CHAPTER 10 Developments in Bench Testing Facilities
for Protective Gear
BYF. L. HAMILTON, AND N. S. ELLIS. INTRODUCTION The testing of protective-gear systems and their con- stituent components calls for test-equipment of a rather specialised nature. The requirements of modern protective-gear systems have increased the complexity and cost of such equipment and the amount of testing to be done has necessitated a speeding up in the procedure of tests. The tests which may be necessary on protective-gear equipment are somewhat varied but, in general, will fall into one or more of the following categories. Investigatory These include those tests which may be essential on circuits and components during development projects. The scope of these test may be large, as they often explore a variety of effects, design factors, parameter changes, etc. Tests of this type may also include investig- ations into more fundamental problems, such as the transient response of current-transformers and the effect of this on various protective-systems. The information obtained from such investigations is often used to check the soundness of new ideas and provide practical design-data upon which new experi- mental equipment may be based or by which existing designs may be modified to improve their performance. Performance Testing The overall performance of protective-systems, relays, and the like is an important aspect of protective- gear testing. Tests of this type may be concerned with experimental and production prototypes or with the cer- tificiation and type-testing of new protective-gear equipment or relays. In the past, a large amount of the testing referred to above has required heavy-current rigs, which are costly and limited in flexibility. Such heavy-current rigs require extensive machine supplies, the demands upon which are so great that they often form a considerable limita- tion to the number of investigations which may be undertaken. The protective-gear test-bench described in this arti- cle was developed in order to replace the conventional heavy-current and secondary-injection equipment in many types of testing particularly those concerned with investigatory work on experimental projects and pro- totypes. The main requirements borne in mind in the design of the equipment are as follows: (a) Extreme flexibility of test circuit and conditions. (b) Rapid setting up of equipment. (c) Use of ac. mains as the source of power. (4 (4 Provision of facilities for close control of the test-conditions and parameters. Rapid rate of testing. General-purpose Test-bench for Protective-gear General An overall view of the test-bench is shown in fig. 1. The main primary circuits for the test bench are supplied from the 440-volt 3-phase mains, with alternative arrangements for taking this supply from a three-phase variable-frequency machine when necessary. The max- imum current which is taken by the primary circuits is of the order of 120 amperes but, as tests at these currents are of a limited time-duration, the supply need not be rated continuously at this current. When the primary currents are of the order of 10 amperes these may be used on a continuous basis. The main primary circuits are shown diagrammati- cally in fig. 2, from which it can be seen that the three- phase supply is applied, by a fault-making switch, to two sets of variable impedances per phase, one of which represents a generating source impedance and the other the impedance of a line. The current-transformers, of which there may be up to four per phase, can be con- nected in various combinations according to the particu- lar fault distribution which it is required to reproduce. The (0) (b) primary circuit has two maln functions: To provide primary currents in various combina- tions of current-transformers, with control of overall time constant, the point of wave at which the fault is applied, the type of fault, and the duration of fault. This function is required when the bench is used for tests where only current is of significance. To provide variable current and voltage condi- tions at a relaying point with control of time constant, duration of fault, point-of-wave, and type of fault. This function is required when the bench is used for the dynamic testing of relays and protective-systems which require both cur- rent and voltage, e.g. distance protection. The equipment required for the above basic functions lends itself to many other test applications which require controlled current and/or voltage conditions. The vari- ous units which make up the complete test-bench are described in more detail overleaf. Source and Line Impedances One of the main requirements of test-equipment of this type is to obtain current and voltage transients of the 140 order of those which may occur in practice. The source impedances are designed with maximum X/R values of practice. The line impedances are designed with a max- the