Contents Description
Description .................................................................... 2 Construction Dimensions Materials .............................. 3 Installation Details ......................................................... 5 Product Range Accessories .......................................... 7 Technical Data .............................................................. 9 Order Details ................................................................ 10
Fire dampers provide an automatic means of localising areas of fire in ventilation systems. The FSD range of curtain bladed fire dampers are suitable for installation in walls and ceilings made from concrete or brickwork, and will stop the spread of fire through duct, walls or floors. There is a wide choice of sizes available suitable for low, medium and high velocity applications and include rectangular, square, circular and flat oval connections. The dampers are fitted with standard release 72C fusible links unless otherwise specified. Note: The installer should note that all fire damper installations plus required access panels have to be to the satisfaction of the District Surveyor or the appropriate Fire Protection Authority.
Type FSP
The construction is similar to type FSD, except that the blades are manufactured from stainless steel grade 430.
Type FSE
Of similar construction to type FSP, except that the case and catchplates are manufactured from stainless steel grade 304L.
Type FSD...P...E Construction Variants: A, B and C have blade packs partially in the airstream
Duct size Dim
Y 10 10 10 20 20 30 30 30 30 40 40 50 50 60 60 60 70 70
Type FSD...P...E A
38 80 38
B or H 150 200
250 300
350
2
Type FSD...P...E B
5 Y x
Type FSD...P...E C
5
6 2
Fusible link
Note: All types shown can have prefix FSD,FSP, FSE 'Y'is dimension of blade protrusion into airstream
2 3
Type FSD...P...E DR
38 80 38
Type FSD...P...E ER
24
Type FSD...P...E DC
Type FSD...P...E EC
235 80
Duct size
BXH BXD D
Dim
X
100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
49
40
50
1 2 3 1 2
74
Type FSD...P...E DO
Type FSD...P...E EO
235 80
99
50
1 2 3 1 2
Note: All types shown can have prefix FSD, FSP, FSE X is dimension of variable top case section
40
Fusible link
2 3
InstalIation Details
HEVAC Installation Frame Type H
The HEVAC Installation Frame Type H is built to specification HVC 615183. Various fire damper designs can be used with this installation frame, see below. The installation frame is factory assembled with its respective fire shutter damper and delivered to site as one unit. This unit should be installed centrally within the thickness of the surrounding wall or floor such that the centre line of the frame is a minimum distance of 50mm from the nearest face of the wall or floor. On installation all fixing tabs except those which are completely inaccessible shall be bent into the mortar joints between the brickwork or blockwork surrounding wall or floor. Then with cement mortar fill all joints solidly. In reinforced concrete the tabs should be bent out and tied with wire to the reinforced bars. The gap between the frame should then be backfilled with concrete or mortar both sides of the frame. Where more than one duct penetrates a fire wall or floor, adjacent fire dampers and frame assemblies must be separated by builder's work of a minimum thickness of 225mm. All FSD, FSP and FSE types can be fitted in the HEVAC installation frame. Note in all cases HEVAC frame is manufactured from galvanised mild steel.
1
10mm clearance between frame and fire damper to allow for expansion. Galvanised steel spacer to permit expansion. Galvanised steel building ties. Aluminium rivets fix the corner angles to the frame Galvanised steel frame the corners left open. Steel corner angles retain frame open corner. 15mm clearance between mitre corner.
2 3 4 5 6 7
HEVAC Installation Frame Type H Rectangular / Square Connection Type FSD...E...P A... C
B + 105mm
H + 105mm
B + 136mm
D + 146mm when X = 49mm D + 171mm when X = 74mm D + 196mm when X = 99mm
7
Note: Two dampers can be supplied assembled in a single HEVAC frame up to size B x H 1524 x 1000mm. Receipt of an order for this configuration will be taken by Trox as the client having obtained this approval from the appropriate authority.
