INTELLIGENT DIRECTIONAL FAULT-CURRENT INDICATOR FOR 10-24kV UNDERGROUND CABLE NETWORKS


Detects and indicates phase to ground and phase to phase (PTP) faults. Directional indication for phase to ground (PTG) faults. Insensitive to capacitive discharge currents and change of feeding direction. Internal fault counter and log. Multiple power-supply solutions. External indication unit. Relay output for connection to Communication devices and SCADA RTUs.

CableTroll 3500 is suitable in electricity distribution networks with resistor earthed neutral, isolated neutral as well as compensated networks (Petersen coil). State of the art technology allowing the utilities the possibility to program the operational parameters to suit their own demands for functionality and complexity.

Established in 1977, Nortroll has gained considerable experience within fault finding, automation and surveillance of distribution networks.

CableTroll 3500 Product News

Page 1

CABLETROLL 3500
CABLETROLL 3500 is used to locate short-circuit /Phase To Phase (PTP)- and earth faults/Phase To Earth (PTG) in underground cable distribution networks. The indicator can be used in networks with isolated or impedance earthed neutral as well as compensated (Petersen coil) networks. The indicators are placed at substations, ringmain units or any installation where you have a cable termination and access to capacitive test points for measuring the phase voltage. Upon detecting a fault in the cable, the indicator gives off an intermittent red or green light-flash (LED). One LED flashing indicating an earth-fault and both LED flashing indicating a short-circuit fault. External indication units for mounting outside the station can be supplied as an option. The colours of the LED will also indicate direction to the fault location for earth-faults with reference to the busbar where the indicator is situated.

HV/MV infeed substation

HV/MV infeed substation

PTG FAULT

G
R

PTP FAULT

RG RG RG

G
R R

R G

G
Busbar

G
Busbar

R G

Fig. 1. Indicators during a fault situation

Upon sensing an earthfault (PTG) all indicators installed on the feeder with fault, both upstream and down stream will operate. Upon sensing a short circuit fault (PTP) only indicators installed between the feeding transformer and the fault location will operate CABLETROLL 3500 provides fast fault location enabling reduction in outage times. This represents enhanced service to the customers thereby improving the quality of electricity-supply.

CableTroll 3500 Product News

red or green light

fault site

R G

alternating red/green light

fault site

Page 2

Another important aspect of using fault indicators is that unnecessary operations of circuit-breakers and sectionalises to locate faults are avoided. This way the indicators help to reduce wear and tear as reclosing cycles causes stress to the switchgears.

FUNCTIONAL DESCRIPTION
CABLETROLL 3500s fault sensing is based on analyses of the current discharge transient and the residua voltage at the time of the fault appearance. The fault current is picked up by three current sensors, one for each phase and the voltage is measured at the capacitive testpoints.

Sensor principle
The processor in the Indicator uses approx. 60ms to detect the fault. It analyses the signals from the current sensors and the capacitive test points before starting indication. Detection of PTP faults is based on Current measurement (ampermetric ). Detection of PTG is based on Analyses of residual current and voltage. This will tell indicators where the earth-fault is with reference to the busbar at the location of the indicator.
Z

I0

I0

I0

Application
The application of CABETROLL 3500 usually requires no previous survey of the cable network. The indicator can be installed: In general, anywhere where you have access to a cable termination and capacitive testpoints. In location with reclosers or sectionalises to rapidly pinpoint and isolate the fault to facilitate rapid reconnection the healthy sections. In connection with remotely controlled outstations where the indicator can be connected to an RTU giving the SCADA operators immediate information of the fault location.

CableTroll 3500 Product News

Page 3

CableTroll 3500 Connected to a SCADA RTU:


The CT 3500 are equipped with internal relays, situated in the indicator housing, giving the possibility of four different relay-outputs to a SCADA RTU. The different output signals can be: Transient Fault in red direction Transient Fault in green direction Permanent Fault in red direction Permanent Fault in green direction There is in addition an input for external reset from a SCADA RTU.

CableTroll 3500 System Overview


3500 COMTROLL

IR

+ _

CABLE

TEST 1 2 3 RESET

4 Battery Compartment

The Intelligent Fault Current Indicator

230V

PHASE-TO-PHASE FAULT SENSORS

CAPACITIVE TEST POINTS

R S T
CableTroll 3500 Product News Page 4

RS 2 3 2

IC P

9 V- B a tte ry

CT 3500 External Indicator Unit

CmT 3500
NORTROLL

CT 3500 TECHNICAL SPECIFICATIONS


BLOCKING TIME FOR INRUSH: 5 seconds INDICATION CRITERIA PTP (SHORT CIRCUIT) FAULT 1) Line energised for more than 5 seconds - followed by a 2) Fault current (50Hz) exceeding a preset value (500A) within 60 ms. INDICATION CRITERIA PTG (EARTH) FAULT 1) Line energised for more than 5 seconds - followed by a 2) Fault current discharge transient exceeding a preset value within 60 ms. 3) 50% increase in the residual voltage REQUIRED FAULT DURATION: Minimum 60 ms INDICATION: 1) Indication by high intensity LED (1Hz); - Two colours, RED and GREEN. The LED flashes for the elapse of the timer, until voltage is restored (if voltage reset is programmed to ON or until the indicator is reset manually. RESET: 1) Voltage reset, delayed 5sec. or disabled. 2) Timer reset: LED factory set to 6 hours. (The number of hours can be changed by Nortroll personnel) 3) Manual reset reset button. CURRENT CONSUMPTION: Non-activated: 250 uA IR activated: 300 uA Flash activated: 125 mA BATTERY: Lithium battery; 3.6V 16.5Ah at 5mA @ 20oC, type KBB-12. NiCd battery: EXTERNAL DC: External DC input 10-24 VDC AMBIENT AND STORAGE TEMP: -40oC to + 74oC
CableTroll 3500 Product News Page 5

HOUSING INDICATOR: Body: Poly Carbonate (PC) / ABS Front cover: Transparent Poly Carbonate/ABS, UV resistant Mechanical strength IK o7 (6J impact) Flame retardant grades: (V-0 UL ) 750 oC IP-55 HOUSING EXTERNAL INDICATOR: Body: Poly Carbonate (PC) / ABS Front cover: Transparent Poly Carbonate/ABS, UV resistant Mechanical strength IK o9 (6J impact) Flame retardant grades: (V-0 UL ) 750 oC IP-55 WEIGHT&VOLUME: Complete box with Indicator, 3pcs sensor elements with cable and screws Weight: 1400 grams (including 3 batteries and 3 current sensor elements) Volume: 300x400x800 mm Weight:

ORDERING INFORMATION:
Order No. Product Description 4010 4020 3595 3625 3626 CT 3500 with 3 pcs of Lithium batteriesCT 3500 with 230VAC adaptor and rechargeable NiCd battery Relay-card upgrade-kit CmT 3500 Testing, Programming and Reading unit. External Indicator No IR communication. External Indicator With IR communication.

DELTATRONIC Technology Sales Ing. Karl Ritter, Schmalenegg 9 A-6850 Dornbirn/Austria Tel.: +43 5572 29005 Fax: +43 5572 29181 Email: sales@deltatronic.com Web: www.deltatronic.com