order of 30 and these produce current-transients imum X/R of about 10 which corresponds to that of a which are large enough to be comparable to those typical 275-kV line. Resistance can be inserted to obtained with generator and transformer impedances in reduced this X/R value to about 2,6 which corresponds to that of a typical 132-kV line. CONNECTION REACTANCE AT 50 C/S UNIT A UNIT 6 3.0 6.0 n 12.0 24.0 48-o / R(O) FOR ALL CONNECTIONS z 35 (0) 96.0 - 0 3.0 12.0 48-O =-iz% 6.0 9.0 160 54.0 24-O 27.0 36.0 72.0 96.0 j 99.0 1 108.0 144-o (h) I-I ol/ol OI 0 2.0 4.0 5.34 0 2.56 8.0 I b-0 0 2.9 10.6 32.0 I I I I I CC) FIG. 3. SOURCEREACTORS,SHOWING(U) CONNECTIONS, (b) RANGEOFSOURCEIMPEDANCEWITHUNITSINSERIES, AND(C) RANGEOFSOURCEIMPEDANCEWITHUNITSIN PARALLEL. The reactors in both source and line impedances are air-cored so that they are completely linear. Two source-reactors are provided for each phase, each having four sections. These two units are provided with switches so that their sections can be connected in a number of ways and the resulting impedances connected singly, in series, or in parallel to give a total source- impedance per phase, variable in relatively close steps between 2 ohms and 144 ohms. This arrangement is shown in fig. 3. The X/R values can be made constant over this range of source-impedance. An earlier version of the bench uses the simpler method of a tapped reactor with manual plug-selection but this has the disadvantage of a varying value of X/R over the range of impedances. Source-impedance is not normally included in the neutral connection, but where tests require a higher value of zero-sequence impedance in the source, the source-impedance of one phase may be connected in the neutral connection. This is permissible, since such tests will invariably be concerned with single or double phase-to-earth faults where one phase is not in use. A neutral link is provided so that resistance may be con- nected to simulate systems which have a resistance- earthed neutral. Three line reactors are provided in each phase and in the neutral. These represent, when all are in series, a line of approximately 3.5 ohms, the sections being 0.5, 1.0, and 2.0 ohms respectively (at 275 kV). By shorting out various sections, the impedance between the relaying point and the fault can be varied from O-3.5 ohms in steps of 0.5 ohm. The neutral line impedances are half the value of the phase line impedances, giving a typical value of ZO/Z1 = 2.5 for the line. The arrangement of the line reactors are shown in fig. 4. Impedance ofllne units: Phase 0 10 3.5 ohm\ in O-5 ohm wzps \~~th phase-angles of 70 10 ns Neutral 0 to l-75 ohms in 0.25 ohm step, with phase-angle5 of ho or 70 FIG. 4. ARRANGEMENTOFLINEIMPEDANCES Make Switch and Main Contactor The function of the main contactor is to connect the voltage-supply to the test-bench a short time (about f sec.) before application of the fault and to interrupt the fault-current after the required duration of the fault. With this arrangement, the main primary circuit is nor- mally dead and is only made alive for the minimum required time. The main contactor is of the heavy indus- trial type and is capable of interrupting repeatedly the maximum currents at very low power-factors. 142 The make switch is required to apply the fault at a particular point-on-wave, so that high speed and con- sistency of operation are essential. Experience has shown that telephone-type relays with heavy-duty con- tacts can perform this duty with comparative ease. The arrangement adopted is shown in fig. 5. One telephone- type relay with two parallel heavy-duy contacts is used per phase, and two auxiliary relays, energised in parallel with these, provide synchronised contacts for timing, interlocking, etc. The standard contacts have been mod- ified by the addition of a momentum transfer-device with practically eliminates contact-bounce. Very consis- tent operation is thus obtained and wear on these con- tacts is negligible. The relays are energised from the master control-unit as will be described later. Current-transformers Up to twelve current-transformers can be energised from the primary circuit in various combinations. They are of typical bar-primary design having normal 300/l and 3001.5 secondaries. Four primary windings are pro- vided to enable the overall transformation-ratio (and thus secondary current level) to be varied over a wide range in close steps. These windings are in the propor- tion 1 : 3 : 9 : 27 giving primary turns by addition or subtraction of 2-80 in steps of two. Selection of the primary turns is by means of a manual plug board which FIG. 5. MAKE" SWITCH ASS~MBLI also provides the facilities for interlinking the primary circuits of the current-transformers to form the various arrangements required. A tapped section of 10 per cent of the secondary turns enables the ratio of some of the current-transformers to be controlled