InstalIation Details
Installation with Sleeve and Peripheral Angles:
As an alternative for use where the HEVAC frame is not desired, cannot be fitted, or for multi section arrangements, peripheral sleeves and angle frames can be constructed in accordance with the following: The damper should be installed centrally within the surrounding wall or floor thickness such that the centre line of the frame is a minimum distance of 50mm from the nearest face of the wall or floor. The damper should be installed in a rectangular galvanised steel sleeve with a minimum thickness of 1.2mm. The fixing of the damper can be by tack welding the case on both sides directly to the sleeve, or by the use of 20 x 20 x 1.2mm steel angles which should be tack welded to the sleeve. In both cases welds to be at a maximum of 225mm pitch. The sleeve should be of a suitable length to extend through the wall or floor opening to enable the fitting of the cover angles and ductwork. The cover angles should be attached to the sleeve by 6mm diameter bolts at a maximum of 225mm centres, and should form a complete frame around the sleeve and cover over the expansion gap (see table) required between sleeve and wall or floor opening. The expansion gap should be filled with compressible, non combustible material (mineral wool). The cover angles should be of such a size as always to form a cover over the wall or floor opening by 25mm minimum, and should be manufactured from a minimum size of 38 x 38 x 3mm steel angle. All fixings must be positioned clear of the damper blade path so as not to impede proper closure. Warning Dampers supplied without installation frames as shown on page 5 or not being fitted into installation sleeves, must not be installed within a solid masonary structure as the outer case has no facility to cater for expansion during fire conditions. Note: Supply and fixing of sleeve and peripheral angles by others.
BxH
Total Clearance
0-500
6mm
3mm
500-1000
2 1 3
13mm
6mm
Installation Requirements
The installer should note that the installation and location of access panels is to be to the satisfaction of the District Surveyor or Building Inspector or the appropriate Fire Protection Authority.
When duct size B or H is greater than 1000mm, multiple dampers sections will be required. With all multi section installations the proposed arrangements must be to the satisfaction of the appropriate local authority and/or fire officer responsible for the installation. Receipt of an order requesting multiple sections will be taken by Trox as the client having obtained this approval from the appropriate authority.
Vertical/horizontal mounting
Vertical/horizontal mounting
High
Functional Description
Fusible link release (basic unit) Automatic closure of the fire damper at an air temperature of t > 72C, in the area of the fusible link; for smouldering fires where t < 72C, the system does not release. Magnetic release: (AC or DC solenoid or DC electro magnet) Thermal closure of fire damper at t > 72C, or electrically when the current is interrupted (power off to close) DC electro magnet, or pulsed (power on to close) AC or DC solenoid. Signal from central control or via a smoke detector built into ventilation system e.g. Trox Smoke Detector Type RM-O or RM-1/2. ETL Release: A dual response fusible link release providing automatic closure of the fire damper; a) at an air temperature t > 74C in the area of the Iink. b) When subject to a short duration low power electrical impluse which triggers a chemical heating of the centre element causing the link to release in approximately 7 seconds. This signal could be provided for example by a smoke detector, e.g. Trox Type RM-O or RM-1/2.
Accessories
Description Code Description Code Z01 Description Code Z02
Fitted to all FSD...P...E variants. Except type FSD...P...E C Ring pull permits the release of the blades from the catchplates when access is from the opposite side to the catchplates.
Mechanical device to indicate blade closure visable externally from the damper.
Sub-frames
Code H U Description Additional HEVAC sub-frame for wall mounting. U channel joining sub-frame for multiple assemblies. HEVAC model sub-frame sub-frame supplied assembled to the fire damper. Supplied loose for site assembly by others.
Accessories
Construction or construction variant
Base holder with fuse link (standard construction)
Combined with
Code
Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicators indicates blades CLOSED
Double changeover contact Circuit breaking capacity max 380V ~, 50Hz, 10A, min 24V, 100mA Contact resistance 60m. Protective system IP 66
Base holder with ETL fuse link which is a dual response device with fusible link which reacts (melts) when subjected to either local heat or an electrical impluse of low power and short duration. The standard temperature rating is 74C. It can be released with an electrical impluse (between 6 volt and 30 volt AC or DC minimum current of 0.2 amperes).
Z04 Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicator indicates blades CLOSED Z05 Z06 Z07
Double changeover contact Circuit breaking capacity max 380V ~, 5OHz, 10A, min 24V, 100mA Contact resistance 60m. Protective system IP 66
Universal release holder with fuse link. Each side of release device has a spring loaded lever allowing the damper to be easily tested for closure and re-loaded with one hand from either side. Standard fusing temperature 72C.
