Академический Документы
Профессиональный Документы
Культура Документы
& = UA ( T i T o ) q
2- Heat to warm outside air (1) desired (2) infiltration The ideal heating system would provide just enough heat to match heat loss from structure. Load is not a constant Outdoor temp changes as well as wind velocity, sunlight (solar), internal heat gains, appliances, people. Heating system must handle the coldest outside average temperature of the year. Most equipment operate at partial load most of the time Unheated Rooms: To< Tu< Ti Assume steady state heat transfer
The following Factors should be considered before performing heat load calculations:
Is the heat capacity of the structure high or low ? Is the structure insulated ? Is the structure exposed to high wind ? Is the ventilation or infiltration load high ? Is there more glass area than normal in the structure ? During what part of the day will the structure be used ? What is the nature of occupancy ? Will there be long periods of operation at reduced indoor temperature ? What is the amplitude between maximum and minimum daily temperature in the locality ? 10. Are there local conditions that cause significant variation from temperatures listed ? 11. What auxiliary heating devices will be in the building ? 12. What is the expected cost of fuel or energy ? 1. 2. 3. 4. 5. 6. 7. 8. 9.
Chapter 4 Design Temp for inside. Low end (70F at = 30%) of comfort zone
Crack Method
Q=AC Pn A= effective leakage area of the cracks C= flow coefficients, which depends on the type of crack and nature of flow in the crack P=outside - inside pressure difference, Po-Pi n=exponent that depends on the nature of the flow crack 0.4<n<1.0
Crack method is complex but in general more accurate. We need to be able to calculate P to put in the equation
P = Pw + PS + PBuilding Pr essure
Pw=Pressure difference due to wind
P = P = C
wind w
Vw
p
2g
Cp= function of angle of wind, Height and length to width ratio of building
P h d o g ( 1 1 ) Ra gc To Ti
Cd range from 1 for buildings with no doors in the stairways to about 0.65-0.85 for modern office buildings
Figure 6.1 Windows and door infiltration Characteristic Figure 6.2 Variation of wall averaged pressure coefficients for low rise buildings Figure 6.3 Variation of wall averaged pressure coefficients for tall buildings Figure 6.4 Average roof pressure coefficients for a tall building Figure 6.5 Pressure difference due to stack effect. Figure 6.6 Curtain wall infiltration for one room or one room floor Figure 6.7 Infiltration through cracks around a closed swinging door Figure 6.8 Swinging door infiltration characteristics with traffic Figure 6.9 Flow coefficient dependence on traffic rate Supply Air for Space Heating Source Media for space heating
Fig. 6.2 Variation of wall averaged pressure coefficients for low rise buildings
Fig. 6.3 Variation of wall averaged pressure coefficients for tall buildings
Fig.6.6 Curtain wall infiltration for one room or one room floor
7.
Select infiltration air quantities and compute the heat load caused by infiltration around doors and windows. 9. When positive ventilation using outdoor air is provided by an air-heating or air-conditioning unit, the energy required to warm the outdoor air to room temperature must be provided by the unit. The principle for calculation of this load component is identical to that for infiltration. If mechanical exhaust from the room is provided in an amount equal to the out-door air drawn in by the unit, the unit must also provide for the natural infiltration losses. If no mechanical exhaust is used, and the outdoor ventilation air sup-plied equals or exceeds the natural infiltration that would occur without ventilation, natural infiltration may be neglected. 10. The sum of the transmission losses or heat transmitted through the confining walls, floors, ceiling, glass, and other surfaces, plus the energy associated with the cold entering air by infiltration or required to replace mechanical exhaust, represents the total heating load. 11. In buildings that have a reasonably steady internal heat release of appreciable magnitude from sources other than the heating system, a computation of this heat release under design conditions should be made and deducted from the total of the heat losses computed above. 12. Additional heating capacity may be required for intermittently heated buildings to bring the temperature of the air, confining surfaces, and building contents to the design indoor temperature within a specified time.
8.
Source Media for space heating Hot water as heating media q = mw cp (t2 t1)
where: q = heating required, Btu/hr or W mw = mass flow rate of hot water, lbm/hr or kg/s cp = specific heat of water, Btu/lbm or kJ/(kg-C) t2 = water temperature leaving coil, F or C t1 = water temperature entering coil, F or C Assuming that cp is constant q = 500 Qgpm(t2 t1) English Units q = 4.2 QL/s(t2 t1) SI units
Source Media for space heating Steam as heating fluid q = mv (i2 i1)
where: q = heating required, Btu/hr or W mv = mass flow rate of the vapor, lbm/hr or kg/s i2 = enthalpy of the vapor leaving the coil, Btu/lbm or kJ/kg i1 = enthalpy of the vapor entering the coil, Btu/lbm or kJ/kg If saturated vapor is the heating medium, i2 i1 = the enthalpy of vaporization, i fg.
q f= mf (HV) = Qf (HV)
where: qf = heating required, Btu/hr or W mf = rate at which fuel is used, lbm/hr or kg/s Qf = Volume flow rate ft3/min or m3/s HV = heating value of the fuel, Btu/lbm or kJ/kg = furnace efficiency