by t10 per cent in steps of 2 per cent. The arrangement permits tests up to a current which is equivalent to 30 times the current- transformer rating at fairly high values of X/R. The amount of influence which the secondary burdening exerts on both the magnitude and time constant of the primary current is relatively small with modern low-VA protection and the arrangement is a fairly close approx- imation to a current source over the whole range of currents. Typical arrangements of the current-transformer cir- cuits are shown in figs 6a, 6b, and 6c. It should be noted that the reversing-switch in the primary circuits of some current-transformers enables rapid change-over between a single-end-fed internal fault, a double-end-fed internal fault, and a through- fault, when balanced-current systems of protection are being tested. The provision of both l-ampere and 5-ampere secon- daries on the current-transformers enables relays and protection for either rating to be tested. Alternatively, one secondary can be used as a search coil while the other is in use, or can be used for the injection of d.c. or a.c. ampere-turns into the current-transformer to simu- late certain conditions. Voltage-transformers These are provided so that the voltage windings of relays may be connected to the relaying point, i.e. bet- ween the source and line impedances. They are of nor- mal accuracy, suitable for burdens up to 75 VA, and are of ratio 440/l 10 volts, open-delta windings being pro- vided for relays requiring residual voltage connection. The primary windings of these voltage-transformers may be connected via a selector-switch to a number of positions as follows: (1) Continuous 440-volt supply. This is of use during those tests and adjustments where a continuous voltage-supply is necessary. (2) The source side of the make switch, so that the relays are energised at normal voltage prior to the appli- cation of the fault-current. This represents the condi- tion, in practice, of a fault occurring on a line which is in service. (3) The line side of the make switch, so that the relays are energised by the fault-voltage simultaneously with application of the fault-current. This represents the con- dition, in practice, of a faulted line being switched into service. The general arrangements of the voltage-transformer connections is shown in fig. 7. It can be seen from this that the current taken by the voltage-transformers is fed through the current-transformers. This is not completely desirable, but with the normal voltage-transformer bur- dens used in practice the reflected impedance of the 143 PLUG CONNECTIONS REVERSING SWITCH I AMP IL REVERSING /SWITCH MP MP FIG. 6. CURRENT-TRANSFORMERSSHOWING (a) ARRANGE- MENTOFTYPE-A UNIT,(b) ARRANGEMENT OFTYPE-B UNIT, AND(c) A VIEWOFTYPE A AND B UNIT. 144 voltage-circuits is so large compared with the line impe- dance that the resulting errors are negligible. This con- nection is preferable to that in which the current- transformers are on the line side of the voltage- transformers, since in this case the small voltage-drop across the current-transformers is imposed on the voltage-circuits. This voltage-drop becomes significant when testing with terminal faults close to the relaying point with heavy currents. MAIN MAKE CONTACTOR SWJTCH VOLTAGE z TRANSFORMER c jjjc- FIG. 7. SELECTIONOFVOLTAGE-TRANSFORMER CONNECTION. Master Control-unit The master control-unit provides the following fea- tures: (1) A safety time-lag of about f second between closing of the main contactor and operation of the make switch. Interlocking contacts on the contactor and make switch ensure that the circuit is always broken by the contactor. (2) 360 control through a selsyn and thyratron cir- cuit for selecting the point-on-wave at which the make switch closes its contacts. This is accurate and consistent within about 1 or 2. (3) A timing circuit which controls the duration of the Eault-current. Extreme accuracy of interruption of the circuit is not possible but the duration of fault may be adjusted from short faults of the order of 3 loops up to long faults of the order of seconds. (4) A variable pulse which can be used for triggering an oscilloscope at any point in the fault-sequence. This means that the whole of the fault may be observed on a slow time base or that any part of the fault or associated phenomena may be recorded in an expanded form by using a fast time base. This feature is extremely valuable, espeically when used with an oscilloscope equipped with a long persistence tube. Full advantage may be taken of the rapid testing-rate as photographic records may be kept down to a minimum. The genera1 arrangement of the lastest type of control-unit which has been developed is shown in block form in fig. 8. The unit is shown withdrawn from the pane1 in fig. 9 which also shows the unit construction of the Dekatron counter stages. These are made withdraw- able