Project Subject Date Pipe

: Radisson, Maldives : Friction Loss in Pipe from Sewage sump to WWTP : 24-Apr-09 : High Density Polyethylene

Hazen-Williams Equation 10.7 x L x Q1.852 Head loss (m) = d4.87 x C1.852

Q = Flow rate in m3/s d = Internal diameter in m C =Hazen-Williams coefficient for HDPE pipe Sewage pump 2 sets for 1 duty 1 standby Flow rate ( max) for each pump Static Head

140

(5 years old)

= = = =

0.393 0.0065 5 7.1

Cu.m. per min. Cu.m. per sec m. PSI

Total length from Drainage sump-03 to site drain Transfer pipe length, L Equivalent length Total pipe length = = = 30 9 39 m. m. m.

Used HDPE For HDPE pipe diameter Head loss from pipe Static Head Residual Outlet Pressure Total Head required Velocity in pipe = = = = =

100 0.10 0.295 5.000 5.00 10.30 0.96

mm. m m m m m m/s

Remarks: 1) The recommended velocity in pipeline can be varied between 0.6 and 2.0 m/s to prevent the sedimentation oc

Note : Friction loss from HDPE dia 400 mm. pipe only

o prevent the sedimentation occurring in the pipeline and minimize the pipe friction loss