Вы находитесь на странице: 1из 8

Software Description

FBP FieldBusPlug

V7

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP


Connection via PROFIBUS DP

SIEMENS

PROFIBUS DP

UMC22

MFI21

MSD11, MSR22

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP


Connection via PROFIBUS DP

V7

Content 1. Overview of the Functions Blocks ........................................................................................................3 2. Example: UMC22 parameterized as Direct Starter' ............................................................................4 3. Installation and Example Program .......................................................................................................5 3.1 PLC Hardware ..............................................................................................................................5 3.2 Installation of the FB Library and the GSD le .............................................................................5 Unpack of the Library ABB_FBP_.ZIP...........................................................................................5 Import of the GSD le....................................................................................................................5 3.3 Conguration of the Bus in the PLC program ..............................................................................6 3.4 Address ordering ..........................................................................................................................6 3.5 Adjustment of the Parameters ......................................................................................................6 3.6 Particularities of the Example Programs ......................................................................................7 3.7 Presentation of the Function Blocks.............................................................................................7 4. Engineering Package "Step7 Function Blocks for FBP" (1SAJ929810R0201.ZIP)...........................7

Corresponding les.............................................................................................................................7 ABB_FBP_.ZIP - Step7 Function Blocks for FBP ...........................................................................7 Example_UMC.ZIP - Step7 Program Example for UMC .................................................................7 Example_MFI.ZIP - Step7 Program Example for MSD, MFI ...........................................................7 2CDC 192 007 D0101.PDF - German description Step7 Function Blockls for FBP ......................7 2CDC 192 007 D0201.PDF - English description Step7 Function Blockls for FBP .......................7

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

-2-

FieldBusPlug / Issue: 10.2005

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP V7


Connection via PROFIBUS DP 1. Overview of the Functions Blocks
The Function Blocks described here facilitate the application of the UMC22-FBP, MFI21-FBP, MSD11FBP and MSR22-FBP when the Step7 programming tool is used. The connection to the devices is made with PDP22 (PROFIBUS DP). FBs for UMC22 FB name UMC_ProbusDP_Command UMC_P-DP_Monitoring UMC_P-DP_Diagnosis UMC_P-DP_Transparent UMC_P-DP_OverloadRelay UMC_P-DP_DirectStarter UMC_P-DP_Reversing Starter UMC_P-DP_StarDeltaStart UMC_P-DP_PoleChangingSt UMC_P-DP_Actuator UMC_P-DP_Diag_Actuator MFI21 MFI_P-DP_Transparent MFI_P-DP_DirectStarter MFI_P-DP_Reversing Starter MFI_P-DP_StarDeltaStart MSD11 MSR22 MSD_ProbusDP MSR_ProbusDP all Control functions except Actuator Control function = Transparent Control function = Overload Relay Control function = Direc Starter Control function = Reversing Starter Control function = Star-delta starter Control function = Pole-Changing starter Control function = Actuator 1, 2, 3 or 4 Control function = Actuator 1, 2, 3 or 4 Transparent Direct starter Reversing starter Star-delta starter MSD11 (direct start) MSR22 (reverse start) Used for can be used for all Control functions

FieldBusPlug / Issue: 10.2005

-3-

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP


Connection via PROFIBUS DP 2. Example: UMC22 parameterized as Direct Starter'
The Function Blocks described here facilitate the application of the UMC22 within the Step7 programming tool. The connection to the devices is made with PDP22 (PROFIBUS DP). The basic relation is shown on the example UMC22 parametrized as Direct Starter

V7

to PLC program

from PLC program

automatic or handmade ordering in the PLC / Bus coupler Bytes in the PROFIBUS telegram <--------------->Bytes on the PLC side (symbolic) Telegram on the PROFIBUDS DP for example Monitoring Byte 0 Byte 1 Word Bit 0 - 7 Bit 3 = RUN FORWARD Bit 7 = DI5 MOTOR CURRENT Command Bit 0 - 7 Byte 0 Bit 3 = RUN FORWARD Byte 1 Bit 7 = DO2

Monitorings: - all digital inputs - internal signals e.g. RUN FORWARD = motor running forward

Commands: - free digital outputs (not used for contactor control ect.) - internal signals e.g. RUN FORWARD = Start of the motor

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

-4-

FieldBusPlug / Issue: 10.2005

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP V7


Connection via PROFIBUS DP 3. Installation and Example Program
3.1 PLC Hardware
PS 307 2A (Order Number: 6ES7-307-1BA00-0AB0) CPU 315-2 DP (Order Number: 6ES7-315-2AF01-0AB0) 8DI/8DO (Order Number: 6ES7-323-1BH80-0AA0) 8DI: Address 4 / 8DO: Address 4

3.2 Installation of the FB Library and the GSD le


Unpack of the Library ABB_FBP_.ZIP Unpacking can be done with the SIMATIC Manager Target directory can be selected as desired STEP7 nds the new library automatically when the program is started and offers the function blocks as program elements in the IL/LD/FBD editor.

File

Open Close

Save as Delete Organize

Print

Import of the GSD le

Install new GSD

Introduce the desired FBP device into the project.

FieldBusPlug / Issue: 10.2005

-5-

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP


Connection via PROFIBUS DP
3.3 Conguration of the Bus in the PLC program

V7

3.4 Address ordering


PROFIBUS slave address Inputs / outputs of the device Addresses of the inputs Addresses of the outputs

3.5 Adjustment of the Parameters

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

-6-

FieldBusPlug / Issue: 10.2005

Step 7 Function Blocks for UMC22-FBP, MFI21-FBP, MSD11-FBP, MSR22-FBP V7


Connection via PROFIBUS DP
3.6 Particularities of the Example Programs
Executive Control Functions that avoit stop of the DP Master CPU in case of faults in the decentralized periphery. OB82: Diagnosis alarm Allows to read the diagnosis data of the slaves. Supposition: Diagnosis alarm of the slaves is released in the HW conguration. OB86: Slave failure Monitors the failureof a slave and also the restart of a slave OB122: Faulty access to I/O Access to a slave or I/O address that is not congured or not available

3.7 Presentation of the Function Blocks


The FBP function blocks have longer signal designations inside and need, therefore, more width. Menu Extra, Einstellungen (selections, adjustments)

4. Engineering Package "Step7 Function Blocks for FBP" (1SAJ929810R0201.ZIP)


Corresponding les
ABB_FBP_.ZIP - Step7 Function Blocks for FBP Example_UMC.ZIP - Step7 Program Example for UMC Example_MFI.ZIP - Step7 Program Example for MSD, MFI 2CDC 192 007 D0101.PDF - German description Step7 Function Blockls for FBP 2CDC 192 007 D0201.PDF - English description Step7 Function Blockls for FBP

FieldBusPlug / Issue: 10.2005

-7-

Step 7 FBs for FBP-Devices Connection via PROFIBUS DP

ABB STOTZ-KONTAKT GmbH Eppelheimer Strae 82 69123 Heidelberg Germany Telephone Telefax E-mail Internet Postfach 101680 69006 Heidelberg Germany