Louver Design Considerations

Feb 1, 2006 9:23 AM, By JAMES LIVINGSTON Ruskin Co. Grandview, Mo. Think about size and shape when choosing a louver After selecting a louver model that best fits an application, system designers need to consider certain characteristics when sizing the louvers. In this article, characteristics that affect water penetration, pressure drop, and louver installation will be examined. By using the following suggestions, designers will maximize louver performance and ensure that louvers are equipped to meet the needs of their specific application. First, consider sizing louvers to minimize water penetration. In the first part of this series, published in January, the difference in airflow capacity between standard and wind-driven-rainresistant louvers was examined. Although wind-driven-rain louvers can significantly reduce or even eliminate water penetration, standard louvers often are used. To keep rain from penetrating standard louvers in storm situations, size the louvers so their operating free-area velocity is less than the maximum beginning point of water penetration defined in an Air Movement and Control Association (AMCA) still-air water-penetration test. This will allow for the effect of wind. While there is no industry standard for this safety factor, most experienced designers reduce the tested AMCA velocity by 15 to 25 percent, depending on the application conditions. The benefit of using wind-driven-rain louvers is that they are tested under wind-driven-rain conditions and can be designed for their maximum published velocities. Another sizing consideration is the effect of bird or insect screens on louver pressure drop. All screens add pressure drop, but some designs are more restrictive than others. Wire-mesh screens typically generate less drop than expanded metal screens in comparable opening sizes. For example, a 12-in.-mesh-by-0.063-in.-wire screen (approximately 75-percent free area) adds roughly 5 percent to a louvers pressure drop. Compare that to a 34-in.-by-0.051-in. expanded metal screen (approximately 70-percent free area), which will add roughly 15-percent pressure drop to a louver. The pressure drop added by either of these screens is not enough to require a change in louver size, in most cases. However, if pressure drop is a ruling factor in louver sizing, screen choice may be important. For insect screens, a commonly used size is 18-16-mesh-by0.011 in.-diameter-wire screen (roughly 65-percent free area), which adds approximately 18 percent to louver free area. Louvers are available in a variety of round, triangular, and trapezoidal shapes. However, these special configurations do not provide the same performance as rectangular shapes. Two main considerations for these special louvers are design velocity and free area. Shaped louvers often do not prevent water penetration as well as rectangular units with the same blade style. This is true particularly with drainable louvers because their blade-gutter/frame-downspout system simply does not work as well in non-rectangular configurations. To lessen the potential of water carryover, it is good practice to reduce the velocity through shaped louvers. Design the

operational free-area velocity of these louvers to be at least 25 to 30 percent below the maximum AMCA test velocity. Special shapes also negatively affect the free-area- vs. louver-face-area percentage. They often have less open area at their tops and bottoms, making their percentage of free area vs. face area less than that of rectangular louvers of comparable size. For example, a common 4-ft square louver that has 54-percent free area will provide only 50-percent free area in a 4-ft-diameter round shape. Always consider that shaped louvers have a lower free-area percentage than comparably sized square or rectangular units. Designers can simplify contractors lives by sizing louvers in dimensions that require the fewest sections. Louvers that are larger than their maximum single-section sizes are shipped to a job site in multiple sections. A contractor must splice the sections together in the field to make the overall assembly. Splicing sections adds time to the installation process, so contractors usually prefer to handle the least number of sections possible. Louver manufacturers also sometimes add a charge for multiple-section louvers to cover their splice hardware. Refer to manufacturers published literature for maximum single-section-size and multiple-section information for louvers. Sometimes, shifting just a fraction of an inch from the width to the height, or vice versa, will make the difference between a single- and a multiple-section unit. This can reduce both the cost of the louver and the labor to install it. Stationary-blade louvers may be provided with rear-mounted blade supports to reinforce blades for wind loads. When properly anchored to a building, blade supports ensure minimal deflection of louver components under windy conditions. They sometimes are referred to as hidden vertical blade supports and are required on some louvers 4-ft wide and larger. Some models may have stronger blades that span 5 or 6 ft before supports are required. Blade supports enable louvers to be made in larger single sections with less-visible mullions. They most often are angled or in channel shapes ranging from 1 to 6 in. deep, depending on the height of the louver and its design wind load. The taller the louver and/or the higher the wind load, the deeper the supports become. It is important to remember that blade supports may add several inches to a louvers depth. This can create interference if items are located close to the back of a louver. To avoid interference, designers can specify that louvers be fabricated with visible mullions to eliminate rear blade supports. Check with the architect to verify that visible mullions are acceptable in their visual scheme. Manufacturers literature or sales representatives can help designers with additional information regarding blade supports. Louver design does not stop at model selection. By considering the items discussed in this article, designers can minimize water penetration, maximize louver efficiency, and lower the cost of installation.