Z08 Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicator indicates blades CLOSED zog Z10 Z11
Double changeover contact Circuit breaking capacity max 380V ~, 50Hz, 10A, min 24V, 100mA Contact resistance 60m. Protective system IP 66
Universal link fitted with an AC electric solenoid 230/240V AC. Provides remote operation from an AC electrical signal. Power ON closes the damper. It incorporates a fusible link within the universal release to also provide normal closure in the event of increasing temperature AC Solenoid U = 230/240V 50Hz P 55VA inrush 20VA closed 100% rated. Universal link fitted with a DC electric solenoid 24V DC. Provides remote operation from a DC electrical signal. Power ON closes the damper. It incorporates a fusible link within the universal release to also provide normal closure in the event of increasing temperature. DC Solenoid 24V DC 1 2W 100% rated
Z12 Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicator indicates blades CLOSED
Double changeover contact Circuit breaking capacity max 380V ~, 50Hz, 10A, min 24V, 100mA Contact resistance 60m. Protective system IP 66
Z16 Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicator indicates blades CLOSED Z17 Z18 Z19
Double changeover contact Circuit breaking capacity max 380V ~, 50Hz, 10A, min 24V , 100mA Contact resistance 60m. Protective system IP 66
Universal link fitted with an electro magnet 24V DC. Provides remote operation from an DC electrical signal. Power OFF closes the damper.lt incorporates a fusible link within the universal release to also provide normal closure in the event of increasing temperature. DC Electro Magnet 24V DC 4W 100% rated.
Z20 Limit switch indicates blades CLOSED Visual indicator indicates blades CLOSED Limit switch with visual indicator indicates blades CLOSED
Double changeover contact Circuit breaking capacity max 380V ~, 50Hz, 10A, min 24V, 100mA Contact resistance 60m. Protective system IP 66
Technical Data
Fire Test BS 476 Part 201987
The fire dampers shown have been tested by an independent authority (Warrington Research Centre) according to British Standards 476 Part 20; 1987 for a period of 4 hours. The time / temperature curve required by this test procedure is shown below, after 4 hours test the FSD retained its integrity with no significant openings being formed. Pressure losses are shown below for units with blades either partially in or out of the airstream.
1100
800
700
600
500
400 100 Static pressure drop Pascals (Pa) 80 60 50 40 30 25 20 15 0 30 60 90 120 150 180 210 240 100 200
300
Order Details
Specification Text
Square or rectangular shutter type fire dampers for the isolation of fire zones in air conditioning systems. Designed to maintain integrity and stability for 4 hours when tested to BS 476 Part 20; 1987. Tests carried out at Warrington Research Centre, England. The FSD fire dampers consist of perimeter frame case and interlocking shutter type blades. As standard the case is complete with catchplates and constant tension closure springs. Suitable for either rectangular, circular or flat oval ducting and available in high or low pressure/velocity construction. Standard release 72C fusible link.
Options:
Universal release mechanism with fusible link or fusible link in conjunction with solenoid or electro magnet release. Fusible links available at other fusing temperatures. Stainless steel blades, or all stainless steel construction (blades grade 430 case grade 304L). For reduced leakage addition of stainless steel side seals (grade 302). For vertical installation only (horizontal duct work) damper without closure springs, catchplates or side seals.
Materials:
Case, blades and catchplates galvanised mild steel to BS EN 101421991 FE PO 2GZ275 NA. Constant force stainless steel closing springs. Brass soldered fusible link.
Order Code
This code must be used when H Dim exceeds 1000mm These codes do not need to be completed for standard products
FSD A V
1000 x 500
Z01
Duct Size Dimensions square or rectangular B x Hmm, circular Dmm dia. Flat oval B x Dmm. All damper with spigots are manufactured down on duct size to fit inside duct work connections.
DR Rectangular Spigot DC Circular Spigot DO Oval Spigot ER Rectangular Spigot EC Circular Spigot EO Oval Spigot
Order Example
Make : TROX Type : FSD A / 1000 x 500 / 0 / Z01. Qty : 4