so that units can be easily replaced or interchanged. The selsyn unit provides a variable-phase supply to an electronic squaring circuit from which a pulse-forming circuit is energised. The 51-cycle oscillator may be used as an alternative to the phase-shifter and this provides AUXILIARY CIRCUITS SELECTOR cR0. TRIGGER FIG. 8. BLOCK DIAGRAM OF CONIXOL-UNIT. the facilities for random point-on-wave switching which is sometimes required. The pulse-forming circuit develops a train of pulses at 10 ms intervals which, when taken from the phase-shifter, are locked to a selected point-on-wave of the main supply-voltage. The pulse train actuates a 3-decade dekatron counter unit which gives a maximum overall time of 10 seconds. The counter system is arranged to start always on a pulse corresponding to the negative going half-cycle of voltage out of the phase-shifter. Thus the firing unit for the make switch, which is selected to a fixed 500-millisecond point on the second decade. always fires at the correct point- on-wave which is indicated by the phase-shifter. The firing unit of the make switch contains a thyratron which is triggered at the correct point, discharging a condenser through the make switch coil. Fast consistent opcra- tion of the make switch is thus obtained. The trigger control for the oscilloscope can be selected to any point in the pulse train thus enabling it to be up to 1 second in advance or 9; seconds later than the firing point of the make switch. This enables the beginning of the fault to be observed or any point after to be expanded on a fast time base. For complete convenience in this respect. a variable IO&20 milliseconds delay is fitted to the trigger circuit to enable triggering to be effected at points between the pulses of the main pulse train. The internal stop selector is also capable of being selected to any pulse in the train and this is used to trip the main contactor. The duration of fault may therefore be controlled in IO-millisecond steps from about 2-3 loops up to 9Q seconds. Facilities are also provided for stopping the sequence, i.e. tripping the main contactor, from a protection relay under test. The whole test-sequence is automatically controlled from on2 push-button. the equipment automatically resetting when this button is released. FIG c). Vlt:U 01. (ON I KOL:UNI T Ancillary Equipment Apart from the facilities offered by the main primary circuit, current-transformers, voltage-transformers, control-unit etc., certain auxiliary equipment has been included in the bench in order to extend its use and provide greater flexibility. The main items are described below: Phase-shifters A variable-phase supply is a frequent necessity in both protective-systems and relay-testing and this facility has been incorporated in the test-bench. The normal rotary phase-shifters have limitations which make them unsuit- able for such use and a special static phase-shifting trans- former has been built. The arrangement is as shown in fig. 10a and is basically a tapped three-phase trans- former energised from the same power-supply as the main primary circuits. The taps are so arranged that the manual plug-selection of the output circuits on the phase-shifter panel provides a 240-volt supply adjust- able in 10 steps through 360. The plug-selection pro- vides a visual indication of the phase-angle selected. The turns on the various secondary taps are so arranged that output-voltage remains constant independent of its phase-angle. Variac transformers can be inserted in the output to give control of the output-voltage. Two plug- selector systems are provided so that two variable-phase supplies may be obtained. The phase-shifter is capable of delivering currents of the order of 10 amperes without significant phase-shift so that there is no zero-correction necessary and the selected phase-angle may be referred to the main supply-voltage. Practice has shown that con- trol in 10 steps is adequate for most tests. Where closer control of phase-angle is necessary an external auto- transformer unit has been designed, as shown in fig. lob, which gives control between the 10 positions in steps of 1. Voltage Simulators It is sometimes advantageous to use the main current circuits of the bench to energise the current circuits of a relay, but to use voltages which change in a predeter- mined way (independent of the bench circuits) on appli- cation of the fault-current. A voltage-simulator unit has been designed for this purpose. Potentiometers in each phase-to-neutral voltage enable the voltages on each phase to be adjusted to a particular value to which they will fall from normal voltage when the current is applied. Primary Shunts and Meters The primary circuits are provided with current-shunts so that the primary current-transient may be observed by oscilloscope. A multi-range ammeter is provided together with current-transformers so that the steady- state