CFD Analysis Assists in Optimization of Displacement-Ventilation System


May 1, 2005 12:00 PM With ventilation-system performance highly dependent on a number of variables, such as the size and placement of supply diffusers and return grilles and the location of heat sources, measuring flow-related parameters to any significant degree of accuracy is difficult using conventional methods, such as rough hand calculations, which do not account for geometry details or the localized effects of supply diffusers and exhausts.

Article Tools

Email Save Print Reprint

advertisement <a href="http://ad.doubleclick.net/jump/hpac.iclick.com/adtarget;page=cfd_analysis_assists;subss=; subs=;area=ventilation-iaq;site=hpac;kw=;sz=180x150;tile=1;pos=1;ord=123456" >< img src="http://ad.doubleclick.net/ad/hpac.iclick.com/adtarget;page=cfd_analysis_assists;subss=;sub s=;area=ventilation-iaq;site=hpac;kw=;sz=180x150;tile=1;pos=1;ord=123456" border="0" alt="" / ></a> That was the reality facing a Minnesota school district planning a new elementary school, the auditorium space of which was rather complicated. The auditorium was designed to seat 680 people 460 in 12 rows on the main floor and 220 in nine rows in the balcony. The stage was designed to accommodate an additional 50 people. The HVAC system featured two 1,600-cfm diffusers and three 1,200-cfm diffusers at the back of the main floor, four 400-cfm diffusers at the front of the main floor, two 600-cfm diffusers on the stage, and five 1,000-cfm diffusers at the back of the balcony. The HVAC system also included two 3,400-cfm returns on the balcony ceiling, one 2,800-cfm wall exhaust, and one 5,000-cfm exhaust in the balcony (Figure 1). Wanting to be sure the specified equipment and design would be able to maintain comfort and energy economy year-round, the project engineers turned to Airpak, a computational-fluiddynamics (CFD) software package from Fluent Inc.

The CFD simulation revealed the ceiling-level exhaust grille was too close to the back wall of the balcony, which led to recirculation. Also, because there was no exit above the stage, warm and contaminated air needed to travel far to exit the space, which resulted in a stagnant area over the stage. The flow-velocity distribution showed a plume of air in the balcony hitting the ceiling and being redirected toward the floor, instead of leaving the room through the exhausts. A particle was shown to travel a convoluted path, moving up and down and around the auditorium. The visual depiction of airflow helped the engineers modify the design (Figure 2). Able to see exactly where air was hitting the ceiling and being deflected to the floor, they moved the exhausts toward those areas to capture the air. The two 3,400-cfm returns on the balcony ceiling were replaced with two 2,400-cfm returns in the same location, while the wall exhaust was reduced to 1,400 cfm and moved to a new location. The balcony exhaust was reduced to 3,100 cfm and moved, while two new 2,750-cfm exhausts were added to the auditorium ceiling. The two diffusers on the stage were raised 2 ft, with the size of the one on the left side increased to 800 cfm because the simulation showed it was much more effective in cooling the stage. All of the problems with the original design were eliminated with a single set of changes. The simulation of the modified design showed that the recirculation problems and hot and cold spots had been eliminated and that fluid particles moved to the exhausts effectively, without the creation of stagnant areas. The modified design also was shown to dramatically increase air quality by reducing the mean age of air, especially on the stage.