DX liquid evaporator
Customer / Project Project Created 1/16/2014 12:22 PM User name Muresan Daniel Selection ID Print date NUJ6A4C2P 1/16/2014
Model: CH20G
Cooling rate (kW) Log mean temp. diff. (C) Overall HTC (W/mK) Orifice pressure drop (kPa) Oversurface percent 27.6 5.6 874 41.4 4.7 Model size Number of refrigerant circuits Nominal surface (m) Dimensions Net weight (kg) 10x20 1 5.9 281W x 543H x 144D 38.1
Design Conditions
Refrigerant Ref. mass flow (kg/min) Target evaporator temp. (C) Leaving pressure (bar ga) Superheat (C) Liquid temp. entering TXV (C) Fluid type Fluid conc. Fluid mass flow rate (kg/min) Entering fluid temp. (C) Leaving fluid temp. (C) Fluid flow rate (L/min) Fluid fouling factor (mK/W) Model Parameters Number of channels Velocity (m/s) Pressure drop (kPa) Heat transfer coef. (W/mK) Internal volume (L)
Side A - Evaporating
R-134a 11.2 -3.0 1.6 6.0 35.0
Side B - Liquid
GEA Heat Exchangers, Inc. PHE Division 100 GEA Drive York, PA 17406 USA Ph: +717-268-6200 Fax: +717-268-6162 info.phe-systems.usa@gea.com Website: www.gea-phe.com/usa
132.8 143.5 154.3 138 5.0 2.0 9.0 150 5.0 2.0 4.7 161 5.0 2.0 0.7
Disclaimer
This software and the generated calculations provided herein are estimates only and should be treated as such. GEA PHE Systems North America, Inc. always strives to give complete and accurate information, but cannot provide any guarantees. This software and its output are provided "as is" and any express or implied warranties, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose are disclaimed. In no event shall GEA PHE Systems North America, Inc. be liable for any direct, indirect, incidental, special, exemplary, or consequential damages (including, but not limited to, procurement of substitute goods or services; loss of use, data, or profits; or business interruption) however caused and on any theory of liability, whether in contract, strict liability, or tort (including negligence or otherwise) arising in any way out of the use of this software, even if advised of the possibility of such damage.
D: 18.11 (460.0)
F:
3.94 (100.1)
Connections Circuit A
Position 1
1-5/8" IDS
Circuit A
Position 4
1-5/8" IDS 0.247 ft (6.988 L)
Circuit B
0.257 ft (7.279 L)
Position 2
7/8" IDS
Installation Notes:
Pipe in counter flow direction. Water strainer should be installed in the fluid inlet circuit to protect the heat exchanger from blockage (20-40 mesh). Solder / Sweat Connections Use 45% silver solder (minimum), AWS grade Bag-24 or equivalent.
Technical Data
Standard construction materials: Braze Alloy: Connector: Plate:
Copper 99.9% 304 Stainless Steel 316L Stainless Steel
Max pressure
Max temperature Min temperature
Circuit A: 450 psig (31.0 bar ga) Circuit B: 450 psig (31.0 bar ga)
350.0 F (176.7 C) -320.0 F (-195.6 C)
Code Approvals: UL Pending Note: Code approval applies to heat exchangers only.