current in any phase or the neutral may be meas- ured. An operations-counter is provided so that the number of operations may be logged. This is useful both from the test and maintenance aspects. SECONDARV I I 440V MAINS INPUT 250 v OUTPUT (h) FIG. 10. PHASE-SHIFTINGTRANSFORMER,SHOWINC (a) ARRANGEMENTFORlo'STEPS,AND (b) THEATTACHMENT FOR 1" STEPS. Auxiliary A.C. and D.C. Supplies In view of the large number of electronic instruments in use which require mains supplies, a number of mains sockets are provided on the bench. These can also be used for auxiliary voltage supplies of fixed phase-angle. A 1 lo-volt d.c. supply which can be used for repeat- contactors is provided on the bench. A repeat-contactor with seal-in contacts and lamp-indication is a built-in feature for relays with no repeat-contactor incorpo- rated. Timing A portable electronic timer is normally used in con- junction with the bench. The provision of contacts sync- hronised with those on the make switch ensure easy measurement of overall operating-times of relays and protection. Auxiliary contacts on the main contactor provide similar facilities for measuring the release times of relays on de-energisation. Oscillographic Work The facilities for triggering oscilloscopes on single- stroke operation enable transient phenomena to be readily investigated on the bench. The ability to repeat shots under controlled test-conditions in conjunction 146 with long persistence tubes reduces photography to a minimum. It is usually only necessary to photograph traces when permanent records of a particular trace are required. Typical Application Some of the applications for which the test-bench has been used are described below. Differential Protection Most of the protective-systems based on current- balance of current-transformers can be explored. Protective-systems with up to four terminals can be tested on a three-phase basis, and those with up to twelve terminals on a single-phase basis. The steady- state and transient balance of current-transformers are readily checked by the equipment. The examples of oscillograms shown in fig. 11 illustrate how clearly the problems of transient balance of current-transformers may be demonstrated. These records also show the con- siderable time constants obtainable and the consistency of point-on-wave switching. Distance Protection lndividual distance-relays or complete distance- protection schemes may be tested in a very realistic manner with extreme rapidity. The provision of line and source impedances affords a realistic relaying point for distance-protection, the source-impedance being varied to simulate the system plant conditions and the line impedance varied to simulate the fault-position. Fine control of the impedance relay setting is effected by means of primary and secondary adjustments on the current-transformers, thus enabling the accuracy of the relays to be determined under switched conditions in addition to ordinary static bench-test. The effects of the primary transients on accuracy is important with high- speed systems and this may be readily explored. Also, the overall time of operation for faults within the zone may be determined for various source conditions and for varying degrees of transients. With suitable interconnections it has been possible to explore the effect of reversal of current-flow when a switch opens under fault. The effect of the zero- sequence impedance of transformers and the efficacy of earth-fault compensation has also been investigated. Relays Tests on individual types of relays may be made with or without the effects of current-transformers. Some examples are as follows: (a) The dynamic characteristics of instantaneous- relays with off-set current-inputs. (b) Timing characteristics of overcurrent relays and overshoot measurements. The effect of current- transformer saturation on time of operation of overcurrent-relays. (c) Dynamic tests on directional-relays. CONCLUSION The illustrations in this article apply to a new design of test-bench just nearing completion. A previous pro- totype design has been in use for three years and has proved invaluable. It is of interest to note that nore than 100,000 operations have been done on the earlier test- bench with practically no maintenance. The principles developed in these test-benches have been applied to the testing of production-equipment, and a bench of similar type is being supplied to the C.E.A. It is also of interest to note that the equipment developed and the methods used are finding application to University research. For example, a bench of this type is being constructed at Manchester College of Technol- ogy for use in post-graduate research and as demonstra- tion equipment, the major items being supplied by Reyrolle. 147 Primary current adding to rcmanence i IP i IP i IP i IP i IP FIG. 11. ZERO-SEQUENCETESTSONBALANCEDEARTH FAULTPROTECTIONWITHLOW-IMPEDANCERELAY. 148