curve
or Nose curve For constant power factor, how will the bus voltage vary with load level? Increase load level, load flow gives bus voltage Nose point for cos=1 at R=Xth P=0.5, V=0.7 Polar coordinates P/Q fixed, S variable P can be system, area or bus load Margin: Pre-contingency level post-contingency nose load Taylor Fig. 2-8 different PF
Olof Samuelsson
Summer 2000
Bottom of PV curve
On the lower side of the PV curve: increased load admittance reduces load power; adding a shunt capacitor reduces bus voltage; tap changers reduces voltage; stable for impedance load; unstable for constant power load.
Olof Samuelsson
Summer 2000
Mechanical PV analog
v 0 x i x P i v x
1 0.7
v1
v v2 P
Right angle corner will move on a circle Triangle area is P two solutions for each P Maximum power Pmax @ Vcrit, crit Vcrit=V1/sqrt(2) crit=45 Pmax =0.5V12/Xline Reactive voltage support corresponds to radial force
Olof Samuelsson
Summer 2000
Short-circuit ratio SCR: SCR=Sequipment/Ssc Relative measure of how stiff the voltage is at bus: VEth(1-Q/Ssc) Rule of thumb for dimensioning reactive compensation.
Olof Samuelsson
Summer 2000
Analysis methods
Static methods for limits and location of problem area Circle diagram Q(P) PV curves V(P) (standard, not in Machowski) QV curves Q(V) Modal analysis of power flow Jacobian matrix Eigenvectors Participation Singular Value Decomposition
Dynamic methods for mechanism and course of events Detailed time simulation Quasi Steady State simulation (van Cutsem)
Olof Samuelsson
Summer 2000
QV curves
For constant real power, how much reactive power injection at a bus is required to obtain a certain voltage there? Make bus PV and schedule P and V, load flow gives Q Rectangular coordinates P fixed, Q variable Q is bus injection Margin: Distance from bottom of curve up to operating point (Q=BSCV2 with BSC=0 if no compensation) Note: Q(V) in Machowski (Fig. 7.6) is upside down!
Olof Samuelsson
Summer 2000
Modal analysis
Modal analysis of power flow Jacobian matrix: Zero eigenvalue no load flow solution collapse Consensus: Eigenvalue magnitude has no meaning Eigenvector of smallest eigenvalue points out problem area and buses
Olof Samuelsson
10
Summer 2000
Stability criteria
Voltage stability margin PV Distance in load level change to collapse point QV Vertical distance: curve to Q=0 or Q=BSCV2 Stability indicators Smallest singular value of power flow Jacobian d(QSQL)/dV < 0 (in Machowski) dE/dV > 0 dQG/dQL > 0
Olof Samuelsson
11
Summer 2000
EPRI Software
VSTAB Voltage Stability Analysis Program Off-line only PV and QV curves Modal analysis Contingency lists Load increase and generation dispatch Limiters and automatic controls
VSAT Voltage Security Assessment Tool On-line or off-line use Contingency screening and analysis Fast time domain (quasi steady state) simulation Transaction analysis Security margin
Olof Samuelsson
12
Summer 2000
Modeling considerations
Load models ZIP, dynamic Tap changers Generator current limiters Induction machines Thermostats
Olof Samuelsson
13
Summer 2000
Load behavior
Induction motors Constant Z in short time-scale Constant P in longer time-scale Time scale: seconds Dominate air conditioner behavior Heating with thermostatic control Constant Z in short time-scale Constant P or energy in longer time-scale Time scale: minutes Load diversity only average power is supplied Tap changers Controls low side voltage to nominal value Counteracts load relief Reduces stability margin if not blocked
Olof Samuelsson
14
Summer 2000
Load modeling
Load recovery common to induction motors, thermostatic loads and tap changers. Taylor Fig. 4-20
1 x p + Pt (v) Tp
s
v Ps (v) = P0 v0
v Pt (v) = P0 v0
Olof Samuelsson
15
Summer 2000
Taylor Figs. 2-13, 14 Qgen0 at normal operation maximizes fast reactive reserves AVR control of high-side transformer voltage reduces Zth Harald Scherers work aims at explicit control of temperature
Olof Samuelsson
16
Summer 2000
Scenarios
All with an initial voltage reduction 1. Transient voltage stability (0-10 s): Induction motor stalling (wind parks) gives domino effect Loss of synchronism 2. Longer-term voltage stability (some minutes): Load recovery due to tap changer action Field current limiter action 3. Longer-term voltage stability (tens of minutes): Load buildup Loss of diversity among thermostatic loads
Olof Samuelsson
17
Summer 2000
Olof Samuelsson
18
Summer 2000
Olof Samuelsson
19
Summer 2000
Reactive compensation
Local compensation improves cos; transfer capacity is used for P.
Remote compensation remote voltage is increased; transfer capacity is used for P and Q; overvoltage at load rejection.
Olof Samuelsson
20
Summer 2000
Shunt compensation
Taylor Fig. 3-16
Do not wait!
Olof Samuelsson
21
Summer 2000
Series compensation
Fixed or thyristor controlled capacitor in series with line
Reactive generation increases with current and load and makes reactive compensation self-regulating
Olof Samuelsson
22
Summer 2000
SVC
Static Var Compensator A Shunt Capacitor which is connected during a variable part of the 50 Hz period by thyristors Variable capacitance
Olof Samuelsson
23